DK 94 7 RGT 12 SVC - Eng
DK 94 7 RGT 12 SVC - Eng
DK 94 7 RGT 12 SVC - Eng
www.tense.com.tr
www.tenseenerji.com
Index
About the device 1
What is the SVC (TCR)? 1
Features 1
Warnings 2
Matters to be Considered in Power Factor Correction 2
Points to Consider in Current Transformer Selection and Connection 3
Maintenance of the Device 3
Quick Installation Guide 4
Measuring Screens 6
Menu Screens 7
3P4W Connection Scheme 8
1P2W Connection Scheme 9
Screen Description 10
How to Install the Device? 11
How to Change Current Transformer Value? 12
How is the Current Transormer Test Performed? 14
How is Step Measurement? 15
How to Enter Step Value Manually? 16
How is Step Control Done? 17
Measurement
Measurement Screen Inroduction 17
Total Powers Page 18
Cosinus Page 18
Ratios Page 18
Voltage and Frequency Page 18
Voltage and Current Page 18
Instant Powers Page 19
Total Energy Page 19
THD-V and THD-I page 19
Index
Settings
Current Transformer Menu 19
Current Transformer Test 20
Current Transformer Value 20
Step Menu 21
Step Values 21
Step Measurement 21
Step Time Settings 22
Power Factor Correction Settings 22
Step Control 23
Manual Step Value Set 23
Automatic Step Measurement Period 24
Advanced Settings Menu 24
Power Factor Correction 24
Power Analysis Samples 25
ModBus RS485 (Communication Settings) 25
Operating Power 26
Operating Harmonic 26
Delete Logs 27
Generator Settings 27
Power Factor Correction Alarm 28
Device Settings Menu 28
Factory Default 28
Change Password 29
Language Options 29
Backlight Settings 30
Capacitor Calculation Table by Connection Type 31
Step Value Determination According to Power Analysis Samples 32
Factory Defaults 33
Dimensions 34
Technicial Specifications 35
Contact Informations 35
About the Device
It is designed to reduce reactive (inductive and capacitive) power that comes from the
network and loads do not use. If the inductive reactive power is attracted from the network,
it interferes by attracting capacitor at the appropriate step. If capacitive reactive power is
attracted from the network, interferes by attracting shunt reactor at the appropriate step.
Thus it endeavors to reduce the inductive/active and capacitive/active rates of the system.
Features
2.9”(128x64) Easy to install and use with graphic LCD.
TCR (SVC) Connectable (Only in models with SVC.)
Generator Input and Generator Compensation
Remote Communication with RS485 (Modbus RTU) (Only in models with communication)
Compensation of GES Systems (Only in RGT-18G model)
Compensation for Inductive and Capacitive Systems
Manual Step Value Enterable
Single, Two and Three Phase Capacitor and Shunt Reactor can be connected
Turkish and English Language Option
Voltage, Harmonic Current/Voltage, Inductive and Capacitive Alarm Output
Step Drive, Step Release, Discharge and Settlement Times are Adjustable
Current Harmonics can be Observed Up To 31st Harmonics
Voltage Harmonics can be Observed Up To 31st Harmonics
Cosine Values of Each Phase Can Be Observed
Power Factor Values of Each Phase can be Observed
Capacitive/Active and Inductive/Active Ratios can be Observed
Total Active and Reactive Energies (Import/Export/Inductive/Capacitive) can be Observed.
THD-V and THD-I values of Each Phase can be Observed.
Creating Power Analysis (20 samples 9999 min.)
It Shows The Total Number of Uses of the Steps.
Encrypted Protection
Same Aging in Steps
1
Warnings
Use the device according to our instructions.
Avoid direct sun light in order not to harm the LCD screen.
Leave at least 10 cm of space behind the device after mounting.
Fix the device with apparatus which comes within the device by avoiding any kind of
shake on the front cover of the board.
Balance the inner and outer heat in the metal boards. Otherwise because of the temperature
difference that originates from the dampish surrounding, water droplets occurs on the ceiling
of the board and this situation is dangerous for the open connected buses.
Mark the switch and circuit breaker as the connection tripping element for the device.
Keep the switch and circuit breaker close to the device and easily accessible by the operator.
There must be no electricity in the connection cables when assembling.
Screened and twisted cord cables should be used on the input and output lines without
connection to the Mains (network). These cables should not pass near high-Voltage lines
and devices.
2
Points to Consider in Current Transformer Selection and Connection
Be careful about the value of the current transformer to be more than the maximum
current which could be/is attracted from the system.
It is recommended that class of the current transformers (it can be also mentioned
class, klas, kl, cl ) should be 0,5 which will be used at the compensations.
Only X5A current transformers can be connected to the device.
Be careful about the absence of any load before the current transformers. Otherwise
there can be differences between reactive and counter.
Current transformer outputs and phase inputs must be in the same order. Connect the
k-l terminals of the current transformer connected to the L1 phase to the k1-l1
terminals, the k-l terminals of the current transformer connected to the L2 phase to the
k2-l2 terminals and the k-l terminals of the current transformer connected to the L3
phase to the k3-l3 terminals.
While connecting output of the current transformer terminals in order to avoid
confusion, use different coloured cable for each phase or number the cables.
Pass the cables which is connected to the output of the current transformer far from the
high voltage line.
It is advised that the cables to be used which are connected to current transformer
should be minimum 1.5 mm2. It is also recommended that the cables should be
thickened as the distance increase.
