Dated: 10/11/2012 Page: 1 / 7 Customer: Contact: Your reference: Skyshot CS Your contact: Andrew Kietzmann Phone: 011 792 3968 Fax: 011 792 3969 E-mail: andrew@skyshot.co.za

Air-cooled packaged water chiller with screw compressor for outdoor installation POWERCIAT LXC 3600X HPS R134a
Compact and attractive unit with hydraulic equipment designed for air conditioning and industrial cooling process applications and easy to install on site User-friendly microprocessor control. Numerous of remote remote possibilities of communication As per technical brochure N CAT Refrigerant / kg : Number of refrigeration circuits Power control : continuous Starting mode : Gross cooling capacity Net cooling capacity Fluid Inlet/outlet temperature Flow rate System available pressure Net EER (EN 14511) Net ESEER (EN 14511) Air inlet temperature Fan rotation speed Air flow Number of fans Unitary motor power : : : : : : : : : : : : : R134a / 120+119 : 2 25-100% Star-Delta 842.6 kW 838.4 kW Water 12.3 C/ 6.0 C 32.0 l/s 157.3 kPa 3.00 3.45 35.0 C 905 rpm 82.0 m3/s 14 2.24 kW

Gross power input : 286.6 kW Net power input : 279.8 kW Electrical supply : Three-phase, 400 V, 50 Hz Intensity for selection of the electric cable : 607.1 A Starting current : 638.0 A

U:\Public\Quotes\2012 Quotes\Q2957 ABSA Project xXx\Airgro New Chiller\Building A+J Cooling Only.MFR - W - 385 LSTFRDW V 02.21.12 E 02/2012

References:
Dated: 10/11/2012 Page: 2 / 7

Net performance at partial load operation under standard Eurovent/EN 14511 conditions EER 100% EER 75% EER 50% EER 25% ESEER 3.00 3.32 3.60 3.41 3.45 DIMENSIONS AND WEIGHT Length : 9 653 mm Width : 2 200 mm Height : 2 260 mm Weight (empty) : 9 035 kg Weight (in operation): 9 280 kg Weight varies with the options chosen (given at +/- 10%). SOUND POWER LEVEL (Lw) Sound power level spectrum (dB Lin) 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 81 94 97 94 94 87 79 Sound power reference as per ISO 3744: 10E-12 W, tolerance +/-3 dB.

Lw Global sound level 97 dB(A)

SOUND PRESSURE LEVEL (Lp) (*) Sound pressure level spectrum (dB Lin) Lp Global sound level 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 48 61 64 61 61 54 46 64 dB(A) Sound pressure level: reference 2 * 10E-5 Pa, tolerance +/-3 dB. * 10E-5 Pa. Calculated according to Lp = Lw - 10 x log S (*) (at 10 m, at 1,5 m from the ground, in free field directivity 2). Sound pressure levels depend on installation conditions and are given for information only. We remind you that only sound power levels are certified and reliable values.

Description

Quantity

Price per unit Without taxes EUR

POWERCIAT LXC 3600X HPS R134a Variable speed drive for fan Anti-vibration mounts kit Skids for container handling Twin pump No. 211

1 1 1 1 1 INCLUDED INCLUDED INCLUDED INCLUDED

As per our general sales conditions in your possession. Validity of prices: 1 month. As part of our policy of continual improvement, we reserve the right to make any technical modifications we feel necessary without prior notice.

