Npower Catalogo
Npower Catalogo
Npower Catalogo
Todays business processes cannot be interrupted. Businesses are buying and selling around the world, around the clock, every day. Even 40-hours-per-week operations need the reliability and maintainability of true 24x7 infrastructure during those 40 hours. Thats why the cornerstone of your infrastructure should be the most reliable and advanced 3-phase UPS in its power range: the Liebert Npower.
Reliability Comes First
Reliability is a Liebert family tradition. All Liebert threephase UPS products use double-conversion technology and all have field-proven critical bus Mean Time Before Failure (MTBF) in excess of one million hours.
Surges Frequency Variations Input Faults Waveform Distortions CommonMode Noise Sags
100% Effectiveness
Spikes Outages
The Liebert Npower has truly spectacular operating performance, unmatched by any UPS in the industry. The all-digital ActiveStar controls are DSP-based and feature unique, patent-pending technology. The Npower makes fast adjustments to changing loads, including subcycle pulse-width corrections to keep the output voltage waveform nearly flawless. Output voltage distortion (THD) typically measures less than 2.5%, under worst-case high-crest-factor, non-linear loads. The Npower is rugged enough to handle load branch faults, input faults, 100% step loads, PDU startup inrush and motor-load startup.
Output Voltage
The combination of rugged inverter and continuous-rated static switch gives the Liebert Npower exceptional overload
225
capability. By itself, the Npower inverter can supply up to 200% of rated capacity for 10 cycles and 150% for a full minute
%Load
200
Static Switch
175 150
while maintaining a true sinusoidal waveform to the load. It can also handle up to 125% of rated capacity for ten minutes. Even during bolted faults, the ActiveStar controls are able to limit inverter output current to safe levels.
Inverter
125
110 % Load
100 10 cycles 5 sec 1 min. 10 min. 100 min.
Time The internal static switch has two operating modes. For faults or transformer inrush currents, the static switch operates in the pulsed-parallel mode: the inverter remains connected while the static switch supplements inverter current with power from the bypass source. If the load continues to exceed the overload rating of the inverter, the static switch operates in the continuous-duty mode. When Npower is used in the 1+1 Redundant configuration, the full overload capacity of both modules is available to source fault current or handle momentary overloads. The inverters and static bypass switches work in parallel to support the critical load. Total power available will be limited by the rating and settings of the system output breaker in the Paralleling Cabinet. This breaker is typically set for the output rating of a single Npower module.
1100 600
Time
The overload curves above tell a remarkable story. The upper curve represents inverter capability as a function of overload versus time. The inverter remains on-line providing regulated power output at full voltage at every point of the overload/time curve. The lower curve represents the capabilities of the internal static switch. If the load moves beyond the line representing inverter capacity, the static switch will support the load to the full extent of its capacity. The static switch has truly exceptional fault-clearing capacity, as shown in the second chart above. All Liebert Npower models have static switches rated for 6000 amps for the first half cycle, 3000 amps for 10 cycles, 1100 amps for one second and 600 amps for 5 seconds.
ActiveStar is a DSP-based control system that makes the UPS behave like a model citizen. ActiveStar controls the entire power train, including the Rectifier, DC Bus, Inverter and Static Switch. This makes the Liebert Npower very aware of its environment, and able to make intelligent adjustments.
Input Inductor
Utility Input
Npower Rectifier
number of short-duration battery "hits," which can greatly reduce battery life expectancy. In addition, the Npower can schedule regular battery self-test procedures, to verify that the battery string is capable of supporting the connected load. The internal battery cycle monitor records the duration, kW and battery end voltage for every battery discharge event. This enables you to evaluate battery
performance and see how hard your batteries are working in this application. The ActiveStar controls also optimize battery performance during longer discharge periods. During longer battery discharge events, the Npower gradually increases the low-battery shutdown voltage. This prevents the batteries from being discharged too deeply, and incrementally improves battery service life.
