Operation manual
1. Mounting site
Instrument transformers of ALCE shall be mounted in accordance with following conditions; a) Ambient temperature: -20C~40C (Avarage temp.: lower than 35C) b) Altitude: lower than 1000 meters. c) At the places not exposed to sea - breeze, rain, snow and sunlight and kept under 90% humidity. d) At places where the exceeded vapor, oil-vapor, explosive flammable gas shall not occur. e) At places not subject to exceeded dust & foreing particles. f) At places where exceeded oscillation and impact shall not occur. d) The connection shall be correctly done as per the terminals marks and connection diagram on the name plate. e) The earthing terminal on primary side of grounding type of instrument transformers shall be absolutely grounded. f) The earthing terminal on secondary side and the mounted base (flame) on the body shall be absolutely grounded. g) Bolts & Nuts for the connection of cables, busbars and lead wires shall be firmly fastened.
2. How to mount
a) Cable and busbar shall not be directly loaded onto CT&PT. b) Enough distance shall be taken that primary lead wires and busbars do not approach the surface of transformers except the connection terminals. Besides, please draw your attention for corona and partial discharge not to occur. c) Secondary lead wires shall be correctly connected to the terminals and shall not be approached to the surface of transformers.
ALCE 2005 - 07
- 01 -
Properties Location Standard, insulation level Frequency Insulation : indoor : IEC - 60044-1, DIN VDE 0414 edition 01/1994, Um: 0,72 kV : 50 - 60 Hz : thermoplastic casing, insulation class E
Rated continious thermal current : 1,2 In Secondary rated current Security factor : 5A or 1A : for class 0.5, at primary current <1500 A, FS5 ; at primary current < 4000 A, FS10 : for class 1.0, at primary current <2000 A, FS5 ; at primary current <4000 A, FS10 Rated short time thermal current : Ith =60 x In Rated dynamic current : Idyn = 2,5 x Ith
Standards
Terminal designation Primary Secondary S1 - S2 S1 - S2 k-l S1 - S2 S1 - S2 x1 - x2 Measuring 0,2 - 0,5 - 1 - 3 - 5 0,2 - 0,5 - 1 - 3 - 5 0,2 - 0,5 - 1 - 3 - 5
P1 - P2 P1 - P2 K-L P1 - P2 P1 - P2 X1 - X2
- secondary terminals M5 bolts. - upon request secondary reconnection - upon request different security factors.
Accessories
Connecting accessory Foot attachment
- 02 -
ALCE 2005 - 07
Types and descriptions Types ASS, ASK ASB ADS 20, A 20, ADS 30, ADB 30 ADS 40, ADB 40, A 50, A 61, ADS 62, ADB 80, ADB 81, A 101, ADB 111, ADB 120 ARS-1, ARS-2 ARK-1, ARK-2 ARD-2, ARD-3 A125 TA-2, TA-3, TA-4, TA-5, TA6 TDR Descriptions Wound current transformers (primary cable) Wound current transformers (primary busbar 25x3 mm x mm) Plug-in current transformers. For bars or round conductor.
Primary cable protection current transformer for relays. Bar-type. Protection current transformer for relays. Bar or cable type. Protection current transformer for relays. Bar-type cast resin. Summation current transformers with up to 6 separate independent primary input circuits. Current transformer for differential protection.
Types according to bar dimensions Bar widths Types ADS 20, A 20 ADS 30, ADB 30 ADS 40, ADB 40 A50 A61 ADS 62 ADB 80 ADB 81 A101 20 mm 30 mm 40 mm 50 mm 60 mm 80 mm 100 mm 120 120 mm mm 150 mm 200 mm
(*)
(*)
ALCE 2005 - 07
- 03 -
Current transformers for low voltage ASS, ADS20, ADS30, ADS40, ADS62, ADS100
Tables and dimensions
ASS
Cable mm Window
mm x mm
ASS
15 21 x 5,5 20 x 5 ADS20
23 31 x10,5 30 x 10 ADS30
28 41 x 15 40 x 10 ADS40
30 61 x 31
52 101 x 53
Bar
mm x mm
0,5 1 2,5 5 10 15 20 25 30 40 50 60 75 80 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1250 1500 1600 1800 2000 2500 3000 3200 2,5 2,5 5 5 5 5
0,5
1,0
