Building Automation
Building Automation
Contents
[hide]
1 Topology
2 Infrastructure
o
2.1 Controller
2.2 Occupancy
2.3 Lighting
4.1 Manufacturers
6 External links
[edit]Topology
Most building automation networks consist of a primary and secondary bus which connect high-level controllers
(generally specialized for building automation, but may be generic programmable logic controllers) with lower-level
controllers, input/output devices and a user interface (also known as a human interface device).
The primary and secondary bus can be BACnet, optical fiber, ethernet, ARCNET, RS-232, RS-485 or a wireless
network.
Most controllers are proprietary. Each company has its own controllers for specific applications. Some are designed
with limited controls: for example, a simple Packaged Roof Top Unit. Others are designed to be flexible. Most have
proprietary software that will work with ASHRAE's open protocol BACnet or the open protocol LonTalk.
Some newer building automation and lighting control solutions use wireless mesh open standards (such as ZigBee).
These systems can provide interoperability, allowing users to mix-and-match devices from different manufacturers,
and to provide integration with other compatible building control systems.
Inputs and outputs are either analog or digital (some companies say binary).
Analog inputs are used to read a variable measurement. Examples
are temperature, humidity and pressure sensor which could be thermistor, 4-20 mA, 0-10 volt or platinum resistance
thermometer(resistance temperature detector), or wireless sensors.
A digital input indicates if a device is turned on or not. Some examples of a digital input would be a 24VDC/AC signal,
an air flow switch, or a volta-free relay contact (Dry Contact).
Analog outputs control the speed or position of a device, such as a variable frequency drive, a I-P
(current to pneumatics) transducer, or a valve or damper actuator. An example is a hot water valve opening up 25%
to maintain a setpoint.
Digital outputs are used to open and close relays and switches. An example would be to turn on the parking lot lights
when a photocell indicate it is dark outside.
[edit]Infrastructure
[edit]Controller
Controllers are essentially small, purpose-built computers with input and output capabilities. These controllers come
in a range of sizes and capabilities to control devices commonly found in buildings, and to control sub-networks of
controllers.
Inputs allow a controller to read temperatures, humidity, pressure, current flow, air flow, and other essential factors.
The outputs allow the controller to send command and control signals to slave devices, and to other parts of the
system. Inputs and outputs can be either digital or analog. Digital outputs are also sometimes called discrete
depending on manufacturer.
Controllers used for building automation can be grouped in 3 categories. Programmable Logic Controllers (PLCs),
System/Network controllers, and Terminal Unit controllers. However an additional device can also exist in order to
integrate 3rd party systems (i.e. a stand-alone AC system) into a central Building automation system).
PLC's provide the most responsiveness and processing power, but at a unit cost typically 2 to 3 times that of a
System/Network controller intended for BAS applications. Terminal Unit controllers are usually the least expensive
and least powerful.
PLC's may be used to automate high-end applications such as clean rooms or hospitals where the cost of the
controllers is less of a concern.
In office buildings, supermarkets, malls, and other common automated buildings the systems will use
System/Network controllers rather than PLC's. Most System controllers provide general purposefeedback loops, as
well as digital circuits, but lack the millisecond response time that PLC's provide.
System/Network controllers may be applied to control one or more mechanical systems such as an Air Handler Unit
(AHU), boiler, chiller, etc., or they may supervise a sub-network of controllers. In the diagram above, System/Network
controllers are often used in place of PLCs.
Terminal Unit controllers usually are suited for control of lighting and/or simpler devices such as a package rooftop
unit, heat pump, VAV box, or fan coil, etc. The installer typically selects 1 of the available pre-programmed
personalities best suited to the device to be controlled, and does not have to create new control logic.
[edit]Occupancy
Occupancy is one of 2 or more operating modes for a building automation system. Unoccupied, Morning Warmup,
and Night-time Setback are other common modes.
Occupancy is usually based on time of day schedules. In Occupancy mode, the BAS aims to provides a comfortable
climate and adequate lighting, often with zone-based control so that users on one side of a building have a different
thermostat (or a different system, or sub system) than users on the opposite side.
A temperature sensor in the zone provides feedback to the controller, so it can deliver heating or cooling as needed.
If enabled, Morning Warmup (MWU) mode occurs prior to Occupancy. During Morning Warmup the BAS tries to bring
the building to setpoint just in time for Occupancy. The BAS often factors in outdoor conditions and historical
experience to optimize MWU. This is also referred to as Optimised Start.
An override is a manually-initiated command to the BAS. For example, many wall-mounted temperature sensors will
have a push-button that forces the system into Occupancy mode for a set number of minutes. Where present, web
interfaces allow users to remotely initiate an override on the BAS.
Some buildings rely on occupancy sensors to activate lighting and/or climate conditioning. Given the potential for long
lead times before a space becomes sufficiently cool or warm, climate conditioning is not often initiated directly by an
occupancy sensor.
