1SDH001330R0002
1SDH001330R0002
1SDH001330R0002
SACE Emax 2
Mechanical accessories............................................................304
1 - Mechanical Protection accessories.............................. 304
PBC: opening and closing pushbutton protection...............304
IP54 protection...................................................................304
HTC / LTC (1): Terminal-cover...............................................305
PB (1): Phase separators......................................................305
2 - Mechanical safety accessories.................................... 306
Circuit-breakers E1.2-E2.2-E4.2-E6.2
1 - Foreword
SACE Emax 2 is the new series of low voltage air circuit-breakers up to 6300 A, designed for managing all low
voltage electrical installations with the maximum efficiency: from industrial installations, marine applications,
conventional power generation and renewable energy installations, to buildings, malls, data centers and
communication networks.
2 - Contents
This manual contains all the useful information for:
• Facilitating the choice of the product and of the features required.
• Rapid access to all the necessary information for proper design.
• Proper use of all the features available with the solid-state protection trip units.
• All the supporting documentation.
• Link to management software.
3 - Standards
Emax 2 circuit-breakers and their accessories comply with the following international standards:
• IEC 60947
• EN 60947
• CEI EN 60947
• IEC 61000
• UL 1066
They comply with the following EC directives:
• "Low Voltage Directives" (LVD) no.. 2006/95/EC
• "Electromagnetic Compatibility Directive" (EMC) no. 2004/108/EC
Emax 2 circuit-breakers also feature a range certified according to these standards:
• Russian - GOST (Russia Certificate of Conformity)
• Chinese - China CCC (China Compulsory Certification)
Foreword The circuit-breaker must check and protect , in case of failure and malfunction, the installation components
that are connected to it. To perform this function, Emax 2 circuit-breakers offer a series of options, that can
be selected by the user according to the particular requirements of the installation.
For a good design, the main characteristics the components must be selected with the greatest care.
In order to help the design engineers in selecting the Emax2 circuit-breakers, a sheet is provided below
containing the main selection criteria for air circuit-breakers. This sheet can be completed (in whole or in part)
by the design engineer to guide subsequent design choices and can be used by the client for work contracts.
Besisdes, this sheet is a useful tool for rapid configuration in CAT selection software.
Device
Type of device
Circuit-breaker
Switch-disconnector
Standard
Reference standard
IEC (EN 60947-2)
UL (UL 1066-ANSI C37.50)
Mechanical characteristics
Insulation function
Yes
No
Nº poles
3
4
Installation version
Fixed
Withdrawable
Terminals
Horizontal/Vertical
Spread
Front
Extended front
Spread front
Floor
For 4x240 FcCuAl cable
NOTE: details of the terminals are given in Emax 2 catalogue available on the website http://
new.abb.com/low-voltage/products/circuit-breakers/emax2.
5 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Guide to the product choice | 1 - List for Emax 2 selection
ABB | SACE Emax 2
Electrical characteristics
Service rated voltage
400 V AC
415 V AC
500 V AC
525 V AC
690 V AC
______ V AC
Rated uninterrupted current (40°C) (Iu)
100 A 800 A 2500 A
200 A 1000 A 3200 A
250 A 1200 A 4000 A
400 A 1250 A 5000 A
600 A 1600 A 6000 A
630 A 2000 A 6300 A
Ultimate short-circuit breaking capacity (lcu)
42 kA 120 kA
50 kA 130 kA
66 kA 150 kA
85 kA 200 kA
100 KA a ______ V:
Service short-circuit breaking capacity (lcs)
According to the reference standard:______ % of Icu
Admissible rated short-time withstand current (Icw)
Without intentional delay (class A)
With intentional time-delay (category B):
1 s Icw ______ kA
3 s Icw ______ kA
NOTE: make sure that the combination of all the electrical values selected is available. For
further details, consult Emax 2 catalogue available on the website http://new.abb.com/low-
voltage/products/circuit-breakers/emax2.
6 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Guide to the product choice | 1 - List for Emax 2 selection
ABB | SACE Emax 2
NOTE: for full details on the operation of the electronic protections, see the relevant chapters
Ekip Dip protection trip unit (starting on page 18) and Ekip Touch protection trip unit
(starting on page 37).