- BASIC EQUIPMENT INCLUDED: All-season operation (-15 C with optional compresso r noise insulation; -5 C without) Water flow controller Main disconnect switch Hours run Pressure sensors
U:\Public\Quotes\2012 Quotes\Q2957 ABSA Project xXx\Airgro New Chiller\Building A+J Cooling Only.MFR - W - 385 LSTFRDW V 02.21.12 E 02/2012

References:
Dated: 10/11/2012 Page: 3 / 7

RS485 output- Open Modbus/Jbus communication protocol Numbered wires and labelled electrical components Phase controller (reversal, loss, asymmetry, over and under voltage) We also offer maintenance contractsmaintenance contracts for all our units. To ensure proper operation of the unit, the system must have a capacity of at least 2963 l. The minimum water volume calculation is provided for nominal Eurovent conditions in cooling mode only. This value is applicable in most air conditioning applications (unit with fan coil units) Comment: The buffer tank must be fitted on systems operating with a small volume of water (unit with air handling unit) or in the case of industrial processes. In the case of heat pump applications, we recommend using a buffer tank to maintain a stable temperature during the defrost cycles. Install a control device between the unit and the circulation pump The evaporator water flow rate must be between 80 and 231 m3/h

U:\Public\Quotes\2012 Quotes\Q2957 ABSA Project xXx\Airgro New Chiller\Building A+J Cooling Only.MFR - W - 385 LSTFRDW V 02.21.12 E 02/2012

References:
Dated: 10/11/2012 Page: 4 / 7

TECHNICAL DESCRIPTION POWERCIAT LXC 3600X HPS R134a The unit meets the following directives: Machinery (2006/42/EC) EMC (92/31/EEC - 93/68/EEC) amended by 2004/108/EC Low voltage (93/68/EC) amended by 2006/95/EC PED 97/23/EC : Category IV The unit meets the following standards: EN 60-204 - EN 378-2 - 2 REFRIGERANT CIRCUIT(S) - 2 SEMI-HERMETIC TWIN-SCREW COMPRESSORS continuous capacity control including the following equipment: 2 spindles (2900 rpm) mounted on ball and roller bearings Built-in two-pole motor cooled by suction gases Full electronic protection of motor - Direction of rotation check Lubrication under controlled differential pressure Crankcase heater Built-in intake filter Valve prevents the compressor running in reverse when the unit stops Bypass valve to protect against potential overpressure Maximum discharge water-temperature control Oil pressure control Built-in three-stage oil separator Low vibrations and noise level Simple and rugged construction Compressors mounted on antivibration mounts Part-winding start for reduced inrush currents Option for compressor noise insulation - 1 SHELL AND TUBE EVAPORATORS Total water capacity 180 l Shell and tube direct-expans High-efficiency copper tube bundle Steel tubeshee Corrosion-resistant baffles Thermal insulation VICTAULIC connection Fouling factor: 0.00005 m2 C/W - HPS (High Power System) 2 brazed plate exchangers System that makes it possible tothe unit's cooling capacity andcoefficients of performance(EERCOP). H.P.S equipment allows to do energy savings - 1 AIR-COOLED CONDENSERS Coil with copper tubes and high-efficiency aluminium fins Direct-drive propeller fans Optimised airfoil blades - Diameter:800 mm
U:\Public\Quotes\2012 Quotes\Q2957 ABSA Project xXx\Airgro New Chiller\Building A+J Cooling Only.MFR - W - 385 LSTFRDW V 02.21.12 E 02/2012

References:
Dated: 10/11/2012 Page: 5 / 7

Sealed motors (IP54)

- HYDRAULIC EQUIPMENT including : It is necessary to check that the water capacity of the installation is sufficient for a right operation of the unit 1 Single-stage hydraulic centrifugal pump(s) with pressure gauges Fluid to be cooled : Water Flow : 32.0 l/s Max. available pressure: 157.3 kPa Pump power : 11.0 kW 1 expansion vessel capacity 80 Litres 1 expansion vessel capacity 80 Litres 1 automatic and manual air vent 1 draining hole with valve 1 safety valve calibrated at 4 bars 2 isolating shut off valves for the pump Nota : Our pumps are designed for operation on closed water lood ( Low NPSH ). For others applications, consult us (open water circuit, high head pressure, etc..)