In order to avoid shake at the current transformers, fix to the bus, cables or rail.
The cable distance connected to the current transformer output ends should not be kept long.
Otherwise there may be errors in the measurements.
Cable connected to current transformer output ends, one piece should be. Otherwise,
measurements may have errors and current transformer testing may not be possible.
3
Quick Installation Guide
Warning!
Three-phase capacitor equivalent to 1/40 of current transformer ratio must be connected in
the first three steps for current transformer test to be performed. Also, the current
transformer connected to the device and the phase order of the voltages must be the same.
Otherwise, the device will give phase inverse or step low warning. After fixing the connection
errors according to the warnings, you can start the device setup again.
1 2
Pressing the SET button while on any While on this page, press the SET button
measurement page displays the to enter the menu.
PASSWORD page to enter the menu.
4 3
While on this page, press SET button
While in this page, press the SET button to access Current Transformer Menu.
to enter the Current Transformer Value
in the system. The Current Transformer Test page
will appear on the screen. Press the UP
Current Transformer Value Entry page button to switch to the Current
will be displayed on the screen. Transformer Value page.
Menu.1.2 Menu.1.0
CURRENT TRANSFORMER
CURRENT TRANSFORMER
MENU
VALUE
5 6
While on this page, enter the Current In case of any problems in the
Transformer Value in the system using connections, the device will give a warning
the UP and DOWN buttons and then and will not accept the connection.
press the SET button to save.
According to the warnings, connection
The device will automatically start errors after correcting, you can start
Current Transformer Test operation. current transformer test again.
9
When the step measurement is finished, a confirmation page will be displayed on the
screen. When the SET button is pressed, all the measured steps are saved and when you
return to the measurements screen with the ESC button, the device starts to intervene.
Pressing the ESC button cancels the step measurements and returns to the Step
Measurement page without saving.
You can check the stored step values on the Step Values screen (2.1.1) in the Step
Menu.
5
Measuring Screens
PF: 1.000 Ind(%) Cosinus(Cos) Ratios(%) Ind. Cap.
P : 0.000kW 0.0 Instant: 0.3 0.2
+Q: 0.000kVar L1: -1.000 Offset
-Q: 0.000kVar Cap(%) Hourly : 0.3 0.2
L2: 1.000 0.0
S : 0.000kVA 0.0 Daily : 0.3 0.2
L3: -1.000
Off: 0.0kVar
_____________________ _____________________ Energy : 0.3 0.2
_____________________
TCR % R:23 S:23 T:23 TCR % R:23 S:23 T:23 TCR % R:23 S:23 T:23
Figure-1 Figure-2 Figure-3
Figure-1: Total power factor, active power, capacitive power, inductive power, apparent power, offset
and active / reactive ratio values are displayed on the screen.
Figure-2: Cosine values of each phase are displayed on the screen. Pressing the RIGHT button
displays the Power Factor values.
Figure-3: Instant, hourly, daily and total active consumption / reactive consumption rates are
displayed on the screen.
Figure-4: Phase-Neutral voltage and frequency values are displayed on the screen. When the RIGHT
button is pressed, phase-phase voltage values are displayed.
Figure-5: Phase-Neutral voltage and current values are displayed on the screen.
Figure-6: Instantaneous power values of each phase are displayed on the screen. Pressing the
RIGHT button displays the Apparent Power values.
Figure-7: Total energy values are displayed on the screen. Active Energy, Inductive Energy,
Capacitive Energy, Export Active Energy and Apparent Energy values are displayed respectively by
pressing the RIGHT button.
Figure-8: THD-V and THD-I values are displayed on the screen. When pressing the RIGHT button,
Voltage Harmonic (L1, L2, L3) and Current Harmonic (L1, L2, L3) values are shown respectively.
6
Menu Screens
Menu.1.0
CURRENT TRANSFORMER
MENU
Menu.4.0 Menu.2.0
Figure-3
DEVICE SETTINGS STEP MENU
MENU
Menu.3.0
Figure-6 Figure-4
ADVANCED SETTINGS
MENU
Figure-5
Entering Settings: When SET button is pressed on any measurement page, the PASSWORD
page (Figure-2) is displayed for entering the menu.
While on this page, press the SET button to enter the menu.
(The password value is “0000” by default. If the password has been changed by the user, the
password determined by the user must be used to enter the menu.)
Current Transformer Menu: It is the first menu that appears after entering the settings page (Figure-3).
In this menu, you can change the current transformer value and have a current transformer test done.
Step Menu: It is the second menu that appears when you proceed by pressing the UP button
after entering the settings page (Figure-4). In this menu, you can see Step Values, take Step
Measurement, change Step Time Settings, make PFC settings, Make Step Control, Manually
Enter Step Value and set Auto Step Measurement Period.
Advanced Settings Menu: It is the third menu that appears when you proceed by pressing the
UP button after entering the settings page (Figure-5). In this menu, Compensation Target Value
can be set, Power Analysis Samples can be viewed, ModBus Communication settings can be
made, Operating Voltage and Operating Harmonics can be set, Logs can be deleted, Generator
Compensation and Compensation Alarm settings can be made.
Device Settings Menu: It is the fourth menu that appears when you proceed by pressing the UP
button after entering the settings page (Figure-6). In this menu, Factory Settings can be
changed, Password and Device Language can be changed, and the duration of the Backlight can
be adjusted.