7 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Guide to the product choice | 1 - List for Emax 2 selection
ABB | SACE Emax 2
NOTE: for full details on Emax 2 electrical and mechanical accessories see chapter “ Electrical
accessories” starting on page 292.
Electronic accessories
Electronic accessories
Ekip Measuring - Protection and measurements of voltage, power and energy
Ekip Signalling 10K/ 4K/ 2K/ 3T/ Modbus TCP - Programmable input and output contacts
Ekip Supply - Power supply for trip units and modules
Ekip COM - Communication with multiple protocols
Ekip Synchrochek - Synchronism between two power supply sources
Ekip Multimeter - Power supply and measurements from switchgear front
Ekip LCD - Interface with LCD display for particular environmental conditions
NOTE: for full details on Emax 2 electronic accessories see chapter “Electronic accessories”
starting on page 207.
8 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Guide to the product choice | 1 - List for Emax 2 selection
ABB | SACE Emax 2
Foreword It is possible to obtain selectivity between ABB SACE circuit-breakers (including Emax 2).
There is selectivity in an installation when, in the event of an overload or short-circuit, it is possible to identify
and isolate the point of overload or fault by opening only some circuit-breakers to guarantee service continuity
to the installation.
NOTE: selectivity is recommended in all installations with multiple switchgears or circuit-
breakers connected, for example cascading or in a tree (with a main circuit-breaker on the
supply side, and other circuit-breakers downstream to protect areas on the other side). Thus,
only the circuit-breaker immediately upstream the overload or fault trips, and avoids opening
of the circuit-breakers further upstream.
Types of selectivity With ABB SACE electronic trip units selectivity can be:
• Current-based selectivity, activated in the event of over-current, and in which the protections of the
trip units are set with different current thresholds, based on the principle the closer the fault point is to the
power supply the greater the current will be.
• Time selectivity, activated in the event of a short-circuit in which the S protection normally trips, and in
which the protections of the trip units are set with different tripping times, so that with cascading circuit-
breakers the circuit-breakers further downstream open before those further upstream.
• Time-current selectivity, which is a combination of the previously mentioned types, and in which the
protections of the trip units are set so that the tripping times and current thresholds increase with proximity
to the power supply.
• Energy selectivity, which uses current-limiting circuit-breakers, characterized by extremely short tripping
times in the event of a short-circuit to avoid the current reaching the peak value (in the case of ABB SACE
circuit-breakers, for example, all the moulded-case circuit-breakers of the Tmax series and certain air
circuit-breakers of the Emax series are limiters).
• Zone Selectivity, which is an evolution of time selectivity, and in which is a dialog created between the
trip units by means of output and input blocking signals. For more information on Zone Selectivity with
ABB SACE circuit-breakers and in particular Emax 2, see the chapter “Specific applications" starting on
page 156.
Further documents For each type of selectivity, the protections must be set so that only those circuit-breakers capable of isolating
the overload or fault open, without the rest of the installation being de-energized. Relevant definitions, operating
principles, areas of application, advantages and disadvantages, requirements, indications for setting the
protections and examples are provided in the Technical Application Paper QT1 1SDC007100G0205 "Low
voltage selectivity with ABB circuit-breakers".
1 - Foreword
Various software programs and documents are available that allow optimization of the performance and
installation of Emax 2. Most of them are available free on the internet.
2 - Software list
The following software programs are available for Emax 2.
e-Design ABB software suite that includes the following tools: DOC, CAT, Curves, DOCSolar, OTC and UniSec (for the
configuration of medium voltage switchgear).
Further information is available on the website abb.com (Overview) which is the direct link to download the
software (e-Design).
DOC ABB SACE software for designing and calculating single-line diagrams for low and medium voltage electrical
installations, for choosing protection and operating devices, and for checking and coordinating the protections.
DOC is available with the e-Design software suite.
CAT ABB SACE software for preparing technical/commercial estimates for ABB SACE products, and to facilitate
the creation of quotations and offers.
CAT is available with the e-Design software suite.
Curves Software for designing, calibrating and to printing the trip curves of the protection devices.
Curves is available with the e-Design software suite.