PWM Pulses
Inverter
The ActiveStar inverter controls have three elements, Voltage Harmonic Control, Sliding Mode Inverter Current Control, and Space-Vector PWM Inverter. Voltage Harmonic Control compares the actual UPS output voltage to a 60Hz reference signal. It senses the content of load-generated harmonics and components introduced by unbalanced loads, and computes the compensating signals necessary to eliminate them. The Stabilizer then computes the amount of current necessary to force the voltage error to zero and ensure system stability. Details of Fast Automatic Harmonic Voltage Control
The Sliding-Mode Current Control takes the output from the Stabilizer and determines the driving voltage necessary to make inverter currents follow what the voltage control desires. The Current Control corrects errors between desired and actual current in a single PWM pulse. On a bolted fault, this allows the inverter to limit its current at a safe level, rather than requiring immediate shutdown when bypass is not available. ActiveStar compensates once per PWM pulse (50 times per line cycle) compared to older UPS technology, which limits currents by gradually reducing its 60 Hz voltage reference once per line cycle (1/60 sec.). ActiveStar constantly monitors the harmonics being reflected by the customers load equipment, and cancels them electronically. The inverter sources (compensates for) the harmonics as it sends pulses through the output isolation transformer. As a result, the output transformer never directly experiences the harmonics, and runs cooler and quieter.
Voltage Error
The Liebert Npower gives you more UPS for about the same initial cost as lesser products. Furthermore, the Npower will usually cost significantly less over the lifetime of the product. The value comes from several elements: exceptional protection, higher efficiency, lower installation, maintenance and operating costs, smaller total system footprint and more standard features.
Higher Efficiency in Real-World Applications
Critical applications require a UPS to have an input filter (to reduce input current distortion) and an output isolation transformer (to isolate your critical load), while powering non-linear (high-crest-factor) loads at less than the rated capacity of the UPS. The fully equipped Liebert Npower has excellent efficiency typically between 92% and 93.5% while powering high-crest-factor loads between 50 and 100% of its rated capacity. Furthermore, the input power factor is exceptionally high, typically 0.95 to 0.96 for models with 480 VAC input. In this power range (up to 130 kVA), the only way to exceed 93.5% efficiency is to leave out something important. Some competitors omit the output isolation transformer; others put your critical load at risk with their single-conversion UPS products. Only you can decide if the claimed savings justify the risk.
High-Availability Configurations
The Liebert Npower UPS can be used reliably as a single module and in various redundant configurations. The Npower 1+1 Redundant option, described on pages 10-11 of this brochure, is a cost-effective parallel-redundant system. Parallel redundancy improves maintainability and fault tolerance, thereby enhancing system availability. For the ultimate in high-availability systems, Npower can be applied in various distributed-redundant (dual-bus) configurations, using Lieberts unique Load Bus Sync option. Both Load Bus Sync and 1+1 Redundant configurations can be factory-installed or retrofitted to existing Npower installations.
The Liebert Npower can be as simple or complete as you need it to be. With matching battery cabinets, maintenance bypass cabinets, Slim-Line power distribution cabinets and Paralleling Cabinets, the Npower can be a bolt-together system.
All bolt-on cabinets have casters and leveling feet, to simplify installation. Furthermore, power cables and control wiring harnesses between cabinets are included for all cabinets (except Paralleling Cabinets), saving time and cost.
130 kVA
130 kVA
130 kVA
80 kVA
50 kVA
80 kVA
50 kVA
80 kVA
50 kVA
80 kVA
5 0
Liebert Npower
Brand M
Brand P
Brand A
50 kVA
One-Line Diagram
Single-Input with delta-wye output
Y
UPS Input Rectifier
Inverter
Critical Load
Battery Cabinet
Specific Configurations
Y
Load
Y
Static Switch Input Module
Y
Load
This configuration is for applications with 480 VAC input and 480 VAC output, and there are no line-to-neutral loads. The UPS provides isolation on both the inverter and the bypass circuit. This configuration has the neutral-to-ground bond at the UPS module. The input and output are both 3-wire plus ground. The output is in phase with the input.
Y
Load
Y
Bypass Input Static Switch Module
Y
Load
The Liebert Npower 1+1 Redundant system is an elegantly simple way to create a parallel-redundant UPS without the cost or complexity of external system controls. Adding a redundant UPS module to a single-module system improves maintainability, because the second module can support the load while the first is being serviced. A redundant module also improves fault tolerance, because a single failure will still leave an intact UPS to support the critical load.
Liebert has nearly 30 years of experience building multi-module UPS systems, but the majority of these systems have system-level controls. These controls are necessary for large-scale power systems, but are less important for smaller systems. The Liebert Npower 1+1 Redundant system strikes a good balance between the simplicity of a single module and the performance of a multi-module system.