7
in models with SVC.
SVC connection is only
N
3P4W Connection Scheme
L1
L2
L3
2A
A2 A2
N L1 L2 L3
A1 A1
8
Voltages
SGND (Input)
B
SRL-XXT
SVC CON
A
Shunt Reactor
Thermal Thermal
Harmonic Filter
Voltages
2A
2A
6A
2A
6A
2A
2A
Thermal (Output)
in1 in2 in3 T1 T2 T3
Kondansatör
k3 I3 k2 I2 k1 I1 L3 L2 L1 N L C1 C2 C3 C4 C5 C6 L C7 C8 C9 C10C11C12 SGND B A
Ct3 Ct2 Ct1 Voltages Steps Steps SVC CON
Currents
1 2 3
Thermal Thermal Thermal
Shunt Reactors
in models with SVC.
SVC connection is only
N
1P2W Connection Scheme
L1
L2
L3
2A
A2 A2
N L1 L2 L3
A1 A1
9
Voltages
SGND (Input)
B
SRL-XXT
SVC CON
A
Shunt Reactor
Thermal Thermal
Harmonic Filter
Voltages
6A
2A
6A
2A
2A
Thermal (Output)
in1 in2 in3 T1 T2 T3
Kondansatör
k3 I3 k2 I2 k1 I1 L3 L2 L1 N L C1 C2 C3 C4 C5 C6 L C7 C8 C9 C10C11C12 SGND B A
Ct3 Ct2 Ct1 Voltages Steps Steps SVC CON
Currents
1 2 3
Thermal Thermal Thermal
Shunt Reactors
Screen Description
1
2
3
4
5
1- Stage Leds: The LEDs are lit when the steps are active.
2- Alarm Led: It is the LED that lights to alert the user in case of alarm.
3- Graphic LCD: It is the screen where all measurements, settings and notifications related to the
device are transferred to the user.
4- Status Leds: Reactive/Active instant rate status and communication notification leds.
(Only in models
COM Led (Communication): This LED is on during ModBus RTU communication. with communication)
IND Led (Inductive): This LED will light if the inductive/active instantaneous rate is more than 20%.
NOR Led (Normal): Inductive/Active instantaneous rate less than 20% and Capacitive/Active
instantaneous rate less than 15% If it is low, this led will light.
CAP Led (Capacitive): If the capacitive/active instantaneous rate is more than 15%, this led will light.
12
Menu.1.2.1 While in this page, press the SET button to enter the
Current Transformer Value in the system.
Current Trans. Value
Current Transformer Value Entry page will be displayed on
the screen.
CTR: 1500 / 5A
While on this page, use the UP and DOWN buttons to enter
the Current Transformer Value in the system and then press
the SET button to save.
Current Trans.Test(A) The device will automatically start Current Transformer
Test operation.
Plase Wait!
L1:0.000
1.Trial L2:0.000 In case of any problems in the connections, the device will
L3:0.000 give a warning and will not accept the connection.
Esc:Cancel
When current transformer test is successful, this page will
be displayed on the screen.
Current Trans.Test(A) If the operation is confirmed by pressing the SET button, the
Contact Learned device will automatically start the Step Measurement process.
k1-l1:(-) After the test, it indicates that the current transformer
k2-l2:(+) terminals indicated with “(-)” are connected reversely. You
k3-l3:(+) don't need to fix the links. The device will fix these
Esc:Cancel Set:OK connections software-wise.
Step Measure. (kVAr) During the step measurement, this page will be displayed
Please Wait! on the screen, all steps will be measured in order and their
values will be displayed on the screen.
L1:-3.333
1.Step L2:-3.333 Capacitor values are shown with a “-” sign and shunt
L3:-3.333 reactors are unsigned.
Esc:Cancel
When the stage measurement is finished, a confirmation
Step Measure. (kVAr) page will be displayed on the screen. When the SET button is
pressed, all measured steps are saved and the device starts
Step Meas. Finished! to intervene.
L1: 3.333
TCR L2: 3.333 Pressing the ESC button cancels the step measurements
and returns to the Step Measurement page without saving.
L3: 3.333
Esc:Cancel Set:OK You can check the stored step values on the Step Values
screen (2.1.1) in the Step Menu.
13
How is the Current Transformer Test Performed?
Three-phase capacitor equivalent to 1/40 of current
transformer ratio must be connected in the first three steps
for current transformer test to be performed. Also, the
Enter Password! current transformer connected to the device and the phase
PASS : 0000 order of the voltages must be the same. Otherwise, the device
will give phase inverse or step low warning. After fixing the
connection errors according to the warnings, you can start
the device setup again.
When SET button is pressed on any measurement page, the
Menu.1.0 PASSWORD page is displayed for entering the menu.
While on this page, press the SET button to enter the menu.
CURRENT TRANSORMER
MENU (The password value is “0000” by default. If the password
has been changed by the user, the password determined by
the user must be used to enter the menu.)
Menu.1.1
After passing the password page, Current Transformer
Menu page will be displayed on the screen.
CURRENT TRANSFORMER While on this page, press the SET button to enter the
TEST Current Test Menu.
Yes : [*]
No : [ ]
When you press the SET button on this page, the device will
automatically start Current Transformer Test operation.
Current Trans.Test(A)
Plase Wait!
L1:0.000 In case of any problems in the connections, the device will
1.Trial L2:0.000 give a warning and will not accept the connection.