OTC Thermal calculation software that allows you to check the thermal behavior of switchgear and to size fans and
air conditioners to be installed in the switchgear
OTC is available with the e-Design software suite.
10 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Documents and Tools for the design engineer | 1 - Foreword
ABB | SACE Emax 2
Front CAD Software that provides libraries of graphical blocks for the products for ABB switchgear design to be used in
the context of the latest available versions of AutoCAD, AutoCAD LT and IntelliCAD.
Further information is available on the website abb.com (Front CAD) which is the direct link to download the
software (Front CAD).
NOTE: the link launches the software package download, which requires about 190 Mb of
space.
Trip Unit simulator It allows you to simulate the operation and the various programming options of the protection trip units.
Further information on the documentation is available on the website abb.com, in particular: Trip unit simulator.
Ekip Connect ABB SACE software for interfacing with the low voltage circuit-breakers equipped with a compatible
protection trip unit.
Further information on the documentation is available on the ABB library website, in particular: Ekip Connect,
and on Android market, in particular: App Ekip Connect.
Slide Rules App for sizing low voltage electrical cables according to the installation methods specified by current
regulations and installation practices.
Further information on the documentation is available on the Apple Store, in particular: Slide rules.
Ekip View It supervises the communication network. It analyzes changes in electrical values and the monitoring of the
installation conditions. The application is only available in English.
Further information is available on the website abb.com (Ekip View) which is the direct link to download the
software (Ekip View).
NOTE: the link starts the download of the software package, which requires approximately
1.3 Gb of space.
11 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Documents and Tools for the design engineer | 1 - Foreword
ABB | SACE Emax 2
3 - Documentation list
The documentation (brochures, flyers, White Papers, etc.) is listed below.
Brochure: History of air circuit- Presentation of the origin and evolution of ABB air circuit-breakers ABB for low voltage applications.
breakers Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200024B0201.
Brochure: retrofitting kit Overview of retrofitting kits for New Emax circuit-breakers.
Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200034L0202.
Product notes for consultants General overview of the features of Emax 2 circuit-breakers, specifically for consultants.
Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200032L0201.
Product notes for switchgear General overview of the features of Emax 2 circuit-breakers, specifically for switchgear engineers
engineers Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200028L0201.
Product notes the Ekip Link Introduction to the new Ekip Link switchgear control system
system Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200031L0202.
Product notes for Power Introduction to the new Power Controller load management system.
Controller Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200030L0202.
Product notes for generator General features for the new generator protections available with Emax 2 protection trip units.
protections Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200035L0202.
Product notes: migration to Advantages and details of migration from New Emax to Emax 2 circuit-breakers.
Emax 2 Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200036L0201.
12 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Documents and Tools for the design engineer | 3 - Documentation list
ABB | SACE Emax 2
White Paper for Ekip Power White Paper on the Power Controller function.
Controller Further information on the documentation is available on the ABB library website, in particular in the document
1SDC007410G0202.
White Paper for communication White paper of communication modules for Emax2.
Further information on the documentation is available on the ABB library website, in particular in the document
1SDC007412G0201.
Product Notes for IEC 61850 Overview of the new IEC 61850 communication modules.
Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200038L0201.
Product notes for Network Introduction to the new Network Analyzer measurement and analysis system.
Analyzer Further information on the documentation is available on the ABB library website, in particular in the document
1SDC200037L0202.
Handbook The scope of this manual for electrical installations is to provide the design engineer and the user of electrical
installations with a rapid access work tool.
Further information on the documentation is available on the ABB library website, in particular in the document
1SDC010002D0206.
13 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Documents and Tools for the design engineer | 3 - Documentation list
ABB | SACE Emax 2
1 - Presentation
Families and functionality SACE Emax 2 can be configured with five different types of protection trip unit, distinguished by type of
interface and functionality. One trip unit has a dip-switch interface (Ekip Dip) while the others are equipped
with a touchscreen display (Ekip Touch).