[edit]Lighting
Lighting can be turned on, off, or dimmed with a building automation or lighting control system based on time of day,
or on occupancy sensor, photosensors and timers.[1] One typical example is to turn the lights in a space on for a half
hour since the last motion was sensed. A photocell placed outside a building can sense darkness, and the time of
day, and modulate lights in outer offices and the parking lot.
Lighting is also a good candidate for Demand response, with many control systems providing the ability to dim (or
turn off) lights to take advantage of DR incentives and savings.
[edit]Air handlers
Most air handlers mix return and outside air so less temperature change is needed. This can save money by using
less chilled or heated water (not all AHUs use chilled/hot water circuits). Some external air is needed to keep the
building's air healthy.
Analog or digital temperature sensors may be placed in the space or room, the return and supply air ducts, and
sometimes the external air. Actuators are placed on the hot and chilled water valves, the outside air and return air
dampers. The supply fan (and return if applicable) is started and stopped based on either time of day, temperatures,
building pressures or a combination.
[edit]Constant volume air-handling units
The less efficient type of air-handler is a "constant volume air handling unit," or CAV. The fans in CAVs do not have
variable-speed controls. Instead, CAVs open and close dampers and water-supply valves to maintain temperatures in
the building's spaces. They heat or cool the spaces by opening or closing chilled or hot water valves that feed their
internal heat exchangers. Generally one CAV serves several spaces
[edit]Variable volume air-handling units
A more efficient unit is a "variable air volume (VAV) air-handling unit," or VAV. VAVs supply pressurized air to VAV
boxes, usually one box per room or area. A VAV air handler can change the pressure to the VAV boxes by changing
the speed of a fan or blower with a variable frequency drive or (less efficiently) by moving inlet guide vanes to a fixedspeed fan. The amount of air is determined by the needs of the spaces served by the VAV boxes.
Each VAV box supply air to a small space, like an office. Each box has a damper that is opened or closed based on
how much heating or cooling is required in its space. The more boxes are open, the more air is required, and a
greater amount of air is supplied by the VAV air-handling unit.
Some VAV boxes also have hot water valves and an internal heat exchanger. The valves for hot and cold water are
opened or closed based on the heat demand for the spaces it is supplying. These heated VAV boxes are sometimes
used on the perimeter only and the interior zones are cooling only.
A minimum and maximum CFM must be set on VAV boxes to assure adequate ventilation and proper air balance.
[edit]VAV hybrid systems
Another variation is a hybrid between VAV and CAV systems. In this system, the interior zones operate as in a VAV
system. The outer zones differ in that the heating is supplied by a heating fan in a central location usually with a
heating coil fed by the building boiler. The heated air is ducted to the exterior dual duct mixing boxes and dampers
controlled by the zone thermostat calling for either cooled or heated air as needed.
[edit]Central plant
A central plant is needed to supply the air-handling units with water. It may supply a chilled water system, hot water
system and a condenser water system, as well as transformers and auxiliary power unit for emergency power. If well
managed, these can often help each other. For example, some plants generate electric power at periods with peak
demand, using a gas turbine, and then use the turbine's hot exhaust to heat water or power an absorptive chiller.
[edit]Chilled water system
Chilled water is often used to cool a building's air and equipment. The chilled water system will have chiller(s)
and pumps. Analog temperature sensors measure the chilled water supply and return lines. The chiller(s) are
sequenced on and off to chill the chilled water supply.
a chiller is a refrigeration unit designed to produce cool (chilled) water for space cooling purposes. The chilled water
is then circulated to one or more cooling coils located in air handling units, fan-coils, or induction units. Chilled water
distribution is not constrained by the 100 foot separation limit that applies to DX systems, thus chilled water-based
cooling systems are typically used in larger buildings. Capacity control in a chilled water system is usually achieved
through modulation of water flow through the coils; thus, multiple coils may be served from a single chiller without
compromising control of any individual unit. Chillers may operate on either the vapor compression principle or the
absorption principle. Vapor compression chillers may utilize reciprocating, centrifugal, screw, or rotary compressor
configurations. Reciprocating chillers are commonly used for capacities below 200 tons; centrifugal chillers are
normally used to provide higher capacities; rotary and screw chillers are less commonly used, but are not rare. Heat
rejection from a chiller may be by way of an air-cooled condenser or a cooling tower (both discussed below). Vapor
compression chillers may be bundled with an air-cooled condenser to provide a packaged chiller, which would be
installed outside of the building envelope. Vapor compression chillers may also be designed to be installed separate
from the condensing unit; normally such a chiller would be installed in an enclosed central plant space. Absorption
chillers are designed to be installed separate from the condensing unit.