No System-Level Controls
All control logic is contained within the individual modules. Unlike conventional multi-module systems, there is no system-level LCD panel or static bypass switch. The module-level static bypass switches work in coordination to provide exceptional overload protection, plus seamless transfers between bypass and online operating modes. Furthermore, the traditional system control cabinet is replaced by a simple paralleling cabinet. Normal operations can be handled efficiently at the individual module control panels.
Bypass Input
Paralleling Cabinet
10
In summary, Liebert system designers chose the performance advantages of a wired paralleling system, but the wires were not permitted to become a failure mode.
New or Retrofit
All configurations of Liebert Npower modules can be used in 1+1 Redundant systems. New systems can be ordered with all the components included. Installed systems can be retrofitted with a simple kit.
11
Liebert has built advanced monitoring and communications capabilities into the Liebert Npower UPS system. Liebert monitoring and control products allow you to take full advantage of these features. You will find a full range of monitoring and control systems, communications modules and other equipment designed to interface with a variety of communication protocols, operating platforms and building management systems. Knowing what is happening with your power equipment, so you can keep it at peak operating efficiency, is vital to system reliability.
Important facility operational and status information needs to be communicated by different means with varying levels of importance. This is why Liebert gives you so many ways to supervise your enterprise:
IT Manager
Single Phase Uninterruptible Power System Three Phase Uninterruptible Power System Power Management Nform
Network
Data Center
Nform
Facility
Enterprise
Liebert SiteScan Web Enterprise Monitoring Systems Liebert SiteScan Web is a comprehensive critical systems monitoring solution dedicated to ensuring reliability through graphics, event management and data extrapolation. The standard Web interface allows users easy access from anywhere at anytime. I Single and multi-site applications. I Event management and unit control. I Trend and historical data captures and reporting. I Full ASHRAE BACnet compatibility. I Java based. I Windows 2000 and XP compatible.
Network-Based Monitoring Systems The Nform family of monitoring software and communications hardware solutions combines the coverage of facility monitoring with the efficiency of a network-based system. They provide a cost-effective, centralized monitoring solution flexible enough to support your critical system configurations while utilizing your existing distributed infrastructure. Stand-Alone Monitoring Solutions UPS shutdown software, as well as autonomous microprocessor controlled modules, are available to provide supervision, control and remote alarm notification for Liebert power equipment.
MultiLink Automated Shutdown Software MultiLink will monitor UPS status and perform user-specified actions to execute notifications and provide automated, unattended system shutdown to protect critical data during extended power outages. Universal Monitor All-purpose microprocessor-based alarm and notification unit that allows a variety of Liebert equipment to be monitored and controlled both remotely and locally from a single point.
12
Enterprise-Wide Support
We can monitor all your critical support equipmentregardless of manufacturer or location.
Industry-Leading Service
The service business of Emerson Network Power is the largest service organization in the world dedicated to maximizing availability of infrastructure required for mission-critical systems. We offer: I Global service with over 2000 certified OEM engineers / technicians I 2-hour mean time to respond I Web-based monitoring and reporting I 24x7 Customer Response Center I Global multi-tiered new parts availability
Well manage alarm activity based on a pre-defined set of escalation procedures. Our specialists review all alarm activity from your enterprise and evaluate them as an integrated system. And, our 24x7 Customer Response Center is ready to respond to any alarm precisely when it occurs.
Predictive Maintenance
Our High Availability Response Center polls your equipment on regular intervals. Our certified engineers analyze the trended data points over time to reveal maintenance that could be requiredidentifying issues before they become problems.
13
General Specifications
Specifications
UPS Rating kVA 30 40 50 65 80 100 130
1 2 3
Battery Nominal (VDC) 480 480 480 480 480 480 480
Maximum Heat Dissipation At Full Load (BTU/Hr)1 8,500 11,000 14,000 18,000 22,000 26,000 33,000 Inches
Approximate Weight3 Pounds 2,200 2,200 2,200 2,700 2,700 3,800 3,800 KG 1,000 1,000 1,000 1,225 1,225 1,725 1,725
kW 24 32 40 52 64 80 104
Heat dissipation figures are for worst-case configurations (including 208 VAC, input and output), supporting 100% load at rated power factor. Dimensions and weights do not include battery or maintenance bypass cabinets. Weights are for heaviest models, with 208 VAC input.
