InteliCompact NT 2.0 Reference Guide
InteliCompact NT 2.0 Reference Guide
InteliCompact NT 2.0 Reference Guide
Reference Guide
Table of contents
1
Installation .................................................................................................................................... 14
3.1 Mounting ................................................................................................................................... 14
3.2 Package contents ..................................................................................................................... 14
3.3 Dimensions ............................................................................................................................... 15
3.4 Terminal diagram ...................................................................................................................... 16
3.5 General ..................................................................................................................................... 16
3.6 Wiring........................................................................................................................................ 17
3.7 Grounding ................................................................................................................................. 17
3.8 Power supply ............................................................................................................................ 17
3.8.1
Power supply fusing ......................................................................................................... 19
3.9 Voltage and current inputs ....................................................................................................... 19
3.10 Speed measurement ................................................................................................................ 21
3.10.1 Pickup .............................................................................................................................. 21
3.10.2 Generator frequency ........................................................................................................ 22
3.10.3 Additional running engine indication ................................................................................ 22
3.11 Binary inputs ............................................................................................................................. 23
3.12 Binary outputs ........................................................................................................................... 23
3.13 Analog inputs ............................................................................................................................ 24
3.13.1 Tristate inputs .................................................................................................................. 25
3.14 Circuit breakers ........................................................................................................................ 26
3.14.1 Breaker control outputs .................................................................................................... 26
3.14.2 MCB special requirements ............................................................................................... 27
3.15 AVR interface ........................................................................................................................... 27
3.15.1 IG-AVRi ............................................................................................................................ 27
3.15.2 AVR list ............................................................................................................................ 30
3.16 Speed governor interface ......................................................................................................... 42
3.16.1 Speed governor list .......................................................................................................... 43
3.17 CAN bus wiring ......................................................................................................................... 50
3.18 Recommended CAN/RS485 connection .................................................................................. 51
3.18.1 CAN bus connection ........................................................................................................ 51
3.18.2 RS485 connection ........................................................................................................... 51
3.19 Extension modules ................................................................................................................... 53
3.19.1 IGS-PTM .......................................................................................................................... 53
3.19.2 IGL-RA15 remote annunciator ......................................................................................... 54
3.19.3 IL-NT-AOUT8 ................................................................................................................... 55
3.19.4 IL-NT BIO8 ....................................................................................................................... 55
3.19.5 IC-NT CT-BIO7 ................................................................................................................ 57
3.20 Communication modules .......................................................................................................... 59
3.20.1 IL-NT RS232 .................................................................................................................... 59
3.20.2 IL-NT RS232-485 ............................................................................................................. 60
3.20.3 IL-NT S-USB .................................................................................................................... 60
NT
Operator guide.............................................................................................................................. 78
5.1 Front panel elements ................................................................................................................ 78
5.2 User interface modes ............................................................................................................... 80
5.3 Display screens and pages structure ....................................................................................... 80
5.4 View measured values ............................................................................................................. 82
5.5 Setpoints view and change ................................................................................................... 82
5.6 Browsing the history log ........................................................................................................... 83
5.7 Browsing alarms ....................................................................................................................... 84
5.8 Entering the password .............................................................................................................. 85
5.9 Controller information screen ................................................................................................... 85
5.10 Controller language selection ................................................................................................... 87
5.11 User interface mode selection .................................................................................................. 87
5.12 Display contrast adjustment ..................................................................................................... 87
7.3.15
10
10.1
10.2
10.3
10.4
10.5
11
Communication .................................................................................................................... 140
11.1 Direct cable connection .......................................................................................................... 140
11.2 Modem connection ................................................................................................................. 141
11.2.1 Recommended GSM modems ...................................................................................... 141
11.2.2 Modem setup procedure ................................................................................................ 142
11.3 Internet connection ................................................................................................................. 142
11.3.1 SPtM .............................................................................................................................. 142
11.3.2 MINT .............................................................................................................................. 143
11.3.3 Using a web browser ..................................................................................................... 144
11.3.4 IB-Lite setup procedure ................................................................................................. 144
11.3.5 System integration ......................................................................................................... 145
11.3.6 InternetBridge-NT setup procedure ............................................................................... 145
11.3.7 IG-IB setup procedure ................................................................................................... 145
11.3.8 SNMP ............................................................................................................................. 145
11.3.9 AirGate ........................................................................................................................... 145
11.3.10 Locate ............................................................................................................................ 145
11.4 Modbus protocol ..................................................................................................................... 146
11.5 IC-NT-RD Remote display software ....................................................................................... 147
12
Maintenance .......................................................................................................................... 148
12.1 Backup battery replacement ................................................................................................... 148
13
14
Technical data ....................................................................................................................... 153
14.1 Power supply .......................................................................................................................... 153
14.2 Operating conditions............................................................................................................... 153
14.3 Physical dimensions ............................................................................................................... 153
14.4 Standard conformity ............................................................................................................... 153
14.5 Binary inputs ........................................................................................................................... 154
14.6 Binary outputs ......................................................................................................................... 154
14.7 Analog inputs .......................................................................................................................... 154
14.8 Generator/Mains measurements ............................................................................................ 154
14.9 Pickup input ............................................................................................................................ 155
14.10 Charging alternator pre-excitation circuit ................................................................................ 155
14.11 AVR output ............................................................................................................................. 155
NT
16
Appendix ............................................................................................................................... 159
16.1 Table of setpoints ................................................................................................................... 159
16.1.1 Group: Process Control ................................................................................................. 159
16.1.2 Group: Basic Settings .................................................................................................... 163
16.1.3 Group: Comms Settings ................................................................................................ 167
16.1.4 Group: Engine Params .................................................................................................. 173
16.1.5 Group: Engine Protect ................................................................................................... 178
16.1.6 Group: Gener Protect .................................................................................................... 182
16.1.7 Group: Pwr Management ............................................................................................... 187
16.1.8 Group: AMF Settings ..................................................................................................... 194
16.1.9 Group: Sync/Load Ctrl ................................................................................................... 198
16.1.10 Group: Volt/PF Ctrl ........................................................................................................ 203
16.1.11 Group: ExtI/O Protect .................................................................................................... 204
16.1.12 Group: SMS/E-Mail ........................................................................................................ 207
16.1.13 Group: AnalogSwitches ................................................................................................. 208
16.1.14 Group: Date/Time .......................................................................................................... 210
16.1.15 Group: Sensors Spec .................................................................................................... 214
16.2 Table of values ....................................................................................................................... 217
16.2.1 Group: Engine ................................................................................................................ 217
16.2.2 Group: Generator ........................................................................................................... 220
16.2.3 Group: Mains ................................................................................................................. 226
16.2.4 Group: Bus ..................................................................................................................... 230
16.2.5 Group: Pwr Management ............................................................................................... 232
16.2.6 Group: Controller I/O ..................................................................................................... 234
16.2.7 Group: Extension I/O ..................................................................................................... 238
16.2.8 Group: Statistics............................................................................................................. 240
16.2.9 Group: Date/Time .......................................................................................................... 242
16.2.10 Group: Info ..................................................................................................................... 243
16.3 Table of binary input functions ............................................................................................... 245
16.3.1 Common functions ......................................................................................................... 245
16.3.2 MINT specific ................................................................................................................. 249
16.3.3 SPtM specific ................................................................................................................. 250
16.4 Table of binary output functions ............................................................................................. 251
16.4.1 Common functions ......................................................................................................... 251
16.4.2 ECU info......................................................................................................................... 259
16.4.3 Alarm mirrors ................................................................................................................. 261
16.4.4 MINT specific ................................................................................................................. 271
16.4.5 SPtM specific ................................................................................................................. 272
16.5 Table of internal alarms .......................................................................................................... 273
NT
1 Document information
InteliCompact-NT Reference guide
Written by: Jan Tomandl, Revised by: Jan Donat, Jan Podlipny
2013 ComAp a.s.
Kundratka 17, Praha 8, Czech Republic
Phone: +420246012111, fax: +420266316647
Web: HTTP://WWW.COMAP.CZ, e-mail: info@comap.cz
DOCUMENT HISTORY
REVISION NUMBER
DATE
1.0
30.05.2008
1.1
25.03.2009
1.2
22.10.2009
1.2.2
11.05.2010
1.3.1
28.11.2011
1.4
06.03.2013
2.0
30.04.2014
NT
1.1
Clarification of notation
HINT
This type of paragraph points out details to help user installation/configuration.
NOTE:
This type of paragraph calls readers attention to a notice or related theme.
CAUTION!
This type of paragraph highlights a procedure, adjustment, etc. which may cause damage or improper
functioning of the equipment if not carried out correctly and may not be clear at first sight.
WARNING!
This type of paragraph indicates things, procedures, adjustments, etc. which demand a high level of
attention, otherwise personal injury or death may occur.
1.2
Conformity Declaration
The following described machine complies with the appropriate basic safety and
health requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type, as
brought into circulation by us.
NT
2 System overview
2.1
General description
NT
InteliCompact (also IC-NT) Family controllers are comprehensive gen-set controllers for single and
multiple generating sets operating in stand-by or parallel modes. A modular construction allows
upgrades to different levels of complexity in order to provide the best solution for various customer
applications. The controllers are equipped with a powerful graphic display showing icons, symbols and
bar graphs for intuitive operation, which, together with its high level of functionality, sets new
standards in Gen-set controls.
The key features are:
2.2
Easy-to-use operation and installation. The factory default configuration covers most
applications
Various customizations are possible thanks to its configurability
Excellent remote communication capabilities
High level of support for EFI engines (most world producers)
High reliability
One of the key features of the controller is the systems high level of adaptability to the needs of each
individual application and wide possibilities for monitoring. This can be achieved by configuring and
using the powerful ComAp PC/mobile tools.
Supported configuration and monitoring tools:
-
NOTE:
Use the LiteEdit PC software to read, view and modify configuration from the controller or disk and
write the new configuration to the controller or disk.
NT
The firmware of InteliCompact contains a large number of binary inputs and outputs needed for all
necessary functions available. However, not all functions are required at the same time on the same
gen-set and also the controller hardware does not have so many input and output terminals. One of
the main tasks of the configuration is mapping of logical firmware inputs and outputs to the physical
hardware inputs and outputs.
Configuration parts:
1. Mapping of logical binary inputs (functions) or assigning alarms to physical binary input
terminals
2. Mapping of logical binary outputs (functions) to physical binary output terminals
3. Assigning sensor characteristics and alarms to analog inputs
4. Assigning control values and output characteristics to analog outputs
5. Selection of peripheral modules which are connected to the controller and doing the same as
the above for them
6. Selection of ECU type if an ECU is connected
7. Changing the language of the controller interface
NT
CONFIGURATION OF
BINARY INPUTS AND
OUTPUTS
Alarm
management
Logical inputs
Main program (control loop)
FIRMWARE
Logical outputs
CONTROLLER
Physical output terminals
2.2.1
LiteEdit
NT
NT
NT
10
2.2.2
InteliMonitor
2.2.3
WinScope
2.2.4
WebSupervisor
Web-based system for monitoring and controlling ComAp controllers. See more at the WebSupervisor
webpage.
This tool provides the following functions:
- Site and fleet monitoring
- Reading of measured values
- Browsing of controller history records
- On-line notification of alarms
- E-mail notification
- Also available as a smartphone application
NT
11
2.3
Applications overview
2.3.1
Single applications
The typical scheme of a single parallel to mains application is shown below. The controller controls
two breakers a mains breaker and a generator breaker. Feedback from both breakers is required.
MCB
GCB
3x
G1
K4
K3
MCB
ECU
3Ph IG
3Ph UG
3x
3Ph UM
3x
GCB
GCB CLOSE/OPEN
BO
MCB CLOSE/OPEN
InteliCompactNT
SPtM
BI
MCB
GCB
IG-AVRi
AVRi
AVR
SPEED GOVERNOR
SG+
CAN1
ECU
MCB FEEDBACK
GCB FEEDBACK
2.3.2
Multiple applications
The typical schemes are multiple island-parallel application without mains and multiple parallel
application with mains. Both are shown below. The controller controls one breaker only, the generator
breaker. Feedback from the generator breaker is required. For parallel to mains operation also mains
breaker feedback is required.
GCB
3x
G1
K3
ECU
3Ph UG
3Ph IG
3Ph UB
3x
GCB
GCB CLOSE/OPEN
BO
InteliCompactNT
MINT
BI
AVR
SPEED GOVERNOR
SG+
CAN2 CAN1
SYS START/STOP
GCB
IG-AVRi
AVRi
ECU
GCB FEEDBACK
CAN
GCB
G2
K3
ECU
3Ph UG
3Ph IG
3Ph UB
3x
GCB
GCB CLOSE/OPEN
BO
InteliCompactNT
MINT
BI
SYS START/STOP
START/STOP
GCB
IG-AVRi
AVRi
AVR
SPEED GOVERNOR
SG+
CAN2 CAN1
ECU
GCB FEEDBACK
CAN
NT
12
MCB
GCB
3x
K4
K3
3Ph IM
3Ph UM
MCB
GCB CLOSE/OPEN
MCB CLOSE/OPEN
SYS START/STOP
CAN
BO
3Ph UG
3Ph IG
InteliCompactNT
MINT
BI
SPEED GOVERNOR
SG+
ECU
CAN
GCB
G2
K3
ECU
3Ph UG
3Ph IG
REM START/STOP
MCB FEEDBACK
AVR
CAN2 CAN1
3x
MCB
IG-AVRi
AVRi
GCB FEEDBACK
MCB FEEDBACK
SYS START/STOP
3Ph UB
MainsCompactNT
BI
ECU
GCB
3Ph UB
GCB
BO
G1
3x
3Ph UB
3x
GCB
GCB CLOSE/OPEN
GCB
BO
InteliCompactNT
MINT
BI
GCB FEEDBACK
MCB FEEDBACK
SYS START/STOP
IG-AVRi
AVRi
AVR
SPEED GOVERNOR
SG+
CAN2 CAN1
ECU
CAN
2.4
This controller measures AC values based on the True RMS principle. This principle corresponds
exactly to the physical definition of alternating voltage and current effective values. Under normal
circumstances the mains voltage and current should have a pure sinusoidal waveform. However,
some nonlinear elements connected to the mains produce harmonic waveforms with frequencies of
multiples of the basic mains frequency and this may result in deformation of the voltage and/or current
waveforms. The True RMS measurement gives accurate readings of effective values not only for
pure sinusoidal waveforms, but also for deformed waveforms.
NOTE:
The harmonic deformation causes that the Power Factor of a generator working parallel with the
mains cannot reach values in a certain range around the PF 1.00. The higher the deformation, the
wider the power factor dead range. If the requested power factor is adjusted inside the dead range,
the controller cannot reach the requested value because of this fact.
NT
13
3 Installation
3.1
Mounting
The controller is to be mounted onto the switchboard door. The requested cut-out size is 175x115 mm.
Use the screw holders delivered with the controller to fix the controller into the door as described in the
pictures below.
3.2
Package contents
Controller
Mounting holders
Terminal blocks
NOTE:
The package does not contain a communication module. The required module should be ordered
separately.
NT
14
3.3
Dimensions
185
58
168
47
29
NT
D+
80
110
125
InteliCompact
NOTE:
The dimensions are in millimetres and are the same for both versions SPTM and MINT.
NT
15
3.4
Terminal diagram
MINT
SPTM
3.5
General
16
3.6
Wiring
Tightening torque, allowed wire size and type, for the Field-Wiring Terminals:
3.7
Grounding
2
The shortest possible piece of wire should be used for controller grounding. Use cable min. 2.5 mm .
A brass M4x10 screw with star washer securing ring type grounding terminal shall be used.
The negative - battery terminal must be properly grounded.
Switchboard and engine must be grounded at a common point. Use as short a cable as
possible to the grounding point.
3.8
Power supply
The maximum continuous DC power supply voltage is 36 V DC. The maximum allowable power
supply voltage is 39 V DC. The InteliCompacts power supply terminals are protected against large
pulse power disturbances. When there is a potential risk of the controller being subjected to
conditions outside its capabilities, an outside protection device should be used.
It is necessary to ensure that potential difference between the generator current COM terminal
and the battery - terminal is maximum 2 V. Therefore, it is strongly recommended to
interconnect these two terminals together.
HINT:
NT
The InteliCompact controller should be grounded properly in order to protect against lighting strikes!!
The maximum allowable current through the controllers negative terminal is 4A (this is dependent on
binary output load).
NT
17
NT
For connection with a 12 V DC power supply, the InteliCompact includes internal capacitors that
allow the controller to continue operation during cranking if the battery voltage dip occurs. If the battery
voltage is 10 V before the dip and it recovers to 7 V within 100 ms the controller continues operating.
During this voltage dip, the controller screen backlight may turn on and off but the controller keeps
operating.
It is possible to further support the controller by connecting the external capacitor and separating
diode or I-LBA module:
Starter
+
Relays
Controller
T1A
C
-
12 VDC Battery
The capacitor size depends on the required time. It shall be approximately in the thousands of
microfarads.
The capacitor size should be 5000 microfarad to withstand a 150 ms voltage dip under the following
conditions:
Voltage before dip is 12 V, after 150 ms the voltage recovers to the min. allowed voltage, i.e. 8 V.
HINT:
Before the battery is discharged the message "Low BackupBatt" appears.
Or by connecting a special I-LBA Low Battery Adaptor module:
Starter
+
Relays
+
-
I-LBA
T1A
Controller
+
-
12 VDC Battery
The I-LBA module ensures a min. 350 ms voltage dip under following conditions:
HINT:
I-LBA may not eliminate voltage drop when used with the low temperature (-40 C) version of the
controller and the display heating element is on (below 5 C). The current drain of the heating element
exhausts LBA capacitors very fast.
NT
18
3.8.1
A one-amp fuse should be connected in line with the battery positive terminal to the controller and
modules. These items should never be connected directly to the starting battery.
Fuse value and type depends on the number of connected devices and wire length.
The recommended fuse type (not fast) is T1A due to internal capacitors charging during
power up.
IC-NT
-
T1A
HUGE
LOADS
STARTER
Battery
3.9
WARNING!
Risk of personal injury due to electric shock when manipulating voltage terminals under voltage! Be
sure the terminals are not under voltage before touching them.
WARNING!
Do not open the secondary circuit of current transformers when the primary circuit is closed!!! Open
the primary circuit first!
2
Use 1.5 mm cables for voltage connection and 2.5 mm for current transformers connection.
Adjust nominal voltage, nominal current, CT ratio and PT ratio by appropriate setpoints in the Basic
Settings group. Learn about how to view and change setpoints in the User interface chapter.
L2
L3
N
L1
L2
GENERATOR
L3
L1
L2
L3
MAINS / BUS
NT
19
B)
L1
L2
L3
N
L1
L2
L3
GENERATOR
L1
L2
L3
MAINS / BUS
C)
L1
L2
L3
L1
L2
L3
GENERATOR
L1
L2
L3
MAINS / BUS
D)
L1
G
N
L1
L2
L3
GENERATOR
L1
L2
L3
MAINS / BUS
L
l
L1
K
k
L2
K
k
L
l
L3
COM
L1 L2 L3
NT
20
NOTE:
IT IS NECESSARY TO ENSURE THAT THE POTENTIAL DIFFERENCE BETWEEN THE GENERATOR CURRENT COM
TERMINAL AND THE BATTERY - TERMINAL IS MAXIMUM 2V. THEREFORE, IT IS STRONGLY RECOMMENDED TO
INTERCONNECT THESE TWO TERMINALS TOGETHER.
CAUTION:
NT
W HEN YOU ARE USING INTELICOMPACT HW VERSION 1.3 OR NEWER IT IS NECESSARY TO UPGRADE THE
FIRMWARE TO IC-NT-1.4.3 OR NEWER.
NT
Since HW version 1.3 the InteliCompact measures current with reversed polarity. It is not
recommended to switch wiring at the current transformer side. To fix this error use FW IC-NT-1.4.3 or
newer.
3.10.1
Pickup
A magnetic speed sensor (pickup) is the most common method of engine speed measurement. To
use this method, mount the pickup opposite to the engine flywheel, connect the cable to the controller
as shown on the picture below and adjust the setpoint Gear Teeth according to the number of teeth on
the flywheel.
D+
COM
RPM
See the chapter Technical data for details about the pickup input parameters.
Pickup
Charging alternator
D+ (L)
T2A
NT
21
3.10.2
Generator frequency
D+
COM
RPM
If the pickup is not used, set the setpoint Gear Teeth to zero. The engine speed will be measured from
the generator frequency. Connect the W terminal from the charging alternator instead of the pickup, if
possible. See picture below.
D+ (L)
T2A
W
Charging alternator
3.10.3
It is helpful to have information other than speed (RPM), whether the engine is rotating or not,
especially if RPM is measured from the generator frequency instead of magnetic pickup. The
generator frequency measurement can be unreliable at very low speeds and/or may have a delayed
reaction to sudden and big changes (i.e. in the moment that the engine has just started).
The following conditions are evaluated as additional running engine indication:
Voltage on the D+ input is higher than 80% of battery voltage. Connect this input to the D+ (L)
terminal of the charging alternator and enable the D+ function by the setpoint D+ Function. If
D+ terminal is not available, leave the input unconnected and disable the function.
The pickup is not used and frequency is detected on the pickup input. Connect the pickup
input to the W terminal of the charging alternator if you do not use pickup and the W terminal
is available. If not, leave the input unconnected.
NOTE:
The starter cut-off frequency has to be adjusted by the setpoint Start W Freq. If you know the charging
alternator nominal frequency, adjust the setpoint to the frequency obtained from following equation:
(
If you do not know the charging alternator nominal frequency, follow this procedure:
1) Make sure that the starting accumulator is fully charged.
2) Close a fuel valve manually to disable the engine from being started.
NT
22
3) Connect a PC with LiteEdit to the controller and display "Values" window, group "Engine", value
W-TerminalFreq.
4) Select MAN mode and press the Start button to crank the gen-set. Make a note about the W
terminal frequency while the gen-set is cranking.
5) Press the Stop button to stop cranking.
6) Adjust the setpoint Start W Freq to a value twice that which you measured during cranking.
Oil pressure > Starting Oil P setpoint. The oil pressure is evaluated from the analog input 1 or
from the ECU if an ECU is configured.
At least one phase of generator voltage is >20% of nominal voltage.
These signals are used during start for powering down the starter motor even if still no RPM is
measured and also during stop in order to evaluate if the engine is really stopped.
To the microprocessor
4k7
Use min. 1 mm cables for wiring of binary outputs. Use external relays as indicated on the schematic
below for all outputs except those where low-current loads are connected (signalization etc...).
NOTE:
The function of each output has to be assigned during configuration.
CAUTION!
Use suppression diodes on all relays and other inductive loads!
NT
23
From the
microprocessor
In the case of grounded sensors, connect the AI COM terminal to the engine body as near to
the sensors as possible.
In the case of isolated sensors, connect the AI COM terminal to the negative power supply
terminal of the controller as well as the opposite poles of the sensors.
NOTE:
The fail sensor alarm is issued if the measured resistance is smaller than one half of the first (lowest)
point of the sensor curve characteristic or is greater than 112.5% of the last (highest) point of the
sensor curve characteristic.
NOTE:
Analog inputs are typically used for: Oil Pressure, Water Temperature and Fuel Level. All of these
parameters are connected with relevant protections.
Protection of Oil Pressure and the relevant condition of a running engine is joined with AI01 only if:
- the ECU is not configured
- the ECU is configured and the AI01 is set to Alarm + ECU.
NT
24
AI COM
AI
AI
AI COM
3.13.1
Tristate inputs
AI COM
Analog inputs can be used also as binary or tri-state, i.e. for contact sensors without or with circuit
check. The threshold level is 750. In the case of tri-state, values lower than 10 and values over
2400 are evaluated as sensor failure (short or open circuit).
BINARY
TRISTATE
100R
1k5
NT
25
It is possible to use either a motorized circuit breaker or contactor. Below is a list of available control
outputs that should fit all types of contactors or breakers. The following rules must be kept to when
designing the wiring of power switches:
The control outputs must be configured and wiring of the power switches must be provided in
such a way, that the controller has full control over the breakers i.e. the controller can open
and close the breaker at any time.
The breaker must respond within max. 2 seconds to a close and open command. Special
attention should be paid to opening of motorized circuit breakers, as it could take more than 2
seconds on some types. In such cases it is necessary to use an undervoltage coil for fast
opening.
The breaker feedback functions must be configured onto some binary inputs and the signals
from the breakers must be connected to it and provide reliable information about the breaker
position.
3.14.1
An output for control of a contactor. Its state represents the breaker position
Close/open requested by the controller. The breaker must react within 2 seconds to a close or
open command, otherwise an alarm is issued.
ON coil
An output giving a 2 second pulse in the moment the breaker has to be closed. The
output is intended for control of close coils of circuit breakers.
OFF coil
An output giving a pulse in the moment the breaker has to be opened. The pulse
lasts until the feedback deactivates, but at least for 2 seconds. The output is
intended for control of open coils of circuit breakers.
UV coil
The output is active the whole time the gen-set is running (GCB, not in idle or
cooling) or the controller is switched on (MCB). The output is deactivated for at least
2 seconds in the moment the breaker has to be switched off. The output is intended
for control of undervoltage coils of circuit breakers.
CLOSE/OPEN
2s
ON COIL
OFF COIL
2s
UV COIL
FEEDBACK
BREAKER OUTPUTS TIMING
NT
26
3.14.2
1. If a contactor is used on the MCB position, it is recommended that the wiring be provided in
such a way that the contactor will be normally closed and will open if the MCB Close/Open
closes. This behaviour is called negative logic and can be adjusted by the setpoint MCB
Logic. The negative logic will prevent accidental opening of the MCB when the controller is
switched off.
2. If a contactor is used on the MCB position, it will open itself immediately after the mains have
failed, because it will lose power for the coil. That is why the following adjustment is necessary
to prevent triggering the MCB fail alarm: MCB Opens On = MAINSFAIL, Mains V Del 1.
3. If a 230 V motor driven circuit breaker is used on the MCB position and an undervoltage coil is
not fitted, it is not possible to open the breaker after the mains have failed, because there is no
power for the motor drive until the gen-set is started and providing voltage. Adjusting the
setpoint MCB Opens On = GEN RUN will prevent triggering the MCB fail alarm.
3.15.1
IG-AVRi
Automatic voltage Regulator interface is used for volt/PF control adjustment through galvanic
separated inputs and outputs.
CAUTION:
Refer each time to the corresponding AVR manual before connecting the interface. IG-AVRi-TRANS
(AC power supply for AVRi) has to be supplied from gen-set voltage.
AVRi output can be connected as symmetrical: OUT1-OUT2 or unsymmetrical OUT1-GND or OUT2GND.
- The potentiometer on the AVRi defines maximum OUT1, OUT2 voltage range.
- Use symmetrical (OUT1, OUT2) AVRi output to connect the AVRi to AVR auxiliary voltage
input.
- Use unsymmetrical output if an external AVR potentiometer has to be replaced with AVRi.
- AVRi output voltage should change the generator voltage typically in the range 10% of the
Nominal voltage.
NOTE:
IG-AVRi is not included in the standard package with the controller.
IG-AVRi TRANS/LV is a power supply unit for IG-AVRi; it is not included with the IG-AVRi package.
Output
OUT1
GND
OUT2
AC1
AC3
Output level
Input
AVRI
AO GND
NT
27
AVRI
AO GND
AVR
VOLTAGE
ADJUST
GENERATOR
VOLTAGE
NT
28
AVRi output
OUT1 - OUT2 [V]
10 V
2V
100 [%]
AVR output
-2V
-10 V
AVRi output
OUT1 - GND
10 V
2V
100 [%]
AVR output
AVRi output
OUT2 - GND
10 V
AVRi trim turned in max.
position (clockwise)
2V
100 [%]
AVR output
AVRi trim turned in min.
position
(counterclockwise)
NT
29
3.15.2
AVR list
3.15.2.1
LeRoy-Somer
OCOM
ST4
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
LeRoy-Somer: R 449
3
ST4 2
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
LeRoy-Somer: R 450
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
HINT:
Use AVRi instead of potentiometer 1k.
Read LeRoy-Somer R450 manual before use.
LeRoy-Somer: R 129
J2
OCOM
IGAVRi
TRANS
iGAVRi
18VAC
230/400VAC
0VAC
AVRI
From
generator
AO GND
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
NT
30
LeRoy-Somer: R 128
4
5
OCOM
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
OUT1
IGAVRi
TRANS
OUT2
iGAVRi
18 VAC
AVRI
AO GND
AVRI
AO GND
OUT1
LeRoy-Somer: R 250
OCOM
J2
IGAVRi
TRANS
iGAVRi
18VAC
230/400VAC
0VAC
From
generator
AVRI
AO GND
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
NT
31
LeRoy-Somer: R 230
OUT2
J4
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
OUT1
500
Remove Link J4 and replace instead of R500
Primary voltage setting with resistors connected: 230 V
HINT:
Disconnect one wire (OUT 1), set voltage on running Generator to U = nom.
Measure Voltage over Resistor
Depending on Value, increase AVRi potentiometer to get Range.
Set exact Value with Bias Voltage//PF regulation (gain = 0)
Stop gen-set and connect when equal Voltage and polarity is achieved.
Set again in regulation loop on demand
LeRoy-Somer: R 230
IGAVRi
TRANS
OUT2
OUT1
iGAVRi
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
NT
32
LeRoy-Somer: R 449
OUT2
230/400VAC
0VAC
iGAVRi
5
4
3
ST4 2
1
IGAVRi
TRANS
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
3.15.2.2
Stamford
STAMFORD SX 460
1
2
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 60-70%
OUT1
HINT:
Before you connect IG-AVRi you should connect the jumper on AVR between pin 1 and 2 to run the voltage
regulator without external control and set the voltage by the voltage trim on SX460 to roughly 227 V (in the
event that the nominal voltage of the system is 230 V).
A1
A2
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
STAMFORD AS480
1
2
OUT2
OCOM
IGAVRi
TRANS
iGAVRi
18VAC
From
generator
AVRI
Volt/PF ctrl:
AVR Bias = 30%
AO GND
AVRI
AO GND
NT
33
STAMFORD MX 341
A1
A2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
OCOM
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
HINT:
Disconnect the droop CT (terminal S1 & S2) and short the droop CT leads.
