Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

5parameter List

Download as pdf or txt
Download as pdf or txt
You are on page 1of 86

Parameter and Signal List Version 41.

222_2

Excitation System
UNITROL F Series

Parameter and Signal List


Version 41.222_2

Rev.
Rev.

G
B

21-08-02 GM
4033 98-09-01 GM

Rev.
Rev.

Rev.

5955 99-06-17 PM
Dept. 1

Rev. F
01-07-02 T.G.
Der.from/Repla.:
Replaced by:

ICA

Dept. 2

D
E

7121 99-11-14 Mo
9595 00-11.02 Mo

Issued: 98-01-08 GM
Check 1: 98-01-15 DE

Document

Format

Langue

Page

No. of pages

ZAB

A4

86

Check 2:
Released: 98-01-15 GM

3BHS102402 E88

Parameter and Signal List Version 41.222_2

Page

Table of Contents
1

PARAMETERS & SIGNALS.........................................................................................................4

1.1
1.2

Display of Parameters and Signals .......................................................................................................... 6


Parameter and Signal List of UNITROL-F ................................................................................................ 6

PARAMETER ...............................................................................................................................9

2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18
2.19
2.20
2.21
2.22
2.23
2.24
2.25
2.26
2.27
2.28
2.29
2.30
2.31

PROGRAMMING........................................................................................................................45

3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
3.15
3.16
3.17
3.18
3.19

4
4.1

ANALOG INPUTS Group 01 .................................................................................................................... 9


ANALOG OUTPUTS Group 02 .............................................................................................................. 12
CONTROL LOGIC Group 03.................................................................................................................. 14
CONVERTER CTRL Group 05............................................................................................................... 15
DATA LOGGER Group 06 .................................................................................................................... 19
DIGITAL I/O Group 07 ........................................................................................................................... 20
DIGITAL I/O EXTD. Group 08 ................................................................................................................ 21
MONITORING Group 09........................................................................................................................ 22
RT MONITORING Group 10 .................................................................................................................. 24
FAULTS, ALARMS Group 11 ............................................................................................................... 25
MAINTENANCE Group 12 ................................................................................................................... 27
IE LIMITER Group 13 .......................................................................................................................... 29
I LIMITER Group 14............................................................................................................................. 30
PQ IEMIN LIM Group 15 ...................................................................................................................... 31
COSPHI CTRL Group 17 ..................................................................................................................... 32
Q CTRL Group 18................................................................................................................................ 33
AVR CTRL Group 19 ........................................................................................................................... 34
AVR IN, PSS Group 20 ........................................................................................................................ 36
MANUAL CTRL Group 21 .................................................................................................................... 38
CH COMMUNICATION Group 24......................................................................................................... 39
FB EXECUTION Group 25 .................................................................................................................. 39
Function Blocks 1 Group 26 ................................................................................................................. 40
Function Blocks 2 Group 27 ................................................................................................................. 40
Function Blocks 3 Group 28 ................................................................................................................. 40
Function Blocks 4 Group 29 ................................................................................................................. 40
Function Blocks 5 Group 30 ................................................................................................................. 40
Function Blocks 6 Group 31 ................................................................................................................. 41
Function Blocks 7 Group 32 ................................................................................................................. 41
Function Blocks 8 Group 33 ................................................................................................................. 41
Function Blocks 9 Group 34 ................................................................................................................. 41
Fieldbus Group 40 ............................................................................................................................. 42

ANALOG INPUTS Group 51 .................................................................................................................. 45


ANALOG OUTPUTS Group 52 .............................................................................................................. 45
CONTROL LOGIC Group 53.................................................................................................................. 45
CONVERTER CTRL Group 55............................................................................................................... 50
DATA LOGGER Group 56 ..................................................................................................................... 50
DIGITAL I/O Group 57 ........................................................................................................................... 50
MONITORING Group 59........................................................................................................................ 51
RT MONITORING Group 60 ................................................................................................................. 51
FAULTS, ALARMS Group 61 ................................................................................................................. 53
MAINTENANCE Group 62 .................................................................................................................. 53
IE LIMITER Group 63 ........................................................................................................................ 53
I LIMITER Group 64........................................................................................................................... 53
PQ IEMIN LIM Group 65 .................................................................................................................... 54
COSPHI CTRL Group 67 ................................................................................................................... 54
Q CTRL Group 68............................................................................................................................... 55
AVR CTRL Group 69 .......................................................................................................................... 56
AVR IN, PSS Group 70 ........................................................................................................................ 57
MANUAL CTRL Group 71 .................................................................................................................... 58
CH COMMUNICATION Group 74......................................................................................................... 58

SIGNALS ...................................................................................................................................58
ANALOG INPUTS Group 101 ................................................................................................................ 58

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
4.17
4.18
4.19
4.20
4.21
4.22
4.23
4.24
4.25
4.26
4.27
4.28
4.29
4.30

ANALOG OUTPUTS Group 102............................................................................................................. 62


CONTROL LOGIC Group 103................................................................................................................ 62
CONVERTER CTRL Group 105 ............................................................................................................ 67
DATA LOGGER Group 106 ................................................................................................................... 68
BASIC DIGITAL I/O GROUP 107........................................................................................................... 69
DIGITAL I/O EXT. Group 108 ................................................................................................................ 70
MONITORING Group 109...................................................................................................................... 71
RT MONITORING Group 110 ................................................................................................................ 73
FAULTS, ALARMS Group 111 ............................................................................................................. 73
MAINTENANCE Group 112.................................................................................................................. 74
IE LIMITER Group 113......................................................................................................................... 76
I LIMITER Group 114........................................................................................................................... 76
PQ IEMIN LIM Group 115 .................................................................................................................... 76
COSPHI CTRL Group 117 ................................................................................................................... 77
Q CTRL Group 118.............................................................................................................................. 78
AVR CTRL Group 119 ......................................................................................................................... 79
AVR IN, PSS Group 120 ...................................................................................................................... 80
MANUAL CTRL Group 121 .................................................................................................................. 81
CH COMMUNICATION Group 124....................................................................................................... 83
CONSTANTS Group 125 ..................................................................................................................... 84
Function Blocks 1 Group 126 ............................................................................................................... 85
Function Blocks 2 Group 127 ............................................................................................................... 85
Function Blocks 3 Group 128 ............................................................................................................... 85
Function Blocks 4 Group 129 ............................................................................................................... 85
Function Blocks 5 Group 130 ............................................................................................................... 85
Function Blocks 6 Group 131 ............................................................................................................... 85
Function Blocks 7 Group 132 ............................................................................................................... 86
Function Blocks 8 Group 133 ............................................................................................................... 86
Function Blocks 9 Group 134 ............................................................................................................... 86

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2

Parameters & Signals


UNITROL-F Standard Excitation System can be adapted to different applications just by
setting its parameters to different values. Parameters are used to define:
-

analog and digital I/O-connections


configurations
limits
controller gains and time constants
reference chain setup
function block application, etc.

UNITROL-F Standard Program (SP) is presented to users with Function Blocks (FB).
Each FB contains one basic function of the Standard Program, like AVR SETPOINT,
AVR PID, CONTROL LOGIC, etc. FBs are connected to each other to create an
excitation application.
The application can include application function blocks (AFBs) as well (see programming
manual).
A Function Block has input pins, output pins and block parameters.
Input pins are usually connected to FB output pins. Input pin is presented as a parameter,
whose value defines the input connection.
Output pins are presented as signals.
Block parameters are used to define the operation of a FB. They are used to give time
constants, gains, limits, etc.

NAME
IN1
IN2

OUT1
OUT2

PAR1
PAR2

Fig. 1: Structure of a function block.

There are parameters and signals as well which do not belong to any FB.
Parameter values can be modified with the UNS 0874 operator's panel or with a special
tool program called CMT (Commissioning and Maintenance Tool), which is running in a
PC which is connected to the UNITROL-F via a communication link.
UNITROL-F has a non-volatile memory for parameter backup. At power-on parameters
are copied to the working memory. The parameter backup can be updated at any time
using
a
special
command
(see
description
of
the
signal
11201,
BACKUP_STORE_MODE). Backup memory can have two different parameter sets. This
is a useful feature if the process requires different settings for the parameters.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2

Signals represent values that are results from measurements or calculations done by the
UNITROL-F control program.

The CMT tool or the UNS 0874 operator's panel can access signals in the same way as
parameters. Signal values can be seen on actual value display of the operator's panel
too.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


1.1

Display of Parameters and Signals


The control program in the UNITROL-F uses 16-bit values for calculations and control. To
have good accuracy and to be able to use the resolution of analog to digital conversions,
certain scaling of values has been used. Scaling has been selected so that resolution of
measurements is maintained and there is space for dynamic variation of values.
On the operator's panel values are usually shown either in relative (in per cent) or
physical (with units) form. Internal values are not available on the panel.
Selection parameters are shown on the panel as texts so that each parameter value is
shown as a short text describing the function if this value is selected.
The CMT can show parameters in different formats. For some parameters three formats
are available:
internal value
relative value in per cent (p.u.)
physical value with units
The format is selected by the user.

1.2

Parameter and Signal List of UNITROL-F


Parameters and signals are divided to several different groups. Parameters and signals
of a certain group belong to the same functional part of the control program. Maximum
number of parameters or signals in one group is 99.

The Group No. is:


1...49
for the parameters
51...99
for the related groups with the programmable input signals
(Offset = 50)
101...149
for the related groups with the signals (Offset = 100)
In the following tables the different columns contain
INDEX

of a parameter contains a group number and an element


number. Last two digits are the element number and other numbers
before them form the group number:
101
parameter group 1, element 01.
10103 signal group 101 related to parameter group 1,
element 03.
5308
programmable input signal group 53 related to parameter
group 1, element 08.
1404
parameter group 14, element 04.
11408 signal group 114 related to parameter group 14, element
08.

INDICATION

is the name of the parameter or signal given in the same format


as it is seen on the panel or CMT. Names with brackets, e.g. [PULSE
BLK] are programmable

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2

FUNCTION

describes (the content of this column is identical to the HELP text


found under More... in CMT ParSig menu):
The function of the parameter or signal.
Short form parameter tuning hints.
DEFAULT using of output signals and programmable
inputs including cross references.
Application hints for output signals and programmable
inputs.

SC

This column defines:


Scaling factor number for the internal values presented
in the columns HL, LL, and DEFAULT to get the values with units
(units defined in column U) presented by CMT or
PANEL UNS 0874.
AI represents an analog process signal input I2
(16-bit signed integer)
AO represents an analog process signal output I2
(16-bit signed integer)
BI represents a binary input by an Boolean value
(0 = FALSE, 0 = TRUE)
BO represents a binary output by an Boolean value
(0 = FALSE, -1 = TRUE)
ENUM enumeration parameter (signal) 0..(n-1), where
n = number of available selections. On panel and CMT only the
selection text is presented.
Maximum value which can be set, given as internal value. For
input pins (signals) HL represents the highest available source signal
address.
Minimum value which can be set. For input pins (signals) LL
represents the lowest available source signal address.
Default values of the firmware. For programmable input pins
(signals) DEF connects the inputs to required source signal. The latter
must only be altered if the configuration will be changed, or AFBs are
implemented to get a new application (see programming manual).
Unit is given for parameters and signals which have an unit or are
relative [per unit p.u.(%)]. Decimal values have the unit d
Tsyn means 1/6 of the converter supply voltage cycle period.
E.g. 1/(6*fn) = 3.333.. ms at fn = 50 Hz supply frequency.

HL

LL
DEF

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


CLASS

Classification used by CMT to display one ore more sets of data


on the screen. This is useful to discriminate data for different tasks.

AL

Alarm

AFB

Application FB

AVR

AVR

CM

Commissioning

COM

Communication

CON
DIAG

Converter
Diagnostics

IMP

Important

IO

I/O

MON
HID
SIP

Monitoring
(Protection)
Special function
Superimposed

SM

Syn Machine

TUN

Tuning

U
VAL

User marked
Not valid

SP

Limits which generate Alarms or Faults, User Event inputs,


Alarm and Fault signals, Alarm and Fault words
SP block inputs which are provided for connecting to
application function blocks (AFB) and all application block pins
and parameters itself
Parameters and Signals of AVR (AUTO), MANual control and
LIMITER functions
Configuration parameters which can be set before first start
(e.g. Id Numbers, Test Ref. Select, Phase Sequence, Limits)
Parameters and signals regarding communication via COM-1
board or COM-5 board
Parameters and signals regarding converter functions
Function block digital outputs which are relevant for
diagnostics, data logger status
Most important parameters at least to be set and most
important signals
Parameters and Signals of I/O function blocks (analog and
digital)
Parameter and signals which are used for Monitoring and
protective functions
Parameters and Signals of less important and special functions
Parameters and Signals of superimposed controllers to the
AVR as P.F.-, Q(VAR)-, Equalizing-CTRL etc.
Parameters and signals regarding synchronous machine and
rotating exciter
Parameters which are needed to tune the system during
commissioning and first start up
Selection of user defined parameter and signals
Parameter or signals which are not valid (yet), depending on
further selections first. On CMT this are grey indicated.

Refers to the Standard Program Block No. in the relevant (GAD)


SW drawing.

Revision history
Rev B (4033) 98-09-01:
510:
Type C6 and C7 added.
521:
Correction and filtering of I_EXC signals in case of ALARM
1215:
Also Italien, Spanish and French available.
5909:
DEFAULT: I_MACH_RELATIVE instead of I_SIN_RELATIVE.
10337:
ALARMs not included anymore. Alarm 109 Common channel fault deleted.
10338:
NEW ALARM RESET of 1s added.
10342:
Alarm 109 deleted.
10902..04: Alarm 144 Batt. fail improved. Difference to UNS0861 HW added.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2

Parameter

2.1

ANALOG INPUTS

Group 01

INDEX

INDICATION

FUNCTION

SC

HL

LL

DEF.

CLASS

SP

101

U ACT HIGH VALUE

65535

14813

CM, IMP, IO

102

U MACHN V

32767

CM, IMP, IO

103

I ACT HIGH VALUE

65535

33333

CM, IMP, IO

104

I MACHN A

32767

CM, IMP, IO

105

ISINPHI OFFSET

100

CM, IO, HID

106

ICOSPHI OFFSET

100

CM, IO, HID

107

AI2 HIGH VALUE

32766

-32767

10000

CM, IO

108

AI2 LOW VALUE

With this setting the p.t. signal will be scaled to get U_MACH_RELATIVE (10101)=10000 at machine nominal voltage
== Un p.t.
Set:
U_ACT_HIGH_VALUE = 1629430 / Un p.t.[V] (DEFAULT for 110V)
Fine tuning: change U_ACT_HIGH_VALUE until U_MACH_RELATIVE (10101) represents the actual machine %
value.
Nominal value of the machine voltage in VOLTS
Tuning:
Set nominal machine Volts which corresponds to U_MACH_RELATIVE (10101)=10000. If the indication
U_MACH_V (10102) is not correct, fine tune U_ACT_HIGH_VALUE (101) again
With this setting the c.t. signal will be scaled to get I_MACH_RELATIVE (10103)=10000 at machine nominal current ==
In c.t.
Set:
I_ACT_HIGH_VALUE= 10000000 / (In c.t.[A]*RB) for 1A c.t.
or 50000000 / (In c.t.[A]*RB) for 5A c.t.
RB
burden resistor on UNS 0862 Interface in Ohm (ref. to HW description). DEFAULT = 300 Ohm
Fine tuning: change I_ACT_HIGH_VALUE until I_MACH_RELATIVE (10103) represents the actual machine % value
Nominal value of the machine current in AMPS
Tuning:
Set nominal machine Amps which corresponds to I_MACH_RELATIVE (10103)=10000. If the indication
I_MACH_A (10104) is not correct, fine tune I_ACT_HIGH_VALUE (103) again
With this parameter HW offset can be eliminated if necessary (1==0.17%):
Tune signal I_SINPHI_REL (10109) to zero, if running machine at least with 50% active load at unity power factor
(ref. to instrumentation e.g. VAR meter etc.)
With this parameter HW offset can be eliminated if necessary (1==0.17%):
Tune signal I_COSPHI_REL (10105) to zero, if running machine at least with 50% reactive load at zero active power
(ref. to instrumentation e.g. WATT meter etc.)
Value that corresponds to max. A/D conv. input value of +10V.
E.g. with AI2_HIGH_VALUE = 10000, the AI2_ACTUAL (10116) becomes 10000 at +10V input.
Set:
AI2_HIGH_VALUE = [(10V-UE_ZERO) / DELTA_UE] * DELTA_UA
UE_ZERO == Burden voltage at AI2_ACTUAL = ZERO
DELTA_UE == Burden voltage range, e.g. 4V if 4...20 mA burdened to 1...5V
DELTA_UA == Range of internal signal AI2_ACTUAL, e.g. 5000 - (-5000) = 10000
Example: 4...20 mA are burdened to 1...5V and transduced to -5000...+5000:
AI2_HIGH_VALUE = [(10V-3V)/4V)*10000= 17500.
Value that corresponds to min. A/D conv. input value of -10V.
E.g. with AI2_LOW_VALUE = -10000, the AI2_ACTUAL (10116) becomes -10000 at -10V input.
Set:
AI2_LOW_VALUE = [(-10V-UE_ZERO) / DELTA_UE] * DELTA_UA
UE_ZERO == Burden voltage at AI2_ACTUAL = ZERO
DELTA_UE == Burden voltage range, e.g. 4V if 4...20 mA burdened to 1...5V
DELTA_UA == Range of internal signal AI2_ACTUAL, e.g. 5000 - (-5000) = 10000
Example: 4...20 mA are burdened to = 1...5V and transduced to -5000...+5000:
AI2_LOW_VALUE = [(-10V-3V)/4V)*10000 = 32500.

32766

-32767

-10000

CM, IO

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2

INDEX
109

AI2 LIVE ZERO

INDICATION

110

AITAC HIGH VALUE

111

AITAC LOW VALUE

112

AITAC LIVE ZERO

113

f MACH NOMINAL

114

AI1E HIGH VALUE

115

AI1E LOW VALUE

10

FUNCTION
If AI2_ACTUAL (10116) falls below this value, AI2_FAILURE (10118) will be generated (Alarm 123
AI failed). Used to monitor live zero input signals, e.g. 4...20 mA. Example: 4...20 mA are burdened to 1...5V and
transduced to -5000...+5000 -> AI2_LIVE_ZERO less than -5000 (calculation see 107).
Value that corresponds to max. A/D conv. input value of +10V.
E.g. with AITAC_HIGH_VALUE =10000, the AITAC_ACTUAL (10119) becomes 10000 at +10V input.
Set:
AITAC_HIGH_VALUE = [(10V-UE_ZERO) / DELTA_UE] * DELTA_UA
UE_ZERO == Burden voltage at AITAC_ACTUAL = ZERO
DELTA_UE == Burden voltage range, e.g. 4V when 4...20 mA burdened to 1...5V
DELTA_UA == Range of internal signal AITAC_ACTUAL, e.g. 5000 - (-5000) = 10000
Example: 4...20 mA are burdened to = 1...5V and transduced to -5000...+5000:
AITAC_HIGH_VALUE = [(10V-3V)/4V)*10000 = 17500.
Value that corresponds to min. A/D conv. input value of -10V.
E.g. with AITAC_LOW_VALUE =10000, the AITAC_ACTUAL (10119) becomes -10000 at -10V input.
Set:
AITAC_LOW_VALUE = [(-10V-UE_ZERO) / DELTA_UE] * DELTA_UA
UE_ZERO == Burden voltage at AITAC_ACTUAL = ZERO
DELTA_UE == Burden voltage range, e.g. 4V when 4...20 mA burdened to 1...5V
DELTA_UA == Range of internal signal AITAC_ACTUAL, e.g. 5000 - (-5000) = 10000
Example: 4...20 mA are burdened to = 1...5V and transduced to -5000...+5000:
AI2_LOW_VALUE = [(-10V-3V)/4V)*10000 = 32500.
If AITAC_ACTUAL (10119) falls below this value, AITAC_FAILURE (10121) will be generated (Alarm 123 AI failed).
Used to monitor live zero input signals, e.g. 4...20 mA. Example: 4...20 mA are burdened to 1...5V and transduced to 5000...+5000 -> AITAC_LIVE_ZERO less than -5000 (calculation see 110).
Nominal frequency of the machine;
0==50 Hz, 1==60 Hz, 2==16 2/3 Hz (1ph), 3==25Hz (1ph), 4==50Hz (1ph),
5==60Hz (1ph)
NOTE:
for 16 2/3 Hz variant 2 (V2) of UNS 1860b is required
for 25 Hz variant 3 (V3) of UNS 1860b is required
( 3 5 only Substatus 3 )
Value that corresponds to max. A/D conv. input value of +10V.
E.g. with AI1E_HIGH_VALUE =10000, the AI1E_ACTUAL (10127) becomes 10000 at +10V input.
Set:
AI1E_HIGH_VALUE = [(10V-UE_ZERO) / DELTA_UE] * DELTA_UA
UE_ZERO == Burden voltage at AI1E_ACTUAL = ZERO
DELTA_UE == Burden voltage range, e.g. 4V if 4...20 mA burdened to 1...5V
DELTA_UA == Range of internal signal AI1E_ACTUAL, e.g. 5000 - (-5000) = 10000
Example: 4...20 mA are burdened to 1...5V and transduced to -5000...+5000:
AI1E_HIGH_VALUE = [(10V-3V)/4V)*10000 = 17500.
Value that corresponds to min. A/D conv. input value of -10V.
E.g. with AI1E_LOW_VALUE = -10000, the AI1E_ACTUAL (10127) becomes -10000 at -10V input.
Set:
AI1E_LOW_VALUE = [(-10V-UE_ZERO) / DELTA_UE] * DELTA_UA
UE_ZERO == Burden voltage at AI1E_ACTUAL = ZERO
DELTA_UE == Burden voltage range, e.g. 4V if 4...20 mA burdened to 1...5V
DELTA_UA == Range of internal signal AI1E_ACTUAL, e.g. 5000 - (-5000) = 10000
Example: 4...20 mA are burdened to = 1...5V and transduced to -5000...+5000:
AI1E_LOW_VALUE = [(-10V-3V)/4V)*10000 = 32500.

3BHS102402 E88

Rev. G

SC
1

HL
32766

LL
-32767

DEF.
-32767

U
-

CLASS
CM, IO

SP
5

32766

-32767

10000

CM, IO

32766

-32767

-10000

CM, IO

32766

-32767

-32767

CM, IO

CM, IMP, IO

32766

-32767

10000

CM, IO

83

32766

-32767

-10000

CM, IO

83

ENUM

Parameter and Signal List Version 41.222_2

INDEX
116

AI1E LIVE ZERO

INDICATION

117

AI2E HIGH VALUE

118

AI2E LOW VALUE

119

AI2E LIVE ZERO

11

FUNCTION
If AI1E_ACTUAL (10127) falls below this value, AI1E_FAILURE (10129) will be generated (Alarm 123
AI failed). Used to monitor live zero input signals, e.g. 4...20 mA. Example: 4...20 mA are burdened to 1...5V and
transduced to -5000...+5000 -> AI2_LIVE_ZERO less than -5000 (calculation see 114).
Value that corresponds to max. A/D conv. input value of +10V.
E.g. with AI2E_HIGH_VALUE =10000, the AI2E_ACTUAL (10130) becomes 10000 at +10V input.
Set:
AI2E_HIGH_VALUE = [(10V-UE_ZERO) / DELTA_UE] * DELTA_UA
UE_ZERO == Burden voltage at AI2_ACTUAL = ZERO
DELTA_UE == Burden voltage range, e.g. 4V if 4...20 mA burdened to 1...5V
DELTA_UA == Range of internal signal AI2E_ACTUAL, e.g. 5000 - (-5000) = 10000
Example: 4...20 mA are burdened to 1...5V and transduced to -5000...+5000:
AI2E_HIGH_VALUE = [(10V-3V)/4V)*10000 = 17500.
Value that corresponds to min. A/D conv. input value of -10V.
E.g. with AI2E_LOW_VALUE = -10000, the AI2E_ACTUAL (10130) becomes -10000 at -10V input.
Set:
AI2E_LOW_VALUE = [(-10V-UE_ZERO) / DELTA_UE] * DELTA_UA
UE_ZERO == Burden voltage at AI2E_ACTUAL = ZERO
DELTA_UE == Burden voltage range, e.g. 4V if 4...20 mA burdened to 1...5V
DELTA_UA == Range of internal signal AI2E_ACTUAL, e.g. 5000 - (-5000) = 10000
Example: 4...20 mA are burdened to = 1...5V and transduced to -5000...+5000:
AI2E_LOW_VALUE = [(-10V-3V)/4V)*10000 = 32500.
If AI2E_ACTUAL (10130) falls below this value, AI2E_FAILURE (10132) will be generated (Alarm 123
AI failed). Used to monitor live zero input signals, e.g. 4...20 mA. Example: 4...20 mA are burdened to 1...5V and
transduced to -5000...+5000 -> AI2E_LIVE_ZERO less than -5000 (calculation see 117).

3BHS102402 E88

Rev. G

SC
1

HL
32766

LL
-32767

DEF.
-32767

U
-

CLASS
CM, IO

SP
83

32766

-32767

10000

CM, IO

84

32766

-32767

-10000

CM, IO

84

32766

-32767

-32767

CM, IO

84

Parameter and Signal List Version 41.222_2


2.2

ANALOG OUTPUTS

INDEX
201

AO1 NOMINAL V

INDICATION

202

AO1 OFFSET REL

203

AO1 NOMINAL VAL

204

AO2 NOMINAL V

205

AO2 OFFSET REL

206

AO2 NOMINAL VAL

207

AO1E NOMINAL V

208

AO1E OFFSET REL

209

AO1E NOMINAL VAL

210

AO2E NOMINAL V

211

AO2E OFFSET RELV

12

Group 02

FUNCTION
Output voltage range which corresponds to nominal value range of selected signal:
Uout = (AO1.[IN] + AO1_OFFSET_REL) * (AO1_NOMINAL_V / AO1_NOMINAL_VAL)
E.g. Uout = (10000+0)*(10V/10000) = 10V; transfers internal RELATIVE value to an +/-10V analog signal.
Offset which is added to the input e.g.:
Uout = (0...10000 + 2500) * (8V/10000) =2...10V transfers internal RELATIVE value 0...10000 to live zero output
2...10V or
Uout = (9000...11000 - 8500) * (8V/2000) = 2...10V transfers internal RELATIVE value 9000...11000 to live zero output
2...10V (e.g. typical AVR ref. value to analog output).
Nominal value range of signal which is connected to the IN-input. E.g. 10000 for internal RELATIVE value, or 2000 for the
DEFAULT signal range of the AVR set point.
Output voltage range which corresponds to nominal value range of selected signal:
Uout = (AO2.[IN] + AO2_OFFSET_REL) * (AO2_NOMINAL_V / AO2_NOMINAL_VAL)
E.g. Uout = (10000 + 0) * (10V/10000) = 10V; transfers internal RELATIVE value to an +/-10V analog signal.
Offset voltage which is added to the input e.g.:
Uout = (0...10000 + 2500) * (8V/10000) = 2...10V transfers internal RELATIVE value 0...10000 to live zero output
2...10V or
Uout = (9000...11000 - 8500) * (8V/2000) = 2...10V transfers internal RELATIVE value 9000...11000 to live zero output
2...10V (e.g. typical AVR ref. value to analog output)
Nominal value range of signal which is connected to the IN-input. E.g. 10000 for internal RELATIVE value.
Output voltage range which corresponds to nominal value range of selected signal:
Uout = (AO1E.[IN] + AO1E_OFFSET_REL) * (AO1E_NOMINAL_V / AO1E_NOMINAL_VAL)
E.g. Uout = (10000 + 0) * (10V/10000) = 10V; transfers internal RELATIVE value to an +/-10V analog signal.
Offset
which is added to the input e.g.:
Uout = (0...10000 + 2500) * (8V/10000)*10000 + 2V = 2...10V transfers internal RELATIVE value 0...10000 to live zero
output 2...10V or
Uout = (9000...11000 - 8500) * (8V/2000) =2 ...10V transfers internal RELATIVE value 9000...11000 to live zero output
2...10V (e.g. typical AVR ref. value to analog output)
Nominal value range of signal which is connected to the IN-input. E.g. 10000 for internal RELATIVE value, or 2000 for the
DEFAULT signal range of the AVR set point.
Output voltage range which corresponds to nominal value range of selected signal:
Uout = (AO2E.[IN] + AO2E_OFFSET_REL) * (AO2E_NOMINAL_V / AO2E_NOMINAL_VAL)
E.g. Uout = (10000 + 0) * (10V/10000)*10000 = 10V; transfers internal RELATIVE value to an +/-10V analog signal.
Offset which is added to the input e.g.:
Uout = (0...10000 + 2500) * (8V/10000)*10000 + 2V = 2...10V transfers internal RELATIVE value 0...10000 to live zero
output 2...10V or
Uout = (9000...11000 - 8500) * (8V/2000) = 2...10V transfers internal RELATIVE value 9000...11000 to live zero output
2...10V (e.g. typical AVR ref. value to analog output)

3BHS102402 E88

Rev. G

SC
1

HL
10000

LL
0

DEF.
10000

mV

CLASS
IO

SP
1

32766

-32767

IO, HID

32766

-32767

10000

mV

IO

10000

10000

mV

IO

32766

-32767

IO, HID

32766

-32767

10000

mV

IO

10000

10000

mV

IO

85

32766

IO, HID

85

32766

-32767

10000

mV

IO

85

10000

10000

mV

IO

86

32766

IO, HID

86

-32767

-32767

Parameter and Signal List Version 41.222_2

INDEX
212

AO2E NOMINAL VAL

INDICATION

213

DATASET2. [IN1]

214

DATASET2. [IN2]

215

DATASET2. [IN3]

216

DATASET4. [IN1]

217

DATASET4. [IN2]

218

DATASET4. [IN3]

13

FUNCTION
Nominal value range of signal which is connected to the IN-input. E.g. 10000 for internal RELATIVE value, or 2000 for
the DEFAULT signal range of the AVR set point.
Fast data output to field bus
DEFAULT: Connected to Status word BINARY-INTEGER converter output (12995) if fieldbus application is loaded.
NOTE:
This option is only available with external field bus adapter HW and if the relevant field bus application is
downloaded.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data output to field bus
DEFAULT: connected to actual reference value REF_ACT (10353) of active controller AUTO (AVR), MANUAL COS
PHI (P.F.) or Q (AVR) CTRL, if fieldbus application is loaded.
NOTE:
This option is only available with external field bus adapter HW and if the relevant field bus application is
downloaded.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data output to field bus.
DEFAULT: not used. Spare output for application.
NOTE:
This option is only available with external field bus adapter HW and if the relevant field bus application is
downloaded.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data output to field bus.
DEFAULT: not used. Spare output for application.
NOTE:
This option is only available with external field bus adapter HW.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data output to field bus.
DEFAULT: not used. Spare output for application.
NOTE:
This option is only available with external field bus adapter HW.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data output to field bus.
DEFAULT: not used. Spare output for application.
NOTE:
This option is only available with external field bus adapter HW.
Ref. to relevant fieldbus installation and start-up instructions.