14
Input
Voltage: 208, 220, 240, 480 or 600 VAC, 60 Hz. 3-phase, 3-or 4-wire plus ground Voltage Range: +10, -15% (no battery discharge at -20%) Frequency Range: 60 Hz, 5 Hz Current Distortion: 10% maximum reflected THD at full load with optional input filter. 30% THD without filter. Current Limit: 115% of full load input current Current Walk-in: 20 seconds to full load. Power Factor: Up to 0.96 lagging at full load with optional input filter. 0.80 lagging minimum at full load without optional input filter. Surge Protection: Sustains input surges without damage, per criteria listed in ANSI C62.41-1980, A & B (IEEE 587).
Standard Features
Like other Liebert UPS products, the Liebert Npower includes some features that are options (or not available) for some competitors: I True double-conversion topology, for protection against 100% of power \disturbances. I Internal bypass switch enables you to isolate the UPS for maintenance. I Continuous-duty static switch performs in pulsed-parallel mode for supplying fault current and momentary overloads, and can operate continuously for longerduration events. I Internal output isolation transformer protects your critical load from \common-mode noise and harmful DC offsets. In some configurations, it \provides a separately derived source, to support 4-wire loads without having to pull a neutral line from the \service entrance. I Automatic input filter disconnect isolates the input filter capacitors at light loads to avoid presenting a leading power factor to the utility or backup generator. I Backlit LCD graphic display enables easy navigation between the graphic mimic screen and the menu screens. I Event Log can display up to 512 time-and-date-stamped alarm events. I Battery self-test helps verify the batterys readiness to carry the critical load. I Battery temperature-compensated charging prevents overcharging in high ambient operating temperature or undercharging in cold weather.
I
Output
Voltage: 208, 220, 240, 480 or 600 VAC, 60 Hz, 3-phase, 4-wire plus ground. Voltage Adjustment Range: 5%. Voltage Regulation: 0.5% for balanced load 1.0% for 100% unbalanced load. Dynamic Regulation: 2.5% deviation for 100% load step. 1% for loss or return of AC input. Transient Response Time: Recover to steady state within 1 cycle. Voltage Distortion: For linear loads, 1% THD. Less than 2.5% THD for 100% nonlinear loads (3:1 crest factor) without kVA/kW derating. Phasing Balance: 120 0.5 for balanced load. 120 1 for 100% unbalanced load. Frequency Regulation: 0.1%. Load Power Factor Range: 1.0 to 0.7 lagging without derating. Overload: 125% of full load for ten minutes. 150% for one minute with true sinusoidal waveform.
Battery Cycle Monitor records up to 132 battery discharge events. Battery Time Remaining feature displays backup time remaining at present connected load. On-generator battery charge limit reduces recharge current until the utility AC power is restored. Front-panel control of all configuration and fieldadjustment options simplify installation and maintenance. Top-and-bottom cable entry gives the installer more options for equipment location. Two-hole bus bar landing space and accessible terminal blocks for options can simplify installation. Casters under the unit are helpful when a forklift is not readily available. One-button startup for simpler operation. Matching valve-regulated lead-acid battery packs Matching maintenance bypass cabinet Matching bolt-on power distribution unit, with one or two 42-pole panels Input filter/power factor correction Internally mounted input isolation transformer Load Bus Sync Systems 1+1 Redundant Systems Flooded rack-mounted battery systems SNMP, SiteScan and other communications interfaces: Remote monitor panel Alarm status contacts Customer alarm inputs
Environmental
Operating Temperature: 0 to 40C (UPS), 20 to 30C (battery) Non-Operating Temperature: -20C to 70C. Relative Humidity: 0-95% non-condensing Operating Altitude: Up to 6,600 feet (2000 meters) without derating. Acoustical Noise: Less than 65 dBA typical, measured 1 meter from the unit.
I I I
Standards
ETL Listed to UL 1778 and UL 924 UPS standards, and CSA certified. Meets current requirements for safe high-performance UPS operation.
I I I
15
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies including Liebert power and cooling technologies that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility, and reduced capital equipment and operating costs.
Liebert Corporation
1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800 877 9222 Phone (U.S. & Canada Only) 614 888 0246 Phone (Outside U.S.) 614 841 6022 FAX Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX Emerson Network Power Asia Pacific 7/F., Dah Sing Financial Centre 108 Gloucester Rd, Wanchai Hong Kong 852 25722201 Phone 852 28029250 FAX
SL-24529 (R11/06)
Printed in USA
Emerson Network Power. The global leader in enabling Business-Critical Continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling
EmersonNetworkPower.com
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2005 Emerson Electric Co.