L3:0.000
Esc:Cancel
When current transformer test is successful, this page will
be displayed on the screen.
Current Trans.Test(A)
Contact Learned If the operation is confirmed by pressing the SET button, the
device will automatically start the Step Measurement process.
k1-l1:(-)
k2-l2:(+) After the test, it indicates that the current transformer
terminals indicated with “(-)” are connected reversely. You
k3-l3:(+) don't need to fix the links. The device will fix these
Esc:Cancel Set:OK connections software-wise.
14
How is Step Measurement?
When SET button is pressed on any measurement page, the
PASSWORD page is displayed for entering the menu.
Enter Password! While on this page, press the SET button to enter the menu.
PASS : 0000
(The password value is “0000” by default. If the password
has been changed by the user, the password determined by
the user must be used to enter the menu.)
Menu.2.2 When you enter the Step Menu page, the Step Values
page is displayed on the screen first.
STEP MEASUREMENT Switch to the Step Measurement page by pressing the UP
button, then enter the Step Measurement page by pressing
the SET button.
Menu.2.6
When you enter the Step Menu page, the Step Values page
MANUAL STEP is displayed on the screen first.
VALUE SET Switch to the Manual Step Value Set page by pressing the
UP button, then enter the Manual Step Value Set page by
pressing the SET button.
Menu.2.6.1
Enter Step Value In this page, you can navigate between parameters (Step,
Type and Value) with the RIGHT button, and change the value
>Step : 1 in the selected parameter with the UP/DOWN buttons.
Type : L123
To change the current value, the relevant parameter must
Value : -10.00kvar be selected with the RIGHT button. The selected parameter is
indicated by the sign ">" on the left side.
Menu.2.6.1
After entering the step information manually, SET button is
Enter Step Value pressed to save. After the saving process, the step
>Step : 1 information recorded and “Step Approved” are displayed on
the screen.
Type : L123
Value : -10.00kvar To exit without saving, pressing the ESC button will return
to the Maneul Step Value Set page.
Step Approved
Example: On the screen above, the three-phase 10kVAr capacitor value has been entered in the 1st step.
If the value to be entered is single phase, “L1, L2 or L3” should be selected from the phase part
according to the phase to which it is connected. If the value to be entered is two phase, “L12, L23 or L31”
should be selected from the phase part according to the phase to which it is connected. If the value to be
entered is three phase, “L123” should be selected.
Note: Capacitor values are entered as (-) signed with DOWN button. Shunt reactor values are entered
unsigned with the UP button.
16
How is Step Control Done?
It is a menu designed to control the connections and
robustness of the shunt reactors, capacitors and contactors
connected to the stages.
Enter Password!
When SET button is pressed on any measurement page,
PASS : 0000 the PASSWORD page is displayed for entering the menu.
While on this page, press the SET button to enter the menu.
(The password value is “0000” by default. If the password
has been changed by the user, the password determined by
Menu.2.0 the user must be used to enter the menu.)
PF: 1.000 Ind(%) This page shows the total instantaneous powers (power
P : 0.000kW 0.0 factor, active power, capacitive power, inductive power,
+Q: 0.000kVar apparent power) values, the offset value defined in the device
-Q: 0.000kVar Cap(%) and the reactive ratios.
S : 0.000kVA 0.0 When RIGHT or UP button is pressed on this page, Cosinus
Off: 0.0kVar
_____________________ page is displayed. When DOWN button is pressed, THDV and
TCR % R:23 S:23 T:23 THDI page is displayed. When the SET button is pressed, the
password page is displayed for entering the menu.
Measurements E Cosinus Page
Kosinus(Cos) This page shows the Cosinus values for each phase.
L1: -1.000 Offset When RIGH button is pressed on this page, Power Factor
L2: 1.000 0.0 page is displayed. When UP button is pressed, Ratios page is
L3: -1.000 displayed. When DOWN button is pressed, Total Power page is
_____________________ displayed. When the SET button is pressed, the password
TCR % R:23 S:23 T:23 page is displayed for entering the menu.
Voltage-V Freq-Hz This page shows the voltage and frequency values between
phase and neutral.
L1:220.0 L1:50.00 When RIGHT button is pressed on this page, Voltage (L-N) &
L2:220.0 L2:50.00 Voltage (L-L) page is displayed. When UP button is pressed,
Voltage (L-N) & Current page is displayed. When DOWN button is
L3:220.0 L3:50.00
_____________________ pressed, Ratios page is displayed. When the SET button is pressed,
TCR % R:23 S:23 T:23 the password page is displayed for entering the menu. When ESC
button is pressed, Home Page (Total Powers) is displayed.
Voltage(V) Curr.(A) This page shows the voltage and current values between phase
and neutral.
L1:220.0 L1:380.0
When RIGHT or UP button is pressed on this page, Instant Powers
L2:220.0 L2:380.0 page is displayed. When DOWN button is pressed, Voltage (L-N) &
L3:220.0 L3:380.0 Frequency page is displayed. When the SET button is pressed, the
_____________________ password page is displayed for entering the menu. When ESC button
TCR % R:23 S:23 T:23 is pressed, Home Page (Total Powers) is displayed.
18
Measurements E Instant Powers Page
Active P Reactive Q This page shows the Instantaneous Power (Active and
kW kVAr Reactive) values for each phase.