Figure 1
All trip units have protection and measuring functions that refer to the primary currents of the installation and
are available in the following versions:
• Ekip DIP: LI, LSI, LSIG
• Ekip Touch: LI, LSI, LSIG
• Ekip Hi-Touch: LSI, LSIG
• Ekip G Touch: LSIG
• Ekip G Hi-Touch: LSIG
The Ekip Touch trip unit can be equipped with the Ekip Measuring module to extend the measurement
functions, or the protection and measurement functions (with the Ekip Measuring Pro module), to voltage,
power and energy.
NOTE: Ekip Hi-Touch, Ekip G Touch and Ekip G Hi-Touch trip units have the Ekip Measuring
Pro module mounted as standard.
The corresponding LCD model (Ekip LCD, Ekip Hi-LCD, Ekip G LCD, Ekip G Hi-LCD) is available for all Ekip
Touch versions if the installation must operate under particularly aggressive environmental conditions.
The following chapters describe all the functional and usage specifications of the Ekip Dip and Ekip Touch
trip units, organised by topic:
• User interface: for correct use of the interface.
• Protections: description of the protections available with each model of the trip unit.
• Measurements: description of the measurements available for each trip unit.
• Test: to allow the operator to perform tests on the unit.
• Self-diagnosis: description of the integrated self-checking function on the trip unit.
• Accessories: presentation of all the accessory modules by trip unit and the related additional functions.
All characteristics are described for each protection trip unit:
Trip units Page
Ekip Dip 18
Ekip Touch 37
14 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Introduction to Ekip trip units | 1 - Presentation
ABB | SACE Emax 2
Protections Numerous protection functions are available to protect the circuit-breaker in abnormal conditions of the
installation. The combination of the protection functions varies depending on the type of trip unit, as shown
in the following table:
Dip Touch
DISTRIBUTION GENERATORS
G Hi-
Touch Pr.
External toroid
S.G.R. Rc
Touch trip units can be connected to an SGR or RC toroid, which allow activation, respectively, of the Gext
protections (page 287) and Rc protections to be activated (page 101).
15 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Introduction to Ekip trip units | 1 - Presentation
ABB | SACE Emax 2
Measurements The trip units include a huge range of measurements. As for the protections, availability and combinations
vary for each version of the trip unit:
Dip Touch
DISTRIBUTION GENERATORS
Dip Meas. Touch Meas. Touch Meas. Touch Meas. Touch Meas.
Integrated functions: Self- All the protection trip units for Emax 2 integrate:
diagnosis, Test and Power • Self-diagnosis: continuous monitoring of the state of the internal and external connections, with signalling
Controller of any faults that may occur.
• Test: checking of the protections and of the other functionalities.
In addition, trip units of the Ekip Touch series can be supplied equipped with Power Controller to manage
the energy demand.
Dip Touch
Self-diagnosis
Test
Power Controller
DISTRIBUTION GENERATORS
The additional functions are described for each protection trip unit:
Trip units Available functions Page
Ekip Dip Test, self-diagnosis 28, 29
Ekip Touch Test, self-diagnosis, Power Controller 118, 120, 131
16 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Introduction to Ekip trip units | 1 - Presentation
ABB | SACE Emax 2
Accessorizing modules The Emax 2 circuit-breakers and Ekip trip units can be equipped as indicated in the combination tables on
page 195.
Various types of modules are available, differing in functionality and in their position on the circuit-breaker.
The modules that can be connected directly to the electronic trip unit are:
Name Description Page
Ekip Measuring
Power supply, protection and measurement modules. 210
Ekip Measuring Pro
Ekip Signalling 4K Signalling module 224
NOTE: the Ekip Signalling 4K module is not available for E1.2 circuit-breakers.
The modules available for the terminal box of the circuit-breaker are:
Name Description Page
Ekip Supply Power supply module 208
Ekip Signalling 2K Signalling module 231
Ekip Signalling 3T Signalling module 239
Module for measuring voltage and synchronism between
Ekip Synchrocheck 216
two power sources
Ekip Com Modbus RTU
Ekip Com Profibus DP
Ekip Com DeviceNet™
Ekip Com Modbus TCP
Communication module 243
Ekip Com Profinet
Ekip Com EtherNet/IP™
Ekip Com IEC 61850
Ekip Com Hub
Link Communication module 275
The supervision, configuration and reporting functions are, in addition, guaranteed by further modules for
temporary power supply and communication (test modules):
Name Description Page
Ekip TT Power supply and test module 289
Ekip T&P Power supply, communication and test module 289
Ekip Programming Power supply, communication and programming module 289
Ekip Bluetooth Power supply and communication module 288
Information about the LCD version of the trip units is available from page 287.