[edit]Condenser water system
Cooling tower(s) and pumps are used to supply cool condenser water to the chillers. Because the condenser water
supply to the chillers has to be constant, variable speed drives are commonly used on the cooling tower fans to
control temperature. Proper cooling tower temperature assures the proper refrigerant head pressure in the chiller.
The cooling tower set point used depends upon the refrigerant being used. Analog temperature sensors measure the
condenser water supply and return lines.
[edit]Hot water system
The hot water system supplies heat to the building's air-handling unit or VAV box heating coils, along with the
domestic hot water heating coils (Calorifier). The hot water system will have a boiler(s) and pumps. Analog
temperature sensors are placed in the hot water supply and return lines. Some type of mixing valve is usually used to
control the heating water loop temperature. The boiler(s) and pumps are sequenced on and off to maintain supply.
[edit]Alarms and security
Many building automation systems have alarm capabilities. If an alarm is detected, it can be programmed to notify
someone. Notification can be through a computer, pager, cellular phone, or audible alarm.
Common temperature alarms are: space, supply air, chilled water supply and hot
water supply.
Some valve actuators have end switches to indicate if the valve has opened or
not.
Carbon monoxide and carbon dioxide sensors can be used to alarm if levels are
too high.
Current sensors can be used to detect low current conditions caused by slipping
fan belts, or clogging strainers at pumps.
At sites with several buildings, momentary power failures can cause hundreds or thousands of alarms from
equipment that has shut down. Some sites are programmed so that critical alarms are automatically re-sent at
varying intervals. For example, a repeating critical alarm (of an [uninterruptible power supply] in 'by pass') might
resound at 10 minutes, 30 minutes, and every 2 to 4 hours thereafter until the alarms are resolved.
Security systems can be interlocked to a building automation system. If occupancy sensors are present, they can
also be used as burglar alarms.
Fire and smoke alarm systems can be hard-wired to override building automation. For example: if the smoke alarm is
activated, all the outside air dampers close to prevent air coming into the building, and an exhaust system can isolate
[edit]Room automation
Room automation is a subset of building automation and with a similar purpose, it is the consolidation of one or
more systems under centralised control, though in this case in one room.
The most common example of room automation is corporate boardroom, presentation suites, and lecture halls, where
the operation of the large number of devices that define the room function (such
as videoconferencing equipment, video projectors, lighting control systems, public address systems etc.) would make
manual operation of the room very complex. It is common for room automation systems to employ a touchscreen as
the primary way of controlling each operation.
[edit]See also
Control engineering
Control system
Crestron
Digital home
Home automation
Smart environment
Alerton Technologies
American Auto-Matrix
AMX, LLC
ASI Controls
Beckhoff Automation
ABB Group
Carrier Corporation
Cisco Systems
Citect
Computrols, Inc.
Echelon Corporation
EnOcean
HomePLC
Honeywell
Iconics
[edit]Manufacturers
KMC Controls
LadderWORK
Novar Controls
Panduit
Priva
SAIA-Burgess Controls
Schneider Electric
StarDraw control
Wonderware
S-Bus
Dynet
Midac
OpenTherm
OpenWebNet
[edit]References
1.
[edit]External links
[hide]
e
Automation protocols
Process automation
BSAP
CIP
ControlNet
DeviceNet
DF-1
DirectNET
EtherCAT
Ethernet Powerlink
EtherNet/IP
FINS
FOUNDATION fieldbus (H1, HSE)
GE SRTP
HART Protocol
Honeywell SDS
HostLink
INTERBUS
MECHATROLINK
MelsecNet
Modbus
Optomux
PieP
Profibus
PROFINET IO
SERCOS interface
SERCOS III
Sinec H1
SynqNet
TTEthernet
RAPIEnet
OPC DA
OPC HDA
Industrial control system
OPC UA
MTConnect
1-Wire
BACnet
C-Bus
DALI
DSI
KNX
Building automation
LonTalk
Modbus
oBIX
X10
xAP
ZigBee
IEC 60870-5
DNP3
IEC 60870-6
IEC 61850
IEC 62351
Modbus
Profibus
ANSI C12.18
IEC 61107
DLMS/IEC 62056
Automatic meter reading
M-Bus
Modbus
Automobile / Vehicle
LIN
J1708
J1587
FMS
J1939
CAN
NMEA 2000
VAN
FlexRay
MOST
Submit ratings
Categories:
Building automation
Article
Discussion
Read
Edit
View history
Main page
Contents
Featured content
Current events
Random article
Donate to Wikipedia
Interaction
Help
About Wikipedia
Community portal
Recent changes
Contact Wikipedia
Toolbox
Print/export
Languages
Dansk
Deutsch
Espaol
Franais
Polski
Suomi
Svenska
Trke
Contact us
Privacy policy
About Wikipedia
Disclaimers
Mobile view