L1:500.0 L1:-005.0 When RIGHT button is pressed on this page, Apparent Powers
L2:500.0 L2: 002.0 page is displayed. When UP button is pressed, Total Energy page
is displayed. When DOWN button is pressed, Voltage (L-N) &
L3:500.0 L3:-003.0 Current page is displayed. When the SET button is pressed, the
_____________________
TCR % R:23 S:23 T:23 password page is displayed for entering the menu. When ESC
button is pressed, Home Page (Total Powers) is displayed.
Total Energy (²) Total Energy values are displayed on this page.
+P: 0234565100.0kWh If you proceed by pressing the RIGHT button while on this
+Q: 1213215100.0kVArh page, Import Active Energy, Inductive Energy, Capacitive Energy,
Export Active Energy and Apparen Energy pages are displayed on
-Q: 0235115500.0kVArh the screen respectively. When UP button is pressed, THD-V and
-P: 0235115500.0kWh
_____________________ THD-I is displayed. When DOWN button is pressed, Instant
TCR % R:23 S:23 T:23 Power page is displayed. When the SET button is pressed, the
password page is displayed for entering the menu. When ESC
button is pressed, Home Page (Total Powers) is displayed.
Menu.1.0 It is the first menu that appears after entering the settings
page. In this menu, you can change the current transformer
value and have a current transformer test done.
CURRENT TRANSFORMER
MENU To enter the Current Transformer Menu, press the SET
button while there is Current Transformer Menu page on the
screen. Use UP and DOWN buttons to access other settings in
the menu.
19
Settings E Current Transformer Menu E Current Transformer Test
It is the first of two different setting parameters in the current transformer menu. To start the
current transformer test, press the SET button with the Current Transformer Test page on the
screen, then select Yes and press the SET button again.
Then the device will start current transformer test by pulling the first 3 steps. In case of any
problems in the connections, the device will give a warning and will not accept the connection.
Three-phase capacitor equivalent to 1/40 of current transformer ratio must be connected in
the first three steps for current transformer test to be performed. Also, the current transformer
connected to the device and the phase order of the voltages must be the same. Otherwise, the
device will give phase inverse or step low warning. After fixing the connection errors according
to the warnings, you can start the device setup again.
When the current transformer test is successful, a confirmation page will appear on the
screen with the words "Connection Learned".
If the operation is confirmed by pressing the SET button, the device will automatically start
the Step Measurement process.
After the test, it indicates that the current transformer terminals indicated with “(-)” are
connected reversely. You don't need to fix the links. The device will fix these connections
software-wise.
Menu.1.2 Menu.1.2.1
Current Trans. Value
CURRENT TRANSFORMER
CTR: 1500 / 5A
VALUE
It is the second of two different setting parameters in the current transformer menu. To
change the current transformer value, press the SET button with the Current Transformer
Value page on the screen, then enter the current transformer value in your system using the UP
and DOWN buttons and press the SET button again to save.
The device will automatically start the current transformer test for the changed current
transformer value. You can review Page 10 and (How to Install the Device) Page 11 (How to
Change Current Transformer Value) for detailed explanation, .
20
Settings E Step Menu
Press the SET button while there is Step Menu page on the screen to enter the Step Menu.
Use UP and DOWN buttons to access other settings in the menu.
Menu.2.1 Menu.2.1.1
1. Kademe L123
STEP VALUES L1: -100.00 kVAr
L2: -100.00 kVAr
L3: -100.00 kVAr
Usage Number :10000
It is the first of 7 different setting parameters in the step menu. For the step values, press the
SET button with the Step Values page on the screen.
Example: The connection status of the 1st stage, its kVAr value in each phase and the number
of uses are displayed on the screen. You can navigate between values by using UP and DOWN
buttons to see other step values.
21
SettingsE Step MenuE Step Time Settings
Menu.2.2
Menu.2.3 Menu.2.3.1
Step Times
KADEME
STEPOLCUMU
TIME >Drive : 3 sec.
SETTINGS Relase : 2 sec.
Discharge: 15 sec.
Settling : 400 msec.
It is the third of 7 different setting parameters in the step menu. To change the Step Time
Settings, press the SET button while the Step Time Settings page is on the screen. To change
the current value, the relevant parameter must be selected with the RIGHT button. The selected
parameter is indicated by the ">" sign on the left side.
Then the selected value can be changed with UP / DOWN buttons. The changed value is saved
by pressing the SET button.
Drive Time: It determines the activation time of the step to intervene in the power change in the system.
Factory Setting = 2.0sec. , Setting Range: 1sec, – 30sec.
Release Time: It determines the time for releasing the step that is activated to interfere with
the power change in the system.
Factory Setting = 2.0sec. , Setting Range: 1sec, – 30sec.
Discharge Time: It determines the duration of the capacitor discharge (being able to
reactivate the same stage).
Factory Setting = 15sec. , Setting Range: 1sec, – 60sec.
Settling Time: When the device needs to activate several steps at once, it determines the time
to wait between the steps.
Factory Setting = 400msec. , Setting Range: 100msec, – 3000msec.
SettingsE Step MenuE PFC Settings
Menu.2.2
Menu.2.4 Menu.2.4.1
PFC Settings
KADEME OLCUMU
PFC SETTINGS
>PFC : Active
TCR : Active
Offset: -10.0 kVAr
It is the fourth of 7 different setting parameters in the step menu. To change the PFC
Settings, press the SET button while the PFC Settings page is on the screen.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the ">" sign on the left side.