Short the terminal S1,S2 on the AVR
3.15.2.3
AVK Newage
t
S
5R5
250R
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
OCOM
From
generator
AO GND
AVRI
AVRI
Volt/PF ctrl:
AVR Bias = 25%
AO GND
OUT1
A1
A2
18VAC
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
2
1
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
3.15.2.4
Caterpillar
Caterpillar CDVR
12-3
12-6
OUT2
IGAVRi
TRANS
iGAVRi
18VAC
230/400VAC
0VAC
From
generator
AVRI
AO GND
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
OUT1
NT
34
Caterpillar DVR
7
45
OCOM
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
OUT1
TR5
TR6
TR7
OCOM
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias
OUT1
2
3
18VAC
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
4
7
From
generator
AO GND
AVRI
AVRI
AO GND
OUT1
3.15.2.5
Volt/PF ctrl:
AVR Bias = 0%
Voltage range (-2 V; 2 V)
Basler
7
6
OCOM
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
B
A
OUT2
IGAVRi
TRANS
iGAVRi
18VAC
230/400VAC
0VAC
From
generator
AVRI
AO GND
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
NT
35
230/400VAC
0VAC
iGAVRi
A10
A9
IGAVRi
TRANS
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
3.15.2.6
Marathon
Marathon DVR2000E
B
A
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
OUT1
6
7
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
Volt/PF ctrl:
AVR Bias = 50%
From
generator
AO GND
AVRI
AVRI
AO GND
OUT1
3.15.2.7
Marelli
8
6
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
Volt/PF ctrl:
AVR Bias = 50%
From
generator
AO GND
AVRI
AVRI
AO GND
OUT1
MarelliMotori (M40FA610A)
8
6
OUT2
iGAVRi
18VAC
IGAVRi
TRANS
230/400VAC
0VAC
Volt/PF ctrl:
AVR Bias = 50%
From
generator
AVRI
AO GND
AVRI
AO GND
OUT1
NT
36
230/400VAC
P
Q
OCOM
IG- AVRi
TRANS
0VAC
iGAVRi
18VAC
AO GND
AVRI
AVRI
Volt/PF ctrl:
AVR Bias = 15%
AO GND
OUT1
3.15.2.8
OUT2
OCOM
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 75%
5B
7
OCOM
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 75%
OUT1
8
6
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
29
30
OCOM
iGAVRi
18VAC
IGAVRi
TRANS
230/400VAC
0VAC
From
generator
AVRI
AO GND
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
OUT1
NT
37
11
10
IGAVRi
TRANS
iGAVRi
AO GND
OCOM
AVRI
AO GND
AVRI
OUT1
Generator
voltage
114%
(or 105%)
Volt/PF ctrl:
AVR Bias = 50%
Nominal voltage
set on DSR
100%
86%
(or 95%)
0V
1.25V
The Vext input (connector CN1 terminals 10 and 11) permits analog remote control of output voltage with a
programmable variation range of up to 10% (parameter 16, by default the setting is 5%) with respect to the
value set. If you want to use continuous voltage, it will be effective if it is in the range between 0 V and
+2.5 V. The input tolerates voltages from -5 V to +5 V, but for values exceeding the limits of 0 V / +2.5 V (or
in the event of disconnection) it is automatically disabled and the voltage adjustment goes back to the value
set through the trimmer (if enabled) or through parameter 19 (as shown on the picture).
Changing the DSR parameters requires a PC with dedicated software and a DI1-DSR unit!
DSR automatically detects the presence of a transformer for parallel operation (if used it works with droop, if
not used then it works isochronous).
NT
38
3.15.2.9
Piller
Piller
18VAC
OUT2
230/400VAC
0VAC
iGAVRi
1
2
IGAVRi
TRANS
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 39%
OUT1
3.15.2.10
Marathon
Marathon DVR2000E
B
A
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
OUT1
6
7
OUT2
IGAVRi
TRANS
230/400VAC
0VAC
iGAVRi
18VAC
Volt/PF ctrl:
AVR Bias = 50%
From
generator
AO GND
AVRI
AVRI
AO GND
OUT1
3.15.2.11
KATO
8
6
OUT2
IGAVRi
TRANS
iGAVRi
18VAC
230/400VAC
0VAC
Volt/PF ctrl:
AVR Bias = 50%
From
generator
AVRI
AO GND
AVRI
AO GND
OUT1
NT
39
230/400VAC
0VAC
iGAVRi
R2
R1
IGAVRi
TRANS
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 45%
OUT1
KATO K-65-12B
2
3
IGAVRi
TRANS
OUT2
230/400VAC
0VAC
iGAVRi
4
7
18VAC
From
generator
AO GND
AVRI
AVRI
AO GND
Volt/PF ctrl:
AVR Bias = 50%
OUT1
3.15.2.12
ENGGA
ENGGA WT-2
230/400VAC
OUT2
AA+
IG- AVRi
TRANS
0VAC
IGAVRi
18VAC
From
generator
AO GND
AVRI
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
OUT1
ENGGA WT-3
230/400VAC
A2
A1
OUT2
IG- AVRi
TRANS
0VAC
AO GND
AVRI
AO GND
OUT1
3.15.2.13
Volt/PF ctrl:
AVR Bias = 50%
From
generator
AVRI
IGAVRi
18VAC
Sincro
POT
EXT
COM
OUT1
IG- AVRi
TRANS
IGAVRi
18VAC
0VAC
From
generator
AVRI
AO GND
AVRI
Volt/PF ctrl:
AVR Bias = 20%
AO GND
NT
40
3.15.2.14
Kutai
Kutai EA448
230/400VAC
ST4
COM
OUT1
IG- AVRi
TRANS
IGAVRi
18VAC
0VAC
From
generator
AVRI
AO GND
AVRI
Volt/PF ctrl:
AVR Bias = 50%
AO GND
NT
41
voltage mode 0 to 10 V
voltage mode 0 to 10 V with serial 10k resistor
5 V PWM mode
NOTE:
The PWM mode is designed and optimized for Caterpillar governors. Since IC-NT SW v. 1.4.4 speed
governor PWM frequency is fixed to 500 Hz.
Vout
VoutR
PWM
The jumpers for speed governor output mode are shown on the picture below.
The initial level of the governor output is adjustable by the setpoint Speed Gov Bias and the
characteristic (positive or negative) can be selected by the setpoint Speed Gov Char.
The active range of the output can be adapted to the governor input range by setpoints
SpeedGovLowLim and SpeedGovHiLim.
NOTE:
Some governors may evaluate input voltage out of the allowed range as a faulty condition and their
functioning may be blocked.
NT
42
3.16.1
15
16 COM
SG +
AO COM
25 +
26 -
SG +
AO COM
WOODWARD
DPG 2201
WOODWARD
2301A
Speed Control
Woodward
WOODWARD
2301 LS &
Speed control
3.16.1.1
470k
ILS:9
GND:2
SG +
AO COM
VoutR
VoutR
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar = POSITIVE
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar = POSITIVE
Sync/Load Ctrl:
Speed Gov Bias = 2.50 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 0 V
SpeedGovHiLim = 5 V
WOODWARD
EPG
11+
12 -
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 1.50 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 0 V
SpeedGovHiLim = 3 V
OUT2
OUT1
iGAVRi
TRANS
230/400VAC From
generator
0VAC
SG+
iGAVRi
18VAC
WOODWARD
EPG
Options 2
HINT:
NT
For Woodward EPG speed governor (revision F) is in case of InteliCompact limit:
Speed Gov Bias = 1 V
SpeedGovLowLim = 0 V
SpeedGovHiLim = 2 V
PWM
AO COM
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar = POSITIVE
NT
43
WOODWARD
2301D
Speed Control
SG +
AO COM
8
2
VoutR
6
MPU
5
4
3
Sync/Load Ctrl:
Speed Gov Bias = 3.10 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 6.5 V
SpeedGovHiLim = 0 V
Actuator
iGAVRi
TRANS
13 OUT2
12 OUT1
3k3
19
20
230/400VAC From
generator
0VAC
SG+
iGAVRi
18VAC
WOODWARD
ProAct II
WOODWARD
EPG 1712/512
1724/524
PWM
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar = POSITIVE
AO COM
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar = POSITIVE
WOODWARD
Flo-tech
Speed Control
WOODWARD
L-series
8 (Aux1)
5
SG +
AO COM
VoutR
11
12
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 2.50 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 0 V
SpeedGovHiLim = 5 V
Sync/Load Ctrl:
Speed Gov Bias = 0.00 V
NT
44
3.16.1.2
Cummins
QST30
11
20
SG +
AO COM
Cummins
ECPG
Cummins
I9
A1
SG +
AO COM
VoutR
Vout
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
POSITIVE
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
POSITIVE
Cummins
ONAN
10k
5V
0V
SG +
AO COM
VoutR
Cummins
EFC
47/50V
8
11
200k
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
POSITIVE
Sync/Load Ctrl:
Speed Gov Bias = 6.40 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 5 V
SpeedGovHiLim = 7.8 V
Cummins
QSL9
Setting at 1500 RPM: Primary setting governor with disconnected speed regulation lines.
9
32
SG +
AO COM
Vout
Sync/Load Ctrl:
Speed Gov Bias = 3.50 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 2.5 V
SpeedGovHiLim = 5 V
NT
45
Cummins
GCS
03-11
03-12
Caterpillar
PEEC
3.16.1.3
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 2.5 V
SpeedGovHiLim = 7.5 V
Caterpillar
9
19
SG +
AO COM
PWM
Caterpillar
ADEM
Caterpillar
Signal
Converter
2
1
VoutR
67k7
12
10
Sync/Load Ctrl:
Speed Gov Bias = 5.10 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 0 V
SpeedGovHiLim = 10 V
SG +
AO COM
PWM
3.16.1.4
MTU MDEC
2000, 4000
SG +
AO COM
MTU
8
36
SG +
AO COM
Vout
Sync/Load Ctrl:
Speed Gov Bias = 4.90 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 0 V
SpeedGovHiLim = 10 V
NT
46
PLUG F
DEUTZ
BF6M
3.16.1.5
Deutz
24
23
SG +
AO COM
21
Vout
Opened for
0% droop
17
Sync/Load Ctrl:
Speed Gov Bias = 2.50 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 0.5 V
SpeedGovHiLim = 4.5 V
Customer interface
connector (ECM connector)
PERKINS
4016 E61 TRS
PERKINS
1300 EDi
PERKINS
2300, 2800
3.16.1.6
Perkins
24 (J1/17)
20 (J1/3)
Vout
2 (J1/49)
12 (J1/18)
RPS INPUT
VBREF GND
SG +
AO COM
18
19
SG +
AO COM
3.16.1.7
GAC
ESD 5500
SG +
AO COM
VoutR
Vout
Sync/Load Ctrl:
Speed Gov Bias = 2.50 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 0.5 V
SpeedGovHiLim = 4.5 V
Sync/Load Ctrl:
Speed Gov Bias = 2.50 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 0.8 V
SpeedGovHiLim = 4.5 V
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 2.5 V
SpeedGovHiLim = 7.5 V
GAC
N
G
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
NEGATIVE
SpeedGovLowLim = 4 V
SpeedGovHiLim = 6 V
NT
47
GAC
ESD 5330
GAC
SDG 735
GAC
EGS 104B
AUX
M
G
SG +
AO COM
25
2
SG +
AO COM
A
L
Barber Colman
DYNA 8000
9
2
SG +
AO COM
9
2
SG +
AO COM
3.16.1.9
Heinzman E6
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
NEGATIVE
SpeedGovLowLim = 4 V
SpeedGovHiLim = 6 V
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
NEGATIVE
SpeedGovLowLim = 2.5 V
SpeedGovHiLim = 7.5 V
TauSpeedActuat = 1 s
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 6.00 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 4 V
SpeedGovHiLim = 8 V
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 6.00 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 4 V
SpeedGovHiLim = 8 V
Barber Colman
Barber Colman
DYN1 10684
3.16.1.8
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar =
NEGATIVE
Heinzmann
9
2
150k
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 0.00 V
SpeedGovChar = POSITIVE
NT
48
Heinzman
E16
SG +
AO COM
Heinzman
KG-1-03F
5
4
3
GND
SG +
AO COM
Heinzman
PANDAROS
DC6
9
2
1 (B3)
3 (A3)
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 0.00 V
SpeedGovChar = POSITIVE
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 0.00 V
SpeedGovChar = POSITIVE
VoutR
10k
TOHO
3.16.1.10
Toho
11
8
SG +
AO COM
VoutR
Sync/Load Ctrl:
Speed Gov Bias = 4.00 V
SpeedGovChar = POSITIVE
10k
3.16.1.11
ECON 4
Sync/Load Ctrl:
Speed Gov Bias = 5.00 V
SpeedGovChar = POSITIVE
SpeedGovLowLim = 0.8 V
Without resistor
Speed Gov Bias = 2.75 V
SpeedGovLowLim = 0 V
SpeedGovHiLim = 6 V
ComAp
8
7
SG +
AO COM
Vout
Sync/Load Ctrl:
Speed Gov Bias = 5.1 V
SpeedGovChar =
POSITIVE
SpeedGovLowLim = 0 V
SpeedGovHiLim = 10 V
NT
49
The maximum length of the CAN bus depends on the communication speed. For a speed of
250 kbps, which is used on the CAN1 bus (extension modules, ECU) and CAN2 bus if it is
switched to 32C mode, the maximum length is 200 m. If the CAN2 bus is switched to 8C mode
the speed is 50 kbps and the maximum length is 800 m.
The bus must be wired in linear form with termination resistors at both ends. No nodes are
allowed except on the controller terminals.
NOTE:
A termination resistor at the CAN is already implemented on the PCB. For connecting, close
the jumper near the appropriate CAN terminal.
Impedance
120
Propagation velocity
Wire crosscut
0.25 mm
Attenuation (@1MHz)
2dB/100 m
120R
120R
NT
50
The bus has to be terminated by 120 resistors at both ends. External units can be connected on the
CAN bus line in any order, but keeping a line arrangement (no tails, no star) is necessary. Standard
maximum bus length is 200 m for 32C CAN BUS MODE and 900 m for 8C CAN BUS MODE. Shielded
cable must be used. Shielding has to be connected to PE on one side (controller side).
1. For shorter distances (all network components within one room) picture 1
Interconnect H and L; shielding connect to PE on controller side
2. For longer distances (connection between rooms within one building) picture 2
Interconnect H, L, COM; shielding connect to PE at one point
3. In case of surge hazard (connection out of building in case of storm etc.) picture 3
We recommend using the following protections:
Phoenix Contact (http://www.phoenixcontact.com): PT 5-HF-12DC-ST with PT2x2-BE
(base element)
Saltek (http://www.saltek.cz): DM-012/2 R DJ
Recommended data cables: BELDEN (http://www.belden.com)
1. For shorter distances: 3105A Paired EIA Industrial RS-485 PLTC/CM (1x2 conductors)
2. For longer distances: 3106A Paired EIA Industrial RS-485 PLTC/CM (1x2+1 conductors)
3. In case of surge hazard: 3106A Paired EIA Industrial RS-485 PLTC/CM (1x2+1 conductors)
3.18.2
RS485 connection
The line has to be terminated by 120 resistors at both ends. External units can be connected on the
RS485 line in any order, but keeping a line arrangement (no tails, no star) is necessary. Standard
maximum link length is 1000 m. Shielded cable must be used. Shielding has to be connected to PE on
one side (controller side).
1. For shorter distances (all network components within one room) picture 1
interconnect A and B; shielding connect to PE on controller side
2. For longer distances (connection between rooms within one building) picture 2
interconnect A, B, COM; shielding connect to PE at one point
3. In case of surge hazard (connection out of building in case of storm etc.) picture 3
We recommend using the following protections:
NT
51
120
120
H/A
L/B
COM
H/A
L/B
COM
Addr.: 1
H
COM
L
H
COM
L
Extension
module
CAN1
1. IC-NT
CAN2 CAN1
120
H
COM
L
120
2. IC-NT
CAN2 CAN1
120
H
COM
L
H
COM
L
120
PT5-HF-12DC-ST (CAN)
PT5HF-5DC-ST (RS485)
H/A
L/B
COM
IN
IN
12
11
11
12
10
10
OUT
OUT
H/A
L/B
COM
NT
52
3.19.1
IGS-PTM
The IGS-PTM is a DIN Rail mounted extension module that is connected to the controller via a CAN1
bus. The module contains:
8 binary inputs with the same properties and configuration as binary inputs of the controller.
8 binary outputs with the same properties and configuration as binary outputs of the controller.
4 analog inputs with selectable electrical range by a jumper: 0250 , 0100 mV, 020 mA,
suitable for Pt100 and thermocouple sensors
NOTE:
The controller selection jumper (iS/iG) must be in the iG position for using the module with the
NT
InteliCompact .
A separate manual for the IGS-PTM module is available for download on the ComAp web site
NT
53
3.19.2
The IGL-RA15 module is a remote annunciator that is connected to the controller via a CAN1 bus. The
module contains:
The siren is activated automatically if a new yellow or red LED switches on, the duration is adjustable
and it can be silenced by pressing the horn reset button. In the controller the LEDs are configured like
binary outputs, so all binary output functions can be used to drive the LEDs.
NOTE:
THE ADDRESS SELECTION JUMPERS MUST BE IN THE IG POSITION FOR USING THE MODULE WITH THE
NT
INTELICOMPACT .
A separate manual for the IGL-RA15 module is available for download on the ComAp website
NT
54
3.19.3
IL-NT-AOUT8
The IL-NT-AOUT8 module is to be directly plugged-in into the slot on the rear side of the controller.
The module contains 8 PWM open collector type outputs. The outputs are specially designed for
driving analog automotive type gauges. Any of the analog values measured or computed in the
controller can be configured to each output and it is possible to configure a different conversion
characteristic (curve) for each output.
NOTE:
The module is compatible with gauges originally designed for resistive sensors, i.e. they have board
voltage compensation. These gauges have 3 terminals: +BATT, SENSOR, GND.
+ BATT
Automotive
type gauge
AO8
AO7
AO6
AO5
- BATT
AO4
AO3
AO2
AO1
+12/24V
GND
AO8
GND
3.19.4
IL-NT BIO8
55
To insert the module, you must open the cover first (use a screwdriver to open) and then insert the
module into the slot. Once you have inserted it, the module will snap under the plastic teeth. It is
supposed to be installed permanently. Should you need to remove it, the safest way is to remove the
entire back cover and then remove the module manually. Installing the IL-NT BIO8 module is similar to
installing the RS 232 module. The difference is that module fits into the extension module slot and
after installing the IL-NT BIO8 you do not put the small cover back.
BATT+
K1
K21
REL
K2
OUT
BIO1
BIO2
IN
BIO3
K11
BIO4
BIO5
BIO6
BIO7
IN
BIO8
SW1
BATTBATT-
+
BATTERY
Technical details:
NT
IL-NT BIO8 plugs into the InteliCompact controller EXTENSION MODULE port.
8 dedicated pins of the plug-in cards terminal can be configured as binary inputs or outputs.
BINARY INPUTS
Number of inputs
Input resistance
4.7 k
Input range
036 V DC
< 0.8 V DC
> 2 V DC
836 V DC
0.5 A
2A
36 V DC
NOTE:
Binary inputs are not galvanically isolated.
NT
56
3.19.5
IC-NT CT-BIO7
K21
MAINS
L3
K2
0-5A
OUT
IN
K11
CT l
CT k
BIO1
BIO2
BIO3
BIO4
BIO5
IN
SW1
BIO6
BIO7
BATT-
+
BATTERY
Technical details:
NT
IC-NT CT-BIO7 plugs into InteliCompact controller EXTENSION MODULE port.
7 dedicated pins of the plug-in cards terminal can be configured as binary inputs or outputs.
CURRENT MEASURING INPUT
Number of inputs
5A
< 0.1
10 A
150 A / 1 s
10 A
NT
57
BINARY INPUTS
Number of inputs
Input resistance
4.7 k
Input range
036 V DC
< 0.8 V DC
> 2 V DC
836 V DC
0.5 A
2A
36 V DC
NOTE:
Binary inputs are not galvanically isolated.
Usage of CT measuring via the IC-NT CT-BIO7 module:
-
3.19.5.1
When the measured current exceeds the set value, which indicates that part of the current is
dispersed to earth, and when the set Earth Fault Del time elapses, the Earth Fault Sd protection and
AL EarthFault output are activated. Earth Fault protection is not active when gen-set does not run and
the Im/EF input parameter is not set to EarthFltC.
Earth Fault Sd
Time [s]
AL Earth Fault
1
0
Time [s]
Earth Fault Del
CAUTION!
Earth fault current measurement is not intended to protect human health, but the machines!
NT
58
3.20.1
IL-NT RS232
This module contains a RS232 port with all modem signals connected internally to the COM1 of the
controller. DB9M connector is used on the RS232 side.
To controller
RS232 port
DB9M
DB9M
To PC COM
port
NT
59
3.20.2
IL-NT RS232-485
The IL-NT RS232-485 is a dual port module with RS232 and RS485 interfaces at independent COM
channels. The RS232 is connected to COM1 and RS485 to COM2.
RS485
balancing
resistor
jumpers
RS232
COM1
Boot jumper
RS485 120R
terminator jumper
B (RxTx -)
GND
RS485
COM2
A (RxTx +)
+5V
Balancing
resistor
RS485 internal
wiring
Terminator
GND
Balancing
resistor
A
GND
B
3.20.3
IL-NT S-USB
This module contains a USB slave port connected internally to the COM1 of the controller and is
designed as an easily removable service module.
This module requires a FTDI USB Serial converter driver installed in the PC. The driver creates a
virtual serial port (COM) in the PC, which must be used in LiteEdit as communication port when a
connection is being opened.
NOTE:
The FTDI driver is installed together with LiteEdit.
NOTE:
When the USB cable from the controller is plugged for the first time into different USB ports on the PC
including USB hubs, it may be recognized as new hardware and the drivers will be installed again with
a different number of the virtual serial port.
CAUTION!
Use a shielded USB cable only!
NT
60
3.20.4
IB-Lite
IB-Lite is a plug-in module with Ethernet 10/100 Mbit interface in RJ45 connector. The module is
internally connected to both COM1 and COM2 serial channels and provides an interface for
connecting a PC with LiteEdit or InteliMonitor through an Ethernet/internet network, for sending active
e-mails and for integration of the controller into a building management (Modbus/TCP protocol).
RJ45
Ethernet
Restore
default
settings
jumper
IB-LITE MODULE
Use an Ethernet UTP cable with a RJ45 connector for linking the module with your Ethernet network.
The module can also be connected directly to a PC using cross-wired UTP cable.
RJ45
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
CROSS-WIRED UTP 10/100Mbit
CABLE
61
NOTE:
The module requires some setup before initial usage. See the chapter IB-Lite setup procedure.
3.20.5
IL-NT GPRS
This plug-in module is a GSM/GPRS modem which can work in two modes of operation based on the
settings in the setpoint COM1 Mode.
Settings DIRECT = the module works in a GPRS network and enables connection via AirGate
to LiteEdit and WebSupervisor as well as sending SMS alarms.
Settings MODEM = the module works as a standard GSM modem enabling a CSD (Circuit
Switch Data) connection to the controller with LiteEdit or InteliMonitor and sending SMS
alarms.
NOTE:
GPRS and CSD services must be provided by your GSM/GPRS operator for successful operation.
NOTE:
THE GPRS AND CSD CONNECTION SHOULD NOT BE USED FOR THE FIRMWARE UPDATE PROCESS. USE
INSTEAD A WIRED CONNECTION LIKE RS232, USB, RS485 OR ETHERNET VIA IB-LITE!
NOTE:
It is necessary to power the controller and individually the IL-NT GPRS module as well.
WARNING
NT
62
Any manipulation of the IL-NT GPRS module should be done only without voltage.
3.20.5.1
SMS Commands
NT
To control the gen-set equipped with InteliCompact controller and IL-NT GPRS communication
module (or modem) via SMS requests, send an SMS in the structure of:
# xxxx, yyyy, zzzz, etc.
to the telephone number of the SIM card in your IL-NT-GPRS module (or modem). Where the # mark
means the controller access code, xxxx means the Command 1, yyyy is Command 2, zzzz is
Command 3, etc.
Example:
When the controller, in AUT mode, with a controller name of IC-NT-Test, with the IL-NT
GPRS module and access code 0 receives the SMS:
0 man, start, d10, gcb close, d300, gcb open, d30, stop, d30, aut
the mode will be changed to MANUAL. The engine will be started and after 10 s the
controller will start the synchronization process and the GCB will close. After 300 s (from
the point of starting synchronization) the GCB will open (after the GCB Opens Del
setpoint), the engine will stop with a 30 s delay and it will go into AUT mode.
The controller will send back the SMS:
#IC-NT-Test:
man<OK>,start<OK>,d_ok,gcb_close<OK>,d_ok,
gcb_open<OK>,d_ok,stop<OK>,d_ok,aut<OK>
if all conditions are correct.
NOTE:
The value OK in an SMS means that the command was successfully transmitted to the controller.
Potential errors/alarms during execution of commands are shown in Event SMS if is set (as is
described below).
3.20.5.2
Event SMS
NT
The InteliCompact controller equipped with the IL-NT GPRS communication module is able to send
Event SMS according to the setting in the SMS/Email setpoint group:
NT
63
Engine Start/Stop
o Manual Start/Stop
o Remote Start/Stop
o Gen Peak Start/Stop
o PMS StartStop (as Power Management System Start/Stop)
o AMF Start/Stop (as Automatic Mains Failure Start/Stop)
o Test Start/Gen-set Stop
Mains Fail
Mains Returned
Load on Mains
Load on Genset
Parallel Operation
Test On Load
3.20.6
InternetBridge-NT
The InternetBridge-NT (IB-NT) is a communication module that allows connection of a single controller
as well as a whole site to the internet or a Local Area Network. The internet connection can be
enabled via the built-in cellular modem supporting 2G and 3G networks or via Ethernet cable.
For InteliCompact
-
NT
Direct Ethernet connection to ComAp configuration and monitoring tools (LiteEdit, InteliMonitor
or WebSupervisor)
AirGate support
Web interface
NOTE:
NT
Support of InteliCompact controllers is in IB-NT 1.2 SW and newer.
For further information and options that can be set, see IB-NT Reference Guide.
NT
64
3.21.1
The main difference is less wiring, sensors and actuators in an EFI-engine application compared to a
classic one. The typical wiring of an EFI-engine application shows that there are no analog sensors,
no pickup and no governor. All this information is being communicated between the controller and the
ECU via the communication bus.
3.21.1.1
Data received from the ECU (if available in the particular ECU)
OBJECT
TYPE
ALARM
Engine speed
Analog
Oil pressure
Analog
Configurable
Coolant temperature
Analog
Configurable
Oil temperature
Analog
None
Boost pressure
Analog
None
Intake temperature
Analog
None
Analog
None
Fuel rate
Analog
None
Fuel level
Analog
Configurable
Engine hours
Analog
None
Yellow lamp
Binary
Warning
Red lamp
Binary
Shutdown
Engine hours
Analog
None
COMMENTS
NT
65
NOTE:
The ECU values Oil pressure, Coolant temperature and Fuel level can be configured as source values
for the controller analog inputs 1, 2, 3 instead of physical terminals. In that case, all analog inputrelated things like protections, switches, etc. work the same way as if physical terminals are used.
In case there is valid value of Running Hours (Engine Hours) coming from ECU, controller will prefer
that value instead of internal calculation
3.21.1.2
OBJECT
TYPE
Analog
Start request
Binary
Stop request
Binary
Idle/Nominal switch
Binary
Shutdown override
Binary
Binary
3.21.1.3
COMMENTS
50/60Hz selection
ECU alarms
Alarms (diagnostic messages) are read from the ECU and displayed in the ECU Alarmlist
3.21.1.4
No
No
Yes
Scania S6 Singlespeed
Yes
Yes
Yes
Scania S8 Singlespeed
Yes
Yes
Yes
Yes
Yes
Yes
Deutz EMR2
No
Yes
Yes
Deutz EMR3
Yes
Yes
Yes
Deutz EMR4
No
Yes
Yes
Cummins CM570
Yes
Yes
Yes
Cummins CM850/CM2150/CM2250
No
No
No
Cummins MODBUS
MTU ADEC
Yes
Yes
Yes
Yes
Yes
Yes
Waukesha ESM
No
No
No
NT
66
Yes
Yes
Yes
No
No
Yes
John Deere
No
No
Yes
Perkins ECM
No
No
Yes
Perkins 1300
No
Yes
No
No
No
Yes
Caterpillar J1939
No
No
Yes
No
No
Yes
VM Industrial
No
No
Yes
VM Marine
No
Yes
Yes
MAN MFR
Yes
Yes
Yes
SISU EEM3
Yes
Yes
No
GM MEFI6
No
No
Yes
GM SECM
No
No
Yes
GM e-control
No
No
Yes
GM e-control LCI
No
No
Yes
ISUZU ECM
Yes
Yes
Yes
DaimlerChrysler ADM2
Yes
Yes
Yes
JCB Delphi
No
No
Yes
NOTE:
NT
Support for electronics engines was unified with the InteliLite Comap controller family. Please use
NT
the ECU List version 5.9 or higher for proper function with the InteliCompact 2.0 firmware. ECU List
5.9 is part of the IC-NT 2.0 Installation Suite.
Support of new ECU types is continuously added to the new firmware releases. If you cannot find your
ECU type in the list, please download the latest release of the document ComAp Electronic Engines
Support from http://www.comap.cz or contact technical support for more information.
