JS Hardware
JS Hardware
(2) Single part weight and size of line fittings should try to reduce to facilitate transportation
and installation; It should pay more attention to the ductility of the material when use high
strength material to avoid crisp fracture; mature technology, mature material and mature
technical processing should be adopted; try best to simplify fittings structure, reduce fittings
quantity; the fittings should be with strong exchangeability to facilitate the maintenance to the
line; external forces on the fittings should shared evenly and reasonably to meet various load
requirements while the line is working.
Web: www.JS-Hardware.com, Email: sales@js-hardware.com
JS Hardware
Spacer should be with good mechanical performance to ensure reliable mechanical strength
with reasonable weight, goods damping performance and ability to endure long time fatigue
vibration.
The corona free design of the line should satisfy the needs of ensuring insulator working
normally under 800kV voltage, radio interference created should be in conformity with the
regulations and requirements specified in GB/T2317.2-2000 Electrical Fittings
Corona
and Radio Interference Tests. It must be ensured that no corona will be discharge during the
normal working of fittings.
Line broken
Joint Broken
Normal Load
Disk
2.7
1.8
1.5
Insulator
Fittings
2.5
1.5
1.5
Note: Composite insulator safety coefficient is supposed to be at 3.0.
4.0
27
31.8
15.9
33.4
Wind Velocitym/s
28
30
33
35.4
16.5
17.7
34.7
37.1
32
37.7
18.8
39.6
35
41.3
20.6
43.3
JS Hardware
2.1.4 Standard Value of Wind Load
Wind pressure uneven coefficient, wind load adjustment of conductor and earth wire,
coefficient c shall be determined according to the following table:
Table 7-2 Wind Pressure Uneven Coefficient and Conductor and Ground Line Wind Load
Adjustment Coefficient c (10 M from the Ground)
Base Wind Velocity V(m/s)
27V<31.5
31.5
Calculate Tower Load
0.75
0.70
For the calculation of coefficient to a smaller span as jump line etc., it is better to set at
1.0
Wind load increasing coefficient of conductor, earth wire and tower shall be considered when
in ice covering condition (including uneven ice). Values are to be determined as per the
following table:
Table 2-3 Wind Load Increasing Coefficient of Covering Ice Conductor, Earth wires and
Tower
Thickness of Covering Ice
mm
10
1.2
15
1.3
20
1.5
>20
1.5
JS Hardware
Table 2-4
Tower Type
Comprehensive
Load (kN)
K=2.7
K=3
Tonnage
Single
Leg
Joints
Number
K=2.7
K=3
343
389
458
548
641
781
381
432
509
609
713
867
400kN
400(240)kN
240(300)kN
300(400)kN
400kN
300kN
1
1(2)
2
2
2
3
Z27101
Z27102
Z27103
Z27104
Z27105
Z27106
0.8
0.75
0.7
0.65
0.7
0.7
ZK2710
0.6
90
617
685
477
530
300kN
0.7
60/30
590
655
495
549
300kN
0.7
63/30
717
796
653
725
400kN
299
357
423
527
661
299
357
423
332
397
469
585
734
332
397
469
400kN
400kN
240kN
300kN
400kN
400kN
400kN
240kN
1
1
2
2
2
1
1
2
ZJ27101
(3-12)
ZJ27102
12-20
ZV3210-1
ZV3210-2
ZV3210-3
ZV3210-4
ZV3210-5
ZVF3210-1P
ZVF3210-2P
ZVF3210-3P
0.8
0.75
0.7
0.65
0.65
0.8
0.75
0.7
JS Hardware
ZVK3210-1
(ZVK3210-1P)
ZVK3210-2
(ZVK3210-2P)
ZVK3210-3
(ZVK3210-3P)
ZVJ3210-1
3-12
ZVJ3210-212-20
ZV3510-1A
ZV3510-2P
ZV3510-3P
ZV3510-4P
ZVK3510-1P
ZVK3510-2P
ZVJ3510-1P
3-12
ZVJ3510-2P
12-20
Z27151
Z27152
Z27153
Z27154
Z27155
0.9
90
588
653
460
511
300kN
0.9
90
558
620
435
484
240(300)kN
0.9
90
528
587
411
457
240kN
0.75
60/40
540
600
533
592
300kN
0.75
60/30
624
694
621
690
400kN
286
372
467
555
501
432
317
414
519
617
557
480
400kN
400(240)kN
240(300)kN
300(400)kN
300kN
240kN
1
12
2
2
2
2
0.85
0.8
0.75
0.7
0.9
0.9
0.75
60/45
540
600
590
656
300(400)kN
0.75
60/30
624
694
602
669
400kN
411
468
552
638
753
456
520
614
709
837
240kN
240(300)kN
300(400)kN
400kN
