EAOM - 36
Hz./
RPM
FAILED TO START
RPM
SPEED
FAILURE
Features
Designed For Generator, Pump & Fire Pump Applications
Remote start / stop capability with zero power consumption
Engine start and stop
Automatic shutdown on fault condition
Provides alarm and status information
Alarm and shutdown inputs
Provides charge alternator excitation current
Lamp test function
CHARGING FAIL
~
~
~
~~
~ HIGH TEMPERATURE
Fail Monitoring
LOW OIL PRESSURE
0
STOP
Oil pressure
Engine temperature
Over speed & Under speed (generator application)
Charging alternator
Conf. Input-1 & 2
I
START
Controls
Engine fuel or stop solenoid
Starter motor
Preheat, simulate fuel solenoid, external alarm
horn, alarm or load contactor out
EAOM-36 Manual Start Unit use microprocessor based technology to provide integrated manual start and
fault protection in a wide range of engine applications. The module is housed in 72x72 DIN size.The module is
used to start and stop the engine, indicating the operational status and fault conditions. Automatically shutting
down the engine and indicating the engine failure by a flashing LED. User can control the engine via a two position
key switch and pushbuttons mounted on the front panel or with remote input.
The module has three application feature; 'Generator', 'Pump' or 'Fire Pump'. (can be selected from
parameter P00).
The module can connect directly with engine, thanks to high current relay outputs.
The module has two feature for fuel. One of energize to run the other energize to stop. User can select the
feature from program parameters.
The module protect the engine against fault conditions. If a fault condition occurred, the module indicate the fault
condition and shut-down the engine.
If the key switch is OFF position the module has zero power consumption to save energy. The module energizes
when the key switch position is getting ON position. If Satart button is pressed, the Conf. Out relay output (if selected
preheat output) will activate until the preheat delay is expired.
Press Start button for starting the engine. When engine is running, module will stop the cranking.
Press Stop button for stoping the engine. After pressing the stop button, the engine will keep running until cooling
time(P21) is expired.
Also the module has remote start facility. Please select suitable type of remote start for your application from
program parameters. If remote start input is active the module will start the engine. If remote start is passive the unit will
stop the engine after cooling time is expired.
The module will check the alarms after safety on timer is expired.
Under one of this fault conditions the module will stop the engine;
- Over speed (generator application),
- Under speed(generator application),
- High Temperature,
- Low Oil Pressure,
- Shutdown (if one of conf. input selected shutdown and activated).
To reset the fault, turn the key switch to the OFF position for a few seconds.
The Charge Failure is a warning alarm so the engine continue to work under this failure condition. Also this input
supplying charge alternator excitation current.
Shutdown the engine;
If the engine fuel type is energize to stop, press Stop button until the engine comes to rest. After that select OFF
position of the key switch.
If the engine fuel type is energize to run, select OFF position of the key switch.
Important note: On the Fire Pump application; If a fault condition occurred, the module will not stop the engine.
The engine will be stopped only when the stop button was pressed or the remote stop signal was detected.
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size
Program Parameters for Generator Application
Prog No
P 00
P 01
P 02
P 03
P 04
P 05
P 06
P 07
P 08
P 09
P 10
P 11
P 12
P 13
P 14
P 15
P 16
P 17
P 18
P 19
P 20
P 21
P 22
Parameter Name
Application Selection (Generator, Pump, Fire Pump)
Frequency Lower Limit
Frequency Upper Limit
Nominal Alternator Frequency
Nominal Speed
Stop/Fuel Solenoid Selection
Stop Solenoid Energising Time
Crank Disconnect on Gen. Frequency
Crank Disconnect on Charge Alternator Voltage
Crank Disconnect on Oil Pressure
Number of Starting Attempts
Starting Attempt Duration
Oil Pressure Bypass Time
Safety On Delay
Frequency Fault Control Delay
Engine Running Time Value & New Engine Running Time
Remote Start Selection:
0 - Disable. The start / stop buton is used. (leave key switch 1 position)
1 - When the -BATTERY applied to Rem. start input (terminal-11),
the engine start cranking. (leave key switch 1 position)
2 - When the +BATTERY applied to +BAT input (terminal-3),
the engine start cranking. (leave key switch 1 position)
Conf. Out Type: 0- Alarm Out, 1- Horn Out,
2- Preheat Out, 3- Simulate Fuel Solenoid Out,
4- Load Contactor Out
Conf. Input 1
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running
Conf. Input 2
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running
Horn Duration
Cooling Time
Password
Unit
Hz.