NT
67
AVRi-TRANS
AC
230V
LOAD
MCB
MAINS INLET
FULL
LOAD
ALARM
REM START/STOP
EMERGENCY STOP
ACCESS LOCK
WARNING ALARM
SHUTDOWN ALARM
SHUTDOWN ALARM
NT
68
IG-AVRi
GCB
Binary inputs
BI8
GENERATOR
AVR
Mains voltage
SPtM
Power
BI7
D+
ENGINE
ECU
Generator voltage
AI3
L1
Generator current
Binary outputs
BI5
BI6
L2
IC-NT
RPM GND
Communication module
BO8
L3
Pickup
RPM
D+ (L)
+B
AI1
BI4
BO7
Analog
inputs
BO2
L1
AI2
BI3
BO6
Governor
AVRi
BO1
N
AI COM
L3
AO GND
CAN1
Ext. modules
AVR+
L2
SG+
BI2
BO5
L3
L
-B
Extension module
BI1
BO4
L1
H
COM
BO3
L2
COM
BI9
STARTER
+B
AVRi-TRANS
AC
230V
LOAD
MCB
MAINS INLET
FULL
LOAD
ALARM
REM START/STOP
EMERGENCY STOP
ACCESS LOCK
WARNING ALARM
SHUTDOWN ALARM
SHUTDOWN ALARM
NT
69
IG-AVRi
GCB
BI8
GENERATOR
Binary inputs
Power
BI7
D+
AVR
Mains voltage
SPtM
Binary outputs
BI5
BI6
ENGINE
GOVERNOR
Generator voltage
RPM GND
L1
Generator current
IC-NT
RPM
Communication module
BO8
L3
Pickup
BO2
L2
AI3
BI4
BO7
Analog
inputs
AI1
BI3
BO6
Governor
AVRi
BO1
L1
AI2
CAN1
Ext. modules
AVR+
N
AI COM
L3
AO GND
BI2
BO5
L3
L
L2
SG+
D+ (L)
-B
Extension module
BI1
BO4
L2
COM
SPEED
PICKUP
COM
STARTER
FUEL SOLENOID
GLOW PLUGS
OIL PRESSURE
FUEL LEVEL
COOLANT TEMPERATURE
BO3
L1
H
BI9
+B
AVRi-TRANS
AC
230V
COMMON
BUSBAR
SYST RES
OK
ALARM
EMERGENCY STOP
ACCESS LOCK
PRIORITY 0
SHUTDOWN ALARM
WARNING ALARM
FUEL SOLENOID
GLOW PLUGS
OIL PRESSURE
FUEL LEVEL
COOLANT TEMPERATURE
SYS START/STOP
MCB FEEDBACK
NETWORK CAN
TO OTHER CONTROLLERS
NT
70
IG-AVRi
GCB
BI8
GENERATOR
Binary inputs
BI7
D+
AVR
Mains voltage
Power
BI5
BI6
ENGINE
GOVERNOR
Generator voltage
MINT
Binary outputs
Communication module
BO8
Generator current
AI3
BI4
BO7
L3
RPM GND
Pickup
RPM
BI3
BO6
L2
IC-NT
AI1
BI2
BO5
Analog
inputs
BO2
L1
AI2
BI1
BO4
Governor
AVRi
BO3
CAN2
Network
BO1
N
AI COM
L3
AO GND
CAN1
Ext. modules
AVR+
L1
L
D+ (L)
-B
Extension module
SPEED
PICKUP
NETWORK CAN
TO OTHER CONTROLLERS
L3
L
L2
SG+
N
COM
L1
H
COM
L2
COM
BI9
STARTER
Connecting a normally closed mushroom-type button to the binary input Emergency Stop.
This is a purely software solution.
A hard-wired solution, where the button also disconnects the power supply from the controller
outputs.
- BATT
EMERGENCY STOP
INPUT
+ BATT
OUTPUTS
NT
71
The controller is delivered with a default configuration that should fit most standard applications.
Nevertheless you may need to modify it because your application is different. Please refer to the
LiteEdit manual or help file for information on using LiteEdit for changing the particular items of the
configuration and writing the configuration to the controller.
4.2
Although the controller is delivered with the latest firmware available at the moment of production, it
may be necessary to upgrade the firmware in future. The process of programming the firmware
involves the following steps:
1. First you need the requested firmware. Firmware of standard branch and major versions are
distributed and installed together with the LiteEdit installation package. Release versions and
branches are distributed as import packages that need to be imported into LiteEdit.
2. The latest installation and/or import packages are available for download at www.comap.cz.
Please register to get access to the download page. Registration is free.
3. The import package is a file with the IWE extension. To perform the import, start LiteEdit, do
not open any connections, go to Options -> Import firmware and select the appropriate file.
4. Create an online connection to the controller and save the archive for backup purposes.
NOTE:
It is not possible to update firmware when the connection is offline!
5. Go to the menu Controller -> Programming and cloning -> Programming, select the
appropriate firmware and press the OK button.
6. The selected firmware will be programmed into your controller.
NT
72
NOTE:
It is possible to program only firmware compatible with the currently attached controller. Other
firmware is disabled and cannot be selected for programming.
CAUTION!
The configuration reverts to the default after firmware has been programmed. You must re-program
the configuration if the default one is not appropriate for your application!
CAUTION!
Also some setpoints may have incorrect values after new firmware was programmed. Please check all
setpoints after programming.
4.3
If the controller does not contain valid firmware, new firmware cannot be programmed in the standard
way. This situation can occur if the connection between the PC and the controller was interrupted e.g.
during a previous firmware upgrade. In such a case the controller has a blank display and does not
communicate with the PC. The boot-jumper must be used to get valid firmware into the controller.
1. Disconnect the power supply from the controller, insert a communication module and close the
boot-jumper.
NT
73
4.5
4.5.1
SPtM
SPtM only
BINARY INPUTS
NO.
DESCRIPTION
CONFIGURED FUNCTION
BI1
GCB Feedback
BI2
MCB Feedback
BI3
Remote start/stop
Rem Start/Stop
BI4
Emergency Stop
BI5
Access Lock
BI6
Warning alarm
None
BI7
None
BI8
Shutdown alarm
None
BI9
Shutdown alarm
None
BINARY OUTPUTS
NO.
CONFIGURED FUNCTION
BO1
Starter
BO2
Fuel Solenoid
BO3
GCB Close/Open
BO4
MCB Close/Open
BO5
Prestart
BO6
Alarm
BO7
Horn
BO8
None
ANALOG INPUTS
NO.
INPUT NAME
CONFIGURED SENSOR
AI1
Oil pressure
AI2
Water temperature
AI3
Fuel level
NOTE:
A wiring diagram that corresponds to the factory default SPtM configuration is available in a separate
chapter in the Installation section of this manual.
NT
74
4.5.2
MINT
MINT only
BINARY INPUTS
NO.
DESCRIPTION
CONFIGURED FUNCTION
BI1
GCB Feedback
BI2
MCB Feedback
BI3
System start/stop
Sys Start/Stop
BI4
Emergency Stop
BI5
Access Lock
BI6
Top Priority
BI7
BI8
Warning alarm
None
BI9
Shutdown alarm
None
BINARY OUTPUTS
NO.
CONFIGURED FUNCTION
BO1
Starter
BO2
Fuel Solenoid
BO3
GCB Close/Open
BO4
BO5
Prestart
BO6
Alarm
BO7
Horn
BO8
SystReserve OK
ANALOG INPUTS
NO.
INPUT NAME
CONFIGURED SENSOR
AI1
Oil pressure
AI2
Water temperature
AI3
Fuel level
NT
75
4.6
Step-by-step guide
In the following you will find several steps which you should carry out when you are putting a gen-set
into operation. It supposes that the switchboard wiring has been already checked.
NOTE:
This guide is not a handbook for a beginner, but it is focused on things specific for ComAp controllers
and expects sufficient knowledge and skills in the field of generating sets!
WARNING!
Some parts of the generator, engine and switchboard may carry dangerous voltage which can cause
injury or death when touched!
WARNING!
Rotating parts of the gen-set can catch hair or clothing and cause serious injury.
1. Disconnect the binary outputs from the controller before connecting the power supply. If you
have an SPtM application, be sure that the MCB and GCB are protected against accidental
switching when you are working in the switchboard.
2. Check the controller configuration according to the wiring diagram of the switchboard. If the
configuration has been modified, write it to the controller
3. Write all setpoints from the default archive and then go through them and readjust all of them
if it is necessary. Pay special attention to nominal values, overspeed, gear teeth, fuel solenoid
and CT ratio.
4. Check all settings regarding speed sensing and additional running information, especially if
you do not use a pickup for speed sensing.
5. Adjust bias setpoints for the governor and AVRi output to the recommended levels and adjust
all delays for generator protections to high values to have enough time for making adjustments
on a running gen-set.
6. Connect the binary outputs back.
7. Adjust all setpoints related to engine start and stabilization phase, then start the gen-set in
MAN mode and then make fine readjustments.
8. Leave the gen-set running and adjust the governor and/or AVRi so that the gen-set will have a
speed and voltage near to the nominal values. If it is not possible to achieve this by turning the
trim on the AVRi and/or governor, you can also slightly change the bias setpoints.
NOTE:
The bias setpoints must not be near the limits for the particular output, because the regulation
loops need sufficient reserve of the output range on both sides to work correctly.
9. Adjust all generator and engine protections according to your needs including the delays.
10. Adjust the setpoint Phase Window to 0. This adjustment will disable issuing of the GCB close
command during synchronization, but the synchronization itself will be performed normally for
the whole adjusted time.
11. Press the GCB button to start the synchronizing. Then, using a voltmeter connected directly
over the contactor, check if the synchroscope indication on the controller screen matches the
voltage. The voltage must be near to 0V when the synchroscope is in a 12 o'clock position
and near to 2*Unominal when it is in a 6 o'clock position. Check all three phases.
NT
76
GCB
MIN
OPEN
MAX
V
I
GCB
MIN
OPEN
MAX
V
I
12. Adjust the setpoint Phase Window back to your desired value (typically 37).
13. Synchronize the gen-set with the mains or other gen-sets. Adjust the setpoints for voltage,
frequency and angle regulation loops to achieve fast and reliable synchronization.
14. Adjust the setpoints for power, power factor, load-sharing and VARsharing loops.
15. Check the rest of the setpoints and then save the archive to disk for backup purposes.
NT
77
5 Operator guide
5.1
16
1
2
3
4
9
10
11
18
19
20
17
15
14
13
12
POSITION
DESCRIPTION
START button. Works in MAN mode only. Press this button to initiate the start
sequence of the engine. See the Engine start chapter in the Reference Guide
to learn more about the start sequence.
STOP button. Works in MAN mode only. Press this button to initiate the stop
sequence of the gen-set. Repeatedly pressing or holding the button for more
than twice will cancel the current phase of stop sequence (like ramping the
power down or cooling) and the next phase will continue. See the Engine cool
down and stop chapter in the Reference Guide to learn more about the stop
sequence.
HORN RESET button. Use this button to deactivate the horn output without
acknowledging the alarms.
NT
78
MODE LEFT button. Use this button to change the mode. The button works
only if the main screen with the indicator of the currently selected mode is
displayed.
5
NOTE:
This button will not work if the controller mode is forced by one of the binary
inputs listed in the Reference Guide in the Operating modes chapter.
MODE RIGHT button. Use this button to change the mode. The button works
only if the main screen with the indicator of the currently selected mode is
displayed.
NOTE:
This button will not work if the controller mode is forced by one of the binary
inputs listed in the Reference Guide in the Operating modes chapter.
GCB button. Works in MAN and TEST modes only. Press this button to open
or close the GCB or start synchronizing manually. Note that certain conditions
must be fulfilled otherwise GCB closing (starting of synchronization) is
blocked. See the Connecting to the load chapter in the Reference Guide for
details.
MCB button. Works in MAN and TEST modes only. Press this button to open
or close the MCB or start the reverse synchronizing manually.
8
CAUTION!
You can disconnect the load from the mains supply with this button! Be sure
you are well aware of what you are about to do!
General alarm. This red indicator lights up if at least one alarm is present in the alarm
list. It blinks if a new alarm has appeared and is still not acknowledged.
Gen-set voltage OK. This green indicator lights up if the generator voltage and
frequency is within the limits.
10
NOTE:
The limits for the generator voltage and frequency are given by setpoints in the Gener
Protect group.
11
GCB position. This green indicator blinks if the forward synchronizing is currently in
progress; otherwise it shows the current status of the generator circuit breaker
according to the feedback input.
12
Bus under voltage. This green indicator shows if the bus is under voltage or not.
13
MCB position. This green indicator blinks if the reverse synchronizing is currently in
progress; otherwise it shows the current status of the mains circuit breaker according to
the feedback input.
14
Mains voltage OK. This green indicator lights up if the mains are evaluated as healthy.
See the AMF function chapter in the Reference Guide for details about mains
evaluation.
15
Mains failure. This red indicator starts blinking when mains failure is detected. After
the gen-set has started and is about to take the load, it lights up permanently until the
mains failure disappears.
DESCRIPTION
NT
79
16
17
PAGE button. Use this button to switch across display pages. See the next
chapter for details about display pages and screens structure
18
19
20
ENTER button. Use this button to finish editing a setpoint or move right in the
history page.
5.2
User mode allows the user to go through all screens with measurements and alarms. The
button does not work, i.e. setpoints and history pages are not accessible.
Engineer mode gives qualified personnel full access to all pages and screens.
See the chapter User interface mode selection to learn how to change the user interface mode.
5.3
The displayed information is structured into pages and screens. Use the
over the pages.
button to switch
1. The Measurement page consists of screens which display measured values like voltages,
current, oil pressure, etc. and computed values such as gen-set power, statistic data and the
alarm list on the last screen.
2. The Setpoints page contains all setpoints organized into groups and also a special group for
entering the password.
3. The History log page shows the history log in order with the last record displayed first.
NOTE:
The picture below shows the structure of displayed data. The contents of each particular screen may
be slightly different according to the firmware branch and version.
NT
80
SETPOINTS
HISTORY LOG
Time
Date
16:00:00
16/11/2011
>15:00:00
16/11/2011
14:35:00
16/11/2011
19:20:00
14/11/2011
-1 Time Stamp
NT
81
5.4
Press the
button repeatedly until you see the main screen with the kW meter and mode
or
MODE SELECTOR
BREAKERS STATUS
ENGINE STATUS
POWER FACTOR
ENGINE SPEED
CURRENT PROCESS
TIMER
ACTIVE POWER
5.5
1. Press the
button repeatedly until you see a screen with a list of setpoint groups. Then
or
or
4. Press the
button to confirm the change or
setpoints of the selected group.
5. Continue by changing another setpoint or press
NT
82
EDITING A SETPOINT
5.6
1. Press the
button repeatedly until you see the main history log screen with the reason
column and the latest record.
NOTE:
The records are numbered in reverse order, i.e. the latest (newest) record is 0 and older
records have "-1", "-2", etc.
2. Use the
button to move over columns within the selected record. Pressing it repeatedly
will move cyclically through the columns, i.e. after the last column the first one will be
displayed.
3. Use the buttons
4. Press the
and
NT
83
5.7
Browsing alarms
The Alarmlist and ECU Alarmlist are displayed on the last two screens in the measurement page. If
the main screen is displayed, then the Alarmlist screen will appear automatically whenever a new
alarm occurs. It can be also displayed manually as described in the chapter View measured values.
Use the
button to move over the alarms in the ECU Alarmlist. Details of the selected
alarm are displayed in the bottom line.
Press the
Active alarms are displayed as white text on a black background. This means the alarm is
still active, i.e. the appropriate alarm conditions are still present.
Inactive alarms are displayed as black text on a white background. This means the alarm is
no longer active, i.e. the appropriate alarm conditions are gone.
Unconfirmed alarms are displayed with an asterisk. This means the alarm is still not
acknowledged (confirmed).
Number of
alarms
ALARMLIST
Active but confirmed alarm
Selected alarm indicator
Active confirmed alarm,
DTC numeric form
Inactive unconfirmed alarm,
DTC numeric form
Ecu AlarmList
EngOil Press
>EngOil
000225 (00E1h)
*000600 (00258h)
________________________
FC
100 OC 1 FMI
1
ECU ALARMLIST
NT
84
NOTE:
The ECU AlarmList is visible only if an ECU is configured.
5.8
A password must be entered prior to adjusting setpoints that are password-protected. The password is
located in the first group of setpoints and the method to enter or change the password is similar to
changing setpoints as described in the setpoints chapter.
NOTE:
It is possible to change only passwords of the same or lower level than the currently entered
password!
NOTE:
Lost password? Display the information screen which contains the serial number and a password
decode number as described in the chapter below. Write down both numbers and send a request to
retrieve the password to your local distributor containing these two numbers. You can also save and
send an archive instead.
5.9
1. Press the
button repeatedly until you will see the main controller screen with the mode
selector and kW analog meter.
2. Hold down the
button and simultaneously press the
button to see the controller
information screen.
3. The information screen will disappear automatically after 5 seconds.
4. Press the
5. Press the
button again to switch to the user interface mode selection screen. This
screen also contains the serial number and password decode number.
6. Pressing the button
7. Press the button
NT
85
1)
2)
Controller Name
Firmware identification string
Serial number of the controller
Firmware version, application version
Application type
Branch name
NT
86
or
button.
buttons to select the desired
button twice.
or
or
repeatedly to increase
NT
87
6 Function description
This chapter describes the most frequent situations in the gen-set control. Non-standard situations and
combinations with a low probability of occurrence are not described.
6.1
StartFail alarm
Connecting to the
load
(closing GCB)
Disconnecting load
(opening GCB)
No
Stop command?
Gen-set not
ready
Yes
Stop not successful
StopFail alarm
Fault reset
Stop sequence
continues
NT
88
6.2
StartFail alarm
SynchroTimeout
alarm
Synchronization
Synchronization not
successful
Connecting to the
load
(closing the GCB)
Soft loading
Parallel operation
(kW/PF regulation
or kW/kVAr sharing)
Soft unloading
Stop command:
either pressing
STOP button in MAN
mode, or automatic
stop in AUT mode
stop sequence
Disconnecting load
(opening GCB)
Gen-set not
ready
Fault reset
No
Stop command?
Yes
Cooling and stop
sequence
StopFail alarm
Stop not successful
Stop sequence
continues
NT
89
6.3
Operating modes
Selecting the operating mode is done through MODE buttons on the front panel or by changing the
Controller mode setpoint (from the front panel or remotely).
NOTE:
If this setpoint is configured as password-protected, the correct password must be entered prior to
attempting to change the mode.
NOTE:
The mode cannot be changed if Access Lock input is active.
The following binary inputs can be used to force one respective operating mode independent of the
mode setpoint selection:
Remote OFF
Remote MAN
Remote AUT
Remote TEST
Rem TEST OnLd
If the respective input is active the controller will change the mode to the respective position according
to the active input. If multiple inputs are active, the mode will be changed according to priorities of the
inputs. The priorities match the order in the list above. If all inputs are deactivated, the mode will return
to the original position given by the setpoint.
6.3.1
OFF
The GCB will be opened and the engine will be immediately stopped in this mode without unloading
and cooling. After that the controller will stay in Not ready status and cannot be started any way. The
MCB is closed permanently (MCB Opens On = GENRUN) or is open or closed according to whether
the mains are present or not (MCB Opens On = MAINSFAIL). No AMF function will be performed. The
buttons MCB, GCB, START, STOP including the appropriate binary inputs for external buttons are not
active.
6.3.2
MAN
The engine can be started and stopped manually using the START and STOP buttons (or external
buttons wired to the appropriate binary inputs) in MAN mode. When the engine is running, GCB can
be closed to a dead bus or synchronizing can be started by the GCB button. Also MCB can be closed
and opened manually using the MCB button, regardless of whether the mains are present or not. No
auto start is performed. No reaction to the inputs Sys Start/Stop or Rem Start/Stop.
A loaded engine in MAN mode will perform Load sharing and VAR sharing, but will not take place
within the power management.
NOTE:
The breakers are internally locked to close two voltages against each other without synchronizing! The
controller will automatically recognize if the breaker can be just closed or must be synchronized.
CAUTION!
The MCB can be opened manually in MAN mode. Accidental opening of the MCB will cause the object
(load) to remain without power!!!
NT
90
6.3.3
AUT
The engine is started and stopped by the binary input Rem Start/Stop (SPtM), by the Load demand
auto start function (SPtM) or by the Power management (MINT). The buttons MCB, GCB, START,
STOP including the appropriate binary inputs for external buttons are not active. The full start
sequence up to the moment when the engine is loaded is automatic as well as unloading and the stop
sequence.
WARNING!
If a red alarm is present and the gen-set is in AUT mode, it can start by itself after all red alarms
become inactive and are acknowledged!!! To avoid this situation, adjust the setpoint Reset to MAN to
the ENABLED position.
6.3.4
TEST
SPtM only
The behaviour of the controller in TEST mode depends mainly on the setting of the ReturnFromTEST
setpoint.
If the GCB button is pressed, the controller will synchronize to the mains, transfer the load to
the gen-set (the maximum time that both breakers are closed is determined by the
BreakerOverlap setpoint) and then open the MCB.
If the MCB button is pressed, the controller will open the MCB, then wait for Transfer Del and
finally close the GCB.
When the load is supplied by the gen-set and the mains are healthy, pressing the MCB button will start
reverse synchronizing and transfer the load back to the mains.
The gen-set remains running until the mode is changed.
synchronize to the mains, transfer the load to the gen-set (the maximum time that both
breakers are closed is determined by the BreakerOverlap setpoint) and then open the MCB
will make a switchover, i.e. open the MCB, wait for Transfer Del and close the GCB.
or
NT
91
This depends on position of the binary input ForwSyncDisable. After the binary input Rem TEST OnLd
has been deactivated, the controller goes back to the previous operation mode and its behaviour
depends on that. In most cases it will be AUT mode and the controller will either stay supplying the
load if the mains have failed, or will transfer the load back to the mains.
NOTE:
During the BreakerOverlap time, when both breakers are closed, the load is controlled either to the
constant Baseload level (if the MCB has to be opened) or to zero level (if the GCB has to be opened).
6.4
6.4.1
Engine start
Diesel engine
NT
92
Starter activated
Yes
Starting RPM
reached?
Starter
deactivated
No
Engine is started
Yes
Another engine
running symptom
present?
Starter
deactivated
No
No
MaxCrank time
elapsed?
Yes
Yes
Last attempt?
No
Start pause
Yes
Starting RPM
reached?
Engine is started
No
Yes
MaxCrank time
elapsed?
Fuel solenoid
deactivated
NT
93
6.4.2
Gas engine
NT
94
Fuel solenoid
and Ignition
activated
30 RPM reached?
Yes
Starting RPM
reached?
Starter
deactivated
Engine is started
No
MaxCrank time
elapsed?
No
Yes
Starter, Fuel
solenoid, Ingition
deactivated
Yes
Last attempt?
Start pause
NT
95
NOTE:
The starting sequence will be interrupted at any time if a stop command comes.
NOTE:
The Underspeed protection starts to be evaluated 5 after the engine has been started (according to
point 4).
NOTE:
When the engine is started (according to point 4) the delay given by the setpoint ProtectHoldOff will
count down. After it has elapsed, the protections configured as engine running only will start to be
evaluated.
Continue to the stabilization phase.
6.5
Stabilization
When the start-up sequence is finished, the gen-set goes into the stabilization phase. There are two
timers (setpoints) in this phase:
1. Min Stab Time starts to count down just after the idle period has finished. Generator voltage
and frequency are not checked (respective protections are not evaluated) and the GCB
cannot be closed even if the generator voltage and frequency are within limits.
2. Max Stab Time starts to count down just after the idle period has finished. Generator voltage
and frequency are not checked (respective protections are not evaluated) but, opposite to the
previous timer, the GCB can be closed (or synchronizing started) if generator voltage and
frequency are within limits.
In situations where the GCB is closed automatically (AUT, TEST modes), the closing of GCB or
starting of synchronization will occur in the first moment when the generator voltage and frequency will
get into limits and the Min Stab Time has already elapsed.
In the event that the generator voltage or frequency are not within limits within the Max Stab Time
period, the appropriate protection(s) will be activated and the gen-set will be cooled down and
stopped.
NOTE:
The limits for the generator voltage and frequency are given by setpoints in the Gener protect group.
NOTE:
The value of the Min Stab Time setpoint must be lower than the value of Max Stab Time setpoint.
Continue to the connecting to the load phase.
6.6
When the stabilization phase is finished, the gen-set can be connected to the load.
The command for connecting the gen-set to the load is issued either automatically (AUT, TEST
modes) or manually by pressing the GCB button. The following conditions must be valid:
The gen-set is running and the Min Stab Time timer has elapsed.
The gen-set voltage and frequency are within limits.
NT
96
NOTE:
The governor and AVR must be adjusted properly to achieve these limits as the controller does not
perform any regulation and the regulation outputs have constant values given by the AVRi Bias and
Speed Gov Bias setpoints.
There are two ways to connect the gen-set to the load (bus bar). This depends on the state of MCB
feedback and on the measured mains/bus voltage.
6.6.1
SPtM: if the MCB is open, the bus bar is considered as voltage-free and the GCB is closed without
synchronizing.
MINT: the measured bus voltage is also taken in account and it must be below 2% of the nominal bus
voltage together with the open MCB to close the GCB without synchronizing.
NOTE:
If the group of gen-sets is activated and multiple gen-sets have to start simultaneously and connect to
the empty bus bar, there is an internal logic to prevent closing of more GCBs to the bus bar at the
same moment without synchronizing. One of the gen-sets will close the GCB, the others will wait and
then they will synchronize to the first one.
NOTE:
There also is a protection of Bus power loss sensing. The Bus Measure Error is detected in MINT
application when the voltage on the controllers bus terminals is out of limits 20 seconds after:
a) GCB (own) was closed in MAN or AUT mode
b) MCB (feedback) was closed in AUT mode
c) Any other GCB in power management group (on CAN bus) was closed.
The alarm is activated after 20s. However, the GCB (own) closing is blocked immediately for safety
reasons.
This protection can avoid e.g. potential direct closing of GCB while the controllers bus conductors are
unintentionally unplugged from the terminals.
6.6.2
Synchronizing
SPtM: If the MCB is closed, the bus bar is considered to have identical voltage as measured on the
mains. If the mains voltage/frequency is within limits, the gen-set is first synchronized with the mains
and then the GCB is closed.
MINT: If the measured bus voltage is within limits, the gen-set is first synchronized with the bus and
then the GCB is closed.
The synchronizing consists of voltage matching and frequency/angle matching. The maximum
duration of synchronizing is given by the setpoint Sync Timeout. If the synchronizing is not successful
within this period of time, the Sync Timeout alarm will be issued.
NOTE:
The synchronization will be interrupted automatically if any of the necessary conditions disappear
during the synchronization process.
When the controller starts to synchronize (the event will change to Synchro) and the Main Measuring
screen is displayed, it will be automatically change to the Synchroscope screen for the entire duration
of synchronization. After synchronization the Synchroscope screen is automatically changed back to
the Main Measuring screen.
NT
97
NOTE:
It is also possible to change screens manually (arrows Up and Down) after displaying the
Synchroscope screen. In this case there is no automatic return to the Main Measuring screen after
synchronization is finished.
6.7
After the gen-set has been synchronized to the mains, the parallel to mains operation follows. It
consists of the following phases:
6.7.1
The first phase of the PTM operation is ramping the gen-set up to the requested power level. The
speed of the ramp is given by the setpoint Load Ramp. The setpoint adjusts the ramp time for a
change from 0% to 100% of nominal power.
6.7.2
Load control
The load is maintained at the constant level given by the setpoint Baseload. Regulation adjustment
setpoints are available in the Sync/load control group.
NOTE:
In every moment when the requested load (e.g. baseload setpoint) changes, the ramp described in the
chapter above will also take place.
6.7.3
The power factor is regulated to a constant value given by the setpoint Base PF. PF regulation loop is
active. Regulation adjustment setpoints are available in the Volt/PF control group.
NT
98
6.7.4
The gen-set can start and stop automatically according to the object load. To enable this function, the
setpoint PeakAutS/S del must not be set to 0 (OFF). An automatic start will occur if the object exceeds
the limit given by the setpoint PeakLevelStart and remains exceeded for a period longer than
PeakAutS/S del. If the object load drops below PeakLevelStop, the gen-set will be stopped with the
same delay as during start. The gen-set load is controlled according to the selected mode (see
above).
NOTE:
The gen-set will continue to run if the binary input Rem Start/Stop is active.
6.7.5
When a stop command is received e.g. the binary input Sys Start/Stop is deactivated or the STOP
button is pressed the gen-set load is ramped down before opening the GCB. The ramp speed is
given by the setpoint Load Ramp, the end level is given by GCB Open Level and the timeout for
finishing the ramping without reaching the open level is given by GCB open Del.
When the GCB button is pressed, the gen-set load is ramped down before opening the GCB as well.
But after the GCB has been opened, the gen-set remains running until a stop command comes or the
GCB is pressed again to reclose the GCB.
Continue to the cool down and stop phase.
6.7.6
Load [kW]
The gen-set can start and stop automatically according to the object load. An automatic start will occur
if the object load exceeds a given upper limit (PeakLevelStart) and remains exceeded for a given
period of time (PeakAutS/S Del). If the object load drops below a given lower limit (PeakLevelStop),
the gen-set will be stopped with the same delay period experienced during start.
Covered by
Mains
Peak Level Start
Start
Start
Stop
2:00
Covered by
Gen-set
4:00
6:00
8:00
10:00
12:00
Stop
14:00
16:00
18:00
20:00
22:00
24:00
Time [h]
NOTE:
For this function it is necessary to use the IC-NT-CT-BIO7 extension module for measurement of
Mains 1Ph current. The Im/EF CT Ratio parameter must be set up according to the current measuring
transformer and the Im/EF input parameter must be set to Mains.
6.7.7
Export Limit
If Export Limit function is enabled, the value of power which is covered by mains is given by value of
setpoint Export kW. E.g. if 100 kW has to be covered always by mains the Export kW parameter is set
to -100 kW. The rest, all peaks, are then covered by gen-set or by group of gen-sets.
NT
99
NOTE:
If the Export kW setpoint is negative, it actually means import. This function can be used to protect the
system from unwanted export. You may set maximum export value or you can set it negative to keep
some import even in cases that there are abrupt load changes.
Import
NT
100
Export
0
Power exported to Mains
Negative value of
Import is Export
NT
101
6.8
If the MCB is closed (MCB feedback is present) and the gen-set has been synchronized to the bus
bar, the parallel to mains operation will follow. It consists of the following phases:
6.8.1
The first phase of the PTM operation is the ramping of the gen-set up to the desired power level
derived from the system baseload or up to the load given by load sharing with other gen-sets
connected to the bus bar. The speed of the ramp is given by the setpoint Load Ramp. The setpoint
adjusts the ramp time for a change from 0% to 100% of nominal power.
