Js 800kv-Hvdc Design

Download as pdf or txt
Download as pdf or txt
You are on page 1of 35

JS Hardware

HARDWARE AND FITTINGS DESIGN for +- 800kV HVDC Line


JS HARDWARE CHINA www.js-hardware.com
1. Project Background:
At 09:57am, October 26, 2009, the Pole I of 800kV DC system in the Fengxian
Converter Station and the transmission line of the independently designed and
constructed Xiangjiaba-Shanghai 800kV UHV DC Demonstration Project were stepped
up to 800kV, indicating the successfully energization of the worlds first DC transmission
project with the largest capacity, longest distance, most advanced technology and
highest voltage.
The project pioneers in the world making breakthroughs in both DC transmission voltage
and current, opening a new era for DC transmission technology and setting up a
milestone for international power industry. The successful energization of the UHV DC
project is of great importance to the buildup of strong and smart grid with UHV
transmission grid as the backbone and coordinated development of its subordinate
networks. It is a leading innovative project in international DC transmission technology,
which will provide important basis for independent development of domestic UHV
equipment manufacturing capability and contribute to the energy distribution in ultra-large
capacity and ultra-long distance. The success of the project will have great significance
and profound influence on the scientific development and innovation of the power
industry, the development of major energy bases and large-scale power delivery, the
acceleration of clean energy development, and the requirement of the soaring power
demand in Eastern China.

The 800kV HVDC transmission line


Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware

Hardware fittings installation at river crossing

The test of spacer damper

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware

The inspection for Vibration damper


2. Insulator String and Fittings
2.1 Principle for Selection
2.1.1 Basic Requirements
(1) The configuration of insulator string first should meet the requirements of mechanical
strength and electrical strength, mechanical strength is mainly control by the maximum load
under normal line working conditions, for electrical strength, it mainly means that the insulator
string should not decrease insulation level, and controls the insulator string field strength and
should be in conformity with electromagnetic environment standard; secondly, economic cost
of various types of strings combinations should be fully considered to ensure the safety,
reliability, economy and reasonability of insulator string type design; string configuration
should be simplified to the best extend.

(2) Single part weight and size of line fittings should try to reduce to facilitate transportation
and installation; It should pay more attention to the ductility of the material when use high
strength material to avoid crisp fracture; mature technology, mature material and mature
technical processing should be adopted; try best to simplify fittings structure, reduce fittings
quantity; the fittings should be with strong exchangeability to facilitate the maintenance to the
line; external forces on the fittings should shared evenly and reasonably to meet various load
requirements while the line is working.
Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
Spacer should be with good mechanical performance to ensure reliable mechanical strength
with reasonable weight, goods damping performance and ability to endure long time fatigue
vibration.

The corona free design of the line should satisfy the needs of ensuring insulator working
normally under 800kV voltage, radio interference created should be in conformity with the
regulations and requirements specified in GB/T2317.2-2000 Electrical Fittings

Corona

and Radio Interference Tests. It must be ensured that no corona will be discharge during the
normal working of fittings.

2.1.2 Safety Coefficient


Mechanical strength safety coefficient of the insulator shall be in conformity with Technical
Regulations of 800kV Overhead Power Transmission Lines Design (for discussion), the
mechanical strength safety coefficients of the insulator and fittings are as following:
Table 2-1 Safety Coefficient of Insulator and Fittings
Maximum
working load

Line broken

Joint Broken

Normal Load

Disk
2.7
1.8
1.5
Insulator
Fittings
2.5
1.5
1.5
Note: Composite insulator safety coefficient is supposed to be at 3.0.

4.0

2.1.3 Determination of Conductor Average Height and Calculation Base


The average height of the conductor line is defined to be at 28 m for this engineering
(corresponding height from the conductor line to the ground is 20 m). The tensile sag
calculation of conductor and earth wire are based on the wind velocity at 28 m and 38 m
heights respectively.
Table 2-2 Wind Velocity when in Gale and Over Voltage Working Condition
Height
10m (base)
Gale
28m
Over Voltage
38m
Gale

27
31.8
15.9
33.4

Wind Velocitym/s
28
30
33
35.4
16.5
17.7
34.7
37.1

32
37.7
18.8
39.6

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

35
41.3
20.6
43.3

JS Hardware
2.1.4 Standard Value of Wind Load
Wind pressure uneven coefficient, wind load adjustment of conductor and earth wire,
coefficient c shall be determined according to the following table:
Table 7-2 Wind Pressure Uneven Coefficient and Conductor and Ground Line Wind Load
Adjustment Coefficient c (10 M from the Ground)
Base Wind Velocity V(m/s)
27V<31.5
31.5
Calculate Tower Load
0.75
0.70

For the calculation of coefficient to a smaller span as jump line etc., it is better to set at
1.0
Wind load increasing coefficient of conductor, earth wire and tower shall be considered when
in ice covering condition (including uneven ice). Values are to be determined as per the
following table:

Table 2-3 Wind Load Increasing Coefficient of Covering Ice Conductor, Earth wires and
Tower
Thickness of Covering Ice
mm

