26 23 00 Smart LV Arc Resistant Switchgear WL
26 23 00 Smart LV Arc Resistant Switchgear WL
26 23 00 Smart LV Arc Resistant Switchgear WL
SCOPE
A.
1.2
This section defines arc resistant low voltage metal-enclosed switchgear assemblies with
drawout circuit breaker elements for use in AC systems, rated 600 V or less.
RELATED DOCUMENTS
A.
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
B.
1.3
SUBMITTALS
A.
Submit shop drawings and product data for approval and final documentation in the quantities
listed according to the Conditions of the Contract. Customer name, customer location and
customer order number shall identify all transmittals.
B.
Documents for Approval: General arrangement drawings showing dimensioned elevation, floor
plan, side view and foundation details, one-line diagram showing major features, nameplate
legends, schematic diagrams and bill of material.
C.
Final Documents: Record documentation to include those in 1.3.B and wiring diagrams,
list of recommended spare parts, instruction and installation manuals [and certified test
reports]
D.
Product Data: Include features, characteristics and ratings of individual circuit breakers and
other components. Also, time-current characteristic curves for over current protective devices,
including circuit-breaker trip devices and fusible devices.
1.4
RELATED STANDARDS
A.
[Project Name]
[26 23 00] [16430]-1
10.
11.
B.
1.5
[Manufacturer Seismic Qualification: The low voltage arc resistant switchgear shall meet
and be certified to seismic requirements specified in the [IBC 2009 International Building
Code] [CBC 2010 California Building Code] [ASCE American Society of Civil Engineers 710].
1.
The low voltage switchgear shall be compliant with IBC 2009 parameters:
a.
Building Occupancy Category (as defined in Table 1.1 from ASCE 2010): [I]
[II] [III] [IV]
b.
Seismic Design Category: [A] [B] [C] [D] [E] [F]
c.
Site Class: [A Hard Rock] [B - Rock] [C Very dense soil and soft rock] [D
Stiff soil profile] [E Soft Soil Profile] [F Soil vulnerable to potential
failure or collapse under seismic loading] as defined in IBC 2006 Table
1613.5.2 Site Class Definitions
d.
Ip Importance Factor: [1.5 Components must function after an
earthquake for life safety purposes (Building Occupancy Code IV)] [1.25 Buildings and structures that represent a substantial hazard to human life in
the event of failure or that can cause substantial economic impact or mass
disruption of day-to-day civilian life (Building Occupancy Code III)] [1.0
Non-essential buildings. Function not life critical. (Building Occupancy
Code I and II)]
e.
Ss Mapped Spectral Accelerations for Short Periods at 0.2 seconds
180%g
f.
Sds 5% Damped Design Spectral Response Accelerations for Short
Periods at 0.2 seconds 1.2.
g.
z/h Height factor ratio: [___] NOTE: Ratio is a calculated value equal to the
floor the gear is installed on divided by 12. A 6th floor installation is a 0.5
value. A basement or ground floor installation is a 0.0 value.
2.
Equipment shall be designed to be located in a concrete and steel, momentresisting frame building not exceeding 12 stories in height with a minimum story
height of 10 feet.]
QUALITY ASSURANCE
A.
1.6
A.
Deliver products in factory labeled packages. Shipping groups shall not exceed 15 ft. in length.
B.
Circuit breakers shall be shipped inside their respective cells in which they were factory
acceptance tested.
C.
Store and handle in strict compliance with manufacturers instructions and recommendations.
Protect from potential damage from weather and construction operations.
Store so
condensation will not form on or in switchgear and if necessary, apply temporary heat where
required to obtain suitable service conditions.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
[The low voltage arc resistant switchgear shall be manufactured by Siemens, Type WLLow Voltage Arc Resistant Switchgear or pre-approved equal. Approved manufacturers
are as follows:
[Project Name]
[26 23 00] [16430]-2
1.
2.
2.2
RATINGS
A.
System Configuration: Switchgear suitable for application in three-phase, [60 Hz] [50 Hz],
[3 wire] [4 wire] [grounded-neutral] [3 wire ungrounded] [3 wire high-impedance
grounded] system.
B.
Electrical Ratings:
1.
Nominal System Voltage: [600V] [480 V] [240 V] [208 V].
2.
Maximum Design Voltage: 635V
3.
Maximum Short-Circuit Current: [100kA at 480V] [85kA at 600V]
4.
Main-Bus Continuous Current: [1600] [2000] [3200] [4000] [5000] [6000] A.
5.
Neutral Bus Continuous Current: [50] [100] percent of main phase bus.
