Emotron M20

Shaft Power Monitor

Data Sheet
English

The M20 provides complete flexibility in terms of the type


of protection required for your application. You may select
either overload and underload protection or simply overload
with pre-alarm or underload with pre-alarm. Independent
response delays are selectable for both overload and underload protection. Additional flexibility is provided in the
form of programmable output relays, number of start
attempts, number of reversing attempts etc.

Sha

ft p Emo
ow tron
er m M
on 20
ito
r

Inst
ruc
tio
nm
a
Eng nual
lish

*)
*)Terminal covers optional.

Fig. 1

Emotron M20 and current transformer (CT), both for mounting on standard DIN rail 35mm.
L1
L2
L3

L1

11

L2

13

L3

A+

NOTE: In power
down, both relays
are always N.O.

AM20
2

S1 S2

CTMxxx

Max. 240 VAC (alt. 0 VDC-)

R1

R2
DIG

Stop

Please see
CTM info

K1

Start

U
V
W

K1

NOTE: Monitor
voltage see
Note below

-Reset
-Auto set
- Block

PREALARM

K1

N (alt. 48 VDC+)

Fig. 2

Connection example

NOTE: Make sure that the monitor voltage range e.g.


3x380-500 VAC matches the connected motor/line
voltage, e.g. 3x 400 V.

CG Drives & Automation 01-5959-01r0

Table 1

Motor and CT less than 100 A

RATED MOTOR CURRENT [A]

CURRENT TRANSFORMER TYPE and NUMBER OF WINDINGS


CTM 010

0.4 1.0

10

1.01 2.0

2.01 3.0

3.1 5.0

5.1 10.0

CTM 025

10.1 12.5

12.6 25.0

CTM 050

26.0 50.0

CTM 100

51.0 100.0

In order to ensure an accurate calibration of the M20, it is


essential that you use the correct CTM and apply the exact
number of windings in accordance with the tables.
Table 2

CT greater than 100A

RATED MOTOR CURRENT [A]

CURRENT TRANSFORMER TYPE and


NUMBER OF PRIMARY WINDINGS

101 150

150:5
1

+
+

CTM 010
2

151 250

250:5
1

+
+

CTM 010
2

251 500

500:5
1

+
+

CTM 010
2

501 999

1000:5
1

+
+

CTM 010
2

NOTE: The current transformer (CTMxxx) must be placed in


the same phase that is connected to terminal 9, phase L1,
see Fig. 2.

CG Drives & Automation 01-5959-01r0

Technical Data

26mm 35mm
(1.02) (1.38)

90mm(3.54)

45x90x115 mm (1.77" x 3.54" x 4.53")

Dimensions (WxHxD)

45mm (1.77)

115mm(4.53)

Mounting

35 mm DIN rail 46277

Weight

0.30 kg (10.5 oz)

Supply voltage (10%)

1x100-240 VAC, 3x100-240 VAC, 3x380-500 VAC 3x525-690 VAC

Frequency

50 or 60 Hz

Current input

Current transformer; CTM 010, 025, 050 and 100. Input 0-55 mA. (>100 A extra transformer
needed)

Power consumption

Max. 6 VA

Start-up delay

1-999 s

Hysteresis

0-50% of rated motor power

Response delay max

0.1-500 s

Response delay min

0.1-500 s

Relay output

5 A/240 VAC Resistive, 1.5 A/240 VAC Pilot duty/AC12

Analogue output

Max. load 500 ohm

Digital input

Max. 240 VAC or 48 VDC. High: 24 VAC/DC,


Low: <1 VAC/DC. Reset >50 ms

Fuse

Max. 10 A

Terminal wire size

Use 75C copper (CU) wire only. 0.2-4.0 mm2 single core (AWG12). 0.2-2.5 mm2 flexible core
(AWG14), stripped length 8 mm (0.32")

Terminal tightening torque

0.56-0.79 Nm (5-7 lb-in)

Accuracy

2%, 1 unit cos phi>0.5; excl. current transformer; +20C (+68F)

Repeatability

1 unit 24h; +20C (+68F)

Temperature tolerance

Max. 0.1%/C

Operating temperature

-20 to +50C (-4F to +122F)

Storage temperature

-30 to +80C (-22F to +176F)

Protection class

IP20

RoHS directive

2002/95/EC

Approved to

CE (up to 690VAC), UL and cUL (up to 600 VAC)

