This exercise shows how the PF can be used to calculate fault currents and set an overcurrent relay. The coordination graphs will be shown and tripping calculations will be displayed.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
2/23
30 4 2014
#2
smart
Guest
The first setp is to model the network. This is done by creating a new project.
3/23
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
30 4 2014
09-04-2010, 08:00 PM
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
#3
4/23
30 4 2014
smart
Guest
As known from basic power system theory that the maximum fault current occurs at network when we have three phase fault. The figure below shows the result when parameters are defined in the PwerFactory model. The maximum fault current = 875 A as expected.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
5/23
30 4 2014
09-04-2010, 08:18 PM
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
#4
6/23
30 4 2014
smart
Guest
The next step is to define the protection relay. Right click below the transformer and select New Devices -----> Relay Model
30 4 2014
This will take you to library as shown in figure below. Choose the following relay as an example in this exercise.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c 8/23
30 4 2014
Other relays can be used if desirable. Library ----> Relays ----> Relays ----> select then Overcurrent Relays ----> GE Alstom ----> MCGG Series ----> MCGG-22.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
9/23
30 4 2014
09-04-2010, 08:29 PM
#5
smart
Guest
Now it is time to define the CT for this relay Click on Create CT as shown below
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
10/23
30 4 2014
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
11/23
30 4 2014
30 4 2014
09-04-2010, 08:47 PM
#6
smart
Guest
Now we need to display the rely using colour. Click on colour map as shown below.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
13/23
30 4 2014
Then from drop down menu select Relays, Current and Voltage Transformers as shown
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
14/23
30 4 2014
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
15/23
30 4 2014
When you click OK, the SLD shows now the line in Red where relay is connected.
09-04-2010, 09:01 PM
#7
smart
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c 16/23
30 4 2014
Guest
We need now to create the graph for the protection devices. Right click on the SLD where the relay is connected as sown below. Then select Create Time-Overcurrent Plot.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
17/23
30 4 2014
We can also click right on the graph and add the Transformer Damage Curve as shown.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
18/23
30 4 2014
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
19/23
30 4 2014
We can also select the voltage base for displaying the graphs, as shown below.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
20/23
30 4 2014
There is also of course option to display the fault current (875 A) in different colour (blue) and also the tripping time of relay (1.357 s) for that fault current.
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
21/23
30 4 2014
Quick Navigation
Top
Overview of PowerFactory Functions | National Grid of UK publishes 2011 Seven Year Statement using DIgSILENT PowerFactory
Thread Information
There are currently 1 users browsing this thread. (0 members and 1 guests)
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c 22/23
30 4 2014
Similar Threads
Replies: 1
Details of Last Post: 06-01-2012, 04:38 PM
Replies: 5
Details of Last Post: 23-02-2010, 08:42 AM
Bookmarks
Posting Permissions
You may not post new threads You may not post replies You may not post attachments You may not edit your posts
BB code is On Smilies are On [IMG] code is On [VIDEO] code is On HTML code is Off Forum Rules
Contact Us Home Archive Top Useful Links : Home Page | Contact Us | Registration | PowerFactory | News | Sectins
All times are GMT +4. The time now is 12:16 PM. All Rights Reserved to Albanah Global L.L.C
http://www.albanah.org/ss/showthread.php?228-Example-of-Over-Current-Protection-Setting-using-DIgSILENT-PowerFactory&s=c053e42d6d74e95bc505cc3af665b46c
23/23