RZ1-K Power Cable
RZ1-K Power Cable
RZ1-K Power Cable
Application
For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment. A flexible power and control cable
designed for fixed applications. Manufactured with flexible conductors in order to facilitate installations with sinuous courses.
Standards
Technical Data
Temperature Rating
-15C to +90C
Conductor
Class 5 flexible plain copper conductor to
BS EN 60228:2005 (previously BS6360)
Insulation
XLPE (Cross-Linked Polyethylene) Type DIX-3
to HD603
Core Identification
1 Core: Black
2 Cores: Blue, Brown
3 Cores including Earth Core: Blue, Brown, Green/Yellow
3 Cores: Brown, Black, Grey
4 Cores including Earth Core: Brown, Black, Grey, Green/Yellow
4 Cores: Brown, Black, Grey, Blue
5 Cores including Earth Core: Brown, Black, Grey, Green/Yellow, Blue
Sheath
LSZH (Low Smoke Zero Halogen) Polyolefin to UNE 21123
Sheath Colour
Green
Voltage Rating
600/1000V
Dimensions
Eland Part Number
No. of Cores x
Nominal Cross
Sectional Area
# x mm
Nominal Thickness
of Insulation
mm
Nominal Weight
kg/Km
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
6.2
6.7
7.3
8.2
9.2
11.0
12.1
13.8
15.7
17.6
19.2
21.5
23.9
26.9
29.6
33.8
37.4
42.7
sales@eland.co.uk www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700
54
70
90
133
189
284
381
517
712
923
1165
1446
1748
2280
2829
3731
4776
6276
Issue 01.0508
A9R01025LS
A9R01040LS
A9R01060LS
A9R0110LS
A9R0116LS
A9R0125LS
A9R0135LS
A9R0150LS
A9R0170LS
A9R0195LS
A9R01120LS
A9R01150LS
A9R01185LS
A9R01240LS
A9R01300LS
A9R01400LS
A9R01500LS
A9R01630LS
Page 1 of 5
Find this product online at www.eland.co.uk | Electrical Cable | Fixed Wiring Cable
No. of Cores x
Nominal Cross
Sectional Area
# x mm
Nominal Thickness
of Insulation
mm
Nominal Weight
kg/Km
2 x 1.5
2 x 2.5
2 x 4.0
2 x 6.0
2 x 10.0
2 x 16.0
0.7
0.7
0.7
0.7
0.7
0.7
8.2
9.2
10.3
11.3
13.2
14.9
90
120
161
211
316
450
3 x 1.5
3 x 2.5
3 x 4.0
3 x 6.0
3 x 10.0
0.7
0.7
0.7
0.7
0.7
8.9
9.8
11.0
12.1
14.3
108
144
198
263
405
3 x 16.0
3 x 25.0
3 x 35.0
3 x 50.0
3 x 70.0
0.7
0.9
0.9
1.0
1.1
16.4
21.3
24.1
27.8
30.8
593
975
1319
1812
2463
4 x 1.5
4 x 2.5
4 x 4.0
4 x 6.0
4 x 10.0
0.7
0.7
0.7
0.7
0.7
9.7
10.7
12.0
13.4
15.7
129
175
243
328
505
4 x 16.0
4 x 25.0
4 x 35.0
4 x 50.0
4 x 70.0
4 x 95.0
4 x 120.0
4 x 150.0
4 x 185.0
4 x 240.0
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
18.2
24.1
26.3
31.3
36.1
40.2
44.6
49.8
56.1
64.5
749
1245
1671
2313
3204
4126
5245
6573
8050
10695
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
10.4
11.6
13.2
14.7
17.2
20.2
25.6
29.3
34.5
153
213
298
403
624
931
1555
2076
2878
5 x 1.5
5 x 2.5
5 x 4.0
5 x 6.0
5 x 10.0
5 x 16.0
5 x 25.0
5 x 35.0
5 x 50.0
sales@eland.co.uk www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700
Page 2 of 5
Find this product online at www.eland.co.uk | Electrical Cable | Fixed Wiring Cable
