H Im 68
H Im 68
H Im 68
March 2000
Replaces H-IM-44
Direct Drive
Fluid Coolers
Installation and
Maintenance Data
Table of Contents
Inspection
System Warranty
Installation ......................................... 2
Rigging Instructions ........................... 3
Internal Volume and Weight .............. 4
Typical Piping
In-Warranty Return Material Procedure........11
System Installation
Piping Installation
Glycol Charge ................................... 7
Inspection
Responsibility should be assigned to a dependable
individual at the job site to receive material. Each shipment
should be carefully checked against the bill of lading. The
shipping receipt should not be signed until all items listed on
the bill of lading have been accounted for.
Check carefully for concealed damage. Any shortage or
damages should be reported to the delivering carrier.
System Warranty
This equipment is designed to operate properly and
produce rated capacity when installed in accordance with
accepted industry standards. Failure to meet the following
conditions may result in voiding of the system warranty:
a.
b.
c.
1.
2.
4.
3.
5.
Installation
NOTE:
CAUTION:
Unit Location
Units are designed for outdoor application and may be
mounted on a roof or concrete slab (ground level installation).
Roof mounted units should be installed level on steel channels
or an I-beam frame to support the unit above the roof. Use of
vibration pads or isolators is recommended. The roof must be
strong enough to support the weight of the unit. Concrete slabs
used for unit mounting should be installed level and be properly
supported to prevent settling. A one-piece concrete slab with
footings extending below the frost line is recommended.
Sound Vibration
Units should be installed away from occupied spaces and
above or outside of utility areas, corridors and auxiliary spaces
to reduce the transmission of sound and vibration to occupied
spaces. The refrigerant piping should be flexible enough to
prevent the transmission of noise and vibration from the unit
into the building. If the refrigerant lines are to be suspended
from the structure of the building, isolation hangers should be
used to prevent the transmission of vibration. Where piping
passes through a wall, it is advisable to pack fiberglass and
sealing compound around the lines to minimize vibration and
retain flexibility in the lines.
x
x
x
x
x
x
x
x
x
x
2
2
2
3
3
4
4
5
5
6
Number
of
Fans
2
2
2
3
3
4
4
5
5
6
Number
of
Rows
2
3
4
3
4
3
4
3
4
4
Internal
Volume
Gallons
6.7
9.2
11.8
13.0
16.7
16.7
21.7
20.4
26.6
31.6
Approximate
Net Weight
(Lbs.)
1540
1590
1600
2360
2420
3150
2190
3510
3990
4790
2
2
2
3
3
4
4
5
5
6
2
3
4
3
4
3
4
3
4
4
13.5
18.5
23.5
25.9
33.4
33.3
43.3
40.7
53.1
63.1
1540
1620
1760
2420
2480
3230
3510
4040
4390
5270
Electrical Wiring
The electrical installation should be in accordance with
National Electrical Code, local codes and regulations. Proper
overcurrent protection should be provided for the fan motors.
Wiring diagrams shown are only basic and do not show fuses,
disconnect switches, etc., which must be provided in the field.
All standard motors have internal inherent overload
protectors. Therefore, contactors can be used instead of
starters requiring thermal protectors, eliminating the problem
of furnishing the proper heating elements.
All dry coolers or units are furnished with either singlephase or three-phase fan motors which are identified by the
unit dataplate.
Diagram 1. Typical Fluid Cooler Wiring Diagram Without Fan Cycle Controls.
Diagram 2. Typical Fluid Cooler Wiring Diagram With Standard Fan Cycle Controls.
System Installation
NOTE: All installation and maintenance are to be performed
only by qualified personnel who are familiar with local codes
and regulations, and experienced with this type of
equipment. CAUTION: Sharp edges and coil surfaces are
a potential injury hazard. Avoid contact with them.
General
1.
2.
of the mixture. Any refill should be controlled so as to maintain the proper glycol-to-water ratio.
Table 3 shows pressure drops for various pipe sizes at
flow rates commonly used with a typical dry cooler. These
pipe sizes are not necessarily always correct for the run from
the condenser to the dry cooler. Proper pipe size will depend
on available pump head. This can be determined by subtracting from the total available pump head at design flow, the condenser pressure drop and the dry cooler pressure drop. Allow
some safety factor for last minute pipe fittings added to the
system and for eventual fouling of the system.
a.