400(300)kN
2
2
2
2
2(3)
0.75
0.7
0.65
0.7
0.7
JS Hardware
Z27156
ZK2715
ZJ2715
3-12
Z30151
Z30152
Z301531
Z301532
Z30154
Z30155
Z30156
ZK3015
ZJ3015
3-12
Note:
5%
increasing
0.7
0.8
90
90
1150
784
1278
872
928
606
1031
673
400kN
400kN
3
2
0.75
60/35
694
771
560
622
300(400)kN
467
531
628
662
764
869
1071
689
519
240kN
590
300kN
697
400kN
735
400kN
849 400(300)kN
965 300(400)kN
1190
400kN
766
400kN
632
702
0.75
0.70
0.65
0.7
0.7
0.7
0.7
0.8
0.75
of
60/40
suspension
point
tension
694
has
been
771
considered
for
400kN
tension
string
2
2
2
2
2(3)
3
3
2
2
load.
JS Hardware
Table 2-5 Allowed Vertical Span for Suspension V String in Heavy Ice Area (m)
Allowed Vertical Span for Suspension Stringm
Number of
Strings x Strength
2300kN
2400kN
2550kN
4210kN
4300kN
4400kN
4550kN
3180
3380
3780
5050
6600
7200
8000
260
430
640
390
660
990
1420
LH=300
175
157
340
275
550
430
300
235
570
430
900
670
1325
980
LH=500
LH=300
110
200
345
155
350
590
900
LH=500
String Weight
(kg)
20mm
30mm
Note:
Remark
70
70
a. 20 mm ice area adopt conductor of 6ACSR720/50 and 30 mm ice area adopt conductor of 6AACSR-720/50 steel core
aluminum alloy
stranded lines.
b. Effect of string weight has been considered for the vertical load calculation.
c. Control working condition is ice covering condition.
d. Typical span is 350 m.
JS Hardware
2.3 Insulator String Assembly Type in Light Ice Area
Subject to the conclusion of Book IV Volume VI of Study on the Insulator
Coordination and Insulator Type Selection, the insulator can be ceramic, glass,
composite or post insulator, while disk insulator or composite insulator can be
used as suspension insulator in light polluted area, which should be selected
according to the weather conditions, working experience and insulator string
configuration along the line. Suspension insulators in medium polluted area and
severely polluted area are using composite insulators. Disk insulators are applied
as tension insulators.
2) V Type String
800 line has far more a string length than that of a normal 500kV line due to the
requirements of insulating configuration, forces on the insulator after being
pressured is better than that for 500kV line, the selection of the angle may be
different, we have carried out specialized research on this point, which is based
Web: www.JS-Hardware.com, Email: sales@js-hardware.com
JS Hardware
on the pressure test research of V type insulator string of 500kV line.
According to the requirements of the tower load, the maximum single leg joint
number of V type string will be 3300kN and 3400kN, for some rare towers
which are with large load and in need of using single leg three joints (3300kN or
3400kN), on one hand, 550kN single leg double joints insulators can be used to
meet the engineering requirements, on the other hand, optimize tower position
when in construction drawing stage to avoid relatively big vertical span. With the
above considerations, it is suggested that the first choice for this engineering
should be single leg single joint and double joints strings, single leg triple joints
strings shall be reserved. In consideration of the significance of super high
voltage line and the properties of the insulator (crisp fracture problem), it is
suggested that double joints mode be adopted when using composite insulator
for suspension string to ensure the safety of this engineering. Each leg 1400kN,
Web: www.JS-Hardware.com, Email: sales@js-hardware.com
JS Hardware
2210kN, 2300kN, 2400kN, 2530kN types of strings are recommended to be
used for conductor V type suspension insulator strings in light ice area of this
engineering. Each leg 2240kN , 2300kN, 2400kN, 2550kN types of strings
are recommended to be used for V type composite insulator strings.