6.8.2
There are two load control modes system baseload and load sharing which are selected by the
setpoint #SysLdCtrl PtM. See the setpoint description for more information. If system baseload mode
is selected, the Load regulation loop is active to maintain the load at the requested level which is
derived from the system baseload. Each running gen-set takes a relatively equal part of the system
baseload.
In load sharing mode, the loop LS (load sharing) is active to maintain the load at the same relative
level as the other loaded gen-sets in the group. The behaviour in this case is identical to multiple
island mode.
NOTE:
The process of determining which gen-sets shall run is described in the power management chapter.
6.8.3
In system baseload mode the power factor is regulated to a constant value given by the setpoint
#SysPwrFactor. The PF regulation loop is active. In load sharing mode, also power factor sharing is
active to keep the power factor of all loaded gen-sets at an equal level. Regulation adjustment
setpoints are available in the Volt/PF control group.
6.8.4
When a stop command is received e.g. power management or binary input Sys Start/Stop is
deactivated or the STOP button is pressed the gen-set load is ramped down before opening the
GCB. The ramp speed is given by the setpoint Load Ramp, the end level is given by GCB Open Level
and the timeout for finishing the ramping without reaching the open level is given by GCB Open Del.
When the GCB button is pressed, the gen-set load is ramped down before opening the GCB as well.
But after the GCB has been opened, the gen-set remains running until a stop command comes or the
GCB is pressed again to reclose the GCB.
Continue to the cool down and stop phase.
6.9
A situation where the MCB is open and the load is supplied from the gen-set is called Island operation.
This situation will occur in the following cases:
1. The GCB has been closed to a dead bus bar, or
2. The gen-set was running parallel to the mains and the MCB has been opened.
NT
102
Neither voltage nor a frequency regulation loop is active. Keeping voltage and frequency at rated
values is the task of AVR and the governor.
When a stop command is received e.g. the binary input Sys Start/Stop is deactivated or the STOP
button is pressed the GCB will be opened and the gen-set will go to cool down phase.
NOTE:
When using the GCB button in MAN mode, the gen-set will not go to cool down and stop.
6.9.1
If the mains are OK, the gen-set can be transferred back to the parallel to mains operation. The
transfer can be done as no-break transfer (Reverse synchronizing) or break transfer (Changeover).
Which of these kinds will be performed depends on the binary input RevSyncDisable.
In AUT mode or TEST mode with automatic return, the reverse synchronizing or changeover is started
automatically after the mains have been restored and remain healthy for a period given by the setpoint
MainsReturnDel. Reverse synchronizing can be started manually by pressing MCB button in MAN
mode.
6.9.1.2 Changeover
The changeover is performed if the reverse synchronizing is disabled with the RevSyncDisable binary
input.
The GCB is opened first and after a time period of Transfer Del the MCB is closed.
103
NOTE:
Using the GCB button in MAN mode the gen-set will not go to cool down and stop.
Continue to the cool down and stop phase.
6.11.1
The concept
The power management is based on the load of the gen-sets, i.e. next gen-set will start when the load
of the group raises above certain level. A next gen-set will stop, when the load drops down below a
certain level. The process of determining of starts and stops is done in each controller; there is no
"master" in the system. Each of the controllers can be switched off without influencing the complete
system (except the situation when the respective gen-set will be not available...)
The load of the group is evaluated as so called reserve. The reserve is calculated as difference
between actual and nominal load of running gen-sets. The reserve can be calculated as absolute (in
kW) or relative (in %). Use the setpoint #PowerMgmt Mode to set the calculation method.
NOTE:
Power management based on relative reserves perfectly fits for applications, where the load portions
connected to the group at once are much lower than the gen-set capacity. This mode helps to achieve
maximal lifetime of the gen-sets, as they can be operated within optimal load range. The maximal
size of the load connected at once depends on number of actually working gen-sets. The more
gen-sets are connected to the busbar, the bigger a load portion can be connected at once.
Power management based on absolute reserves can be successfully used also for cases where the
load portions are similar to the gen-set capacity or even bigger. The goal of the absolute reserve mode
is that the system provides always the same reserve power capacity independent of how many
gen-sets are currently running and this why this mode perfectly fits for industrial plants with large
loads.
There is a new way of power management implemented (Efficient mode; LDS) since version IC-NT
2.0. Basic principles and functions are explained in the chapter below.
6.11.2
Basics
The setpoint Pwr Management enables and disables the gen-set to be active within the power
management of the group and make automatic load demand start/stop or swap. If the power
management is disabled, the gen-set will run or not depending only on the binary input Sys
Start/Stop and the start and stop will not depend on the load of the group.
The binary input Sys Start/Stop activates and deactivates the gen-set. If the input is not active,
the gen-set will stop with delay #SysAMFstopDel after the input has been deactivated and will
not start again. It can be started in MAN mode only. When the input is activated again, the
delay #SysAMFstrtDel will start to count down and after that the gen-set is activated and can
start due to power management.
NOTE:
The gen-set will take part of the power management (= will be active) only if the controller is in AUT
mode!
NT
104
NOTE:
The gen-set performs load and VAR sharing whenever it is connected to the busbar i.e. it is
independent on whether the controller is in AUT or MAN mode or whether the power management is
active or not.
6.11.3
The value
The value
[kW] is called absolute reserve. It is the difference between the
actual load of the group and the nominal capacity of currently loaded gen-sets.
Running ActPwr = the sum of the actual load of all active gen-sets within the group, that
are connected to the bus. In parallel to mains operation and baseload mode the
baseload level is used in the equation instead of the actual gen-sets load.
Running NomPwr = the sum of the nominal power of all active gen-sets within the
group, that are connected to the bus.
If the current system reserve drops below the adjusted reserve for start, the delay
#NextStrt Del will start to count down on the gen-sets, which have decided to start. If the
reserve remains under the limit for the entire countdown period, the gen-set(s) will start.
If the system reserve drops below zero (i.e. the system is overloaded), the delay
#OverldNext Del will start to count down on the gen-sets, which have decided to start. If the
reserve remains under the limit for the whole countdown period, the gen-set(s) will start.
If the system reserve goes above over the adjusted reserve for stop, the delay
#NextStopDel will start to count down on the gen-sets, which have decided to stop. If the
reserve still remains over the limit, the gen-sets will stop.
There are two pairs of setpoints for adjusting reserves for start and stop. Normally the pair
#LoadResStrt 1 and #LoadResStop 1 is active. By the binary input Load Reserve 2 the
second pair #LoadResStrt 2 and #LoadResStop 2 is activated.
With adjusting nonzero value to the setpoint #Min Run Power and activating the function by
binary input Min Run Power => based on the nominal power, the gen-sets needed for
equalizing the actual MinRunPower requirement are started (or kept running even if stop
reserve is fulfilled). Note, that LBIs Min Run Power needs to be activated on all gen-sets in
the same time.
6.11.4
Priorities
The priority of the gen-set within the group is determined by the setpoint Priority. A lower
number represents higher priority, i.e. a gen-set with a lower number will start before another
one with higher number.
For Load Demand Star/Stop regime:
- If the binary input Top Priority is active, the gen-set gets highest priority (0)
independent of the setpoint setting.
- If more than one gen-set have the same priority, they will act as one big gen-set.
For Load Demand Swap regime and Run Hour Equalisation:
- Priorities are managen automatically by the controller and value written in the setpoint
is ignored
- Binary input Top Priority has no function
NT
105
6.11.5
The controller will decide to start the gen-set at the moment when the reserve has dropped
below the reserve for start and the gen-sets with higher priorities (lower priority numbers), that
are available for power management, do not have enough capacity to get the reserve back
over the start level or cannot fulfil the adjusted minimal running power
The controller will decide to stop the gen-set at the moment when the reserve has increased
over the reserve for stop and the gen-sets with higher priorities (lower priority numbers), that
are available for power management, have enough capacity to keep the reserve over the start
level and also can fulfil the adjusted minimal running power
NOTE:
When evaluating the stop condition, the controller computes actual reserve without taking in account
its own nominal power, i.e. it evaluates how the reserve will be if the respective gen-set stops.
Load
[kW]
Pnom Gen-set 3
Priority 3
Pg_nom_1+Pg_nom_2+Pg_nom_3 [kW]
Pnom Gen-set 2
Priority 2
Pg_nom_1+Pg_nom_2 [kW]
Pnom Gen-set 1
Priority 1
Pg_nom_1 [kW]
#SysAMFstopDel
Gen-set 1
running
Gen-set 2
running
#SysAMFstrtDel
#NextStrt Del
Gen-set 3
running
#NextStop Del
#NextStrt Del
#NextStop Del
NT
106
Load
[kW]
Pnom Gen-set 3
Priority 3
100% Pg_nom_1+Pg_nom_2+Pg_nom_3
Pnom Gen-set 2
Priority 2
100% Pg_nom_1+Pg_nom_2
Pnom Gen-set 1
Priority 1
100% Pg_nom_1
#SysAMFstopDel
Gen-set 1
running
Gen-set 2
running
#SysAMFstrtDel
#NextStrt Del
Gen-set 3
running
#NextStop Del
#NextStrt Del
#NextStop Del
6.11.6
If a Shutdown or BOC alarm occurs, the gen-set will be taken out from the power
management and the next gen-set will start if necessary.
If a Slow stop alarm occurs, the gen-set will be taken out from the power management, but the
alarm will be suppressed for a definite period of time to give the next gen-set chance to start
and connect to the bus to get the reserve back over the start level. The alarm is suppressed
until the reserve gets back over the start level (this can occur either because the next gen-set
has connected to the bus or the load has decreased) or the timeout given by the setpoint
#SlowStopDel has elapsed. The alarm will not be suppressed if there is no other available
gen-set that can start.
6.11.7
1.
2.
3.
4.
Reaction to alarms
Sys Start/Stop
Load Reserve 2
Top Priority
Min Run Power
NT
107
6.11.8
1. System Ready
2. SystReserve OK
3. EnginesSwapped
6.11.9
There is a new way of power management implemented (Efficient mode; LDS) since version IC-NT
2.0. Basic principles and functions are explained in the chapter below.
CAUTION!
NT
MainsCompact is not supported for use with IC-NT 2.0+ firmware. Please use IC-NT 1.4.5 instead.
Principles of the Load Demand Swap (#PriorAutoSwap = EFFICENT)
To evaluate, which gen-set will start as next, two situations need to be distinguished:
1) First start (activation of Sys Start/Stop binary input)
2) Already running group of gen-sets
Add1) master controller (the one with the lowest CAN address) makes the calculation and sorts all
the gen-sets in the group based on their nominal power and running hours from the biggest to
smallest. Gen-set which fulfils following formula will be selected:
Pnom < #LoadResStrt 1
Where Pnom is the nominal power of the selected gen-set
If two gen-sets with the same nominal power are available, the one with least amount of run hours is
started.
Add2)
a) Master controller on the fly sorts available gen-sets based on their nominal power from the
biggest to smallest
b) If two or more gen-sets with the same nominal power are available, least amount of run hours is
preferred (lower run hours = higher priority)
c) Selection of which gen-set has to start next is from the bottom of the list to the top (small genset starts first) following formula:
Pnom > Load demand + #LoadResStrt 1
Where Pnom is the nominal power of selected gen-set
d) If load demand is higher than nominal power of the biggest gen-set, this one is fixed and the
whole process repeats from c).
e) For gen-sets with the same nominal power also run hour equalization will be performed.
NT
108
Example:
#PowerMgmtMode = ABS
#LoadResStrt 1 = 20kW
#LoadResStop 1 = 30kW
G1
G3
G2
G4
CAN 2
50kW
100h
100kW
100h
300kW
100h
50kW
0h
How to set EFFICENT mode (Load demand swap function); available since IC-NT 2.0
In Pwr management setpoint group:
make sure Power Management is enabled (Pwr Management = ENABLED)
set #PowerMgmtMode = ABS (kW)
set #PriorAutoSwap = EFFICIENT
select appropriate load reserve for start (#LoadResStrt 1)
select appropriate reserve for stop (#LoadResStop 1)
set suitable delay for power band change (PwrBnChngDlUp / PwrBnChngDlDn)
NT
109
How to set Load demand start/stop power management (Load Demand Start/Stop)
In Pwr management setpoint group:
make sure Power Management is enabled (Pwr Management = ENABLED)
set #PowerMgmtMode = ABS (kW) or REL (%)
set the priority of the gen-set (Priorty)
set #PriorAutoSwap = DISABLED (controller will not change priorities in the
background and will respect the value set in Priority setpoint)
select appropriate load reserve for start (#LoadResStrt 1)
select appropriate reserve for stop (#LoadResStop 1)
6.12.1
The mains are considered as faulty when one or more of the following conditions are valid:
The mains voltage is out of the limits given by the setpoints Mains >V and Mains <V for a time
period longer than Mains V Del.
The mains frequency is out of the limits given by the setpoints Mains >Freq and Mains <Freq
for a time period longer than Mains Freq Del.
The Vector shift protection occurs.
The MCB close command was not successful and the alarm MCB fail still was not reset.
The binary input Ext MF Relay is active.
6.12.1.1
Vector shift
If a mains failure occurs during parallel to mains operation, in most cases it causes a fast change of
the generator load. This change can be measured as a jump of the vector of the generator voltage and
evaluated as a symptom of mains failure. The vector shift limit for evaluation of a mains failure is
adjustable by the setpoint VectorShiftLim.
NT
110
NOTE:
Vector shift is evaluated only while the gen-set is working parallel to the mains.
6.12.2
The mains are considered to be healthy when all of following conditions are valid:
The mains voltage is within the limits given by the setpoints Mains >V and Mains <V.
The mains frequency is within the limits given by the setpoints Mains >Freq and Mains <Freq.
The alarm MCB fail is not active.
The binary input Ext MF Relay is not active.
NOTE:
There is a hysteresis for Mains under and over voltage added in the same way as in the InteliLiteNT
family.
6.12.3
When the mains failure is detected, the following steps are performed:
1. If the setpoint MCB Opens On is set to MAINSFAIL, the MCB is opened
2. The timer for automatic start of the gen-set EmergStart Del begins to count down.
3. After the timer has elapsed, the gen-set is started.
NOTE:
The automatic start of the gen-set due to AMF function can be disabled by the input
MainsFailBlock. If the gen-set is already running and the input is activated, the gen-set will
cool down and stop. The control of breakers is not affected by this input.
4. If the setpoint MCB Opens On is set to GENRUN, the MCB is opened once the generator
voltage is within limits.
5. If the mains are restored to health and the gen-set is still not connected to the load, the
controller interrupts the startup process and closes back the MCB.
6. The GCB is closed and the gen-set begins to supply the load.
7. After the mains are restored to normal, the timer MainsReturnDel begins to count down and
when finished, either reverse synchronizing or switchover is performed. This depends on the
binary input RevSyncDisable. If active, switchover is performed instead of reverse
synchronizing.
8. Maximum time between closing of GCB and opening MCB is given by the setpoint
BreakerOverlap.
9. If no demand for parallel operation is active (binary input Rem Start/Stop), the GCB is opened
and the gen-set cools down and a stop follows.
NOTE:
For a description of how to make a test of AMF function, see the chapter operating modes, TEST
mode paragraph.
Duration of the cool down phase is determined by the setpoint Cooling Time.
Cooling is performed either at nominal speed (generator voltage and frequency protections
are evaluated) or at idle speed (generator voltage and frequency protections are not
evaluated). Selection of the speed is done by the setpoint Cooling Speed.
NT
111
The cool down can be finished manually in MAN mode by pressing the STOP button.
If a new start request comes, the cool down will be interrupted and the gen-set will go back to
the stabilization phase. If the cooling was at nominal speed, the stabilization timers will not
count down again so the GCB is immediately ready to be closed.
When the cool down is finished, the output Fuel Solenoid is de-energized and Stop Solenoid is
energized. The engine will stop within the time period determined by the setpoint Stop Time. If the
engine does not stop within this time, the alarm Stop fail will be issued.
The output Stop Solenoid is energized until the engine is stopped, but at least for the duration of Stop
Time. If the Stop time has elapsed and the engine has still not stopped, the stop solenoid is deenergized for 5 s and then energized again for max. Stop time and this repeats until the engine is
stopped.
The output Ignition is continuously energized until the engine is stopped.
6.13.1
The gen-set is considered as stopped when all of following conditions are valid:
NT
112
Analog
value
No alarm
issued
Red alarm
issued
Yellow alarm
issued
Red alarm
level
Yellow alarm
level
alarm
delay
alarm
delay
Time [s]
t < alarm delay
6.14.1
Alarm handling
There are two different alarm categories regarding the period when the alarms are evaluated.
The category is selectable for alarms assigned to binary/analog inputs and fixed for built-in
alarms. The categories are the following:
1) The alarm is evaluated all the time when the controller is switched on.
2) The alarm is evaluated only when the engine is running. This type should be used
for e.g. oil pressure. These alarms begin to be evaluated after the engine has been
started with the delay given by the setpoint ProtectHoldOff.
3) The alarm is evaluated only when the generator is excited. These alarms begin to be
evaluated after the engine has been started and Max Stab Time has elapsed or the
GCB has been closed. They remain evaluated until cooling has finished. Only
Generator under/overvoltage, Generator voltage unbalance and Generator
under/overfrequency belong to this category. This category is not configurable to
binary and analog input alarms.
If an alarm is being evaluated and the appropriate alarm condition is fulfilled, the delay of
evaluation will start to run. The delay is adjustable by a setpoint (in the case of built-in alarms,
analog input alarms) or is fixed to 500ms (in the case of binary input alarms). If the conditions
persist, the alarm will activate. The alarm will not activate if the condition is dismissed while
the delay is still running.
After pressing the Fault reset button or activating the binary input FaultResButton, all active
alarms change to confirmed state. Confirmed alarms will disappear from the Alarmlist as soon
as the respective condition dismisses. If the condition is dismissed before acknowledging the
alarm, the alarm will remain in the Alarmlist as Inactive. See also the Browsing alarms
chapter.
NOTE:
The input Sd Override can be used for temporary disabling of red alarms to shutdown the engine. This
input may be used in situations where providing the power is extremely important e.g. if the gen-set
drives pumps for fire extinguishers (sprinklers).
6.14.2
Alarm states
NT
113
Active alarm: the alarm condition persists, alarm delay has elapsed.
Inactive alarm: the alarm condition has disappeared, but the alarm has not been confirmed.
Confirmed alarm: the alarm condition persists, but the alarm has already been confirmed.
6.14.3
The yellow alarm indicates that a value or parameter is out of normal limits, but has still not reached
critical level. Obviously it is indicated by a yellow colour. This alarm does not cause any actions
regarding the gen-set control.
6.14.3.1
Warning (WRN)
The Warning alarm does not perform any actions regarding gen-set control.
6.14.4
The red level alarm indicates that a critical level of the respective value or parameter has been
reached. Obviously it is indicated by red colour. The controller will take one of the following actions:
6.14.4.1
The BOC (electric trip) alarm category is used above all for built-in alarms assigned to the generator
electric values (voltage, current, power, etc.). The GCB is opened immediately, but after that the
engine will perform the standard stop procedure including cooling.
6.14.4.2
The Slow stop alarm differs from the BOC in that the gen-set will perform a soft unload before opening
the GCB (if possible). After that the standard stop procedure including cooling follows.
NOTE:
In the MINT application if the power management is active and a slow stop alarm occurs, the controller
will wait until another gen-set is started (if there is at least one available) before unloading and
stopping the gen-set. The maximum time the controller will wait is given by the setpoint #SlowStopDel.
6.14.4.3
Shutdown (SD)
The Shutdown alarm opens the GCB immediately and stops the engine immediately without cooling.
NOTE:
It is not possible to start the engine if any red level protection is active or not confirmed.
CAUTION!
The gen-set can start by itself after acknowledging the alarms if there is no longer an active red alarm
and the controller is in AUT or TEST mode!
6.14.5
If the measured resistance (or voltage or current in case of IGS-PTM module) on an analog input
exceeds the valid range, a sensor fail will be detected and a sensor fail message will appear in the
Alarmlist. The valid range is defined by the most-left (RL) and most-right (RH) points of the sensor
characteristic 12.5% from RH-RL.
NT
114
Bar
10.6
10
Sen
rea
il a
12.5% of the
sensor range
0
10
Sensor fail limit would be -1
Ohm what is physically
imposible so sensor fail is not
detected even for 0 ohm
fa
so r
180 191
First point of
the curve
6.14.6
If a GSM modem and/or Internet Bridge are connected to the controller, the controller can send SMS
messages and/or emails at the moment when a new alarm appears in the Alarmlist. The message will
contain a copy of the Alarmlist.
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm Msg the levels
of alarms to be announced (red/yellow/both) and also enter a valid GSM phone number and/or e-mail
address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to set either a GSM
number or e-mail at both setpoints.
The list of all supported terminals shows the table below:
Terminal
Active alarm
sms
Active event
sms
Active alarm
email
Active event
email
IB-Lite
NA
NA
yes
yes
IB-NT
yes
yes
yes
yes*
IL-NT-GPRS
yes
yes
Not
supported
Not
supported
Controller is capable to detect which communication terminal is connected to the network and send
the email/SMS via the active one. InternetBridge-NT is preferred terminal if more possibilities are
detected.
NT
115
NOTE:
An internet module must be available for sending e-mails and a GSM modem is necessary for sending
SMS. See the Communications chapter for more information.
6.14.7
Alarmlist
Alarmlist is a container of active and inactive alarms. It will appear automatically on the controller
display, if a new alarm occurs, or can be displayed manually from the display menu
It can contain up to 16 alarms, but the first 7 are visible on the screen. If it is full, recently
coming alarms are not displayed.
Active alarms are shown as inverted, not yet confirmed alarms are marked with asterisk
before them.
An alarm message in the alarmlist begins with a prefix, which represents the alarm type
(e.g. WRN). Then the alarm name follows. In some cases the prefix can be omitted.
NOTE:
The Alarmlist can be read out from the controller via Modbus. See the Modbus description chapter.
6.14.8
ECU Alarmlist
The ECU Alarmlist contains alarms that are received from the ECU. The alarms are represented by
the Diagnostic Trouble Code, which contains information about the subsystem where the alarm
occurred, the alarm type and the alarm occurrence counter.
The most common fault codes are translated into text form. Other fault codes are displayed as a
numeric code and the engine fault codes list must be used to determine the reason.
NOTE:
The ECU AlarmList is visible only if an ECU is configured.
NT
116
6.14.9
Built-in alarms
ANSI CODE
PROTECTION (ALARM)
Emergency stop
12
Engine overspeed
14
Engine underspeed
Start Fail
RPM measurement failure
Stop Fail
GCB Fail
MCB Fail
Forward synchronization timeout
Reverse synchronization timeout
32
Generator overload
32R
59, 27
Generator under/overvoltage
47
81H, 81L
Generator under/overfrequency
51
Generator overcurrent
50
46
47
Phase sequence
Maintenance timer
Charging alternator fail
Battery voltage
Governor output at limit
AVR output at limit
Battery flat
Low backup battery
The event which caused the record (e.g. Overspeed alarm or GCB closed)
The date and time when it was recorded
All important data values like RPM, kW, voltages, etc. from the moment that the event
occurred.
BASIC VALUES
NT
117
NAME
ABBREVIATION DESCRIPTION
Number
Num
Reason
Reason
Date
Date
Date
Time
Time
Time
RPM
RPM
Power
Pwr
Power Factor
PF
Load Character
LChr
Generator Voltage
Vg1
Generator Voltage
Vg2
Generator Voltage
Vg3
Generator Current
Ig1
Generator Current
Ig2
Generator Current
Ig3
Oil Pressure
OilP
Engine Temperature
EngT
Fuel Level
FLvl
AIM1
AIM2
AIM3
AIM4
Binary Inputs
BIN
BIM
Binary Inputs/Outputs
Extension
BIOE
Binary Outputs
BOUT
BOM
SRO
6.15.1.1
ECU values
ECU VALUES
NAME
ABBREVIATION
EFR
ECT
EIT
EOP
EOT
NT
118
EBP
EPL
EFL
FC
FMI
6.15.1.2
SPTM VALUES
NAME
ABBREVIATION
DESCRIPTION
Mains Frequency
Mfrq
Mains frequency
Mains Voltage
Vm1
Mains Voltage
Vm2
Mains Voltage
Vm3
Pmns
Qmns
MPF
MLCh
MVS
6.15.1.3
Information about gen-sets with GCB closed and their overall P and Q. Values can be also found in
LiteEdit Values / Pwr Management and Info (LE ver. 4.4 and higher).
MINT VALUES
NAME
ABBREVIATION DESCRIPTION
Bus Frequency
Bfrq
Bus frequency
Bus Voltage
Vb1
Bus Voltage
Vb2
Bus Voltage
Vb3
ActualReserve
Ares
Actual reserve
GensLoaded16
GL16
GensLoaded32
GL32
Running ActPwr
TRPA
Running Q-Pwr
TRQA
TRPN
APN
NT
119
NOTE:
The contents of the history log will be deleted after programming firmware or configuration into the
controller.
The history log can be displayed on the controller screen or in LiteEdit. If an archive (*.ail file) is saved
in LiteEdit, it will also contain the history log. The archive can be later opened in offline mode to view
the history log offline.
NOTE:
The first history record after the controller is switched on, programmed or a watchdog reset occurs
contains diagnostic values instead of operational values. Some fields in these records may seem to
have nonsense values. Do not take these values into account.
NT
120
6.16.1
MINT
No Func
There is no function other than activation of the binary outputs Exerc Timer 1 or Exerc
Timer 2.
Mode
OFF
When this option is chosen, the Timer output is also internally connected to the
Remote OFF binary input.
AutoRun
When this option is chosen, the Timer directly starts gen-set (in AUT mode).
6.16.2
SPtM
No Func
There is no other function besides binary output Exerc Timer 1 or Exerc Timer 2
activation.
Mode
OFF
When this option is chosen, the Timer output is also internally connected to the
Remote OFF binary input.
MFail Blk
When this option is chosen, the Timer output is also internally connected to the
MainsFailBlock binary input.
TEST
When this option is chosen, the Timer output is also internally connected to the
Remote TEST binary input.
TEST
OnLd
When this option is chosen, the Timer output is also internally connected to the Rem
TEST OnLd binary input.
The timer outputs are available as binary outputs Exerc Timer 1 and Exerc Timer 2.
NOTE:
Timers are activated even in the middle of the cycle. This means that even when the controller is
switched on after the moment when the timer should have been started and before it should have
finished, the timer is activated for the remainder of the duration period.
Timer functions can be activated only in AUT mode (not in OFF, MAN or TEST). There are 2 timers.
In the event that both Timers are active at the same time, Timer 1 has a higher priority than Timer 2.
NT
121
SWITCH
OUTPUT
OFF
LEVEL OFF
LEVEL ON
ANALOG VALUE
SWITCH
OUTPUT
OFF
LEVEL ON
LEVEL OFF
ANALOG VALUE
OFF
LEVEL OFF
LEVEL ON
ANALOG VALUE
SWITCH
OUTPUT
OFF
LEVEL ON
LEVEL OFF
ANALOG VALUE
6.19.1
SPtM
LOADED ISLAND
PARALLEL TO M AINS
LOADED IN PARALLEL
TO M AINS
Running
GCB opened
GCB closed
MCB opened
Synchronizing
GCB closed
MCB closed
NT
122
Speed/frequency
control loop:
Freq Gain
Freq Int
Angle control loop:
Angle Gain
LOADED ISLAND
PARALLEL TO M AINS
Running
GCB opened
GCB closed
MCB opened
Synchronizing
GCB closed
MCB closed
Voltage control loop: Voltage control loop: Voltage control loop: Power factor control loop:
Voltage Gain
Voltage Gain
Voltage Gain
PF Gain
Voltage Int
Voltage Int
Voltage Int
PF Int
6.19.2
MINT
LOADED ISLAND
PARALLEL TO M AINS
LOADED IN
PARALLEL TO M AINS
Running
GCB opened
GCB closed
MCB opened
Synchronizing
GCB closed
MCB closed
Speed/frequency control
loop:
LoadShare Gain
LoadShare Int
background nominal
frequency matching
Speed/frequency
control loop:
Freq Gain
Freq Int
Angle control loop:
Angle Gain
MULTIPLE LOADED
ISLAND
MULTIPLE PARALLEL TO
M AINS
Running
GCB opened
GCB closed
MCB opened
Synchronizing
GCB closed
MCB closed
Voltage control
loop:
Voltage Gain
Voltage Int
Voltage control
loop:
VAr Share Gain
VAr Share Int
The following regulation loops are built into the controller. All of them are PI type except angle loop,
which is P type.
NOTE:
Since IC-NT SW v. 1.4.1 only the first controller (with the lowest address at the CAN has) active
voltage control loop. Other controllers are adapting voltage according to bus to the first one. All
controllers have active VAr Share regulation loop.
NT
123
6.19.3
6.19.3.1
The speed/frequency control loop is active during the synchronization, when the gen-set frequency is
controlled to the same value as the mains or bus have, i.e. to achieve zero slip frequency.
6.19.3.2
The differential angle control loop is active during the synchronization, when the near to zero slip
frequency has been successfully achieved and then the differential angle between generator and
mains/bus voltage shall be reduced to zero.
6.19.3.3
The power control loop is active during the parallel to mains operation. The recognition of parallel to
mains operation is done on the basis of the binary input MCB feedback. In MINT the setpoint
#SysLdCtrl PtM must be also set to BASELOAD.
6.19.3.4
The load sharing control loop is active in MINT, whenever the GCB is closed and the binary input MCB
feedback is not active or the setpoint #SysLdCtrl PtM is in LDSHARING position.
6.19.3.5
The voltage control loop is active during synchronization (the generator voltage is controlled to the
same value as the mains or bus have) and during island operation in SPtM (the gen-set voltage is
controlled to the nominal voltage). During multiple island operation in MINT, the voltage control loop is
also running in the background of the VAr sharing loop (using P, I parameters multiplied by 0.1) to
maintain the voltage at the nominal level.
NOTE:
Since IC-NT SW v. 1.4.1 only the first controller (with the lowest address at the CAN has) active
voltage control loop. Other controllers are adapting voltage according to bus to the first one. All
controllers have active VAr Share regulation loop.
6.19.3.6
The power factor control loop is active during the parallel to mains operation. The recognition of
parallel to mains operation is done on the basis of the binary input MCB feedback.
