Control Building :Wall RCW1&2 : Thermal shrinkage considerations for concrete pours due to heat of hydration.
Report on concrete placement temperature & pour thickness is referred.
Location :
Control Building Basement
Length of pour of concrete (L) :
11800 mm
Report no. is TAPP-3&4/TCE.2191/DR/CV/24000/16.
full length of wall
Width of pour of concrete (B) :
800 mm
& (L/H) is:
3.93
> 2.5
for this pour size.
Overall depth of concrete: (H)
3000 mm
Height of pour of concrete (H') :
1900 mm
6.233596 ft
h
L
Location h of upper surface of pour from farthest restraining surface:
1900 mm
2 H
H
Specific heat Ch :
Grade of concrete:
25 MPa.
0.231 Btu/lbF
K =
for .( L/ H ) >=2 . 5
Volume of pour of concrete :
17.936 m3
5.278E-006 per 0F
Thermal expansion coefficient (Ct) :
Exposed surface area :
Side faces ------>>
Upper surface--->>
1.08 Btu/ft.hr.F
Thermal conductivity of concrete, K :
3
Density of concrete wc:
25 kN/m
159.08
(Volume/exposed surface) Ratio :
0.31291 met or as
Thermal diffusivity of concrete hh : 0.705354
Effective V/S ratio :
1.747 ft
hh=
360 kg/m3
23 0C or as
80.6 0F or as
[ ]
[ ]
L
+1
H
L
1
H
KR=
L
+ 10
H
16 0C or as
Tallowable :
68.48 0F being
<
T allowable=
1510
K RECT
0
80.6 F being the design temperature difference (T E).
% of reinforcement :
0.000
for . ( L / H )<2. 5
60.8 0F
K
C h w c
KRE :
269906516.xls
m=
1+
A g Ec
Af Ef
design
Calculations are performed for crack-width control & thermal shrinkage considerations.
Control Building Basement
full length of wall
Cylinder strength of concrete, fc':
20 MPa or as
2900.653 psi
t
c
Tensile strength of concrete :
323.14624 psi
Diameter of reinforcement bar :
25 mm
Contributory area per bar, A :
37500 mm2
Spacing of bars :
300 mm
or as
58.12512 in2
Clear cover to bars:
50 mm or as
1.968504 in
L' =
Effective cover to bars 'dc' :
62.5 mm or as
2.46063 in
No.of bars NH/2:
6.3333333 bars over ONE face of wall
18 K
0.25 mm or as
0.009843 in
A =2d cs, in
w
RE C T T E
ft'
Ec
1
b
p3 :
185.6349
f s NH
2h
p4 :
1
Area of single bar :
0 in2 or as
0 mm2/met
Bar area :
0 mm2 or bar diameter is :
0.0 mm equivalent diameter
% of reinforcement :
0.000 % required on each face of wall to be added to the design reinforcement if any.
Assumed reinforcement was :
24617 mm2/met
Conclusion :
Bar dia assumed is adequate for limiting the crack-width !!
Minimum reinforcement is :
960.0 mm2/met
Final design reinforcement is :
960.0 mm2/met
269906516.xls
psi
design
269906516.xls
960.0 mm2/met/face/direction
0.2400 % with respect to gross area