Shunt Reactor
Shunt Reactor
Shunt Reactor
RESEARCH ARTICLE
www.ijera.com
OPEN ACCESS
ABSTRACT
In this paper we will cover the techniques used locally to accomplish the reactive power compensation. First, the
importance of reactive power compensation is explained through defining the different types of electrical power
and showing the effect of power compensation on the electric power network quality. The power under ground
cable is the first technique used to compensate for the inductance of overhead transmission lines and power
transformers during heavy loading of the network. Then, we explore the application of the two types of shunt
reactors in different locations of the network to compensate for the capacitance of the network during light
loading. Finally, a conclusion is presented.
Key words- compensation, reactive power, shunt reactor, under ground power cable.
I. INTRODUCTION
Reactive power has been recognized as an
important factor in the design and operation of
alternating current electric power systems. Since the
impedance of the network components are mainly
reactive, the transmission of active power requires a
difference in angular phase between the voltages at
the sending end and the receiving end. While the
transmission of reactive power requires a difference
in magnitude of these same voltages. Reactive power
is consumed not only by most of the network
elements , but also by most of the consumer loads.
The required reactive power must be supplied some
where and if we can not transmit it very easily then it
must be generated at the point where it is needed. The
reactive power must be supplied at the same voltage
of the load who requires it.
Reactive power compensation is defined as the
management of reactive power flow to improve the
performance of the power system. It is related to both
the system and customers. Generally we can look to
the reactive power compensation from two aspects:
load compensation and voltage support. In load
compensation the objectives are to increase the value
of the system power factor, to balance he real power
drawn from the supply, compensate voltage
regulation and to eliminate current harmonic
components produced by large and fluctuating non
linear industrial loads [1], [2]. While voltage support
is generally required to reduce voltage fluctuation at
a given point of the system.
Recently, reactive power compensation and
control acquired more importance for at least four
reasons :first, the huge demand on electrical power,
second, the need to increase transmission capacity as
www.ijera.com
www.ijera.com
(1)
(2)
(3)
(4)
51 | P a g e
www.ijera.com
Figure 4. Phase representation of complex power for lagging power factor load
Figure 5. shows the distributed impedance of the
transmission line. The transmission line in general
can be represented by its lumped model as in Figure
6. The value of R, XL, and XC depends on the line
length and characteristics. The series inductance
reduces the line transfer capability and also results in
voltage drop. The series inductance absorbs reactive
power from the network and it must be supplied
52 | P a g e
www.ijera.com
Figure 7. Shunt reactor as a tertiary winding for 300 MVA power transformer
www.ijera.com
(5)
53 | P a g e
www.ijera.com
For 300 KV long over head transmission lines a shunt reactor of 250 MVAR is installed as in Fig. 8 to
compensate for the shunt capacitance of the transmission line.
Figure 8. Shunt reactor installed for 300 KV over head transmission line .
For 132KV long over head transmission lines a
50MVAR shunt reactor is connected as shown in Fig.
9.
For 132/11 KV substations a shunt reactor is
installed as a feeder panel with a reactive power of 45
V.
CONCLUSION
www.ijera.com
REFERENCES
[1]
[2]
[3]
[4]
[5]
www.ijera.com
55 | P a g e