Refer to the following for single joint and double joints V string arrangements in
light ice area:
Figure 2-1 Schematic Diagram for Single Joint and Double Joints V String in Light Ice
Area
4) L Type String
L type string is used in small tangent angle tower, as per calculation, 2300kN
and 2400kN combination should be adopted for L type string, the angle of which
are 60+30, 60+35, 60+40 and 60+45 respectively, with double hanging
points, refer to the following for L type string arrangements:
Figure 2-2 Schematic Diagram of L Type String Arrangement in Light Ice Area
Web: www.JS-Hardware.com, Email: sales@js-hardware.com
JS Hardware
2.3.2 Conductor Tension String
For the above tension string types, if one hanging point is used, when the fitting
connected to the tower is malfunctioning, this is a sign that the malfunction phase
conduction connects to ground directly which will cause severe accident, in the
consideration of the significance of this engineering and the designing and
operation experiences of domestic super high voltage line, independent hanging
point for each joint is suggested for double joints and triple joints strings, and
double hanging points is suggested for a quadruple tension string. To facilitate
maintenance, horizontal arrangement type is suggested for tension strings.
JS Hardware
experiences in the domestic 500kV and large spanning line; 4300kN horizontal
tension string is with the most complicated structure, the most insulator number,
higher insulator failure rate and largest maintenance workload.
Economically, 300kN, 400kN, and 550kN are all meeting the requirements of this
engineering, set light polluted area for example, the insulator cost for each base
tower is as following:
Table 2-6
Insulator Strength
(kN)
Number
of Joints
300
400
550
4
3
2
Number
of
Insulators
56
64
58
From the above we can see: triple joints 400kN insulator is with competitive price,
the issue to be cleared is the influences on the weight of the tower of the three
types insulator strings. According to previous experiences, quadruple joints
300kN, triple joints 400kN and double joints 550kN insulator string types are with
little influence to the tower weight, price will be the dominant factor, assuming
515 bases for the whole line tension towers, when calculating at a minimum price
difference of RMB 15.3 thousand, there will be a saving of RMB 7.88 million for
the whole line when using triple joints 400kN type, this is a considerable amount
for this engineering, the triple joints 400kN insulator string is with obviously
lowest price, quadruple joints 300kN is with a higher price and double joints
550kN, the highest. Above all, the least joints 3400kN tension string in light ice
area is suggested to be the first choice, and 3400kN, the second choice,
2550kN (light ice area), the third choice. Refer to the following for the assembly
of the first recommendation 3x400kN tension string:
JS Hardware
Figure 2-4 Schematic Diagram of Light Ice Conductor 3400kN Tension String
For electrical performance, according to the analysis of the pollution voltage test
results carried out by science research units for DC double joints insulator strings
in high altitude areas, when SDD/ESDD is under a working condition of
0.05mg/cm2 and the net spacing of dual joints parallel strings of bell type
insulators is large than 200 mm, the discharging can be developed independently,
but flashover probability is increased, therefore the pollution flashover voltage of
dual joints parallel strings is lower than that of single joint strings, when the net
spacing of dual joints strings is at 200 mm and 500 mm respectively, the pollution
flashover voltage is 2.03% and 5.08% lower respectively than that of single joint
strings. Under a salt concentration of 0.10 mg/cm2, when the net spacing of dual
joints parallel strings is at 500 mm, the discharging can be developed
Web: www.JS-Hardware.com, Email: sales@js-hardware.com
JS Hardware
independently, the pollution flashover voltage of dual joints parallel strings is 3.9%
higher than that of single joint strings, which indicates a little difference between
the pollution flashover voltages of dual joint parallel strings and the single joint
strings. When in heavy ice, smaller joints spacing will cause the filling up of the
clearance between the joints by ice, which will bridge the insulators and decrease
ice cover voltage of the insulator, in this case, it is necessary to enlarge the joints
spacing to improve electrical performance.