Hz.
Hz.
Rpm
Sec.
Hz.
Number
Sec.
Sec.
Sec.
Sec.
Hour
-
Limits
GEn, PUP, FPU
30.0 - 75.0
30.0 - 75.0
30.0 - 75.0
500 - 5000
StoP - FUEL
1 - 99
25.0 - 75.0
diS - EnAb
diS - EnAb
1 - 10
5 - 99
0 - 99
0 - 99
0.0 - 10.0
0 - 9999
0= diS 1 - 2
Default
GEn
47.0
53.0
50.0
1500
FUEL
20
30.0
diS
EnAb
3
5
30
10
3.0
0
diS
0-4
0-5
0-5
Sec.
Sec.
-
0= Cont. 1 - 999
0(dis) - 3600
0 - 9999
30
0
0
Warning: P16 Remote Start Selection parameter option 2 can not be used with stop solenoid type generators.
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size
Program Parameters for Pump (Fire Pump) Applications
Prog No
P 00
P 05
P 06
P 08
P 09
P 10
P 11
P 12
P 13
P 15
P 16
P 17
P 18
P 19
P 20
P 21
P 22
Parameter Name
Application Selection (Generator, Pump, Fire Pump)
Stop/Fuel Solenoid Selection
Stop Solenoid Energising Time
Crank Disconnect on Charge Alternator Voltage
Crank Disconnect on Oil Pressure
Number of Starting Attempts
Starting Attempt Duration
Oil Pressure Bypass Time
Safety On Delay
Engine Running Time Value & New Engine Running Time
Remote Start Selection:
0 - Disable. The start / stop buton is used. (leave key switch 1 position)
1 - When the -BATTERY applied to Rem. start input (terminal-11),
the engine start cranking. (leave key switch 1 position)
2 - When the +BATTERY applied to +BAT input (terminal-3),
the engine start cranking. (leave key switch 1 position)
Conf. Out Type 0- Alarm Out, 1- Horn Out,
2- Preheat Out, 3- Simulate Fuel Solenoid Out,
4- Load Contactor Out
Conf. Input 1
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running
Conf. Input 2
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running
Horn Duration
Cooling Time
Password
Unit
Sec.
Number
Sec.
Sec.
Sec.
Hour
-
Limits
GEn, PUP, FPU
StoP - FUEL
1 - 99
diS - EnAb
diS - EnAb
1 - 10
5 - 99
0 - 99
0 - 99
0 - 9999
0= diS 1 - 2
Default
PUP
FUEL
20
diS
EnAb
3
5
30
10
0
diS
0-4
0-5
0-5
Sec.
Sec.
-
0= Cont. 1 - 999
0(dis) - 3600
0 - 9999
30
0
0
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size
Specifications
Equipment Use
Housing & Mounting
Panel Cut-out
Protection
Weight
Environmental Rating
Operating / Storage Temperature
Operating / Storage Humidity
Installation Over Voltage Cat.
Pollution Degree
Mode of Operation
EMC
Electrical Safety
Supply Voltage(Z)
Generator Speed Measurement
Alternator Frequency Range
Frequency Meas. Accuracy
Cranking Dropouts
Relay Outputs
Failure Indicators
Status Indicators
Hz./RPM
Engine running time
Engine start
Engine stop
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size
Dimensions & Front View
EAOM - 36
Hz./
RPM
RPM
SPEED
FAILURE
72 mm
FAILED TO START
CHARGING FAIL
~
~
~
~~
~ HIGH TEMPERATURE
0
STOP
START
72 mm
5 mm
47 mm
68 mm
Panel Cut-Out
TEN A
68 mm
+BAT
FUEL
CONF.O
5
6
7
HIGH TEMP.
CONF. INPUT-2
OR REMOTE START
(P16=1 => REM. INPUT)
+BAT
START
10A@28VDC
FUEL
10A@28VDC
CONF.O
10A@28VDC
+BAT
12
-BAT
13
L1
N
10
11
(+)CHARGE GEN.
D+(W.L.)