Conductors
Class 5 flexible Copper Conductors for Single Core and Multi-Core cables
1
Nominal Cross Sectional Area
2
Maximum Diameter of Wires
in Conductor
mm2
3
Maximum Resistance of Conductor at 20 C
Plain Wires
mm
ohms/Km
2.50
0.26
7.9800
4.00
0.31
4.9500
3.3000
6.00
0.31
10.00
0.41
1.9100
16.00
0.41
1.2100
25.00
0.41
0.7800
35.00
0.41
0.5540
50.00
0.41
0.3860
70.00
0.51
0.2720
95.00
0.51
0.2060
120.00
0.51
0.1610
150.00
0.51
0.1290
185.00
0.51
0.1060
240.00
0.51
0.0801
300.00
0.51
0.0641
400.00
0.51
0.0486
500.00
0.61
0.0384
630.00
0.61
0.0287
Electrical Characteristics
Current Carrying Capacity (amperes) and Resistance Values (ohms per kilometre)
No. of Cores x Nominal Cross
Section Area
# x mm
Voltage Drop
V/A/Km
In Earth
Amps
Amps
29
40
53
74
101
135
169
207
268
328
383
444
510
607
703
823
946
1088
29
37
46
61
79
101
122
144
178
211
240
271
304
351
396
464
525
596
17.700
11.000
7.320
4.230
2.680
1.730
1.230
0.860
0.603
0.457
0.357
0.286
0.235
0.178
0.142
0.108
0.085
0.064
26
36
49
63
86
26
34
44
56
73
34.000
20.400
12.700
8.450
4.890
sales@eland.co.uk www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700
Page 3 of 5
Find this product online at www.eland.co.uk | Electrical Cable | Fixed Wiring Cable
2 x 16.0
115
95
3.100
26
26
34.000
3 x 2.5
36
34
20.400
12.700
3 x 4.0
49
44
3 x 6.0
63
56
8.450
3 x 10.0
86
73
4.890
2.680
100
79
3 x 25.0
127
101
1.730
3 x 35.0
158
122
1.230
3 x 50.0
192
144
0.860
3 x 70.0
246
178
0.603
29.500
23
22
4 x 2.5
32
29
17.700
4 x 4.0
42
37
11.000
4 x 6.0
54
46
7.320
4 x 10.0
75
61
4.230
2.680
100
79
4 x 25.0
127
101
1.730
4 x 35.0
158
122
1.230
4 x 50.0
192
144
0.860
4 x 70.0
246
178
0.603
4 x 95.0
298
211
0.457
4 x 120.0
346
240
0.357
4 x 150.0
399
271
0.286
4 x 185.0
456
304
0.235
4 x 240.0
538
351
0.178
29.500
23
22
5 x 2.5
32
29
17.700
5 x 4.0
42
37
11.000
5 x 6.0
54
46
7.320
5 x 10.0
75
61
4.230
2.680
5 x 16.0
100
79
5 x 25.0
127
101
1.730
5 x 35.0
158
122
1.230
5 x 50.0
192
144
0.860
0.1
0.2
0.3
0.5
1.0
1.5
2.0
2.5
3.0
452
320
261
202
143
117
101
90
83
sales@eland.co.uk www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700
Page 4 of 5
Find this product online at www.eland.co.uk | Electrical Cable | Fixed Wiring Cable
Correction Factors
For air temperature other than 30C
Air Temperature
20C
25C
30C
35C
40C
45C
50C
55C
60C
Factor
1.08
1.04
1.00
0.96
0.91
0.87
0.82
0.76
0.71
10C
15C
20C
25C
30C
35C
40C
45C
50C
Factor
1.07
1.04
1.00
0.96
0.93
0.89
0.85
0.80
0.76
For soil thermal resistivity, which depends on damp, other than 2.5K m/W
Moisture degree of soil
Very Damp
Slightly Damp
Slightly Dry
Dry
Very Dry
1.0
1.5
2.0
2.5
3.0
Factor
1.18
1.10
1.05
1.00
0.96
The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable
dimensions may vary due to manufacturing tolerances.
sales@eland.co.uk www.eland.co.uk tel +44 (0)20 7241 8787 fax +44 (0)20 7241 8700