Wind Load Increasing Coefficient of Conductor, Earth wire


and Insulator in ice covering condition

10

1.2

15

1.3

20

1.5

>20

1.5

2.2 Mechanical Load


Conductor used for the Ice area under 20 mm shall adopt 6ACSR-720/50, while those under
30 mm is temporarily defined to be 6AACSR720/50 steel core aluminum alloy stranded
lines. The wind velocity is defined according to the conditions as 10 m high above ground,
once 100 years, average 10 minutes' maximum wind velocity which is also the base design
base wind velocity is at 27m/s, 28m/s, 30m/s, 32m/s and 35m/s.The designed covering ice
includes 10 mm light ice, 15 mm medium ice, 20 mm heavy ice and 30 mm heavy ice etc.
Based on tower plan conclusion, the total load of each type of tower is as following:

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
Table 2-4

Light Ice Area Conductor Insulator String (V String) Load

Tower Type

Shifting Angle Coefficient V Type String Angle ()

Comprehensive
Load (kN)
K=2.7

K=3

Section IV27/28/30 m/s b10mm H<1000m


90
440
488
90
499
554
90
588
653
90
706
784
90
824
916
90
1002
1114

Single Leg Load


(kN)

Tonnage

Single
Leg
Joints
Number

K=2.7

K=3

343
389
458
548
641
781

381
432
509
609
713
867

400kN
400(240)kN
240(300)kN
300(400)kN
400kN
300kN

1
1(2)
2
2
2
3

Z27101
Z27102
Z27103
Z27104
Z27105
Z27106

0.8
0.75
0.7
0.65
0.7
0.7

ZK2710

0.6

90

617

685

477

530

300kN

0.7

60/30

590

655

495

549

300kN

0.7

63/30

717

796

653

725

400kN

Section IIV32m/s b=10mm H<500m


90
381
423
95
440
489
95
499
555
100
559
621
100
707
785
90
381
423
95
440
489
95
499
555

299
357
423
527
661
299
357
423

332
397
469
585
734
332
397
469

400kN
400kN
240kN
300kN
400kN
400kN
400kN
240kN

1
1
2
2
2
1
1
2

ZJ27101
(3-12)
ZJ27102
12-20
ZV3210-1
ZV3210-2
ZV3210-3
ZV3210-4
ZV3210-5
ZVF3210-1P
ZVF3210-2P
ZVF3210-3P

0.8
0.75
0.7
0.65
0.65
0.8
0.75
0.7

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
ZVK3210-1
(ZVK3210-1P)
ZVK3210-2
(ZVK3210-2P)
ZVK3210-3
(ZVK3210-3P)
ZVJ3210-1
3-12
ZVJ3210-212-20
ZV3510-1A
ZV3510-2P
ZV3510-3P
ZV3510-4P
ZVK3510-1P
ZVK3510-2P
ZVJ3510-1P
3-12
ZVJ3510-2P
12-20
Z27151
Z27152
Z27153
Z27154
Z27155

0.9

90

588

653

460

511

300kN

0.9

90

558

620

435

484

240(300)kN

0.9

90

528

587

411

457

240kN

0.75

60/40

540

600

533

592

300kN

0.75

60/30

624

694

621

690

400kN

Section IIIV35m/s b10mm H<500m


95
351
390
100
440
489
100
499
555
115
559
621
90
646
718
90
558
620

286
372
467
555
501
432

317
414
519
617
557
480

400kN
400(240)kN
240(300)kN
300(400)kN
300kN
240kN

1
12
2
2
2
2

0.85
0.8
0.75
0.7
0.9
0.9
0.75

60/45

540

600

590

656

300(400)kN

0.75

60/30

624

694

602

669

400kN

411
468
552
638
753

456
520
614
709
837

240kN
240(300)kN
300(400)kN
400kN
400(300)kN

2
2
2
2
2(3)

0.75
0.7
0.65
0.7
0.7

Section IVV27/28 m/s b15mm H<1000m


90
529
588
90
602
669
90
712
791
90
821
913
90
931
1035
Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
Z27156
ZK2715
ZJ2715
3-12
Z30151
Z30152
Z301531
Z301532
Z30154
Z30155
Z30156
ZK3015
ZJ3015
3-12
Note:
5%
increasing

0.7
0.8

90
90

1150
784

1278
872

928
606

1031
673

400kN
400kN

3
2

0.75

60/35

694

771

560

622

300(400)kN

Section VV30m/s b15mm H<1000m


90
529
588
95
602
669
100
712
791
95
712
791
95
821
913
95
931
1035
95
1150
1278
90
784
872

467
531
628
662
764
869
1071
689

519
240kN
590
300kN
697
400kN
735
400kN
849 400(300)kN
965 300(400)kN
1190
400kN
766
400kN

632

702

0.75
0.70
0.65
0.7
0.7
0.7
0.7
0.8
0.75
of

60/40

suspension

point

tension

694
has

been

771

considered

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

for

400kN

tension

string

2
2
2
2
2(3)
3
3
2
2
load.