3BHS102402 E88

Rev. G

SC
1

HL
32766

LL
-32767

DEF.
10000

CLASS
IO

SP
86

AI

19999

12501

IO, COM

126

AI

19999

12501

IO, COM

126

AI

19999

12501

IO, COM

126

AI

19999

12501

--

IO, COM

128

AI

19999

12501

IO, COM

128

AI

19999

12501

IO, COM

128

Parameter and Signal List Version 41.222_2


2.3
INDEX
301

CONTROL LOGIC
INDICATION
RELEASE FCB OFF

302

IMPOSED CTRL
MODE

303
304

RECLOSE INH TIME


FLASH OFF LEVEL

305
306

FLASH MAX TIME


CMPD ON LEVEL

307
308

CMPD MAX TIME


CH CONFIG

14

Group 03

FUNCTION
Releases FCB_OFF signal (10309) in parallel with EXC_OFF status (10308):
0==NO, 1==YES
Preselects the available imposed control mode(s):
0==NO (Imposed control mode blocked)
1==COSPHI CTRL (only cosphi (P.F.) control possible)
2==Q CTRL (only Q (VAR) control possible)
3==EXTERNAL SEL (releases the inputs SEL_Q_CTRL (5312) and SEL_COSPHI_CTRL (5313)
Defines the minimum time between FCB closing operations.
Machine voltage level (higher value of U_MACH_REL or U_SYN_REL for types C1...C4, I_EXC_RELATIVE for type
C5 respectively) at which field flashing breaker is switched off (FLASH_ON_FIELD (10330) =0). Effective only if
SUPPLY_MODE (901) is set to SHUNT (value = 0).
Maximum allowed field flashing period. If exceeded excitation is shut down by FLASH_FAILURE (10331).
Machine voltage level (higher value of U_MACH_REL or U_SYN_REL for types C1...C4, I_EXC_RELATIVE for type
C5 respectively) below which DC compounding will be switched on with FLASH_ON_FIELD (10330) = TRUE. Effective
only if SUPPLY_MODE (901) is set to SHUNT (value = 0).
NOTE: compounding and field flashing is switched by the same contactor.
Ref. to HW schematic diagram for more information.
Maximum allowed DC compounding period. If exceeded excitation is shut down by CMPD_FAILURE (10332).
Configuration parameter to set the channel configurations:
0==SFE
Single channel system
1==AFT CH1
Physical channel 1 of an AUTO-AUTO 2 channel system, both channels are identical
with AUTO and MANUAL control
2==AFT CH2
Physical channel 2 of an AUTO-AUTO 2 channel system, both channels are identical
with AUTO and MANUAL control
3==Not configured ! == DEFAULT setting. CH FAULT 13 "Not configured !" is forced
NOTE: While downloading release UN41x22x rom file to target, this channel is set as "not configured"
(DEFAULT=3). This leads to CH FAULT 13 "Not configured !", which indicates that this unit must be
configured first.
Values >0 start channel communication via 2nd serial RS 485 link.
During operation of a 2 channel system, the active channel can be put to single operation SFE making the
standby channel ready for maintenance works. After that, the channel interconnection cable can be removed.
Its not possible to put the non active standby channel to SFE, since this would unconditionally take
over the operation.

3BHS102402 E88

Rev. G

SC
ENUM

HL
1

LL
0

DEF.
0

U
-

CLASS
CM, IMP

SP
74

ENUM

1,2,3

CM, IMP, SIP

79

0.1
0.01

600
5000

0
1500

100
3000

s CM, TUN
% CM, IMP

74
75

0.1
0.01

600
8000

10
0

100
5000

s CM, TUN
% CM, IMP

75
75

0.1
ENUM

600
1,2

10
0

100
0

s
-

75
76

CM, TUN
AVR, CM,
IMP

Parameter and Signal List Version 41.222_2

INDEX
309

INDICATION
CB CONFIG

FUNCTION
0==AC SIDE:
1==DC W/O DEEXC:

2==DC WITH DEEXC:

3==W/O CROWBAR:
310

2.4

DLY FLDB ACKN

U EXC V NOMINAL

INDICATION

502

I EXC A NOMINAL

503

PHASE SEQ CW

504

U SYN V NOMINAL

505

U SYN MIN

Field breaker is on the converter input side. Discharge by CROWBAR thyristor.


EXC_OFF causes PULSE_BLOCKING, if parameter 301 set to YES.
Field breaker WITHOUT discharge contact is on converter output.
Discharge by CROWBAR thyristor.
EXC_OFF causes INV_CTRL prior to PULSE_BLOCKING
Field breaker WITH discharge contact is on converter output.
Discharge by breaker itself.
EXC_OFF causes INV_CTRL prior to PULSE_BLOCKING
No crowbar used (indirect excitation system)

During this time the FLDB_REF_OK signal (10354) will be reset, enabling the fieldbus masters balancing to REF_ACT
(10353). Set time bigger than normal fieldbus response time.
NOTE:
This option is only available with external field bus adapter HW and if the relevant field bus application is
downloaded.
Ref. to relevant fieldbus installation and start-up instructions.

CONVERTER CTRL

INDEX
501

15

SC
HL
ENUM 0,1,2

LL
0

DEF.
3

U
-

CLASS
CM, CON,
IMP

SP
74

0,1

CM, TON

77

100

Group 05

FUNCTION
SC
Nominal excitation voltage Uen in VOLTS (at converter output).
1
Tuning: Set nominal excitation Volts which corresponds to U_EXC_RELATIVE (10505) =10000.
0.1
Nominal excitation current Ien in AMPS
Tuning: Set nominal excitation Amps. If indication I_EXC_A (10502) doesnt correspond exactly with expected value
(shunt sensing etc.) because of burden or gain error, use SET_I_CONV_A (507) for fine tuning.
NOTE: The set value cant be bigger than the HW code which is read from interface, even if a bigger value
SET_I_CONV_A (507) has been saved to FPROM.
ENUM
Phase sequence of converter supply; 1==R-T-S, 2==R-S-T
NOTE: Parameter altering becomes effective only after rebooting (power up). Converter will be started with this setting
regard-less of real phase sequence applied. If started with wrong sequence the CH FAULT 34 Converter fault.
appears with rising excitation current.
1
Nominal converter supply voltage U SYN in VOLTS. (no load)
Tuning: Set nominal supply voltage in VOLTS. This parameter can be used as well for fine tuning (compensating for
voltage divider or gain error) of U_EXC_V (10506) signal (used for panel and CMT).
NOTE: Single phase operation of the converter (CONV_SUPPLY (515) set to 1_PH_CONV) causes sensing error
of 0 to -15% (depending on firing angle) of U_SYN_V (10504) and U_SYN_RELATIVE (10503) signals.
Set point of the undervoltage Monitoring. If supply voltage drops below that, Conv. undervoltage EVENT is written to fault 1
logger. There is no ALARM generated by this event.

3BHS102402 E88

Rev. G

HL
1000

LL
0

DEF.
0

U
V

CLASS
CON, SM,
IMP

SP
73

5000
0

CON, SM,
IMP

73

CM, CON,
HID

73

1000

CM, CON,
IMP

73

130

AL, CON,
MON

73

Parameter and Signal List Version 41.222_2


INDEX
506

INDICATION
I EXC MAX LEVEL

507

SET I CONV A

508

SET U CONV V

509

SET MAX BR TEMP

510

SET CONV TYPE

511

SET QUADR TYPE

16

FUNCTION
Instantaneous excitation overcurrent tripping level in % of conv. rated current I_CONV_A_RATED (10509).
If the excitation current exceeds this level for longer than DLY_IE_MAX (513),
CH FAULT 2 Inst. exc. overcurrent will be generated.
NOTE: The set value is related to nominal converter current instead of nominal excitation current.
Set I_EXC_MAX_LEVEL corresponding to approx. 3 times of the value of 502.
Overriding of HW code I_CONV_A by a parameter value > 0 (0 = type code resistors in use)
NOTE: this parameter overwrites the nominal output current of the converter defined by type code resistors of the C1, C2,
C3, C5 types, if the set parameter value >0. Consider if doing so, that the c.t. burden on the power interface must
fit with the changed setting. With all C4 types there is no type code resistor available; therefore this parameter has
to be set according to converter data.
If this parameter is used for fine tuning (compensating for burden or gain error) of I_EXC_A (10502) signal used
for panel and CMT, consider that the ALARM 129 Type code changed will be generated, which will be cleared
only after the new parameter set has been saved (BACKUPSTOREMODE). Consider as well that bigger values
than the read hardware code are not accepted to be saved (except C4 without HW code).
Overriding of HW code U CONV V by parameter value > 0 (0 = type code resistors in use)
NOTE: This parameter overwrites the nominal input voltage of the converter defined by type code resistors of the C1, C2,
C3, C5 types, if the set parameter value >0. Consider if doing so, that the voltage divider on the power interface
must fit with the altered setting. With all C4 types there is no type code resistor available; therefore this parameter
must be set according to converter data.
Consider that at values >0 the ALARM 129 "Type code changed" will be generated, which will be cleared only after
the new parameter set has been saved (BACKUPSTOREMODE). Consider as well that bigger values than the
read hardware code are not accepted to be saved (except C4 without HW code).
Overriding of HW code MAX BR TEMP DEG by parameter value > 0 (0 = type code resistors in use)
NOTE: This parameter overwrites the maximum bridge temperature of the converter
defined by type code resistors, if the set parameter value >0.
C4 type measures the air inlet temperature instead of heat sink temperature at C1...C3 types. The value must be
set to 45 DEG for nominal converter rating (Alarm Conv.overtemp.alarm (code 105) above 35 DEG. Increase this
value if converter used with derating at higher ambient temperature.
Consider that at values >0 the ALARM 129 "Type code changed" will be generated, which will be cleared only after
the new parameter set has been saved (BACKUPSTOREMODE). Consider as well that bigger values than the
read hardware code are not accepted to be saved (except C4 without HW code).
Overriding of HW code CONV TYPE by parameter value > 0:
0 = type code resistors used, 1==C1, 2==C2, 3==C3, 4==C4, 5==C5 (Chopper), 6==C6(3 phase AC controller),
7==C7 (fn converter 50/60 Hz)
NOTE: This parameter overwrites the type size of the converter defined by type code resistors, if the set parameter value
>0. C6 and C7 uses the same HW code regarding converter voltage and current as type C2. With all C4 types
there is no type code resistor available; therefore this parameter must be set according to converter data.
Consider that at values >0 the ALARM 129 "Type code changed" will be generated, which will be cleared only after
the new parameter set has been saved (BACKUPSTOREMODE).
Overriding of HW code QUADR TYPE by parameter value > 0:
0 = type code resistors used, 1==TWO QUADRANT, 4==FOUR QUADRANT
NOTE: This parameter overwrites the type of the converter defined by type code resistors,
if the set parameter value >0.
With this SW version the value 4 must not be used!
Consider that at values >0 the ALARM 129 "Type code changed" will be generated, which will be cleared only after
the new parameter set has been saved (BACKUPSTOREMODE).

3BHS102402 E88

Rev. G

SC
1

HL
330

LL
20

DEF.
230

U
%

CLASS
AL, CON,
MON

SP
73

0.1

6000
0

CM, CON,
HID

73

2000

CM, CON,
HID

73

150

AL, CM,
CON, HID

73

ENUM

CM, CON,
HID

73

ENUM

1,4

CM, CON,
HID

73

Parameter and Signal List Version 41.222_2


INDEX
512

INDICATION
RIPPLE TIME

513

DLY IE MAX

514

CONV CT LOCATION

515

CONV SUPPLY

516

ALPHA MIN LIMIT

517

ALPHA MAX LIMIT

17

FUNCTION
SC
ON delay of the RIPPLE MONITOR. If converter current ripple occur for longer than the set time, depending on parameter 1
RIPPLE_MON_MODE (521), ALARM 124 "Converter failed" or, FAULT 34 Converter fault will be generated. The fault
branch no. will be logged in the CYCLE LOG. MEM (see 10515).
The set value is the number of faults which are counted before responding. With a single branch fault the time
NOTE:
is given by set integer value times the cycle time of the converter supply voltage 1/fn.
E.g. DEFAULT value = 10 corresponds to a delay of 10 * 20 ms = 200 ms at 50Hz.
1
ON delay of the instantaneous exc. current relay. If the excitation current exceeds I_EXC_MAX_LEVEL (506) for longer
than DLY_IE_MAX (513), CH FAULT 2 inst. exc. overcurrent will be generated.
During the delay time + 30*Tsyn the FREEWHL_CROWBAR (10516) output is TRUE for external freewheeling function
at 2 channel (TWIN converter) application.
The resulting time delay is equal to the set integer value multiplied by 1/(6*fn).
NOTE:
E.g. DEFAULT value of 4 corresponds to a delay of 4 * 3.3ms = 13.3ms at 50 Hz
ENUM
Selection of the converter C.T. location:
0==AT CONV INPUT
DEFAULT, valid for all C1 and C2 thyristor types and also for C3 in single
channel configuration
1==AT COMMON LINE
Only for 2 Channel (TWIN) type AFT, if converter C.T.s put to common line
input or if the chopper version UNS 4870 (type C5) is used. In this case
current will be measured also in the non duty channel for back up protection.
NOTE: In AFT application with mode AT CONV INPUT, the stand-by channel receives the excitation current signal only
across the Modbus channel-to-channel communication link. This link is not fast enough to ensure instanteanous
overcurrent protection (CH FAULT 2) in the stand-by channel, only delayed overcurrent (CH FAULT 3)
protection is available.
ENUM
Type of converter supply source:
0==3 PH CONV
1==1 PH CONV / CHOPPER (fully controlled / C5= Chopper).
NOTE: Parameter altering becomes effective only after rebooting (power up).
Single phase operation (1 PH CONV) causes sensing error between 0 and -15% on U_SYN_RELATIVE
(10503) and U_SYN_V (10504) depending on firing angle.
1
ALPHA MIN (minimum firing angle).
Setting for max. positive output voltage of converter. Value in degree.
NOTE: Type C5 (Chopper): The setting is ignored. IGBT duty cycle internally limited to (180 -3 DEG)/180 DEG.
Thyristor duty cycle = 100%.
Download only permitted with values between LL and HL -> change value temporarily
at C5 !
1
ALPHA MAX (maximum firing angle).
Setting for max. negative output voltage of converter. Value in degree. Consider required commutation reserve if DXN
(519) is not used (set to 0). With correct setting of DXN (519) the value can be increased up to 165 degree.
NOTE: Type C5 (Chopper): The setting is ignored. IGBT duty cycle = 0.31 ms * 2 fn.
fn = syn. machine nominal frequency
Thyristor duty cycle = (180 -170 DEG)/180 DEG.
Download only permitted with values between LL and HL -> change value temporarily
with C5 !

3BHS102402 E88

Rev. G

HL
10

LL
1

DEF.
10

1/fn

CLASS
AL, CM, CON,
IMP, MON

SP
73

30

*Tsyn

AL, CM, CON,


IMP, MON

73

CM, CON,
HID

73

CM, CON,
IMP

47

60

10

15

el

CON, HID

47

165

130

150

el

CON, HID

47

Parameter and Signal List Version 41.222_2


INDEX
518

INDICATION
USYN COMPENS SEL

519

DXN

520

I EXC FILT TC

521

RIPPLE MON. MODE

18

FUNCTION
SC
ENUM
0==OFF: The actual value of converter supply is not considered for ALPHA calculation
1==ON: The converter output is kept constant at constant UCTRL if converter supply voltage varies in the range of +/-30%
U SYN V NOMINAL (504).
CAUTION: dont use this option with single phase supply (515=1 PH CONV) because of the error of U_SYN sensing (see
signals 10503 and 10504). Dont use it together with series compounding.
NOTE: Type C5 (Chopper): The setting is ignored, there is no compensation available
0.1
Additional commutation reserve proportional to the excitation current.
Set:
DXN = 2 * ek * (I_CONV_A_RATED/I_EXC_A_NOMINAL) [%].
ek = short circuit reactance of excitation transformer in %.
NOTE: Type C5 (Chopper): The setting is ignored, there is no current depending reserve required.
1
Optional excitation current measurement filter time constant.
NOTE:
Can be used if the load inductance is to small, especially with indirect excitation systems and single phase
converter supply. Consider the increased measuring time constant influence to the closed loop controllers
MANUAL CTRL and EXC CURRENT limiter etc.
ENUM
Modes OFF and ALARM are only applicable from SW release 41.221!
Ref. also to RIPPLE_TIME (512) and BRANCH_NO (10515)
0==OFF
To be used only if surplus monitor action expected.
1==ALARM
Used for converter redundancy at single channel system SFE In case one branch may fail.
ALARM 124 "Coverter failed" is generated in case of branch fault.
Note: Not selfresetting, must be reset.
2==CH_FAULT
Standard. Must be used at 2 channel system AFT.
CH FAULT 34 "Converter fault" is generated in case of branch fault.
NOTE:
Ripple Monitor trigger condition:
DCPEAK + SCHWEL > DCEND
DCPEAK Peak current of the thyristor branch conducting cycle (at 30 DEG)
DCEND
Current at the end of previous conducting cycle
SCHWEL 6% of converter nominal current (corresponding to 1.5V burden voltage).
The branch number failed can be read from signal BRANCH_NO (10516).
From release 41.221_1:
In case of an ALARM, the burden signal has an error since the converter gets a freewheeling period of 60 deg. This error
will be corrected by a factor 1.2 to the I_EXC_RELATIVE(10501) and I_EXC_A (10502) signal. In addition
I_EXC_RELATIVE is filtered by 20ms in this case. Consider this increased measuring time constant for manual control
and excitation current limiter.

3BHS102402 E88

Rev. G

HL
1

LL
0

DEF.
0

U
-

CLASS
CON, HID

SP
47

300

CON, HID

47

100

ms

DIA, HID

AL, CM,
CON, MON,
IMP

73

Parameter and Signal List Version 41.222_2


2.5

19

DATA LOGGER Group 06

INDEX
601

DLOG.[IN1]

INDICATION

602

DLOG.[IN2]

603

DLOG.[IN3]

604

DLOG.[IN4]

605

DLOG.[IN5]

606

DLOG.[IN6]

607

DLOG.TRIGG COND

608

DLOG.TRIGG VALUE

609
610

DLOG.TRIGG DELAY
DLOG.SAMPL INT

611

[DLOG.TRIG]

612

[DLOG.STOP]

613

[DLOG.RESTART]

FUNCTION
Input of DATA_LOGGER. Selects the signal which is measured in channel 1. This channel is as well used as trigger
channel if DLOG.TRIGG_COND (607) is set to 2, 3 or 4.
DEFAULT: connected to U_MACH_RELATIVE (10101).
Input of DATA_LOGGER. Selects the signal which is measured in channel 2.
DEFAULT: connected to I_EXC_RELATIVE (10501).
Input of DATA_LOGGER. Selects the signal which is measured in channel 3.
DEFAULT: connected to U_CTRL_OUT_CH (12110).
Input of DATA_LOGGER. Selects the signal which is measured in channel 4.
DEFAULT: connected to P_MACH_RELATIVE (10106).
Input of DATA_LOGGER. Selects the signal which is measured in channel 5.
DEFAULT: connected to Q_MACH_RELATIVE (10110).
Input of DATA_LOGGER. Selects the signal which is measured in channel 6.
DEFAULT: connected to U_EXC_RELATIVE (10505).
Selects the triggering condition for the data logger:
0
EXTERNAL, i.e. by CMT TRIG button or if input 611 = TRUE.
1
FAULT + EXT.
2
DIFFERENCE: two successive values of data logger CH1 are larger than DLOG.TRIGG_VALUE (608).
3
MAX / 4==MIN value of data logger CH1 exceeds / falls below DLOG.TRIGG_VALUE (608).
Reference value that is used for the triggering conditions DIFFERENCE, MAX or MIN set by parameter
DLOG.TRIGG_COND (607).
Number of samples collected after triggering instant. Length of data logger is 1000 samples in each channel.
Sampling interval defining how often a measurement is made in each channel.
The DATA_LOGGER will be triggered if the input is TRUE and the parameter 607 has been set for 0==EXTERNAL or
1==FAULT + EXT.
DEFAULT: not used (12501).
After triggering, the DATA_LOGGER will be stopped if the input is TRUE and the logger is not full yet.
DEFAULT: not used (12501).
The DATA_LOGGER will be restart (ready for new trigger command) after it has been stopped (either full or by
DLOG.STOP command)
DEFAULT: not used (12501).

3BHS102402 E88

Rev. G

SC
AI
BI

HL
19999

LL
0

DEF.
10101

U
-

CLASS
DIAG, HID

SP
130

AI
BI

19999

10501

DIAG, HID

130

AI
BI

19999

12110

DIAG, HID

130

AI
BI

19999

10106

DIAG, HID

130

AI
BI

19999

10110

DIAG, HID

130

AI
BI

19999

10505

DIAG, HID

130

0,2,3

DIAG, HID

130

32767

-32768

20000

DIAG, HID

130

1
1

1000
1000

0
1

200
3

DIAG, HID
DIAG, HID

130
130

BI

19999

12501

m
s
-

DIAG, HID

130

BI

19999

12501

DIAG, HID

130

BI

19999

12501

DIAG, HID

130

ENUM

Parameter and Signal List Version 41.222_2


2.6

DIGITAL I/O

INDEX
701
702

DOX02.[IN]
DOX03.[IN]

INDICATION

703

DOX04.[IN]

704

DOX05.[IN]

705

DOX06.[IN]

706

DOX07.[IN]

707

DOX08.[IN]

708

DOX09.[IN]

709

DOX10.[IN]

710

DOX11.[IN]

711

DOX12.[IN]

712

DOX13.[IN]

713

DOX14.[IN]

714

DOX15.[IN]

715
716
717

DOX16.[IN]
DOX17.[IN]
DOX18.[IN]

20

Group 07
FUNCTION
DEFAULT: EXC_TRIP from CONTROL LOGIC. Pulls TRIP relay on UNS 0863. (Ref. to 10350 for more information).
DEFAULT: Field breaker closing command (1.5s) FCB_ON_CTRL from CONTROL LOGIC.
NOTE: No action in the non active channel.
DEFAULT: Field breaker trip command (1.5s) FCB_OFF from CONTROL LOGIC.
NOTE: No action in the non active channel.
DEFAULT: Status AUTO_ON from CONTROL LOGIC. AUTO (AVR) control is active.
NOTE: No action in the non active channel.
DEFAULT: Status MAN_ON from CONTROL LOGIC. MANUAL CTRL is active.
NOTE: No action in the non active channel.
DEFAULT: Status ON_SUPERIMPOSED from CONTROL LOGIC. Preselected controller is active.
NOTE: No action in the non active channel.
DEFAULT: Status REF_MAX_ACTIVE from CONTROL LOGIC. Set point (ref.) of selected controller in MAX (HL)
position. NOTE: No action in the non active channel.
DEFAULT: Status REF_MIN_ACTIVE from CONTROL LOGIC. Set point (ref.) of selected controller in MIN (LL) position.
NOTE: No action in the non active channel.

SC
BI
BI

HL
19999
19999

LL
0
0

DEF.
10350
10305

U
-

CLASS
AFB, IO
AFB, IO

SP
9
10

BI

19999

10309

AFB, IO

11

BI

19999

10310

AFB, IO

12

BI

19999

10311

AFB, IO

13

BI

19999

10314

AFB, IO

14

BI

19999

10312

AFB, IO

15

BI

19999

10313

AFB, IO

16

DEFAULT: Status ON_OE_LIMITER from AVR INPUT. One of the Over Excitation Limiters (OEL) is active.
NOTE: No action in the non active channel.
DEFAULT: Status ON_UE_LIMITER from AVR INPUT. One of the Under Excitation Limiters (UEL) is active.
NOTE: No action in the non active channel.
DEFAULT: Status LOCAL from CONTROL LOGIC. System has been put to LOCAL CTRL by panel or CMT.
NOTE: No action in the non active channel.
DEFAULT: Status RDY_XFER_A_M from FOLLOW UP CTRL. Difference between AUTO and MANUAL is below
NOT_OK_LEVEL (2120). This signal enables A-M transfer by Panel or CMT in LOCAL mode.
NOTE: No action in the non active channel.
DEFAULT: Status EXC_ON from CONTROL LOGIC. Excitation is switched ON.
NOTE: No action in the non active channel.
DEFAULT: Field flashing contactor ON command FLASH_ON_FIELD from CONTROL LOGIC. The same output will be
activated during battery compounding cycle as well (ref. 10331). NOTE: No action in the non active channel.
DEFAULT: not used. Spare digital output for application. NOTE: No action in the non active channel.
DEFAULT: not used. Spare digital output for application. NOTE: No action in the non active channel.
DEFAULT: Status ALARM from CONTROL LOGIC. Any ALARM is active.
NOTE:
No action in the non active channel.
2 channel system: No action in the standby channel. Any ALARM (including also channel faults) from standby
channel operates the ALARM relay via the duty channel using the serial 2 channel communication link.

BI

19999

12002

AFB, IO

17

BI

19999

12003

AFB, IO

18

BI

19999

10339

AFB, IO

19

BI

19999

12117

AFB, IO

20

BI

19999

10307

AFB, IO

21

BI

19999

10330

AFB, IO

22

BI
BI
BI

19999
19999
19999

0
0
0

12501
12501
10338

AFB, IO
AFB, IO
AFB, IO

23
24
25

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


2.7

DIGITAL I/O EXTD.

INDEX
801

DO02E.[IN]

INDICATION

802

DOE03.[IN]

803

DOE04.[IN]

804

DOE05.[IN]

805

DOE06.[IN]

806

DOE07.[IN]

807

DOE08.[IN]

808

DOE09.[IN]

809

DOE10.[IN]

810

DOE11.[IN]

811

DOE12.[IN]

812

DOE13.[IN]

813

DOE14.[IN]

21

Group 08

FUNCTION
DEFAULT: EXC_TRIP from CONTROL LOGIC. Pulls TRIP relay on 2nd UNS 0863. (Ref. to 10350 for more
information).
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.

3BHS102402 E88

Rev. G

SC
BI

HL
19999

LL
0

DEF.
10350

U
-

CLASS
AFB, I/O

SP
104

BI

19999

12501

AFB, I/O

105

BI

19999

12501

AFB, I/O

BI

19999

12501

AFB, I/O

106
,10
7

BI

19999

12501

AFB, I/O

108

BI

19999

12501

AFB, I/O

109

BI

19999

12501

AFB, I/O

110

BI

19999

12501

AFB, I/O

111

BI

19999

12501

AFB, I/O

112

BI

19999

12501

AFB, I/O

113

BI

19999

12501

AFB, I/O

114

BI

19999

12501

AFB, I/O

115

BI

19999

12501

AFB, I/O

116

Parameter and Signal List Version 41.222_2


INDEX
814

DOE15.[IN]

815

DOE16.[IN]

816

DOE17.[IN]

817

DOE18.[IN]

2.8

INDICATION

MONITORING

INDEX
901

INDICATION
SUPPLY MODE

902

START IE MONITOR

903

DLY IE MONITORING

904

START UEL MONIT

905

DLY UEL MONITOR

906

DLY DIODE ALARM

907

DEV U MONITORING

22

FUNCTION
DEFAULT: not used. Spare digital output for application.
NOTE:
Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.
DEFAULT: not used. Spare digital output for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
No action in the non active channel.

SC
BI

HL
19999

LL
0

DEF.
12501

U
-

CLASS
AFB, I/O

SP
117

BI

19999

12501

AFB, I/O

118

BI

19999

12501

AFB, I/O

119

BI

19999

12501

AFB, I/O

120

HL
1

LL
0

DEF.
0

U
-

CLASS
IMP, MON

SP
80

0.01

2000

100

500

CM, MON

80

0.1

100

20

CM, MON,
TUN

80

0.01

10000

100

100

CM, MON

80

0.1

100

20

CM, MON,
TUN

80

0.1

500

20

100

CM, MON,
HID

80

0.01

5000

500

1500

CM, MON

81

Group 09
FUNCTION
Normal converter supply mode:
0==SHUNT (from machines terminals)
1==LINE or PE supply (from aux. LINE or Pilot Exciter machine)
NOTE: If LINE supply is used temporarily only (e.g. for BRAKING sequence), this parameter must not be altered, but
the ALARM 145 "Test supply" can be suppressed via input A145_BLK/C5_TST(5907).
Margin, in % of nominal excitation current, between actual excitation current limiting and Monitoring characteristics. If exc.
current exceeds this margin, then exc. overcurrent Monitoring starts.
NOTE: Consider the selectivity to other OEL protections and the control error of the limiter.
ON delay of overcurrent Monitoring. After delay OC1_EXC_CURR (10905) will be TRUE, i.e. IE_LIMITER was not
successful within set ON delay.
NOTE: Consider the selectivity to other OEL protections and the limiter settling time after big transients.
Margin, in % of nominal reactive current, between set -Q(P) limiting and loss of excitation Monitoring characteristics. If
reactive current drops below this margin, then UEL Monitoring starts.
NOTE: Consider the selectivity to other UEL protections and the control error of the limiter.
ON delay of UEL Monitoring. After delay Signal UE1 FAULT (10907) will be TRUE, i.e. Q(P) limiter was not successful
within set ON delay.
NOTE: Consider the selectivity to other UEL protections and the limiter settling time after big transients.
Delay of DIODE_ALARM (10718) signal from optional UNS 0864. If TRUE for longer than the set delay, the
BR_INTRPT_ROT_REC (10911) will be TRUE and ALARM 115 Rot. rectifier OC will be released, i.e. a branch interrupt
in the rotating rectifier was detected.
Margin, in % of nominal voltage, between U_MACH_REL and U_SYN_REL. If the difference between this two signals
exceeds the set margin, either one of following signal will be TRUE after a delay of 100 ms:
If U_MACH_REL < (U_SYN_REL - DEV_U_MONITORING) then U_MACH_FAIL (10908) = TRUE
If U_SYN_REL < (U_MACH_REL - DEV_U_MONITORING) then U_SYN_FAIL (10909) = TRUE
NOTE: This Monitoring function is not available at 1_PH_CONV and/or LINE or PE supply.

3BHS102402 E88

Rev. G

SC
ENUM

Parameter and Signal List Version 41.222_2

23

INDEX
908

INDICATION
SEL B/L MODE

FUNCTION
Not applicable for this release 41.22x

SC
ENUM

HL
-

LL
-

DEF.
0

U
-

909

DELTA U MACH

Not applicable for this release 41. 22x

0.01

910
911
912

BOOST TRIG
DLY B/L MONITOR
START V/HZ MON

913

DLY V/HZ MONITOR

914

SEL PT FAIL DYN

915

DELAY DU/DT

916

TRIG DI/DT BLK

917

FLDBFAULT MODE

918

200

Not applicable for this release 41. 22x


0.01
Not applicable for this release 41. 22x
1
Margin in % between V/Hz limiting characteristic set by parameters 1911 and 1912 and protection characteristic.
0.01
Monitoring starts if U_MACH_RELATIVE is higher than the set characteristic.
ON delay of the V/Hz Monitoring function. After delay V/HZ_FAULT (10920) will be TRUE, i.e. the limiter was not
0.1
successful within set ON delay.
NOTE: In MANUAL CTRL mode, the V/Hz limiter is a superimposed type, whose response time has to be considered.
ENUM
Selects for the dynamic P.T. failure detection mode:
0==OFF
Function not used.
1==ON
Dynamic P.T. failure detection released.
2==TEST
As ON but only U_MACH_FAIL_DYN (10921) is life, the ALARM 120 Machine P.T. fail and the output
U_MACH_FAIL (10908) are inhibited.
NOTE: To avoid surplus action the parameters 915 and 916 must be carefully set up and tested before final release.
Dont use this function at 3 phase shunt supply, because the Monitoring function set by DEV_U_MONITORING
(907) is more robust and doesnt need performance tests.
1
ON delay of the dU/dt_TRIGGER input. ON delay is required to compensate for the measuring time constant of the input
5909 signal. Increase this delay if the blocking effect by input 5909 signal transients occurs to late. Vice versa the delay
must be decreased if the blocking action occurs also and to early at a P.T. failure, because of fast syn. machine response.
After setting of 916 check for correct delay by load applications which just releases dU/dt_TRIGGER. In this case blocking
action must be prior to dU/dt_TRIGGER.
0.01
Trigger point of the input 5909 transients. Transients above this point are instantaneously blocking the dU/dt_TRIGGER
input. Set this value as small as possible, but so that no blocking effect occurs at steady state operation. Check the action
of the monitor in TEST position by interrupting one phase of the P.T. leads, when ON_LINE and in MAN operation. Output
U_MACH_FAIL_DYN (10921) indicates the action also in TEST position.
ENUM
Selects the type of fieldbus communication fault:
0==EVENT
Only logging to FAULT LOGGER
1==ALARM
Forces output ALARM (10338)
2==CHANNEL FAULT
Forces output CH_FAIL LOGGED (10349)
3==EXCITATION TRIP Forces output EXC_TRIP (10350)

-0
2000

100

12000
250
500

100

FLDBFAULT
TIMEOUT

Selects the activation delay:


Communication FAULT was to be active for longer than the set time until it is accepted.