6.19.3.7
The VAr sharing control loop is active during multiple island operation in MINT application.
6.19.4
PI regulation adjustment
The exact adjustment of a PI loop always depends on the engine and generator characteristics.
However, a general rule can be followed in the beginning of the adjustment process:
Prepare the system for adjustment, i.e. set the limits for related alarms temporarily to values
which will disable the alarms, set the synchro timeout to the maximum value, etc.
Adjust the gain to 5% and integration to 0%.
Switch the gen-set to MAN mode, start it and put it into the operation phase, where the
appropriate regulation loop is active.
Increase the gain slightly until the controlled quantity starts to oscillate. Then put it back to
approx. one half of the value where the oscillations started.
NT
124
Increase the integrative factor slightly to achieve acceptable response to changes. Too small
an I-factor will cause an excessively slow response, while too high an I-factor will cause
overshooting or even oscillations.
NOTE:
It may be helpful to disable issuing the GCB close command when adjusting synchronization loops.
Adjust the setpoint Phase Window to 0 to disable it. Adjust the setpoint back to its original value after
the adjustment is finished.
CAUTION!
Be ready to press the emergency stop button in the event that the regulation loop starts to behave
unacceptably.
NT
125
7 Setpoints
Setpoints are analog, binary or special data objects which are used for adjusting the controller to the
specific environment. Setpoints are organized into groups according to their meaning. Setpoints can
be adjusted from the controller front panel, PC, MODBUS, etc.
7.1
Password protection
Each setpoint can be protected by a password against unauthorized changes. Password protection
can be assigned to the setpoints during the configuration procedure. See the chapter Operator guide
for instructions on how to enter and modify a password. See also the LiteEdit help to learn about
working with a password in LiteEdit.
7.2
Setpoint synchronization
Setpoints marked with a # sign at the beginning of their names are synchronized with other
controllers present on the CAN bus line, i.e. the system will ensure that the respective setpoint will
have an identical value in each connected controller. If the setpoint is changed in one controller, the
same change will occur in all other controllers. This function is necessary especially for MINT
application, where the system of Power management is based on fact that the respective setpoints are
identical in all controllers.
All parameters marked as shared (#) are overwritten during archive download in case there is no
another single controller visible on the CAN bus. In case there is another controller on the CAN bus,
the shared parameters are not overwritten.
7.3
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
Setpoint groups
Process Control
Basic Settings
Comms Settings
Engine Params
Engine Protect
Gener Protect
Pwr Management
AMF Settings
Sync/Load Ctrl
Volt/PF Control
ExtI/O Protect
SMS/E-Mail
AnalogSwitches
Date/Time
Sensors Spec
CAUTION!
Do not write setpoints repeatedly (e.g. power control from a PLC by repeated writing of baseload
setpoint via Modbus) The setpoints are stored in EEPROM memory, which can be overwritten up to
5
10 times without risk of damage or data loss, but it may become damaged, when the allowed number
of writing cycles is exceeded!
NT
126
7.3.1
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
7.3.2
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
7.3.3
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
127
7.3.4
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
7.3.5
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
7.3.6
1.
2.
3.
4.
5.
6.
7.
8.
128
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
7.3.7
EarthFault Del
Gen >V Sd
Gen <V BOC
Gen V Del
Volt Unbal BOC
Volt Unbal Del
Gen >Freq BOC
Gen <Freq BOC
Gen Freq Del
BusMeasError
Reverse Pwr BOC
Reverse Pwr Del
ExcitationLoss
ExctLoss Del
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
7.3.8
Pwr Management
Pwr Manag Del
#PowerMgmtMode
Priority
#PriorAutoSwap
#SysAMFstrtDel
#SysAMFstopDel
#LoadResStrt 1
#LoadResStop 1
#LoadResStrt 2
#LoadResStop 2
#Min Run Power
#NextStrt Del
#OverldNextDel
#NextStopDel
#SlowStopDel
RunHoursBase
#RunHrsMaxDiff
#PwrBnChngDlUp
#PwrBnChngDlDn
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
EmergStart Del
MainsReturnDel
Mains >V
Mains <V
Mains V Del
Mains >Freq
Mains <Freq
Mains Freq Del
VectorShiftLim
Transfer Del
MCB Close Del
MCB Opens On
RetFromIsland
BreakerOverlap
ReturnFromTEST
NT
129
7.3.9
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
7.3.10
1.
2.
3.
4.
5.
6.
7.
AVRi Bias
Voltage Gain
Voltage Int
PF Gain
PF Int
VAr Share Gain
VAr Share Int
7.3.11
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
7.3.12
Setpoints SMS/E-Mail
130
4. TelNo/Addr Ch1
5. TelNo/Addr Ch2
7.3.13
1.
2.
3.
4.
5.
6.
7.
8.
AnaSwitch1 ON
AnaSwitch1 OFF
AnaSwitch2 ON
AnaSwitch2 OFF
AnaSwitch3 ON
AnaSwitch3 OFF
PowerSwitch ON
PowerSwitch OFF
7.3.14
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Setpoints Date/Time
7.3.15
1.
2.
3.
4.
5.
6.
7.
Setpoints AnalogSwitches
AI1Calibration
AI2Calibration
AI3Calibration
IOM AI1 Calibr
IOM AI2 Calibr
IOM AI3 Calibr
IOM AI4 Calibr
NT
131
8 Values
Values (or quantities) are analog or binary data objects, measured or computed by the controller, that
are intended for reading from the controller screen, PC, MODBUS, etc. Values are organized into
groups according to their meaning.
NOTE:
A complete overview of all data objects available in the controller can be exported by LiteEdit into a
text file. Open any connection (also offline with a previously saved archive) and go to the menu
Controller -> Generate CFG image.
8.1
Invalid flag
If valid data is available for a particular value, the invalid flag is set to it. This situation may be due to
the following:
The value is not being evaluated in the scope of the current application and configuration.
Sensor fail has been detected on an analog input.
The configured ECU or extension module does not provide the particular value.
The communication with the ECU or extension module is interrupted.
A value containing the invalid flag is displayed as #### in LiteEdit and on the controller screen. If
such a value is read out via Modbus, it will contain the data 32768 in the case of signed values and
65535 in the case of unsigned values.
8.2
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
8.2.1
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Value groups
Engine
Generator
Mains
Bus
Pwr Management
Controller I/O
Extension I/O
Statistics
Date/Time
Info
Values Engine
RPM
W-TerminalFreq
ECU State
Fuel Rate ECU
Cool Temp ECU
IntakeTemp ECU
Oil Press ECU
Oil Temp ECU
BoostPress ECU
Perc Load ECU
FuelLevel ECU
NT
132
12.
13.
14.
15.
16.
8.2.2
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
8.2.3
ECU FreqSelect
Speed Request
SpeedReq RPM
DPF1 Soot Load
DPF1 Ash Load
Values Generator
Gen kW
Gen kW L1
Gen kW L2
Gen kW L3
Gen kVAr
Gen kVAr L1
Gen kVAr L2
Gen kVAr L3
Gen kVA
Gen kVA L1
Gen kVA L2
Gen kVA L3
Gen PF
Gen Load char
Gen PF L1
Gen Lchr L1
Gen PF L2
Gen Lchr L2
Gen PF L3
Gen Lchr L3
Gen Freq
Gen V L1-N
Gen V L2-N
Gen V L3-N
Gen V L1-L2
Gen V L2-L3
Gen V L3-L1
Gen A L1
Gen A L2
Gen A L3
EarthFaultCurr
Values Mains
SPtM only
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
Mains Freq
Mains V L1-N
Mains V L2-N
Mains V L3-N
Mains V L1-L2
Mains V L2-L3
Mains V L3-L1
Mains A L3/EF
Mains kW I
Mains kVAr I
Mains PF
Mains LChr
Load kW
Load kVAr
NT
133
15.
16.
17.
18.
19.
8.2.4
Load PF
Load LChr
Slip
Angle
MaxVectorShift
Values Bus
MINT only
1.
2.
3.
4.
5.
6.
7.
8.
9.
8.2.5
Bus Freq
Bus V L1-N
Bus V L2-N
Bus V L3-N
Bus V L1-L2
Bus V L2-L3
Bus V L3-L1
Slip
Angle
1.
2.
3.
4.
5.
6.
7.
8.
8.2.6
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
8.2.7
Actual Reserve
Running ActPwr
Running Q-Pwr
Running NomPwr
Avail Nom Pwr
Priority
Act Pwr Band
Next Pwr Band
1. IOM AI1
2. IOM AI2
3. IOM AI3
NT
134
4.
5.
6.
7.
8.
IOM AI4
IOM Bin Inp
ExtM Bin Inp
RA Bin Out
IOM Bin Out
Values Statistics
8.2.8
1.
2.
3.
4.
5.
6.
7.
8.
9.
Energy kWh
Energy kVAhr
Run Hours
Num Starts
Maintenance
Num E-Stops
Shutdowns
TotFuelConsum
PerTotFuelCons
Values Date/Time
8.2.9
1. Time
2. Date
8.2.10
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Values Info
Engine State
Breaker State
Timer Text
Timer Value
FW Version
FW Branch
PasswordDecode
CAN16
CAN32
GensLoaded16
GensLoaded32
NT
135
9.1
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
9.2
Common functions
GCB Feedback
MCB Feedback
Emergency Stop
Sd Override
Access Lock
Remote OFF
Remote MAN
Remote AUT
RemControlLock
Emergency MAN
Start Button
Stop Button
FaultResButton
HornResButton
GCB Button
ForwSyncDisabl
NeutralCB fdb
PerFuelConsRes
MINT specific
MINT only
1.
2.
3.
4.
9.3
Sys Start/Stop
Load Reserve 2
Min Run Power
Top Priority
SPtM specific
SPtM only
1.
2.
3.
4.
5.
6.
7.
Rem Start/Stop
Remote TEST
Rem TEST OnLd
RevSyncDisable
MCB Button
Ext MF Relay
MainsFailBlock
NT
136
Starter
Battery B
Fuel Solenoid
Stop Solenoid
Stop Pulse
Ignition
Prestart
Alarm
Horn
Fault Reset
GCB Close/Open
GCB ON Coil
GCB OFF Coil
GCB UV Coil
Speed Up
Speed Down
AVR Up
AVR Down
Ready To Load
Synchronizing
Running
Loaded
Unloading
AnalogSwitch 1
AnalogSwitch 2
AnalogSwitch 3
Ctrl HeartBeat
Gen Healthy
Yellow Alarm
Red Alarm
Mode OFF
Mode MAN
Mode AUT
Exerc Timer 1
Exerc Timer 2
Power Switch
Neutral CB C/O
Breaker Trip
kWh pulse
ECU Comm OK
ECU Comm Error
ECU YellowLamp
ECU RedLamp
ECU PowerRelay
NT
137
AL Gen Volts
AL Gen Freq
AL Overcurrent
AL Gen V,Freq
AL Overspeed
AL Underspeed
AL Overload
AL Reverse Pwr
AL Start Fail
AL Stop Fail
AL Sync Fail
AL Batt Volt
AL Earth Fault
BI1 Status
BI2 Status
BI3 Status
BI4 Status
BI5 Status
BI6 Status
BI7 Status
BI8 Status
BI9 Status
IOM BI1 Status
IOM BI2 Status
IOM BI3 Status
IOM BI4 Status
IOM BI5 Status
IOM BI6 Status
IOM BI7 Status
IOM BI8 Status
ExtBI 1 Status
ExtBI 2 Status
ExtBI 3 Status
ExtBI 4 Status
ExtBI 5 Status
ExtBI 6 Status
ExtBI 7 Status
ExtBI 8 Status
AL AI1 Yel
AL AI2 Yel
AL AI3 Yel
AL AI1 Red
AL AI2 Red
AL AI3 Red
AL IOM AI1 Yel
AL IOM AI2 Yel
AL IOM AI3 Yel
AL IOM AI4 Yel
AL IOM AI1 Red
AL IOM AI2 Red
AL IOM AI3 Red
AL IOM AI4 Red
AL Common Wrn
AL Common Sd
AL Common Stp
AL Common BOC
AL Common Fls
AL Exct Loss
NT
138
Bus Healthy
System Ready
SystReserve OK
EnginesSwapped
MCB Close/Open
MCB ON Coil
MCB OFF Coil
MCB UV Coil
Ready To AMF
Mains Healthy
Mains Fail
Mode TEST
NT
139
11 Communication
For details about communication with extension modules and EFI equipped engines, see the
appropriate chapters in this manual.
More detailed information about all topics regarding communications is available in the document Inteli
Communication Guide, which is regularly updated and can be downloaded from the website
www.comap.cz.
RS232
CROSS-WIRED
RS232 CABLE
RS232
RS485
RS485 CABLE
RS485
IL-NT RS232-485
Physical COM Port
RS232
CROSSED-WIRED
RS232 CABLE
USB
RS232
IL-NT RS232
USB
Virtual COM Port
USB
IL-NT S-USB
Shielded USB A
cable
USB
NT
140
IL-NT RS232
IL-NT RS232-485
RS232
LAN / WAN /
INTERNET
GSM
MODEM
Ethernet
RJ45
BTS / Mobile
provider
OR
IL-NT RS232
IL-NT RS232-485
RS232
GSM
MODEM
IL-NT RS232
IL-NT RS232-485
GSM
MODEM
RS232
LAN / WAN /
INTERNET
Ethernet
RJ45
ANALOG
MODEM
OR
IL-NT RS232
IL-NT RS232-485
RS232
ANALOG
MODEM
ANALOG
MODEM
11.2.1
Siemens/Cinterion M20, TC35, TC35i, ES75, MC39 (baud rate 9600 bps)
Wavecom M1200/WMOD2 (baud rate 9600 bps)
Wavecom Maestro 20
Wavecom Fastrack M1306B (Fastrack M1206B is not recommended)
Falcom A2D
NT
141
11.2.2
Analog modems obviously do not require any setup. The only case in which setup could be necessary
is if the modem has been bought in a country with a telephony system different than the target country
where the modem will be used.
GSM modems need to be set up prior to using them with the controller. Use the gm_setup program
(installed together with LiteEdit) to perform initial setup of the modem. See the latest Inteli
Communication Guide (available on the ComAp web site) for details. The setup must be done while a
SIM card is inserted.
NOTE:
It is always recommended to use modems bought in and approved for the target country.
11.3.1
SPtM
Use a plug-in communication module IB-Lite or IL-NT-GPRS to connect to the IC-NT SPtM controller
via the internet. The setpoint COM1 Mode must be set to the DIRECT position.
IB-Lite
Ethernet
RJ45
CROSS-WIRED
ETHERNET CABLE
Ethernet
RJ45
Static IP
IB-Lite
Ethernet
RJ45
Ethernet
RJ45
LAN / WAN /
INTERNET
Static (Public) IP
LAN / WAN /
INTERNET
IL-NT GPRS
Static (Public) IP
IB-Lite
Ethernet
RJ45
BTS / Mobile
provider
Ethernet
RJ45
LAN / WAN /
INTERNET
Non-static non-public IP
Only AirGate ID
(controller nickname)
Ethernet
RJ45
LAN / WAN /
INTERNET
IL-NT GPRS
Non-static non-public IP
Only AirGate ID
(controller nickname)
BTS / Mobile
provider
Ethernet
RJ45
NT
142
11.3.2
MINT
Use a plug-in communication module IB-Lite or IL-NT-GPRS on each controller for connecting to ICNT MINT controllers via the internet. The setpoint COM1 Mode must be set to the DIRECT position.
Ethernet
RJ45
IB-Lite
CROSS-WIRED
ETHERNET CABLE
CAN
Ethernet
RJ45
LAN / WAN /
INTERNET
Ethernet
RJ45
IB-Lite
IL-NT GPRS
CAN
Ethernet
RJ45
IL-NT GPRS
BTS / Mobile
provider
Ethernet
RJ45
IB-Lite
CAN
Non-static non-public IP
Only AirGate ID
(controller nickname)
LAN / WAN /
INTERNET
Ethernet
RJ45
Ethernet
RJ45
IB-Lite
Non-static non-public IP
Only AirGate ID
IL-NT GPRS
CAN
Non-static non-public IP
Only AirGate ID
LAN / WAN /
INTERNET
IL-NT GPRS
CAN
Non-static non-public IP
Only AirGate ID
or
Eth
IB-NT
Ethernet
RJ45
BTS / Mobile
provider
Non-static non-public IP
BTS / Mobile
provider
Only AirGate ID
LAN / WAN /
INTERNET
Ethernet
RJ45
CAN
143
11.3.3
The IB-Lite module with firmware version 1.1 and above makes it possible to use any web browser for
basic monitoring and adjustment of the controller. Direct your web browser to the IP address of the
module, e.g. http://192.168.1.254 and then enter the access code.
11.3.4
NOTE:
Setting the module up requires a certain familiarity with network administration. Ask your IT specialist
for assistance.
The default settings of the module are IP = 192.168.1.254, Netmask = 255.255.255.0 and
Gateway = 192.168.1.1. The default password for service webpages is comap (or 0).
To restore the default settings, close the restore default setting jumper located on the module before
switching the controller on and remove it few seconds after the controller has been switched on.
NOTE:
The default settings can be changed directly from the controller panel by pressing the Page button
and using , and Enter to get to the Comms Settings menu (THIS APPLIES TO FIRMWARE VERSIONS
1.3 AND HIGHER).
11.3.4.1
Configuration
1. Plug the module into the controller and power the controller on.
2. Connect the module into your Ethernet network. If the default address does not match local
network parameters (i.e. the network segment does not use the IP range 192.168.1.xxx or the
IP 192.168.1.254 is occupied), connect the module directly to your PC using a cross-wired
cable. See details in the Installation chapter.
3. If you are connected directly, you have to change temporarily the IP address and subnet mask
of your PC Ethernet connection. Use the following settings: DHCP disabled, IP from the range
192.168.1.1 192.168.1.253 and subnet mask 255.255.255.0. After the IB-Lite setup is
finished, restore your PC setting back to the original values.
4. Start a web browser and direct it to http://192.168.1.254/sp_config.htm.
5. After a successful login the configuration page will be displayed.
6. It is recommended to change the user name and password and keep the new values
confidential.
7. Consult your IT specialist for proper IP settings.
8. Consult your e-mail provider for proper e-mail settings. Note that also most public SMTP
servers require authentication and e-mails must be sent from an existing address.
9. If you want to enable access only for clients with a specified IP address, tick the checkbox
Trusted clients and fill-in the allowed IP addresses.
NOTE:
See also the latest LiteEdit Reference Guide (available on the ComAp web site) for more information
about IB-Lite setup.
11.3.4.2
1.
2.
3.
4.
5.
Firmware upgrade
NOTE:
Interrupting the upload will NOT cause any damage. Just repeat the upload again.
NT
144
11.3.5
System integration
The controller can be integrated into a building management or similar system using an RS232,
RS485 or Ethernet interface and MODBUS protocol. The following modules can be used for this
purpose:
1. IL-NT RS232
2. IL-NT RS232-485
3. IB-Lite (Modbus/TCP)
The setpoint COM1 Mode (RS232) resp. COM2 Mode (RS485, Ethernet) must be set to the MODBUS
position. The speed of MODBUS communication for RS232 and RS485 can be adjusted by the
setpoint ModbusCommSpeed. See a more detailed description of the MODBUS protocol in a separate
chapter.
NOTE:
The controller is able to detect IB-Lite module and performs automatic configuration. Related setpoints
COM1 Mode = DIRECT; COM2 Mode = MODBUS; ModbusCommSpeed = 57600 (THIS APPLIES TO
FIRMWARE VERSIONS 2.0 AND HIGHER).
11.3.6
See the latest InternetBridge-NT Reference Guide for the information on how to set up the IB-NT
module.
11.3.7
See the latest InteliCommunicationGuide for the information on how to set up the IG-IB module.
11.3.8
SNMP
Support for Simple Network Management Protocol was implemented. To generate MIB table go to
LiteEdit 4.6 or higher and use Controller -> Generate Cfg image -> Generate SNMP MIB table.
11.3.9
AirGate
technology for easy plug-and-play wireless communication is incorporated into the product. An
ordinary SIM card with GPRS service is suitable for this system. This overcomes problems with the
necessity for a special SIM card (fixed and public IP), firewalls and difficult communication settings.
http://www.comap.cz/news-room/news-and-events/detail/AirGate
http://www.comap.cz/news-room/news-and-events/detail/The-Rainbow-rises-for-remotemonitoringapplications/
11.3.10 Locate
The controller supports the
technology for GSM localization using an IL-NT-GPRS
communication module. It is possible to view the localization in WebSupervisor.
NT
145
8 data bits
1 stop bit
no parity
communication speed selectable by the setpoint ModbusComSpeed
The Modbus/TCP protocol uses the TCP/IP frames as the transport layer for Modbus frames. This
protocol is available via the IB-Lite module on port 502.
The following features from the Modbus specification are supported:
The response to an incoming message depends on the communication speed. The delay is not
shorter than the time needed to send/receive 3.5 characters. See the latest Inteli Communication
Guide (available on the ComAp website) for details and examples.
The complete description of the Modbus communication protocol can be found in the Modbus Protocol
Reference Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are
available on the web.
NOTE:
The complete list of available registers can be obtained from LiteEdit. Open an online connection to
the controller or open offline an archive and go to the menu Controller -> Generate Cfg image to get
the register list.
CAUTION!
Do not write setpoints repeatedly (e.g. power control from a PLC by repeated writing of baseload
setpoint via Modbus) The setpoints are stored in EEPROM memory, which can be overwritten up to
5
10 times without risk of damage or data loss, but it may become damaged, when the allowed number
of writing cycles is exceeded!
NT
146
IC-NT-RD is remote display software for an InteliCompact controller. Remote display provides the
same control and monitoring functions as controller itself (except limitations given by HW differences
between remote display and controller). Remote display for IC-NT controllers uses standard IL-NT
controller platform with IC-NT Remote display software. No further programming of the display is
required unit is self configurable from the main controller. It is connected with the controller via
IL-NT-RS232 communication modules using RS232 line. Longer distances (up to 1200m) are possible
using IL-NT-RS232-485 communication module or when RS232/RS485 converters are used.
NOTE:
In case of IL-NT-AMF25 HW only Bus under voltage LED (indicating if the bus is under voltage or
not/if the Load is supplied or not) is missing. This information is anyway given by combination of GCB
and MCB position LEDs placed on the right and left side next to the Bus under voltage LED.
The other IL-NT hardware types have other limitations according to HW variations from IC-NT HW.
HINT:
IC-NT RD SW works analogically to IL-NT RD SW. See IC-NT RD SW website to find out more
information about installation and configuration.
NT
147
12 Maintenance
12.1 Backup battery replacement
The internal backup battery lifetime is approx. 10 years. Replace the battery if the alarm Low
BackupBatt occurs. Follow these instructions:
1. Connect the controller to a PC and save an archive for backup purposes.
2. Disconnect all terminals from the controller and remove the controller from the switchboard.
3. Release the rear cover using a flat screwdriver or other suitable tool.
NT
148
6. Put the rear cover back. Use slight pressure to lock the snaps into the housing. Ensure that
the cover is in the correct position and not upside down!
7. Plug the modules back into the slots.
8. Power the controller on, adjust the date and time and check all setpoints.
NOTE:
NT
When the internal RTC battery is drained, the InteliCompact function (e.g. Ready for standby) does
not change until the controller power supply is switched off. After the next power switch on (with
drained battery already), the controller will:
-
NT
149
13 Troubleshooting
SYMPTOM
The unit is dark, no display, no LEDs are lit.
CAUSE
SOLUTION
SYMPTOM
No display, only the backlight is on.
CAUSE
SOLUTION
SYMPTOM
The unit shows Configuration table error and does not work.
CAUSE
SOLUTION
SYMPTOM
The unit shows INIT and does not work, controller mode cannot be changed. This
situation occurs after controller reset if the checksum of setpoints is not correct.
CAUSE
SOLUTION
NT
150
SYMPTOM
You do not know the password.
CAUSE
SOLUTION
SYMPTOM
The controller does not respond to mode buttons on the front panel.
CAUSE
SOLUTION
SYMPTOM
The controller does not respond to the START, STOP or breaker buttons on the front
panel.
CAUSE
SOLUTION
SYMPTOM
It is not possible to change setpoints.
CAUSE
SOLUTION
Some setpoints can be configured as protected Enter the password prior going to change
by password.
protected setpoints
The binary input Access Lock is active.
SYMPTOM
Incorrect kW and power factor reading, but correct voltage and current readings.
CAUSE
SOLUTION
151
SYMPTOM
Governor output does not work; the output level is continuously at the lower or upper
limit.
CAUSE
SOLUTION
Wrong (opposite) position of the setpoint Speed Check the setpoint position if it fits the Governor
Gov Char.
requirements.
Opposite or wrong wiring of the Governor/AVRi
Check and correct the wiring.
output.
The governor output is switched to PWM mode Put the PWM jumper at the governor output into
but the governor needs voltage mode or vice
the proper position according to the Governor
versa.
requirements.
SYMPTOM
The cranking is cut off too early, the engine does not start.
CAUSE
SOLUTION
SYMPTOM
The MCB control does not work properly, the alarm MCB fail is present all the time.
CAUSE
SOLUTION
The position of the setpoint MCB Logic does not Switch the setpoint MCB Logic into proper
match the current MCB wiring.
position.
SYMPTOM
The communication via CAN bus with other engines, extension units or ECU does not
work, i.e. you do not see other engines in the CAN16 or CAN32 value or the controller
shows an alarm in the Alarmlist that some of extension units or ECU does not
communicate.
CAUSE
SOLUTION
NT
152
14 Technical data
14.1 Power supply
Power supply range
836 V DC
Power consumption
approx. 200 mA / 8 V; 50 mA / 36 V
CR 1225
10 years
-2070 C
-4070 C
Operating humidity
IP65
Vibration
Shocks
Storage temperature
-3080 C
185x125x60 mm (WxHxD)
Weight
Mounting cutout size
175x115 mm (WxH)
EN 61010-1:95 +A1:97
NT
153
Galvanic insulation
Not insulated
Common pole
Positive, Vs = 836 V DC
<2 V
4 V - Vs
Input resistance
4.2 k
Galvanic insulation
Not insulated
Type
Operating voltage
836 V DC
Switching current
Total current
Galvanic insulation
Not insulated
Electrical range
02500
Resolution
10 bits, 4 digits
Precision
Measurement type
True RMS
Voltage range
340 V Ph-N
Voltage accuracy
Current range
5A
9A
12 A continuous, 50 A/1
Current accuracy
NT
154
CT input burden
<0.5 VA
Frequency range
Frequency accuracy
0.05 Hz
270 Vpp
Frequency range
Accuracy
0.2%
80% of Usupply
Galvanic insulation
1525 V AC or 2035V DC
Inputs
Outputs
max 15 mA
Mechanical dimensions
230277 V AC
230 V AC 20%
277 V AC + 20%
Primary voltage 2
400480 V AC
400 V AC 20%
480 V AC + 20%
Frequency
5060 Hz
Secondary voltage
18 V AC, 5 VA
NT
155
Operating temperature
-30..+70 C
100120 V AC
100 V AC - 20%
120 V AC + 20%
Frequency
5060 Hz
Secondary voltage
18 V AC
Operating temperature
-30..+70 C
Galvanic insulation
Not insulated
RS485
Baud rate
USB
Ethernet
CAN bus
Galvanic insulation
Insulated, 500 V
Baud rate
250 kbps
Bus length
max. 200 m
Termination resistor
Galvanic insulation
Insulated, 500 V
Baud rate
250 kbps
Bus length
max. 200 m
NT
156
Termination resistor
NT
157
15 Language support
The controller contains memory slots for 2 languages. English and Chinese are provided in the default
archives. The languages can be changed in the LiteEdit software using dictionaries. There are two
types of dictionaries:
The custom dictionary is used for storing translations that were made by the user because there was
no default dictionary for the particular language, the default dictionary was incomplete or the user
simply wishes to have different translations. For more information about languages and translations,
see the LiteEdit help.
It is possible to create any language using a code page supported by the controller:
NOTE:
See the Operator guide for information on how to select the controller front panel language.
NT
158
16 Appendix
16.1 Table of setpoints
16.1.1
16.1.1.1
Setpoint: Baseload
Group
Process Control
Range [units]
Related
applications
SPtM
Description
16.1.1.2
Setpoint: Base PF
Group
Process Control
Range [units]
Related
applications
SPtM
Description
Required gen-set power factor when the gen-set is running parallel to the
mains.
16.1.1.3
Setpoint: AMFStartEnable
Group
Process Control
Range [units]
Related
applications
SPtM
Description
16.1.1.4
Group
ProcessControl
Range [units]
Related
applications
SPtM
Description
Tells controller to activate protection against power export to the Mains. The
function limits gen-set requested power to hold export power lower or equal
to the setpoint Export kW.
NT
159
Setpoint: Export kW
16.1.1.5
Group
ProcessControl
Range [units]
Related
applications
SPtM
Description
Defines max limit for export/import in case Export Limit setpoint is set to
ENABLED. A negative value means import limit, a positive value export limit,
zero means no export/import.
16.1.1.6
Group
Process Control
Range [units]
Related
applications
MINT
Description
Load control mode in parallel to mains operation of the whole group of gensets.
BASELOAD: The total power of the group is controlled to constant level
given by the setpoint #SysBaseLoad. Each loaded gen-set takes equal part
(relative to their nominal power) from this requested value. The load is
regulated locally in each controller by Load control regulation loop, loadsharing is not active. The setpoint #Sys base load is also used for
determining which gen-sets have to run or not.
LDSHARING: Gen-sets load is controlled by MainsCompact controller to
share the total load (given by the setpoint #SysBaseLoad) with other loaded
gen-sets in such a way, that all loaded gen-sets will be loaded at the same
level (relative to gen-set nominal power). Load-sharing regulation loop is
active.
NOTE:
The LOADSHARING mode shall be used in case a MainsCompact controller
is present in the system. In systems without MainsCompact the setpoint must
be in the BASELOAD position.
NOTE:
The power factor (PF) is regulated to constant level given by the setpoint
#SysPwrFactor in parallel to mains operation and does not depend on active
load control mode.