The determination of joints spacing should be carried out on the premise that the
mechanical performance can satisfy a safety working, while with the control
condition that the pollution flashover voltage of double joints structure is not less
than that of the single joint structure; for the 400 mm large insulator used in this
engineering, it is considered that 20 cm net spacing between the joints can
satisfy the requirements for pollution flashover voltage; it is suggested that a
basic spacing of 650 mm be used for suspension insulator strings and tension
insulator strings.
It is suggested that the science research units to carry out tests of joints spacing
to verify the relationship between the pollution flashover voltage of double joints
structure and that of single joint structure.
Refer to the following for the recommended values of the joints spacing for
JS Hardware
multiple joints insulator strings in this engineering.
Table 2-7 Recommended Values of the Conductor Joints Spacing
Ice Area
Light Ice Area
Suspension String
650mm
Tension String
650mm
Kv Coefficient
ZV21
ZV22
ZV23
ZV31
ZV32
ZV33
0.85
0.65
0.75
0.85
0.65
0.75
40
49.7
44
40
49.7
44
V String Angle
70
80
75
70
80
75
According to the conductor selection and separation number in heavy ice area,
and based on mechanical load calculation, the conductor suspension V string
configuration in heavy ice area of this engineering is as following:
The combination of each leg single joint 400kN and 550kN insulator strings and
double joints 210kN, 300kN and 400kN insulator strings can be used for 20 mm
ice area conductor suspension V string.
JS Hardware
The combination of each leg double joints 210kN, 300kN and 400kN insulator
strings can be used for 30mm ice area conductor suspension V string.
In order to avoid the uneven ice covering and the uneven force of double joints
insulators or the collision of them when in off ice jumping, it is recommended to
use single hanging point for double joints V type string in heavy ice area. Refer to
Figure 7-5 for double joint V type strings arrangement in heavy ice area.
Figure 7-5 Schematic Diagram for Heavy Icy Area Double Joints V String
2 The maximum load of each pole conductor tension string in 30 mm ice area
is 592.42kN, the insulator strength of the tension string is required to be
1599.5kN, therefore 3550kN and 4400kN types can be used as the tension
strings.
JS Hardware
Quadruple strings are with the shortcomings of complicated structure, more
insulators and fittings, higher insulator failure rate during working, large
maintenance workload, difficult to adjust when the two independently connected
strings are with different lengths and easy to cause the long term uneven force of
the insulator strings. While the triple joints structure is in a simpler structure, with
even force, when the string lengths are different, it can get back to even force
status automatically with the function of combination joints board, moreover, it is
with the advantages of less insulators, lower failure rate and less maintenance
workload. Therefore, triple string type is recommended for using.
Figure 7-6 Schematic Diagram for 30mm Ice Area Tension String Arrangement
JS Hardware
Off ice jumping is supposed to be happening to the insulator string in heavy ice
area, which shall become more serious following the increasing of the thickness
of the covering ice. After the conductor off ice jumping, the insulator string will be
shaking severely, as there is too long a string length, the shaking of the string is
more severe than that of 500kV line, if the joints spacing is too small, collision of
the strings between the joints will be happening, at present there is no such kind
of research in China and foreign countries, for safety purpose, appropriate joints
spacing should be added in heavy ice area than in light ice area.
Table 2-9
Spacing
Ice Area
Heavy Ice Area
Suspension String
800mm
Tension String
1000mm
JS Hardware
breaking point and corona can occur easily, especially in coupling area of
aluminum tube and terminal, and with higher cost of manufacturing than cage
type jumper. Therefore, cage type rigid jumper is recommended for strain tower.
At present there are two patterns of cage rigid jumpers of V-String and I-String. it
will add an additional cost of RMB 6,580,000 by adopt V-String cage rigid jumper
than I-string cage rigid jumper for the whole line. However, the property to avoid
wind deflection of V-string cage rigid jumper and its electric reliability is better.
