Study of Relay Protection Modeling and Simulation
Study of Relay Protection Modeling and Simulation
Coordinate
Set events to
Set relay Short circuit
DIgSILENT PowerFactoy provides various models and End validate the
parameters calculation
parameters of electrical components from different reliability
manufacturers, which can be easily used and modified in
graphics environment, especially in power system simulation Fig. 1. The general procedure of relay protection simulation
application of new energy sources like PV, fan and stored
energy[5-7]. Meanwhile, this software can operate simulation in In relay protection simulation, the short circuit calculation
conjunction with Matlab via the interface, taking in the can be used to determine the parameter of relay protection
advantage of Matlab in processing large-scale data and control components and fuse capacity, as well as to coordinate
different protection devices. After a stable outcome achieved
Supported by The National Key R&D Plan of China (2017YFB0902801). by current analysis, this tool can be used to set short-circuit
,(((
point, select short circuits types and set up different short- output trip signal is used to control the disconnection of the
circuit conditions in a single line diagram. Based on standards circuit breaker when action is needed.
like VDE, IEC, ANSI, different calculating methods can be
chosen in the dialog boxes so as to meet the needs of the results B. Some Basic Function Blocks for Relays
in differing situations. Fig.4 displays the basic modeling frame of relays in
Then, with the result, considering the need of relay DIgSILENT, which is made up of various function blocks for
protection, users can directly add relays, fuses and element simulation. Some regular function blocks are shown as below.
such as CT or VT in the corresponding positions in the network. The measurement block is responsible for the simulation
They can choose existing relay model of each manufacturer or processing of the real part and the imaginary part of the
relay models build by themselves. Through the basic secondary voltage and current into those taken up by the other
information dialog box, users can easily revise the setting value succeeding protection function blocks, including the RMS
of relay and observe the coordination among relays via time- value, the positive and negative sequence components of
current curves and R-X graphs. currents and voltages.
Finally, the RMS simulation can set different events in The polarization block serves to provide polarized current
different positions to gain corresponding actions of relays in and voltage signal for distance protection block. The
fault, which can test the coordination and reliability of the relay calculation of input and output signals is determined by the
protection. allocation of the function blocks and the polarization method.
III. THE MODELING THEORY OF RELAY PROTECTION As a means to detect faults, the starting block is
exclusively designed for distance relays. When a fault is
A. The Modeling Frame of Relay Protection detected, a starting signal would be sent to distance block and
activates the comparison block.
DIgSILENT performs the modeling of relays through three
levels: frame, type and element. Fig.2 shows the relation The instantaneous overcurrent block would send signals
between the three levels. when the measured current exceeds the set starting current.
Meanwhile, the block also supports directional and delay
Relay Frame function. The block can protect the current when the measured
Relay Type current exceeds the starting current determined by the
characteristic curve. And, the curve can be modified by
Ranges
Types
changing the staring current or the delay.
The distance admittance block performs admittance based
on the traditional method, impedance protection. The polygon
distance block is responsible for the simulation of the
Voltage characteristics supported by modern digital distance protection
97
Relay Element
Tripping Signal
relays, in order to prevent resistance fault. The timing block
Settings Current
can defer the sending time of the trip signal from the distance
&7 * * block to the logic block.
Fig. 2. The relation between three modelling levels The logic block combines the trip signals within the other
function blocks into a comprehensive output signal into a logic
The relay frame uses box diagrams to specify the functions sum output signal to validate the trip of the circuit breaker.
of general relays. Fig.4 shows the general modeling frame of
relays, and the boxes stand for various function blocks, with
IV. SIMULATION EXAMPLES
arrow lines representing the connection between different
blocks. These boxes can be defined as measurement blocks, A. The Example of Overcurrent Protection Simulation
comparison protection blocks, logic blocks and timing blocks.
They define the function of relay protection and the relation
among them.