919

PWR PACK/I-O HW

Selects the type of power supply unit in combination with interface UNS 1860 type
0==0861 power pack 1860a or b measuring interface
1==0868 power pack supply and 1860a measuring interface
2==0868 power pack supply and 1860b measuring interface

3BHS102402 E88

20

ENUM

Rev. G

%
ms
%

CLASS
CM, HID,
MON
CM, MON,
TUN
CM, MON
CM, MON
CM, MON

SP

80

20

CM, MON

80

HID, MON

81

100

50

ms

MON, TUN

81

2000

250

MON, TUN

COM

81

150

20

m
s

COM

81

MON

80

Parameter and Signal List Version 41.222_2


2.9

RT MONITORING

INDEX
1001

INDICATION
SEL RTM MODE

1002

U BRUSH RELATIVE

1003

U DROP RELATIVE

1004
1005
1006

TC OFF LINE
TC ON LINE
RFN RELATIVE

1007

RF0 RELATIVE

1008

RTEMP DEG NOM

1009

RTEMP DEG ALARM

1010

RTEMP DEG FAULT

24

Group 10

FUNCTION
SC
HL
ENUM 4
Preselects the available Rotor Temp. Monitoring mode:
0==OFF
RTM inactive (DEFAULT)
1==ON
RTM released
2==TEST1
Temp. simulating (R = U_EXC_TEST (1012) / 100% I_EXC)
ALARM and FAULT outputs blocked
3==TEST2
Temp. simulating (R = U_EXC_TEST (1012) / 100% I_EXC)
ALARM and FAULT outputs released
4==TEST3
RTM released but ALARM and FAULT outputs blocked
NOTE: Preadjust the parameters 1002... 1008 and use TEST3 to verify measured temperature before releasing.
Refer also to U_EXC_TEST (1012) setting for temperature indication results during test. Consider the
10s measuring time constant as well (it takes about 50s for steady state indication).
0.01
1000
Fixed part of voltage drop across the slip ring brushes.
Set U_BRUSH_RELATIVE [%] = 100 * U_BRUSH [V] / U_EXC_V_NOMINAL (501)
NOTE: U_BRUSH = Current independent voltage drop across both brushes (+ and -)
U_EXC_V_NOMINAL = Required converter output voltage at set rotor temp. RTEMP_DEG_NOM
(1008), which includes both voltage drops U_BRUSH_RELATIVE and U_DROP_RELATIVE. Readjust
parameter 501 first if required.
0.01
2000
Current dependent drop between Exciter output and field winding including current dependent brush drop.
Set U_DROP_RELATIVE [%] = 100 * RL [Ohm] / RFN [Ohm]
NOTE: RL = resistance of connections between converter output and field winding including brush resistance
RFN = Field winding resistance at RTEMP_DEG_NOM (1008)
Effective time constant if machine OFF_LINE = no load time constant Td0 of the synchronous machine.
0.01
2000
Effective time constant if machine ON_LINE = transient time constant Td of the synchronous machine.
0.01
100
0.01
15000
Relative total resistance seen from converter output at RTEMP_DEG_NOM (1008):
Set RFN_RELATIVE = 10000% / [100% - U_BRUSH_RELATIVE (1002) - U_DROP_RELATIVE (1003)]
NOTE: After this setting output RF_RELATIVE (11001) represents relative field winding resistance = 100% at
set nominal rotor temp. RTEMP_DEG_NOM (1008).
Use RFN_RELATIVE parameter for fine tuning of RTEM_DEG (11002) output if required.
0.01
15000
Relative field resistance at zero degree centigrade:
Set RF0_RELATIVE = (100% * DEG_R0) / (DEG_R0 + RTEMP_DEG_NOM (1008))
NOTE: DEG_R0 is the fictive temperature for zero field resistance (Cu = 235K).
RTEM_DEG_NOM: see 1008.
Rotor temperature at RF_RELATIVE (11001) = 100%
1
150
Reduce this value to the specified rotor temp. at full load point.
Rotor temperature ALARM level. If temp. increases above this level RTEMP_ALARM (11004) will be TRUE, which 1
generates ALARM 104 Rotor temp. Alarm.
Set this level to the required ALARM level.
1
Rotor temperature FAULT level. If temp. increases above this level RTEMP_FAULT (11005) will be TRUE, which
generates FAULT 7 Rotor overtemp.trip.
Reduce this level to the required FAULT level.
NOTE: Be sure that rotor temp. measurement is O.K. before reducing to avoid the risk of unexpected TRIP of the
system.

3BHS102402 E88

Rev. G

LL
1

DEF.
0

U
-

CLASS
CM, MON

SP
121

CM, MON, TUN

121

CM, MON, TUN

121

20
10
5000

600
100
10000

s
s
%

CM, MON
121
CM, MON
121
CM, MON, TUN 121

4000

7460

CM, MON, TUN

121

30

80

CM, MON

121

150

50

110

CM, MON

121

200

50

160

CM, MON

121

Parameter and Signal List Version 41.222_2

INDEX
1011

INDICATION
HOT SPOT CONST

1012

U EXC TEST

2.10

FUNCTION
With this constant the hot spot temp. HS_RTEMP_DEG (11003) will be calculated as follows:
HS_RTEMP_DEG = RTEMP_DEG (11002) + ((HOT_SPOT_CONST/100) * IE^2[p.u])
NOTE: The hot spot is not considered in for ALARM and FAULT evaluations.
Test parameter simulating excitation voltage if SEL_RTM_MODE = TEST 1 or TEST 2.
RF_RELATIVE [%] = RE_TOT_RELATIVE [%] * (U_EXC_TEST / 100%)

FAULTS, ALARMS

INDEX
1101
1102

USER EVENT1.[IN]
USER EVENT1.TYPE

INDICATION

1103

USER EVENT1.TEXT

1104

USER EVENT1.DLY

1105
1106
1107

USER EVENT2.[IN]
USER EVENT2.TYPE
USER EVENT2.TEXT

1108

USER EVENT2.DLY

1109
1110
1111

USER EVENT3.[IN]
USER EVENT3.TYPE
USER EVENT3.TEXT

1112

USER EVENT3.DLY

1113
1114
1115

USER EVENT4.[IN]
USER EVENT4.TYPE
USER EVENT4.TEXT

1116

USER EVENT4.DLY

1117
1118

USER EVENT5.[IN]
USER EVENT5.TYPE

25

SC
0.01

HL
2000

LL
0

DEF.
0

U CLASS
% CM, MON

SP
121

0.01

20000

10000

% CM, MON,
HID

121

SC
BI
ENUM

HL
19999
4

LL
0
1

DEF.
12501
4

U
-

CLASS
AL
AL

SP
48
48

HID

48

0.01

32767

HID

48

BI
ENUM
-

19999
4
-

0
1
-

12501
4
-

AL
AL
HID

49
49
49

0.01

32767

HID

49

BI
ENUM
-

19999
4
-

0
1
-

12501
4
-

AL
AL
HID

50
50
50

32767

HID

50

0,01
ENUM
-

19999
4
-

0
1
-

12501
4
-

AL
AL
HID

51
51
51

0.01

32767

HID

51

BI
ENUM

19999
4

0
1

12501
4

AL
AL

52
52

Group 11

FUNCTION
Activates logging of an external ALARM or FAULT into the FAULT LOGGER.
Selects the type of external EVENT:
0==EXCITATION TRIP
Forces output EXC_TRIP (10350)
1==CHANNEL FAULT
Forces output CH_FAIL_LOGGED (10349)
2==AVR FAULT
Forces output AVR_FAULT (10910)
3==ALARM
Forces output ALARM (10338)
4==EVENT
Only logging to FAULT LOGGER
Defines the text which can be read from the FAULT LOGGER.
NOTE: With this SW version TEXT cannot be changed. Default text read: User Event 1
Selects the activation delay:
External EVENT has to be active for longer than the set time delay until it is accepted.
Activates logging of an external ALARM or FAULT into the FAULT LOGGER.
Selects the type of external EVENT: (See USER EVENT1.TYPE for available values).
Defines the text which can be read from the FAULT LOGGER.
NOTE: With this SW version TEXT cannot be changed. Default text read: User Event 2
Selects the activation delay:
External EVENT has to be active for longer than the set time delay until it is accepted.
Activates logging of an external ALARM or FAULT into the FAULT LOGGER.
Selects the type of external EVENT: (See USER EVENT1.TYPE for available values).
Defines the text which can be read from the FAULT LOGGER.
NOTE: With this SW version TEXT cannot be changed. Default text read: User Event 3
Selects the activation delay:
External EVENT has to be active for longer than the set time delay until it is accepted.
Activates logging of an external ALARM or FAULT into the FAULT LOGGER.
Selects the type of external EVENT: (See USER EVENT1.TYPE for available values).
Defines the text which can be read from the FAULT LOGGER.
NOTE: With this SW version TEXT cannot be changed. Default text read: User Event 4
Selects the activation delay:
External EVENT has to be active for longer than the set time delay until it is accepted.
Activates logging of an external ALARM or FAULT into the FAULT LOGGER.
Selects the type of external EVENT: (See USER EVENT1.TYPE for available values).

3BHS102402 E88

BI

Rev. G

Parameter and Signal List Version 41.222_2


INDEX
1119

INDICATION
USER EVENT5.TEXT

1120

USER EVENT5.DLY

1121
1122

USER EVENT6.[IN]
USER EVENT6.TYPE

1123

USER EVENT6.TEXT

1124

USER EVENT6.DLY

26

FUNCTION
Defines the text which can be read from the FAULT LOGGER.
NOTE: With this SW version TEXT cannot be changed. Default text read: User Event 5
Selects the activation delay:
External EVENT has to be active for longer than the set time delay until it is accepted.
Activates logging of an external ALARM or FAULT into the FAULT LOGGER.
Selects the type of external EVENT: (See USER EVENT1.TYPE for available values).
Defines the text which can be read from the FAULT LOGGER.
NOTE: With this SW version TEXT cannot be changed. Default text read: User Event 6
Selects the activation delay:
External EVENT has to be active for longer than the set time delay until it is accepted.

3BHS102402 E88

Rev. G

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
HID

SP
52

0.01

32767

HID

52

BI
ENU
M
-

19999
4

0
1

12501
4

AL
AL

53
53

HID

53

0.01

32767

HID

53

Parameter and Signal List Version 41.222_2


2.11

27

MAINTENANCE Group 12

INDEX
1201

TEST MODE

INDICATION

1202

CMT UNF ADDR

1203

DEVICE ID

1204

POT1 VALUE

1205

POT2 VALUE

1206

PERIOD BTW POT1/2

1207

DEBUG ADDR 1

1208

DEBUG ADDR 2

1209

DEBUG ADDR 3

1210

DEBUG ADDR 4

1211

DEBUG ADDR 5

1212

DEBUG ADDR 6

1213

WRITE ENABLE KEY

FUNCTION
This parameter is used to start special functions for testing and maintenance. After the function has been completed TEST
MODE changes to value 0. If an error occurs during special function, TEST MODE is set to value 12.
Following functions are available:
0==NOT_ACTIVATED
No function is active
1==CLEAR_FAULT_LOGG.
Clears the content of the Fault Logger
2==CALC_PROGRAM_LOAD
Calculates the load of UN-F control program. The result can be read from
PROGRAM_LOAD (11209). The calculation will take about 20 s.
The node address of the device in the communication link for CMT/UNF PC tool. Not used with CMT for DCS500 (only
single drive application available).
The node address number at the Modbus panel link. The UNS 0874 panel is always Master and has the ID = 0.
DEFAULT: ID of the channel 1 (or single channel).
NOTE:
Set the ID No. to 2 in the 2nd channel. The address will only be accepted from master (UNS 0874) after
disconnection of the panel UNS 0874 (reboot).
Constant test reference 1 for commissioning. (Upper) value of the SQUARE_WAVE (11203) signal. Normally used for
manual tuning PI(D) controllers.

HL
1,2

LL
0

DEF.
0

U
-

CLASS
CM, HID

250

250

CM, HID

31

CM, HID

32767

TUN

Constant test reference 2 for commissioning. (Lower) value of the SQUARE_WAVE (11203) signal. Normally used for
manual tuning PI(D) controllers.

32767

TUN

The cycle period of the square wave generator for commissioning. During this period the SQUARE_WAVE (11203) signal
becomes the POT1_VALUE (1204) and the POT2_VALUE (1205) with a duty cycle of 50% each. Normally used for
manual tuning PI(D) controllers.
Debugging address which gives access to any known address in the firmware. Mainly used for debugging of not
documented addresses within the function blocks (SP) by ABB software experts.
Debugging address which gives access to any known address in the firmware. Mainly used for debugging of not
documented addresses within the function blocks (SP) by ABB software experts.
Debugging address which gives access to any known address in the firmware. Mainly used for debugging of not
documented addresses within the function blocks (SP) by ABB software experts.
Debugging address which gives access to any known address in the firmware. Mainly used for debugging of not
documented addresses within the function blocks (SP) by ABB software experts.
Debugging address which gives access to any known address in the firmware. Mainly used for debugging of not
documented addresses within the function blocks (SP) by ABB software experts.
Debugging address which gives access to any known address in the firmware. Mainly used for debugging of not
documented addresses within the function blocks (SP) by ABB software experts.
KEY number: To enable parameter change, KEY has to be equal to PIN.

0.01

30000

800
327
68
50
327
68
1
100

TUN

65535

DIAG

65535

DIAG

65535

DIAG

65535

DIAG

65535

DIAG

65535

DIAG

1000

358

HID

3BHS102402 E88

Rev. G

SC
ENUM

SP

Parameter and Signal List Version 41.222_2


INDEX
1214

INDICATION
WRITE ENABLE PIN

1215

LANGUAGE

1216

ACTUAL VALUE 1

1217

ACTUAL VALUE 1

1218

ACTUAL VALUE 1

1219

FIELDBUS NODE ADD

1220

MACRO SELECT

28

FUNCTION
SC
1
PIN number to protect the parameter settings. Indication is 0 if the KEY number (1213) is not correct. In this case the
parameters are write protected.
Important: if PIN number is other than DEFAULT, before saving parameters to FPROM you should write the PIN
number down to the system documentation and save enabled state (KEY==PIN) to disk, if CMT
available.
Don't use "0" as PIN number since KEY number has to be >0!
NOTE:
if PIN number gets lost, download saved parameter set (with KEY==PIN) or set parameters to DEFAULT
values and change parameters according to application by hand.
ENUM
Selects the language used for texts in the panel and in the CMT.
0==ENGLISH
1==GERMAN
2==ITALIAN
3==SPANISH
4==FRENCH
NOTE:
ITALIAN, SPANISH, FRENCH are only available from release 41.221_1 (Substatus 1).
Address of the actual value signal displayed on the panel row 2.
BI
DEFAULT: MODE_INDICATION (10301)
Address of the actual value signal displayed on the panel row 3.
BI
DEFAULT: U_MACH_V (10102)
Address of the actual value signal displayed on the panel row 4.
BI
DEFAULT: I_EXC_A (10502)
1
Node Address of the DDCS link.
NOTE:
DDCS link is only used as point to point connection to the fieldbus adapter module, therefore the address is
always 1.
ENUM
Not applicable for this firmware release 41.22x:
0==NONE
1==MACRO 1
2==MACRO 2
3==MACRO 3

3BHS102402 E88

Rev. G

HL
1000

LL
0

DEF.
358

U
-

CLASS
HID

CM, IMP

19999

1030
1

CM, HID

19999

1030
1

CM, HID

19999

1030
1

CM, HID

255

CM, HID

CM, HID

SP

Parameter and Signal List Version 41.222_2


2.12

IE LIMITER

INDEX
1301

REF1 IETH

INDICATION

1302

REF2 IETH

1303

REF1 IEMAX

1304

REF2 IEMAX

1305

TIME IEMAX SEL

1306

TC IERED MAX-TH

1307

TIME IE BACK INT

1308

not used

1309

KOEL IE

29

Group 13
FUNCTION
(Upper) thermal limiting setpoint (1) of excitation current. Parameter is active as long as the input SEL_REF2_IETH
(6303) is not active. Set continuous allowed excitation current (100...110% I_EXC_RELATIVE). If the REF2_IETH (1302)
is used too, set REF1_IETH equal to or higher than REF2_IETH (1302).
(Lower) thermal limiting setpoint (2) of excitation current. Parameter is active as long as the input SEL_REF2_IETH
(6303) is active. Set REF2_IETH equal to or lower than REF1_IETH (1301).
(Upper) ceiling limiting setpoint (1) of excitation current. Parameter is active as long as the input SEL_MAX2_IEMAX
(6304) is not active. Set ceiling excitation current which is allowed during TIME_IEMAX_SEL (1305). If the REF2_IEMAX
(1304) is used too, set REF1_IEMAX equal to or higher than REF2_IEMAX (1304).
(Lower) ceiling limiting setpoint (2) of excitation current. Parameter is active as long as the input SEL_MAX2_IEMAX
(6304) is active. Set REF2_IEMAX equal to or lower than REF1_IEMAX (1303).
Ceiling cycle at excitation current equal to selected ceiling setpoint REF1_IEMAX (1303) or REF2_IEMAX (1304).
Overcurrent cycle for any current IE between IETH and IEMAX:
t=[(REF_IEMAX[p.u.]-0.9REFx_IETH)2 / (IE[p.u.]-0.9REFx_IETH) 2]*TIME_IEMAX_SEL.
With this time constant the reference value REF_IE_LIM_ACT will be reduced to selected IETH after an overcurrent
cycle.
Time which is needed to fully reset overcurrent integrator after I_EXC_RELATIVE (10501) has been fallen below selected
REF1, 2_IETH value.

Limiter gain in % of actual AVR gain. Lead/lag time constants TA, TB see AVR CTRL group 19.

3BHS102402 E88

Rev. G

SC
0.01

HL
20000

LL
1000

DEF.
10500

U
CLASS
% AVR, TUN

SP
55

0.01

20000

1000

10500

% HID, AVR

55

0.01

32767

1000

16000

% AVR, TUN

55

0.01

32767

1000

16000

% HID, AVR

55

0.1

1000

10

100

AVR, TUN

55

0.01

1000

10

100

HID, AVR

55

0.1

32767

100

1000

AVR, TUN

55

0.01

32767

16000

200

% CM, HID,
AVR
% AVR, TUN

55

1000
0
0

50

55

Parameter and Signal List Version 41.222_2


2.13

30

I LIMITER Group 14

INDEX
1401

REF1 I MACH TH

INDICATION

1402

REF2 I MACH TH

1403

I MACH EQUIVALENT

1404

TIME I EQUIVALENT

1405

TC I MACH RED

1406

TIME I BACK INT

1407

KOEL I MACH

1408

KUEL I MACH

FUNCTION
(Upper) thermal limiting setpoint (1) of stator current. Parameter is active as long as the input SEL_REF2_ITH2 (6402) is
not active. Set continuous allowed stator current (100...110% I_MACH_RELATIVE). If the REF2_I_MACH_TH (1402) is
used too, set REF1_I_MACH_TH equal or higher than REF2_I_MACH_TH (1402).
(Lower) thermal limiting setpoint (2) of stator current. Parameter is active as long as the input SEL_REF2_ITH2 (6402) is
active. Set REF2_I_MACH_TH equal or lower than REF1_I_MACH_TH (1401).
At this current level the overcurrent cycle time is equal to set time TIME_I_EQUIVALENT (1404).
NOTE: There is no instantaneous stator current limitation at this current level.
Time delay at stator current level equal to I MACH EQUIVALENT. Overcurrent cycle for any stator overcurrent I:
t=[(I_MACH_EQUIVALENT[p.u.]-0.9REFx_I_MACH_TH)2 / (I[p.u.]-0.9REFx_I_MACH_TH) 2]*TIME_I_EQUIVALENT
NOTE: There is no instantaneous stator current limitation at I_MACH_EQUIVALENT.
With this time constant the reference value REF_I_LIM_ACT will be reduced from 332% to selected REF_I_MACH_TH
after an overcurrent cycle.
Time which is needed to fully reset overcurrent integrator after I_MACH_RELATIVE (10103) has been fallen below
selected REF1, 2_I_MACH_TH value.
OE (lag) limiter gain in % of actual AVR gain. Lead/lag time constants TA, TB see AVR CTRL group 19.
NOTE: With parameter value = 0, the whole limiter block is skipped. Consider processor load increase of approx. 1%
when using this limiter function (Check CPU load by parameter 1201). Ref. also to parameter 7005 for activation
of limiter.
UE (lead) limiter gain in % of actual AVR gain. Lead/lag time constants TA, TB see AVR CTRL group 19.
NOTE: if the value is set very low (<10%) to get stable operation, then PSS option UN 0869 may be required. Ref. to
7008 regarding limiter using.
With parameter value = 0, the whole limiter block is skipped. Consider processor load increase of approx. 1%
when using this limiter function (Check CPU load by parameter 1201). Ref. also to param. 7008 for activation of
limiter.

3BHS102402 E88

Rev. G

SC
0.01

HL
20000

LL
1000

DEF.
10500

U
CLASS
% AVR, TUN

SP
56

0.01

20000

1000

10500

% HID, AVR

56

0.01

32767

1000

16000

% AVR, TUN

56

0.1

1000

10

100

AVR, TUN

56

0.01

1000

10

100

HID, AVR

56

0.1

32767

10

1000

AVR, TUN

56

200

50

% AVR, TUN

56

200

50

% AVR, TUN

56

Parameter and Signal List Version 41.222_2


2.14

PQ IEMIN LIM

INDEX
1501

REF0 Q(P) LIM

1502

REF25 Q(P) LIM

1503

REF50 Q(P) LIM

1504

REF75 Q(P) LIM

1505

INDICATION

Q(P) LIM

1506

KUEL Q(P) LIM

1507

REF IEMIN LIM AVR

1508

KUEL IEMIN LIM A

31

Group 15
FUNCTION
Characteristic -Q = f(P) at P = 0%. Consider that the characteristic in the power chart will be moved by the square
of U_MACH [p.u.]. E.g. If U_MACH_RELATIVE = 0.9, then -Qlim = 0.81*-Qlim set.
Characteristic -Q = f(P) at P = 25%. Consider that the characteristic in the power chart will be moved by square of
U_MACH [p.u.]. E.g. If U_MACH_RELATIVE = 0.9, then -Qlim = 0.81*-Qlim set.
Characteristic -Q = f(P) at P = 50%. Consider that the characteristic in the power chart will be moved by square of
U_MACH [p.u.]. E.g. If U_MACH_RELATIVE = 0.9, then -Qlim = 0.81*-Qlim set.
Characteristic -Q = f(P) at P = 75%. Consider that the characteristic in the power chart will be moved by square of
U_MACH [p.u.]. E.g. If U_MACH_RELATIVE = 0.9, then -Qlim = 0.81*-Qlim set.
Characteristic -Q = f(P) at P = 100%. Consider that the characteristic in the power chart will be moved by square of
U_MACH [p.u.]. E.g. If U_MACH_RELATIVE = 0.9, then -Qlim = 0.81*-Qlim set.
P Q limiter gain in % of ACTUAL AVR gain. Lead/lag time constants TA, TB see AVR CTRL group 19.
NOTE: if the value is set very low (<10%) to get stable operation, than PSS option UN 0869 is may be required.
Ref. to 7007 regarding limiter using too.
Minimum excitation current limit.
NOTE: It is not required using this limiter to hold a minimum converter (thyristor hold) current, because the gate
pulse stream always ensures converter starting. Ref. to 7009 for limiter using.
IE MIN limiter gain in % of actual AVR gain. Lead/lag time constants TA, TB see AVR PID group 19.
Ref. to 7009 for limiter using.

3BHS102402 E88

Rev. G

SC
0.01

HL
0

LL
-15000

DEF.
-15000

U
CLASS
% AVR, TUN

SP
61

0.01

-15000

-15000

% AVR, TUN

61

0.01

2000

-15000

-15000

% AVR, TUN

61

0.01

2000

-15000

-15000

% AVR, TUN

61

0.01

2000

-15000

-15000

% AVR, TUN

61

200

50

% AVR, TUN

61

0.01

5000

% AVR, TUN

62

200

50

% AVR, TUN

62

Parameter and Signal List Version 41.222_2


2.15

COSPHI CTRL Group 17

INDEX
1701

INDICATION
RELEASE FOLLOW C

1702

RAMPTIME REF COS

1703

HL REF COSPHI

1704

LL REF COSPHI

1705

PRESET REF COSPHI

1706

DEADBAND IMP CTRL

1707

32

DELAY IMP CTRL

FUNCTION
SC
ENUM
COSPHI setpoint follows the actual operating condition; 0==OFF, 1==ON.
NOTE: Use this option if no setpoint feedback via analog output is made to control desk. It ensures that COSPHI_CTRL
starts from actual operating point if switched ON.
Setpoint ramp time , valid for remote RAISE, LOWER commands (traveling time between HL and LL at permanent
0.1
command).
1
COSPHI setpoint maximum limit.
NOTE: Value to be set = 10000 - [(COSPHImin overexcited)*10000]. E.g. for COSPHImin overexcited = 0.6, set
10000-[(0.6)*10000] = 4000. Where COSPHImin = lowest overexcited P.F.
Dont set this parameter below LL_REF_COSPHI (1704).
Consider that the set value is valid as well for the IN_REF_EXT_COS (6705) signal, thus use the same range at
analog input channel (ref. to 107..112), otherwise the remote ref. signal range doesnt correspond to the set
limits.
1
COSPHI setpoint minimum limit.
Value to be set = [(COSPHImin underexcited)*10000] -10000, e.g. for COSPHImin underexcited = 0.8, set [(0.8)*10000] 10000 = -2000. Where COSPHImin = lowest underexcited P.F.
NOTE: Dont set this parameter above HL_REF_COSPHI (1703). Consider that the set value is valid as well for the
IN_REF_EXT_COS (6705) signal, thus use the same range at analog input channel (ref. to 107..112 and
115...120), otherwise the remote ref. signal range doesnt correspond to the set limits.
1
COSPHI setpoint preset value. Preset value which becomes active if TRIG_PRST_COS (6704) is TRUE. Set it between
HL and LL_REF_COSPHI. Consider the setpoint characteristic:
VALUE = 10000 - [(PRESET_REF_COSPHI overexcited)*10000] e.g. = 10000 - [0.8 * 10000] = 2000
VALUE = [(PRESET_REF_COSPHI underexcited)*10000] -10000 e.g. = [0.9 * 10000] -10000 = -1000
DEFAULT: This value will dynamically be set by ON_PRESET_CMD (10304) at start excitation and if machine goes
OFF_LINE.
0.01
Error dead band of the selected imposed controller. Within the set dead band there is no imposed controller action. If the
error signal leaves the dead band, first DELAY_IMP_CTRL (1707) must elapse before action.
NOTE: If set value is too small, the timer may not be reset because of fluctuations and the timer function may be lost i.e.
instantaneous action at external transients. On the other hand if set value is too big, then accuracy of control
decreases.
Delay which starts if imposed controller error signal exceeds dead band. Ref. to 1706.
0.1

3BHS102402 E88

Rev. G

HL
1

LL
0

DEF.
0

U
-

CLASS
CM, IMP, SIP

SP
58

1000

600

CM, HID, SIP

58

7000

5000

CM, HID, SIP

58

-7000 -5000

CM, HID, SIP

58

7000

-7000 0

CM, HID, SIP

58

1000

50

% SIP, TUN

58

1000

50

58

SIP, TUN

Parameter and Signal List Version 41.222_2


2.16

33

Q CTRL Group 18

INDEX
1801

INDICATION
RELEASE FOLLOW Q

1802

RAMPTIME REF Q

1803
1804
1805

HL REF Q CTRL
LL REF Q CTRL
PRESET REF Q CTRL

FUNCTION
Q_CTRL setpoint follows the actual operating condition; 0==OFF, 1==ON.
NOTE: Use this option if no setpoint feedback via analog output is made to control desk. It ensures that Q_CTRL
starts from actual operating point if switched on.
Setpoint ramp time , valid for remote RAISE, LOWER commands (traveling time between HL and LL at permanent
command).
Q_CTRL setpoint maximum limit. 100% == 1p.u. overexcited. -100% == 1p.u. underexcited.
Q_CTRL setpoint minimum limit. 100% == 1p.u. overexcited. -100% == 1p.u. underexcited.
Q_CTRL setpoint preset value. Preset value which becomes active if TRIG_PRST_Q (6804) is TRUE. Set it between
HL and LL_REF_Q_CTRL.

3BHS102402 E88

Rev. G

SC
ENUM

HL
1

LL
0

DEF.
0

U
-

CLASS
CM, IMP, SIP

SP
57

0.1

1000

600

CM, HID, SIP

57

0.01
0.01
0.01

10000
10000
10000

-10000
-10000
-10000

10000
-10000
0

% CM, HID, SIP


% CM, HID, SIP
% CM, HID, SIP

57
57
57

Parameter and Signal List Version 41.222_2


2.17

AVR CTRL

INDEX
1901

HL REF AVR

INDICATION

1902

LL REF AVR

1903

PRESET1 REF AVR

1904

PRESET2 REF AVR

1905

RAMP TIME1 REF A

1906

RAMP_TIME2 REF A

1907

TC FOLLOW UP AVR

1908

TC IMPOSED CTRL A

1909

Q DROOP/COMPENS

34

Group 19
FUNCTION
AVR (AUTO) setpoint max. limit.
NOTE: The following signals: Q, P_DROOP/COMPENS (1909, 10), ADD_IN_REF1_A (6908),
ADD_INPUT_AVR (7002) influence the operation range of the AVR too.
E.g. Q_DROOP (1909) = -5% reduces the max. setpoint by 5% at 100% reactive load generation.
Consider the settings of the V/Hz limiter in group 21 too.
Dont set this parameter below LL_REF_AVR (1902).
AVR (AUTO) setpoint min. limit.
NOTE: The following signals: Q, P_DROOP/COMPENS (1909, 10), ADD_IN_REF1_A (6908),
ADD_INPUT_AVR (7002) influence the operation range of the AVR too.
E.g. Q_COMPENSATION (1909) = +5% increases the min. setpoint by 5% at 100% reactive load generation.
Dont set this parameter above HL_REF_AVR (1901).
AVR setpoint PRESET1 value.
1st preset value which becomes active if SEL_PRESET2_AVR (6906) is FALSE and TRIG_PRST_AVR (6907) is
TRUE. Set it between HL and LL_REF_AVR.
DEFAULT: This value will dynamically be set by ON_PRESET_CMD (10304) at start excitation and if machine goes
OFF_LINE.
AVR setpoint PRESET2 value.
2nd preset value which becomes active if SEL_PRESET2_AVR (6906) and TRIG_PRST_AVR (6907) is TRUE. Set it
between HL and LL_REF_AVR.
DEFAULT: not used (12501).
AVR setpoint ramp time 1, valid for remote RAISE, LOWER commands (traveling time between HL and LL at
permanent COMMAND). Becomes active if SEL_RAMPTIME2_A is FALSE = DEFAULT.
AVR setpoint ramp time 2, valid for remote RAISE, LOWER commands (traveling time between HL and LL at
permanent COMMAND). Becomes active if SEL_RAMPTIME2_A is TRUE. DEFAULT: not used (12501).
Time constant of the auto follower. Because of superimposed action to the AVR setpoint, the TC should be at least 10
times bigger than selected TA (1920...1922) during MANUAL operation.
Time constant of the imposed follower. Because of superimposed action to the AVR setpoint, the TC should be 50..100
times bigger than selected TA (1920...1922) during imposed ctrl operation.
NOTE: The reason for the big TC is because the reactive power change rate resulting from an AVR setpoint change
depends on the resulting Q-droop of the system by:
delta Q = delta REF_AVR / Q_DROOP
e.g. 40% delta Q = 2% delta REF_AVR / 5% Q_DROOP.
Determines characteristic U_MACH_RELATIVE = f (Q_MACH_RELATIVE):
DROOP = negative values (-3..-8%) are required for parallel operation with rigid grid or to get reactive load sharing with
other machines which are connected to the same bus bar without unit transformers.
COMPENSATION = positive values to compensate a part of the unit transformers reactance to get the same resulting
droop of -3..-8% instead of transformer reactance. DEFAULT: -5% DROOP.