16.1.1.7
Setpoint: #SysBaseLoad
Group
Process Control
Range [units]
Related
applications
MINT
Description
NT
160
16.1.1.8
Setpoint: #SysPwrFactor
Group
Process Control
Range [units]
Related
applications
MINT
Description
Required gen-set power factor when the group of gen-sets is running parallel
to the mains. The PF is regulated locally in each controller by PF control
regulation loop, VARsharing is not active.
16.1.1.9
Group
ProcessControl
Range [units]
Related
applications
All
Description
16.1.1.10
NONE
FORWARD
REVERSE
BOTH
Setpoint: PeakLevelStart
Group
Process Control
Range [units]
Related
applications
SPtM
Description
Load consumption level the gen-set has to start at. Function is inactive when
PeakAutS/S Del = OFF. Gen-set start is PeakAutS/S Del delayed after the
consumption of the Load exceeds the PeakLevelStart limit.
NOTE:
The actual setpoint units and range depend on setting of the Power format
(see the LiteEdit manual).
NOTE:
It is necessary to use IC-NT CT-BIO7 module and measure 1Ph Mains
current.
NT
161
Setpoint: PeakLevelStop
16.1.1.11
Group
Process Control
Range [units]
Related
applications
SPtM
Description
Load consumption level the gen-set has to stop at. Gen-set stop is
PeakAutS/S Del delayed after PeakLevelStop limit is reached. Load
consumption is calculated (not directly measured) as a sum of gen-set and
mains active power.
NOTE:
The actual setpoint units and range depend on setting of the Power format
(see LiteEdit manual).
NOTE:
It is necessary to use IC-NT CT-BIO7 module and measure 1Ph Mains
current.
16.1.1.12
Group
Process Control
Range [units]
Related
applications
SPtM
Description
The condition for the peak automatic start or stop must be valid for a period
longer than the value of this setpoint to execute the automatic start or stop.
Adjusting to 0 causes stop of the gen-set (if there is no other demand for
running) and disables the automatic peak shaving start.
NT
162
16.1.1.13
Group
Process Control
Range [units]
Related
applications
SPtM
Description
16.1.2
16.1.2.1
Setpoint: ControllerName
Group
Basic Settings
Range [units]
[-]
Related
applications
All
Description
NT
163
16.1.2.2
Group
Basic Settings
Range [units]
Related
applications
All
Description
16.1.2.3
Group
Basic Settings
Range [units]
Related
applications
All
Description
This is the current limit for the generator. Generator short current and
generator overcurrent alarms are based on this setpoint.
16.1.2.4
Setpoint: CT Ratio
Group
Basic Settings
Range [units]
Related
applications
All
Description
16.1.2.5
Setpoint: EF CT Ratio
Group
Basic Settings
Range [units]
Related
applications
MINT
Description
Defines current transformer ratio for current measuring input of IC-NT CTBIO7 extension module if used.
16.1.2.6
Group
Basic Settings
Range [units]
Related
applications
SPtM
Description
Defines mains current transformer ratio for current measuring input of IC-NT
CT-BIO7 extension module if used.
NT
164
16.1.2.7
Group
Basic Settings
Range [units]
Related
applications
SPtM
Description
16.1.2.8
Group
Basic Settings
Range [units]
Related
applications
All
Description
16.1.2.9
Setpoint: PT Ratio
Group
Basic Settings
Range [units]
Related
applications
All
Description
Generator voltage potential transformers ratio. If no PTs are used, adjust the
setpoint to 1.
16.1.2.10
Setpoint: Vm PT Ratio
Group
Basic Settings
Range [units]
Related
applications
SPtM
Description
Mains voltage potential transformers ratio. If no PTs are used, adjust the
setpoint to 1.
16.1.2.11
Setpoint: Vb PT Ratio
Group
Basic Settings
Range [units]
Related
applications
MINT
Description
Bus voltage potential transformers ratio. If no PTs are used, adjust the
setpoint to 1.
NT
165
16.1.2.12
Group
Basic Settings
Range [units]
45 ... 65 [Hz]
Related
applications
All
Description
16.1.2.13
Group
Basic Settings
Range [units]
Related
applications
All
Description
16.1.2.14
Group
Basic Settings
Range [units]
Related
applications
All
Description
Number of teeth on the engine flywheel where the pick-up is installed. Set to
zero if no pick-up is used and the Engine speed will be counted from the
generator frequency.
NOTE:
If no pickup is used, the D+ or W terminal should be used to prevent possible
overcranking, which can occur if at least 25% of nominal generator voltage is
not present immediately after exceeding firing speed.
16.1.2.15
Setpoint: ControllerMode
Group
Basic Settings
Range [units]
Related
applications
All
Description
This setpoint can be used for changing the operating mode remotely, e.g. via
Modbus. Use the mode selector on the main screen for changing the mode
from the front panel. Use mode selector in the control window for changing
the mode from LiteEdit.
NT
166
16.1.2.16
Group
Basic Settings
Range [units]
Related
applications
All
Description
16.1.2.17
Group
Basic Settings
Range [units]
0 240 [min]
Related
applications
MINT
Description
Function will switch off the screen backlight after preset number of minutes.
Pressing any button on the controller or automatic start of the gen-set (e.g.
due to power management) will switch the backlight back on.
Default value is 15 minutes. It is possible to switch the function off by setting
0 (backlight will be on all the time).
16.1.3
16.1.3.1
Setpoint: ControllerAddr
Group
Comms Settings
Range [units]
Related
applications
All
Description
NT
167
16.1.3.2
Group
Comms Settings
Range [units]
Related
applications
All
Description
16.1.3.3
Group
Comms Settings
Range [units]
Related
applications
All
Description
16.1.3.4
Setpoint: ModemIniString
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
16.1.3.5
Setpoint: ModbusComSpeed
Group
Comms Settings
Range [units]
Related
applications
All
Description
NT
168
16.1.3.6
Group
Comms Settings
Range [units]
32C, 8C [-]
Related
applications
MINT
Description
NOTE:
Use low speed for a long-distance connection only. Set all connected
controllers to the same speed.
16.1.3.7
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
16.1.3.8
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
16.1.3.9
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
169
16.1.3.10
Group
Comms Settings
Range [units]
Related
applications
All
Description
The setpoint is used to select the method how the Ethernet connection is
adjusted.
DISABLED:
The Ethernet connection is fixed by means of the setpoints IP Addr, NetMask,
GateIP, DNS IP Address.
This method should be used for a classic Ethernet or internet connection.
When this type of connection opens, the controller is specified by its IP
address. This means that it would be inconvenient if the IP address were not
fixed (static).
ENABLED:
The Ethernet connection setting is obtained automatically from the DHCP
server. The obtained settings are then copied to the related setpoints. If the
process of obtaining the settings from the DHCP server is not successful, the
value 000.000.000.000 is copied to the setpoint IP address and the module
continues to try to obtain the settings.
16.1.3.11
Group
Comms Settings
Range [units]
Related
applications
All
Description
This setpoint is used to adjust the port number, which is used for Ethernet
connection to a PC with any of ComAp PC program (i.e. LiteEdit,
InteliMonitor). This setpoint should be adjusted to 23, which is the default port
used by all ComAp PC programs. A different value should be used only in
special situations such as sharing a single public IP address among many
controllers or to overcome firewall restrictions.
16.1.3.12
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
170
16.1.3.13
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
16.1.3.14
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
16.1.3.15
Setpoint: AirGate
Group
Comms Settings
Range [units]
Related
applications
All
Description
16.1.3.16
Setpoint: AirGate IP
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
This setpoint is used for entering the domain name or IP address of the
AirGate server. Use the free AirGate server provided by ComAp at
airgate.comap.cz if your company does not operate its own AirGate server.
NT
171
16.1.3.17
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
Use this setpoint to enter the username for the SMTP server.
16.1.3.18
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
Use this setpoint to enter the password for the SMTP server.
16.1.3.19
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
16.1.3.20
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
Enter an existing e-mail address in this setpoint. This address will be used as
the sender address in active e-mails that will be sent from the controller.
NT
172
16.1.3.21
Group
Comms Settings
Range [units]
Related
applications
All
Description
This setpoint is used to select the time zone where the controller is located.
Refer to your computer time zone settings (click on the time indicator located
in the rightmost position of the Windows task bar) if you are not sure about
your time zone.
HINT:
If the time zone is not selected properly the active e-mails may contain
incorrect information about the time they were sent, which may result in
confusion about when the respective problem actually occurred.
16.1.3.22
Group
Comms Settings
Range [units]
[-]
Related
applications
All
Description
If DHCP is DISABLED this setpoint is used to adjust the domain name server
(DNS), which is needed to translate domain names in e-mail addresses and
server names into correct IP addresses.
If DHCP is ENABLED this setpoint is used to display the DNS server
assigned by the DHCP server.
16.1.4
16.1.4.1
Group
Engine Params
Range [units]
5 ... 50 [%]
Related
applications
All
Description
This setpoint defines the firing speed level as percent value of the nominal
speed. If this level is exceeded the engine is considered as started. More
information is available in the Engine start chapter.
NT
173
16.1.4.2
Group
Engine Params
Range [units]
0 2000 [Hz]
Related
applications
All
Description
16.1.4.3
Group
Engine Params
Range [units]
Related
applications
All
Description
The controller will stop cranking (starter goes OFF) if the oil pressure rises
above this limit. See the description of the start procedure in a separate
chapter.
NOTE:
If an EFI engine is used, the oil pressure is read from its ECU. In the case of
a traditional engine, the analog input 1 is configured as fixed for oil pressure
measurement.
16.1.4.4
Group
Engine Params
Range [units]
Related
applications
All
Description
Duration of the closing of the Prestart output prior to the starter motor being
energized. Set it to zero to disable this function.
16.1.4.5
Group
Engine Params
Range [units]
Related
applications
All
Description
NT
174
16.1.4.6
Group
Engine Params
Range [units]
5 ... 60 [s]
Related
applications
All
Description
16.1.4.7
Group
Engine Params
Range [units]
1 ... 10 [-]
Related
applications
All
Description
16.1.4.8
Group
Engine Params
Range [units]
Related
applications
All
Description
This setpoint determines the duration of the Idle period which begins after the
engine is started. The output Idle/Nominal remains inactive during the idle
period. This output can be used for switching the governor between idle and
nominal speed.
16.1.4.9
Group
Engine Params
Range [units]
Related
applications
All
Description
When the gen-set has been started and the idle timer has elapsed, the
controller will wait for a period adjusted by this setpoint before closing GCB or
starting synchronizing, even if the generator voltage and frequency are
already in limits.
NT
175
16.1.4.10
Group
Engine Params
Range [units]
Related
applications
All
Description
When the gen-set has been started and the idle timer has elapsed, the
generator voltage and frequency must get within limits within this period of
time, otherwise an appropriate red alarm (generator voltage and/or
frequency) is issued.
16.1.4.11
Group
Engine Params
Range [units]
IDLE, NOMINAL
Related
applications
All
Description
16.1.4.12
Group
Engine Params
Range [units]
Related
applications
All
Description
Duration of the gen-set is running unloaded to cool the engine down before
stop.
16.1.4.13
Group
Engine Params
Range [units]
Related
applications
All
Description
Under normal conditions the engine must certainly stop within this period
after the fuel solenoid has been de-energized and the stop solenoid
energized. The stop solenoid remains energized for the entire stop time
period.
NOTE:
See the chapter Cool down and stop for details about the stop procedure.
NT
176
16.1.4.14
Group
Engine Params
Range [units]
0 ... 60 [s]
Related
applications
All
Description
In case Fuel Solenoid is set to GAS, the SDVentilTime adjusts the time of the
starter to be switched on for engine pre-ventilation in the case of a first start
attempt after shutdown or controller switch-on.
16.1.4.15
Group
Engine Params
Range [units]
Related
applications
All
Description
This setpoint selects the type of start-up sequence according to engine fuel
type. See details in chapter Engine start.
16.1.4.16
Setpoint: D+ Function
Group
Engine Params
Range [units]
Related
applications
All
Description
16.1.4.17
Group
Engine Params
Range [units]
Related
applications
All
Description
177
16.1.4.18
Setpoint: MaxFuelDrop
Group
Engine Params
Range [units]
0 (OFF) 50 [%/h]
Related
applications
All
Description
Setpoint indicates the maximum allowable drop of fuel in fuel tank per running
hour. When the engine is not running, the maximum allowed fuel drop-off is
preset to 5% of the total tank volume per hour.
In case of detection of theft or leak, the alarm Wrn FuelTheft is raised and the
same alarm is sent via SMS and displayed by WebSupervisor (if used).
NOTE:
Set 0 to disable Fuel Theft Protection function.
16.1.4.19
Setpoint: FuelTankVolume
Group
Engine Params
Range [units]
0 10000 [L]
Related
applications
All
Description
16.1.5
16.1.5.1
Group
Engine Protect
Range [units]
Related
applications
All
Description
Maximum time the Horn output is active. The horn always activates whenever
a new alarm occurs and can be silenced earlier by pressing the HORN
RESET button. Acknowledging alarms by pressing FAULT RESET will
silence the horn as well.
If a new alarm appears, the timeout starts to count down again from the
beginning even if the previous countdown has still not elapsed. Adjust this
setpoint to zero if you want to disable the horn completely.
16.1.5.2
Setpoint: ProtectHoldOff
Group
Engine Protect
Range [units]
Related
applications
All
Description
Use this setpoint to adjust the delay starting evaluation of engine running only
alarms. The delay starts to count down in the moment of transition from
starting phase to the idle phase.
NT
178
16.1.5.3
Setpoint: Overspeed Sd
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.4
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.5
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.6
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.7
Group
Engine Protect
Range [units]
Related
applications
All
Description
NT
179
16.1.5.8
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.9
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.10
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.11
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.12
Group
Engine Protect
Range [units]
Related
applications
All
Description
NT
180
16.1.5.13
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.14
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.15
Group
Engine Protect
Range [units]
Related
applications
All
Description
16.1.5.16
Setpoint: WrnMaintenance
Group
Engine Protect
Range [units]
Related
applications
All
Description
Adjust this setpoint to the requested next maintenance interval. The value will
count down when engine is running and if reaches zero, the alarm
Maintenance timer will appear.
This timer is also available in the value group Statistics, but it cannot be
modified there.
In the event that WrnMaintenance is set to 10000 h the timer is disabled and
not visible on the controller display.
NT
181
16.1.6
16.1.6.1
Group
Gener Protect
Range [units]
Related
applications
All
Description
Limit for the generator overload alarm in % of the nominal power. The delay
of this alarm is adjustable by the setpoint Overload Del.
16.1.6.2
Group
Gener Protect
Range [units]
Related
applications
All
Description
Delay for the generator overload alarm. The limit for this alarm is adjustable
by the setpoint Overload BOC.
16.1.6.3
Group
Gener Protect
Range [units]
Related
applications
All
Description
IDMT curve shape selection. Amps IDMT Del is Reaction time of IDMT
protection for 200% overcurrent
IDMT is very inverse generator over current protection. Reaction time is not
constant but depends on generator over current level according to the
following formula:
HINT:
Reaction time is limited to 3600 = 60 minutes. IDMT protection is not active
for Reaction time values longer than 60 minutes.
Igen is maximal value of all measured phases of generator current.
Example
Example of Reaction time for different over current levels. Values in column
200% are IDMT Curr Del.
Reaction time
200% =
IDMT Curr
Del
0.2s
2s
20s
Overcurrent
100%
101%
No action
No action
No action
20s
200s
No action
(time > 3600s)
110%
2s
20s
200s
NT
182
Reaction time
Igen
Nominal Current
16.1.6.4
Short Crct Sd
Group
Gener Protect
Range [units]
Related
applications
All
Description
Limit for the generator short circuit alarm. The delay of this alarm is
adjustable by the setpoint Short Crct Del.
16.1.6.5
Group
Gener Protect
Range [units]
Related
applications
All
Description
Delay for the generator short circuit alarm. The limit for this alarm is
adjustable by the setpoint Short Crct BOC.
16.1.6.6
Group
Gener Protect
Range [units]
Related
applications
All
Description
NT
183
16.1.6.7
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.8
Setpoint: EarthFault Sd
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.9
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.10
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.11
Group
Gener Protect
Range [units]
Related
applications
All
Description
NT
184
16.1.6.12
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.13
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.14
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.15
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.16
Group
Gener Protect
Range [units]
Related
applications
All
Description
NT
185
16.1.6.17
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.18
Setpoint: BusMeasError
Group
Gener Protect
Range [units]
Related
applications
MINT
Description
16.1.6.19
Group
Gener Protect
Range [units]
1 ... 50 [%]
Related
applications
All
Description
Threshold for generator reverse power alarm, relative to the Nominal power.
16.1.6.20
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.6.21
Setpoint: ExcitationLoss
Group
Gener Protect
Range [units]
Related
applications
All
Description
Loss of excitation is based on measurement of negative kVAr and it is BOCtype protection. Value is calculated from the Nominal Power. For example for
NT
186
200 kW gen-set 50% will represent -100 kVAr. Default value is 30%.
16.1.6.22
Group
Gener Protect
Range [units]
Related
applications
All
Description
16.1.7
16.1.7.1
Group
Pwr Management
Range [units]
Related
applications
MINT
Description
The setpoint enables and disables the gen-set to be active within the power
management of the group. It performs automatic load dependent starts and
stops or load demand swap. If the power management is disabled the gensets nominal power is not part of the power management calculation,
however gen-set itself will start/stop onSys Start/Stop signal.
16.1.7.2
Group
Power Management
Range [units]
0 3600 [s]
Related
applications
MINT
Description
16.1.7.3
Setpoint: #PowerMgmtMode
Group
Power Management
Range [units]
Related
MINT
NT
187
applications
Description
Use this setpoint to select whether the power management has to be based
on absolute reserve (in kW) or relative (in %).
NT
188
Setpoint: Priority
16.1.7.4
Group
Pwr Management
Range [units]
1 ... 32 [-]
Related
applications
MINT
Description
This setpoint adjusts the priority of the gen-set within the group. A lower
number represents a higher priority, i.e. a gen-set with lower number will
start before another one with higher number.
If the binary input Top Priority is active, the gen-set gets the highest
priority (0) independent of the setpoint setting.
NOTE:
If more than one gen-set have the same priority they will act as one big genset.
CAUTION:
Value of the setpoint Priority is taken into account only for Load Demand
Start/Stop power management.
16.1.7.5
Setpoint: #PriorAutoSwap
Group
Pwr management
Range [units]
Related
applications
MINT
Description
NOTE:
Binary input Top Priority can be used only if #PriorAutoSwap = DISABLED
NT
189
NOTE:
Since version IC-NT 2.0 setting #RunHrsMaxDiff = 0 or 65000 no longer switch
off the function of run hours equalization.
NOTE:
There is additional 200 ms time gap after SysAMFstrtDel in order to allow the
controllers to calculate which gen-set has to start.
16.1.7.6
Setpoint: #SysAMFStrtDel
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the delay of the system activation after the binary input
Sys Start/Stop has been activated.
This delay is typically used as AMF start delay, similar to the setpoint
EmergStart Del in SPtM, on multiple AMF applications without
MainsCompact. See MINT basic schemes.
16.1.7.7
Setpoint: #SysAMFStopDel
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the delay of the system deactivation after the binary
input Sys Start/Stop has been deactivated.
This delay is typically used as Mains return delay, similar to the setpoint
MainsReturnDel in SPtM, on multiple AMF applications without
MainsCompact. See MINT basic schemes.
16.1.7.8
Setpoint: #LoadResStrt 1
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the reserve for start if the set 1 of reserves is selected,
i.e. binary input Load Reserve 2 is not active. See the power management
description to learn more about reserves.
NT
190
16.1.7.9
Setpoint: #LoadResStop 1
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the reserve for stop if the set 1 of reserves is selected,
i.e. binary input Load Reserve 2 is not active. See the power management
description to learn more about reserves.
16.1.7.10
Setpoint: #LoadResStrt 2
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the reserve for start if the set 2 of reserves is selected,
i.e. binary input Load Reserve 2 is active. See the power management
description to learn more about reserves.
16.1.7.11
Setpoint: #LoadResStop 2
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the reserve for stop if the set 2 of reserves is selected,
i.e. binary input Load Reserve 2 is active. See the power management
description to learn more about reserves.
16.1.7.12
Group
Power Management
Range [units]
Related
applications
MINT
Description
In case of activation LBI MinRunPower -> based on the nominal power, the
gen-sets needed for equalizing the actual MinRunPower requirement are
started (or kept running even if stop reserve is fulfilled). Note, that LBIs Min
Run Power needs to be activated on all gen-sets in the same time.
16.1.7.13
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the delay for starting the next gen-set after the reserve
has dropped below the reserve for start.
NT
191
16.1.7.14
Setpoint: #OverldNextDel
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the delay for starting the next gen-set after the reserve
has dropped below zero, i.e. the system is overloaded.
NOTE:
Adjust this setpoint as short as possible to avoid system shutdown due to
overload caused by too fast load rising.
16.1.7.15
Setpoint: #NextStopDel
Group
Power Management
Range [units]
Related
applications
MINT
Description
This setpoint adjusts the delay for stopping the gen-set after the reserve has
risen above the reserve for stop.
16.1.7.16
Setpoint: #SlowStopDel
Group
Power Management
Range [units]
Related
applications
MINT
Description
If a slow stop red alarm occurs, the affected gen-set will notify the other gensets that it is no longer available, but will remain loaded until the next gen-set
starts and connects to the bus. This setpoint adjusts the maximum time the
affected gen-set will wait for another one to start. After this period it will
perform a slow stop regardless of other gen-sets.
16.1.7.17
Setpoint: RunHoursBase
Group
Power Management
Range [units]
Related
applications
MINT
Description
NT
192
16.1.7.18
Setpoint: #RunHrsMaxDiff
Group
Power Management
Range [units]
0 65000 [h]
Related
applications
MINT
Description
PwrManagement = ENABLED
BI Sys Start/Stop = ACTIVE
#PriorAutoSwap = RUN HOURS
#RunHrsMaxDiff is not set to 0 or 65000; only for fw version less than
2.0 (these values DISABLE Running Hours Equalization function)
16.1.7.19
Setpoint: #PwrBnChngDIUp
Group
Pwr Management
Range [units]
0 - 3600 [s]
Related
applications
MINT
Description
Power Band Change Delay Up - this setpoint is used for adjusting the delay of
changing the power band if the load demand rose above the upper limit of the
current power band. Setpoint is taken into account only if #PriorAutoSwap =
EFFICENT.
16.1.7.20
Setpoint: #PwrBnChngDIDn
Group
Pwr Management
Range [units]
0 - 3600 [s]
Related
applications
MINT
Description
Power Band Change Delay Down - this setpoint is used for adjusting the delay of
changing the power band if the load demand drops below the lower limit of the
current power band. Setpoint is taken into account only if #PriorAutoSwap =
EFFICENT.
NT
193
16.1.8
16.1.8.1
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
Delay between the mains failure and the automatic start of the gen-set to an
AMF operation. See more in the AMF operation chapter.
16.1.8.2
Setpoint: MainsReturnDel
Group
AMF Settings
Range [units]
1 3600 [s]
Related
applications
SPtM
Description
This is a mains stabilization time. If the mains are continuously healthy for
this period after they have returned, the controller will finish the AMF
operation (e.g. by reverse synchronization or a switchover). See more in the
AMF operation chapter.
16.1.8.3
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
16.1.8.4
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
16.1.8.5
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
NT
194
16.1.8.6
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
16.1.8.7
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
16.1.8.8
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
16.1.8.9
Setpoint: VectorShiftLim
Group
AMF Settings
Range [units]
1 ... 45 []
Related
applications
SPtM
Description
Threshold for detection of mains failure due to Vector shift. A mains failure is
detected immediately when the vector surge has occurred without any delay.
16.1.8.10
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
When a switchover of the MCB and GCB is performed (in both directions),
this setpoint defines the period between one breaker being opened and the
other closed.
NT
195
16.1.8.11
Group
AMF Settings
Range [units]
0 ... 60 [s]
Related
applications
SPtM
Description
If the gen-set is still not in AMF operation e.g. GCB has not started and not
closed yet, and the mains becomes healthy again, the MCB is reclosed after
the mains are continuously healthy for this time period.
NOTE:
If the gen-set is already supplying the load, the setpoint MainsReturnDel will
be active instead of this setpoint.
16.1.8.12
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
16.1.8.13
Setpoint: RetFromIsland
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
MANUAL: When RetFromIsland = MANUAL and there is a Mains Fail, gensets are started and after Mains Return operator can manually transfer the
load back to Mains even if the controller stays in AUT mode.
AUTO: No automatic mode change is performed.
NOTE:
Select RetFromIsland = MANUAL in case you need to manually control the
moment when the load is transferred back to the mains.
NT
196
16.1.8.14
Setpoint: BreakerOverlap
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
This setpoint adjusts maximal time period the both GCB and MCB are closed
together during the interrupt-free transfer of the load from the mains to the
gen-set and vice versa.
16.1.8.15
Setpoint: ReturnFromTEST
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
Adjusting of the behaviour of the controller if the gen-set is supplying the load
in TEST mode (after mains have failed) and the mains are recovered:
DISABLED: The gen-set will remain running and supplying the load until
operating mode is changed. See Manual return from test description.
ENABLED: The controller will transfer the load back to the healthy mains and
remain running unloaded. See Automatic return from test description.
16.1.8.16
Group
AMF Settings
Range [units]
Related
applications
SPtM
Description
NT
197
16.1.9
16.1.9.1
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
This setpoint selects the characteristic of the speed governor output of the
controller. Adjust it according to the behaviour of the remote speed input of
the governor:
POSITIVE: raising the voltage on the governor remote speed input causes
engine speed to rise.
NEGATIVE: raising the voltage on the governor remote speed input causes
engine speed to go down.
16.1.9.2
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
This setpoint adjusts the initial voltage level for the speed governor output,
which is present on the output, if no speed or power regulation loop is active.
See the chapter Governor interface for details about the recommended
settings for various governor types. To make a fine adjustment, start the genset in MAN mode, leave it running unloaded and then make fine adjustment
of this setpoint to achieve nominal engine speed.
16.1.9.3
Setpoint: SpeedGovLowLim
Group
Sync/Load Ctrl
Range [units]
0 SpeedGovHiLim [V]
Related
applications
All
Description
Lower limit of the speed governor output. Use this setpoint to adjust the
governor output range according to your governor type.
16.1.9.4
Setpoint: SpeedGovHiLim
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
Upper limit of the speed governor output. Use this setpoint to adjust the
governor output range according to your governor type.
NT
198
16.1.9.5
Setpoint: TauSpeedActuat
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
Time constant of the speed actuator connected to the binary outputs Speed
Up/Speed Down. Setting of this parameter affects the length of the pulses on
these binary outputs. This is to match the reaction of the controllers regulator
with the actual reaction time of the actuator.
16.1.9.6
Group
Sync/Load Ctrl
Range [units]
0 100.0 [%]
Related
applications
All
Description
16.1.9.7
Group
Sync/Load Ctrl
Range [units]
0 ... 90 []
Related
applications
All
Description
X = PhaseWindow
0
-X
NT
199
16.1.9.8
Group
Sync/Load Ctrl
Range [units]
0 25.0 [s]
Related
applications
All
Description
The period of time that the phase angle difference must be within +/- Phase
Window and voltage difference within Voltage Window before the breaker is
closed.
16.1.9.9
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
16.1.9.10
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
16.1.9.11
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
NT
200
16.1.9.13
Group
Sync/Load Cont
Range [units]
Related
applications
All
Description
All changes of requested gen-set load (except in load-sharing mode) are not
made as one step, but are ramped i.e. the requested load is changing
slowly with the rate adjusted by this setpoint.
The rate is adjusted in seconds for 100% load change (from 0 to 100% of
nominal power). So if the requested load change is 50% of nominal power,
the ramp duration will be 50% of this setpoint.
The ramp takes place in the following situations:
16.1.9.14
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
16.1.9.15
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
16.1.9.16
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
After a stop command has been issued in parallel to mains or other gen-sets
operation, the gen-set load is ramped down before the GCB will open. Use
this setpoint to adjust the end-point of the ramp, e.g. the load level (in % of
Nominal Power) where the GCB will be opened.
NT
201
16.1.9.17
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
Use this setpoint to adjust the timeout for reaching the load level GCB Open
Level during the gen-set is being unloaded. When the timeout has elapsed,
the GCB will open regardless of the load.
16.1.9.18
Group
Sync/Load Ctrl
Range [units]
Related
applications
All
Description
16.1.9.19
Group
Sync/Load Ctrl
Range [units]
Related
applications
MINT
Description
16.1.9.20
Group
Sync/Load Ctrl
Range [units]
Related
applications
MINT
Description
NT
202
Group
Volt/PF Ctrl
Range [units]
Related
applications
All
Description
This setpoint adjusts the initial PWM level for the AVR output, which is
present on the output, if no voltage or power factor regulation loop is active.
See the chapter AVR interface for details about the recommended settings
for various AVR types.
NOTE:
The voltage level on the AVR remote voltage input depends also on AVRi
output wiring and potentiometer position.
16.1.10.2
Group
Volt/PF Ctrl
Range [units]
0 200.0 [%]
Related
applications
All
Description
16.1.10.3
Group
Volt/PF Ctrl
Range [units]
Related
applications
All
Description
16.1.10.4
Setpoint: PF Gain
Group
Volt/PF Ctrl
Range [units]
Related
applications
All
Description
NT
203
16.1.10.5
Setpoint: PF Int
Group
Volt/PF Ctrl
Range [units]
Related
applications
All
Description
16.1.10.6
Group
Volt/PF Ctrl
Range [units]
Related
applications
MINT
Description
16.1.10.7
Group
Volt/PF Ctrl
Range [units]
Related
applications
MINT
Description
Group
ExtI/O Protect
Range [units]
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 1 of the
extension module IG-IOM or IGS-PTM.
16.1.11.2
Group
ExtI/O Protect
Range [units]
Related
applications
All
Description
Threshold for the red alarm configured to the analog input 1 of the extension
module IG-IOM or IGS-PTM.
NT
204
16.1.11.3
Group
ExtI/O Protect
Range [units]
Related
applications
All
Description
Delay of the alarms configured to the analog input 1 of the extension module
IG-IOM or IGS-PTM.
16.1.11.4
Group
ExtI/O Protect
Range [units]
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 2 of the
extension module IG-IOM or IGS-PTM.