JS Hardware
Table 2-5 Allowed Vertical Span for Suspension V String in Heavy Ice Area (m)
Allowed Vertical Span for Suspension Stringm

Number of
Strings x Strength

2300kN

2400kN

2550kN

4210kN

4300kN

4400kN

4550kN

3180

3380

3780

5050

6600

7200

8000

260

430

640

390

660

990

1420

LH=300

175
157

340
275

550
430

300
235

570
430

900
670

1325
980

LH=500
LH=300

110

200

345

155

350

590

900

LH=500

String Weight
(kg)
20mm

30mm
Note:

Remark

70

70

a. 20 mm ice area adopt conductor of 6ACSR720/50 and 30 mm ice area adopt conductor of 6AACSR-720/50 steel core
aluminum alloy
stranded lines.
b. Effect of string weight has been considered for the vertical load calculation.
c. Control working condition is ice covering condition.
d. Typical span is 350 m.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
2.3 Insulator String Assembly Type in Light Ice Area
Subject to the conclusion of Book IV Volume VI of Study on the Insulator
Coordination and Insulator Type Selection, the insulator can be ceramic, glass,
composite or post insulator, while disk insulator or composite insulator can be
used as suspension insulator in light polluted area, which should be selected
according to the weather conditions, working experience and insulator string
configuration along the line. Suspension insulators in medium polluted area and
severely polluted area are using composite insulators. Disk insulators are applied
as tension insulators.

2.3.1 Conductor Suspension String


1) String Type Selection
Normally there are I string and V string for conductor suspension string, V string
can reduce conductor spacing and further reduce the tower single base weight,
decrease corridor width, lessen house demolition, reduce trees felling and
electromagnetic environment impacts, besides, V string is better than I string
under same string length, except that the number of insulators is double as that
of I string. Upon comprehensive comparison while in consideration of
macroeconomic and social benefits, V string arrangement is recommended for
suspension insulator string.

In this connection, V type insulator string is recommended to be used as the


conductor suspension string in light ice area of this engineering. L type insulator
string is recommended for tangent angle tower.

2) V Type String
800 line has far more a string length than that of a normal 500kV line due to the
requirements of insulating configuration, forces on the insulator after being
pressured is better than that for 500kV line, the selection of the angle may be
different, we have carried out specialized research on this point, which is based
Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
on the pressure test research of V type insulator string of 500kV line.

According to the research results of V type insulator string voltage tests by


Southwest Electric Power Design Institute and Wuhan High Voltage Research
Institute, when the maximum offset angle of windward leg insulator is between
911, the Insulator pin stress value is related with V type clamp angle, which
shows a maximum value when the angle is at 110and a minimum value at 70
90(where the maximum horizontal load is only around 50% as that at 110). For
disk type insulator, when V string angle is at 110, it is suggested to control the
maximum offset angle of the windward leg insulator string within 7, in the
consideration that the safety coefficient of the Insulator pin should not be less
than 2.5; for V string with an angle of 9070, the maximum offset angle can
add 911; with consideration of the frequency of voltage, surging effect and
electrical clearance reduction etc., the actual angle for insulators controlling
during the engineering process is within 5, which shows no broken or damage of
the insulators by far. Based on calculation, V string angle is at 90100 in light
ice area of this engineering.

According to the requirements of the tower load, the maximum single leg joint
number of V type string will be 3300kN and 3400kN, for some rare towers
which are with large load and in need of using single leg three joints (3300kN or
3400kN), on one hand, 550kN single leg double joints insulators can be used to
meet the engineering requirements, on the other hand, optimize tower position
when in construction drawing stage to avoid relatively big vertical span. With the
above considerations, it is suggested that the first choice for this engineering
should be single leg single joint and double joints strings, single leg triple joints
strings shall be reserved. In consideration of the significance of super high
voltage line and the properties of the insulator (crisp fracture problem), it is
suggested that double joints mode be adopted when using composite insulator
for suspension string to ensure the safety of this engineering. Each leg 1400kN,
Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
2210kN, 2300kN, 2400kN, 2530kN types of strings are recommended to be
used for conductor V type suspension insulator strings in light ice area of this
engineering. Each leg 2240kN , 2300kN, 2400kN, 2550kN types of strings
are recommended to be used for V type composite insulator strings.

Refer to the following for single joint and double joints V string arrangements in
light ice area:

Figure 2-1 Schematic Diagram for Single Joint and Double Joints V String in Light Ice
Area

4) L Type String

L type string is used in small tangent angle tower, as per calculation, 2300kN
and 2400kN combination should be adopted for L type string, the angle of which
are 60+30, 60+35, 60+40 and 60+45 respectively, with double hanging
points, refer to the following for L type string arrangements:

Figure 2-2 Schematic Diagram of L Type String Arrangement in Light Ice Area
Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
2.3.2 Conductor Tension String

1) Tension String Type


The maximum load of tension string in 10 mm ice area is 372.96 kN, tension
string insulator strength is required to be 1007kN. While that in 15 mm ice area is
408.52 kN, and a tension string insulator strength of 1103 kN is required. Tension
string can be the types as 2550kN10mm ice area, 3400kN or 4300kN,
the safety coefficients of these type when in broken joints and normal load
conditions are in conformity with the regulations.

For the above tension string types, if one hanging point is used, when the fitting
connected to the tower is malfunctioning, this is a sign that the malfunction phase
conduction connects to ground directly which will cause severe accident, in the
consideration of the significance of this engineering and the designing and
operation experiences of domestic super high voltage line, independent hanging
point for each joint is suggested for double joints and triple joints strings, and
double hanging points is suggested for a quadruple tension string. To facilitate
maintenance, horizontal arrangement type is suggested for tension strings.