3BHS102402 E88

Rev. G

SC
0.01

HL
15000

LL
0

DEF.
11000

U
CLASS
% CM, HID, AVR

SP
43

0.01

15000

9000

% CM, HID, AVR

43

0.01

15000

10000

% CM, HID, AVR

43

0.01

15000

10000

% CM, HID, AVR

43

0.1

6000

10

600

CM, HID, AVR

43

0.1

6000

10

600

CM, HID, AVR

43

0.1

10000

10

100

AVR, TUN

43

0.1

10000

10

1000

SIP, TUN

43

0.01

2000

200
0

-500

% CM, IMP, AVR,


TUN

44

Parameter and Signal List Version 41.222_2

INDEX
1910

INDICATION
P
DROOP/COMPENS

1911

REF V/Hz LIM AVR

35

FUNCTION
Determines characteristic U_MACH_RELATIVE = f (P_MACH_RELATIVE):
Normally used to compensate (positive values) for line droop, or to get overexcited with increasing active power after
synchronization, e.g. P.F. = 0.8. DEFAULT: not used (12501).
V/Hz gradient in % voltage / 100% speed (frequency):
DEFAULT = 115% V/Hz means that the AVR setpoint drops with a gradient of 1.15 p.u. voltage/speed from the point
REF_UMAX_fNOM_AVR (1912)
NOTE: The V/Hz characteristic is effective also at nominal frequency (point REF_UMAX_fNOM_AVR (1912)) an up to
the point where it hits the frequency independent limit REF_UMAX_AVR (1913). The cut off frequency in % at
nominal voltage is therefore given by:
f[%] = 100% - [(100% / REF_V/Hz_LIM_AVR) * (REF_UMAX_fNOM_AVR-100%)].
With DEFAULT settings: 100%-[(100/115)*(115-100)] = 86.96% fn or 43.47 Hz if fn = 50 Hz.
And at zero voltage is:
f0[%] = 100% - [(100% / REF_V/Hz_LIM_AVR) * (REF_UMAX_fNOM_AVR )].
With DEFAULT settings 100%-[(100/115)*115] = 0%.
Ref. to SW description for more details.
V/Hz limit in % voltage at 100% frequency = fn. This means that V/Hz characteristic crosses always this point with the
gradient set at REF_V/Hz_LIM_AVR (1911). Cut off frequency see REF_V/Hz_LIM_AVR (1911).

SC
0.01

HL
2000

0.01

20000

0.01

20000

Absolute voltage limit in % independent of overspeed. DEFAULT = 115%.

0.01

20000

0.1
0.1

1912

REF UMAX fNOM


AVR

1913

REF UMAX AVR

1914
1915

DELAY V/Hz LIM A Independent ON delay of the V/Hz limiter. DEFAULT: not used (12501).
SOFTSTART RAMP SOFTSTART ramp time for 100% voltage.
NOTE: The actual voltage is taken over as start point of the integrator at field flashing OFF instant. Therefore the
effective ramp time from this point to 100% is given by:
t = SOFTSTART_RAMP * [(100% - Uflash off[%])/100]
Represents the external part of the loop gain caused by the converter itself:
CEILING FACTOR
A
Converter gain = non load ceiling exc. voltage divided by required no load exc. voltage (air gap value).
If data not known set CEILING FACTOR A as follows:
[UT2n * 1.35] / [(no load exc. voltage) * 0.88]
3 phase supply type C1...C4:
[UT2n * 0.9] / [(no load exc. voltage) * 0.88]
Single phase supply type C1:
[UC+/-] / [(no load exc. voltage) * 0.88]
Chopper version type C5:
UT2n
nominal excitation transformer secondary voltage
UC+/intermediate circuit voltage at no load excitation
0.88
estimated saturation factor
AVR overall DC loop gain. This setting includes CEILING_FACTOR_A (1916). Internal DC gain
DC GAIN AVR
OUT_PID_AVR / IN_AVR_ERR = DC_GAIN_AVR * 100 / CEILING_FACTOR_A.
For setting consult commissioning instructions.
AVR overall Proportional loop gain. This setting includes CEILING_FACTOR_A (1916). Internal P gain
P GAIN AVR
OUT_PID_AVR / IN_AVR_ERR = P_GAIN_AVR * 100 / CEILING_FACTOR_A
For setting consult commissioning instructions.
AVR overall High Frequency loop gain. This setting includes CEILING_FACTOR_A (1916). Internal HF gain
HF GAIN AVR
OUT_PID_AVR / IN_AVR_ERR = HF_GAIN_AVR * 100 / CEILING_FACTOR_A
For setting consult commissioning instructions.

1916

1917

1918

1919

3BHS102402 E88

Rev. G

LL
200
0
0

DEF.
0

U
CLASS
% CM, HID, AVR

SP
44

11500

% CM, HID, AVR

44

100
00

11500

% CM, HID, AVR

44

11500

% CM, HID, AVR

44

600
600

100
00
0
10

0
50

s
s

CM, HID, AVR


CM, HID, AVR

44
44

2000

100

500

% CM, IMP, AVR

42

1000

10

500

p.
u.

AVR, TUN

42

300

50

p.
u.

IMP, AVR, TUN

42

1000

250

p.
u.

AVR, TUN

42

Parameter and Signal List Version 41.222_2

36

INDEX
1920

INDICATION
TA1

FUNCTION
AVR integration time constant 1. Active with normal AVR operation.
For setting consult commissioning instructions.

SC
0.01

HL
1000

LL
1

DEF.
100

U
s

CLASS
IMP, AVR, TUN

INDEX
1921

INDICATION
TA2

SC
0.01

HL
1000

LL
1

DEF.
10

U
s

CLASS
AVR, TUN

1922

TA3

0.01

1000

100

AVR, TUN

1923

TB1

2000

100

m IMP, AVR, TUN


s

1924

TB2

2000

m AVR, TUN
s

1925

TB3

FUNCTION
AVR integration time constant 2. DEFAULT: active if IE_LIMITER or IEMIN_LIMITER is active.
For setting consult commissioning instructions.
AVR integration time constant 3. DEFAULT: active if Q(P)_LIMITER or I_LIMITER is active.
For setting consult commissioning instructions.
AVR differentiation time constant 1. Active with normal AVR operation.
NOTE: settings below 25 ms switch off the differentiation effect.
For setting consult commissioning instructions.
AVR differentiation time constant 2. DEFAULT: active if IE_LIMITER or IEMIN_LIMITER is active.
NOTE: settings below 25 ms switch off the differentiation effect.
For setting consult commissioning instructions.
AVR differentiation time constant 3. DEFAULT: active if Q(P)_LIMITER or I_LIMITER is active.
NOTE: settings below 25 ms switch off the differentiation effect.
For setting consult commissioning instructions.

2000

100

m AVR, TUN
s

SC
-

HL
1

LL
0

DEF.
0

U
-

CLASS
CM, HID, AVR

SP
41

CM, HID, AVR

122

500

50

2.18
INDEX
2001

AVR IN, PSS


INDICATION
SEL LIM
PRIORITY

2002

SEL PSS MODE

2003

PSS KS1

2004
2005
2006

PSS KS2
PSS KS3
PSS T1

SP
42

SP

Group 20

FUNCTION
Selection of dominating limiter group: The group without priority can not respond as long as the group with priority is active.
0==OEL group (IELIM, IOEL, USER_OEL).
1==UEL group (Q(P)_LIM, IUE, IEMINLIM).
Enables PSS control:
0==OFF
PSS inactive (DEFAULT)
1==ON
PSS active
2==ON (external P) PSS active, power signal input connected to AI1.
NOTE: PSS function is available only with hardware option UNS 0869 installed (sub module to the signal
processing device UNS 1860b)!
For PSS mode ==2, an external power transducer must be connected to the analog input AI1 on the UNS
0863 and signal 10115 must be connected to IN_P_PSS (7012). In addition, the low pass filter in the
frequency measuring is disabled.
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.

0.1
0.01

Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.

0.01

Rev. G

122

TUN

Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.

3BHS102402 E88

p.u. CM, HID, AVR,

500

20

p.u. CM, HID, AVR,

122

TUN

0.01

500
250

1
1

100
20

p.u. CM, HID, AVR,

122

TUN
CM, HID, AVR,
TUN

122

Parameter and Signal List Version 41.222_2


INDEX
2007

INDICATION
PSS T2

2008

PSS T3

2009

PSS T4

2010

PSS T7

2011

PSS T8

2012

PSS T9

2013

PSS TW1

2014

PSS TW2

2015

PSS TW3

2016

PSS TW4

2017

PSS N

2018

PSS M

2019

PSS VST LIM

2020

P MACH MIN

2021

PSS T10

2022

PSS T11

2023
to
2027

37

FUNCTION
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: If both T8 and T9 are set to 0 the output of the ramp-tracking filter is equal to the input (no filtering).
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: If both T8 and T9 are set to 0 the output of the ramp-tracking filter is equal to the input (no filtering).
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: With the time constant set to 0 the output of the ramp-tracking filter is equal to the input (no filtering).
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: With the time constant set to 0 the output of the ramp-tracking filter is equal to the input (no filtering).
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: With the time constant set to 0 the output of the ramp-tracking filter is equal to the input (no filtering).
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: With the time constant set to 0 the output of the ramp-tracking filter is equal to the input (no filtering).
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: For N = 0 the output of the ramp-tracking filter is permanently forced to 0.
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
Limitation of the PSS influence.
NOTE: If MODE 1 is selected, the DEFAULT value can normally be used to achieve acceptable under- or over voltage if
PSS remains at one of its limits (20% means +/- 20% of nominal machine voltage).
Below this level PSS is automatically blocked.
NOTE: If PSS is required for a reactive power compensatory machine, this parameter should probably be reduced to zero.
In this case PSS has to be blocked via BLK_PSS (7014)) if OFF-LINE.
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: If parameter is set to zero 3rd LEAD LAG is skipped (as for PSS2A).
Parameter of Power System Stabilizer according to IEEE Std 421.5 Type PSS2B. Setting according PSS calculation study by
ABB or Utility.
NOTE: If parameter is set to zero 3rd LEAD LAG is skipped (as for PSS2A).
Not available with this SW release

3BHS102402 E88

Rev. G

SC
0.01

HL
250

LL
1

DEF.
4

U
s

CLASS
CM, HID, AVR,
TUN
CM, HID, AVR,
TUN
CM, HID, AVR,
TUN
CM, HID, AVR,
TUN
CM, HID, AVR,
TUN

SP
122

0.01

250

36

0.01

250

12

0.01

3000

0.2

200

0.01

250

0.01

250

10

CM, HID, AVR,


TUN

122

0.1

300

20

CM, HID, AVR,


TUN

122

0.1

300

20

CM, HID, AVR,


TUN

122

0.1

300

20

CM, HID, AVR,


TUN

122

0.1

300

CM, HID, AVR,


TUN

122

122

122

0.01

2000

1000

% CM, HID, AVR

122

0.01

5000

500

% CM, HID, AVR

122

0.01

250

CM, HID, AVR,


TUN

122

0.01

250

CM, HID, AVR,


TUN

122

122
122
122
122

122

Parameter and Signal List Version 41.222_2


2.19

38

MANUAL CTRL Group 21

INDEX
2101

INDICATION
TC IMPOSED CTRL M

2102

TC FOLLOW UP MAN

2103

RAMP TIME1 REF M

2104

RAMP TIME2 REF M

2105

LL REF MANUAL

2106
2107

HL REF MANUAL
PRESET1 REF MAN

2108

PRESET2 REF MAN

2109

REF0 IE(P) LIM

2110

REF25 IE(P) LIM

2111

REF50 IE(P) LIM

2112

REF75 IE(P) LIM

2113

REF100 IE(P) LIM

2114
2115

TA MANUAL
P GAIN MANUAL

FUNCTION
Time constant of the imposed controller. DEFAULT: V/Hz manual restrict. Because of superimposed action to the
MANUAL_CTRL setpoint, the TC should be at least 10 times bigger than TA_MANUAL (2114).
Time constant of the auto follower. Because of superimposed action to the MAN setpoint, the TC should be at least 10
times bigger than TA_MANUAL (2114).
MANUAL_CTRL setpoint ramp time 1, valid for remote RAISE, LOWER commands (traveling time between HL and LL
at permanent COMMAND). Becomes active if SEL_RAMPTIME2_M is FALSE = DEFAULT.
MANUAL_CTRL setpoint ramp time 2, valid for remote RAISE, LOWER commands (traveling time between HL and LL
at permanent COMMAND). Becomes active if SEL_RAMPTIME2_M is TRUE. DEFAULT: not used (12501).
MANUAL_CTRL setpoint min. limit. DEFAULT: 0 to have the full operating range at line or separate (TEST) supply, i.e.
for SHUNT supply application. The starting ref. at SHUNT supply is given by PRESET1_REF_MAN (2107).
MANUAL_CTRL setpoint max. limit. DEFAULT: 110% of nominal excitation current I_EXC_NOMINAL (502)
MANUAL_CTRL setpoint PRESET1 value.
1st preset value which becomes active if SEL_PRESET2_MAN (7106) is FALSE and TRIG_PRST_MAN (7107) is
TRUE. Normally set to 90...100% no load excitation current, to get approx. nominal voltage if starting or going OFF_LINE
at MANUAL_CTRL. DEFAULT: This value will dynamically be set at start excitation and if machine goes off line by
ON_PRESET_CMD (10304).
MANUAL_CTRL setpoint preset 2 value.
2nd preset value which becomes active if SEL_PRESET2_MAN (7106) is TRUE and TRIG_PRST_MAN (7107) is
TRUE. Normally set to 0 excitation current, for starting manually from zero at Test supply.
UE manual restrict characteristic I_EXC_RELATIVE=f(P) at P=0%. Set the characteristic if ON_LINE at
MANUAL_CTRL and zero active power by increasing the parameter value to the max. permitted reactive power value.
Leave the value at zero if manual restrict is not required.
UE manual restrict characteristic I_EXC_RELATIVE=f(P) at P=25%. Set the characteristic if ON_LINE at
MANUAL_CTRL and 25% active power by increasing the parameter value to the max. permitted reactive power value.
Leave the value at zero if manual restrict is not required.
UE manual restrict characteristic I_EXC_RELATIVE=f(P) at P=50%. Set the characteristic if ON_LINE at
MANUAL_CTRL and 50% active power by increasing the parameter value to the max. permitted reactive power value.
Leave the value at zero if manual restrict is not required.
UE manual restrict characteristic I_EXC_RELATIVE=f(P) at P=75%. Set the characteristic if ON_LINE at
MANUAL_CTRL and 75% active power by increasing the parameter value to the max. permitted reactive power value.
Leave the value at zero if manual restrict is not required.
UE manual restrict characteristic I_EXC_RELATIVE=f(P) at P=100%. This setting must normally be extrapolated from
previous settings because of the turbine power limits. Set the parameter value to the max. permitted reactive power value.
Leave the value at zero if manual restrict is not required.
Integration time constant of manual PI controller. For setting consult commissioning instructions.
Proportional gain of manual PI controller (external part of the loop gain caused by the converter is not considered). For
setting consult commissioning instructions.

3BHS102402 E88

Rev. G

SC
0.1

HL
10000

LL
0

DEF.
100

U
s

CLASS
AVR, TUN

SP
45

0.1

10000

100

AVR, TUN

45

0.1

10000

600

CM, HID

45

0.1

10000

600

AVR, CM, HID

45

0.01

15000

% AVR, CM, HID

45

0.01
0.01

15000
15000

0
0

11000
2500

% AVR, CM, HID


% AVR, CM, HID

45
45

0.01

15000

% AVR, CM, HID

45

0.01

10000

% AVR, HID, TUN

45

0.01

10000

% AVR, HID, TUN

45

0.01

10000

% AVR, HID, TUN

45

0.01

10000

% AVR, HID, TUN

45

0.01

10000

% AVR, HID, TUN

45

0.01
0.1

500
200

1
1

10
10

s
-

59
59

AVR, IMP, TUN


AVR, IMP, TUN

Parameter and Signal List Version 41.222_2

INDEX
2116

INDICATION
DC GAIN MANUAL

2117

FB GAIN

2118

REL LEVEL

2119

BLK TIME

2120

NOT OK LEVEL

2.20
INDEX
-

2.21

39

FUNCTION
DC gain of manual PI controller (external part of the loop gain caused by the converter is not considered). For setting consult
commissioning instructions.
Feedback rate of the inactive controller AVR (AUTO) or MAN. E.g. 10% means that only 10% of the A_M_DFF (12118) or
CH_STB_DIFF (12119) difference is fed back to the inactive controller input.
NOTE: If value is too big then accuracy of auto follower is restricted and the A_M_DIFF or CH_STB_DIFF signal
becomes smaller for the same error. On the other hand if value is too small, auto follower tends for hunting and
then the A_M_DIFF or CH_STB_DIFF indication could be too big for the same error.
Above this level the auto follower becomes active. With increasing A_M_DIFF or CH_STB_DIFF there is an ON delay set by
BLK_TIME (2119) to avoid follower action during short time transients.
NOTE: This setting determines auto follower accuracy.
ON delay of follower action after error signal A_M_DIFF or CH_STB_DIFF have exceeded REL_LEVEL (2118). This delay
blocks follower action during short time transients.
If error signal A_M_DIFF is below this level, RDY_XFER_A_M (12117) signal becomes TRUE for back indication ready for
transfer to control room. If FALSE, transfer is not possible by local control panel.
NOTE: This setting is used only for indication and has no influence for follower accuracy.

SC
1

HL
300

LL
0

DEF.
100

U
-

CLASS
AVR, TUN

SP
59

50

10

AVR, HID

46

0.01

20000

20

AVR, HID

46

0.1

200

100

AVR, HID

46

0.01

20000

500

AVR, TUN

46

SC

HL

LL

DEF.

CLASS

SP

SC

HL
10000

LL
0

DEF.
0

U
-

CLASS
AFB

SP

ARRAY

ARRAY

10000

AFB

ARRAY

10000

AFB

ENUM

AFB

ENUM

AFB

CH COMMUNICATION Group 24
INDICATION

FUNCTION
-

FB EXECUTION Group 25

INDEX
2501

INDICATION
TASK 1 EXEC ORDER

2502

TASK 2 EXEC ORDER

2503

TASK 3 EXEC ORDER

2504

FB APPL ENABLE

2505

FB TASK LOCK

FUNCTION
Execution order of function blocks of task 1, which is executed at 5 ms interval.
Ref. to FB programming instructions.
Execution order of function blocks of task 2, which is executed at 20 ms interval.
Ref. to FB programming instructions.
Execution order of function blocks of task 3, which is executed at 200 ms interval.
Ref. to FB programming instructions.
Selection parameter for execution of function block application:
0 == DISABLED (FBs are not executed), 1 == ENABLED (FBs are executed).
NOTE: It should be carefully considered, what stopping of the application means for the hole application.
Save this parameter always by BACKUPSTOREMODE (by Panel or by CMT on line communication). The
download program sets this parameter automatically to 0.
Interlocking flag of the function blocks application:
0 == DISABLED (locking flag is not set), 1 == ENABLED (locking flag is set).

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


2.22
INDEX
26012699

2.23
INDEX
27012799

2.24
INDEX
28012899

2.25
INDEX
29012999

2.26
INDEX
30013099

Function Blocks 1
INDICATION

40

Group 26

FUNCTION
Parameters for application function blocks
See application function block data sheets.

Function Blocks 2
INDICATION

INDICATION

FUNCTION

INDICATION

FUNCTION

INDICATION

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

Group 29

FUNCTION
Parameters for application function blocks
See application function block data sheets.

Function Blocks 5

LL
-

Group 28

Parameters for application function blocks


See application function block data sheets.

Function Blocks 4

HL
-

Group 27

Parameters for application function blocks


See application function block data sheets.

Function Blocks 3

SC
-

Group 30

FUNCTION

SC
-

Parameters for application function blocks


See application function block data sheets.

3BHS102402 E88

Rev. G

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

Parameter and Signal List Version 41.222_2


2.27
INDEX
31013199

2.28
INDEX
32013299

2.29
INDEX
33013399

2.30
INDEX
34013499

Function Blocks 6
INDICATION

41

Group 31

FUNCTION

SC
-

Parameters for application function blocks


See application function block data sheets.

Function Blocks 7
INDICATION

FUNCTION

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP
442,445

FUNCTION

SC

HL

LL

DEF.

CLASS

SP

Parameters for application function blocks


See application function block data sheets.

AFB

Function Blocks 8

Group 33

FUNCTION
Parameters for application function blocks
See application function block data sheets.

Function Blocks 9
INDICATION

LL
-

Group 32

Parameters for application function blocks


See application function block data sheets.

INDICATION

HL
-

Group 34

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


2.31

Fieldbus

INDEX
4001

INDICATION
Fieldbus Par. 1

4002

Fieldbus Par. 2

42

Group 40
FUNCTION
Selects the fieldbus adapter type:
0==DISABLED
1==PROFIBUS
2==CS31
3==MODBUS
4==DEVICENET
5==ADVANT / DDCS
6==NOT USED
7==MODBUS PLUS
8==NOT ACTIVATED
NOTE: The required fieldbus adapter HW must be installed and connected to DDCS link. The changes of parameter do
not take effect immediately. To change the module settings, the power must be disconnected from fieldbus
adapter module. Refer also to fieldbus type specific Installation and Start-up Instructions
MODBUS MODE: Shows the logical protocol on the HW communication option module. Specifies the binary, or Remote
Terminal Unit (RTU) mode:
0==RTU wdg:flt
On a watch dog error, the module will indicate a watch-dog error.
1==RTU wdg:rst On a watch-dog error, the module will reset itself.

SC
ENUM

HL
8

LL
0

DEF.
0

U
-

CLASS
AFB

SP
129

255

AFBN

129

255

AFBN

129

PROFIBUS MODE:
0==FMS
FMS protocol is used
1==DP-PPO1
DP protocol used with PPO1 message type 1
2==DP-PPO2
DP protocol used with PPO1 message type 2
3==DP-PPO3
DP protocol used with PPO1 message type 3
4==DP-PPO4
DP protocol used with PPO1 message type 4
5==DP-PPO5
DP protocol used with PPO1 message type 5

4003

Fieldbus Par. 3

NOTE: The changes of parameter do not take effect immediately. To change the module settings, the power must be
disconnected from fieldbus adapter module. Refer also to fieldbus type specific Installation and Start-up
Instructions
STATION NUMBER:
Sets the node number for the module on the network.
Modbus:
1 ... 247
Profibus:
3 ... 126
NOTE: Use different node numbers for each channel in a 2-channel system. The changes of parameter do not take
effect immediately. To change the module settings, the power must be disconnected from fieldbus adapter
module. Refer also to fieldbus type specific Installation and Start-up Instructions

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


INDEX
4004

INDICATION
Fieldbus Par. 4

4005

Fieldbus Par. 5

43

FUNCTION
Defines the communication speed BAUD RATE:
Modbus
Profibus
[kbit/s]
[kbit/s]
0== 1.200
9.6
1== 2.4
19.2
2== 4.8
93.75
3== 9.6
187.5
4== 19.2
500
5==
1500
6==
AUTO
NOTE:
The changes of parameter do not take effect immediately. To change the module settings, the power must be
disconnected from fieldbus adapter module. Refer also to fieldbus type specific Installation and Start-up
Instructions
Modbus:
PARITY: Defines the parity to be used with the Modbus communication. This parameter also defines the number of stop
bits in use. With Modbus communication the number of stop bits must be 2 with NONE parity bit, and 1 with
EVEN or ODD parity
0==EVEN
1==ODD
2==NONE

SC
1

HL
255

LL
0

DEF.
0

U
-

CLASS
AFBN

SP
129

255

AFBN

129

255

AFBN

129

Profibus:
3==WRITE PPO DATA SET SEL (fixed)
NOTE:

4006

Fieldbus Par. 6

The changes of parameter do not take effect immediately. To change the module settings, the power must be
disconnected from fieldbus adapter module. Refer also to fieldbus type specific Installation and Start-up
Instructions

Modbus:
GOOD MESSAGES: This diagnostic counter increases by one every time a valid Modbus message has been received by
the adapter module. This counter roll over from 32767 to 0. During normal operation, this counter is increasing
constantly.
Profibus:
4==READ PPO DATA SET SEL (fixed)
NOTE:

The changes of parameter do not take effect immediately. To change the module settings, the power must be
disconnected from fieldbus adapter module. Refer also to fieldbus type specific Installation and Start-up
Instructions

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


INDEX
4007

INDICATION
Fieldbus Par. 7

FUNCTION
Modbus:
BAD MESSAGES: This diagnostic counter increases by one every time the Modbus adapter module finds any kind of
communication error. This counter roll over from 32767 back to 0. During normal operation, this counter hardly
ever increases.
Profibus: not used
NOTE:

4008
4009
4010
4011
4012
4013
4014
4015

Fieldbus Par. 8
Fieldbus Par. 9
Fieldbus Par. 10
Fieldbus Par. 11
Fieldbus Par. 12
Fieldbus Par. 13
Fieldbus Par. 14
Fieldbus Par. 15

44
SC
1

HL
255

LL
0

DEF.
0

U
-

CLASS
AFBN

SP
129

1
1
1
1
1
1
1
1

255
255
255
255
255
255
255
255

0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0

AFBN
AFBN
AFBN
AFBN
AFBN
AFBN
AFBN
AFBN

129
129
129
129
129
129
129
129

The changes of parameter do not take effect immediately. To change the module settings, the power must be
disconnected from fieldbus adapter module. Refer also to fieldbus type specific Installation and Start-up
Instructions

Not used.
Not used.
Not used.
Not used.
Not used.
Not used.
Not used.
Not used.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2

Programming

3.1

ANALOG INPUTS

45

Group 51

INDEX

INDICATION

FUNCTION

SC

HL

LL

DEF.

CLASS

SP

5101

[POLARITY]

Input which inverts all outputs 10105 .... 10112. Used if the phase sequence of the p.t. is changed e.g. using syn.
machine for 2 operation modes, either as generator or as motor.
DEFAULT: not used (12501)

BI

19999

12501

AFB, HID

3.2

ANALOG OUTPUTS

Group 52

INDEX

INDICATION

FUNCTION

SC

HL

LL

DEF.

5201
5202
5203

AO1.[IN]
AO2.[IN]
AO1E.[IN]

AI
AI
AI

19999
19999
19999

0
0
0

12501
12501
12501

AFB, IO
AFB, IO
AFB, IO

1
85
2

5204

AO2E.[IN]

Input IN of AO1 SP. DEFAULT: spare == 0 (12501). Connect to signal needed in AO1.
Input IN of AO2 SP. DEFAULT: spare == 0 (12501). Connect to signal needed in AO2.
Input IN of AO1E SP. DEFAULT: spare == 0 (12501). Connect to signal needed in AO1E.
NOTE: Only available if optional hardware UNS 0867 on CON-2 and second UNS 0863 are installed.
Input IN of AO2E SP. DEFAULT: spare == 0 (12501). Connect to signal needed in AO2E.
NOTE: Only available if optional hardware UNS 0867 on CON-2 and second UNS 0863 are installed.

AI

19999

12501

AFB, IO

86

3.3

CONTROL LOGIC

CLASS

SP

Group 53

INDEX

INDICATION

FUNCTION

SC

HL

LL

DEF.

CLASS

5301

[BLOCK START UP]

BI

19999

10351

AFB, IMP

74

5302

[START EXCITATION]

Input for blocking of excitation startup. DEFAULT: INH_OF_START (10351).


NOTE: With DEFAULT connection, start up is blocked by all ALARMS are except, following:
- ALARM 111 Common STBY fault
- ALARM 113 2 channel comerror
- ALARM 122 fieldbus timeout
- ALARM 137 Standby trip
- ALARM 145 Test supply
If input not connected, then start up is independent from any alarm.
Excitation start command: closes FCB if not yet closed and releases thyristor firing, field flashing with shunt
excitation and then the SOFTSTART_RAMP (1915). DEFAULT: DIX01 (10701).
NOTE: Start up is completed only by the active channel of a 2 channel configuration (AFT).

BI

19999

10701

AFB, IMP

74

3BHS102402 E88

Rev. G

SP

Parameter and Signal List Version 41.222_2


INDEX
5303

[EXC OFF CMD]

INDICATION

5304

[RAISE CMD]

5305

[LOWER CMD]

5306

[ON AUTO CMD]

5307

[ON MAN CMD]

5308

[ON CH1 CMD]

5309

[ON CH2 CMD]

5310

[ON IMP CMD]

5311

[OFF IMP CMD]

5312

[SEL Q CTRL]

5313

[SEL COSPHI CTRL]

46

FUNCTION
SC
Input for Excitation OFF (STOP) command. Stops excitation by inverter mode and opens the field breaker as well, if
RELEASE_FCB_OFF (301) is set to YES. After 60 s inverter mode, the firing pules are blocked too. Instead of
inverter mode, the pulses are blocked immediately, if the converter input side (field) C.B. opens (parameters
RELEASE_FCB_OFF (301) = YES and CB_CONFIG (309) = AC SIDE).
DEFAULT: Connected to DIX02 (10702).
NOTE:
At the configuration with field C.B. on converter input (parameter CB_CONFIG (309) = 0==AC SIDE)
and parameter RELEASE_FCB_OFF (301) set to 0==NO, this input must only be used for remote OFF
cmd. In that case, the external F.C.B. TRIP command must be connected to input OFF_BLK_CMD
(5335).
RAISE command to active controller AUTO (AVR), MANUAL CTRL, COSPHI (P.F.) or Q (VAR)
DEFAULT: connected to DIX03 (10703)
LOWER command to active controller AUTO (AVR), MANUAL CTRL, COSPHI (P.F.) or Q (VAR).
DEFAULT: connected to D1X04 (10704)
BI
Input which transfers to AUTO (AVR) operation mode.
NOTE: To be used only for interlocking between DIX05 and this input.
DEFAULT: connected to DIX05 (10705).
BI
Input which transfers to MANUAL operation mode.
NOTE: To be used only for interlocking between DIX06 and this input.
DEFAULT: connected to DIX06 (10706).
Input for external channel 1 ON command e.g. for remote ctrl. Connect to corresponding digital input, if remote ctrl is BI
required.
NOTE: Remote channel transfer is normally not useful, because with an AFT system both channels are identically
and from MTBF figures, the 2nd channel converter should always serve as cold standby.
Use the same digital input for both channels (same parameter set).
Input for external channel 2 ON command e.g. for remote ctrl. Connect to corresponding digital input, if remote ctrl is BI
required.
NOTE: Remote channel transfer is normally not useful, because with an AFT system both channels are identically
and from MTBF figures, the 2nd channel converter should always serve as cold standby.
Use the same digital input for both channels (same parameter set).
B1
Input which activates preselected IMPOSED CTRL mode, if in AUTO mode and ON_LINE.
NOTE: To be used only for interlocking between DIX07 and this input.
DEFAULT: connected to DIX07 (10707).
B1
Input which deactivates preselected IMPOSED CTRL mode, if in AUTO mode and ON_LINE.
NOTE: To be used only for interlocking between DIX08 and this input.
DEFAULT: connected to DIX08 (10708).
Input which preselects Q CTRL function if at remote ctrl and the parameter IMPOSED_CTRL_MODE (302) is set to BI
EXTERNAL SEL (value = 3). DEFAULT: not used == 0 (12501).
Input which preselects COS PHI CTRL function if at remote ctrl and the parameter IMPOSED_CTRL_MODE (302) BI
is set to EXTERNAL SEL (value = 3). DEFAULT: not used == 0 (12501).