GND
TX
RX
CONF. INPUT-2
OR REMOTE START
(P16=1 => REM. INPUT)
10A@28VDC
10A@28VDC
10A@28VDC
CONF. INPUT-1
-BAT
11
CONF. INPUT-1
-BAT
2
3
(+)CHARGE GEN.
D+(W.L.)
START
10
-BAT
RS 232
-BAT
HIGH TEMP.
RS 232
+BAT
12
-BAT
13
GND
TX
RX
L1
N
GENERATOR
VOLTAGE
300VAC (Ph-N) Max.
GENERATOR
VOLTAGE
300VAC (Ph-N) Max.
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size
Connection Schematic (Without Remote Start P16 = 0 (dis))
c2
12
10
11
CONF.OUT
STARTER
HORN
CONF. INPUT-2
CHARGE
GEN. D+(W.L.)
CONF. INPUT-1
HIGH TEMPERATURE
BATTERY
CHARGE
GENERATOR
40 A
START
RELAY
40 A
SOLENOID
RELAY
B+
OR LOAD CONTACTOR
+BAT
FUSE-1
-BAT
+BAT
PREHEAT, ALARM
10A@28VDC
10A@28VDC
13
10A@28VDC
N
L1
FUSE-2
ALTERNATOR
1- Connect the unit as shown in the appropriate diagram above. Be sure to connect the battery supply the right way round and
battery negative should be grounded.
2- Use Alternator connection only generator application (P00 = Gen)
c2
12
10
11
PREHEAT, ALARM
CONF.OUT
HORN
STARTER
CONF. INPUT-1
CHARGE
GEN. D+(W.L.)
HIGH TEMPERATURE
40 A
40 A
START
RELAY
+
BATTERY
FUSE-1
SOLENOID
RELAY
B+
OR LOAD CONTACTOR
CHARGE
GENERATOR
+BAT
-BAT
8
+BAT
10A@28VDC
10A@28VDC
13
10A@28VDC
N
L1
FUSE-2
ALTERNATOR
1- Connect the unit as shown in the appropriate diagram above. Be sure to connect the battery supply the right way round and
battery negative should be grounded.
2- Use Alternator connection only generator application (P00 = Gen)
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size
Connection Schematic (With Remote Start, No Power Consumption P16 = 2)
c2
12
10
11
CONF.OUT
STARTER
HORN
CONF. INPUT-2
CHARGE
GEN. D+(W.L.)
CONF. INPUT-1
HIGH TEMPERATURE
40 A
START
RELAY
40 A
SOLENOID
RELAY
B+
BATTERY
CHARGE
GENERATOR
REMOTE
SWITCH
OR LOAD CONTACTOR
+BAT
FUSE-1
-BAT
+BAT
PREHEAT, ALARM
10A@28VDC
10A@28VDC
13
10A@28VDC
N
L1
FUSE-2
ALTERNATOR
1- Connect the unit as shown in the appropriate diagram above. Be sure to connect the battery supply the right way round and
battery negative should be grounded.
2- Use Alternator connection only generator application (P00 = Gen)
c2
12
10
11
PREHEAT, ALARM
CONF.OUT
HORN
CONF. INPUT-2
STARTER
CONF. INPUT-1
CHARGE
GEN. D+(W.L.)
HIGH TEMPERATURE
40 A
40 A
START
RELAY
+
BATTERY
FUSE-1
SOLENOID
RELAY
B+
OR LOAD CONTACTOR
CHARGE
GENERATOR
+BAT
-BAT
8
+BAT
10A@28VDC
10A@28VDC
13
10A@28VDC
N
L1
FUSE-2
ALTERNATOR
1- Connect the unit as shown in the appropriate diagram above. Be sure to connect the battery supply the right way round and
battery negative should be grounded.
2- Use Alternator connection only generator application (P00 = Gen)
Product Codes
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size, with relay outputs
EAOM-36.R
EAOM-36.RF Manual and Remote Start Unit with Key Switch, 72x72 DIN Size, with relay outputs & fail safe inputs
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size
Other Informations
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A..
Demirta Organize Sanayi Blgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repair and Maintenance Service Information:
Emko Elektronik Sanayi ve Ticaret A..
Demirta Organize Sanayi Blgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Thank you very much for your preference to use Emko Elektronik
Your Technology Partner
Products.
www.emkoelektronik.com.tr