Double V-string is adopted in cage type rigid jumper. It will help to fix rigid jumper
and is the safest to electric reliability of the project. Therefore, it is recommended
that double V-string cage rigid string be used. According to structure distribution
and spacing analysis, the intersection angle of V-string should be 7090. Cage
type rigid jumper should be arranged as follows:
JS Hardware
JS Hardware
2.8.1 hardware fittings connected to towers
GD Clevises and GD trunnion clevises are the main two kind of fittings connected
to towers in extra high voltage network. By use of these two fittings will avoid the
irrational stress casued by UB Clevises and U-shaped assembly and improved
the safety operation of transmission line. GD clevises reduce the space to the
most of the run-on point of fair line and transverse line, in which improved the
reliability of the hardware fittings connected to towers greatly. But they shall be
installed when towers are being assembled. So the cross arm structure of towers
becomes relatively complicated as the bolts are connected with the body leading
to uneasy installation. The connection of GD clevises and trunnion clevises to
other fittings is shown in the following figure.
JS Hardware
According to design and operation experience of extra voltage transmission line
and in consideration to factors like abrasion, the strength grade of fittings for
connecting towers is generally higher than that of other connection fittings, i.e.
matching the grade of insulator strength. According to the distribution condition of
suspension string and patterns of strain string, there are six strength grades of
fittings for connecting towers, are 320kN, 420kN, 530kN, 640kN, 840kN, and
1060kN. Whole forging workmanship shall be used to process fittings for
connecting towers.
JS Hardware
It may adopt 420kN640kN840kN1280kN1680kN (In heavy icing areas)
because the strength of suspension yoke plate is same as the strength of
insulator string.
JS Hardware
2.8.4 Suspension clamp
The corona issue of hardware fittings shall become a major problem by the
increasing of voltage in HVDC line. There are two anti-corona methods for
suspension clamp: one is to adopt Corona free suspension clamp; the other is to
add shielding ring for anti-corona. It recommends Corona free clamp to use as
the project suspension clamp because Corona free suspension clamp has been
widely used in 500kV and 750kV HVDC line in China.
Carried-up type suspension clamp is mainly used in flat area. It may adopt
Carried-up suspension clamp because the hills, flats and river network of the
project is about 870km, then if it is adopted, it shall pay high attention to its
corona features. Besides, it needs to research the voltage share of insulator
string. From the present research result, it needs to raise Grading rings to the
place of three pieces insulator, about 550mm. while it need further research
about how much to go deep for insulator string if Carried-up suspension clamp is
adopted, because it can not raise the enough height according to same height.
So in the report, it is temporarily not recommend Carried-up suspension clamp in
hills, flats and river network.
The main difference between trunnion type and Envelope type suspension clamp
is the relative position between shaft and vertical axis of suspension clamp. IEC
standard only requires that rotation axis shall have enough wear resistance but
without specification. CIGRE standard recommend that rotation axis shall not be
higher than the conductor diameter of 1 to 2 times conductor axis, which can
make the inertia moment of rotation axis as small as possible to reduce dynamic
stress. The design of suspension clamp shall ensure the vibration of conductor
and clamp to a minimum to avoid any damage towards conductor caused by
stress.
When conductor swing up and down in vertical direction, the torque of it towards
JS Hardware
swinging up and down of suspension clamp is small, because of the stressed
shaft of trunnion type suspension clamp is on the axle wire of conductor, thats to
say the caused stress by the swinging up and down of suspension clamp is small
to conductor, and will minimize the fatigue damage of conductor to the most,
especially the conductor fatigue damage at line outlet area.
The AGS suspension clamp have the advantage of protect the conductor well
and minimize the damage to conductor. It is mainly used in OPGW, and may
used to protect conductor abroad. Due to the well protective property of AGS
suspension clamp, we adopt AGS suspension clamp to the first 750kV
transmission line in China, which the mostly applied to the large diameter
conductor. We do not recommend the AGS suspension clamp because the cross
section of current widely used conductor is small and no running experiences of
applied to the conductor with large cross section.
To 800kV HVDC transmission line project, it not only need to adopt products
with high performance, but also to use these products with abundant experience
under operation, so it suggest to adopt the common Envelope type suspension
clamp suspension clamp to the HVDC transmission line in China.