3BHS102402 E88

Rev. G

HL
19999

LL
0

DEF.
10702

U
-

CLASS
AFB, IMP

SP
74

19999

10703

AFB, IMP

77

19999

10704

AFB, IMP

77

19999

10705

AFB, HID

76

19999

10706

AFB, HID

76

19999

12501

AFB, HID

76

19999

12501

AFB, HID

76

19999

10707

AFB, HID

79

19999

10708

AFB, HID

79

19999

12501

AFB, SIP

79

19999

12501

AFB, SIP

79

Parameter and Signal List Version 41.222_2


INDEX
5314

[ON LINE]

5315

[RDY XFER A M]

5316

INDICATION

[READY XFER TWIN]

5317

[AUTO FAIL]

5318
5319

[MAN FAIL]
[IN CH FAULT]

5320

[IN CH1 FAULT]

5321

[IN CH2 FAULT]

5322
5323
5324

[TRIP CMD]
[PULSE BLK]
[RESET]

5325
5326

[DISABLE LOCAL]
[PARAMETER SET2]

47

FUNCTION
Input which indicates that machine is connected to grid (normally machine main breaker closed). Internally used for
different processes.
NOTE: as long as this input is FALSE, following signals are forced to zero:
I_MACH_A (10104), P_MACH_KW (10107), P_MACH_MW (10108), Q_MACH_KVAR (10111),
Q_MACH_MVAR (10112), S_MACH_KVA (10113), S_MACH_MVA (10114), COSPHI_AO (10126).
COSPHI (10124) is forced to 1.
At motor application (motor breaker is closed before excitation start), this input must not be TRUE until
excitation is started. Put an AND gate to release this input only if EXC_ON (10307) is TRUE.
DEFAULT: connected to DIX15 (10715).
Input which enables LOCAL A-M transfer commands from Panel or CMT.
DEFAULT: connected to RDY_XFER_A_M (12117).
Input which enables LOCAL channel transfer commands from Panel or CMT.
DEFAULT: connected to RDY_XFER_TWIN (12120).
Input which transfers from AUTO (AVR) to MANUAL control.
NOTE: If CH_CONFIG (308) = 1 (AFT CH1) or 2 (AFT CH2), this input causes channel transfer prior to A-M
transfer.
For combination of faults ref. to SW diagram and description.
DEFAULT: connected to AVR_FAULT (10910).
Not applicable for this SW release 41.220
Input which unconditionally forces output CH_FAIL (10342). With a 2 channel system (CH_CONFIG >0) it forces
channel transfer via serial link and via hard wire connection (DOX01 relay drops).
DEFAULT: connected to fault logger output CH_FAIL_LOGGED (10349).
Input for external channel 1 failure signal, e.g. converter C.B. open or converter fuses blown. To use identical
parameter sets in both channels (except CH_CONFIG (308)), this signal is evaluated for CH_FAULT 47 Ext. CH
fault in the physical channel 1 of an AFT system or in a single channel system (CH_CONFIG (308) = 1 (AFT
CH1)or 0 (SFE).
DEFAULT: DIX09 (10709)
Connect to corresponding spare digital input if separate converter C.B. or converter fuses with indicators are
provided.
Input for external channel 2 failure signal, e.g. converter C.B. open or converter fuses blown. To use identical
parameter sets in both channels (except CH_CONFIG (308)), this signal is evaluated for CH_FAULT 47 Ext. CH
fault in the physical channel 2 of an AFT system (CH_CONFIG (308) = 2 (AFT CH2).
DEFAULT: DIX10 (10710)
Connect to corresponding spare digital input if separate converter C.B. or converter fuses with indicators are
provided.
Input which immediately and unconditionally shuts down excitation. DEFAULT: EXC_TRIP (10350).
Input which blocks firing pulses by application program. DEFAULT: not used (12501).
Reset command. This command will reset those fault memories which corresponding fault is not active any more.
NOTE: This input RESET the fault logger of both channels.
DEFAULT: not used, because all faults (and some alarms) can be reset via panel or CMT.
This command will disable local control of the excitation system, both from panel and CMT.
The unit has 2 parameter sets. This input activates the second parameter set:
0 = Parameter set no. 1, <>0 = Parameter set no. 2.
NOTE: the 2nd parameter set can only be activated at open field breaker.

3BHS102402 E88

Rev. G

SC
BI

HL
19999

LL
0

DEF.
10715

U
-

CLASS
AFB, IMP

SP
74

BI

19999

12308

AFB, HID

76

19999

12311

AFB, HID

76

BI

19999

12410

AFB, IMP

76

BI
BI

19999
19999

0
0

12501
10350

AFB, HID
AFB, HID

76
76

BI

19999

10709

AFB, HID

76

BI

19999

10710

AFB, HID

76

BI
BI
BI

19999
19999
19999

0
0
0

10350
12501
12501

AFB, IMP
AFB, CON
AFB, IMP

74
74
123

BI
BI

19999
19999

0
0

12501
12501

AFB, HID
AFB, HID

74
74

BI

Parameter and Signal List Version 41.222_2


INDEX
5327

[IN FLDB REQ]

INDICATION

5328

[FLDB ON/OFF]

5329

[FLDB START STOP]

5330

[FLDB A/M]

5331

[FLDB CMD IMP]

5332

[FLDB SEL IMP]

5333

[FLDB REQ REF]

5334

[IN FLDB REF]

48

FUNCTION
Input from fieldbus. Enables inputs 5328...5334 to be controlled via fieldbus.
Connection by application program required (Ref. to 3BHS100500) and fieldbus type specific Installation and Startup Instructions.
DEFAULT: Connected to Control word INTEGER- BINARY converter output (12972) if fieldbus application is
loaded.
Input from fieldbus. Controls field breaker via fieldbus.
Connection by application program required (Ref. to 3BHS100500) and fieldbus type specific Installation and Startup Instructions.
DEFAULT: Connected to Control word INTEGER- BINARY converter output (12962) if fieldbus application is
loaded.
Input from fieldbus. Controls EXCITATION START / STOP via fieldbus.
Connection by application program required (Ref. to 3BHS100500) and fieldbus type specific Installation and Startup Instructions.
DEFAULT: Connected to Control word INTEGER- BINARY converter output (12963) if fieldbus application is
loaded.
Input from fieldbus. Controls AUTO-MANUAL CHANGEOVER via fieldbus.
Connection by application program required (Ref. to 3BHS100500) and fieldbus type specific Installation and Startup Instructions.
DEFAULT: Connected to Control word INTEGER- BINARY converter output (12973) if fieldbus application is
loaded.
Input from fieldbus. Controls preselected IMPOSED CONTROL ON-OFF via fieldbus.
Connection by application program required (Ref. to 3BHS100500) and fieldbus type specific Installation and Startup Instructions.
DEFAULT: Connected to Control word INTEGER- BINARY converter output (12974) if fieldbus application is
loaded.
Input from fieldbus. Preselects IMPOSED COTROLLER TYPE (VAR or P.F.) via fieldbus.
Connection by application program required (Ref. to 3BHS100500) and fieldbus type specific Installation and Startup Instructions.
DEFAULT: Connected to Control word INTEGER- BINARY converter output (12975) if fieldbus application is
loaded.
Input from fieldbus. Enables REFERENCE VALUE of active controller to be received via fieldbus.
Connection by application program required (Ref. to 3BHS100500) and fieldbus type specific Installation and Startup Instructions.
DEFAULT: Connected to Control word INTEGER- BINARY converter output (12965) if fieldbus application is
loaded.
Input from fieldbus. REFERENCE VALUE to active controller via fieldbus.
Connection by application program required (Ref. to 3BHS100500) and fieldbus type specific Installation and Startup Instructions.
DEFAULT: Connected to Control word DATASET 1 OUT2 (10134) if fieldbus application is loaded.

3BHS102402 E88

Rev. G

SC
B1

HL
19999

LL
0

DEF.
12501

U
-

CLASS
AFB, HID

SP
77

B1

19999

12501

AFB, HID

77

B1

19999

12501

AFB, HID

74

B1

19999

12501

AFB, HID

74

B1

19999

12501

AFB, HID

74

B1

19999

12501

AFB, HID

76

B1

19999

12501

AFB, HID

79

B1

19999

12501

AFB, HID

79

Parameter and Signal List Version 41.222_2


INDEX
5335

INDICATION
[OFF BLK CMD]

49

FUNCTION
Input for Excitation OFF (STOP) command. Stops excitation by inverter mode or by pulse blocking together with
opening of the converter input (field) breaker, if RELEASE_FOB_OFF (301) is set to YES.
DEFAULT: not used (12501).
NOTE: At the configuration with field C.B. on converter input (parameter CB_CONFIG (309) = 0==AC SIDE) and
parameter RELEASE_FCB_OFF (301) set to 0==NO, this input must only be used in parallel to the external F.C.B.
TRIP command. In that case the normal EXCITATION_OFF COMMAND must be connected to input
EXC_OFF_CMD (5303).

3BHS102402 E88

Rev. G

SC
BI

HL
19999

LL
0

DEF.
12501

U
-

CLASS
AFB, IMP

SP
74

Parameter and Signal List Version 41.222_2


3.4

CONVERTER CTRL

INDEX
5501

[SEL SEQUENCE]

5502

[UCTRL]

5503

[INV CTRL]

5504

[IN FREEWHEELING]

3.5
INDEX
-

3.6
INDEX
-

INDICATION

50

Group 55

FUNCTION
Input which selects for reversed converter input phase sequence. Same functionality as parameter 503. Used for MOTORGENERATOR applications when sequence has to be selected by control logic. Back indication by REVERSE_SEQ
(10518). DEFAULT: not used (12501).
NOTE: Input command is only accepted when excitation off.
Gate control input signal:
-10000==ALPHA 180 DEG (C5: MIN thyristor duty cycle in Q4); +10000==ALPHA 0 DEG (C5: MAX. IGBT duty cycle in
Q1). DEFAULT: connected to U_CTRL_OUT_CH (12110).
Inverter operation mode control input. Forces firing angle ALPHA to ALPHA_MAX_LIMIT (517).
DEFAULT: not used (12501).
Freewheeling mode control input. Forces permanent firing to + and - thyristors of phase 1 (L1 input), if pulses released (No
pulse blocking active) while all other pulses are blocked. Duration is internally limited to 10s and repetition is only available
again after 20s without freewheeling.
DEFAULT: not used (12501)
NOTE: Connect this input to N.C. aux. contact of HV side breaker, if it can be opened during normal operation.

SC
BI

HL
19999

LL
0

DEF.
12501

U
-

CLASS
AFB, HID

SP
73

BI

19999

12301

AFB, CON,
IMP

47

BI

19999

12501

47

BI

19999

12501

AFB, CON,
IMP
AFB, HID

47

SC

HL

LL

CLASS

SP

DATA LOGGER Group 56


INDICATION
-

DIGITAL I/O
INDICATION
-

FUNCTION
-

DEF.

Group 57
FUNCTION
-

SC

3BHS102402 E88

Rev. G

HL

LL

DEF.

CLASS

SP

Parameter and Signal List Version 41.222_2


3.7

MONITORING

51

Group 59

INDEX
5901

INDICATION
[OVP CURRENT]

5902

[OVT1 TRAFO]

5903

[OVT2 TRAFO]

5904

[NO EXT ALARM]

5905

[IN B/L MONITOR]

FUNCTION
Input for external crowbar current Monitoring detector. If TRUE, EXCITATION_ON and no FREEWHL_CROWBAR
(10516) present, the Fault 35 Field overvoltage is generated. DEFAULT: not used (12501).
Connect to corresponding spare digital input DIX... if crowbar provided (always needed for static excitation).
NOTE:
This signal is monitored during normal field discharge by crowbar (CB_CONFIG (309) = 0 or 1). If no signal
detected during discharge, ALARM 135 Crowbar failed will be generated.
Input for external excitation transformer temperature detector. If TRUE the Alarm 103 Trafo temp. Alarm is generated.
DEFAULT: not used (12501).
Connect to corresponding spare digital input DIX... if signal provided (normally for static excitation).
Input for excitation transformer temperature detector. If TRUE the Fault 06 Trafo overtemp.trip is generated. DEFAULT:
not used (12501).
Connect to corresponding spare digital input DIX... if signal provided (normally for static excitation).
Input for general alarm of secondary external auxiliaries like M.C.Bs of aux. supply heater, etc.
DEFAULT: DIX14 (10714).
NOTE: This is an inverting input. With default setting of BLOCK_START_UP (5301), starting excitation is NOT
POSSIBLE as long as external alarm loop isnt closed.
Not applicable for this SW release 41.22x

5906

[BLK B/L MONITOR]

5907

[A145 BLK/C5 TST]

5908

[IN PT FAIL]

5909

[IN PT FAIL DYN]

3.8

SC
BI

HL
19999

LL
0

DEF.
12501

U
-

CLASS
AFB, AL, IMP

SP
80

BI

19999

12501

AFB, AL, IMP

80

BI

19999

12501

AFB, AL, IMP

80

BI

19999

10714

AFB, AL, IMP

80

AI

19999

10101

Not applicable for this SW release 41.22x

AI

19999

12501

Input which blocks the ALARM 145 Test supply, or forces it in case of chopper (type C5). Used in case when supply can
be switched over from shunt to separate supply, e.g. for braking operation, or in case C5 at normal TEST SUPPLY
condition. DEFAULT: not used (12501).
Input for external or AFB made P.T. FAIL relay. If input TRUE, U_MACH_FAIL (10908) and AVR_FAULT (10910)
become TRUE and Alarm 120 Machine P.T. fail is generated.
DEFAULT: not used (12501).
Input for reactive or armature current. If this signals changes dynamically before the P.T. signals drops (dU/dt_TRIGGER
(10125) = TRUE), then the Monitoring will be blocked.
DEFAULT: I_SINPHI_RELATIVE (10109). From Rel. 41.221_1: I_MACH_RELATIVE (10103)
NOTE: I_MACH_RELATIVE should be used instead of I_SINPHI_RELATIVE since in case P.T. phase 2 or 3 fails,
I_SINPHI_RELATIVE fails too.

BI

19999

12502

CM, HID,
MON
CM, HID,
MON
AFB, HID

80

BI

19999

12501

AFB, HID

81

BI

19999

12405

AFB, HID

81

CLASS
AFB, CM,
MON
AFB, CM,
MON

SP
121

RT MONITORING

Group 60

INDEX
6001

INDICATION
[IN U RTM]

FUNCTION
Input voltage for calculation of RF RELATIVE. DEFAULT: U EXC RELATIVE (10505).

SC
AI

HL
19999

LL
0

DEF. U
10505

6002

[IN I RTM]

Current input for calculation of RF RELATIVE. DEFAULT: I EXC RELATIVE (10501).

AI

19999

10501

3BHS102402 E88

Rev. G

121

Parameter and Signal List Version 41.222_2

52

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


3.9
INDEX
-

3.10
INDEX
-

3.11

FAULTS, ALARMS
INDICATION
-

IE LIMITER

INDEX
6301

[ADD REF IETH]

INDICATION

6302

[ADD REF IEMAX]

6303
6304
6305

[SEL REF2 IETH]


[SEL MAX2 IEMAX]
[IEL MAX RETRIG]

6306

[IN I IELIM]

3.12

I LIMITER

INDEX
6401

[ADD REF I MACH]

6402
6403

[SEL REF2 ITH2]


[I UNLTD TRIGGER]

INDICATION

Group 61

FUNCTION
-

MAINTENANCE
INDICATION
-

53

SC

HL

LL

DEF.

CLASS

SP

SC

HL

LL

DEF.

CLASS

SP

SC
AI

HL
19999

LL
0

DEF.
12501

U
-

CLASS
AFB, HID, AVR

SP
55

AI

19999

12501

AFB, HID, AVR

55

BI
BI
BI

19999
19999
19999

0
0
0

12501
12501
10125

AFB, HID, AVR


AFB, HID, AVR
HID, AVR

55
55
55

A1

19999

10501

AFB, HID AVR

55

SC
AI

HL
19999

LL
0

DEF.
12501

U
-

CLASS
AFB, CM, AVR

SP
56

BI
BI

19999
19999

0
0

12501
10125

AFB, CM, AVR


AFB, CM, AVR

56
56

Group 62

FUNCTION
-

Group 63
FUNCTION
Spare input added to selected REF1, 2_IETH for correction by e.g. cooling medium temp.
DEFAULT: not used (12501).
Spare input added to selected REF1, 2_IEMAX for correction by e.g. cooling medium temperature.
DEFAULT: not used (12501).
Control input for REF2_IETH selection. DEFAULT: not used (12501).
Control input for REF2_IEMAX2 selection. DEFAULT: not used (12501).
Control input to release selected ceiling setpoint REF1, 2_IEMAX if machine voltage drops, e.g. caused by line faults.
DEFAULT: dU/dt_TRIGGER (10125).
Actual value input to IE limiter. Connect it to spare analog input if e.g. EXCITER output current must be limited instead of
EXCITER field current.
DEFAULT: connected to I_EXC_RELATIVE (10501)

Group 64
FUNCTION
Spare input added to selected REF_I_MACH TH for correction by e.g. cooling medium temp.
DEFAULT: not used (12501).
Control input for REF2_I_MACH_TH selection. DEFAULT: not used (12501).
Control input to release non limiting condition if machine voltage drops, e.g. caused by line faults.
DEFAULT: dU/dt_TRIGGER (10125).

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


3.13
INDEX
-

3.14

PQ IEMIN LIM
INDICATION
-

Group 65
FUNCTION
-

COSPHI CTRL

INDEX
6701

INDICATION
[RAISE COSPHI]

6702

[LOWER COSPHI]

6703

[SEL REF EXT COS]

6704

[TRIG PRESET COS]

6705

[IN REF EXT COS]

6706

[IN ERR EXT COS]

6707

[SEL ERR EXT COS]

6708

[ICOSPHI IN]

6709

[ISINPHI IN]

54

SC

HL

LL

DEF.

CLASS

SP

SC
BI

HL
19999

LL
0

DEF.
10324

U
-

CLASS
AFB, SIP

SP
58

BI

19999

10325

AFB, SIP

58

BI

19999

12501

AFB, HID, SIP

58

BI

19999

10304

AFB, HID, SIP

58

AI

19999

12501

AFB, HID, SIP

58

AI

19999

12501

AFB, HID, SIP

58

BI

19999

12501

AFB, HID, SIP

58

AI

19999

10105

AFB, SIP

58

AI

19999

10109

AFB, SIP

58

Group 67

FUNCTION
Remote cosphi (P.F.) RAISE command input.
DEFAULT: connected to RAISE_COSPHI_CMD (10323).
Remote cosphi (P.F.) LOWER command input.
DEFAULT: connected to LOWER_COSPHI_CMD (10324).
Control input which activates user defined setpoint input connected to IN REF EXT COS (6705).
DEFAULT: not used (12501).
Input which unconditionally forces the REF_COSPHI_ACT (11704) to the set PRESET_REF_COSPHI (1705) value.
Use a MONO AFB (TP = 1s) between ON_COSPHI_CTRL (10315) and this input if COSPHI controller should start
always at PRESET point instead of actual operation point after switched on. If permanent PRESET is required to operate
the machine with constant P.F., then connect this input to 12502 = TRUE.
DEFAULT: connected to ON_PRESET_CMD (10304).
User defined COSPHI setpoint input. E.g. an analog input can be connected to this input, if remote analog setpoint (e.g.
4...20 mA) is provided instead of RAISE/LOWER commands, or a User Parameter can be used if a 2nd constant
setpoint is required beside PRESET_REF_COSPHI. DEFAULT: not used (12501).
Consider the setpoint characteristic:
VALUE = 10000 - [(PRESET_REF_COSPHI overexcited)*10000] e.g. = 10000 - [0.8 * 10000] = 2000
VALUE = [(PRESET_REF_COSPHI underexcited)*10000] -10000 e.g. = [0.9 * 10000] -10000 = -1000
NOTE: The value will be limited by the HL_REF_COSPHI (1703) and LL_REF_COSPHI (1704) if the external signal
exceeds the HL, LL values set. Therefore it is recommended to scale analog input to HL, LL set.
User defined ERR_SUPERIMPOSED signal. This input is used if superimposed control is defined by user with AFBs
instead of firmware COSPHI_CTRL. E.g. reactive power equalizing between several machines. DEFAULT: not used
(12501).
This input activates IN_ERR_EXT_COS (6706) input. If in use, the ON_COSPHI_CTRL is required as well to get
superimposed ctrl active. DEFAULT: not used (12501).
Input for active current of the machine. If tie connection P.F. is controlled instead of machine P.F., then external active
power transducer is put to this input via a spare analog input.
DEFAULT: connected to I_COSPHI_REL (10105).
Input for reactive current of the machine. If tie connection P.F. is controlled instead of machine P.F., then external
reactive power transducer is put to this input via a spare analog input.
DEFAULT: connected to I_SINPHI_REL (10109).

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2

55

3.15

Q CTRL

Group 68

INDEX
6801

INDICATION
[RAISE Q CTRL]

FUNCTION
Remote Q (VAR) RAISE command input. DEFAULT: connected to RAISE_Q_CTRL_CMD (10325).

SC
BI

HL
19999

LL
0

DEF.
10325

U
-

CLASS
AFB, SIP

SP
57

6802

[LOWER Q CTRL]

Remote Q (VAR) LOWER command input. DEFAULT: connected to LOWER_Q_CTRL_CMD (10326).

BI

19999

10326

AFB, SIP

57

6803

[SEL REF EXT Q]

BI

19999

12501

AFB, HID, SIP

57

6804

[TRIG PRESET Q]

BI

19999

10304

AFB, HID, SIP

57

6805

[IN REF EXT Q]

AI

19999

12501

AFB, HID, SIP

57

6806

[IN ERR EXT Q]

AI

19999

12501

AFB, HID, SIP

57

6807

[IN UNLOAD Q]

BI

19999

12501

AFB, HID, SIP

57

6808

[SEL ERR EXT Q]

BI

19999

12501

AFB, HID, SIP

57

6809

[Q IN]

Control input which activates user defined ref. signal connected to IN REF EXT Q (6805).
DEFAULT: not used (12501).
Control input which unconditionally forces the REF_Q_ACTUAL (11805) to the set PRESET_REF_Q_CTRL (1805)
value. Use a MONO AFB (TP = 1s) between ON_Q_CTRL (10316) and this input if Q controller should start always at
PRESET point instead of actual operation point after switched on. If permanent PRESET is required to operate the
machine with constant reactive power., then connect this input to 12502 = TRUE. DEFAULT: connected to
ON_PRESET_CMD (10304).
User defined Q_CTRL setpoint input. E.g. an analog input can be connected to this input, if remote analog setpoint (e.g.
4...20 mA) is provided instead of RAISE/LOWER commands, or an User Parameter can be used if beside
PRESET_REF_Q_CTRL a 2nd constant setpoint is required. DEFAULT: not used (12501)
NOTE: The value will be limited by the HL_REF_Q_CTRL (1803) and LL_REF_Q_CTRL (1804) if the external signal
exceeds the HL, LL values set.
Therefore it is recommended to scale analog input to HL, LL set.
User defined ERR_SUPERIMPOSED signal. This input is used if superimposed control is defined by user with AFBs
instead of firmware Q_CTRL. E.g. reactive power equalizing between several machines. DEFAULT: not used (12501).
As long as this input is TRUE, the Q controller unloads the machine aperiodically at the time constant set by
TC_IMPOSED_CTRL_A (1908) to zero reactive power, independent whether Q_CTRL is activated by the
CONTROL_LOGIC.
This input activates IN_ERR_EXT_Q (6806) input. If using, the ON_Q_CTRL from CONTROL_LOGIC is required as well
to get superimposed ctrl active. DEFAULT: not used (12501)
Input for reactive power of the machine. The controller can be used alternatively by the user, if putting here instead of
absolute reactive power e.g. reactive power difference, getting from optional equalizing bus. DEFAULT: connected to
Q_MACH_RELATIVE (10110).

AI

19999

10110

AFB, HID, SIP

57

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


3.16

AVR CTRL

INDEX
6901
6902
6903
6904
6905
6906
6907

[RAISE AVR
[LOWER AVR
[SEL IMPOSED AVR]
[ERR IMPOSED AVR]
[SEL RAMPTIME2 A]
[SEL PRESET2 AVR]
[TRIG PRST AVR]

INDICATION

6908
6909

[ADD IN REF1 A]
[PID SET2 SEL1]

6910

[PID SET2 SEL2]

6911
6912
6913

[PID SET2 SEL3]


[PID SET2 SEL4]
[PID SET3 SEL1]

6914

[PID SET3 SEL2]

6915

[PID SET3 SEL3]

6916
6917
6918
6919
6920

[PID SET3 SEL4]


[IN AVR ERR]
[ADD IN1 AVR]
[ADD IN2 AVR]
[ADD AVR OUT]

56

Group 69
FUNCTION
Remote AVR setpoint RAISE command input. DEFAULT: RAISE_AUTO_CMD (10319).
Remote AVR setpoint LOWER command input. DEFAULT: LOWER_AUTO_CMD (10320).
Activates the ERR_IMPOSED_AVR (6904) input. DEFAULT: ON_SUPERIMPOSED (10314).
Input for the error signal from superimposed controller output. DEFAULT: ERR_SUPERIMPOSED (11708).
Control input for RAMP_TIME2_REF_A (1906) selection. DEFAULT: not used (12501).
Control input for PRESET2_REF_AVR (1904) selection. DEFAULT: not used (12501).
Control input which unconditionally forces the REF1_AVR_REL (11901) to the selected PRESET1_REF_AVR or
PRESET2_REF_AVR value. DEFAULT: ON_PRESET_CMD (10304).
Extra summing input to REF1_AVR_REL. DEFAULT: not used (12501).
Input 1 which selects TA2 and TB2. DEFAULT: connected to ON_IE_LIMITER (12004). If DEFAULT source is
disconnected because of other requirements, PID_SET1 becomes active for IE_LIMITER.
Input 2 which selects TA2 and TB2. DEFAULT: connected to ON_IEMIN_LIMITER (12009). If DEFAULT source is
disconnected because of other requirements, PID_SET1 becomes active for IEMIN_LIMITER.
Input 3 which selects TA2 and TB2. DEFAULT: not used (12501).
Input 4 which selects TA2 and TB2. DEFAULT: not used (12501).
Input 1 which selects TA3 and TB3. DEFAULT: connected to ON_IOE_LIMITER (12005). If DEFAULT source is
disconnected because of other requirements, PID_SET1 becomes active for IOE_LIMITER.
Input 2 which selects TA3 and TB3. DEFAULT: connected to ON_IUE_LIMITER (12008). If DEFAULT source is
disconnected because of other requirements, PID_SET1 becomes active for IUE_LIMITER.
Input 3 which selects TA3 and TB3. DEFAULT: connected to ON_Q(P)_LIMITER (12007). If DEFAULT source is
disconnected because of other requirements, PID_SET1 becomes active for Q(P)_LIMITER.
Input 4 which selects TA3 and TB3. DEFAULT: not used (12501).
AVR PID controller input error signal. DEFAULT: connected to ERR1_AVR (12001).
Additional AVR PID controller input 1. DEFAULT: connected to OUT_PSS (12010).
Additional AVR PID controller input 2. DEFAULT: not used (12501).
Adder input at AVR PID output. DEFAULT: not used (12501).

3BHS102402 E88

Rev. G

SC
BI
BI
BI
AI
BI
BI
BI

HL
19999
19999
19999
19999
19999
19999
19999

LL
0
0
0
0
0
0
0

DEF.
10319
10320
10314
13808
12501
12501
10304

U
-

CLASS
AFB, AVR
AFB, AVR
AFB, SIP
AFB, SIP
AFB, HID, AVR
AFB, HID, AVR
AFB, HID, AVR

SP
43
43
43
43
43
43
43

AI
BI

19999
19999

0
0

12501
12004

AFB, HID, AVR


CM, HID, AVR

44
42

BI

19999

12009

CM, HID, AVR

42

BI
BI
BI

19999
19999
19999

0
0
0

12501
12501
12005

CM, HID, AVR


CM, HID, AVR
CM, HID, AVR

42
42
42

BI

19999

12008

CM, HID, AVR

42

BI

19999

12007

CM, HID, AVR

42

BI
AI
AI
AI
AI

19999
19999
19999
19999
19999

0
0
0
0
0

12501
12001
12010
12501
12011

CM, HID, AVR


AFB, HID, AVR
AFB, HID, AVR
AFB, HID, AVR
AFB, HID, AVR

42
42
42
42
42

Parameter and Signal List Version 41.222_2


3.17

AVR IN, PSS

INDEX
7001
7002
7003

[REF INPUT AVR]


[ADD INPUT AVR]
[FB IN FOLLOW A]

INDICATION

7004

[IN IELIM ERR A]

7005

[IN IOEL ERR AVR]

7006

[IN USER OEL ERR]

7007

[IN Q(P) LIM ERR]

7008

[IN IUEL ERR AVR]

7009

[IN IEMINLIM ERR]

7010

[BLK LIMITER]

7011

[LIM INDIC ON]

7012

[IN P PSS]

7013

[IN f PSS]

7014

[BLK PSS]

57

Group 70
FUNCTION
Input for the finally processed AVR (AUTO) setpoint (ref.) signal. DEFAULT: REF4_AVR_REL (11906).
Spare input to AVR summing point. DEFAULT: not used (12501).
Feedback input from FOLLOW_UP_CTRL (group 21). This feedback closes the control loop of the inactive AVR (AUTO)
channel to get stable auto follower loop. DEFAULT: FBA_FOLLOW_AUTO (12113).
Input for the IE_LIMITER error signal. If lower than the AVR error signal it takes over loop control instead of the AVR. This
action is indicated by the output ON_IE_LIMITER (12004) and ON_OE_LIMITER (12002) at AUTO mode. DEFAULT:
OUT_IE_LIMITER (11301).
NOTE: The limiter is made inactive by setting the input to CONST_20000 (12509).
Input for the I_LIMITER OE error signal. If lower than the AVR error signal it takes over loop control instead of the AVR.
This action is indicated by the output ON_IOE_LIMITER (12005) and ON_OE_LIMITER (12002) at AUTO mode.
DEFAULT: not used == CONST_20000 (12509).
NOTE: Connect to OUT_I_OE_LIMITER (11401) if I_OE limiter required. The parameter 1407 must be set prior to
>0, otherwise the AVR input high limit will be set to zero by this action. Ref. also to parameter 1407.
Spare input for the user defined OE_LIMITER error signal. If lower than the AVR error signal it takes over loop control
instead of the AVR. This action is indicated by the output ON_IE_USER_LIM (12006) and ON_OE_LIMITER (12002) at
AUTO mode. DEFAULT: not used == CONST_20000 (12509).
Input for the Q(P)_LIM error signal. If higher than the AVR error signal it takes over loop control instead of the AVR. This
action is indicated by the output ON_Q(P)_LIMITER (12007) and ON_UE_LIMITER (12003) at AUTO mode. DEFAULT:
OUT_Q(P)_LIMITER (11501).
NOTE: The limiter is made inactive permanently by setting the input to CONST_N20000 (12510).
Input for the I_LIMITER UE error signal. If higher than the AVR error signal it takes over loop control instead of the AVR.
This action is indicated by the output ON_IUE_LIMITER (12008) and ON_UE_LIMITER (12003) at AUTO mode.
DEFAULT: not used == CONST_N20000 (12510).
NOTE: Use this limiter very restrictively for TURBO machine, since the Q(P) limiter covers normally all requirements.
Connect to OUT_I_UE_LIMITER (11402) if I_UE limiter required. The parameter 1408 must be set prior to
>0, otherwise the AVR input low limit will be set to zero by this action. Ref. also to parameter 1408.
Input for the IEMIN_LIMITER error signal. If higher than the AVR error signal it takes over loop control instead of the
AVR. This action is indicated by the output ON_IEMIN_LIMITER (12009) and ON_UE_LIMITER (12003) at AUTO mode.
DEFAULT: not used == CONST_N20000 (12510).
General blocking input. If TRUE all AVR limiter actions are suppressed. DEFAULT: LIM_BLK (10345) which is TRUE if
MAN or STBY_ON. The MANUAL Limiters (restrictions) are released separately.
Release input for the indication signals 12002...12009. DEFAULT: LOGIC_1 (12502) == permanently released.
NOTE: The indications ON_OE_LIMITER (12002) and ON_UE_LIMITER (12003) include the indication from the
MANUAL Limiters too.
Power signal Input to PSS.
DEFAULT: connected to P_MACH_RELATIVE (10106)
Frequency signal input to PSS.
DEFAULT: connected to f_MACH_RELATIVE (10122)
PSS blocking input. DEFAULT: not used (12501).
Used e.g. for blocking when OFF_LINE if P_MACH_MIN is set to zero. (see PSS P_MACH_MIN (2020)). The output
12010 becomes zero, but PSS is still processed.

