0.85 (as given in spec) 1.3 101.10 square feet (all cylinders max) 7406.74 lbs
Net Moment about Origin "O" Must be zero Location of tower wind force 4.74 Location of cylinder wind force 5.33 Anchoring force required 2061.15 lbs Total shear force Maximum Horizontal force Number of bolts Maximum Horizontal shear Allowable shear
OK - selection passes Tension force (if moment component above is positive) Anchoring force required 2061.15 Number of anchors 3 Tensile strength required 687.05 lbs/anchor Allowable tension 3774 lbs/anchor OK - selection passes Recommend using 1/2" grade 2 bolts placed as indicated on steel support configuration drawing in cooling tower submittal package.
Engineer :______________
TFR-80 Force on cooling tower with a face area less than (101.10 ft 2) 9.39m2 9.39m x 320 kg/m 3005.6 kg Tower footing design = 3800 kg Tower structure design = 4200 kg Note: 1. Instantaneous pressure may vary significantly above and below these averages and peak pressure two or three times the mean values are possible. 2. Actual force transmitted to cooling tower will depend on surface roughness of the cooling tower. Other correction factors such as exposure coefficient, wind directionality, gust effect factor and force coefficient etc might need to be used in the determinaiton of the actual wind forces.
2 2
Date : December 23, 2006 Therflow Cooling Tower Division Therflow Cooling Tower Division