2) The curvature radius of the hulls slots should not less than 8 to 10 times of the
diameter of the conductors; and the contacting area between the wire clips and
the conductors should remain smooth;
3) The suspension clamps on the line should be able to turn flexibly; and the
swinging angle should no less than 30;
JS Hardware
4) There should be enough contacting surface between the suspension clamps
and the installed conductors, and the damages caused by fault current will
minimize.
5) The grip strength of the suspension clamps should no less than 24% of the
calculated tensile strength of the conductors;
According to the situations of the suspension string applied to this project, the
strength of suspension clamps will classified to four grades, 100kN, 160kN,
210kN and 300kN (for the heavy ice zones).
it is usually install the preformed armor rods at the condition of large vertical span,
therefore, the suspension clamps need meet the requirements for installation.
The suspension clamps commonly divided into envelope type and trunnion type,
which used for extra-high voltage transmission line. The trunnion type
suspension clamps are poplar in oversea countries, while the envelope type
suspension clamps are used in China, basically ,for all the extra-high voltage
transmission lines. Please see the following diagrams for the envelope type and
trunnion type suspension clamps.
JS Hardware
with good performance; and also have the requirement on the products of large
operation experiences. So, the envelope type suspension clamps, which have
abundant operating experience, are recommended for this project.
2.8.5 Spacers
There are two types of spacers, one is the integral type, the other is spreadassembled type. integral type spacers were adopted for ultra-high voltage line
project in the Former Soviet Union, and spread-assembled type were once used
for extra-high voltage transmission lines and in the testing stages of 1,150 kV.
In Japan market, it is adopted integral type spacer with spring, and without
elastomer. The energy will consume by the contraction of spring and will led
clamps able to turn flexibly, to achieve the purpose of eliminate the vibration. It is
adopt the Integral type in China, applied to the 500kV and 750 kV transmission
lines, therefore, integral type spacers are recommended.
Due to the convenient installation and reliable grip strength of hinge type clamp
assembled with pins , it is widely used up to now. And this type is also used of
this design, the two differences are, that it is add a structure on the pins to limit
the position, and have the advantage of fixed pin position while installation; the
pins will hardly fall when the structure limiting the fastening pins after the
conductors are gripped by the clamps.
In order to allow the clamps to rotate around the joints to 15, the problem of
position limiting between the clamp body and the spacer frames, which was
solved by designing a convex part (or called the limit stop) at the tale of the joint
in the past, should be taken into consideration. For more reliable position limiting,
it is recommended to adopt double position limiting design, which will limit the
position at the reverse direction besides the tale part of the limit stop.
JS Hardware
Limit stop
Double
position limiting
High-strength bolts shall used for connecting tthe clamps and the body frames,
that will to led convenient to replacing the clamps if needed. It is required that the
spacer bodies installed at the lines should completely surrounded by the bundle
sub-conductors. And the tension (pressure) strength between clamps is generally
required no less than 6.0 kN. Too short clamps will increase the weight of
spacers and will easily cause corona; while over-long clamps will lead to overlarge bending torque and is not easy to ensure the strength. Referring to data
from domestic and abroad, it is relatively suitable to set the distance of 150 mm
between the center lines of the conductors to the joint axis.
The spacers are classified into rigid and flexible spacers. The rigid spacers will
prevent any shifting between the sub-conductors, however, the effectiveness to
prevent aeolian vibration and restrain sub-span oscillation is not good, therefore,
flexible spacers are mostly used in the world. Due to the different damping types
of the flexible spacers, generally could classified into two types, one is elastomer
damping type and the other is spring damping type.
Strictly speaking, the spring damping type spacers cannot consume energy of
JS Hardware
vibration, only storage the energy by using the springs and then release it slowly.
While by embed the elastomer in the joints, the elastomer damping type spacers
will consume the energy of vibration, which obviously restrain the aeolian
vibration and sub-span oscillation. And as our experience, the effectiveness are
perfect. To install the elastomer damping type spacers with unequal space is
recommended.