3BHS102402 E88

Rev. G

SC

HL

LL

DEF.

AI
AI
AI

19999
19999
19999

0
0
0

12101
12501
12304

AI

19999

AI

19999

AI

CLASS

SP

AFB, HID, AVR


AFB, HID, AVR
AFB, HID, AVR

41
41
41

11301

CM, HID, AVR

41

12509

CM, HID, AVR

41

19999

12509

AFB, HID, AVR

41

AI

19999

11501

CM, HID, AVR

41

AI

19999

12510

CM, HID, AVR

41

AI

19999

12510

CM, HID, AVR

41

BI

19999

10345

AFB, HID, AVR

41

BI

19999

12502

AFB, HID, AVR

41

AI

19999

10106

AFB, HID

122

AI

19999

10122

AFB, HID

122

BI

19999

12501

AFB, HID

122

Parameter and Signal List Version 41.222_2


3.18 MANUAL CTRL
INDEX
7101

INDICATION
[SEL IMPOSED MAN]

7102

[ERR IMPOSED MAN]

7103
7104
7105
7106

[RAISE MANUAL]
[LOWER MANUAL]
[SEL RAMPTIME2 M]
[SEL PRESET2 MAN]

7107

[TRIG PRST MAN]

7108
7109
7110
7111

[IN ACT MANUAL]


[IN REF MANUAL]
[ADD IN MANUAL]
[FB IN FOLLOW M]

7112

[FOLLOW RELEASE]

3.19

Group 71
FUNCTION
Activates the ERR_IMPOSED_MAN (7102) input. DEFAULT: V_HZ_MANUAL_ON (12108) which becomes TRUE if
OFF_LINE the V/Hz manual restrict interferes (ref. 7102, 12107, 12108).
NOTE: The limiter can be switched OFF temporarily by deleting the connection to V_HZ_MANUAL_ON (12108), but
consider that the indication ON_OE_LIMITER is not influenced by this action.
Input for the error signal from superimposed controller output. DEFAULT: V_HZ_ERR (12107) which is switched ON at
negative values if OFF_LINE and MANUAL_CTRL is ON. Then the V/Hz manual restrict interferes by reducing the
MANUAL_CTRL setpoint. For V/Hz characteristic ref. to 1911...13.
Remote MANUAL_CTRL setpoint RAISE command input. DEFAULT: RAISE_MANUAL_CMD (10321).
Remote MANUAL_CTRL setpoint LOWER command input. DEFAULT: LOWER_MANUAL_CMD (10322).
Control input for RAMP_TIME2_REF_M (2104) selection. DEFAULT: not used (12501).
Control input for PRESET2_REF_MAN (2108) selection. DEFAULT: connected to TEST_SUPPLY (10901). Since
PRESET2_REF_MAN default value is 0, the MANUAL excitation starts automatically at zero if Test supply is recognized
at SUPPLY_MODE (901) = SHUNT.
Control input which unconditionally forces the REF_MAN_ACTUAL (12105) to the selected PRESET1_REF_MAN or
PRESET2_REF_MAN value. DEFAULT: ON_PRESET_CMD (10304).
MANUAL controller actual value input. DEFAULT: connected to I_EXC_RELATIVE (10501).
MANUAL controller reference input. DEFAULT: connected to REF_MAN_ACTUAL (12105)
Extra summing input to MANUAL controller. DEFAULT: not used (12501).
Feedback input from FOLLOW_UP_CTRL. This feedback closes the control loop of the inactive MANUAL_CTRL channel
to get stable auto follower loop. DEFAULT: FBM_FOLLOW_MAN (12114).
Auto follower action is released by the control logic via this input. DEFAULT: ON_FOLLOW_UP (10303).

SC
BI

HL
19999

LL
0

DEF.
14008

U
-

CLASS
AFB, AVR, HID

SP
45

BI

19999

14007

AFB, AVR, HID

45

BI
BI
BI
BI

19999
19999
19999
19999

0
0
0
0

10321
10322
12501
12401

AFB, AVR
AFB, AVR
AFB, AVR, HID
AFB, AVR, HID

45
45
45
45

BI

19999

10304

AFB, AVR, HID

45

AI
AI
AI
AI

19999
19999
19999
19999

0
0
0
0

10501
14005
12501
12305

AFB, AVR, HID


AFB, AVR, HID
AFB, AVR, HID
AFB, AVR, HID

59
59
59
59

BI

19999

10303

AFB, HID, AVR

46

SC
BI

HL
19999

LL
0

DEF.
12501

U
-

CLASS
AFB, HID

SP
82

AI

19999

12501

AFB, HID

82

SC
0.01

HL
-

LL
-

DEF.
-

CH COMMUNICATION Group 74

INDEX
7401

INDICATION
[USER DO]

7402

[USER AO]

FUNCTION
Input for user digital (Boolean) signal, which has to be transmitted to second (STBY) channel USER_DI (12407) pin.
DEFAULT: not used (12501). Connect to required digital output with BO scaling.
Input for user analog (INTEGER2) signal, which has to be transmitted to second (STBY) channel USER_AI (12409) pin.
DEFAULT: not used (12501). Connect to required output signal.
NOTE: Since only 14 Bits are transmitted, the 2 LSBs are set to 0.

Signals

4.1

ANALOG INPUTS

INDEX
10101

58

INDICATION
U MACH RELATIVE

Group 101

FUNCTION
Actual machine voltage RELATIVE.
DEFAULT: used for AVR, Limiters and Monitoring.

3BHS102402 E88

Rev. G

U
%

CLASS
IMP, IO, SM,
AVR

SP
3

Parameter and Signal List Version 41.222_2


INDEX
10102

U MACH V

INDICATION

10103

I MACH RELATIVE

10104

I MACH A

10105

I COSPHI REL

10106

P MACH RELATIVE

10107

P MACH KW

10108

P MACH MW

10109

I SINPHI REL

10110

Q MACH RELATIVE

10111

Q MACH KVAR

10112

Q MACH MVAR

10113

S MACH KVA

10114

S MACH MVA

10115

AI1 ACTUAL

59

FUNCTION
Actual relative machine voltage in VOLTS.
NOTE: refresh cycle of 1s. DEFAULT: used for Panel/CMT only.
Actual machine current RELATIVE.
DEFAULT: used for AVR, Limiters and Monitoring.
Actual machine current in AMPS.
NOTE: refresh cycle is 1s. Signal is forced to zero if machine is OFF_LINE.
DEFAULT: used for Panel/CMT only.
Actual machine active current RELATIVE (+ sign means power generation).
DEFAULT: used for AVR, Limiters and Monitoring.
Actual relative machine active power RELATIVE (+ sign means power generation).
DEFAULT: used for AVR, Limiters and Monitoring
Machine active power in kW (+ sign means power generation). Use P_MACH_MW (10108) for values bigger than 32767
kW.
NOTE: refresh cycle is 1s. Signal is forced to zero if machine is OFF_LINE. CMT and Panel indication toggle between
0 and 11111 if value is bigger than 32767.
DEFAULT: used for Panel/CMT only.
Machine active power in MW (+ sign means power generation). Use P_MACH_KW (10107) if resolution is not sufficient.
NOTE: refresh cycle is 1s. Signal is forced to zero if machine is OFF_LINE.
DEFAULT: used for Panel/CMT only.
Actual machine reactive current RELATIVE (+ sign means reactive power generation == overexcited). DEFAULT: used for
AVR, Limiters and Monitoring.
Actual relative machine reactive power RELATIVE (+ sign means reactive power generation == overexcited). DEFAULT:
used for AVR, Limiters and Monitoring.
Machine reactive power in kVAr(+ sign means reactive power generation == overexcited). Use Q_MACH_MVAR (10112)
for values bigger than 32767 kVAR.
NOTE: refresh cycle is 1s. Signal is forced to zero if machine is OFF_LINE. CMT and Panel indication toggle between
0 and 11111 if value is bigger than 32767.
DEFAULT: used for Panel/CMT only.
Machine reactive power in MVAr (+ sign means reactive power generation == overexcited). Use P_MACH_KVAR (10111)
if resolution is not sufficient.
NOTE: refresh cycle is 1s. Signal is forced to zero if machine is OFF_LINE.
DEFAULT: used for Panel/CMT only.
Machine armature power in kVA. Use S_MACH_MVA (10114) for values bigger than 32767 kVA. CMT and Panel
indication toggle between 0 and 11111 if value is bigger than 32767.
NOTE: refresh cycle is 1s. Signal is forced to zero if machine is OFF_LINE.
DEFAULT: used for Panel/CMT only
Machine armature power in MVA. Use S_MACH_KVA (10113) if resolution is not sufficient.
NOTE: refresh cycle is 1s. Signal is forced to zero if machine is OFF_LINE.
DEFAULT: used for Panel/CMT only.
Actual machine active power from PSS option UNS 0869 V2 or spare analog input from X3:8 terminal if S100 on UNS
1860b in Pos. 2.
NOTE: Signal must be scaled by application function block (MULDIV) if required.
DEFAULT: not used.

3BHS102402 E88

Rev. G

SC
1

HL
-

LL
-

DEF.
-

U
V

CLASS
SM, HID

SP
3

0.01

IO, SM, HID

0.1

SM, HID

0.01

IMP, IO, SM

0.01

SM, IMP

KW

SM, HID

0.1

M
W

SM, HID

0.01

IMP, IO, SM

0.01

IMP, IO, SM

KVAR

SM, HID

0.1

MVA
R

SM, HID

KVA

SM, HID

0.1

MVA SM, HID

0.01

SM, IO, HID

Parameter and Signal List Version 41.222_2


INDEX
10116

AI2 ACTUAL

INDICATION

10117

AI2 NEG ACTUAL

10118

AI2 FAILURE

10119

AITAC ACTUAL

10120

AITAC NEG ACTUAL

10121

AITAC FAILURE

10122

f MACH RELATIVE

10123
10124

f MACH HERTZ
COS PHI

10125

dU/dt TRIGGER

10126

COSPHI AO

10127

AI1E ACTUAL

10128

AI1E NEG ACTUAL

10129

AI1E FAILURE

10130

AI2E ACTUAL

10131

AI2E NEG ACTUAL

10132

AI2E FAILURE

60

FUNCTION
Spare analog input scaled by AI2_HIGH_VALUE (107) and AI2_LOW_VALUE (108) parameters.
DEFAULT: not used.
Negated value of AI2_ACTUAL (10116).
DEFAULT: not used.
Signal AI2_ACTUAL (10116) is below AI2_LIVE_ZERO (109) setting. Generates ALARM 123 AI failed.
DEFAULT: not used.
Spare analog input scaled by AITAC_HIGH_VALUE (110) and AITAC_LOW_VALUE (111) parameters.
DEFAULT: not used.
Negated output of AITAC_ACTUAL (10119).
DEFAULT: not used.
Signal AITAC_ACTUAL (10119) is below AITAC_LIVE_ZERO (112) setting. Generates ALARM 123 AI failed.
DEFAULT: not used.
Actual machine terminal frequency RELATIVE. DEFAULT: used for AVR, Limiters and Monitoring.
NOTE: If f-sensing failed (10717 = TRUE):
Signal is switched to 100% if EXC_ON or ON_LINE,
or switched to zero, if EXC_OFF, OFF_LINE and no PULSE_BLOCKING (10328). If PSS is selected and
ON_LINE, the output ramp filter is switched off.
Actual machine terminal frequency in Hz. DEFAULT: used for Panel/CMT only.
Machine power factor signal used for PANEL/CMT indication.
NOTE: refresh cycle is 1s. Signal is forced to zero if machine is OFF_LINE.
+ sign means P and Q have the same signs (e.g. power and reactive power generation).
- sign means P and Q have different signs (e.g. power generation and reactive power consumption).
Negative machine voltage gradient > 5 p.u./s.
This signal is used to release ceiling ref. of the overexcitation Limiters.
DEFAULT: connected to IEL_MAX_RETRIG (6305) and I_UNLTD_TRIGGER (6403).
Power factor signal used for analog output which normally feeds an external instrument:
-10000...0... +10000 means P.F. = 0 (lead)...1...0 (lag) normally scaled to -10...0...+10V output signal.
Spare analog input scaled by AI1E_HIGH_VALUE (114) and AI1E_LOW_VALUE (115) parameters.
NOTE: Only available if optional hardware UNS 0867 on CON-2 and second UNS 0863 are installed.
Negated value of AI1E_ACTUAL (10127).
NOTE: Only available if optional hardware UNS 0867 on CON-2 and second UNS 0863 are installed.
Signal AI1E_ACTUAL (10127) is below AI1E_LIVE_ZERO (116) setting. Generates ALARM 123 AI failed.
NOTE: Only available if optional hardware UNS 0867 on CON-2 and second UNS 0863 are installed.
Spare analog input scaled by AI2E_HIGH_VALUE (117) and AI2E_LOW_VALUE (118) parameters.
NOTE: Only available if optional hardware UNS 0867 on CON-2 and second UNS 0863 are installed.
Negated value of AI2E_ACTUAL (10130).
NOTE: Only available if optional hardware UNS 0867 on CON-2 and second UNS 0863 are installed.
Signal AI2E_ACTUAL (10130) is below AI2E_LIVE_ZERO (119) setting. Generates ALARM 123 AI failed.
NOTE: Only available if optional hardware UNS 0867 on CON-2 and second UNS 0863 are installed.

3BHS102402 E88

Rev. G

SC
1

HL
-

LL
-

DEF.
-

U
-

CLASS
IO

SP
5

IO, HID

BO

AL, IO, HID

IO

IO, HID

BO

AL, IO, HID

0.01

IO, SM

0.01
0.01

Hz
-

IO, SM, HID


SM, HID

7
3

BO

-1

SM, HID,
AVR

IO, SM

IO

83

IO, HID

83

BO

AL, IO, HID

83

IO

84

IO, HID

84

BO

AL, IO, HID

84

Parameter and Signal List Version 41.222_2


INDEX
10133

DATASET 1 OUT 1

INDICATION

10134

DATASET 1 OUT 2

10135

DATASET 1 OUT 3

10136

DATASET 3 OUT 1

10137

DATASET 3 OUT 2

10138

DATASET 3 OUT 3

61

FUNCTION
Fast data input from field bus.
DEFAULT: Control word connected to INTEGER-BINARY converter input (3312) if fieldbus application is loaded.
NOTE:
This option is only available with external field bus adapter HW and if the relevant field bus application is
downloaded.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data input from field bus.
DEFAULT: Reference signal IN_FLDB_REF (5334) to the active controller AUTO (AVR), MANUAL COS PHI (P.F.) or Q
(AVR) CTRL, if fieldbus application is loaded.
NOTE:
This option is only available with external field bus adapter HW and if the relevant field bus application is
downloaded.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data input from field bus.
DEFAULT: not used. Spare input for application.
NOTE:
This option is only available with external field bus adapter HW.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data input from field bus.
DEFAULT: not used. Spare input for application.
NOTE:
This option is only available with external field bus adapter HW.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data input from field bus.
DEFAULT: not used. Spare input for application.
NOTE:
This option is only available with external field bus adapter HW.
Ref. to relevant fieldbus installation and start-up instructions.
Fast data input from field bus.
DEFAULT: not used. Spare input for application.
NOTE:
This option is only available with external field bus adapter HW.
Ref. to relevant fieldbus installation and start-up instructions.

3BHS102402 E88

Rev. G

SC
AO

HL
32767

LL
3276
8

DEF.
-

U
-

CLASS
COM, IO

SP
125

AO

32767

3276
8

COM, IO

125

AO

32767

3276
8

COM, IO

125

AO

32767

3276
8

COM, IO

125

AO

32767

3276
8

COM, IO

125

AO

32767

3276
8

COM, IO

127

Parameter and Signal List Version 41.222_2


4.2
INDEX
-

4.3

ANALOG OUTPUTS
INDICATION

INDICATION
MODE INDICATION

10302

MODE SELECTION

10303
10304

ON FOLLOW UP
ON PRESET CMD

10305

FCB ON CTRL

Group 102

FUNCTION
-

CONTROL LOGIC

INDEX
10301

62

SC

HL

LL

DEF.

CLASS

SP

HL
-

LL
-

DEF.
-

U
-

CLASS
DIAG

SP
-

CM, IMP

DIAG, HID
DIAG, HID

75
74

DIAG, HID

74

Group 103

FUNCTION
SC
ENUM
Actual status of operation mode for panel & CMT indication with different priorities. If more than one status is given, the
status with the highest priority (lowest priority No.) is indicated. The first digit indicates the active physical channel (1=
Channel 1 or Single Channel, 2= Channel 2 of an AFTsystem).
1/2 OEL
priority 1 indicates any Over Excitation Limiter is active
1/2 UEL
priority 1 indicates any Under Excitation Limiter is active
1/2 REF MIN
priority 2 REFerence (set point) of active ctrl is in MINimal position
1/2 REF MAX
priority 2 REFerence (set point) of active ctrl is in MAXimal position
1/2 XFER BLKD priority 3 AUTO<->MAN transfer blocked for panel in LOCAL
1/2 MAN
priority 4 MANual control is active
1/2 COSPHI
priority 5 Superimposed COS PHI (P.F.) control to AVR setpoint
1/2 Q
priority 5 Superimposed Q (VAR) control to AVR setpoint
1/2 AUTO
priority 6 AUTO (AVR) control is active without superimposed ctrl
ENUM
Operation mode signal which can be forced by panel or CMT (In LOCAL CTRL mode only):
MAN ON
selects MANual control mode if RDY_XFER_A_M (12117) = TRUE (selects MAN in both channels of
an AFT system).
COSPHI ON
selects Superimposed COS PHI (P.F.) ctrl, if all preconditions O.K. (in both channels of an AFT
system).
Q ON
selects Superimposed Q (VAR) control, if all preconditions O.K. (in both channels of an AFT system.
AUTO ON
selects AUTO (AVR) mode, if no AUTO_FAIL (5317) is present and RDY_XFER_A_M (12117) =
TRUE (selects AUTO in both channels of an AFT system).
CHANGEOVER
Toggles between the channels. Delayed data transfer if Panel/CMT is connected to the CH2 (slave)
instead of CH1 (master). Take notice of NOTE below.
NOTE: Activating the channel which is not communicating with the Panel/CMT means, that all signals, parameters,
Alarms and Faults presented on Panel/CMT are now from the inactive (nonduty) channel. Only the control
functions LOCAL-REMOTE, ON - OFF, START - STOP and Ref. setting are valid for both channels.
If the transfer is NOT only for TEST measure, then the communication should be transferred as well by
selecting Panel communication (and/or connecting CMT) to the newly activated channel (Ref. to Panel UNS
0874 instructions).
Releases the auto follower after SOFTSTART period. DEFAULT: connected to FOLLOW_RELEASE (7112).
BO
BO
Preset pulse generated at START_EXCITATION and if machine goes OFF_LINE.
DEFAULT: connected to TRIG_PRST_AVR (6907), TRIG_PRST_MAN (7107), TRIG_PRST_COS (6704) and
TRIG_PRST_Q (6804).
Closing command 1.5s to field circuit breaker (FCB). DEFAULT: connected to DOX03.[IN] (702).
BO
NOTE: This is completed only by the active channel of a 2 channel configuration AFT.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


INDEX
10306

INDICATION
FCB FAILURE

10307
10308

EXC ON
EXC OFF INV CTRL

10309

FCB OFF

10310

AUTO ON

10311

MAN ON

10312

REF MAX ACTIVE

10313

REF MIN ACTIVE

10314
10315

ON SUPERIMPOSED
ON COSPHI CTRL

10316

ON Q CTRL

10317
10318
10319

PRESEL COSPHI
PRESEL Q CTRL
RAISE AUTO CMD

10320

LOWER AUTO CMD

10321

RAISE MANUAL CMD

10322

LOWER MANUAL CMD

10323

RAISE COSPHI CMD

63

FUNCTION
FCB_ON_CTRL (10305) or FCB_OFF (10309) were not successful within 1s. Releases ALARM 127 FCB failed.
NOTE: Signal is transient in case of ON_CTRL. It disappears with end of Signal FCB ON CTRL.
Status: Excitation is ON. DEFAULT: connected to DOX14.[IN] (713).
Status: Excitation is OFF. DEFAULT: internal use only.
C1...C4: Exc. shut down by INVERTER_CTRL (firing angle = max.: see 10520)
After another 60s PULSE_BLOCKING (10328) gets TRUE as well.
NOTE: If the machine is stopped without LOCAL or REMOTE OFF command, excitation is automatically
switched off at to low frequency. This feature is only active 60s after start up (EXC_ON = TRUE).
At CB_CONFIG (309) = AC SIDE an RELEASE_FCB_OFF = YES: instantaneous PULSE_BLOCKING.
C5
Exc. shut down by PULSE_BLOCKING (10328) which means max. operation at quadrant 4.
1.5s pulse trip command to field breaker. DEFAULT: connected to DOX04.[IN] (703).
NOTE: This is completed only by the active channel of a 2 channel configuration (AFT).
Status: AUTO (AVR) CTRL mode is active. DEFAULT: connected to DOX05.[IN] (704).
For panel/CMT indication ref. to 10301.
Status: MANUAL CTRL mode is active. DEFAULT: connected to DOX06.[IN] (705).
For panel/CMT indication ref. to 10301.
Status: Ref. (set point) maximum of active controller is reached. DEFAULT: connected to DOX08.[IN] (707).
For panel/CMT indication ref. to 10301.
NOTE: While superimposed control is ON, it may happen that max. setpoint of the led AVR is reached and indicated
before that one of the imposed controller. Coordinate the two setpoint ranges.
This is completed only by the active channel of a 2 channel configuration (AFT).
Status: Ref.(set point) minimum of active controller is reached. DEFAULT: connected to DOX09.[IN] (708).
For panel/CMT indication ref. to 10301.
NOTE: While superimposed control is ON, it may happen that max. setpoint of the led AVR is reached and indicated
before that one of the imposed controller. Coordinate the two setpoint ranges.
This is completed only by the active channel of a 2 channel configuration (AFT).
Status: preselected superimposed control is active. DEFAULT: connected to DOX07.[IN] (706).
Status: preselected superimposed COSPHI (P.F.) CONTROL is active. DEFAULT: no programmable connection. For
panel/CMT indication ref. to 10301.
Status: preselected superimposed Q (VAR) CONTROL is active. DEFAULT: no programmable connection.
For panel/CMT indication ref. to 10301.
Status: superimposed COSPHI (P.F.) CONTROL is preselected. DEFAULT: no programmable connection.
Status: superimposed Q (VAR) CONTROL is pre selected. DEFAULT: no programmable connection.
RAISE CMD which increases AUTO (AVR) set point. DEFAULT: connected to RAISE_AVR (6901).
NOTE: Effective in both channels of a 2 channel configuration (AFT).
LOWER CMD which decreases AUTO (AVR) set point. DEFAULT: connected to LOWER_AVR (6902).
NOTE: Effective in both channels of a 2 channel configuration (AFT).
RAISE CMD which increases MANUAL set point. DEFAULT: connected to RAISE_MANUAL (7103).
NOTE: Effective in both channels of a 2 channel configuration (AFT).
LOWER CMD which decreases MANUAL set point. DEFAULT: connected to LOWER_MANUAL (7104).
NOTE: Effective in both channels of a 2 channel configuration (AFT).
RAISE CMD which increases COSPHI set point. DEFAULT: connected to RAISE_COSPHI (6701).
RAISE means reactive power moves in direction for generation (overexcitation).
NOTE: Effective in both channels of a 2 channel configuration (AFT).

3BHS102402 E88

Rev. G

SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
AL, DIAG

SP
74

BO
BO

DIAG
DIAG, HID

74
74

BO

DIAG, HID

74

BO

DIAG, AVR

76

BO

DIAG, AVR

76

BO

DIAG, HID

78

BO

DIAG, HID

78

BO
BO

DIAG, SIP
DIAG, HID, SIP

79
79

BO

DIAG, HID, SIP

79

BO
BO
BO

79
79
77

BO

BO

BO

BO

DIAG, HID, SIP


DIAG, HID, SIP
DIAG, HID,
AVR
DIAG, HID,
AVR
DIAG, HID,
AVR
DIAG, HID,
AVR
DIAG, HID, SIP

77
77
77
77

Parameter and Signal List Version 41.222_2


INDEX
10324

INDICATION
LOWER COSPHI CMD

10325

RAISE Q CTRL CMD

10326

LOWER Q CTRL CMD

10327

FCB ACTION COUNT

10328

PULSE BLOCKING

10329
10330

USYN OK
FLASH ON FIELD

10331

FLASH FAILURE

10332

64

FUNCTION
LOWER CMD which decreases COSPHI set point. DEFAULT: connected to LOWER_COSPHI (6702).
LOWER means reactive power moves in direction for absorption (underexcitation).
NOTE: Effective in both channels of a 2 channel configuration (AFT).
RAISE CMD which increases Q (VAR) set point. DEFAULT: connected to RAISE_Q_CTRL (6801).
NOTE: Effective in both channels of a 2 channel configuration (AFT).
LOWER CMD which decreases Q (VAR) set point. DEFAULT: connected to LOWER_Q_CTRL (6802).
NOTE: Effective in both channels of a 2 channel configuration (AFT).
Counter status of F.C.B. closing actions.
NOTE: counter is cleared if electronic power is OFF more than min. 8 hours (typically more than several days).
DEFAULT: not used.

HL
-

LL
-

DEF.
-

U
-

CLASS
DIAG, HID, SIP

SP
77

BO

DIAG, HID, SIP

77

BO

DIAG, HID, SIP

77

NUM

30000

DIAG

74

BO

DIAG

74

BO
BO

HID
DIAG

75
75

BO

AL, DIAG

75

CMPD FAILURE

Fault: If machine voltage doesnt return within time set by CMPD_MAX_TIME (307). DEFAULT: FAULT 27 Compounding BO
trip which trips the system.

AL, DIAG

75

10333

LOCAL PAN REF

Reference value from local operation panel UNS 0874 or CMT. Active on selected controller if in LOCAL mode.
NOTE: Refresh cycle is 1s.

0.01

15000

% DIAG

77

10334

PAN REF

0.01

15000

% DIAG

10335

RDY ON

BO

DIAG

74

10336

FCB ON

BO

DIAG

74

10337

FAULT

BO

AL, DIAG

123

10338

ALARM

BO

AL, DIAG

123

10339

LOCAL

Reference value (set point) from local operation panel UNS 0874 or CMT which is fed to the active controller AVR, MAN,
P.F or Q CTRL. Effective there at LOCAL CTRL and if channel is active only.
NOTE: Refresh cycle is 1s.
Status: neither TRIP_CMD (5322) connected to EXC_TRIP (10350) nor BLOCK_START_UP cmd (5301) connected to
INH_OF_START (10351) is active; ready to close field breaker. If EXC_ON, this status is TRUE independent from any
alarm. CMT status.
Status: Field breaker is ON (acknowledged); ready to start excitation. CMT status. DEFAULT: no programmable
connection.
Status: FAULT (CHANNEL FAULT or TRIP signal) from fault logger present. CMT status.
NOTE: ref. to CH_FAIL (10342) and CH_FAIL_LOGGED (10349).
DEFAULT: not used.
Status: ALARM from fault logger present. CMT status.
If an existing ALARM is followed by a new one, this output will be reset for 1s.
NOTE: The ALARM relay is only activated by the active channel. An ALARM of the standby channel is indicated via the
active channel alarm 119 Standby alarm.
DEFAULT: connected to 2nd channel and DOX18.[IN] (717), which activates ALARM relay.
Status: LOCAL control activated by panel or CMT. 1==LOCAL, 0==REMOTE.
DEFAULT: connected to DOX12.[IN] (711).

1000
0
1000
0
-

BO

DIAG, HID

74

Status: The thyristor firing pulses are blocked.


NOTE: Dont connect to input PULSE_BLK (5323), this causes a loop back.
Not applicable with this SW version 41.220.
SHUNT mode: Controls field flashing contactor if OFF LINE and machine voltage below FLASH_OFF_LEVEL (304).
NOTE: by the same output and external contactor, the battery compounding is controlled too while ON LINE and if
machine voltage drops below CMP_ON_LEVEL (306) (if set >0). The field flashing action is generated only once
per excitation start up sequence.
DEFAULT: connected to DOX15[IN] (714).
Fault: Field flashing was not successful within time set by FLASH_MAX_TIME (305). DEFAULT: FAULT 28 Field flash
fault which trips the system.