PFC: It enables/disables the device's intervention to reactive powers in the system with
capacitors and shunt reactors. When PFC is disabled, the device does not activate steps.
TCR: Activates/deactivates the device's intervention to reactive powers in the system with an
inductive load driver (if the system has an inductive load driver). When TCR is passive, the
device will not activate the inductive load driver.
SVC (TCR) connection is only available on models with SVC.
22
Offset: It is the value used for reactive powers between the electricity meter and the reactive relay that the reactive
relay cannot measure. This value that the device cannot measure is calculated software and intervened accordingly.
Example: If offset is entered as -10kVAr, it means that there is a three-phase 10kVAr capacitive power that the
reactive relay cannot measure. The reactive relay will interfere with this power, in addition to the target cosine value,
with three-phase 10kVAr inductive power. (If offset capacitive (-) is entered, the power to be applied becomes
inductive (+), If offset inductive (+) is entered, the power to be applied becomes capacitive (-).)
SettingsE Step MenuE Step Control
It is the fifth of the 7 different setting parameters in the step menu. To perform the Step
Check, press the SET button while the Step Check page is on the screen.
You can navigate between the levels with UP/DOWN buttons, you can use the RIGHT button to
control/activate/deactivate the steps and to deactivate the active steps.
When you return to the measurements screen by pressing the ESC button, the device will
inactivate these stages one by one if there are activated stages.
Menu.2.2
Menu.2.7 Menu.2.7.1
Step Measure. Period
KADEME OLCUMU
AUTOMATIC STEP
MEASUREMENT PERIOD Period : 0 Week
Period Passive
The capacitors connected at the stages experience a decrease in their capacities depending
on the frequency of use and time. With this parameter, it is aimed that the current values of the
capacitors can be learned by the device at certain time intervals and the device can intervene
more precisely.
At the end of the set period, the device will automatically measure and record all steps in the
system and perform its intervention according to the current step values.
It is the seventh of 7 different setting parameters in the step values menu. To change the Automatic
Step Measurement Period, press the SET button while the Automatic Step Measurement Period page
is on the screen.
You can use UP / DOWN buttons to change the current value. Press the SET button to save.
To enter the Advanced Settings Menu, press the SET button while the Advanced Settings
Menu page is on the screen. Use UP and DOWN buttons to access other settings in the menu.
Menu.3.1 Menu.3.1.1
PF Correction
POWER FACTOR
CORRECTION >Set : 5%
Tolerance: % 1.0
Cos:0.9988 Induct.
It is the first of the 8 different setting parameters in the advanced settings menu. To change
the Power Factor Correction Settings, press the SET button with the Power Factor Correction
page on the screen.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the ">" sign on the left side.
24
Set: The targeted compensation set value is entered here. Inductive or Capacitive set can be
entered. The Cosinus value that will occur as a result of the entered set value appears at the
bottom of the screen.
Tolerance: It is the movement area that will be given to the device in an inductive and
capacitive direction in order to ensure less activation / passivation to extend the lifetime of the
contactors, capacitors and reactors in the stages. The device will not change its current
response for reactive power changes within the SET ± Tolerance value in this field.
Example: If the SET value is 0% (Cos: 1) and the Tolerance value is 2%, the device will not
change its current response for reactive power changes within this area after reaching a ratio
between Inductive 2% and Capacitive 2%.
Settings E Advanced Settings Menu E Power Analysis Samples
Menu.3.2 Menu.3.2.1
SAMPLE: 1
POWER ANALYSYS L1: -100.00 kVAr
SAMPLES L2: -100.00 kVAr
L3: -100.00 kVAr
Sample Time:10000 min
It is the second of 8 different setting parameters in the advanced settings menu. To view the
Power Analysis Samples, press the SET button while the Power Analysis Samples page is on the
screen.
In this page, reactive powers drawn from each phase are recorded along with their duration.
(capacitive powers are indicated by a (-) sign.)
If the power consumption remains constant over a certain period of time, it is recorded as an
sample. If the next sample is 15% above the previous one, it will be saved as a different one. If
the under 15%, only the duration is added to the previous example. Contains a total of 20
samples. It can take samples for up to 9999 minutes.
You can use the UP / DOWN buttons to navigate through the samples.
You can review Page 31 for detailed explanation. (Step Value Determination According to
Power Analysis Examples.)
It is the third of the 8 different setting parameters in the advanced settings menu. To change
the ModBus RS485 Settings, press the SET button while the ModBus RS485 page is on the screen.
In this page, you can navigate between parameters (Baudrate, Parity, Stop Bit and ModBus ID)
with the RIGHT button, and change the value in the selected parameter with the UP / DOWN buttons.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the ">" sign on the left side.
25
Settings E Advanced Settings Menu E Operating Voltage
Menu.3.4 Menu.3.4.1 Voltage(V) Curr.(A)
Operating Voltage L1:220.0 L1:380.0
OPERATING VOLTAGE >Control : Active L2:220.0 L2:380.0
High V.: 260 V
L3:220.0 L3:380.0
Low V.: 150 V _____________________
Delay : 5sec ALR! Low Voltage
It is the fourth of the 8 different setting parameters in the advanced settings menu. To change
the Operating Voltage Settings, press the SET button while the Operating Voltage page is on the
screen.
In this page, you can navigate between the parameters (Control mode, High Voltage, Low
Voltage and Delay) with the RIGHT button and change the value in the selected parameter with
the UP / DOWN buttons.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the ">" sign on the left side.