16.1.11.5
Group
ExtI/O Protect
Range [units]
Related
applications
All
Description
Threshold for the red alarm configured to the analog input 2 of the extension
module IG-IOM or IGS-PTM.
16.1.11.6
Group
ExtI/O Protect
Range [units]
Related
applications
All
Description
Delay of the alarms configured to the analog input 2 of the extension module
IG-IOM or IGS-PTM.
16.1.11.7
Group
ExtI/O Protect
Range [units]
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 3 of the
extension module IG-IOM or IGS-PTM.
NT
205
16.1.11.8
Group
ExtI/O Protect
Range [units]
Related
applications
All
Description
Threshold for the red alarm configured to the analog input 3 of the extension
module IG-IOM or IGS-PTM.
16.1.11.9
Group
ExtI/O Protect
Range [units]
0 180 [s]
Related
applications
All
Description
Delay of the alarms configured to the analog input 3 of the extension module
IG-IOM or IGS-PTM.
ExtI/O Protect
Range [units]
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 4 of the
extension module IG-IOM or IGS-PTM.
ExtI/O Protect
Range [units]
Related
applications
All
Description
Threshold for the red alarm configured to the analog input 4 of the extension
module IG-IOM or IGS-PTM.
ExtI/O Protect
Range [units]
Related
applications
All
Description
Delay of the alarms configured to the analog input 4 of the extension module
IG-IOM or IGS-PTM.
NT
206
Group
SMS/E-Mail
Range [units]
OFF, ON [-]
Related
applications
All
Description
Set this setpoint to YES if you want to get messages when a yellow alarm
occurs.
NOTE:
The target address (GSM phone number or e-mail address) must be set
correctly to the setpoint(s) Phone/Addr 1 or Phone/Addr 2.
16.1.12.2
Group
SMS/E-Mail
Range [units]
OFF, ON [-]
Related
applications
All
Description
Set this setpoint to YES if you want to get messages when a red alarm
occurs.
NOTE:
The target address (GSM phone number or e-mail address) must be set
correctly to the setpoint(s) Phone/Addr 1 or Phone/Addr 2.
16.1.12.3
Group
SMS/E-Mail
Range [units]
OFF, ON [-]
Related
applications
All
Description
Set this setpoint to ON if you want to get messages when a new event
occurs. For target address (GSM phone number or e-mail address) must be
set correctly to the setpoint(s) TelNo/Addr Ch1 or TelNo/Addr Ch2.
NT
207
16.1.12.4
Group
SMS/E-Mail
Range [units]
[-]
Related
applications
All
Description
Enter in this setpoint either a valid GSM phone number or e-mail address
where the alarm messages shall be sent.
NOTE:
For GSM numbers use either the national format (i.e. the number you would
dial if you wanted to make a local call) or the full international format
beginning with a + character followed by the country prefix.
NOTE:
This setpoint can be modified from a PC only!
16.1.12.5
Group
SMS/E-Mail
Range [units]
[-]
Related
applications
All
Description
Enter in this setpoint either a valid GSM phone number or e-mail where the
alarm messages shall be sent.
NOTE:
For GSM numbers use either the national format (i.e. the number you would
dial if you wanted to make a local call) or the full international format
beginning with a + character followed by the country prefix.
NOTE:
This setpoint can be modified from a PC only!
Setpoint: AnaSwitch1 ON
Group
AnalogSwitches
Range [units]
Related
applications
All
Description
Threshold level for switching ON the analog switch assigned to the analog
input 1 of the controller.
NT
208
16.1.13.2
Group
AnalogSwitches
Range [units]
Related
applications
All
Description
Threshold level for switching OFF the analog switch assigned to the analog
input 1 of the controller.
16.1.13.3
Setpoint: AnaSwitch2 ON
Group
AnalogSwitches
Range [units]
Related
applications
All
Description
Threshold level for switching ON the analog switch assigned to the analog
input 2 of the controller.
16.1.13.4
Group
AnalogSwitches
Range [units]
Related
applications
All
Description
Threshold level for switching OFF the analog switch assigned to the analog
input 2 of the controller.
16.1.13.5
Setpoint: AnaSwitch3 ON
Group
AnalogSwitches
Range [units]
Related
applications
All
Description
Threshold level for switching ON the analog switch assigned to the analog
input 3 of the controller.
16.1.13.6
Group
AnalogSwitches
Range [units]
Related
applications
All
Description
Threshold level for switching OFF the analog switch assigned to the analog
input 3 of the controller.
NT
209
16.1.13.7
Setpoint: PowerSwitch ON
Group
AnalogSwitches
Range [units]
0 32000 [kW]
Related
applications
All
Description
16.1.13.8
Setpoint: PowerSwitchOFF
Group
AnalogSwitches
Range [units]
Related
applications
All
Description
Off level for power switch activation, see Power switch chapter.
Group
Date/Time
Range [units]
0 240 [min]
Related
applications
All
Description
If the gen-set is running, the Time stamp records are written periodically into
the history. Use this setpoint to adjust the period in which these records are
written. Adjust the setpoint to 0 to disable this function.
NOTE:
The shorter the timestamp period, the earlier the history log will be
overwritten by Time stamp records. For example, if the period is set to 1 min,
the history will be overwritten after approx. 2 hours of continuous operation.
16.1.14.2
Setpoint: #SummerTimeMod
Group
Date/Time
Range [units]
Related
applications
All
Description
NT
210
16.1.14.3
Setpoint: #Time
Group
Date/Time
Range [units]
[hh.mm.ss]
Related
applications
All
Description
System time can be modified here. The system time is stored in a batterybackup RTC circuit and does not normally need to be adjusted except for
initial setting and occasional corrections.
The system date and time is used for the exercise timers as well as for the
history log. Each record in the history log contains a date/time stamp.
NOTE:
If the system date and time become inaccurate after the controller has been
switched off for a long period of time, it may indicate that the backup battery
needs to be replaced.
16.1.14.4
Setpoint: #Date
Group
Date/Time
Range [units]
[dd.mm.yyyy]
Related
applications
All
Description
System date can be modified here. The system date is stored in a batterybackup RTC circuit and does not normally need to be adjusted except for
initial setting.
The system date and time is used for the exercise timers as well as for the
history log. Each record in the history log contains a date/time stamp.
NOTE:
If the system date and time becomes incorrect after the controller has been
switched off for a long period of time, it may indicate that the backup battery
needs to be replaced.
16.1.14.5
Group
Date/Time
Range [units]
NONE, MONDAY, TUESDAY, ... SUNDAY, MON-FRI, MON-SAT, MONSUN, SAT-SUN [-]
Related
applications
All
Description
This setpoint adjusts the repetition period of the Timer 1. Learn more about
exercise timers in a separate chapter.
NT
211
16.1.14.6
Group
Date/Time
Range [units]
[hh:mm:ss]
Related
applications
All
Description
Timer 1 will be activated at this time on selected day(s). Learn more about
exercise timers in a separate chapter.
16.1.14.7
Setpoint: Timer1Duration
Group
Date/Time
Range [units]
Related
applications
All
Description
This setpoint adjusts the duration that Timer 1 will be active within one cycle.
Learn more about exercise timers in a separate chapter.
16.1.14.8
Setpoint: Timer1Function
Group
Date/Time
Range [units]
Related
applications
All
Description
When this option is chosen the Timer directly starts gen-set (in
AUT mode)
SPtM Only
No Func
TEST
TEST
OnLd
NT
212
16.1.14.9
Group
Date/Time
Range [units]
NONE, MONDAY, TUESDAY, ... SUNDAY, MON-FRI, MON-SAT, MONSUN, SAT-SUN [-]
Related
applications
All
Description
This setpoint adjusts the repetition period of Timer 2. Learn more about
exercise timers in a separate chapter.
Date/Time
Range [units]
[hh:mm:ss]
Related
applications
All
Description
Timer 2 will be activated at this time on selected day(s). Learn more about
exercise timers in a separate chapter.
Date/Time
Range [units]
1 1440 [min]
Related
applications
All
Description
This setpoint adjusts the duration that Timer 2 will be active within one cycle.
Learn more about exercise timers in a separate chapter.
NT
213
Date/Time
Range [units]
Related
applications
All
Description
Mode OFF
AutoRun
SPtM Only
No Func
Mode OFF
MFail Blk
TEST
TEST OnLd
Setpoint: AI1Calibration
Group
Sensors Spec
Range [units]
Related
applications
All
Description
This setpoint can be used to calibrate the controller analog input 1, i.e. shift
the measured value on the analog input with a constant. The setpoint
(constant) is always added to the measured analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
NT
214
Setpoint: AI2Calibration
16.1.15.2
Group
Sensors Spec
Range [units]
Related
applications
All
Description
This setpoint can be used to calibrate the controller analog input 2, i.e. shift
the measured value on the analog input with a constant. The setpoint
(constant) is always added to the measured analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
16.1.15.3
Setpoint: AI3Calibration
Group
Sensors Spec
Range [units]
Related
applications
All
Description
This setpoint can be used to calibrate the controller analog input 3, i.e. shift
the measured value on the analog input with a constant. The setpoint
(constant) is always added to the measured analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
16.1.15.4
Group
Sensors Spec
Range [units]
Related
applications
All
Description
This setpoint can be used to calibrate the analog input 1 of the extension
module IG-IOM or IGS-PTM, i.e. shift the measured value on the analog input
with a constant. The setpoint (constant) is always added to the measured
analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
NT
215
16.1.15.5
Group
Sensors Spec
Range [units]
Related
applications
All
Description
This setpoint can be used to "calibrate" the analog input 2 of the extension
module IG-IOM or IGS-PTM, i.e. shift the measured value on the analog input
with a constant. The setpoint (constant) is always added to the measured
analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
16.1.15.6
Group
Sensors Spec
Range [units]
Related
applications
All
Description
This setpoint can be used to calibrate the analog input 3 of the extension
module IG-IOM or IGS-PTM, i.e. shift the measured value on the analog input
with a constant. The setpoint (constant) is always added to the measured
analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
16.1.15.7
Group
Sensors Spec
Range [units]
Related
applications
All
Description
This setpoint can be used to calibrate the analog input 4 of the extension
module IG-IOM or IGS-PTM, i.e. shift the measured value on the analog input
with a constant. The setpoint (constant) is always added to the measured
analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
NT
216
Group: Engine
16.2.1.1
Value: RPM
Group
Engine
Units
RPM
Related
applications
All
Description
This value contains the current engine speed. The value is obtained from one
of the following sources:
16.2.1.2
Value: W-TerminalFreq
Group
Engine
Units
Hz
Related
applications
All
Description
16.2.1.3
Group
Engine
Units
Related
applications
All
Description
16.2.1.4
Group
Engine
Units
Related
applications
All
Description
Current fuel consumption obtained from the ECU. Contains invalid flag if ECU
is not configured or if the particular ECU does not provide this value.
NT
217
16.2.1.5
Group
Engine
Units
Related
applications
All
Description
Coolant temperature obtained from the ECU. Contains invalid flag if ECU is
not configured or if the particular ECU does not provide this value.
16.2.1.6
Group
Engine
Units
Related
applications
All
Description
Intake air temperature obtained from the ECU. Contains invalid flag if ECU is
not configured or if the particular ECU does not provide this value.
16.2.1.7
Group
Engine
Units
Related
applications
All
Description
Oil pressure obtained from the ECU. Contains invalid flag if ECU is not
configured or if the particular ECU does not provide this value.
16.2.1.8
Group
Engine
Units
Related
applications
All
Description
Oil temperature obtained from the ECU. Contains invalid flag if ECU is not
configured or if the particular ECU does not provide this value.
16.2.1.9
Group
Engine
Units
Related
applications
All
Description
Engine boost pressure obtained from the ECU. Contains invalid flag if ECU is
not configured or if the particular ECU does not provide this value.
NT
218
16.2.1.10
Group
Engine
Units
Related
applications
All
Description
Percent load at current speed value obtained from the ECU. Contains
invalid flag if ECU is not configured or if the particular ECU does not provide
this value.
16.2.1.11
Group
Engine
Units
Related
applications
All
Description
Fuel level obtained from the J1939 bus. Contains invalid flag if ECU is not
configured or if the particular ECU does not provide this value.
16.2.1.12
Group
Engine
Units
Related
applications
All
Description
16.2.1.13
Group
Engine
Units
Related
applications
All
Description
Requested speed
0%
1350 RPM
0%
50%
1500 RPM
50%
100%
1650 RPM
100%
NOTE:
This function (speed adjust via CAN bus) has to be supported by the engine
ECU. Without the support, ComAp controllers can not adjust the engine
speed.
NT
219
16.2.1.14
Group
Engine
Units
RPM
Related
applications
All
Description
16.2.1.15
Group
Engine
Units
Related
applications
All
Description
16.2.1.16
Group
Engine
Units
Related
applications
All
Description
16.2.2
Group: Generator
16.2.2.1
Value: Gen kW
Group
Generator
Units
kW
Related
applications
All
Description
16.2.2.2
Value: Gen kW L1
Group
Generator
Units
kW
Related
applications
All
Description
16.2.2.3
Value: Gen kW L2
Group
Generator
NT
220
Units
kW
Related
applications
All
Description
16.2.2.4
Value: Gen kW L3
Group
Generator
Units
kW
Related
applications
All
Description
16.2.2.5
Group
Generator
Units
kVAr
Related
applications
All
Description
16.2.2.6
Group
Generator
Units
kVAr
Related
applications
All
Description
16.2.2.7
Group
Generator
Units
kVAr
Related
applications
All
Description
16.2.2.8
Group
Generator
Units
kVAr
Related
applications
All
Description
NT
221
16.2.2.9
Group
Generator
Units
kVA
Related
applications
All
Description
16.2.2.10
Group
Generator
Units
kVA
Related
applications
All
Description
16.2.2.11
Group
Generator
Units
kVA
Related
applications
All
Description
16.2.2.12
Group
Generator
Units
kVA
Related
applications
All
Description
16.2.2.13
Value: Gen PF
Group
Generator
Units
Related
applications
All
Description
NT
222
16.2.2.14
Group
Generator
Units
Related
applications
All
Description
16.2.2.15
Value: Gen PF L1
Group
Generator
Units
Related
applications
All
Description
16.2.2.16
Group
Generator
Units
Related
applications
All
Description
16.2.2.17
Value: Gen PF L2
Group
Generator
Units
Related
applications
All
Description
16.2.2.18
Group
Generator
Units
Related
applications
All
Description
NT
223
Value: Gen PF L3
16.2.2.19
Group
Generator
Units
Related
applications
All
Description
16.2.2.20
Group
Generator
Units
Related
applications
All
Description
16.2.2.21
Group
Generator
Units
Hz
Related
applications
All
Description
16.2.2.22
Group
Generator
Units
Related
applications
All
Description
16.2.2.23
Group
Generator
Units
Related
applications
All
Description
NT
224
16.2.2.24
Group
Generator
Units
Related
applications
All
Description
16.2.2.25
Group
Generator
Units
Related
applications
All
Description
16.2.2.26
Group
Generator
Units
Related
applications
All
Description
16.2.2.27
Group
Generator
Units
Related
applications
All
Description
16.2.2.28
Value: Gen A L1
Group
Generator
Units
Related
applications
All
Description
NT
225
Value: Gen A L2
16.2.2.29
Group
Generator
Units
Related
applications
All
Description
16.2.2.30
Value: Gen A L3
Group
Generator
Units
Related
applications
All
Description
16.2.2.31
Value: EarthFaultCurr
Group
Generator
Units
Related
applications
MINT
Description
16.2.3
Group: Mains
16.2.3.1
Group
Mains
Units
Hz
Related
applications
SPtM
Description
16.2.3.2
Group
Mains
Units
Related
applications
SPtM
Description
NT
226
16.2.3.3
Group
Mains
Units
Related
applications
SPtM
Description
16.2.3.4
Group
Mains
Units
Related
applications
SPtM
Description
16.2.3.5
Group
Mains
Units
Related
applications
SPtM
Description
16.2.3.6
Group
Mains
Units
Related
applications
SPtM
Description
16.2.3.7
Group
Mains
Units
Related
applications
SPtM
Description
NT
227
16.2.3.8
Group
Mains
Units
Related
applications
SPtM
Description
16.2.3.9
Value: Mains kW I
Group
Mains
Units
kW
Related
applications
SPtM
Description
16.2.3.10
Group
Mains
Units
kVAr
Related
applications
SPtM
Description
16.2.3.11
Value: Mains PF
Group
Mains
Units
Related
applications
SPtM
Description
16.2.3.12
Group
Mains
Units
Related
applications
SPtM
Description
NT
228
Value: Load kW
16.2.3.13
Group
Mains
Units
kW
Related
applications
SPtM
Description
16.2.3.14
Group
Mains
Units
kVAr
Related
applications
SPtM
Description
16.2.3.15
Value: Load PF
Group
Mains
Units
Related
applications
SPtM
Description
16.2.3.16
Group
Mains
Units
Related
applications
SPtM
Description
16.2.3.17
Value: Slip
Group
Mains
Units
Hz
Related
applications
All
Description
NT
229
Value: Angle
16.2.3.18
Group
Mains
Units
Related
applications
All
Description
The phase shift between the gen-set and the mains voltage.
16.2.3.19
Value: MaxVectorShift
Group
Mains
Units
Related
applications
SPtM
Description
This is the maximum measured value of the vector shift of the generator
voltage. The value is reset to 0 automatically in the moment of closing the
GCB.
16.2.4
Group: Bus
16.2.4.1
Group
Bus
Units
Hz
Related
applications
MINT
Description
16.2.4.2
Group
Bus
Units
Related
applications
MINT
Description
16.2.4.3
Group
Bus
Units
Related
applications
MINT
Description
NT
230
16.2.4.4
Group
Bus
Units
Related
applications
MINT
Description
16.2.4.5
Group
Bus
Units
Related
applications
MINT
Description
16.2.4.6
Group
Bus
Units
Related
applications
MINT
Description
16.2.4.7
Group
Bus
Units
Related
applications
MINT
Description
16.2.4.8
Value: Slip
Group
Mains
Units
Hz
Related
applications
MINT
Description
NT
231
Value: Angle
16.2.4.9
Group
Mains
Units
Related
applications
MINT
Description
The phase shift between the gen-set and the mains voltage.
16.2.5
16.2.5.1
Group
Power management
Units
Related
applications
MINT
Description
16.2.5.2
) [ ]
= Running ActPwr.
Group
Power management
Units
kW
Related
applications
MINT
Description
Sum of active power of all gen-sets within the group that are connected to
the bus and are performing the power management, i.e. that are in AUT
mode and have power management enabled.
NT
232
16.2.5.3
Group
Power management
Units
kVAr
Related
applications
MINT
Description
Sum of reactive power of all gen-sets within the group that are connected to
the bus and are performing the power management, i.e. that are in AUT
mode and have power management enabled.
16.2.5.4
Group
Power management
Units
kW
Related
applications
MINT
Description
Sum of nominal power of all gen-sets within the group that are connected to
the bus and are performing the power management, i.e. that are in AUT
mode and have power management enabled.
16.2.5.5
Group
Power management
Units
kW
Related
applications
MINT
Description
16.2.5.6
Value: Priority
Group
Power management
Units
Related
applications
MINT
Description
This value shows the current priority number. If the binary input Top Priority is
active, the priority number will be 0, otherwise the value will correspond to the
setpoint Priority. See the chapter Power management for details.
16.2.5.7
Group
Power management
Range [units]
Related
applications
MINT
Description
The values show which gen-sets (controller CAN addresses) are running in
current active power band.
NT
233
16.2.5.8
Group
Power management
Range [units]
Related
applications
MINT
Description
The values show which gen-sets (controller CAN addresses) will run if the load
demand rose above the upper limit of the current power band.
16.2.6
16.2.6.1
Group
Controller I/O
Units
Related
applications
All
Description
16.2.6.2
Value: D+
Group
Controller I/O
Units
Related
applications
All
Description
D+ terminal voltage.
16.2.6.3
Group
Controller I/O
Units
configurable
Related
applications
All
Description
This is the value of the analog input 1 of the controller. It will contain an
invalid flag if the input is not used or sensor fail is detected on it.
16.2.6.4
Group
Controller I/O
Units
configurable
Related
applications
All
Description
This is the value of the analog input 2 of the controller. It will contain an
invalid flag if the input is not used or sensor fail is detected on it.
NT
234
16.2.6.5
Group
Controller I/O
Units
configurable
Related
applications
All
Description
This is the value of the analog input 3 of the controller. It will contain an
invalid flag if the input is not used or sensor fail is detected on it.
16.2.6.6
Group
Controller I/O
Units
Related
applications
All
Description
This is a bit array containing the status of the physical binary inputs of the
controller. Bit0 represents BI1, bit1 represents BI2, etc.
NOTE:
In LiteEdit and on the controller screen this value is displayed in normal
order, i.e. BI1 in the leftmost position
16.2.6.7
Group
Controller I/O
Units
Related
applications
All
Description
This is a bit array containing the status of the physical binary outputs of the
controller. Bit0 represents BO1, bit1 represents BO2, etc.
NOTE:
In LiteEdit and on the controller screen this value is displayed in normal
order, i.e. BO1 in the leftmost position.
16.2.6.8
Group
Controller I/O
Units
Related
applications
All
Description
This is the actual voltage on the speed governor output of the controller. In
the event that the output is switched to PWM mode, the relation is
10V ~ 100% PWM.
16.2.6.9
Group
Controller I/O
Units
NT
235
Related
applications
All
Description
This is the actual PWM percentage on the AVRi output of the controller.
16.2.6.10
Group
Controller I/O
Units
Related
applications
All
Description
16.2.6.11
Group
Controller I/O
Units
Related
applications
All
Description
16.2.6.12
Group
Controller I/O
Units
Related
applications
All
Description
Diagnostic code for the IL-NT-GPRS modem. Standard GSM modems usually
support this value as well. Helps in troubleshooting.
TABLE OF DIAGNOSTIC CODES
Code
Description
OK. No error.
IL-NT-GPRS is switched on
10
11
12
No GSM signal
13
14
GSM modem did not accept particular initialization command, possibly caused by
NT
236
16.2.6.13
15
Unknown modem
16
17
18
19
No CDMA network
20
255
Group
Controller I/O
Units
Related
applications
All
Description
16.2.6.14
Code
Description
Value: AirGate ID
Group
Controller I/O
Units
Related
applications
All
Description
16.2.6.15
Group
Controller I/O
Units
Related
applications
All
Description
--------
Trying
Ready
NT
237
16.2.7
16.2.7.1
Group
Extension I/O
Units
configurable
Related
applications
All
Description
This is the value of the analog input 1 of the IOM/PTM extension module. It
will contain an invalid flag if the input or module is not used or sensor fail is
detected on it.
16.2.7.2
Group
Extension I/O
Units
configurable
Related
applications
All
Description
This is the value of the analog input 2 of the IOM/PTM extension module. It
will contain an invalid flag if the input or module is not used or sensor fail is
detected on it.
16.2.7.3
Group
Extension I/O
Units
configurable
Related
applications
All
Description
This is the value of the analog input 3 of the IOM/PTM extension module. It
will contain an invalid flag if the input or module is not used or sensor fail is
detected on it.
16.2.7.4
Group
Extension I/O
Units
configurable
Related
applications
All
Description
This is the value of the analog input 4 of the IOM/PTM extension module. It
will contain an invalid flag if the input or module is not used or sensor fail is
detected on it.
NT
238
16.2.7.5
Group
Extension I/O
Units
Related
applications
All
Description
This is a bit array containing the status of physical binary inputs of the
IOM/PTM extension module. Bit0 represents BI1, bit1 represents BI2, etc.
NOTE:
In LiteEdit and on the controller screen this value is displayed in normal
order, i.e. BI1 in the leftmost position.
16.2.7.6
Group
Extension I/O
Units
Related
applications
All
Description
This is a bit array containing the status of physical binary inputs of the
extension plugin module. Bit0 represents ExM BI1, bit1 represents ExM BI2,
etc.
NOTE:
In the LiteEdit and on the controller screen this value is displayed in normal
order, i.e. ExM BI1 in the leftmost position.
16.2.7.7
Group
Extension I/O
Units
Related
applications
All
Description
This is a bit array containing the status of the LED indicators of the RA15
module. Bit0 represents the top left LED, bit14 represents the bottom right
LED.
NOTE:
In LiteEdit and on the controller screen this value is displayed in normal
order, i.e. bit0 in the leftmost position.
NT
239
16.2.7.8
Group
Extension I/O
Units
Related
applications
All
Description
This is a bit array containing the status of physical binary outputs of the
IOM/PTM module. Bit0 represents BO1, bit1 represents BO2, etc.
NOTE:
In LiteEdit and on the controller screen this value is displayed in normal
order, i.e. BO1 in the leftmost position.
16.2.8
Group: Statistics
16.2.8.1
Group
Statistics
Units
kWh
Related
applications
All
Description
16.2.8.2
Group
Statistics
Units
kVArh
Related
applications
All
Description
16.2.8.3
Group
Statistics
Units
Related
applications
All
Description
NT
240
16.2.8.4
Group
Statistics
Units
Related
applications
All
Description
16.2.8.5
Value: Maintenance
Group
Statistics
Units
Related
applications
All
Description
Countdown until next maintenance. Initial value can be set in Engine Protect
WrnMaintenace.
16.2.8.6
Group
Statistics
Units
Related
applications
All
Description
16.2.8.7
Value: Shutdowns
Group
Statistics
Units
Related
applications
All
Description
NT
241
16.2.8.8
Value: TotFuelConsum
Group
Statistics
Units
Related
applications
All
Description
16.2.8.9
Value: PerTotFuelCons
Group
Statistics
Units
Related
applications
All
Description
16.2.9
Group: Date/Time
16.2.9.1
Value: Time
Group
Info
Units
hh:mm:ss
Related
applications
All
Description
16.2.9.2
Value: Date
Group
Info
Units
dd.mm.yyyy
Related
applications
All
Description
NT
242
Group
Info
Units
Related
applications
All
Description
The value contains the numeric code of the engine state message which is
shown on the main screen of the controller.
The assignment of texts to the codes can be obtained using LiteEdit. Open
any connection (also offline with a previously saved archive) and go to the
menu Controller -> Generate CFG image. The resulting file will contain the
assignment of texts to the codes.
16.2.10.2
Group
Info
Units
Related
applications
All
Description
The value contains the numeric code of the breaker state message which is
shown on the main screen of the controller.
The assignment of texts to the codes can be obtained using LiteEdit. Open
any connection (also offline with a previously saved archive) and go to the
menu Controller -> Generate CFG image. The resulting file will contain the
assignment of texts to the codes.
16.2.10.3
Group
Info
Units
Related
applications
All
Description
The value contains the numeric code of the Current process timer text
which is shown on the main screen of the controller.
The assignment of texts to the codes can be obtained using LiteEdit. Open
any connection (also offline with a previously saved archive) and go to the
menu Controller -> Generate CFG image. The resulting file will contain the
assignment of texts to the codes.
NT
243
16.2.10.4
Group
Info
Units
Related
applications
All
Description
The value contains the "Current process timer" value which is shown on the
main screen of the controller.
16.2.10.5
Value: FW Version
Group
Info
Units
Related
applications
All
Description
Major and minor firmware version number. This value does not contain the
release version number.
16.2.10.6
Value: FW Branch
Group
Info
Units
Related
applications
All
Description
16.2.10.7
Value: PasswordDecode
Group
Info
Units
Related
applications
All
Description
This value contains a number which can be used for retrieving a lost
password. Send this number together with the controller serial number to
your distributor if you have lost your password.
16.2.10.8
Value: CAN16
Group
Info
Units
Related
applications
MINT
Description
Each bit of this value shows if a controller with the corresponding address is
found on the bus. Bit 0 represents address 1 etc.
NT
244
16.2.10.9
Value: CAN32
Group
Info
Units
Related
applications
MINT
Description
Each bit of this value shows if a controller with the corresponding address is
found on the bus. Bit 0 represents address 16 etc.
Info
Units
Related
applications
MINT
Description
Info
Units
Related
applications
MINT
Description
Common functions
16.3.1.1
Related
applications
All
Description
NT
245
16.3.1.2
Related
applications
All
Description
This is an input from the Mains circuit breaker or contactor auxiliary contact. If
the input is active, the controller will consider the MCB as closed and vice
versa. According to the MCB position the controller differentiates between
Parallel to Mains operation and Island operation.
SPtM, MainsCompact: If the MCB is not in the expected position, the alarm
MCB Fail will occur.
16.3.1.3
Related
applications
All
Description
This input will activate the built-in Emergency Stop alarm. It is recommended
to use the NC button for this input because of safety reasons.
CAUTION!
This is a software function only. See the chapter Emergency stop in the
Installation section of this manual if a hard-wired emergency stop function is
needed.
16.3.1.4
Related
applications
All
Description
If this input is active, all red alarms except emergency stop and overspeed
are suppressed. The suppressed alarms will be displayed in the alarmlist, but
they will not take effect regarding the gen-set control.
NOTE:
This input is designed to be used only while the gen-set is supplying pumps
for automatic fire-extinguishing devices (sprinklers) or in other situations,
where providing power is more important than protecting the gen-set.
CAUTION!
Misuse of this input can cause damage to the gen-set!
16.3.1.5
Related
applications
All
Description
If this input is active, then change of all setpoints and controller mode is
disabled, even if the password is entered.
NOTE:
Active access lock is indicated by an L letter in the upper right corner of the
controller main screen.
NOTE:
This input does not disable remote changes of setpoints i.e. from LiteEdit.
NT
246
16.3.1.6
Related
applications
All
Description
This input switches the controller into OFF mode independent of which mode
is selected by the mode selector on the controller main screen. Learn more
about controller modes in the Operating modes chapter.
If multiple remote mode inputs are active at the same time, the highest
priority has Remote OFF, then Remote TEST, Remote MAN and Remote
AUT.
16.3.1.7
Related
applications
All
Description
This input switches the controller into MAN mode independent of which mode
is selected by the mode selector on the controller main screen. Learn more
about controller modes in the Operating modes chapter.
If multiple remote mode inputs are active at the same time, the highest
priority is held by Remote OFF, then Remote TEST, Remote MAN and
Remote AUT.