2.3
GENERAL REQUIREMENTS
A.
Smart-Gear Low Voltage Switchgear. Each low voltage switchgear lineup shall be supplied with
the following functionality:
1.
CPU with factory programmed software that supports remote monitoring, configuration
and control of embedded intelligent devices and structural monitoring devices.
2.
Communication backbone linking embedded intelligent devices, CPU and HMI.
3.
[15] [19] touch screen HMI pre-configured and programmed with application specific
graphical user interface (application specific elevation and one-line drawings) that act as
user home page.
4.
The HMI must communicate with the pre-programmed CPU and act as the local master.
Using the touch screen HMI, the user must be able to navigate back and forth between
the elevation and one-line views of the LVS lineup. Utilizing the elevation or one-line
screens, the user must be able to select (touch) an embedded intelligent device (breaker,
meter, relay, SPD, etc) and drill down to access screens that support monitoring,
configuring and control of the intelligent devices.
5.
Utilizing the touch screen HMI, the user must be able to access the following information
and functions:
a.
LVS one-line view
1.)
Breaker status open/closed/tripped
2.)
Breaker position connect/test/disconnect
3.)
Dynamic Arc Flash Sentry (DAS) status activated/deactivated
4.)
Bus status dead/healthy/unhealthy
5.)
System alarm warning (when applicable)
b.
LVS elevation view
1.)
Breaker status open/closed
2.)
Breaker position connect/test/disconnect
3.)
Dynamic Arc Flash Sentry (DAS) status activated/deactivated
4.)
Bus status dead/healthy/unhealthy
5.)
System alarm warning (when applicable)
c.
Breaker control (Password or hardware enabled/disabled)
1.)
Open selected breaker
2.)
Close selected breaker
3.)
Activate DAS (arc flash maintenance mode)
4.)
De-activate DAS (arc flash maintenance mode)
5.)
Breaker status open/closed (Info only)
6.)
Ready to close indication OK/No (Info only)
7.)
Spring charge status charged/discharged (Info only)
d.
Breaker monitoring
1.)
Breaker temperature (current temperature, time stamped minimum
temperature and time stamped maximum temperature)
[Project Name]
[26 23 00] [16430]-3
2.)
3.)
4.)
5.)
6.)
7.)
8.)
9.)
10.)
11.)
12.)
13.)
14.)
15.)
16.)
minimum
[Project Name]
[26 23 00] [16430]-4
d.)
e.
f.
[Project Name]
[26 23 00] [16430]-5
3.)
[Project Name]
[26 23 00] [16430]-6
8.)
k.
l.
m.
B.
The switchgear shall be factory assembled and tested and comply with applicable industry
standards. It shall be a coordinated design so that shipping groups are easily connected
together at the site into a continuous line-up. Necessary connecting materials shall be
furnished. All power circuit breakers and assemblies shall be produced by a single
manufacturer.
C.
The switchgear assembly shall consist of one or more metal-enclosed sections in an indoor
NEMA 1 enclosure.
1.
End sections shall include provisions for main bus extension and installation of future
vertical sections.
2.
The design shall incorporate preformed steel channels, angles and structural
components bolted together and reinforced to form a rigid, self-supporting assembly.
3.
Fabricate enclosure with removable, [rear cover panels, secured by captive
screws], [hinged rear doors with captive screws] [hinged rear doors with threepoint latch and padlockable handle] to allow access to rear interior of switchgear.
D.
Front breaker doors and covers must be free of any ventilation openings.
E.
F.
Circuit breaker compartments shall include stationary primary contact disconnects that shall be
silver-plated copper at the connection points and of one-piece construction.
G.
1.
The upper set of disconnects shall bolt directly to the main bus and, for feeder circuit
breakers, the lower set shall extend to the rear cable area and shall be insulated where
they pass through the main bus compartment.
2.
Primary disconnects shall be sized for the maximum continuous current for the frame size
of the circuit breaker which is located in the compartment.
3.
Interlocks shall be provided to prevent a circuit breaker element of the incorrect frame
size or interrupting rating from being inserted into the compartment.
4.
All control wiring within the assembly shall be continuous and shall terminate on each end at a
suitable terminal block. Control wiring shall be 14-gauge minimum, stranded type SIS and shall
be labeled at each end with sleeve-type wire markers.
1.
Wire markers shall be machine imprinted with the wire name as indicated on the wiring
diagrams.
2.
Terminals shall be insulated locking fork or ring tongue type except where connecting to
components that do not accept these terminations.