2) Comparison of Tension Strings

Technically, 2550kN horizontal arrangement tension string is with simple


structure, least insulator number, balanced force for each joint, lower accident
probability and convenient for maintenance, it is the mature and commonly used
tension string type in previous super high voltage power transmission
engineering, however, it is with relatively small margin of mechanical strength
and restricted working conditions, which means it can only be used in some parts
of 10 mm ice area; 3400kN horizontal arrangement tension string has a more
complicated structure than double joints type and a simpler structure than
quadruple joints type, with balanced force in each joint, with successful running

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
experiences in the domestic 500kV and large spanning line; 4300kN horizontal
tension string is with the most complicated structure, the most insulator number,
higher insulator failure rate and largest maintenance workload.

Economically, 300kN, 400kN, and 550kN are all meeting the requirements of this
engineering, set light polluted area for example, the insulator cost for each base
tower is as following:

Table 2-6

Tower Insulator Cost

Insulator Strength
(kN)

Number
of Joints

300
400
550

4
3
2

Number
of
Insulators
56
64
58

Cost for Each base Tower


(10 thousand yuan)
37.63
36.10
39.44

From the above we can see: triple joints 400kN insulator is with competitive price,
the issue to be cleared is the influences on the weight of the tower of the three
types insulator strings. According to previous experiences, quadruple joints
300kN, triple joints 400kN and double joints 550kN insulator string types are with
little influence to the tower weight, price will be the dominant factor, assuming
515 bases for the whole line tension towers, when calculating at a minimum price
difference of RMB 15.3 thousand, there will be a saving of RMB 7.88 million for
the whole line when using triple joints 400kN type, this is a considerable amount
for this engineering, the triple joints 400kN insulator string is with obviously
lowest price, quadruple joints 300kN is with a higher price and double joints
550kN, the highest. Above all, the least joints 3400kN tension string in light ice
area is suggested to be the first choice, and 3400kN, the second choice,
2550kN (light ice area), the third choice. Refer to the following for the assembly
of the first recommendation 3x400kN tension string:

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware

Figure 2-4 Schematic Diagram of Light Ice Conductor 3400kN Tension String

2.3.3 Joints Spacing


The distance between the strings of multiple joints is determined based on the
field strength distribution of the insulator string and the premise of non-contact
and non-collision when the insulators between the joints are under working
conditions, which means the distance between the joints of the strings is
determined by the electrical and mechanical performances of the insulator strings.

For electrical performance, according to the analysis of the pollution voltage test
results carried out by science research units for DC double joints insulator strings
in high altitude areas, when SDD/ESDD is under a working condition of
0.05mg/cm2 and the net spacing of dual joints parallel strings of bell type
insulators is large than 200 mm, the discharging can be developed independently,
but flashover probability is increased, therefore the pollution flashover voltage of
dual joints parallel strings is lower than that of single joint strings, when the net
spacing of dual joints strings is at 200 mm and 500 mm respectively, the pollution
flashover voltage is 2.03% and 5.08% lower respectively than that of single joint
strings. Under a salt concentration of 0.10 mg/cm2, when the net spacing of dual
joints parallel strings is at 500 mm, the discharging can be developed
Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
independently, the pollution flashover voltage of dual joints parallel strings is 3.9%
higher than that of single joint strings, which indicates a little difference between
the pollution flashover voltages of dual joint parallel strings and the single joint
strings. When in heavy ice, smaller joints spacing will cause the filling up of the
clearance between the joints by ice, which will bridge the insulators and decrease
ice cover voltage of the insulator, in this case, it is necessary to enlarge the joints
spacing to improve electrical performance.

For mechanical performance, as 800kV insulating string is longer, when


determining the spacing between the joints, not only the disk diameter of the
insulator, but also the shifting of insulator strings due to wind load function should
be considered. After calculation, the maximum shifting is about 24 mm, together
with the disk diameter of 400 mm, the total joints spacing should not be less than
424 mm. If the spacing is more than the above value, it can be ensured that there
will be no collision of insulators under such an assembly.

The determination of joints spacing should be carried out on the premise that the
mechanical performance can satisfy a safety working, while with the control
condition that the pollution flashover voltage of double joints structure is not less
than that of the single joint structure; for the 400 mm large insulator used in this
engineering, it is considered that 20 cm net spacing between the joints can
satisfy the requirements for pollution flashover voltage; it is suggested that a
basic spacing of 650 mm be used for suspension insulator strings and tension
insulator strings.

It is suggested that the science research units to carry out tests of joints spacing
to verify the relationship between the pollution flashover voltage of double joints
structure and that of single joint structure.

Refer to the following for the recommended values of the joints spacing for

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
multiple joints insulator strings in this engineering.
Table 2-7 Recommended Values of the Conductor Joints Spacing
Ice Area
Light Ice Area

Suspension String
650mm

Tension String
650mm

2.4 Insulator String Assembly Type in Heavy Ice Area


According to the conclusion in Technical Research of Heavy Ice Area Line
Design, disk insulator should be used in heavy ice area.

