Multi Level Statcom For Harmonic Reduction
Multi Level Statcom For Harmonic Reduction
Multi Level Statcom For Harmonic Reduction
Web Site: www.ijaiem.org Email: editor@ijaiem.org, editorijaiem@gmail.com Volume 2, Issue 10, October 2013 ISSN 2319 - 4847
Abstract
To improve the performance of power system, by reducing harmonics and managing reactive power, new power equipment is required. During the last decade, many control devices called Flexible AC Transmission Systems (FACTS) have been implemented. The new and dominant converters in FACTS controllers are synchronous condenser, static VAR compensator (SVC) and static synchronous compensator (STATCOM). STATCOM is one of the devices used for compensation of reactive power and harmonic reduction. This paper concentrates on harmonic reduction in two level, three level and five level diode clamped inverter based STATCOM. To verify the effectiveness, simulation will be done using MATLAB/ SIMULINK.
1. Introduction
Transmission lines when travels over large distances, they suffer with considerable losses. In order to compensate these voltage losses, many FACTS (Flexible AC Transmission Systems) devices like static VAR compensator (SVC), synchronous condenser, Static Synchronous Compensator (STATCOM). In which STATCOM is a shunt compensation device also known as ASVG (Advanced Static VAR Generator) is coupled with a transformer and connected to a transmission line [1]. It is capable of generating and or/ absorbing reactive power. The STATCOM basically consists of a step down transformer with a leakage reactance, a three phase GTO or IGBT voltage source inverter (VSI) and a DC capacitor. The AC voltage difference across the leakage reactance produces reactive power exchange between the STATCOM and power system, such that the AC voltage at the bus bar can be regulated to improve the voltage profile of power system. Day by day, the demand for the power is goes on increasing. So, the converter/ inverter used within the STATCOM should be able to withstand the increased power levels. In power electronics, the most basic controllable device is the two level converter. But, this basic device injects unwanted harmonics into the power system [2]. So, in order to overcome this problem, the term multi level is brought out in 1981[3]. The very important thing of using multilevel inverters is that creating more output steps and to reduce the Total Harmonic Distortion (THD). Three different multi level inverter topologies have been proposed. Those are diode-clamped, flying capacitor and cascade H-bridge. Out of which diode clamped multi level inverter can compensate the reactive power and reduce the Total Harmonic Distortion effectively even though with the higher levels, capacitor voltage balancing is a problem. This paper introduces a STATCOM with three level and five level inverter and mainly concentrates on Total Harmonic Distortion.
2. Operation of STATCOM:
Fig 1.One line diagram of STATCOM The STATCOM basically consists of a step-down transformer with a leakage reactance, a voltage source inverter (VSI), a capacitor in its DC side and a control system. The inverter in conventional STATCOM, switched with a single pulse per period and the transformer is connected in order to provide harmonic minimization and serve as a link between VSI and
Page 133
Fig.2. Reactive current detection principle Fig 3 shows the basic block diagram for generating the reference currents required for producing gate pulses to the switches. In this, shunt active power filter control is accomplished by monitoring the three phase line currents to the nonlinear load and the three phase line-to-neutral voltages at the load bus and then generating the three phase reference currents that should be supplied to the voltage source inverter [6]. Mathematical Analysis: In a, b, c coordinates, the a, b and c axes are fixed on the same plane, apart from each other by 2/3. The instantaneous space vectors V and i are set on the - axis and their amplitude and direction vary with the passage of time. These space vectors are easily transformed into , coordinates as follows
(1)
(2) The instantaneous active and reactive power in the , coordinates are calculated with the following expressions: P(t) = V(t).i(t) + V(t).i(t) (3)
Q(t) = -V(t).i(t) + V(t).i(t) (4) It is evident that p(t) becomes equal to the conventional instantaneous real power defined in the a, b, c reference frame.