Control wiring for external
[Project Name]
[26 23 00] [16430]-7
Finish: Steel parts shall be prepared for painting by a five-stage wash system consisting of an
alkaline cleaner, fresh water rise, iron phosphate treatment, fresh water rise and non-chromate
sealer. After cleaning and stabilization, the steel parts shall be coated with a thermosetting
polyester powder applied with electrostatic equipment at a nominal 2 mils dry film thickness and
then cured properly. The paint finish shall have a pencil hardness of 2H, a salt spray rating as
defined in ASTM B-117-73 of 600 hours. Paint color shall be ANSI 61 light gray.
I.
Bus isolation barriers shall be arranged to isolate the buses on either side of each main and tie
circuit breaker from each other.
J.
[Incoming line isolation barriers shall be arranged to isolate the incoming line
connections from the main horizontal and vertical bus].
K.
Main bus shall connect vertical sections and shall be uniform capacity the entire length of
assembly. Vertical and horizontal bus bar shall utilize a channel shape design to maximize
short circuit withstand capability and minimize heat rise. The main horizontal bus shall be run in
a vertical, edge-to-edge arrangement for high short circuit strength. Access to the rear cable
termination area shall be possible without reaching over the main and vertical bus.
1.
Bus shall be [98 % minimum conductivity copper silver-plated over entire length of
the bus bar] [98 % conductivity copper tin-plated over entire length of the bus bar].
2.
Feeder Circuit-Breaker Load Terminals: Plated copper bus extensions equipped with
[mechanical] [compression] cable connectors for outgoing circuit conductors.
3.
Ground Bus shall be copper of 98 % minimum conductivity, minimum size 1/4 by 3
inches.
4.
Bus bracing shall be equal to the short circuit interrupting rating of the lowest rated circuit
breaker applied in the assembly or 100kA minimum.
5.
Provide for future extensions from either end of main phase, neutral and ground bus by
means of predrilled bolt holes and connecting links.
L.
Bus/Cable compartment barriers: Barriers shall be supplied to isolate the rear cable area from
the main bus area.
M.
Insulated bus bar shall consist of bus bars enclosed in factory-applied, flame-retardant UL
recognized insulation system. Bolted bus joints shall be insulated with secure joint covers that
can easily be removed and reinstalled.
N.
1.
[Project Name]
[26 23 00] [16430]-8
O.
2.4
A.
B.
[Project Name]
[26 23 00] [16430]-9
C.
Provision for Future Devices: Equip future circuit breaker compartments with rails, mounting
brackets, supports, necessary appurtenances and bus connections.
D.
Control Power Supply: Control power transformer supplying 120-V control circuits through
secondary disconnect devices are to be dry-type transformers with primary and secondary
fuses.
1.
Transformers shall be mounted in auxiliary compartments.
2.
[Multiple source with control power transfer.] Two control power transformers
located in separate compartments with necessary interlocking relays shall be
provided.
a.
Each transformer shall be connected to line side of associated main circuit
breaker.
b.
[Secondary windings connected through a relay or relays to control bus to
affect an automatic control power transfer scheme.]
3.
[(24) (48) (125) volt DC battery system]
E.
[Mimic Bus]: Continuous mimic bus applied to front of switchgear, arranged in singleline diagram format, shall indicate the arrangement of the circuit breakers in the power
circuit.
2.5
CIRCUIT BREAKERS
A.
Circuit breakers shall comply with the requirements of IEEE/ANSI C37.13, C37.16, C37.17,
C37.50, UL1066, NEMA SG3. All breakers shall be three-pole, 100% rated type WL low voltage
power breaker manufactured by Siemens Industry, or approved equal.
1.
Circuit beaker element shall have connected, test and disconnected position indicators,
spring charged/discharged indicators and circuit breaker open or closed and ready to
close indicators all of which shall be visible to the operator with the compartment door
closed. It shall be possible to rack the circuit breaker element from the connected to the
disconnected position with the compartment door closed otherwise known as through
the door drawout.
2.
Provide interlocks to prevent racking the circuit breaker unless the breaker is open.
3.
Raking handle shall be integral to the breaker.
B.
Ratings: Interrupting up to 100 kA at 480V without fuses. Short time current ratings for each
circuit breaker shall be as indicated on the drawings or data tables. Circuit breakers shall be
600-volt class.
C.
D.
Each low voltage power circuit breaker shall be equipped with self-powered, microprocessorbased trip-device to sense overload and short circuit conditions. The device shall measure true
RMS current. The tripping system shall consist of Rogowski coil sensors on each phase, a
release mechanism and the following features:
1.
Field Installable and interchangeable so that any trip unit can be used with any frame size
circuit breaker. Trip units can be upgraded for future expansion in functionality, such as
communication.