The clamp head of spacers may fall off and led to damaged under the huge
forces of the rotation and dancing phenomena caused by covering ice in heavy
ice zones, especially the jumping of conductors because of ice.
That will effect the safe operating of the transmission lines. And there is already
successful operating experience adopt preformed spacers to slove the problem
.
As above listing, elastomer damping type integral spacers are recommended in
light ice zones, while preformed type spacers are recommended in heavy ice
zones.
For ultra high voltage 800kV DC transmission line, because of the voltage level
Web: www.JS-Hardware.com, Email: sales@js-hardware.com
JS Hardware
increase, the number of insulators will be increase greatly than that of extra high
voltage line. In insulator string, the voltage borne by single piece of insulator will
also increase.
For the safe working condition of the insulators, the voltage borne by single piece
of insulator of ultra high voltage line shall not increased greatly compared with
that of extra high voltage, thats to say the required that voltage percentage
borne by single piece of insulator of extra high voltage shall decrease, which
requires a relatively great improvement in the design of corona ring.
For the tension insulator-strings, due to the coupling length is relatively long, with
more the quantity of joining fittings, and the coupling type is complex, in order to
elinimate the corona loss of the fittings, as well as the radio inference and audible
noise level, its necessary to proceed effective shield to the fittings of tension
string.
Guidance to the design and assembly of corona ring and shielding ring are as
follows list:
For suspension string and tension string, the installing position of grading ring is
between the second and third piece of insulator, the equalizing effect is relatively
good, diameters of both grading ring and shielding path adopt aluminum tube of
120mm, which the radius of grading ring is 620mm.
JS Hardware
2.9 Suggestions
(1) Suspension insulator in light pollution area may adopt disc-type insulator or
composite insulator, which shall chosen for configuring with the factors of climate
conditions, operation experience and the type of insulator string. The insulator of
suspension string in medium and heavy pollution area are adopt composite
insulators. Tension insulator adopts disk-type insulator.
(2) It is recommended that adopt type V insulators as the main suspension string
in the light ice area of this project, the angle of type V string in light ice area
adopts 90~100. For tangent angle tower, it is recommended to adopt type L
insulator string.
(3) Due to this project adopt duplex connection, and hinged joints between two
side of yoke plate are relatively more, that will not consider change the ball and
socket couplings aside the line connectoed the composite insulator; while fullpart insulator can be temporarily considered for the use of preliminary design,
two-parts composite insulator will be taken as the comparison proposal after the
conduct the electric true type test and after verification in the future.
JS Hardware
(4) Tension string in light ice area of this project is recommended threeconnection horizontal arrangement for 400kN disc-type insulator.
(5) It is suggested that scientific research unit conduct the test of distance
between the connections, to validate the relations of flashover voltage between
the duplex connection structure and single connection structure.
(6) It is suggested to adopt rigid jumper with double V string of this project. The
angle selection of V-type string is 70~90 based on structure arrangement and
clearance analysis.
(1) For hanging point hardware & fittings of V type suspension string, Trunnion
Clevis is adopted. It is suggested to adopt GD clevis or assembled clevis as the
hanging point hardware fittings of the tension insulator-string, and the diameter of
screw will not change, only to adjust the hole diameter and thickness at coupling
area between the clevis and hardware fittings. Hardware & Fittings of towerconnected shall be fabricated as integral forging.
(2) Integral yoke plate is recommended for six bundles suspension yoke plates of
this project, combined yoke plate is recommended for strain yoke plate of this
project in 20mm and lower-than-20mm area. When in 30mm ice area, because of
ice covering is severely, the stability of integral forging is relatively good, so is
recommended.
(3) Corona free envelope-type suspension clamp is recommended for the use of
this project.
JS Hardware
(4) It is recommended to adopt elastomer damping spacer for the light ice area,
and preformed type spacer for the heavy ice area of this project.
(5) For suspension string and tension string, the installing position of grading ring
shall between the second and the third insulator, the voltage sharing result is
relatively good. Both the diameter of grading and shielding ring all adopt tube of
120mm, the radius of grading ring is 620mm. Suspension string is only installed
the grading ring, and no more installation of shielding ring.