Page 134
The expression of the currents in the plane, as a function of the instantaneous power is given by the following equation:
= The values of p and q can be expressed in terms of the DC components plus the AC Components, that is: P= Q=
(6)
The final compensating currents including the zero sequence components in a, b, c reference frame are the following:
(10)
4. Inverter Analysis:
Comparing two-level inverter topologies at the same power ratings, MLIs also have the advantages that the harmonic components of line-to-line voltages fed to load are reduced owing to its switching frequencies [6]. Two level Inverter:
Fig 3.Two level Inverter Table.1.Switching States and output voltages of two level inverter
S1 ON OFF S2 ON OFF S3 OFF ON S4 OFF ON Output Voltage Vdc -Vdc
From Fig.3, it can be observed that for two level inverter, the output voltages are Vdc and -Vdc. The switches turn on and off for every period according to the mode show in table 1. Simulation Results: A system with inductive load having R=70, L=0.2H.Voltage and current waveform before switching in STATCOM are as shown in Fig 4.
Fig.4 voltage and current waveforms without STATCOM compensation with inductive load
Page 135
Fig .5.voltage and current waveforms with STATCOM compensation with inductive load From Fig 5, it can be observed that current and voltage waveforms are in phase after STATCOM compensation. The power factor of the system becomes unity as the reactive component is provided by the STATCOM.
Fig.6. THD analysis for 2 level with and without STATCOM. Three level Diode Clamped Inverter:
Fig 7.Three phase three level Diode Clamped Multi Level Inverter Diode clamped multilevel inverter is a very general and widely used topology. DCMLI works on the concept of using diodes to limit voltage stress on power devices. A DCMLI typically consists of (m-1) capacitors on the DC bus where m is the total number of positive, negative and zero levels in the output voltage [7]. From Fig.7 one can say that for three level inverter, the output voltages are Vdc/2, 0, -Vdc/2. The switches turn on and off for every period according to the mode show in table 2. Switches Sx1, Sx3(X=1,2,3) and Sx2, Sx4 mix in pairs.
Page 136
Fig 8.voltage and current waveforms before STATCOM compensation with capacitive load From Fig.8, it can be observed that as the load has capacitive part, the current waveform leading behind the voltage waveform with certain angle. Therefore system power factor is not equal to unity. Hence there is a need of reactive power compensation for the system. A system with capacitive load having R=10, C=0.6e-3F.Voltage and current waveform of A phase after switching in STATCOM are as shown in Fig 9.
Fig 9.voltage and current waveforms after STATCOM compensation with capacitive load From Fig.9, it can be observed that current and voltage waveforms are in phase after STATCOM compensation. The power factor of the system becomes unity as the reactive component is provided by the STATCOM.
Page 137
Fig.11. Three phase five-level Diode Clamped Multilevel Inverter. Fig.11 shows a three phase five level diode clamped inverter. The order of numbering of the switches for phase A is Sa1, Sa2, Sa3, Sa4, Sa1, Sa2, Sa3 and Sa4 and likewise for other two phases. The DC bus consists of four capacitors C1, C2, C3 and C4 acting as voltage divider. For a DC bus voltage Vdc, the voltage across each capacitor is Vdc/4 and voltage stress on each device is limited to Vdc/4 through clamping diode. The middle point of the four capacitors N can be defined as the neutral point. The principle of diode clamping to DC-link voltages can be extended to any number of voltage levels. Table.3.Switching States and output voltages of five level Diode Clamped Multi Level inverter.
Simulation Results:
Fig.12. Simulink model of a system with STATCOM with capacitive load A system with capacitive load having R=10, C=0.6e-3F.Voltage and current waveform of A phase after switching in STATCOM are as shown in Fig 13.
Page 138
Fig.13. Voltage and Current waveforms after STATCOM compensation with capacitive load From Fig.13, it can be observed that current and voltage waveforms are in phase after STATCOM compensation. The power factor of the system becomes unity as the reactive component is provided by the STATCOM.
Fig.15 THD analysis for 5 level with and without STATCOM Table.4 Comparison table o total harmonic distortion for two level, three level and five level inverter based STATCOM.
Two level without with STATCOM STATCOM 29.63% 28.29% Total Harmonic Distortion Three level without with STATCOM STATCOM 28.28% 11.44% Five level without with STATCOM STATCOM 6.64% 0.8%
Table 5. Switching losses and dv/dt stress For 2 level 3level Dv/dt stess Switching losses 2Vdc 8Vdc Vdc 2Vdc
Conclusion:
From the simulation results, it is observed that STATCOM can compensate the inductive and capacitive reactive power irrespective of the levels in the inverter. Compared to two level inverter and three level inverter, five level inverter has reduced harmonic distortion, less dv/dt stress and switching losses are reduced.
Page 139
Page 140