Article numbers
Article number

Designation

01-2520-25

Emotron M20 1x100-240/3x100-240 VAC

01-2520-45

Emotron M20 3x380-500 VAC

01-2520-55

Emotron M20 3x525-690 VAC

CG Drives & Automation 01-5959-01r0

Technical Data for Current Transformer (CT)


Type

Dimension (WxQ)

Weight*

Mounting

CTM 010

27 (35) x48mm

0.20 kg

35mm DIN rail 46277

CTM 025

27 (35) x48mm

0.20 kg

35mm DIN rail 46277

CTM 050

27 (35) x48mm

0.20 kg

35mm DIN rail 46277

CTM 100

45 (58) x78mm

0.50 kg

35mm DIN rail 46277

*)Weight including 1m (39 inch) cable. Please note that


max. length of the CTM cable is 1 m and this cable cannot
be extended.

Fig. 3

Current transformer, CTM xxx.

Accessories and documentation


Article number

Designation

01-2471-10

Current Transformer (CT) CTM010, max. 10 A

01-2471-20

Current Transformer (CT) CTM025, max. 25 A

01-2471-30

Current Transformer (CT) CTM050, max. 50 A

01-2471-40

Current Transformer (CT) CTM100, max. 100 A

01-2368-00

Front Panel Kit 1 (2xterminal covers included)

01-4136-01

2xTerminal covers

01-5958-00

Instruction manual (Swedish)

01-5958-01

Instruction manual (English)

01-5958-02

Instruction manual (German)

01-5958-03

Instruction manual (Dutch)

01-5958-04

Instruction manual (Spanish)

01-5958-08

Instruction manual (French)

01-5958-09

Instruction manual (Russian)

EU (European Union) specifications


EMC
Electrical safety
Rated insulated voltage
Rated impulse
withstand voltage

EN 50081-1, EN 50081-2,
EN 50082-1, EN 61000-6-2
IEC 947-5-1
690 V

Pollution degree
2
Terminals 3, 4, 5, 6, 7 and 8 are basic insulated from the
line.
Terminals 3 and 4 are basic insulated from terminals 5, 6, 7
and 8.

4000 V

CG Drives & Automation 01-5959-01r0

Parameter List
Window
00

Function

Range

Default

Custom

Symbol

Alarm indication
Measured shaft power in % of rated power

0-125

Measured shaft power in kW

0-745

kW

Measured shaft power in % of rated power

0-125

Measured shaft power in HP

0-999

02

Measured line voltage

90-760 V

03

Measured current

0.00-999 A

04

Parameter lock

0-999

Monitor function

OVER- and UNDERLOAD, OVERLOAD and


OVERLOAD, UNDERLOAD UNDERLOAD

01

05

11

12

13

14

MAX Main Alarm


(relay R1)

MAX Pre-Alarm
(relay R2)

MIN Pre-Alarm
(relay R2)

MIN Main Alarm


(relay R1)

0-125

100

0-745

2.2

kW

0-125

100

0-999

0-125

100

0-745

2.2

kW

0-125

100

0-999

0-125

0-745

kW

0-125

0-999

0-125

0-745

kW

0-125

0-999

21

MAX Main Alarm margin

0-100

16

22

MAX Pre-Alarm margin

0-100

23

MIN Pre-Alarm margin

0-100

24

MIN Main Alarm margin

0-100

16

31

Start delay

1-999

32

Response delay, overload

0.1-500 s

0.5

33

Hysteresis

0-50

34

Response delay, underload

0.1-500s

0.5

35*

Pause/Reverse time

3-90

36*

Autoreset (start attempts)

0-5

41

Rated motor power

0.10-745

2.2

0.13-999

42

Rated current

0.01-999

5.6

43

Number of phases

1PH/3PH

3PH

61

Main alarm latch

on/OFF

OFF

62

Alarm at no motor
current

on/OFF

OFF

kW
A

CG Drives & Automation 01-5959-01r0

Window

Function

Range

Default

63

Main Alarm relay R1

nc/no

nc

64

Pre-Alarm relay R2

nc/no

no

65*

Relay function

0 = M20
1 = DLM
2 = Reverse

81

Digital input

rES/AU/bLo

rES

82

Block timer

0.0-90

0.0

91

Analogue output

0.20/4.20/20.0/20.4

0.20

92**

Analogue Out low value

0-100

93**

Analogue Out high value

0-125

99

Factory defaults

dEF/USr

Custom

Symbol

dEF

* See Special functions in chapter 9, Emotron M20


Instruction manual.
** See Setting analogue output range in chapter 9,
Emotron M20 Instruction manual.