2.4.1 Conductor Suspension String


As per calculation, tower weight can be decreased when V string is used in
heavy ice area, meanwhile the using of V string restricts the wind shifting of the
insulator string, reduces the corridor width. Therefore V string is recommended to
be used as conductor insulator string in heavy ice area. The maximum shifting
angle of windward leg insulator string should be controlled within 7, V string
angle should be designed according to the following:
Table 2-8 Heavy Ice Area V String Angle (20 mm and 30 mm ice, 30m/s wind)
Tower Type

Kv Coefficient

ZV21
ZV22
ZV23
ZV31
ZV32
ZV33

0.85
0.65
0.75
0.85
0.65
0.75

Wind Shifting Angle

40
49.7
44
40
49.7
44

V String Angle

70
80
75
70
80
75

According to the conductor selection and separation number in heavy ice area,
and based on mechanical load calculation, the conductor suspension V string
configuration in heavy ice area of this engineering is as following:

The combination of each leg single joint 400kN and 550kN insulator strings and
double joints 210kN, 300kN and 400kN insulator strings can be used for 20 mm
ice area conductor suspension V string.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
The combination of each leg double joints 210kN, 300kN and 400kN insulator
strings can be used for 30mm ice area conductor suspension V string.

In order to avoid the uneven ice covering and the uneven force of double joints
insulators or the collision of them when in off ice jumping, it is recommended to
use single hanging point for double joints V type string in heavy ice area. Refer to
Figure 7-5 for double joint V type strings arrangement in heavy ice area.

Figure 7-5 Schematic Diagram for Heavy Icy Area Double Joints V String

2.4.2 Conductor Tension String


1) The maximum load of each pole conductor tension string in 20 mm ice area is
436.3kN, therefore 3400kN and 4300kN types can be used as tension strings.

2 The maximum load of each pole conductor tension string in 30 mm ice area
is 592.42kN, the insulator strength of the tension string is required to be
1599.5kN, therefore 3550kN and 4400kN types can be used as the tension
strings.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
Quadruple strings are with the shortcomings of complicated structure, more
insulators and fittings, higher insulator failure rate during working, large
maintenance workload, difficult to adjust when the two independently connected
strings are with different lengths and easy to cause the long term uneven force of
the insulator strings. While the triple joints structure is in a simpler structure, with
even force, when the string lengths are different, it can get back to even force
status automatically with the function of combination joints board, moreover, it is
with the advantages of less insulators, lower failure rate and less maintenance
workload. Therefore, triple string type is recommended for using.

That means 3400kN tension string type is recommended to be using in 20 mm


ice area and 3550kN tension string type is recommended to be using in 30 mm
ice area. Refer to the following for the recommended tension string arrangement:

Figure 7-6 Schematic Diagram for 30mm Ice Area Tension String Arrangement

2.4.3 Joints Spacing

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
Off ice jumping is supposed to be happening to the insulator string in heavy ice
area, which shall become more serious following the increasing of the thickness
of the covering ice. After the conductor off ice jumping, the insulator string will be
shaking severely, as there is too long a string length, the shaking of the string is
more severe than that of 500kV line, if the joints spacing is too small, collision of
the strings between the joints will be happening, at present there is no such kind
of research in China and foreign countries, for safety purpose, appropriate joints
spacing should be added in heavy ice area than in light ice area.
Table 2-9

Recommended Values for Conductor Insulator Strings Joints

Spacing
Ice Area
Heavy Ice Area

Suspension String
800mm

Tension String
1000mm

2.5 Jumper wire pattern


Reducing sag of jumper wire and angle of wind deflection is an effective method
to reduce the dimension of strain tower. Sag of jumper wire and angle of wind
deflection are related to patterns of jumper wire and rigid jumper wire. At present,
strain tower has many patterns such as flexible jumpers, cage rigid jumpers and
aluminum-tube rigid jumpers etc.

Flexible jumpers are widely applied in domestic circuits under 500kV. It


possesses mature operation experience, but has great influence on cross arm
dimension of strain tower. Compared to flexible jumper, cage type rigid is added
with a support tube on basis of flexible jumper by a spacer damper. Besides, the
jumper is fixed on support tube by spacer and support tube is connected to strain
insulator string or strain tower through straining rod or stain insulator string.
Though the sag of the jumper is small and cross arm of the strain tower is short,
the installation is complicated. Compared to cage type rigid jumper, support tube
of cage type rigid jumper and flexible jumper are replaced with two aluminum
alloy tube,The aluminum aloy tube plays the role of conduction currecny and
supporting and its installation is relative easy. But this method increases electric

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
breaking point and corona can occur easily, especially in coupling area of
aluminum tube and terminal, and with higher cost of manufacturing than cage
type jumper. Therefore, cage type rigid jumper is recommended for strain tower.

At present there are two patterns of cage rigid jumpers of V-String and I-String. it
will add an additional cost of RMB 6,580,000 by adopt V-String cage rigid jumper
than I-string cage rigid jumper for the whole line. However, the property to avoid
wind deflection of V-string cage rigid jumper and its electric reliability is better.
Double V-string is adopted in cage type rigid jumper. It will help to fix rigid jumper
and is the safest to electric reliability of the project. Therefore, it is recommended
that double V-string cage rigid string be used. According to structure distribution
and spacing analysis, the intersection angle of V-string should be 7090. Cage
type rigid jumper should be arranged as follows:

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware

Figure 2-7 Diagram of arrangement of cage rigid jumper

2.6 Earth wire fittings


As being computed for mechanic property and tested for overload capacity on
heavy icing area, 20mm of the earth wire and off-ice area shall adopt LBGJ-18020AC aluminum clad steel standed conductor and 30mm ice area shall adopt GJ210 galvanized steel stranded wire. Suspension fitting string of earth wire and
strain fitting string should directly connected to the ground.