3BHS102402 E88

Rev. G

SC
BO

Parameter and Signal List Version 41.222_2


INDEX
10340

INDICATION
CH ON

10341

STBY ON

10342

CH FAIL

10343

XFER FAIL

10344

AFT CHANNEL 1

10345

LIM BLK

10346

STBY FAIL

10347

CH1 FAN RUN

10348

CH2 FAN RUN

10349

CH FAIL LOGGED

10350

EXC TRIP

10351

INH OF START

65

FUNCTION
SC
BO
Status: This physical channel is selected. Fix connected to ON_OFF logic, REF_MAX/MIN evaluation,
GATE_CONTROL and CH_COMMUNICATION blocks. For panel/CMT indication ref. to 10301.
CMT status.
NOTE: In a single channel system (SFE) this output is unconditionally forced to TRUE.
Status: This physical channel is not selected. Fix connected to CONVERTER and FOLLOW_UP_CTRL blocks. For
BO
panel/CMT indication ref. to 10301.
NOTE: In a single channel system (SFE) this output is unconditionally forced to FALSE.
BO
Common channel fault signal.
DEFAULT: Fix connected to DOX01 and DO01E for optional I/O extension. (hard wired channel O.K. signal drop if
CH_FAIL = TRUE). Channel fail relay (output 1) on UNS 0863 interface drops, if both CH_FAIL signals occur
in a 2 channel system, which then trips the field breaker. If I/O extension is used, then the channel fail relay on
2nd UNS 0863 can be used for 2nd trip coil. Check system with ref. to specific indicated FAULTS and
ALARMS in the provided physical channels according trouble shooting instructions.
NOTE:
This signal will not be TRUE if standby failed (STBY_FAIL (10346) = TRUE) before CH_FAIL, but will be
TRUE if ALARM 113 "2 channel comerror" occurred while STBY_ON.
Not used in a single channel system SFE.
Alarm: The status EXC_ON/OFF, AUTO/MAN, SUPERIMPOSED CTRL ON/OFF, CH_ON/STBY_ON of the 2 channels BO
are not conform with reference configuration CH_CONFIG.
DEFAULT: ALARM 107 CH transfer failed. Check system according trouble shooting instructions.
NOTE: With a single channel configuration this signal is always forced to FALSE.
Status: TRUE if this unit is physical channel 1 of a 2 channel system. It means that this unit serves as master for the serial BO
2-channel link (2nd RS 485). DEFAULT: not used.
NOTE: Use this signal to multiplex I/O channels, so that identical application SW can be used in both channels.
Status: TRUE if STBY_ON or MAN_ON. Used to block the limiter actions of non active system.
BO
DEFAULT: connected to BLK_LIMITER (7010).
BO
Common standby channel fault signal transmitted by serial or hard wired link. DEFAULT: ALARM 111 Common STBY
fault. Check specific indicated FAULTS of standby system according trouble shooting instructions.
NOTE: Use Panel communication to standby channel to read the fault logger there (done by connecting the Panel/CMT to
standby channel) and RESET pending FAULTS.
Control output for the channel 1 converter fan. Controls the fan of the active channel 1.
BO
NOTE: Connect this output to the same spare digital output number in both channels of a 2 channel system, since
common output relay is driven by both channel SW (fulfilled if downloading identical parameter sets).
Control output for the channel 2 converter fan. Controls the fan of the active channel 2.
BO
NOTE: Connect this output to the same spare digital output number in both channels of a 2 channel system, since
common output relay is driven by both channel SW (fulfilled if downloading identical parameter sets).
BO
Channel Fault output from fault logger. Includes all faults which lead to a channel fault.
DEFAULT: connected to IN_CH_FAIL (5317). Ref. to specific indicated FAULTS.
NOTE: SFE:
Not used. The signal is internally transferred to EXC_TRIP (10350) (TRIP LEVEL1)
AFT:
If standby channel already failed (STB_FAIL (10346) = TRUE), this signal
is internally transferred to EXC_TRIP (10350) (TRIP LEVEL1)
Excitation Trip output.
BO
Includes all faults which lead to a final excitation shut down (TRIP). Ref. to specific indicated FAULTS. DEFAULT:
connected to DOX02 (701) and TRIP_CMD (5322).
Collection of all ALARMS which normally are blocking start up (if connected to BLOCK_START_UP (5301) = DEFAULT). BO

3BHS102402 E88

Rev. G

HL
-

LL
-

DEF.
-

U
-

CLASS
DIAG

SP
76

DIAG

76

AL, DIAG

76

AL, DIAG

76

AL, DIAG

76

AVR, DIAG

76

AL, DIAG

76

DIAG, HID

76

DIAG, HID

76

AL, DIAG

123

AL, DIAG

123

AL, DIAG

123

Parameter and Signal List Version 41.222_2


INDEX
10352

INDICATION
OUT RESET

10353

REF ACT

10354

FLDB REF OK

66

FUNCTION
STATUS: Collection of all RESET activities: from local panel, fieldbus, standby channel or remote.
DEFAULT: not used.
Demultiplexed reference signal of the active controller AUTO (AVR), MANUAL, COS PHI (P.F.) or (VAR) CTRL.
DEFAULT: not used.
STATUS: Indicates to the fieldbus master, that received ref. signal IN_FLDB_REF (5334) from FB master is equal to the
internal REF_ACT (10353) signal. If not equal, the FB master must balance to REF_ACT (10353).

3BHS102402 E88

Rev. G

SC
BO

HL
-

LL
-

DEF.
-

0.01

30000

BO

3000
0
-

U
-

CLASS
AL, DIAG

SP
123

% DIAG, HID

78

77

AL, DIAG

Parameter and Signal List Version 41.222_2


4.4

CONVERTER CTRL

INDEX
10501

I EXC RELATIVE

INDICATION

10502

I EXC A

10503

U SYN RELATIVE

10504

U SYN V

10505
10506
10507
10508

U EXC RELATIVE
U EXC V
BRIDGE TEMP DEG
Udi0 V NOMINAL

10509

I CONV A RATED

10510
10511

I TRIP A LEVEL
U CONV V RATED

10512

MAX BR TEMP DEG

10513

CONV TYPE

10514

QUADR TYPE

67

Group 105

FUNCTION
Actual excitation current RELATIVE. DEFAULT: used for MANUAL CTRL, LIMITERS and MONITORING.
NOTE: In the standby channel of a 2 channel system this signal is read from the active channel.
Actual excitation current in AMPS. DEFAULT: used for panel and CMT only.
NOTE: refresh cycle is 1s. Signal forced to zero when gate pulses blocked (PULSE_BLOCKING (10328) = TRUE).
Actual converter input voltage RELATIVE. DEFAULT: used for field flashing and Monitoring
NOTE: Single phase operation of the converter (CONV_SUPPLY (515) set to 1_PH_CONV) causes sensing
error between 0 and -15% (depending on firing angle).
This signal will be forced to 100% in case of chopper converter UNS 4860 (type C5) because there is no
converter input sensing available.
Actual converter input voltage in VOLTS. DEFAULT: used for panel and CMT only.
NOTE: Single phase operation of the converter (CONV_SUPPLY (515) set to 1_PH_CONV) causes sensing
error between 0 to -15% (depending on firing angle).
This signal will be forced to 0V in case of chopper converter UNS 4860 (type C5) because there is no
converter input sensing available.
Actual excitation voltage RELATIVE. DEFAULT: used for Rotor Temperature measuring.
Actual excitation voltage in VOLTS, DEFAULT: used for panel and CMT only.
Actual converter heat sink temperature (air inlet temp. at type C4) used for Monitoring. Ref. to 10512 for more information.
Nominal voltage of full rectified supply voltage calculated by 1.35 * U_SYN_V_NOMINAL (504).
DEFAULT: not used.
Rated output current of the converter set by hardware coding or parameter SET_I_CONV_A (507).
The type code resistors, which define the rating plate value of C1, C2, C3, C5 types, are in use if parameter 507 is set to 0.
Instantaneous Exc. overcurrent trip level in AMPS, set by parameter I_EXC_MAX_LEVEL (506).
Rated input voltage of the converter set by hardware coding or parameter SET_U_CONV (508).
The type code resistors, which define the rating plate value of C1, C2, C3, C5 types, are in use if
parameter 508 is set to 0.
Converter overtemperature TRIP LEVEL set by parameter SET_MAX_BR_TEMP (509). The type code resistors, which
define the value of C1, C2, C3 types, are in use if parameter 509 is set to 0.
FAULT 04 Converter overtemp. is generated if set value is exceeded.
ALARM 105 Conv.overtemp.alarm is released 10K below the FAULT level.
NOTE: At C4 type, the air inlet temperature is monitored instead of the heat sink temp. Set the parameter value 10K
above the max. possible inlet air temp.
Converter type set by parameter SET_CONV_TYPE (510).
The type code resistors, which define the type of C1, C2, C3, C5 converters, are in use
if parameter 510 is set to 0.
1==C1, 2==C2, 3==C3, 4==C4, 5==C5 (Chopper)
NOTE: At C4 type, this parameter must be set to 4, because there are no type code resistors available.
Type of converter function (1==TWO QUADRANT, 4==FOUR QUADRANT)==rating plate value, if parameter 511 is set
to 0.
NOTE: with this SW version the value 4 must not be used!

3BHS102402 E88

Rev. G

SC
0.01

HL
-

LL
-

DEF.
-

U
%

CLASS
CON, SM, IMP

SP
73

0.1

CON, SM, IMP

73

0.01

CON, SM, HID

73

CON, SM, HID

73

0.01
1
1
1

%
V
C
V

CON, SM, IMP


CON, SM, IMP
CON, IMP
CON, HID

73
73
73
73

0.1

CON, HID

73

0.1
1

A
V

CON, HID
CON, HID

73
73

CON, HID

73

NUM

CON, HID

73

NUM

CON, HID

73

Parameter and Signal List Version 41.222_2


INDEX
10515

10516

INDICATION
BRANCH NO

FREEWHL CROWBAR

10517

P BLK INT

10518

REVERSED SEQ

10519

ALPHA ACT

10520

ON INVERTER CTRL

10521

U SYN FREQUENCY

4.5
INDEX
10601

68

FUNCTION
Status: Output of the CYCLE LOG. MEM. The RIPPLE MONITOR output will be logged by the CYCLE LOG. MEM. The
logger will be stopped at the occurrence of ALARM 124 "Converter failed" or CH FAULT 34 Converter fault depending on
the parameter RIPPLE_MON_MODE (521).
The value is set in case of detected branch faults as follows:
Value
0
1
2
3
4
5
6
Panel/CMT
NONE
W+
VU+
WV+
UNOTE: Only one branch fault can be logged. The status will be cleared at next excitation start only.
Freewheeling command during set time DLY_IE_MAX (513) + 83/100 ms (= 30*Tsyn) for the external freewheeling
thyristor(s) of the CROWBAR unit at a 2 channel (TWIN converter) application.
DEFAULT: not connected. Connect to spare digital output DOX17.[IN] (716) for freewheeling at 2 channel (TWIN
converter) application.
NOTE: Use exclusively DOX17 output since that one will be handled with priority (Tmed = 15 ms) if connected to 10516,
or use a fast output of extended I/O if available..
Blocks the thyristor firing (or turns IGBT off in case of chopper) instantaneously by the I_EXC_MAX_LEVEL (506) trigger
prior to CH FAULT 2 inst. exc. overcurrent. In parallel the output FREEWHL_CROWBAR (10516) is TRUE during
DLY_IE_MAX (513) + 30*Tsyn.
DEFAULT: internally connected to P_BLK_INT input of EXCITATION-ON/OFF-CTRL Logic.
Status: If TRUE, converter input phase sequence has been reversed by parameter PHASE_SEQ_CW (503) or by input
SEL_SEQUENCE (5501) to R-T-S.
DEFAULT: not used.
Actual firing angle value. (Value in degree). Type C5: 0 = 100% duty in Q1, 90 = 0% duty in Q1, 180 = 100% duty in Q4
, ALPHA = f(UCTRL) = linear. DEFAULT: not connected.

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
CON, DIAG

SP
73

BO

CM, CON,
DIAG

73

BO

CON, DIAG

73

BO

CON, DIAG

73

el.

CON, IMP

47

Status: Firing pulses are forced to inverter position (ALPHA MAX LIM) via input INV_CTRL (5503) or while excitation is in
OFF state. Type C5: Thyristor MIN. duty cycle in Q4.
Actual frequency of the converter supply voltage of types C1...C4.
DEFAULT: internally used in firing unit only.

BO

CON, DIAG

47

CON, HID

73

SP
130

BO

SC
NUM

HL
-

DATA LOGGER Group 106


INDICATION
DLOG STATUS

FUNCTION
Status of Data Logger:
0
logger is empty.
1
logger is collecting data.
2
a trigger has occurred.
3
logger has stopped after a trigger.
4
logger has stopped after a stop command.
5
logger has stopped after a trigger and a stop command.

3BHS102402 E88

Rev. G

LL
-

DEF.
-

CLASS
DIAG, HID

Parameter and Signal List Version 41.222_2


4.6

69

BASIC DIGITAL I/O GROUP 107

INDEX
10701

DIX01

INDICATION

FUNCTION
DEFAULT: connected to START_EXCITATION (5302). Excitation ON (START) command closes field breaker if not
already closed and then starts excitation if all preconditions are fulfilled.

SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
IO

SP
26

10702

DIX02

DEFAULT: connected to EXC_OFF_CMD (5303). Fast input DI4 for Excitation OFF (STOP) command. Stops excitation
by inverter mode and opens the field breaker as well, if RELEASE_FCB_OFF (301) is set to YES. After 60s inverter mode
the firing pulses are blocked too.
NOTE:
At the configuration with field C.B. on converter input (parameter CB_CONFIG (309) = 0==AC SIDE) and
parameter RELEASE_FCB_OFF (301) set to 0==NO, this input must only be used for the external F.C.B.
TRIP command and must therefore be connected to input OFF_BLK_CMD (5335). For the normal EXC_OFF
CMD input (5303) a spare digital input must be used.
DEFAULT: connected to RAISE_CMD (5304), which is operating the active controller AUTO (AVR), MANUAL CTRL,
COS PHI (P.F.) CTRL or Q (VAR) CTRL.

BO

IO

65

10703

DIX03

BO

IO

28

10704

DIX04

DEFAULT: connected to LOWER_CMD (5305), which is operating the active controller AUTO (AVR), MANUAL CTRL,
COS PHI (P.F.) CTRL or Q (VAR) CTRL.

BO

IO

29

10705
10706

DIX05
DIX06

BO
BO

IO
IO

30
31

10707

DIX07

DEFAULT: connected to ON_AUTO_CMD (5306). Selects AUTO (AVR) mode if no AUTO_FAIL (5317) signal present.
DEFAULT: connected to ON_MAN_CMD (5307). Selects MANUAL CTRL mode (field current regulator) if no MAN_FAIL
(5318) signal present.
DEFAULT: connected to ON_IMP_CMD (5310). Activates selected imposed controller if ON_LINE and in AUTO mode.
This input can be used for other application if IMPOSED_CTRL_MODE (302) is set to NO.

BO

IO

32

10708

DIX08

DEFAULT: connected to OFF_IMP_CMD (5311). Stops selected imposed controller. This input can be used for other
application if IMPOSED_CTRL_MODE (302) is set to NO.

BO

IO

33

10709
10710
10711
10712
10713
10714
10715

DIX09
DIX10
DIX11
DIX12
DIX13
DIX14
DIX15

DEFAULT: not used. Spare digital input for application.


DEFAULT: not used. Spare digital input for application.
DEFAULT: not used. Spare digital input for application.
DEFAULT: not used. Spare digital input for application.
DEFAULT: not used. Spare digital input for application.
DEFAULT: connected to NO_EXT_ALARM (5904) input. Ref. to 5904 for more information.
DEFAULT: connected to ON_LINE (5314). ON_LINE signal (machine connected to grid). Internally used for different
processing. Ref. to 5314 at motor application.

BO
BO
BO
BO
BO
BO
BO

IO
IO
IO
IO
IO
IO
IO

34
35
36
37
38
39
40

10716
10717

DIX16
FAIL FREQ A/B

BO
BO

IO
IO, HID

70
64

10718

DIODE ALARM

BO

AL, DIAG

27

10719

DIODE TRIP

BO

AL, DIAG

66

10720

FAIL 2ND CHANNEL

F.C.B. acknowledge input. TRUE if field breaker closed. Internally connected to CONTROL LOGIC group 3.
Input from UNS 1860. TRUE if frequency x-ducer fault detected. Sets F_MACH_RELATIVE (10122) = 0 during STOP
sequence until firing pulses will be blocked. Sets U_MACH_V (10102) = 0 too. Generates ALARM 121 f sensing failed if
ON_LINE and U_MACH_REL >30%.
Input from UNS 0864. TRUE if rotating rectifier bridge arm interrupt detected. This output is internally connected to
MONITORING group 9. Generates ALARM 115 Rot. rectifier OC after DLY_DIODE_ALARM (906).
Input from UNS 0864. TRUE if rotating rectifier bridge arm short circuit detected. This output is internally connected to
MONITORING group 9. Generates FAULT 39 Rot. rectifier SC. Delay is set on UNS 0864 hardware.
Input from UNS 0863. TRUE if second channel failed (or permanent TRUE at single channel system).
This input is internally connected to STBY_FAIL_HW of the TRANSFER CTRL of group 3.

BO

AL, DIAG

67

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


INDEX
10721

10722

4.7

INDICATION
FAIL DIG OUT

FAIL AC/DC SUPPLY

FUNCTION
Input from UNS 1860. TRUE when relay driver failure detected. Sets all digital outputs to "0", causing all interface output
relays to drop and disconnects all digital inputs with UNS 1860a HW (with UNS 1860b and later HW, the inputs are not
longer influenced by this failure).
CHANNEL_OK Relay 1, driven by DOX01 of both channels, trips the field breaker at single channel, or forces channel
changeover at 2 channel application when dropping.
Generates channel fault 32 D/O driver fault.
Input from UNS 1860. Either AC or DC electronic supply input to POW-1 is missing. This output internally is connected to
MONITORING group 9.
UNS 1860b:
DC input missing: output continuously TRUE. Generates ALARM 144 "Batt. fail".
AC input missing: output toggles by 1 Hz. Generates ALARM 141 "Aux. AC fail".
Ref. to 10902 and 10903 for more informations.

DIGITAL I/O EXT.

INDEX
10801

DI01E

INDICATION

10802

DI02E

10803

DI03E

10804

DI04E

10805

DI05E

10806

DI06E

10807

DI07E

10808

DI08E

10809

DI09E

10810

DI10E

10811

DI11E

10812

DI12E

70
SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
AL, DIAG

SP
68

BO

AL, DIAG

69

SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB, I/O

SP
87

BO

AFB, I/O

88

BO

AFB, I/O

89

BO

AFB, I/O

90

BO

AFB, I/O

91

BO

AFB, I/O

92

BO

AFB, I/O

93

BO

AFB, I/O

94

BO

AFB, I/O

95

BO

AFB, I/O

96

BO

AFB, I/O

97

BO

AFB, I/O

98

Group 108

FUNCTION
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


INDEX
10813

DI13E

10814

DI14E

10815

DI15E

10816

DI16E

10817

FAIL DIG OUT EXTD

4.8

INDICATION

MONITORING

INDEX
10901

INDICATION
TEST SUPPLY

10902

AUX AC FAIL

10903

BATT FAIL

10904

PWR 24V FAIL

10905

OC1 EXC CURR

10906

OC2 EXC CURR

71

FUNCTION
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
DEFAULT: not used. Spare digital input for application.
NOTE: Only available with optional I/O extension board UNS 0867 and 2nd I/O board UNS 0863.
Input from UNS 0867. TRUE when relay driver failure detected.
Sets all digital outputs to "0", causing all interface output relays to drop.
CHANNEL_OK Relay 1 on 2nd UNS 0863, driven by DO01E of both channels, can be used for 2nd field breaker trip coil.
(Ref. also to FAIL_DIG_OUT (10721)). Generates channel fault 32 D/O driver fault.

SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB, I/O

SP
99

BO

AFB, I/O

100

BO

AFB, I/O

101

BO

AFB, I/O

102

BO

AL, DIAG

124

SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
AL, DIAG

SP
80

BO

AL, DIAG

80

BO

AL, DIAG

80

BO

AL, DIAG

80

BO

AL, DIAG

80

BO

AL, DIAG

80

Group 109
FUNCTION
Alarm: TEST_SUPPLY of converter was detected during stand still or excitation start up.
DEFAULT: connected to SEL_PRESET2_MAN (7106) and ALARM 145 Test supply.
Restore normal shunt supply for further operation.
NOTE: Only available with shunt supply with type C1...C4 and C7. This is an ALARM which does not block excitation
start.
Alarm: Missing AC input to power supply unit UNS 0861 or UNS 0868. DEFAULT: ALARM 141 Aux AC fail.
Check, restore AC supply circuits.
NOTE: This alarm works only while converter supply voltage >50%, and at type C5 (chopper) only 10s after excitation is
switched on. With UNS0861 power pack (Parameter 919==0) also 24_PWR_FAIL (10904) must be TRUE.
Ref. to param. PWR_PACK/I-O HW (919).
Alarm: Missing battery back up supply to power supply unit UNS 0861 or UNS 0868. DEFAULT: ALARM 144 Batt fail.
Check, restore battery supply circuits.
NOTE: With UNS0861 power pack (Parameter 919 = 0): This alarm works only while converter supply voltage >50%,
24_PWR_FAIL (10904) = TRUE and at type C5 (chopper) only 10s after excitation is switched on. Ref. to
param. PWR_PACK/I-O HW (919).
Alarm: 24 VDC output of power supply unit UNS 0861 or UNS 0868 is missing or FCB was switched off by external
command or by hand. DEFAULT: ALARM 143 PWR FCB off/24V fail. Check FCB status or 24V supply unit
UNS 0861 or UNS 0868.
NOTE: This alarm works only while converter supply voltage >50% or type C5 and excitation ON.
With a 2 channel system, the 24 VDC outputs of both power supply units UNS 0861 or 0868 are missing.
Alarm: Overexcitation ALARM. The excitation current limiter was not successful. Ref. to 902 and 903. DEFAULT: ALARM
106 OC1 exc curr and AVR_FAULT which forces transfer to MAN_CTRL (group 3). Check system according
maintenance and trouble shooting instructions.
Fault: Overexcitation TRIP. The transfer to MAN_CTRL, forced by (10905) was not successful within 3s. DEFAULT:
FAULT 3 Dlyd.exc.overcurrent which trips the system.
Check system according maintenance and trouble shooting instructions.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


INDEX
10907

INDICATION
UE1 FAULT

10908

U MACH FAIL

10909

USYN FAIL

10910

AVR FAULT

10911

BR INTRPT ROT REC

10912

f MACH FAIL

10913

UE2 FAULT

10914

SYN2 FAULT

10915
10916
10917
10918
10919
10920

LOSS EXC
BOOST EXC
B/L FAULT
MAN FAULT
EXC SENSE FAIL
V/HZ FAULT

10921

U MACH FAIL DYN

10922

COMM FAULT

72

FUNCTION
Channel fault: Loss of excitation step 1. UE limiter -Q(P) was not successful. Ref. to 904 and 905. DEFAULT: FAULT 14
Loss of exc CHANNEL which forces transfer to 2nd CHANNEL at 2 channel system or trips a single channel system.
Check system according maintenance and trouble shooting instructions.
Alarm: Machine P.T. signal is missing. Ref. to 907 or 914...916.
DEFAULT: ALARM 120 Machine P.T. fail which forces transfer to MAN_CTRL (group 3).
Check system according maintenance and trouble shooting instructions.
Channel fault: Converter power supply is missing at thyristor type C1...C4 and 3 PH shunt supply. Ref. to 907.
DEFAULT: CH FAULT 23 Loss conv. supply which forces transfer to 2nd CHANNEL at 2 channel system or trips a
single channel system.
Check system according maintenance and trouble shooting instructions.
Status: AVR failure detected: These are U_MACH_FAIL (10908) or OC1_EXC_CURR (10905).
DEFAULT: connected to AUTO_FAIL (5317). Ref. to relevant signals for trouble shooting.
Alarm: Rotating rectifier bridge arm interrupt was detected longer than set delay 906.
DEFAULT: ALARM 115 Rot. rectifier OC. Check system according maintenance and trouble shooting instructions.
Alarm: Frequency sensing disturbed, although U_MACH_REL is bigger than 30% and machine ON LINE. DEFAULT:
ALARM 121 f sensing failed. Check system according maintenance and trouble shooting instructions.
Channel fault: Loss of excitation step 2. The transfer to STBY_CH, forced by (10907) was not successful within 2s.
DEFAULT: FAULT 5 Loss of exc trip which trips the system.
Check system according maintenance and trouble shooting instructions.
Channel fault: "Not in synchronism" detected at U_SYN_V >10V. Gate control synchronization is missing => HW failure
expected. DEFAULT: FAULT 31 Not in synchronism which forces transfer to 2nd CHANNEL at 2 channel system or
trips a single channel system. Check system according maintenance and trouble shooting instructions.
Not applicable for this SW release 41.220
Not applicable for this SW release 41.220
Not applicable for this SW release 41.220
Not applicable for this SW release 41.220
Not applicable for this SW release 41.220
Fault: Overfluxing TRIP. The V/Hz limiter was not successful within set DLY_V/HZ_MON (913). DEFAULT: FAULT 46
V/Hz fault. Check system according maintenance instructions.

SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
AL, DIAG

SP
80

BO

AL, DIAG

81

BO

AL, DIAG

81

BO

AL, DIAG

81

BO

AL, DIAG

80

BO

AL, DIAG

80

BO

AL, DIAG

80

BO

AL, DIAG

80

BO
BO
BO
BO
BO
BO

AL, DIAG
AL, DIAG
AL, DIAG
AL, DIAG
AL, DIAG
AL, DIAG

80

Output of the dynamic P.T. monitor. Mainly used for tuning of the monitor in TEST position selected by parameter
SEL_PT_FAIL_DYN (914) (ref. to 915 and 916). DEFAULT: not used.
Communication to fieldbus master is disturbed. Depending on FLDBFAULT_MODE (917) either an EVENT, ALARM,
CHANNEL FAULT or EXCITATION TRIP is generated after the set FLDBFAULT_TIMEOUT (918).
DEFAULT: not used.

BO

AL, DIAG

81

BO

DIAG

81

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


4.9

RT MONITORING

INDEX
11001

INDICATION
RF RELATIVE

11002

RTEMP DEG

11003

HS RTEMP DEG

11004

RTEMP ALARM

11005

RTEMP FAULT

11006

dIE/dt

4.10

FAULT WORD 1

INDICATION

11102

FAULT WORD 2

11103
11104

FAULT WORD 3
ALARM WORD 1

11105

ALARM WORD 2

11106

ALARM WORD 3

11107
11108
11109

LATEST FAULT
LATEST ALARM
OPERATING HOURS

Group 110

FUNCTION
Calculated field winding resistance RELATIVE:
RF_RELATIVE [%] = RE_TOT_RELATIVE * [U_EXC_RELATIVE - U_BRUSH_RELATIVE (U_DROP_RELATIVE * IE [p.u.])] /100
DEFAULT: not used
Calculated field winding temperature in DEG CENTIGRADE:
RTEMP_DEG = RTEMP_DEG_NOM * (RF_RELATIVE - RF0_RELATIVE) / (100% - RF0_RELATIVE)
DEFAULT: not used
Calculated hot spot field winding temperature in DEG CENTIGRADE:
HS_RTEMP_DEG = RTEMP_DEG + ((HOT_SPOT_CONST/100) * IE^2[p.u])
DEFAULT: not used
Alarm: Measured rotor temp. is above set RTEMP_DEG_ALARM (1009) value.
DEFAULT: ALARM 104 Rotor temp. Alarm.
Check system according maintenance instructions.
FAULT: Measured rotor temp. is above set RTEMP_DEG_FAULT (1010) value.
DEFAULT: FAULT 7 Rotor overtemp.trip.
Check system according maintenance instructions.
Output of excitation current transitions:
dIE/dt = I_EXC_RELATIVE - [I_EXC_RELATIVE / (1+ pTC_SEL)]
NOTE: TC_SEL = TC_OFF_LINE (1004) if OFF_LINE or TC_ON_LINE (1005) if ON_LINE
DEFAULT: not used.

FAULTS, ALARMS

INDEX
11101

73

SC
0.01

HL
-

LL
-

DEF.
-

U
%

CLASS
SM, HID

SP
121

IO, SM, HID

121

SM, HID

121

BO

AL, DIAG

121

BO

AL, DIAG

121

0.01

SM, HID

121

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AL, HID

SP
123

AL, HID

123

AL, HID
AL, HID

123

AL, HID

123

AL, HID

123

AL
AL

123
123

Group 111

FUNCTION
Signal from fault handler. Each bit represents one fault status, active fault sets bit to one.
For bit allocation see SW diagram and maintenance and trouble shooting instructions.
Signal from fault handler. Each bit represents one fault status, active fault sets bit to one.
For bit allocation see SW diagram and maintenance and trouble shooting instructions.
Not used in this firmware release 41.220.
Signal from alarm handler. Each bit represents one alarm status, active alarm sets bit to one.
For bit allocation see SW diagram and maintenance and trouble shooting instructions.
Signal from alarm handler. Each bit represents one alarm status, active alarm sets bit to one.
For bit allocation see SW diagram and maintenance and trouble shooting instructions.
Signal from alarm handler. Each bit represents one alarm status, active alarm sets bit to one.
(not used in this firmware release 41.220).
Error code of the latest fault.
Error code of the latest alarm.
Operating hours in 0,1 h resolution. Counter is reset if auxiliary power of CON board is switched off for more than 8 hours
(typical 24...96 hours).
NOTE:
This signal will not be indicated at CMT ParSig menu. It must be allocated to the object push button in the
Trending menu.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


4.11
INDEX
11201

11202

74

MAINTENANCE Group 112


INDICATION
BACKUPSTOREMODE

BC

FUNCTION
Parameter handling function (overwriteable signal). Used to give commands to the parameter handling function in the
system:
0== NONE (DEFAULT after writing or reading of parameters to or from FPROM).
1== SAVE PARAM SET1 (Copies the RAM values as SET1 to FPROM. Normally only this parameter set is
used).
2== SAVE PARAM SET2 (Copies the RAM values as SET2 to FPROM. 2nd parameter can be activated by
function no. 5 below or via input 5326 by an external order).
CAUTION: the following operations should only be done at open field breaker, otherwise the alarm 134
Backup not allowed will be generated, which only can be reset by power OFF.
3== FACTORY SET VALUE (CAUTION: DEFAULT values are restored to RAM.).
4== SELECT PARAM SET1 (The SET1 is read from FPROM to RAM and becomes active).
5== SELECT PARAM SET2 (CAUTION: The SET2 is read from FPROM to RAM and becomes active. Same
as by external order via input 5326).
6== READ APPL BLOCKS (the order of AFB's is read from FPROM to RAM. They become active at first with
2504==1).
While the command is executing, the value of BACKUPSTOREMODE will show what is happening or the reason if the
command fails:
7== ERASE ERROR (FPROM can not be erased -> exchange CON-2 board).
8== ERASING (indicating FPROM erasing).
9== PROGRAM ERROR => Alarm 136 Write backup alarm.
10== PROGRAMMING (indicating FPROM programming).
11== ID ERROR
12== READING (indicating FPROM values are transferred to RAM).
13== READ ERROR => Alarm 134 Backup not allowed (FPROM can not be read -> exchange CON-2 board).
14== reserved
15== VERS ERROR (RAM and FPROM parameter versions are not equal).
16== reserved
17== SIZE ERROR
Status of the gate control unit:
If one or more bits are set, gate control is forced to inverter operation (max. firing angle).
B0==overcurrent == FAULT 02: Inst.exc.overcurrent
B1==inverter control by control logic==EXC_OFF (10308) or [INV_CTRL](5503).
B2==not used
B3==not used
B4==not used
B5==not used
B6==converter supply overvoltage == FAULT 30: Conv. overvoltage
B7==not used
B8==not used
B9==not used
B10==not used
B11==not used
B12==power failure on internal power supply POW-1==FAULT 01: Auxil. undervoltage

3BHS102402 E88

Rev. G

SC
ENUM

HL
-

LL
-

DEF.
-

U
-

CLASS
CM, IMP

DIAG, HID

SP

Parameter and Signal List Version 41.222_2


INDEX

INDICATION

11203

SQUARE WAVE

11204
11205
11206

CMT COM ERRORS


not used
CNT SW VERSION

11207

CNT BOOT SW VER.