Glycol piping requires no insulation except when fluid temperature will be below ambient dewpoint temperatures.
Dry coolers normally produce about 70 or higher fluid
temperatures.
b.
c.
4.
5.
Provide sufficient valves and unions to permit easy access to parts subject to wear and possible repair or replacement.
6.
7.
8.
Pipe
Size
Steel
1
1
1
1 1/4
1 1/4
1 1/4
1 1/2
1 1/2
2
2
2 1/2
2 1/2
3
3
3 1/2
4
4
4
Type "L"
O.D.
Copper
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 5/8
2 5/8
3 1/8
3 1/8
3 5/8
4 1/8
4 1/8
4 1/8
Schedule 40 Steel
Head Ft./100 Ft.
Equiv. Length
17.6
30.2
11.5
16.3
21.8
13.0
16.5
7.9
13.7
8.5
18.6
10.7
16.5
11.1
5.9
7.9
10.2
Glycol Charge
Piping Installation
The piping system should provide maximum leak prevention. Weld or sweat joints should be used where possible
or tightly drawn Teflon tape threaded pipe joints should be made
if needed. The fact that glycol solutions or other heat transfer
fluids will leak where water will not, must be taken into account.
The glycol system should not employ a pressure reducing valve. This is because a slight leak would lead to dilution
The holding volume of the system which includes the holding capacity of the condenser, the holding capacity of the
interconnecting piping (Table 3) and the holding capacity
of the dry cooler (see Table 3).
b.
Percentage of glycol required by volume to provide protection at the design minimum outside temperature (see
Table 2).
7
-3
-14
-23
-38
Pump is selected for piping friction loss plus fluid pressure drop through the dry cooler coil, plus pressure drop
through the heat source. No allowance for vertical lift is made
since in a closed system a counterhead acts on the pump suction.
2.
3.
1.
2.
3.
4.
Start-up
1.
Prestart:
Connect a pump and hose to the hose bibb away
from the pump and a hose to the hose bibb closest
to the pump. Begin pumping the glycol mixture into
the system at FULL PRESSURE. For the return
hose you should close the hose bibb so that you
get only a small flow of fluid or air. This is
necessary so you will build a head of fluid which will
force the air from the system. Once all the air is out
you will have a steady flow of only fluid. At this joint
you should close off the two hose bibbs and open
the shut off valve. See Diagram 3.
Check for correct dry cooler fan rotation. This can be done
by quickly jogging the fan contactor. Be sure that the fans
run freely. The same check is recommended for pumps.
2.
b.
3.
4.
Instruction Envelope:
Keep wiring diagrams, instructions, list of spare parts, in
an envelope within easy reach of the installed dry cooler.
Diagram 3.
Walls or Obstructions
The unit should be located so that air may circulate freely
and not be recirculated. For proper air flow and access all
sides of the unit should be a minimum of W away from any
wall or obstruction. It is preferred that this distance be increased
whenever possible. Care should be taken to see that ample
Multiple Units
For units placed side by side, the minimum distance
between units is the width of the largest unit. If units are placed
end to end, the minimum distance between units is 4 feet.
Units in Pits
The top of the unit should be level with the top of the pit,
and side distance increased to 2W.
If the top of the unit is not level with the top of pit, discharge cones or stacks must be used to raise discharge air to
the top of the pit. This is a minimum requirement.
Decorative Fences
Fences must have 50% free area, with 1 foot undercut,
a W minimum clearance, and must not exceed the top of
11
Replacement Parts
When writing to the factory for service or replacement parts,
refer to the model number and serial number of the unit as stamped
on the serial plate attached to the unit. If replacement parts are
Part Number
208-230/3/60
25301801
22900401
23100301
460/3/60
25301801
22900401
23100301
575/3/60
25302001
22900401
23100301
Contact Customer Service Department for parts to specific fluid cooler models.
Since product improvement is a continuing effort at Heatcraft, we reserve the right to make changes in specifications without notice.