2.
Functions: Long time, short time and extended instantaneous protection function shall be
provided {EIP} to allow the breaker to be applied at the withstand rating of the breaker
with minus 0% tolerance so that there is no instantaneous override whatsoever. This
feature shall furthermore allow the circuit breaker to be applied up to the full
instantaneous rating of the breaker on systems where the available fault current exceeds
the breakers withstand rating. Each shall have an adjustable pick-up setting. In addition,
long time and short time bands shall each have adjustable time delay. Short time
[Project Name]
[26 23 00] [16430]-10
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
function shall include a switchable I2t ramp and optionally I4t to improve co-ordination with
fuses or inverse relays.
A software program shall be made available free of charge to support system coordination studies .The software will allow time current curves to be generated for the
chosen settings.
Individual LEDs shall indicate an overcurrent, short circuit or ground fault trip condition.
The data shall be maintained for a minimum of 48 hours without the need for a separate
battery.
Time-current characteristics shall be field adjustable locally or optionally remotely via a
bus system [ModBus] [Profibus] [Ethernet].
[Current Adjustability: Parameter settings and rating plugs on the trip units.]
Pickup Points: 10 Long Time Settings.
Field Installable Ground-fault protection with at least three time-delay bands. Adjustable
current pickup and an I2t ramp. Arrange to provide protection for [three-wire] [four-wire]
service.
[Field installable zone selective interlocking: Connections will be made between
main, tie and feeder circuit breakers to ensure that the circuit breaker closest to
the fault trips for short time and ground fault conditions.]
[Field Installable Communications shall be provided per schedule]
[A LCD graphical display with keypad shall be provided to simplify settings &
viewing data locally.]
[The option to remotely switch protection settings shall be provided whenever a
generator is part of the power distribution system.]
Field installable configurable [analog], [digital] output relays shall be available to
connect directly to the trip unit.
[Waveform display option on LCD display. ETU776 only]
Estimated contact wear shall be capable of being communicated remotely in addition to a
local mechanical indication flag.
E.
[MOC {mechanism operated cell switch} operated by the circuit breaker operating
mechanism]
F.
Terminal Block Connections, shall be front mounted and utilize [Screw Type Terminals]
[Ring Tongue Terminals] [Tension Spring Terminals]
G.
Padlocking Provisions: For installing at least three padlocks on each circuit breaker to prevent
movement of the drawout mechanism.
H.
Operating Handle: shall be built in complete with handle and integral to breaker. No external
tools shall be required to rack the breaker
I.
J.
[Key Interlocks: Mountings and hardware are included where future installation of keyinterlock devices is indicated.]
K.
L.
M.
[Fused Circuit Breakers: Circuit breaker and fuse combinations must comply with
requirements for circuit breakers and trip devices and include the following:]
1.
Fuses: NEMA FU 1, Class L current limiting, sized to coordinate with and protect
associated circuit breaker.
2.
Blown-Fuse Trip Device: fused circuit breakers are to be equipped with blown fuse
lockout devices to prevent closing the breaker if a fuse is blown or not present.
Open-fuse status is indicated at the front of the circuit breaker or fuse drawout
element.
N.
[Indicating Lights: To indicate circuit breaker is open or closed, for electrically operated
circuit breakers.]
[Project Name]
[26 23 00] [16430]-11
O.
Modular communication and relaying accessories are to be available for retrofitting by the
clients chosen engineer. It shall not be necessary for the manufacturers personnel to retrofit
accessories
P.
The following items must be capable of being changed in the field: main contacts, CTs, trip
units, racking mechanism and all internal & external accessories
Q.
[The main breaker shall have a Dynamic Arc Flash Sentry. The main breaker shall have a
dual protective setting capability with graphic waveform display, similar to the Siemens
WL breakers ETU776 trip unit. The main breaker will allow the installer to set two
different trip curves into one breaker. One curve will be set for standard operating mode
and the second curve, with instantaneous protection shall be set for arc flash mode.
The switchboard shall be outfitted with a 24 VDC power supply, CubicleBus digital input
module, annunciator panel with flashing light and a UPS power supply. The arc flash
mode shall be actuated by a [keyed switch] [selector switch] [a light curtain installed
behind the gear to sense open doors on the back of the panel] [remote control panel]
[occupancy sensor]].
2.6
ACCESSORIES
A.
B.
[Portable test set for testing all functions of circuit breaker, solid-state trip devices
without removal from switchgear.]
C.
D.
[Spare Fuses: Six, of each type and rating of fuse used. Include spares for potential
transformer fuses and control power fuses.]
