Model TA-2100 Allyl Alcohol Gas Detector: Smarter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

Glycol Production

Chemical Processing
Plastics Production
Laboratories
Optical Resins
Paints & Coatings
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Allyl Alcohol Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0-50 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26177
Water Treatment
Wastewater Treatment
Refrigeration
Chemical Processing
Pulp & Paper
Food & Beverage
Laboratories
Metal Treatment
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Ammonia NH3 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 200 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 5 ppm
Temperature Range: -40C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <60 sec. to 90% of final reading
Recovery Time: <2 min. to 90% recovery
Sensor Service Life: >2 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2611
Water Treatment
Wastewater Treatment
Refrigeration
Chemical Processing
Pulp & Paper
Food & Beverage
Laboratories
Metal Treatment
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Ammonia NH3 MOS Gas Detector
Detection Principle: Solid State MOS
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 300 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 5 ppm minimum detection level
Zero Drift: less than 5 ppm
Temperature Range: -40C to +75C
Humidity Range: 5 - 100% RH, non-condensing
Response Time: <20 sec. to 50% of final reading
Recovery Time: <20 sec. to 50% recovery
Sensor Service Life: >3-5 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms solid state MOS sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +75C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26159
Semiconductors
Chemical Processing
Lead Plating
Galvanizing
Battery Production
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Arsine AsH3 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.00 - 1.00 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.01 ppm minimum detection level
Zero Drift: less than 0.02 ppm
Temperature Range: -20C to +40C
Humidity Range: 15 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >2 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +40C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2640
Oil Refining
Chemical Processing
Pharmaceuticals
Pesticides
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Benzene Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26144
Water Purification
Chemical Processing
Flame Retardants
Pharmaceuticals
Bleaching Agents
Laboratories
Disinfectants
Pesticides
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Bromine Br2 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 5.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2603
Rubber Production
Chemical Processing
Plastics Production
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
1,3-Butadiene Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0-100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26185
Chemical Processing
Pharmaceuticals
Plastics Production
Laboratories
Pesticides
Rubber Vulcanization
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
N-Butylamine Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -200 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26186
Beverage Carbonation
Chemical Processing
Lasers
Oil Well Injection
Natural Gas Pipelines
Laboratories
Metal Production
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
IR Infrared Carbon Dioxide CO2 Gas Detector
Detection Principle: Infrared (NDIR)
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 5% Volume (ranges to 100% CO2)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1% Vol. minimum detection level
Zero Drift: less than 0.1% volume
Temperature Range: -20C to +50C
Humidity Range: 0 - 99% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >5 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms infrared (NDIR) sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26116
Rayon Manufacturing
Chemical Processing
Cellulose Production
Agricultural Fumigants
Metal Plating
Cellophane Production
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Carbon Disulfide Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -200 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26181
Lasers
Chemical Processing
Confined Spaces
Air Quality Management
Combustion Processes
Industrial Emissions
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Carbon Monoxide COGas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 200 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 3 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <60 sec. to 90% recovery
Sensor Service Life: >2 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2622
Water Purification
Chemical Processing
Pulp & Paper Mills
Pharmaceuticals
Plastics Production
Laboratories
Swimming Pools
Agrochemicals
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Chlorine Cl2 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 5.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -40C to +50C
Humidity Range: 10 -95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2601
Water Purification
Wastewater Treatment
Pulp & Paper Mills
Chemical Processing
Food Processing
Laboratories
Sanitation
Biocidal Uses
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Chlorine Dioxide ClO2 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 5.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2604
Pesticides
Chemical Processing
Metal Degreasing
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Chlorobenzene Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -50 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26183
HCFC-22 Production
Chemical Processing
Pesticides
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Chloroform CHCl3 MOS Gas Detector
Detection Principle: Solid State MOS
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 250 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 5 ppm minimum detection level
Zero Drift: less than 5 ppm
Temperature Range: -40C to +75C
Humidity Range: 5 - 100% RH, non-condensing
Response Time: <30 sec. to 50% of final reading
Recovery Time: <30 sec. to 50% recovery
Sensor Service Life: >3-5 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms solid state MOS sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +75C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26169
Oil & Gas Exploration
Chemical Processing
Oil Refining
Steel Mills
Mud Logging
Laboratories
Natural Gas Distribution
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Catalytic LEL Combustible Gas Detector
Detection Principle: Catalytic bead LEL combustible
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 100% LEL (lower explosive limit)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1% LEL minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -40C to +75C
Humidity Range: 0 - 99% RH, non-condensing
Response Time: <10 sec. to 50% of full-scale
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. locations
Specifications Applications
Features
no false alarms catalytic bead sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +75C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2620
Oil & Gas Exploration
Chemical Processing
Oil Refining
Steel Mills
Mud Logging
Laboratories
Natural Gas Distribution
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
IR Infrared Combustible Gas Detector
Detection Principle: Infrared (NDIR)
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 100% LEL (lower explosive limit)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1% LEL minimum detection level
Zero Drift: less than 1% of full scale
Temperature Range: -40C to +65C
Humidity Range: 0 - 99% RH, non-condensing
Response Time: <10 sec. to 50% of full-scale
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >5 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. locations