2.8 Main selection of fittings


Fittings mainly include tower-connecting fittings, suspension clamps, six-bundle
yoke plates, spacer dampers, and grading rings. Fittings are the important parts
connected to circuit for safe operation. If fittings become ineffective and damaged,
circuit will be damaged and interruption of power supply will be caused.
Therefore, fittings shall be of high reliability. They shall meet current related
standards and other special requirements in this project. In addition, the
conveniences to transport, install, repair, and replace fittings shall be taken
seriously.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
2.8.1 hardware fittings connected to towers
GD Clevises and GD trunnion clevises are the main two kind of fittings connected
to towers in extra high voltage network. By use of these two fittings will avoid the
irrational stress casued by UB Clevises and U-shaped assembly and improved
the safety operation of transmission line. GD clevises reduce the space to the
most of the run-on point of fair line and transverse line, in which improved the
reliability of the hardware fittings connected to towers greatly. But they shall be
installed when towers are being assembled. So the cross arm structure of towers
becomes relatively complicated as the bolts are connected with the body leading
to uneasy installation. The connection of GD clevises and trunnion clevises to
other fittings is shown in the following figure.

(a) GD Connection method of GD clevis

(b) Connection method of trunnion clevis

Figure 2-8 trunnion clevis and GD clevis

From the perspective of simplifying clevis design and construction convenience,


trunnion clevises shall be adopted for suspension V-string hanging-point fitting. It
is recommended that GD clevis or assembled clevises shall be used for strain
hanging-point fitting and the diameter of threaded rod shall not be changed
except the followings:

Adjust the diameter and thickness at connections of clevis and fittings.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
According to design and operation experience of extra voltage transmission line
and in consideration to factors like abrasion, the strength grade of fittings for
connecting towers is generally higher than that of other connection fittings, i.e.
matching the grade of insulator strength. According to the distribution condition of
suspension string and patterns of strain string, there are six strength grades of
fittings for connecting towers, are 320kN, 420kN, 530kN, 640kN, 840kN, and
1060kN. Whole forging workmanship shall be used to process fittings for
connecting towers.

2.8.2 Six-bundle suspension yoke plate


The key hardware fittings in suspension string is the type selection of six-bundle
suspension yoke plate, which adopts combination yoke plate and integral yoke
plate in 750kV AC transmission line.The six-bundle suspension yoke plate of
500kV compact line in China all adopt integral type, which have the advantage of
stability, fewer hardware fittings, simply structure, but heavier for single part. It is
easy to transport in mountainous area from the experience of design and
construction. Therefore, the integral six-bundle suspension yoke plate is
recommended in this project. Six-bundle suspension integral yoke plate is as the
following drawing:

Drawing 7-9 Sketch map of six-bundle Suspension yoke plate.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
It may adopt 420kN640kN840kN1280kN1680kN (In heavy icing areas)
because the strength of suspension yoke plate is same as the strength of
insulator string.

2.8.3 Six-bundle tension yoke plate


The six-bundle tension yoke plate also has two types: integral and combination
type . The integral type is good in stability, fewer hardware fittings, simply
structure. The single piece of combination yoke plate is easy to fabricated,
transport and installation of its light weight. It recommends combination yoke
plate to the project area with 20mm and below, due to integral yoke plate is
weight 200kg for a single part, it is inconvenient for transport and installation.
While for the area of 30mm icing areas, it is recommended to use integral type
because of good stability of integral type. The following drawing is the
recommended six-bundle tension string combination yoke plate and integral yoke
plate when tension string adopts 3400kN insulator string.

Drawing 7-10 Sketch map of six-bundle Tension yoke plate


The strength grade of six-bundle tension yoke plate which is matched with
3400kN tension insulator string is 1280kN. The strength grade of six-bundle
tension yoke plate which is matched with 3550kN tension insulator string is
1590kN.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
2.8.4 Suspension clamp
The corona issue of hardware fittings shall become a major problem by the
increasing of voltage in HVDC line. There are two anti-corona methods for
suspension clamp: one is to adopt Corona free suspension clamp; the other is to
add shielding ring for anti-corona. It recommends Corona free clamp to use as
the project suspension clamp because Corona free suspension clamp has been
widely used in 500kV and 750kV HVDC line in China.

Carried-up type suspension clamp is mainly used in flat area. It may adopt
Carried-up suspension clamp because the hills, flats and river network of the
project is about 870km, then if it is adopted, it shall pay high attention to its
corona features. Besides, it needs to research the voltage share of insulator
string. From the present research result, it needs to raise Grading rings to the
place of three pieces insulator, about 550mm. while it need further research
about how much to go deep for insulator string if Carried-up suspension clamp is
adopted, because it can not raise the enough height according to same height.
So in the report, it is temporarily not recommend Carried-up suspension clamp in
hills, flats and river network.