E.
F.
G.
[Test Cabinet: Wall mountable cabinet to hold necessary equipment for testing
electrically operated breakers.]
H.
I.
[Remote Breaker Racking Siemens offers two types of Remote Breaker Racking. Delete
one or both of these options below. (Bracket Mounted and/or SARRACS)
1.
[Bracket Mounted
a.
A remote racking device shall be supplied to allow qualified personnel to
rack Siemens Type WL breakers into Connect, Test and Disconnect
positions from up to 30 feet away from the breaker and outside the arc flash
hazard boundary.
b.
The remote racking device shall support utilization on any Frame Size 2 or
Frame Size 3 WL breaker (including fuse carriage on fused Frame Size 3 WL
breaker).
c.
The remote racking device shall be portable and weigh less than 30 pounds
(excluding cables and remote control panel).
d.
The remote racking device shall have integral torque overload sensing to
prevent damage to the breaker racking mechanism.
e.
The remote racking device shall allow breaker to be racked to any position
(disconnect, test, connect) regardless of the starting position of the breaker
and without the need for user input as to the starting position.
[Project Name]
[26 23 00] [16430]-12
f.
g.
2.
The 120v remote breaker racking device shall be attached to the factory
mounted switchgear brackets (field retrofit capable) and secured by locking
pins. No modification of the gear or circuit breakers shall be required for
installation or operation.
The remote racking device shall support field retrofit on Type WL Low
Voltage Switchgear.]
[SARRACS Cart
a.
Remote racking device shall consist of a Gear Motor mounted onto a mobile
metal frame. The frame shall be equipped with wheel brakes. The Gear Motor
shall be vertically adjustable via actuator control on the frame. The Gear
Motor shall be laterally movable with linear spring loading. The Gear Motor
shall incorporate a digital Encoder for position control and sensing. The
Gear Motor controls shall be located in a control box mountable on the
frame. The remote racking device shall be controlled from a portable
Operators Station connected to the remote racking device by a 75 foot
communications/control cable. The remote racking device shall be equipped
with the following features:
1.)
Aluminum frame with powder coat protection
2.)
Rear mounted Rubber wheels, front mounted casters
3.)
Weatherproof control cabinet with duplex receptacle for power
connection
4.)
120V power cord reel mounted on the frame
5.)
Three Phase Gear Motor with Digital Encoder to supply Racking
Power
6.)
Single Phase to Three Phase Variable Frequency Drive to control and
power the Gear Motor
7.)
Electrically Linear Actuator to supply vertical adjustment for the Gear
Motor Assembly
8.)
Motor Carriage Position Sensor
9.)
Programmable Logic Controller (PLC) to control and monitor the
system
10.)
Capacity to store 20 discrete breaker operating profiles
11.)
Touch Screen Operators Panel with ON/OFF Switch for Operator
control and monitoring
12.)
Adapters for breakers with racking screws
13.)
Gravel wheels, large diameter
14.)
Interlock defeating adapters
15.)
UPS for operation in areas with no 120v power
16.)
Cover for dust prevention
17.)
Breaker position indicator lights]
PART 3 - EXECUTION
3.1
Examine elements and surfaces to receive switchgear for compliance with installation
tolerances and other conditions affecting performance. Proceed with installation only after
unsatisfactory conditions have been corrected.
B.
3.2
CONNECTIONS
A.
3.3
Tighten bus joints, electrical connectors and terminals according to manufacturer's published
torque-tightening values. Install equipment-grounding conductors for switchgear with ground
continuity to main electrical ground bus.
ADJUSTING AND CLEANING
[Project Name]
[26 23 00] [16430]-13
A.
B.
Clean exposed surfaces using manufacturer recommended materials and methods. Touch-up
damaged coating and finishes using non-abrasive materials and methods recommended by
manufacturer. Eliminate all visible evidence of repair.
3.4
WARRANTY
A.
3.5
Equipment manufacturer warrants that all goods supplied are free of non-conformities in
workmanship and materials for one year from date of initial operation, but not more than
eighteen months from date of shipment.
[STARTUP SERVICES]
A.
B.
Train Owner's maintenance personnel on procedures and schedules for energizing and
de-energizing, troubleshooting, servicing and maintaining equipment and schedules.
C.
Verify that switchgear is installed and connected according to the Contract Documents.
D.
Verify that electrical control wiring installation complies with manufacturer's submittal
by means of point-to-point continuity testing. Verify that wiring installation complies
with requirements in Division [26] [16] Sections.
E.
END OF SECTION
[Project Name]
[26 23 00] [16430]-14