In this page, voltage control mode can be activated or deactivated, high voltage and low
voltage value can be set. If the voltage rises above the set high voltage set value while the
voltage control mode is active or falls below the low voltage set value, the device waits for the
set delay time and then stops compensation. Then “High Voltage” or “Low Voltage” warning is
displayed on the screen. Also, "ALR" contact is activated. When the voltage control mode is
passive, the device does not control the voltage.
It is the fifth of the 8 different setting parameters in the advanced settings menu. To change
the Operating Harmonics Settings, press the SET button while the Operating Harmonics page is
on the screen.
In this page, you can navigate between parameters (Control mode, Voltage Harmonic Set
Value, Current Harmonic Set Value and Delay) with the RIGHT button and change the value of
the selected parameter with the UP / DOWN buttons.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the ">" sign on the left side.
In this page, voltage control mode can be activated or deactivated, voltage harmonic and
current harmonic value can be set. If harmonics exceed the set values while harmonic control
mode is active, the device waits for the set delay time, then stops compensation. Then “High
THDI” or “High THDV” warning is displayed on the screen. Also, "ALR" contact is activated.
When the harmonic control mode is passive, the device does not control the harmonics.
26
Settings E Advanced Settings Menu E Delete Logs
Menu.3.6 Menu.3.6.1
Delete Logs
DELETE LOGS Del/Undel
>Energy Value : Undel
Power Analys.: Undel
Ratios : Undel
It is the sixth of the 8 different setting parameters in the advanced settings menu. To enter
the Delete Records menu, press the SET button while the Delete Records page is on the screen.
In this page, you can navigate between the parameters (Energy Value, Power Analysis and
Ratios) with the RIGHT button, and change the value of the selected parameter with (UP /
DOWN) buttons.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the ">" sign on the left side.
Example: To delete the ratios, after entering the menu, we select the “Ratios” parameter by
pressing the RIGHT button 2 times. Then we change the “Undel” option to “Del” by pressing the
UP or DOWN button. Finally, when we press the SET button, all parameters marked as “Del”
are deleted. If you exit the menu with ESC button without pressing the SET button, the selected
parameters will not be deleted.
It is the seventh of the 8 different setting parameters in the advanced settings menu. To
change the Generator Compensation Settings, press the SET button while the Generator
Compensation page is on the screen.
In this page, you can navigate between the parameters (Control, Set and Tolerance) with the
RIGHT button and change the value in the selected parameter with the UP / DOWN buttons.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the ">" sign on the left side.
In this page, generator control mode can be activated or passive, generator compensation set
and tolerance value can be entered. When the generator mode is activated, it compensates
according to the set and tolerance value set while the generator is activated. When the
generator mode is passive, compensation is stopped when the generator is activated.
NOTE: In order to use this feature, phase-neutral connection should be made to the
Generator connection terminal of the device so as to energize this terminal when the generator
is running.
NOTE: While the generator in the system is activated, the word “GEN” will appear on the
device's screen (bottom left of the screen) as in the figure above.
27
Settings E Advanced Settings Menu E PF Correction Alarm
Menu.3.8 Menu.3.8.1
PF Correction Alarm
PF CORRECTION ALARM >Control :Active
Induct. Set :20%
Capacit. Set:15%
Delay :5 min
It is the last of the 8 different setting parameters in the advanced settings menu. To change
the PF Correction Alarm Settings, press the SET button while the PF Correction Alarm page is
on the screen.
In this page, you can navigate between the parameters (Control, Inductive Set, Capacitive Set
and Delay) with the RIGHT button and change the value in the selected parameter with the UP /
DOWN buttons.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the ">" sign on the left side.
In this page, reactive / active alarm mode can be activated and can be passived, inductive /
active and capacitive / active ratios can be set. When the ratios exceed the set set value, “High
Inductive” or “High Capacitive” warning is displayed on the screen after the set delay time. Also,
"ALR" contact is activated. When the alarm mode is passive, no warning is given.
Settings E Device Settings Menu
Menu.4.1 Menu.4.1.1
Save Factory Default
FACTORY Are you sure?
DEFAULT Yes : [ ]
No : [*]
It is the first of the 4 different setting parameters in the device settings menu. To return to
factory values, press the SET button while the Factory Values page is on the screen, then select
Yes and press the SET button again.
NOTE: After returning to the factory settings, it requires re-installation of the device!
(Current transformer value, step values, menu settings etc. all values and records will be
reset.)
28
Settings E Device Settings Menu E Change Password
Menu.4.2 Menu.4.2.1
New Password
CHANGE PASSWORD
PASS : 0000
It is the second of the 4 different setting parameters in the device settings menu. To change
the password, press the SET button while the Change Password page is on the screen.
In this page, you can navigate between the digits with the RIGHT button and change the value
in the selected digit with the UP / DOWN buttons.
To change the current digit, the relevant parameter must be selected with the RIGHT button.
The selected digit is indicated by the "_" sign below it.
After setting the password value, pressing the SET button, the new password entered is
saved.
Note: After changing the default password value (“0000”), the new password will need to be
entered each time it is desired to enter the Settings menu.
Menu.4.3 Menu.4.3.1
Choose Language
LANGUAGE SETTINGS
Turkce :[ ]
English:[*]
It is the third of 4 different setting parameters in the device settings menu. To change the
device language, press the SET button while the Language Option page is on the screen.