The main difference between trunnion type and Envelope type suspension clamp
is the relative position between shaft and vertical axis of suspension clamp. IEC
standard only requires that rotation axis shall have enough wear resistance but
without specification. CIGRE standard recommend that rotation axis shall not be
higher than the conductor diameter of 1 to 2 times conductor axis, which can
make the inertia moment of rotation axis as small as possible to reduce dynamic
stress. The design of suspension clamp shall ensure the vibration of conductor
and clamp to a minimum to avoid any damage towards conductor caused by
stress.

When conductor swing up and down in vertical direction, the torque of it towards

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
swinging up and down of suspension clamp is small, because of the stressed
shaft of trunnion type suspension clamp is on the axle wire of conductor, thats to
say the caused stress by the swinging up and down of suspension clamp is small
to conductor, and will minimize the fatigue damage of conductor to the most,
especially the conductor fatigue damage at line outlet area.

The AGS suspension clamp have the advantage of protect the conductor well
and minimize the damage to conductor. It is mainly used in OPGW, and may
used to protect conductor abroad. Due to the well protective property of AGS
suspension clamp, we adopt AGS suspension clamp to the first 750kV
transmission line in China, which the mostly applied to the large diameter
conductor. We do not recommend the AGS suspension clamp because the cross
section of current widely used conductor is small and no running experiences of
applied to the conductor with large cross section.

To 800kV HVDC transmission line project, it not only need to adopt products
with high performance, but also to use these products with abundant experience
under operation, so it suggest to adopt the common Envelope type suspension
clamp suspension clamp to the HVDC transmission line in China.

Other requirements for suspension clamps are,

1) The overhanging angle of suspension clamps should no less than 25;

2) The curvature radius of the hulls slots should not less than 8 to 10 times of the
diameter of the conductors; and the contacting area between the wire clips and
the conductors should remain smooth;

3) The suspension clamps on the line should be able to turn flexibly; and the
swinging angle should no less than 30;

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
4) There should be enough contacting surface between the suspension clamps
and the installed conductors, and the damages caused by fault current will
minimize.

5) The grip strength of the suspension clamps should no less than 24% of the
calculated tensile strength of the conductors;

According to the situations of the suspension string applied to this project, the
strength of suspension clamps will classified to four grades, 100kN, 160kN,
210kN and 300kN (for the heavy ice zones).

it is usually install the preformed armor rods at the condition of large vertical span,
therefore, the suspension clamps need meet the requirements for installation.

The suspension clamps commonly divided into envelope type and trunnion type,
which used for extra-high voltage transmission line. The trunnion type
suspension clamps are poplar in oversea countries, while the envelope type
suspension clamps are used in China, basically ,for all the extra-high voltage
transmission lines. Please see the following diagrams for the envelope type and
trunnion type suspension clamps.

The trunnion type suspension clamp

The envelop type suspension clamp

Fig. 7-11 The suspension clamp types

For 800kV EHV DC transmission line projects, it is required to used products

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
with good performance; and also have the requirement on the products of large
operation experiences. So, the envelope type suspension clamps, which have
abundant operating experience, are recommended for this project.

2.8.5 Spacers

There are two types of spacers, one is the integral type, the other is spreadassembled type. integral type spacers were adopted for ultra-high voltage line
project in the Former Soviet Union, and spread-assembled type were once used
for extra-high voltage transmission lines and in the testing stages of 1,150 kV.

In Japan market, it is adopted integral type spacer with spring, and without
elastomer. The energy will consume by the contraction of spring and will led
clamps able to turn flexibly, to achieve the purpose of eliminate the vibration. It is
adopt the Integral type in China, applied to the 500kV and 750 kV transmission
lines, therefore, integral type spacers are recommended.

Due to the convenient installation and reliable grip strength of hinge type clamp
assembled with pins , it is widely used up to now. And this type is also used of
this design, the two differences are, that it is add a structure on the pins to limit
the position, and have the advantage of fixed pin position while installation; the
pins will hardly fall when the structure limiting the fastening pins after the
conductors are gripped by the clamps.

In order to allow the clamps to rotate around the joints to 15, the problem of
position limiting between the clamp body and the spacer frames, which was
solved by designing a convex part (or called the limit stop) at the tale of the joint
in the past, should be taken into consideration. For more reliable position limiting,
it is recommended to adopt double position limiting design, which will limit the
position at the reverse direction besides the tale part of the limit stop.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
Limit stop

(a) The traditionally designed Position

Double
position limiting

(b) The design of double position limiting

limiting of clamp rotation

High-strength bolts shall used for connecting tthe clamps and the body frames,
that will to led convenient to replacing the clamps if needed. It is required that the
spacer bodies installed at the lines should completely surrounded by the bundle
sub-conductors. And the tension (pressure) strength between clamps is generally
required no less than 6.0 kN. Too short clamps will increase the weight of
spacers and will easily cause corona; while over-long clamps will lead to overlarge bending torque and is not easy to ensure the strength. Referring to data
from domestic and abroad, it is relatively suitable to set the distance of 150 mm
between the center lines of the conductors to the joint axis.