Relay1 Relay2 Relay3
The choice of function blocks in relay frame determines the
type of relays. DIgSILENT system has contained some relay A B C
models from manufacturers, which can be straightly used, or Fig. 3. The Simulation network of overcurrent protection
users can copy the model into the project library to revise or
remodel. Furthermore, the relay type also specifies the range of As is shown in Fig.3, the simulation network of overcurrent
the relay parameter setting. protection adopts 6kV distribution network with the respective
circuit length between nodes: 5km, 1.5km, 1.5km, and
Relay elements are used to simulate actual relays in the connects to a 0.4kV distribution network through a 10MVA
network, which is determined by the type of relay and the transformer. Add relays in the three positions, and get the
setting of parameters. It achieves operational aspect of power characteristic equation from the general math model of the
system through CT/VT installed in measuring points, and inverse time overcurrent relays:
Three-phase voltage
Three-phase current Polarize Polarizing voltage and current
Zero-sequence current block Comparison block for
distance protection
Starting signal after
Starting fault type judgment
block
Comparison block for
Secondary
overvoltage or
current
CT RMS value of three-phase voltage
undervoltage protection
Measurement
block for Comparison block for
RMS value of zero-sequence voltage
Primary phase zero-sequence
current sequence overvoltage protection
component and
to earth
component RMS value of phase current Comparison block for
Secondary phase-fault overcurrent
voltage
VT protection
Measurement
block for Frequency Comparison block for
frequency over or under frequency
protection
Lock
block
Tripping signal
0.14 K (1) The function blocks compare the signals and send the trip
t
M 0.02 -1 signal to the logic block which decides the breaker’s switch.
K refers to time setting coefficient; M=I/Iop, Iop stands for the
starting current; I, the short current flowing through a relay. Logic
measurement block. The measurement block then gives out the Ioc Ioc Toc
RMS values of three-phase current and zero sequence current Ie> Ie>> Ie
and offers them respectively to the corresponding function
blocks of the relay. The above four blocks consist of inverse Logic
adjusted according to the distance from the power supply, and 33kV
33kV
the action time limit of the succeeding relays should be one ∆t
length unit, longer than the previous ones, thus, t2= t1+∆t.
ü
S
Relay1
ü Relay2 50km
ü Relay3
Relay1 132kV
100km
Relay2
SG
a
Fig. 8. The Simulation network of distance protection
Relay3
CT
Measur Polarize Logic
ement
VT
Starting
Relay2
PGZ1 PGZ2 PGZ3
Timer Timer
Relay1
ü State variable
ü Tripping Signal
Fig. 9. The modelling frame of distance relays
ü Relay1
[3] SUN Yuanzhuang, YANG Jun, ZHANG Xiaodong㸪et al. Protection
ü Relay2 Model for Dynamic Simulation of Power System[J].Automation of
Electric Power Systems, 2009,33(20):47-51.
[4] YUAN Xin. Application of the Interface Technique Between
PSCAD/EMTDC and Matlab in Power System Simulation[J].Journal of
Electric Power, 2010,25(3):214-217.
[5] L Tao, HAN Zhen-xiang. Introduction of power system simulation
software DIgSILENT[J]. East China Electric Power,2004,12:37-41.
[6] ZHANG Xiaoping, ZHENG Wenjie, CHEN Hui, et al. Simulation and
modeling of wind power storage system based on DIgSILEN[J].
Renewable Energy Resources.2015(01),63-67.
[7] WANG Yixiao, ZHANG Xinchang, LU Jinsheng, et al. Modeling and
simulation of grid connected photovoltaic power generation system
based on DIgSILENT[J]. Power System Protection and
Control..2014(03):49-55.
Pri.Ohm [8] YUAN Tianqing, WU Xiaomei, LIU Guoxiang, et al. Simulation
Modeling for Interface between DIgSILENT and MATLAB[J].
Fig. 10. The impedance characteristic diagram of distance relays Guangdong Electric Power,2014(3):49-52.
[9] ZHANG Baohui, YIN Xianggen. Relay Protection of Power System.
The impedance characteristic of two relays can be achieved Beijing: China Power Press,2009.
by similar settings for Relay2 parameters, as shown in Fig.10 [10] DIgSILENT PowerFactory Application Guide Overcurrent Protection
Through setting up simulation events of RMS, it can be Tutorial DIgSILENT Technical Documentation[M]. Gomaringen,
concluded that relays can cooperate with each other in the Germany: DIgSILENT GmbH, 2013.
event of a fault. [11] DIgSILENT PowerFactory Application Guide Distance Protection
Tutorial DIgSILENT Technical Documentation[M]. Gomaringen,
Germany: DIgSILENT GmbH, 2013.
V. CONCLUSION
The feature of graphic and model integration of
DIgSILENT PowerFactoy, vast applications of virtual
instruments, as well as rich electrical component model, which