On this page, select the language you want to use as the device language by pressing the
RIGHT button and there will be “*” sign next to the language you selected. After selecting the
language, you can change the device language by pressing the SET button.
To exit without changing the current language option, press the ESC button to return to the
Language Settings page.
29
Settings EDevice Settings Menu E Backlight Settings
Menu.4.4 Menu.4.4.1
Shutdown Time
BACKLIGHT SETTINGS
Time : 5 min.
30
Capacitor Calculation Table by Connection Type
R S T S T S T S N S N
0,5 KVAR 0,16 KVAR 0,16 KVAR 0,12 KVAR 0,11 KVAR 0,08 KVAR
1 KVAR 0,33 KVAR 0,33 KVAR 0,25 KVAR 0,22 KVAR 0,16 KVAR
1,5 KVAR 0,5 KVAR 0,5 KVAR 0,37 KVAR 0,33 KVAR 0,25 KVAR
2,5 KVAR 0,83 KVAR 0,83 KVAR 0,62 KVAR 0,55 KVAR 0,41 KVAR
5 KVAR 1,66 KVAR 1,66 KVAR 1,25 KVAR 1,11 KVAR 0,83 KVAR
7,5 KVAR 2,5 KVAR 2,5 KVAR 1,87 KVAR 1,66 KVAR 1,25 KVAR
10 KVAR 3,33 KVAR 3,33 KVAR 2,5 KVAR 2,22 KVAR 1,66 KVAR
20 KVAR 6,66 KVAR 6,66 KVAR 5 KVAR 4,44 KVAR 3,33 KVAR
25 KVAR 8,33 KVAR 8,33 KVAR 6,25 KVAR 5,55 KVAR 4,16 KVAR
31
Step Value Determination According to Power Analysis Samples
Table1 Table2
3 Phase Single phase Single phase Single phase
Time
L1 L2 L3 Capacitor (L1) Capacitor (L2) Capacitor (L3) Capacitor
(min.)
(kvar) (kvar) (kvar) (kvar)
According to the power analysis examples in Table 1, the capacitor structure was created in
Table 2. Intermediate values should be intervenable when creating a step structure.
Connect the highest three-phase capacitor values to the first stages.
The single phase capacitors to be used in the L1 phase have the lowest 0.50kVAr and the
highest 2.2kvAr. 0.5kVAr, 1kVAr ve 1.5kVAr single phase capacitor can be used.
The single phase capacitors to be used in the L2 phase have the lowest 0.20kvAr and the
highest 2.3kVAr.0.25kVAr, 0.5kVAr, 1kVAr ve 1.5kVAr single phase capacitor can be used.
The single phase capacitors to be used in the L3 phase have the lowest 0.40kvAr and the
highest 2.1kVAr 0.25kVAr, 0.5kvar, 1kVAr ve 1.5kVAr single phase capacitor can be used.
32
Factory Defaults
Factory Min. Max.
Menu Name Parameter Name Unit
Value Value Value
Current Trans. Menu Current Transformer Value 5/5 5/5 5000/5 A
Step Drive Time 3 1 30 sec.
Step Time Step Release Time 3 1 30 sec.
Settings
Step Discharge Time 15 1 60 sec.
Step Settling Time 400 100 3000 msec.
PFC (A/P) Active Active Active Passive -
PFC
TCR (A/P) Passive Passive Active Passive -
Settings
Offset Value 0.00 -99.00 99.00 kVAr
Step Menu Auto Step Measure. Period (A/P) Passive 0 0 26 week
Power Factor Set Value 0 -50 50 %
Correction Settings Tolerance Value 1.0 1.0 10.0 %
Baudrate 9600 1200 19200 bps.
ModBus Parity No Even Odd -
RS485
Settings Stop Bit 1 1 2 -
Modbus ID 1 1 247
Control Mode (A/P) Passive Passive Active Passive -
Operating High Voltage Value 250 240 270 V
Voltage Low Voltage Value 180 120 210 V
Settings
Delay Value 5 1 60 sec.
Control Mode (A/P) Passive Passive Active Passive -
Operating Harmonic Voltage Value 10 3 99 %
Harmonic Harmonic Current Value 50 3 99 %
Settings
Delay Value 30 1 60 sec.
Control Mode (A/P) Passive Passive Active Passive -
Generator
Set Value 20 -50 50 %
Settings
Tolerance Value 4.0 1.0 10.0 %
Inductive Alarm Value (A/P) Passive 20 1 50 %
PF Correction
Alarm Capacitive Alarm Value (A/P) Passive 15 1 50 %
Settings
Delay Value (A/P) Passive 5 1 90 min.
Device Password 0000 0000 9999 -
Settings Backligh Shutdown Time (A/P) Active 5 1 30 min.
(A/P): It can be active or passive.
33
Dimensions
Left Side
138mm
147mm
22mm
43mm
147mm
6mm
147mm
143mm
138mm
Back View
Fixing apparatus
114.5mm
138mm
147mm
34
Technicial Specifications
Contact Informations
Web: www.tense.com.tr Muratpaşa Mh., Uluyol Cd., İşkent Sanayii Sitesi, E Blok, 1. Kat,
Mail: info@tense.com.tr Bayrampaşa / İstanbul / TÜRKİYE | Tel: 0212 578 04 38 - 48
35
QUALITY SOLUTIONS
Energy and
Compensation
Rev:1.50_220523 Tracking System
Document Number: DK-094-6