For secondary 5A or 1A Rated power VA Class 0,5 1,0 0,5 1,0 0,5
ADS 20
1,0 0,5 1,0
ADS 30
() () () () () () 2,5 3,75 5 () () () () () () 2,5 2,5 5 5 5 () () 2,5 3,75 5 5 5 2,5 2,5 5 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 15 15 30 30 30 30 30 10 10 15 15 15 15 15 30 30 30 30 30 15 15 15 30 30 30 30 30 30 30 15 15 15 30 30 30 30 30 30 30
ADS 40
ADS 62
ADS 100
- 04 -
ALCE 2005 - 07
Current transformers low voltage ASK, ASB, A20, ADB30, ADB40, A50, A61
Tables and dimensions
Cable mm Window
mm x mm
ASK
ASB
16 21 x 11 20 x 10 A20
26 31 x 11 30 x 10 ADB30
30 41 x 11 40 x 10 ADB40
40 51 x 11 50 x 10 A50
62 x 12 60 x 10 A61
ASK
Bar
mm x mm
Types Primary current A 1 2,5 5 10 15 20 25 30 40 50 60 75 80 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1250
ASB
0,5 1,0 0,5 1,0 0,5 1,0
0,5 10 10 15 15 15
1,0 10 10 15 15 15
0,5
1,0
15 15 15 15 15 15 15 15 15 15 15 15 15
A20
ADB30
ADB40
A50
A61
All types are protected against contact (except type A20) ALCE 2005 - 07
- 05 -
Current transformers for low voltage ADB80, ADB81, A101, ADB111, ADB120
Tables and dimensions
ADB80
Cable mm Window
mm x mm
30 102 x 32
56 102 x 58
70 121 x 72
Bar
mm x mm
Types Primary current A 400 500 600 750 800 1000 1200 1500 1600 1800 2000 2500 3000 4000 5000
ADB81
1,0 0,5 1,0
0,5 10 10 15 15 15 30 30 30 30 30 30 30 30
1,0 10 15 15 30 30 30 30 30 30 30 30 30 30
0,5 10 10 10 15 15 15 30 30 30 30 30 30 30
A101
ADB111
ADB120
- 06 -
ALCE 2005 - 07
Current transformers for low voltage ARS-1, ARS-2, ARK-1, ARK-2, ARD-2, ARD-3
Tables and dimensions
ARS-1
Cable mm Window
mm x mm
ARS - 1
ARS - 2
ARK - 1
ARK - 2
30 82 - 32
30 102 - 32
Bar
mm x mm
Types
For secondary 5A or 1A Primary current A 5 10 15 20 25 30 40 50 60 75 80 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1250 1500 1600 1800 2000 2500 3000 4000 Rated power VA Class
5P5 5P10 5P5 5P10 5P5 5P10 5P5 5P10 5P5 5P10 5P5 5P10 10P5 10P10 10P5 10P10 10P5 10P10 10P5 10P10 10P5 10P10 10P5 10P10
ARS-2
15 15 15 15
5 5 5 5
30 30 30 30
15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 5 5 5 5 5 5 5 5 5 5 5 5 5 5 30 30 30 30 30 30 30 30 30 30 30 30 30 30 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 30 30 30 30 30 30 30 5 5 5 5 15 15 15 15 30 30 30 30 30 30 30 30 30 30 30 30 30 30 45 45 45 15 15 15 15 15 15 15 15 30 30 30 30 30 30
ARK-1
ARK-2
ARD-2
ARD-3
All types are protected against contact Primary bars (for type ARK) Primary current A 25 - 200 250 - 400 ALCE 2005 - 07 Bar width mm 5 10
- 07 -
Summation current transformers for low voltage TA-2, TA-3, TA-4, TA-5, TA-6
Tables and dimensions
Type 1
Primary A TA-2
5+5 / 5
TA-3
5+5+5 / 5
TA-4
5+5+5+5 / 5
TA-5
5+5+5+5+5 / 5
TA-6
5+5+5+5+5+5 / 5
Type 2
Example :
Main current transformers : Summation current tranformers : Result : 300A , 100A , 100A 5 1 5 5+1+5 A 5
R S T K A k L * l
* *
K B k
L * l
* *
K C k
L * l
* *
R S T
Burden for measuring
AK AL BK BL k R
- 08 -
ALCE 2005 - 07
Indoor current transformer Type A125 cast resin, for busbar fastening
A125
Window
mm x mm
126 x 72 4(120 x 10) A125 For secondary 5A or 1A Rated power VA Class 0,5 1,0 30 45 30 45 60 45 60 100
Bar
mm x mm
ALCE 2005 - 07
- 09 -
Type 1 2
L1 40 50
L2 90 100
VM
Secondary voltage = Earth-fault winding = 100 V 110 V , 3 3 100 V 110 V , 3 3
2VM
For secondary voltage 100 V or 110 V Secondary thermal burden current; Isth
Rated voltage factor = 1.9 (30 sec.) Secondary thermal burden current; Isth
Primary voltage 100 : 3 110 : 3 200 : 3 220 : 3 380 : 3 400 : 3 500 : 3 1.2 kV, Isth=2A* 500 : 3 600 : 3 750 : 3 1000 : 3 15 30 45 60 VA
Class 0.5
Class 1
Class 3
Class 0.5
Class 1
Class 3
100 V 110 V 200 V 220 V 380 V 400 V 500 V 1.2 kV, Isth=1A
30 45 60
2 -
1 1 1
1 1 1
1 -
1 1 2 2
1 1 1 2
15 30 45 60
1 2 -
1 1 2 2
1 1 1 1
- 10 -