16.3.1.8
Related
applications
All
Description
This input switches the controller into AUT mode independent of which mode
is selected by the mode selector on the controller main screen. Learn more
about controller modes in the Operating modes chapter.
If multiple remote mode inputs are active at the same time, the highest
priority is held by Remote OFF, then Remote TEST, Remote MAN and
Remote AUT.
16.3.1.9
Related
applications
All
Description
If the input is active, the controller will not accept any actions regarding the
gen-set control e.g. writing of commands and setpoint changes from
remote communication interfaces (RS232, Modem, Modbus, iG-IB, i-LB).
NT
247
16.3.1.10
Related
applications
All
Description
16.3.1.11
Shows the text EmergMan in the engine status on the main screen.
Stops all functions regarding the gen-set control, deactivates all
outputs related to it.
Stop Fail alarm is not being evaluated and stop solenoid is not
activated if nonzero speed is detected.
When the input is deactivated, the controller takes control over the
gen-set according to the situation the gen-set was in the moment of
deactivation, i.e. the gen-set remains running loaded if it was running
and GCB was closed in the moment the input was deactivated.
Related
applications
All
Description
This input is to be used as an external start button for control of the gen-set in
manual mode. It works the same way as the start button on the panel.
16.3.1.12
Related
applications
All
Description
This input is to be used as an external stop button for control of the gen-set in
manual mode. It works the same way as the stop button on the panel.
NOTE:
For safety reasons it is recommended to configure this input as NC input and
use a NC button.
16.3.1.13
Related
applications
All
Description
This input is to be used as an external fault reset button. It works the same
way as the fault reset button on the panel.
16.3.1.14
Related
applications
All
Description
This input is to be used as an external horn reset button. It works the same
way as the horn reset button on the panel.
NT
248
16.3.1.15
Related
applications
All
Description
This input is to be used as an external GCB button for control of the gen-set
in manual mode. It works the same way as the GCB button on the panel.
16.3.1.16
Related
applications
All
Description
If the input is active, the controller will not continue to synchronize after
MinStabTime elapsed even in AUT mode. If an island condition occurs
(mains fails), the gen-set will take the island load.
16.3.1.17
Related
applications
All
Description
Use this input to detect whether the Neutral circuit breaker is open or closed.
See also setpoint #Neutral cont and binary output Neutral CB C/O.
16.3.1.18
Related
applications
All
Description
If the input is active, the controller will not continue to synchronize after
MinStabTime elapsed even in AUT mode. If an island condition occurs
(mains fails), the gen-set will take the island load.
16.3.2
MINT specific
16.3.2.1
Related
applications
MINT
Description
This input activates the power management in the controller. If this input is
not active, the gen-set is stopped in AUT mode and does not take part within
the power management of the group.
NOTE:
In most cases this input is wired parallel into all controllers within the group to
activate and deactivate the whole group. If you want to deactivate one
particular gen-set, switch it out from AUT mode.
NOTE:
If the power management is disabled by the Pwr Management setpoint, the
gen-set is started and stopped only according to this input.
NT
249
16.3.2.2
Related
applications
MINT
Description
This input selects the currently used pair of reserves for the power
management. If the input is active, the pair LoadResStrt 2 and LoadResStop
2 is active instead of LoadResStrt 1 and LoadResStop 1.
16.3.2.3
Related
applications
MINT
Description
Use this input if you need to ensure that the nominal power of loaded gensets does not drop below the value of Min Run Power even if the reserve for
stop is fulfilled.
16.3.2.4
Related
applications
MINT
Description
If this input is active, the controller will have the highest priority in the group
independent of the setpoint Priority. Setpoint is evaluated only in Load
Demand Star/Stop regime.
16.3.3
SPtM specific
16.3.3.1
Related
applications
SPtM
Description
Use this input to start and stop the gen-set in AUT mode.
16.3.3.2
Related
applications
SPtM
Description
This input switches the controller into TEST mode independent of which
mode is selected by the mode selector on the controller main screen. Learn
more about controller modes in the Operating modes chapter.
If multiple remote mode inputs are active at the same time, the highest
priority is held by Remote OFF, then Remote TEST, Remote MAN and
Remote AUT.
16.3.3.3
Related
applications
SPtM
Description
This input switches the controller into TEST mode like Remote TEST, but
forces the controller to take the load, i.e. perform the test on load procedure.
NT
250
16.3.3.4
Related
applications
SPtM
Description
If the input is active, the controller will not perform reverse synchronizing
when the mains have returned, but performs a changeover instead.
16.3.3.5
Related
applications
SPtM
Description
This input is to be used as an external MCB button for control of the breaker
in manual mode. It works the same way as the MCB button on the panel.
16.3.3.6
Related
applications
SPtM
Description
This input can be used for connecting an external mains protection relay. If
the input is activated, the controller will consider the mains to have failed and
will perform all appropriate actions.
16.3.3.7
Related
applications
SPtM
Description
If the input is active, the gen-set will not start after the mains fail although the
controller is in AUT mode. If the gen-set is already running and the input has
been activated, the timer ReturtnDel starts to count then the GCB is opened,
gen-set goes to cooling procedure and stops The input simulates healthy
mains.
NOTE:
THE MCB WILL CLOSE WHILE THE GCB IS OPENING!
Common functions
16.4.1.1
Related
applications
All
Description
NT
251
16.4.1.2
Related
applications
All
Description
This output should be used in case that two batteries for starting are used.
Batter B output switches between two alternative sources of power, battery A
and battery B. Battery B output is opened for the first cranking cycle which is
designated for Battery A and closes for the second cranking cycle which is
designated for Battery B (in case that two batteries for cranking are used).
Starter
(=Cranking)
Battery B
16.4.1.3
1st attempt
Crank pause
Battery A in use
2nd attempt
Battery B in use
Related
applications
All
Description
This output is dedicated to controlling the fuel solenoid (valve). The output is
closed 0.5 before Starter and remains closed all the time the gen-set shall
run.
NOTE:
Learn more about starting procedure in the chapter Engine start.
16.4.1.4
Related
applications
All
Description
This output is dedicated to control the stop solenoid (valve). The output is
closed in the moment when the gen-set shall stop and remains active until
the gen-set is stopped, but at least for time period of Stop Time. If the Stop
time has elapsed and the engine is still not stopped, the stop solenoid is deenergized for 5 and then energized again for max. Stop time and this repeats
until the engine is stopped.
NOTE:
Learn more about evaluation of stopped engine in the chapter Stopped genset evaluation.
16.4.1.5
Related
applications
All
Description
This output will give a 1 pulse whenever a stop command is issued to the
gen-set, i.e. when the binary output Stop Solenoid is activated.
NT
252
16.4.1.6
Related
applications
All
Description
This output is dedicated to controlling the ignition at a gas engine. The output
is closed together with Fuel Solenoid in the moment the gen-set reaches
30RPM during cranking. The output is opened when the gen-set has
stopped.
16.4.1.7
Related
applications
All
Description
This output can be used for control of any device, which has to be activated
just before start, i.e. glow plugs. The output is closed for time period of
Prestart Time prior to activation of the starter motor and remains closed
during cranking and also during pause between cranking attempts.
16.4.1.8
Related
applications
All
Description
This output is dedicated for coolant pump control. It is closed in the moment
the gen-set is started and remains closed until the gen-set is stopped.
16.4.1.9
Related
applications
All
Description
This output is used for switching between idle speed and nominal speed of
the engine during the startup phase, if this feature (input) is available on the
particular engine. In the case of some EFI engines, the idle/nominal switching
is performed over the communication bus.
16.4.1.10
Related
applications
All
Description
NT
253
16.4.1.11
Related
applications
All
Description
16.4.1.12
Related
applications
All
Description
The output is a copy of Fault Reset button on controller and binary input
FaultResButton.
16.4.1.13
Related
applications
All
Description
16.4.1.14
Related
applications
All
Description
This output is to be used for control of the ON coil of the generator circuit
breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
16.4.1.15
Related
applications
All
Description
This output is to be used for control of the OFF coil of the generator circuit
breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
16.4.1.16
Related
applications
All
Description
This output is to be used for opening the generator circuit breaker via the
undervoltage coil. See the chapter Circuit breakers for details about all
outputs available for generator/mains power switches.
NT
254
16.4.1.17
Related
applications
All
Description
This output together with the complementary output Speed Down is designed
for speed and power control at gen-sets, where the governor does not
support analog control. The outputs are also used for direct control of a gas
throttle at asynchronous gen-sets.
NOTE:
Droop function is required when these outputs are used for power control
through a governor.
16.4.1.18
Related
applications
All
Description
This output together with the complementary output Speed Up is designed for
speed and power control at gen-sets, where the governor does not support
analog control. The outputs are also used for direct control of a gas throttle at
asynchronous gen-sets.
NOTE:
Droop function is required when these outputs are used for power control
through a governor.
16.4.1.19
Related
applications
All
Description
This output together with the complementary output AVR Down is designed
for voltage and power factor control at gen-sets, where the AVR does not
support analog control.
NOTE:
Droop function is required when these outputs are used for power factor
control.
16.4.1.20
Related
applications
All
Description
This output together with the complementary output AVR Up is designed for
voltage and power factor control at gen-sets, where the AVR does not
support analog control.
NOTE:
Droop function is required when these outputs are used for power factor
control.
NT
255
16.4.1.21
Related
applications
All
Description
The output is closed whenever the GCB is closed or can be closed. Details
about conditions when the GCB can be closed are available in the chapter
Connecting to the load.
16.4.1.22
Related
applications
All
Description
16.4.1.23
Related
applications
All
Description
16.4.1.24
Related
applications
All
Description
The output is closed whenever the GCB is closed except the unloading phase
prior to opening the GCB.
16.4.1.25
Related
applications
All
Description
The output is closed during the unloading phase (ramping the power down)
prior to opening the GCB. More detailed description is available in the chapter
Parallel to mains operation.
16.4.1.26
Related
applications
All
Description
16.4.1.27
Related
applications
All
Description
NT
256
16.4.1.28
Related
applications
All
Description
16.4.1.29
Related
applications
All
Description
16.4.1.30
Related
applications
All
Description
This output is active when the generator voltage and frequency is within
limits. It is deactivated:
16.4.1.31
Related
applications
All
Description
16.4.1.32
Related
applications
All
Description
16.4.1.33
Related
applications
All
Description
NT
257
16.4.1.34
Related
applications
All
Description
16.4.1.35
Related
applications
All
Description
16.4.1.36
Related
applications
All
Description
This is an output from the Exercise timer 1. This output makes it easy to
make periodic tests of the gen-set and its activation depends on the setpoints
in the Date/time group.
16.4.1.37
Related
applications
All
Description
16.4.1.38
Related
applications
All
Description
16.4.1.39
Related
applications
All
Description
NT
258
16.4.1.40
Related
applications
All
Description
16.4.1.41
Related
applications
All
Description
This output generates a 100 ms pulse whenever the internal kWh counter is
incremented.
16.4.2
ECU info
16.4.2.1
Related
applications
All
Description
16.4.2.2
Related
applications
All
Description
This output is active when an ECU is configured, but the communication with
the ECU is not established or has dropped out.
16.4.2.3
Related
applications
All
Description
This output is active when the ECU sends an active yellow lamp flag, i.e. it
has detected a non-critical malfunction. This flag is taken from the DM1 frame
on standard J1939 ECUs. Some ECUs provide this flag in their own
proprietary frames and some do not provide the flag at all.
NT
259
16.4.2.4
Related
applications
All
Description
This output is active when the ECU sends an active red lamp flag, i.e. it has
detected a critical malfunction and the engine should not be operated until a
service check is performed. This flag is taken from the DM1 frame on
standard J1939 ECUs. Some ECUs provide this flag in their own proprietary
frames and some do not provide the flag at all.
16.4.2.5
Related
applications
All
Description
Binary Outputs
Starter
On
Starter
Off
Prestart
On
Prestart
Off
Prestart Time
Start
Engine is running
Starting RPM
Time
NT
260
16.4.3
Alarm mirrors
16.4.3.1
Related
applications
All
Description
16.4.3.2
Related
applications
All
Description
16.4.3.3
Related
applications
All
Description
This output is active when the generator overcurrent or short current alarm is
present in the alarmlist.
16.4.3.4
Related
applications
All
Description
16.4.3.5
Related
applications
All
Description
This output is active when the overspeed alarm is present in the alarmlist.
16.4.3.6
Related
applications
All
Description
This output is active when the underspeed alarm is present in the alarmlist.
16.4.3.7
Related
applications
All
Description
This output is active when the overload alarm is present in the alarmlist.
NT
261
16.4.3.8
Related
applications
All
Description
This output is active when the reverse power alarm is present in the alarmlist.
16.4.3.9
Related
applications
All
Description
This output is active when the start fail alarm is present in the alarmlist.
16.4.3.10
Related
applications
All
Description
This output is active when the stop fail alarm is present in the alarmlist.
16.4.3.11
Related
applications
All
Description
16.4.3.12
Related
applications
All
Description
This output is active when the Battery voltage or Battery flat is present in the
alarmlist.
16.4.3.13
Related
applications
All
Description
This output is active when Earth Fault Current alarm is present in alarm list
(extension module IC-NT CT-BIO7 is needed).
16.4.3.14
Related
applications
All
Description
This output gives information about the status of binary input 1 of the
controller.
NT
262
16.4.3.15
Related
applications
All
Description
This output gives information about the status of binary input 2 of the
controller.
16.4.3.16
Related
applications
All
Description
This output gives information about the status of binary input 3 of the
controller.
16.4.3.17
Related
applications
All
Description
This output gives information about the status of binary input 4 of the
controller.
16.4.3.18
Related
applications
All
Description
This output gives information about the status of binary input 5 of the
controller.
16.4.3.19
Related
applications
All
NT
263
Description
This output gives information about the status of binary input 6 of the
controller.
16.4.3.20
Related
applications
All
Description
This output gives information about the status of binary input 7 of the
controller.
16.4.3.21
Related
applications
All
Description
This output gives information about the status of binary input 8 of the
controller.
16.4.3.22
Related
applications
All
Description
This output gives information about the status of binary input 9 of the
controller.
16.4.3.23
Related
applications
All
Description
This output gives information about the status of binary input 1 of the
extension IOM/PTM module.
NT
264
16.4.3.24
Related
applications
All
Description
This output gives information about the status of binary input 2 of the
extension IOM/PTM module.
16.4.3.25
Related
applications
All
Description
This output gives information about the status of binary input 3 of the
extension IOM/PTM module.
16.4.3.26
Related
applications
All
Description
This output gives information about the status of binary input 4 of the
extension IOM/PTM module.
16.4.3.27
Related
applications
All
Description
This output gives information about the status of binary input 5 of the
extension IOM/PTM module.
NT
265
16.4.3.28
Related
applications
All
Description
This output gives information about the status of binary input 6 of the
extension IOM/PTM module.
16.4.3.29
Related
applications
All
Description
This output gives information about the status of binary input 7 of the
extension IOM/PTM module.
16.4.3.30
Related
applications
All
Description
This output gives information about the status of binary input 8 of the
extension IOM/PTM module.
16.4.3.31
Related
applications
All
Description
This output gives information about the status of binary input 1 of the
extension module.
NT
266
16.4.3.32
Related
applications
All
Description
This output gives information about the status of binary input 2 of the
extension module.
16.4.3.33
Related
applications
All
Description
This output gives information about the status of binary input 3 of the
extension module.
16.4.3.34
Related
applications
All
Description
This output gives information about the status of binary input 4 of the
extension module.
16.4.3.35
Related
applications
All
Description
This output gives information about the status of binary input 5 of the
extension module.
NT
267
16.4.3.36
Related
applications
All
Description
This output gives information about the status of binary input 6 of the
extension module.
16.4.3.37
Related
applications
All
Description
This output gives information about the status of binary input 7 of the
extension module.
16.4.3.38
Related
applications
All
Description
This output gives information about the status of binary input 8 of the
extension module.
16.4.3.39
Related
applications
All
Description
The output is closed when there is the yellow alarm from the analog input 1 of
the controller present in the alarmlist.
16.4.3.40
Related
applications
All
Description
The output is closed when there is the yellow alarm from the analog input 2 of
the controller present in the alarmlist.
NT
268
16.4.3.41
Related
applications
All
Description
The output is closed when there is the yellow alarm from the analog input 3 of
the controller present in the alarmlist.
16.4.3.42
Related
applications
All
Description
The output is closed when there is the red alarm from the analog input 1 of
the controller present in the alarmlist.
16.4.3.43
Related
applications
All
Description
The output is closed when there is the red alarm from the analog input 2 of
the controller present in the alarmlist.
16.4.3.44
Related
applications
All
Description
The output is closed when there is the red alarm from the analog input 3 of
the controller present in the alarmlist.
16.4.3.45
Related
applications
All
Description
The output is closed when there is the yellow alarm from the analog input 1 of
the extension IOM/PTM module present in the alarmlist.
16.4.3.46
Related
applications
All
Description
The output is closed when there is the yellow alarm from the analog input 2 of
the extension IOM/PTM module present in the alarmlist.
16.4.3.47
Related
applications
All
Description
The output is closed when there is the yellow alarm from the analog input 3 of
the extension IOM/PTM module present in the alarmlist.
NT
269
16.4.3.48
Related
applications
All
Description
The output is closed when there is the yellow alarm from the analog input 4 of
the extension IOM/PTM module present in the alarmlist.
16.4.3.49
Related
applications
All
Description
The output is closed when there is the red alarm from the analog input 1 of
the extension IOM/PTM module present in the alarmlist.
16.4.3.50
Related
applications
All
Description
The output is closed when there is the red alarm from the analog input 2 of
the extension IOM/PTM module present in the alarmlist.
16.4.3.51
Related
applications
All
Description
The output is closed when there is the red alarm from the analog input 3 of
the extension IOM/PTM module present in the alarmlist.
16.4.3.52
Related
applications
All
Description
The output is closed when there is the red alarm from the analog input 4 of
the extension IOM/PTM module present in the alarmlist.
16.4.3.53
Related
applications
All
Description
The output is closed when there is any warning type alarm present in the
alarmlist.
16.4.3.54
Related
applications
All
Description
The output is closed when there is any shutdown type alarm present in the
alarmlist.
NT
270
16.4.3.55
Related
applications
All
Description
The output is closed when there is any slow stop type alarm present in the
alarmlist.
16.4.3.56
Related
applications
All
Description
The output is closed when there is any BOC type alarm present in the
alarmlist.
16.4.3.57
Related
applications
All
Description
The output is closed when there is any sensor fail alarm present in the
alarmlist.
16.4.3.58
Related
applications
All
Description
This output gives the information about the status of the excitation loss
protection. It is active when the generator Excitation Loss alarm is present in
the alarm list.
16.4.4
MINT specific
16.4.4.1
Related
applications
MINT
Description
This output is active when the bus voltage and frequency are within limits. It
is deactivated with an appropriate delay after the voltage/frequency has got
out of limits. The limits for under/overvoltage and under/overfrequency as well
as appropriate delays are the same as for generator voltage/frequency and
can be found in the Gener protect setpoint group.
16.4.4.2
Related
applications
MINT
Description
This output is closed if the gen-set group is able to take the current load and
keep the reserve greater than the currently selected reserve for start. This
output should be normally closed while the group works in automatic power
management mode. If the output is open, it means the whole gen-set group is
overloaded. It will open i.e. if a red alarm occurs on one gen-set and there is
no other gen-set available to start instead of the stopped one.
NT
271
NOTE:
This output does not provide information that the reserve is already reached.
It only gives information that there is enough capacity within the gen-set
group to reach the reserve.
16.4.4.3
Related
applications
MINT
Description
The output is closed while the Actual Reserve is greater than the currently
selected reserve for start.
16.4.4.4
Related
applications
MINT
Description
The output is activated by the master controller for 100 ms pulse when the
priority of two gen-sets was swapped by the Running Hours Equalization
function (setpoint #RunHrsMaxDiff).
16.4.5
SPtM specific
16.4.5.1
Related
applications
SPtM
Description
16.4.5.2
Related
applications
SPtM
Description
This output is to be used for control of the ON coil of the mains circuit
breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
16.4.5.3
Related
applications
SPtM
Description
This output is to be used for control of the OFF coil of the mains circuit
breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
NT
272
16.4.5.4
Related
applications
SPtM
Description
This output is to be used for control of the undervoltage coil of the mains
circuit breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
16.4.5.5
Related
applications
SPtM
Description
The output is closed if the gen-set is ready to start automatically and take the
load if the mains fails, i.e.:
16.4.5.6
Related
applications
SPtM
Description
This output is active while mains failure is not detected, i.e. the mains are
healthy.
16.4.5.7
Related
applications
SPtM
Description
16.4.5.8
Related
applications
All
Description
Alarm type
Shutdown
Related
applications
All
Description
Use red emergency button placed on the switchboard door and connect it to
a binary input of the controller. Then configure the function Emergency Stop
NT
273
16.5.1.2
Alarm type
Shutdown
Related
applications
All
Description
This alarm occurs immediately when the engine speed has exceeded the limit
adjusted by the setpoint Overspeed Sd. There is no delay for this alarm. See
chapter Speed sensing to learn more about methods of speed measurement.
16.5.1.3
Alarm type
Shutdown
Related
applications
All
Description
This alarm will be issued when the gen-set is running and then stops by itself,
i.e. the RPM drops under the value of setpoint Starting RPM.
The underspeed alarm starts to be evaluated 5 after successful gen-set start
and is being evaluated for the entire time that the fuel solenoid is on.
16.5.1.4
Alarm type
Shutdown
Related
applications
All
Description
This alarm will be issued after all attempts to start the gen-set (setpoint Crank
Attempts) have run out but the gen-set did not start. See also Engine start
chapter.
NOTE:
The gen-set cannot be started again until this alarm is reset.
NT
274
16.5.1.5
Stop fail
Alarm
evaluated
Related
All
applications
Description This alarm occurs if the gen-set shall be stopped, but some symptom indicates that it is
not stopped. The period when the gen-set shall be stopped begins after the fuel has
been switched off and time delay Stop time has elapsed and lasts for the entire time the
fuel resp. starter motor are off.
ENGINE STOP
ENGINE START
STARTER
FUEL SOLENOID
Stop time
See the chapter Cool down and stop to learn more about symptoms that are taken into
account for the evaluation of stopped engine.
NOTE:
The gen-set cannot be started until this alarm is inactive and reset.
16.5.1.6
Alarm type
Warning
During cranking
Related
applications
All
Description
The alarm is issued if the engine speed has not exceeded the Starting RPM
within the MaxCrank Time, although some of additional running engine
indication sources indicate that the engine has started.
NT
275
16.5.1.7
Alarm type
BOC
Related
applications
All
Description
This alarm will occur when the GCB feedback input does not match the
expected position given by the GCB Close/Open output. It stays active until
the mismatch between the output and feedback persists.
16.5.1.8
Alarm type
Warning
Related
applications
SPtM
Description
This alarm will occur when the MCB feedback input does not match the
expected position given by the MCB Close/Open output. It stays active until
the mismatch between the output and feedback disappears.
NT
276
16.5.1.9
Alarm type
Related
applications
All
Description
16.5.1.10
Alarm type
Warning
Related
applications
SPtM
Description
16.5.1.11
Alarm type
Related
applications
All
Description
The alarm is issued when the gen-set power is over the limit for time period
longer than the delay.
NT
277
16.5.1.12
Alarm type
Related
applications
All
Description
This alarm protects the gen-set running parallel to mains or other gen-sets
against the situation, when the engine loses power and becomes to be driven
by the generator acting as an electric motor supplied from the mains or other
gen-sets.
The following setpoints are related to this alarm:
16.5.1.13
Alarm type
Related
applications
All
Description
This alarm evaluates the generator phase voltage in all three phases. The
following setpoints are related to it:
NOTE:
The generator voltage must be within limits to enable closing of GCB or
starting of synchronization.
16.5.1.14
Alarm type
Related
applications
All
Description
This alarm evaluates the unbalance of the phase voltages, i.e. difference
between highest and lowest phase voltage at any given time. The following
setpoints are related to it:
NT
278
16.5.1.15
Alarm type
Related
applications
All
Description
This alarm evaluates the generator frequency in the phase L3. The following
setpoints are related to it:
NOTE:
The generator voltage must be within limits to enable closing of GCB or
starting of synchronization.
16.5.1.16
Alarm type
Related
applications
All
Description
NT
279
Multiple of base
Reaction time
level
1,1
1,2
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
50,0
25,0
16,7
12,5
10,0
8,3
7,1
6,3
5,6
5,0
2,1
2,2
2,3
2,4
2,5
2,6
2,7
2,8
2,9
3,0
4,5
4,2
3,8
3,6
3,3
3,1
2,9
2,8
2,6
2,5
REACTION TIME =
2NOM_DEL * BASE
ACTUAL - BASE
1,0
50,0
40,0
30,0
20,0
10,0
0,0
1,0
1,5
2,0
2,5
3,0
16.5.1.17
Alarm type
Related
applications
All
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
16.5.1.18
Alarm type
Related
applications
All
Description
This alarm evaluates the unbalance of the phase currents, i.e. the difference
between highest and lowest phase current at any given time. The following
setpoints are related to it:
NT
280
16.5.1.19
Alarm type
Warning
Related
applications
All
Description
16.5.1.20
Alarm type
Warning
Related
applications
All
Description
16.5.1.21
Alarm type
Warning
Related
applications
All
Description
This alarm is issued if the engine is running and the voltage on the D+
terminal is lower than 80% of the controller supply voltage. This alarm works
similar to the red battery alarm indicator on a vehicle dashboard.
The setpoint D+ Function has to be in CHRGFAIL or ENABLED position to
enable this alarm.
NT
281
16.5.1.22
Alarm type
Warning
Related
applications
All
Description
This alarm informs the operator that the controller supply voltage is too low or
too high. The following setpoints are related to it:
16.5.1.23
Alarm type
Warning
Related
applications
All
Description
This alarm will be issued if the governor output has 0V or 10V for more than
2. This situation can occur, for example, if the Speed Gov Char setpoint is in
the wrong position or if the connection of the governor output to the governor
is not correct.
16.5.1.24
Alarm type
Warning
Related
applications
All
Description
This alarm will be issued if the governor output has 0% or 100% for more
than 2 . This situation can occur, for example, if the connection of the AVRi
output to the AVR is not correct.
16.5.1.25
Alarm type
Shutdown
During cranking
Related
applications
All
Description
This alarm will be issued if the controller was reset during cranking of the
gen-set. If this situation occurs, the controller supposes the starting battery is
so exhausted that its voltage drops so low when starter motor is energized
that it causes controller reset.
NT
282
16.5.1.26
Alarm type
Shutdown
Related
applications
All
Description
This alarm indicates that the internal backup battery needs to be replaced.
16.5.1.27
Alarm type
Warning
Related
applications
All
Description
This alarm indicates that the fuel level is lower than the set yellow alarm of
relevant AI (Fuel Level).
16.5.1.28
Alarm type
Related
applications
All
Description
This alarm indicates that the fuel level is lower than the set red alarm of
relevant AI (Fuel Level).
16.5.1.29
Alarm type
Warning
Related
applications
All
Description
This alarm indicates that the water temperature is higher than the set yellow
alarm of relevant AI (Water Temp).
NT
283
16.5.1.30
Alarm type
Shutdown
Related
applications
All
Description
This alarm indicates that the water temperature is higher than the set red
alarm of relevant AI (Water Temp).
16.5.1.31
Alarm type
Warning
Related
applications
All
Description
This alarm indicates that the oil pressure is lower than the set yellow alarm of
relevant AI (Oil Press).
16.5.1.32
Alarm type
Shutdown
Related
applications
All
Description
This alarm indicates that the oil pressure is lower than the set red alarm of
relevant AI (Oil Press).
16.5.1.33
Alarm type
Warning/Shutdown
Related
applications
All
Description
Engine stop fail indication. Stop fail means that the engine does not reach
still engine state within Engine params: Stop time.
NOTE:
Still engine conditions:
Engine speed (RPM) = 0 and
AI: Oil press < Starting POil and
D+ terminal is not active and
BI: RunIndication 1 and 2 and 3 are not active and
Generator voltage < 15 V (in all phases) and
Generator frequency = 0 Hz
NT
284
If all these conditions are fulfilled, additional 2 delays are used to confirm still
engine state.
16.5.1.34
Alarm type
Warning
Related
applications
MINT
Description
The Bus Measure Error is detected in MINT application when the voltage on
the controllers bus terminals is out of limits 20 after:
a) GCB (own) was closed in MAN or AUT mode
b) MCB (feedback) was closed in AUT mode
c) Any other GCB in power management group (on CAN bus)
was closed.
The alarm is activated after 20 s. However, the GCB (own) closing is blocked
immediately for safety reasons.
This protection can avoid e.g. potential direct closing of GCB while the
controllers bus conductors are unintentionally unplugged from the terminals.
16.5.1.35
Alarm type
Related
applications
All
Description
16.5.1.36
Alarm type
Warning
Related
applications
All
Description
This alarm occurs when the fuel level value measured at relevant AI (Fuel
Level) drops faster than is the limit adjusted by setpoint MaxFuelDrop.
16.5.1.37
Alarm type
Shutdown
Related
applications
All
NT
285
This alarm indicates that the value of earth current EarthFaultCurr is higher
than the setpoint EarthFault Sd and EarthFaulth Del delay has elapsed. The
alarm activates binary output AL Earth Fault.
Description
16.5.1.38
Alarm type
Related
applications
All
Description
16.5.1.39
Alarm: Override
Alarm type
Shutdown
Related
applications
All
Description
16.5.1.40
Alarm type
Shutdown
Related
applications
All
Description
16.5.1.41
Alarm: RA Fail
Alarm type
Warning
Related
applications
All
Description
16.5.1.42
Alarm type
Warning
NT
286
Alarm evaluated
Related
applications
MINT
Description
This alarm occurs when at least two or more controllers in MINT have a
different power decimals setting.
16.5.1.43
Alarm type
Warning
Related
applications
All
Description
16.5.1.44
Alarm type
Warning
Related
applications
All
Description
This alarm occurs when an ECU is configured, but the communication with
the ECU is not established or has dropped out.
16.5.1.45
Alarm type
Warning
Related
applications
All
Description
Indication of unsuccessful active call 1-3. See Inteli Communication Guide for
information about active calls and SMS/E-mail group of setpoints for setting.
NT
287