- ELECTRICAL PANEL (in accordance with NF C 15-100 and EN 60204) Main safety fused disconnect Control transformer Protection of power and control circuits Compressor motor contactor Fan motor contactor Main earth lug Electrical panel with wiring identification Phase controller (reversal, loss, asymmetry, over and under voltage) - INTUITIVE & NETWORKED INTUITIVE, NETWORKED XtraCONNECT2 CONTROLLER AND DISPLAY performs the following functions: All information displayed and directly accessible via a 24 character x 4 line LCD (pressures - temperatures - runtimes - machine parameters) with a history of the 20 most recent faults 3 password-protected access levels Water temperature control (on exchanger return or supply) The setpoint may be adjusted based on the outdoor temperature (energy savings feature). Control of condensing pressure (air-to-water unit only) Dual setpoint switchable by remote control Management of short-cycle protection Compressor runtime balancing and management of number of compressor starts Master/slave con Setpoint adjustments via remote control (4-20 mA signal) Remote control of unit via built-in RS485 output (supplied as standard) possible - Open Modbus/Jbus protocol (LON protocol and TCP Ethernet connection optional)
volt free contacts available for input:

Weekly

- 6 programming stages - 6 holidays zones Automatic operation control for remote On/Off control (pumps and units)

U:\Public\Quotes\2012 Quotes\Q2957 ABSA Project xXx\Airgro New Chiller\Building A+J Cooling Only.MFR - W - 385 LSTFRDW V 02.21.12 E 02/2012

References:
Dated: 10/11/2012 Page: 6 / 7

Compressor load shedding Setting 1/Setting 2 switchover / Heating / Cooling changeover

volr free contacts available for output:

General fault - Fault per circuit Pump control RELAY BOARD option (kit delivered separately) Volt-free contact card: Water flow fault Frost protection fault Pump fault Fan fault (Packaged air unit only) HP high pressure fault LP low pressure fault Compressor safety fault Discharge temperature fault Compressor overheat fault Compressor operation status REMOTE CONTROL option (kit supplied separately) Performs the same functions as those available on the unit console Can be placed at a distance of up to 1000 m Option: MANAGEMENT OF SEVERAL UNITS MULTICONNECT (kit delivered separately) Primary functions: Management of up to 8 units on the same water loop Cooling or heating mode management Chilled water or hot water pump management Safety unit management Load shedding of each unit System time programming Management of ice storage mode Fault management for each unit Runtime balancing for each unit Integrated GTC MODBUS-JBUS connection for viewing each unit's operating status and faults Optional ENERGY METER Energy meter fitted in the machine's electrical cabinet measures the following: Voltage across each phase Total input current Total input power Total electricity consumption The meter also enables the machine's maximum electricity consumption to be kept below a customisable limit - STANDARD ELECTRICAL SUPPLY Three-phase, 400 V, 50 Hz + Earth Voltage tolerance: +/- 10% Machine protection rating: IP44 - STANDARD REFRIGERATION COMPONENTS Filter dryer(s) Sight glass(es) Electronic expansion valve Solenoid valve(s) on liquid line - CONTROL AND SAFETY DEVICES

U:\Public\Quotes\2012 Quotes\Q2957 ABSA Project xXx\Airgro New Chiller\Building A+J Cooling Only.MFR - W - 385 LSTFRDW V 02.21.12 E 02/2012

References:
Dated: 10/11/2012 Page: 7 / 7

HP safety pressure sensor(s) LP safety pressure sensor(s) Evaporator water flow switch Evaporator anti-freeze sensor Chilled water control sensor External sensor temperature Discharge and suction temperature sensors

- UNIT CONSTRUCTION Frame made of metal sheet finished with a protective powder coating (RAL 7035 light grey and RAL 7024 graphite grey) Casing made of metal sheet with a lacquered finish (RAL 7035 light grey and RAL 7024 graphite grey) New, forward-thinking design blends in seamlessly with surroundings Tested and adjusted in the factory. Delivered in running order. Design and manufacture following ISO 9001 certification