11208
11209

SW SUBSTATUS
PROGRAM LOAD

11210
11211
11212
11213
11214
11215

ADDR 1 VAL DEBUG


ADDR 2 VAL DEBUG
ADDR 3 VAL DEBUG
ADDR 4 VAL DEBUG
ADDR 5 VAL DEBUG
ADDR 6 VAL DEBUG

75

FUNCTION
B13==synchronizing signal missing ==FAULT 31: Not in synchronism if Usyn > 10V eff.
B14==pulse firing section not in synchronism ==FAULT 31: Not in synchronism if Usyn > 10V eff.
B15==not released == any alarm present
Output of square wave generator used for commissioning. For the parameters see 1204...1206. Normally used for manual
tuning PI(D) controllers.
Number of transmission errors in CMT communication link.
Not used.
UNITROL F software revision 41...
The first two characters (41) indicating software from UNITROL-F family.
UNITROL F bootstrap software revision.
NOTE: Substatus are released after any bugfixes of the firmware. They have no influence to the parameter structure and
application program. An up-date of the firmware can just be done by downloading the new xxxxx.rom file to the
target by donwload.bat file. The existing parameter settings and application FBs are not influenced an will be valid
again after power up.
Indicates SW revision status 0, 1, 2...etc. within release 41.xxx
Calculated load of UNITROL-F control program. Calculation is started by setting TEST MODE (1201) = PROGRAM
LOAD (2). The calculation will take about 20 s.
Content of the memory address selected by DEBUG_ADDR_1 (1207).
Content of the memory address selected by DEBUG_ADDR_2 (1208).
Content of the memory address selected by DEBUG_ADDR_3 (1209).
Content of the memory address selected by DEBUG_ADDR_4 (1210).
Content of the memory address selected by DEBUG_ADDR_5 (1211).
Content of the memory address selected by DEBUG_ADDR_6 (1212).

3BHS102402 E88

Rev. G

SC

HL

LL

DEF.

CLASS

SP

TUN

1
1
-

DIAG, HID
DIAG, HID
HID

HID

BO
0.01

HID
DIAG, HID

1
1
1
1
1
1

d
d
d
d
d
d

DIAG
DIAG
DIAG
DIAG
DIAG
DIAG

Parameter and Signal List Version 41.222_2


4.12
INDEX
11301
11302
11303

4.13

IE LIMITER
INDICATION
OUT IE LIMITER
START IE LIMITER
REF IE LIM ACT

Group 113
FUNCTION
Excitation current limiter output. DEFAULT: connected to IN_IELIM_ERR_A (7004).
Status: Excitation current I_EXC_RELATIVE (10501) > selected REF1, 2_IETH). DEFAULT: not used.
Actual reference value to summing point. This signal is used for IE_MONITORING (over excitation protection) in group 9.

SC
0.01
BO
0.01

HL
30000
30000

LL
-30000
-30000

DEF.
-

U
%
%

CLASS
HID, AVR
DIAG, HID
HID, AVR

SP
55
55
55

SC
0.01

HL
30000

LL
-30000

DEF.
-

U
%

CLASS
HID, AVR

SP
63

0.01

30000

-30000

HID, AVR

63

BO
0.01
BO

%
-

DIAG, HID
HID, AVR
DIAG, HID

56
56
63

FUNCTION
UE Q(P) limiter output. DEFAULT: connected to IN_Q(P)_LIM_ERR (7007).

SC
0.01

HL
-

LL
-

DEF.
-

U
%

CLASS
HID, AVR

SP
61

IE_MIN limiter output. DEFAULT: not used.


NOTE: It is not required using this limiter to hold a minimum converter (thyristor hold) current, because the gate pulse
train always ensures converter starting. Ref. to 7009 for limiter using.
Actual reference value to summing point. This signal is used for UE_MONITORING (loss of excitation protection) in
group 9.

0.01

HID, AVR

62

HID, AVR

61

I LIMITER Group 114

INDEX
11401

OUT I OE LIMITER

11402

OUT I UE LIMITER

11403
11404
11405

START IOE LIM


REF I LIM ACT
ON Q0 CTRL

4.14

76

INDICATION

PQ IEMIN LIM

INDEX
11501

OUT Q(P) LI

INDICATION

11502

OUT IEMIN LIM

11503

REF Q(P) ACT

FUNCTION
OE (lag) stator current limiter output. DEFAULT: not used.
Connect to IN_IOEL_ERR_A (7005) if limiter required. NOTE: Ref. to 7005 prior to this action.
UE (lead) stator current limiter output. DEFAULT: not used.
Connect to IN_IUEL_ERR_A (7008) if limiter required. NOTE: Ref. to 7008 prior to this action.
Status: Stator current I_MACH_RELATIVE (10103) > selected REF1/2_I_MACH_TH). DEFAULT: not used.
Active reference value to summing point. DEFAULT: not used.
Status unity P.F. (Q=0) instead of limited stator current: If the I limiter tries to reduce reactive current below 2%, i.e. stator
current can be limited by excitation system because of to much ACTUAL power which cant be transmitted within stator
current limits, then the power factor is kept to unity (Q=0) regardless of stator current level.

Group 115

3BHS102402 E88

Rev. G

0.01

Parameter and Signal List Version 41.222_2


4.15

COSPHI CTRL Group 117

INDEX
11701

INDICATION
REF HL COSPHI

11702

REF LL COSPHI

11703

PRST C ON COSPHI

11704

REF COSPHI ACT

11705

REF TANPHI ACT

11706
11707

ERR COSPHI
REF ISINPHI ACT

11708

77

ERR SUPERIMPOSED

11709

REF COSPHI AO

11710

IMP REF

FUNCTION
Status: Output REF_COSPHI_AO (11709) and REF_COSPHI_ACT (11704) at max. limit. Internally connected to
REF_MAX/MIN multiplexer (group 3) which generates REF_MAX_ACTIVE (10312) at COSPHI mode. For panel/CMT
indication ref. to 10301.
Status: Output REF_COSPHI_AO (11709) and REF_COSPHI_ACT (11704) at min. limit. Internally connected to
REF_MAX/MIN multiplexer (group 3) which generates REF_MIN_ACTIVE (10313) at COSPHI mode. For panel/CMT
indication ref. to 10301.
Status: Acknowledge signal REF_COSPHI_AO (11709) = PRESET_REF_COSPHI (1705) if TRIG_PRESET_COS
(6704) is TRUE. DEFAULT: not used. Consider the COSPHI setpoint characteristic of REF_COSPHI_AO (11709)
Actual COSPHI reference value. The sign indicating whether it is in the overexcited (no sign) or underexcited (- sign)
section of the machine:
+/-10000==COSPHI 1, -3000==COSPHI 0.3 underexcited, 3000==COSPHI 0.3 overexcited.
DEFAULT: internally used only for panel/CMT indication
COSPHI reference transformed to TANPHI reference, which is the reference for the required reactive current I_SINPHI.
This ensures stable COSPHI control even at zero active power. DEFAULT: Internally used only.
COSPHI controller error output. DEFAULT: internally used only.
REF_TANPHI_ACT (11705) multiplied with actual active current ICOSPHI_IN (6708) to get the reference signal
REF_ISINPHI_ACT for the required reactive current I_SINPHI. This ensures stable COSPHI control even at zero active
power. DEFAULT: Internally used only.
Selected superimposed controller error output: either ERR_COSPHI (11706) or ERR_Q_CTRL (11804). DEFAULT:
Internally connected to ERR_IMPOSED_AVR (6904).
Analog output signal for COSPHI ref. indication via analog output:
-10000...0...10000 == COSPHI 0 underexcited...1...0 overexcited. The signal is limited by HL/LL_REF_COSPHI (1703/04)
DEFAULT: Internally used only.
E.g. to be connected to an instrument which indicates +/- 10V having a linear P.F. scale 0 lead...1...0 lag. Ref. to used
analog output parameters for other indication range.
Reference signal of the selected imposed controller. Either REF_COSPHI_AO (11709) if COSPHI CTRL selected or
REF_Q_ACTUAL (11805) if Q CTRL selected. DEFAULT: Internally fed to standby channel IMP_REF_STBY input.
Standby imposed controller follow up CTRL.

3BHS102402 E88

Rev. G

SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
DIAG, HID

SP
58

BO

DIAG, HID

58

BO

DIAG, HID

58

3000

-3000

HID, SIP

58

3000

-3000

HID, SIP

58

1
1

30000
30000

-30000
-30000

HID, SIP
HID, SIP

58
58

30000

-30000

HID, SIP

58

30000

-30000

HID, SIP

58

HID, SIP

58

Parameter and Signal List Version 41.222_2


4.16

78

Q CTRL Group 118

INDEX
11801

INDICATION
REF HL Q CTRL

11802

REF LL Q CTRL

11803

PRST Q ON

11804

ERR Q CTRL

11805

REF Q ACTUAL

FUNCTION
Status: Output REF_Q_ACTUAL (11805) is at max. limit. Internally connected to REF_MAX/MIN multiplexer (group 3)
which generates REF_MAX_ACTIVE (10312) at Q_CTRL mode. For panel/CMT indication ref. to 10301.
Status: Output REF_Q_ACTUAL (11805) is at min. limit. Internally connected to REF_MAX/MIN multiplexer (group 3)
which generates REF_MIN_ACTIVE (10313) at Q_CTRL mode. For panel/CMT indication ref. to 10301.
Status: Acknowledge signal REF_Q_ACTUAL (11805) = PRESET_REF_Q_CTRL (1805) if TRIG_PRESET_Q (6804) is
TRUE. DEFAULT: not used.
Q controller error output. DEFAULT: Internally connected to COSPHI_CTRL where the selection is made between
Q_CTRL and COSPHI_CTRL.
Actual Q controller reference value: -100%...0...+100% == 1p.u. underexcited ...0...1p.u. overexcited reactive power. The
signal is limited by HL/LL_REF_Q_CTRL (1803/04). DEFAULT: Internally used only. E.g. to be connected to an
instrument which indicates +/- 10V having a Q scale 0 lead...1...0 lag.
Ref. to used analog output parameters for other indication range.

3BHS102402 E88

Rev. G

SC
BO

HL
-

LL
-

DEF. U
-

CLASS
DIAG, HID

SP
57

BO

DIAG, HID

57

BO

DIAG, HID

57

0.01

30000

-30000

% HID, SIP

57

0.01

30000

-30000

% HID, SIP

57

Parameter and Signal List Version 41.222_2


4.17

AVR CTRL

INDEX
11901

REF1 AVR REL

INDICATION

11902

REF HL AVR

11903

REF LL AVR

11904

PRSTA1 ON AVR

11905

PRSTA2 ON AVR

11906

REF4 AVR REL

11907

ON V/Hz LIMITER

11908
11909

ON SOFTSTART
OUT PID AVR

11910
11911

SEL TB PID AVR


SEL TA PID AVR

79

Group 119
FUNCTION
AVR setpoint from setpoint generator (softpot). The signal is limited by HL_/ LL_REF_AVR (1901/02). Consider the
additional setpoint influences Q, P_DROOP/COMPENS (1909/10), ADD_IN_REF1_A (6908), ADD_INPUT_AVR (7002)
which influence the active ref. signal at the AVR summing point too.
Internally connected to AVR_REF_INFLUENCE block group 19.
Status: Output REF1_AVR_REL (11901) at max. HL_REF_AVR (1901). Internally connected to REF_MAX/MIN
multiplexer (group 3) which generates REF_MAX_ACTIVE (10312) in AUTO mode.
For panel/CMT indication ref. to 10301.
Status: Output REF1_AVR_REL (11901) at min. LL_REF_AVR (1902). Internally connected to REF_MAX/MIN
multiplexer (group 3) which generates REF_MIN_ACTIVE (10313) in AUTO mode.
For panel/CMT indication ref. to 10301.
Status: Acknowledge signal REF1_AVR_REL = PRESET1 REF AVR (1903) if TRIG PRST AVR (6907) is TRUE and
SEL_PRESET2_AVR (6906) is FALSE. DEFAULT: not used.
Status: Acknowledge signal REF1_AVR_REL = PRESET2 REF AVR (1904) if TRIG PRST AVR (6907) and
SEL_PRESET2_AVR (6906) are TRUE. DEFAULT: not used.
Finally processed AVR ref. signal after V/Hz limiter and softstart integrator.
DEFAULT: connected to REF_INPUT_AVR (7001).
Status: V/Hz limiter is active.
DEFAULT: internally used to drive signal ON_OE_LIMITER (12002) if channel and excitation are ON.
Status: SOFTSTART is running. Internally used to inhibit auto follower action and limiter activities during start up.
AVR PID controller output. Internally connected to AUTO-MAN selector in the FOLLOW_UP_CTRL (group 21). This
signal is internally limited to +/- 10000.
Output representing the active differentiation time constant TB1, TB2, TB3. DEFAULT: not used.
Output representing the active integration time constant TA1, TA2, TA3. DEFAULT: not used.

3BHS102402 E88

Rev. G

SC
0.01

HL
30000

LL
-30000

DEF. U
-

CLASS
HID, AVR

SP
43

BO

AVR, DIAG

43

BO

AVR, DIAG

43

BO

AVR, DIAG

43

BO

AVR, DIAG

43

0.01

30000

-30000

HID, AVR

44

BO

DIAG, HID

44

BO
0.01

10000

-10000

DIAG, HID
AVR, HID

44
42

0.001
0.01

30000
30000

-30000
-30000

ms
s

AVR, HID
AVR, HID

42
42

Parameter and Signal List Version 41.222_2


4.18

AVR IN, PSS

INDEX
12001

ERR1 AVR

INDICATION

12002

ON OE LIMITER

12003

ON UE LIMITER

12004

ON IE LIMITER

12005

ON IOE LIMITER

12006
12007

ON OE USER LIM
ON Q(P) LIMITER

12008

ON IUE LIMITER

12009

ON IEMIN LIMITER

12010

PSS OUT

12011

ON PSS

12012

PSS FAILURE

12013
12014

not used
DELTA fEP

12015

OUT P EL

12016

OUT P MECH

12017

OUT P ACCEL

80

Group 120
FUNCTION
Finally processed (AVR) PID controller error signal after Limiters interference.
DEFAULT: connected to IN_AVR_ERR (6917).
Status: One of the AVR OE Limiters or the MAN_CTRL_OE restrict V_HZ_MANUAL_ON (12108) is active. DEFAULT:
connected to digital output DOX10.[IN] (709). For panel/CMT indication ref. to 10301.
Status: One of the AVR UE Limiters or the MAN_CTRL_UE restrict UEL_ON_MAN (12106) is active. DEFAULT:
connected to digital output DOX11.[IN] (710). For panel/CMT indication ref. to 10301.
Status: Excitation current limiter is active. DEFAULT: connected to PID_SET2_SEL1 (6909) which activates the 2nd set of
PID controller time constants TA2 (1921) and TB2 (1924).
Status: Stator OE current limiter is active. DEFAULT: connected to PID_SET3_SEL1 (6913) which activates the 3rd set of
PID controller time constants TA3 (1922) and TB3 (1925).
Status: User defined limiter is active. DEFAULT: not used.
Status: -Q = f(P) limiter is active. DEFAULT: connected to PID_SET3_SEL3 (6915) which activates the 3rd set of PID
controller time constants TA3 (1922) and TB3 (1925).
Status: Stator UE current limiter is active. DEFAULT: connected to PID_SET3_SEL2 (6914) which activates the 3rd set of
PID controller time constants TA3 (1922) and TB3 (1925).
Status: Minimum excitation current limiter is active. DEFAULT: connected to PID_SET2_SEL2 (6910) which activates the
2nd set of PID controller time constants TA2 (1921) and TB2 (1924).
PSS output. This signal is limited to +/- the value set by PSS_VST_LIM (2019). DEFAULT: connected to ADD_IN1_AVR
(6918).
NOTE: Signal available only with optional PSS board UNS 0869.
Status: PSS is active. Connect to spare digital output if status is required for remote indication.
DEFAULT: not used.
NOTE: Signal available only with optional PSS board UNS 0869.
Status: PSS failed. This signal will be generated during F_MACH_FAIL (10912) = TRUE.
Connect this to a spare USER_EVENT Block, if this signal should lead to an AVR_FAULT (USER_EVENTx.TYPE = 2
(AVR_FAULT)).
NOTE: Signal available only with optional PSS board UNS 0869.
Not used
Corrected rotor frequency signal fEP-10000.
DEFAULT: not used. NOTE: Signal available only with optional PSS board UNS 0869.
Integral of electrical power variations (INT_DELTA_Pel).
(Low Word of 32 BIT value. High Word is presented by TP1)
DEFAULT: not used. NOTE: Signal available only with optional PSS board UNS 0869.
Integral of drive power variations (INT_DELTA_Pdrive).
(Low Word of 32 BIT value. High Word is presented by TP3)
DEFAULT: not used. NOTE: Signal available only with optional PSS board UNS 0869.
Integral of accelerating power variations (INT_DELTA_Paccel).
(Low Word of 32 BIT value)
DEFAULT: not used. NOTE: Signal available only with optional PSS board UNS 0869.

3BHS102402 E88

Rev. G

SC
0.01

HL
30000

LL
-30000

DEF. U
%

CLASS
HID, AVR

SP
41

BO

DIAG, HID

41

BO

DIAG, HID

41

BO

DIAG, HID

41

BO

DIAG, HID

41

BO
BO

DIAG, HID
DIAG, HID

41
41

BO

DIAG, HID

41

BO

DIAG, HID

41

0.01

HID, AVR

122

BO

AVR, DIAG

122

BO

AL, DIAG

122

0.01

I/O, SM

122

0.01

I/O, SM

122

0.01

I/O, SM

122

0.01

I/O, SM

122

Parameter and Signal List Version 41.222_2


4.19

81

MANUAL CTRL Group 121

INDEX
12101

INDICATION
REF HL MANUAL

12102

REF LL MANUAL

12103

PRSTM1 ON MANUAL

12104

PRSTM2 ON MANUAL

12105
12106

REF MAN ACTUAL


UEL ON MANUAL

12107

V HZ ERROR

12108

V HZ MANUAL ON

12109

OUT MAN CTRL

12110

U CTRL OUT CH

12111

ERRM FOLLOW MAN

12112

ERRA FOLLOW AUTO

12113

FBA FOLLOW AUTO

12114

FBM FOLLOW MAN

12115

ON FW AUTO

12116

ON FW MANUAL

FUNCTION
Status: Output REF_MAN_ACTUAL (12105) at max. HL_REF_MANUAL (2106). Internally connected to
REF_MAX/MIN multiplexer (group 3) which generates REF_MAX_ACTIVE (10312) at MANUAL mode. For
panel/CMT indication ref. to 10301.
Status: Output REF_MAN_ACTUAL (12105) at min. LL_REF_MANUAL (2105). Internally connected to
REF_MAX/MIN multiplexer (group 3) which generates REF_MIN_ACTIVE (10313) at MANUAL mode. For panel/CMT
indication ref. to 10301.
Status: Acknowledge signal REF_MAN_ACTUAL = PRESET1 REF MAN (2107) if TRIG PRST MAN (7107) is TRUE
and SEL_PRESET2_MAN (7106) is FALSE. DEFAULT: not used.
Status: Acknowledge signal REF_MAN_ACTUAL = PRESET2 REF MAN (2108) if TRIG PRST MAN (7107) and
SEL_PRESET2_MAN (7106) are TRUE. DEFAULT: not used.
MANUAL setpoint from setpoint generator (softpot). The signal is limited by LL_/ HL_REF_MAN (2106/05).
Status: Underexcited MANUAL restrict is active.
DEFAULT: not used. Panel/CMT indication = 1 UEL (ref. 10301).
NOTE: If at MANUAL this status is indicated by ON_UE_LIMITER (12003) too.
MANUAL V/Hz limiter error output. This signal decreases superimposed the MANUAL_CTRL setpoint as long as
V_HZ_MANUAL_ON (12108) is active. DEFAULT: connected to ERR_IMPOSED_MAN (7102)
Status: MAN_CTRL_OE_RESTRICT is active. This releases the imposed action to the MANUAL_CTRL setpoint if
OFF_LINE and V/Hz characteristic (set by 1911...13) is exceeded. (ref. 12107). Panel/CMT indication = 1 OEL (ref.
10301).
DEFAULT: connected to SEL_IMPOSED_MAN (7101) and driving signal ON_OE_LIMITER (12002) if channel and
excitation are ON.
NOTE:
If at MANUAL_CTRL, this status is indicated by ON_OE_LIMITER (12002) too, even if limiter has been
switched off according 7101.
MANUAL controller output. Internally connected to AUTO-MAN selector in the FOLLOW_UP_CTRL (group 21). This
signal is internally limited to +/- 10000, except in case of chopper (type C5), where it is limited to 0 and +10000
because quadrant 4 is not available at manual control and type C5.
Selected output signal either OUT_PID_AVR (11909) in AUTO mode or OUT_MAN_CTRL (12109) in MANUAL
mode. DEFAULT: connected to gate control UCTRL (5502).
Difference (error) between inactive OUT_MAN_CTRL (12109) and active controller output either OUT_PID_AVR
(11909) or UCTRL (12402) of standby channel.
Internally connected to ERRM_FOLLOW_MAN (group 21).
Difference (error) between inactive OUT_PID_AVR (11909) and active controller output either OUT_MAN_CTRL
(12109) or UCTRL (12402) of standby channel.
Internally connected to ERRA_FOLLOW_AUTO (group 19).
Feedback signal to the inactive AVR, switched OFF during AUTO operation.
DEFAULT: connected to FB_IN_FOLLOW_A (7003).
Feedback signal to the inactive MAN controller, switched OFF during MANUAL operation.
DEFAULT: connected to FB_IN_FOLLOW_MAN (7111).
Status: Auto follower of the AVR is active.
DEFAULT: Internally connected to ON_FW_AUTO (group 19).
Status: Auto follower of MANUAL CTRL is active.
DEFAULT: Internally connected to ON_FW_MAN in group 21.

3BHS102402 E88

Rev. G

SC
BO

HL
-

LL
-

DEF.
-

U
-

CLASS
DIAG, HID

SP
45

BO

DIAG, HID

45

BO

DIAG, HID

45

BO

DIAG, HID

45

0.01
BO

30000
-

-30000
-

% AVR, HID
- DIAG, HID

45
45

0.01

30000

-30000

% AVR, HID

60

BO

60

0.01

10000

-10000

% AVR, HID

59

0.01

30000

-30000

% AVR, IMP

46

0.01

30000

-30000

% AVR, HID

46

0.01

30000

-30000

% AVR, HID

46

0.01

30000

-30000

% AVR, HID

46

0.01

30000

-30000

% AVR, HID

46

BO

AVR, DIAG

46

BO

AVR, DIAG

46

DIAG, HID

Parameter and Signal List Version 41.222_2


INDEX
12117

INDICATION
RDY XFER A M

12118

A M DIFF

12119

CH STB DIFF

12120

RDY XFER TWIN

82

FUNCTION
Status: A-M difference (error) below NOT_OK_LEVEL (2120) for back indication ready for transfer to control room. If
FALSE, A-M transfer is not possible by local control panel. For panel/CMT indication ref. to 10301.
DEFAULT: connected to DOX13.[IN] (712) and RDY_XFER_A_M (5315).
Output: A-M difference [OUT_PID_AVR (11909)] - [OUT_MAN_CTRL (12109)] which can be used for remote
indication if connected to analog output. DEFAULT: not used.

SC
BO

HL
-

LL
-

DEF.
-

U
-

0.01

30000

-30000

% AVR; HID

46

Output: Channel difference [UC_STB] - [U_CTRL_OUT_CH] (12110)] which can be used for remote indication if
connected to analog output. DEFAULT: not used.
NOTE: Signal available only with 2 channel system (AFT)
Status: Channel difference (difference between the outputs of the selected controllers A or M) is below
NOT_OK_LEVEL (2120). If FALSE, channel transfer is not possible by local control panel. For panel/CMT indication
ref. to 10301. DEFAULT: connected to READY_XFER_TWIN (5316).

0.01

30000

-30000

% AVR; HID

46

BO

46

3BHS102402 E88

Rev. G

CLASS
AVR, DIAG

AVR, DIAG

SP
46

Parameter and Signal List Version 41.222_2


4.20

83

CH COMMUNICATION Group 124

INDEX
12401

INDICATION
STBY STATUS

12402

UC STBY

12403

U MACH STBY

12404

I EXC STBY

12405

U SYN STBY

12406

U EXC STBY

12407

USER DI

12408

IMP REF STBY

12409

USER AI

FUNCTION
2 channel interaction: Status WORD of the standby channel. Each bit represents one standby channel status (ref. to
transmitted signals):
Received signal from STBY
Transmitted signal in STBY
B0
STBY_EXC_ON
EXC_ON (10307)
B1
--B2
A-M_STBY_OK
A-M_CH_OK
B3
STBY_RESET
RESET
B4
STBY_IMP_ON
ON_SUPERIMPOSED (10314)
B5
STBY_COSPHI_ON
ON_COSPHI_CTRL (10315)
B6
STBY_LOCAL
LOCAL_CMD (TRUE if LOCAL control is active)
B7
RDY_XFER_STBY
RDY_XFER_CH
B8
CHANGEOVER_STBY
CHANGEOVER_CH
B9
STBY_ALARM
ALARM (10338)
B10
STBY_TRIP
EXC_TRIP (10350)
B11
--B12
STBY_FAIL_BU
CH_FAIL (10342)
B13
USER_DI (12407)
USER_DO (7401)
B14
--2 channel interaction: Transmitted U_CTRL_OUT_CH (12110) signal from standby CH. Ref. to 12110. DEFAULT: used
for follow up ctrl (group 21)

SC
-

HL
-

0.01

2 channel interaction: Transmitted U_MACH_RELATIVE (10101) signal from standby CH. Ref. to 10101. DEFAULT: not
used.
NOTE: Since only 14 Bits are transmitted, the 2 LSB are set to 0.
2 channel interaction: Transmitted I_EXC_CH signal from standby CH.
DEFAULT: used as I_EXC_RELATIVE signal as long as standby channel is active, but not at type C5 or if
CONV_CT_LOCATION (514) is set to AT COMMON LINE.
NOTE:
Since only 14 Bits are transmitted, the 2 LSB are set to 0
2 channel interaction: Transmitted U_SYN_RELATIVE (10503) signal from standby CH. Ref. to 10503. DEFAULT: not
used.
NOTE: Since only 14 Bits are transmitted, the 2 LSB are set to 0
2 channel interaction: Transmitted U_EXC_RELATIVE (10505) signal from standby CH. Ref. to 10505. DEFAULT: not
used.
NOTE: Since only 14 Bits are transmitted, the 2 LSB are set to 0
2 channel interaction: Transmitted USER_DO (7401) signal from standby CH.
Ref. to connected source signal. DEFAULT: not used.

DEF.
-

U
-

CLASS
MON, HID

SP
82

+16383 -16384

MON, HID

82

0.01

+32764 -32768

MON, HID

82

0.01

+32764 -32768

MON, HID

82

0.01

+32764 -32768

MON, HID

82

0.01

+32764 -32768

MON, HID

82

BO

MON, HID

82

2 channel interaction: Transmitted IMP_REF (11710) signal from standby CH. Ref. to 11710.
DEFAULT: used as reference for selected imposed controller as long as channel not active (groups 17, 18).

+16383 -16384

MON, HID

82

2 channel interaction: Transmitted USER_AO (7402) signal from standby CH.


Ref. to connected source signal. DEFAULT: not used.
NOTE: Since only 14 Bits are transmitted, the 2 LSB are set to 0

0.01

+32764 -32768

MON, HID

82

3BHS102402 E88

Rev. G

LL
-

Parameter and Signal List Version 41.222_2


INDEX
12410

4.21
INDEX
12501
12502
12503
12504
12505
12506
12507
12508
12509
12510

INDICATION
CH STATUS

FUNCTION
2 channel interaction: Channel status WORD which is transmitted to the standby channel.
Ref. to signal STBY_STATUS (12401). Each bit represents one channel status (ref. to transmitted signals):
Transmitted signal to STBY
B0
EXC_ON (10307)
B1
-B2
A-M_CH_OK
B3
RESET
B4
ON_SUPERIMPOSED (10314)
B5
ON_COSPHI_CTRL (10315)
B6
LOCAL (10339) (TRUE if LOCAL control is active)
B7
RDY_XFER_CH
B8
CHANGEOVER_CH
B9
ALARM (10338)
B10
EXC_TRIP (10350)
B11
-B12
CH_FAIL (10342)
B13
USER_DO (2401)
B14
--

CONSTANTS
INDICATION
CONSTANT
CONSTANT
CONSTANT
CONSTANT
CONSTANT
CONSTANT
CONSTANT
CONSTANT
CONSTANT
CONSTANT

84

0
-1
1
2
10
100
10000
-10000
20000
-20000

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
MON, HID

SP
82

HL
-

LL
-

DEF.
0
-1
1
2
10
100
10000
-10000
20000
-20000

U
-

CLASS
IMP
IMP
IMP
IMP
IMP
IMP
IMP
IMP
IMP
IMP

SP
54
54
54
54
54
54
54
54
54
54

Group 125
FUNCTION
Value which always is ZERO (HEX 0000 == FALSE for logic inputs).
Value which always is -1 (HEX FFFF == TRUE for logic inputs).
Value which always is 1.
Value which always is 2.
Value which always is 10.
Value which always is 100.
Value which always is 10000.
Value which always is -10000.
Value which always is 20000.
Value which always is -20000.

3BHS102402 E88

SC
1
1
1
1
1
1
1
1
1
1

Rev. G

Parameter and Signal List Version 41.222_2


4.22
INDEX
1260112699

4.23
INDEX
1270112799

4.24
INDEX
1280112899

4.25
INDEX
1290112999

4.26
INDEX
1300113099

4.27
INDEX
1310113199

Function Blocks 1
INDICATION

85

Group 126

FUNCTION
Signals for application function blocks
See application function block data sheets.

Function Blocks 2
INDICATION

INDICATION

FUNCTION

INDICATION

FUNCTION

INDICATION

FUNCTION

INDICATION

U
-

CLASS
AFB

SP
050

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP
442,445

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

Group 130

FUNCTION
Signals for application function blocks
See application function block data sheets.

Function Blocks 6

DEF.
-

Group 129

Signals for application function blocks


See application function block data sheets.

Function Blocks 5

LL
-

Group 128

Signals for application function blocks


See application function block data sheets.

Function Blocks 4

HL
-

Group 127

Signals for application function blocks


See application function block data sheets.

Function Blocks 3

SC
-

Group 131

FUNCTION
Signals for application function blocks
See application function block data sheets.

3BHS102402 E88

Rev. G

Parameter and Signal List Version 41.222_2


4.28
INDEX
1320113299

4.29
INDEX
1330113399

4.30
INDEX
1340113499

Function Blocks 7
INDICATION

86

Group 132

FUNCTION
Signals for application function blocks
See application function block data sheets.

Function Blocks 8
INDICATION

INDICATION

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

SC
-

HL
-

LL
-

DEF.
-

U
-

CLASS
AFB

SP

Group 133

FUNCTION
Signals for application function blocks
See application function block data sheets.

Function Blocks 9

SC
-

Group 134

FUNCTION
Signals for application function blocks
See application function block data sheets.

3BHS102402 E88

Rev. G

You might also like