Specifications Applications
Features
no false alarms infrared (NDIR) sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +65C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26140
Nylon Manufacture
Chemical Processing
Refinery Emissions
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Cyclohexane Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0-200 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26172
Semiconductors
Chemical Processing
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Diborane B2H6 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.00 - 1.00 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.01 ppm minimum detection level
Zero Drift: less than 0.02 ppm
Temperature Range: -20C to +40C
Humidity Range: 15 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >2 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +40C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2641
Industrial Solvents
Chemical Processing
Pesticides
Pharmaceuticals
Plastics Production
Laboratories
Synthetic Leathers
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Dimethylformamide DMF Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26201
Nuclear Power
Chemical Processing
UF
6
Production
SF
6
Production
Semiconductors
Laboratories
Freon Production
Water Treatment
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Fluorine F2 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 5.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2602
Rocket Propellent
Chemical Processing
Military Fuel Cells
Nickel Plating
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Hydrazine N2H4 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.00 - 1.00 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.01 ppm minimum detection level
Zero Drift: No data
Temperature Range: -20C to +40C
Humidity Range: 15 - 95% RH, non-condensing
Response Time: <90 sec. to 90% of final reading
Recovery Time: <60 sec. to 90% recovery
Sensor Service Life: >12 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +40C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2643
Plasma Etching
Chemical Processing
Electronics
Pharmaceuticals
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Hydrogen Bromide HBr Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 20.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <60 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2616
Hydrochloric Acid
Production
Chemical Processing
Semiconductor
Electroplating
Metal Cleaning
Textile Production
Rubber Production
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Hydrogen Chloride HCl Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 20.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <60 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2606
Precious Metal Extraction
Chemical Processing
Synthetic Fiber Production
Electroplating
Plastics Production
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Hydrogen Cyanide HCN Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 50 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <60 sec. to 90% recovery
Sensor Service Life: >2 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2615
Oil Refining Process
Chemical Processing
Metal Pickling
Uranium Conversion
Aluminum Production
Laboratories
Water Treatment
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Hydrogen Fluoride HF Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 20.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 -95% RH, non-condensing
Response Time: <60 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2607
Chemical Processing
Pharmaceuticals
Laboratories
Disinfectants
Reductive Chemistry
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Hydrogen Iodide HI Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 20.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <60 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.

Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2609
Oil & Gas
Chemical Processing
Pulp & Paper Mills
Sewage Treatment
Leather Tanning
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Hydrogen Sulfide H2S Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 50 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1 ppm
Temperature Range: -40C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2610
Oil & Gas
Chemical Processing
Pulp & Paper Mills
Sewage Treatment
Leather Tanning
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Hydrogen Sulfide H2S MOS Gas Detector
Detection Principle: Solid State MOS
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 2 ppm
Temperature Range: -40C to +75C
Humidity Range: 5 - 100% RH, non-condensing
Response Time: <30 sec. to 50% of final reading
Recovery Time: <30 sec. to 50% recovery
Sensor Service Life: >3-5 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms solid state MOS sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +75C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26127
Chemical Processing
Pharmaceuticals
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Iodine I2 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 5.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2628
Aviation Fuels
Jet Turbine Engines
Kerosene Uses
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Jet Fuel (Jet A - JP - 8) Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0-100 ppm (parts-per-million )
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26190
Water Purification
Chemical Processing
Gas & Oil Treatment
Paper Production
Pharmaceuticals
Laboratories
Resin Production
Agrochemicals
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Methylamine Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0-200 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26187
Degreasing
Chemical Processing
Paint Stripping
Aerosol Propellents
Plastics Production
Laboratories
Wood Stains & Finishes
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Methylene Chloride Me-Cl2 Gas Detector
Detection Principle: Solid State MOS
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 250 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 5 ppm minimum detection level
Zero Drift: less than 5 ppm
Temperature Range: -40C to +75C
Humidity Range: 5 - 100% RH, non-condensing
Response Time: <30 sec. to 50% of final reading
Recovery Time: <30 sec. to 50% recovery
Sensor Service Life: >3-5 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms solid state MOS sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -40C to +75C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26165
Paints & Coatings
Chemical Processing
Industrial Cements
Plastics Production
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Methyl Ethyl Ketone Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -200 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26192
Chemical Processing
Food Processing
Explosives Production
Dye Production
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Nitric Acid Vapor HNO3 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 20.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <60 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2612
Nitric Acid Production
Chemical Processing
Semiconductors
Laboratories
Agrochemicals
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Nitric Oxide NO Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 3 ppm
Temperature Range: -25C to +50C
Humidity Range: 15 - 90% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <45 sec. to 90% recovery
Sensor Service Life: >2 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2623
Nitric Acid Production
Chemical Processing
Industrial Emissions
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Nitrogen Dioxide NO2 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 20.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <45 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2605
Aerospace
Chemical Processing
Pulp & Paper Mills
Boilers
Combustion Processes
Gasification
Steel Mills
Pharmaceuticals
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Oxygen O2 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 25.0 % Volume
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 % Vol. minimum detection level
Pressure Coefficient: 0.01% signal/mBar
Temperature Range: -15C to +40C
Humidity Range: 15 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >12 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loca. avail.
Specifications Applications
Features
no false alarms electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -15C to +40C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2625
Semiconductors
Chemical Processing
Grain Fumigation
Tobacco Fumigaton
Flame Retardants
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Phosphine PH3 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.00 - 1.00 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.01 ppm minimum detection level
Zero Drift: less than 0.02 ppm
Temperature Range: -20C to +40C
Humidity Range: 15 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >2 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +40C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2645
Semiconductors
Chemical Processing
Solar Panel Production
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Silane SiH4 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 50.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.3 ppm
Temperature Range: -20C to +40C
Humidity Range: 15 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >2 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +40C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2646
Styrene Polymer
Production
Chemical Processing
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Styrene Monomer Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26171
Sulfuric Acid Production
Chemical Processing
Pulp & Paper Mills
Food & Beverage
Dried Fruit Production
Fruit Preservatives
Fungicides
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Sulfur Dioxide SO2 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 20.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <60 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2608
Chemical Processing
Battery Rooms
Fertilizer Production
Pharmaceuticals
Laboratories
Detetergents
Insecticides
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Sulfuric Acid Vapor H2SO4 Gas Detector
Detection Principle: Electrochemical - Amperometric
Detection Method: Diffusion or Sample Drawing
Detection Range: 0.0 - 20.0 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.08 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 0.1 ppm minimum detection level
Zero Drift: less than 0.1 ppm
Temperature Range: -25C to +50C
Humidity Range: 10 - 95% RH, non-condensing
Response Time: <60 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >3 years typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Certifications: CSA, Class I GR B,C,D haz. loc. avail.
Specifications Applications
Features
no false alarms patented electrochemical sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -25C to +50C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Available suitable for use in SIL 2 environments / Advanced diagnostics
Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2614
Paint Manufacturing
Chemical Processing
Metal Degreasing
Electroplating
Pharmaceuticals
Laboratories
Pesticides
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Toluene Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26216
Electroplating
Chemical Processing
Iron & Steel Production
Metal Degreasing
Paper Production
Laboratories
Rubber Production
Semiconductors
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Trichloroethylene Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26184
Chemical Processing
Degreasing
Cleaning Solvents
Disinfectants
Laboratories
Paints & Varnishes
Pesticides
Industrial Emisssions
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
PID VOC Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 - 200 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26114
PVC Production
Chemical Processing
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Vinyl Chloride Monomer Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -250 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-2669
Cleaning Agents
Chemical Processing
Paint Thinners
Aviation Fuels
Pesticides
Laboratories
More
Specifications subject to change without notice
due to continued program of product
innovation.
Model TA-2100 smarter
Xylene (-o, -m, -p) Gas Detector
Detection Principle: PID Photo-Ionization
Detection Method: Diffusion or Sample Drawing
Detection Range: 0 -100 ppm (parts-per-million)
Calibration Method: Non-intrusive, magnetic tool
Operating Voltage: 12 - 30 VDC, 24 VDC nominal
Power Requirements: 1.82 W @ 24 VDC
Electrical Connections: Power (24 VDC) and Signal (4-20mA)
Cable Requirements: 3 or 4 wires, shielded
Optional Connections: RS-485 Half-duplex (Modbus RTU)
Resolution: 1 ppm minimum detection level
Zero Drift: less than 1% of full-scale
Temperature Range: -20C to +55C
Humidity Range: 5 - 95% RH, non-condensing
Response Time: <30 sec. to 90% of final reading
Recovery Time: <30 sec. to 90% recovery
Sensor Service Life: >18 mos. typical; normal conditions
Electronic Enclosure: Ex-Proof, alum. or 316 SS, Nema 4x
Enclosure Certifications: CSA/UL/FM Class I GR B,C,D
Specifications Applications
Features
no false alarms PID Photo-Ionization sensor technology
Self-Calibration adjusts monthly based on sensor life curve
Auto-Gas Calibration, non-intrusive, hands-free, magnetic switches
Not affected by temperature -20C to +55C, stable by design
LCD display - 12 characters x 2 lines - provides user interface with
magnetic switches - no dip switches - LED alarm indicators
Offsite sensor calibration with memory chip embedded in sensor
Peak Value, 15-min. TWA, Remaining Sensor Life, Replace Sensor
indication and number of days since last gas calibration
Optional Relay Module; low, mid, high and fault conditions
Optional RS-485 Modbus RTU Network interface
Advanced diagnostics - continuous on-board systems monitoring

Options
- Modbus RTU
- Relay Module
- Sensor Cable
- Sample Pump
- Duct Mount Kit
- Dust Guard
- Splash Guard
- Wireless Module
- 110/220 VAC
- Calibration Kits
- 316 SS Enclosure
Part No. 01-26145