The spacers are classified into rigid and flexible spacers. The rigid spacers will
prevent any shifting between the sub-conductors, however, the effectiveness to
prevent aeolian vibration and restrain sub-span oscillation is not good, therefore,
flexible spacers are mostly used in the world. Due to the different damping types
of the flexible spacers, generally could classified into two types, one is elastomer
damping type and the other is spring damping type.

Strictly speaking, the spring damping type spacers cannot consume energy of

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
vibration, only storage the energy by using the springs and then release it slowly.
While by embed the elastomer in the joints, the elastomer damping type spacers
will consume the energy of vibration, which obviously restrain the aeolian
vibration and sub-span oscillation. And as our experience, the effectiveness are
perfect. To install the elastomer damping type spacers with unequal space is
recommended.

The clamp head of spacers may fall off and led to damaged under the huge
forces of the rotation and dancing phenomena caused by covering ice in heavy
ice zones, especially the jumping of conductors because of ice.

That will effect the safe operating of the transmission lines. And there is already
successful operating experience adopt preformed spacers to slove the problem
.
As above listing, elastomer damping type integral spacers are recommended in
light ice zones, while preformed type spacers are recommended in heavy ice
zones.

(a) Spacers for light ice zones

(b) Spacers for heavy ice zones

Fig. 7-12 The recommended types of spacers

2.8.6 Equalizing ring, shielding ring

For ultra high voltage 800kV DC transmission line, because of the voltage level
Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
increase, the number of insulators will be increase greatly than that of extra high
voltage line. In insulator string, the voltage borne by single piece of insulator will
also increase.

For the safe working condition of the insulators, the voltage borne by single piece
of insulator of ultra high voltage line shall not increased greatly compared with
that of extra high voltage, thats to say the required that voltage percentage
borne by single piece of insulator of extra high voltage shall decrease, which
requires a relatively great improvement in the design of corona ring.

For the tension insulator-strings, due to the coupling length is relatively long, with
more the quantity of joining fittings, and the coupling type is complex, in order to
elinimate the corona loss of the fittings, as well as the radio inference and audible
noise level, its necessary to proceed effective shield to the fittings of tension
string.

Guidance to the design and assembly of corona ring and shielding ring are as
follows list:

For suspension string and tension string, the installing position of grading ring is
between the second and third piece of insulator, the equalizing effect is relatively
good, diameters of both grading ring and shielding path adopt aluminum tube of
120mm, which the radius of grading ring is 620mm.

Suspension string could only installed grading ring, no more installation of


shielding ring, and tension insulator string could installed with shielding ring and
grading ring. Both shielding ring and grading ring of tension string are shown as
the following figures.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware

Grading ring of tension string

Shielding ring of tension string

Figure 7-13 Grading ring and shielding ring of tension string

2.9 Suggestions

(1) Suspension insulator in light pollution area may adopt disc-type insulator or
composite insulator, which shall chosen for configuring with the factors of climate
conditions, operation experience and the type of insulator string. The insulator of
suspension string in medium and heavy pollution area are adopt composite
insulators. Tension insulator adopts disk-type insulator.

(2) It is recommended that adopt type V insulators as the main suspension string
in the light ice area of this project, the angle of type V string in light ice area
adopts 90~100. For tangent angle tower, it is recommended to adopt type L
insulator string.

(3) Due to this project adopt duplex connection, and hinged joints between two
side of yoke plate are relatively more, that will not consider change the ball and
socket couplings aside the line connectoed the composite insulator; while fullpart insulator can be temporarily considered for the use of preliminary design,
two-parts composite insulator will be taken as the comparison proposal after the
conduct the electric true type test and after verification in the future.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
(4) Tension string in light ice area of this project is recommended threeconnection horizontal arrangement for 400kN disc-type insulator.

(5) It is suggested that scientific research unit conduct the test of distance
between the connections, to validate the relations of flashover voltage between
the duplex connection structure and single connection structure.

(6) It is suggested to adopt rigid jumper with double V string of this project. The
angle selection of V-type string is 70~90 based on structure arrangement and
clearance analysis.

(7) Selections of the primary fittings

(1) For hanging point hardware & fittings of V type suspension string, Trunnion
Clevis is adopted. It is suggested to adopt GD clevis or assembled clevis as the
hanging point hardware fittings of the tension insulator-string, and the diameter of
screw will not change, only to adjust the hole diameter and thickness at coupling
area between the clevis and hardware fittings. Hardware & Fittings of towerconnected shall be fabricated as integral forging.

(2) Integral yoke plate is recommended for six bundles suspension yoke plates of
this project, combined yoke plate is recommended for strain yoke plate of this
project in 20mm and lower-than-20mm area. When in 30mm ice area, because of
ice covering is severely, the stability of integral forging is relatively good, so is
recommended.

(3) Corona free envelope-type suspension clamp is recommended for the use of
this project.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com

JS Hardware
(4) It is recommended to adopt elastomer damping spacer for the light ice area,
and preformed type spacer for the heavy ice area of this project.

(5) For suspension string and tension string, the installing position of grading ring
shall between the second and the third insulator, the voltage sharing result is
relatively good. Both the diameter of grading and shielding ring all adopt tube of
120mm, the radius of grading ring is 620mm. Suspension string is only installed
the grading ring, and no more installation of shielding ring.

Web: www.JS-Hardware.com, Email: sales@js-hardware.com