17 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Introduction to Ekip trip units | 1 - Presentation
ABB | SACE Emax 2
1 - Operator interface
Introduction The operator interface of the Ekip Dip protection trip unit allows you to:
• Set the parameters relating to the available protections.
• View the status of the trip unit and alarms.
• Connect to the frontal connector to communicate and perform the opening test.
Components of the interface The Ekip Dip operator interface appears as follows:
Figure 2
IMPORTANT: the figure above refers to an Ekip Dip, LSIG version. In the case of Ekip
Dip LI or LSI versions, LEDs and dip-switches related only to the protections present
are available.
LEDs The LEDs are useful on Ekip Dip in order to distinguish and identify various types of information on the
protection trip unit, the circuit-breaker and state of the line currents.
Operational conditions
The operation of the LED is determined by the power supply conditions of the trip unit:
• With the trip unit energized (by current sensors or by auxiliary power supply or by Ekip TT or by Ekip T&P
or by Ekip Bluetooth) the LEDs are operational for all the signals.
• With the trip unit de-energized, the LEDs are limited to the signalling of the last switch-off or trip event
(combined with the check via iTest, described below).
NOTE: with the trip unit off, the operation of the LEDs is guaranteed if the internal battery of
the trip unit is working properly.
About
The LEDs combined with the protections provide various information, through different combinations of
lighting and blinking.
NOTE: all the combinations related to protection LED signals are described in chapter Self-
diagnosis and signalling , on page 29.
The power-on LED provides information about the power status of the protection trip unit:
• LED on (default configuration) fixed or blinking, signals trip unit energized.
• LED off signals trip unit de-energized.
NOTE: with Ekip T&P and Ekip Bluetooth modules and Ekip Connect software, it is possible
to configure how the power LED functions (LED fixed or blinking).
Protections: thresholds The thresholds of all the protections can be modified with various dip-switches, as specified on the serigraph
of the interface.
The values of the protections make reference to the current In, a nominal value of the trip unit defined by the
Rating Plug.
IMPORTANT:
• Modification of the thresholds must be performed in the absence of protection alarms.
• Modifications carried out in alarm conditions are accepted by the trip unit when resting
condition is restored (absence of protection alarms).
Protections: times The times and the curves of the protections can be modified with various dip-switches, as specified on the
serigraph of the interface.
IMPORTANT:
• Modification of the times must be performed in the absence of protection alarms.
• Modifications carried out in alarm conditions are accepted by the trip unit when resting
condition is restored (absence of protection alarms).
• the power-on LED, if the trip unit is off due to an energy drop (primary current less than the
minimum level of operation, removal of auxiliary power supply with circuit-breaker open, etc…).
• the protection tripped LED if the trip unit is off due to a protection trip.
Test connector The test connector allows the connection of Ekip TT, Ekip T&P and Ekip Bluetooth modules, in order to
perform the following operations:
• Temporary energizing of the trip unit to check the status, and perform the trip test (option possible with
all the front interface modules).
• Analysis, supervision and setting of additional parameters through external communication test units (Ekip
T&P, Ekip Bluetooth).
19 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 1 - Operator interface
ABB | SACE Emax 2
2 - Protections
NOTE: the protection is available and active for all the versions of the trip unit.
When the activation threshold is exceeded, the protection trips in a time that decreases as the current read
t I1 L increases.
Parameters
t1 All the parameters that can be modified by the user affect the response curve, and related tripping times.
I Parameter Description
The value I1 contributes in calculating the tripping time, and also defines the current
value that, if exceeded, activates the protection (with reference to the curve, it is the
part parallel to the y-axis).
Threshold I1 IMPORTANT:
• The protection is activated and starts timing for currents between
1.05 and 1.2 of the threshold I1 set (1).
• The delay is interrupted if the current drops below the activation
threshold.
The value t1 contributes in calculating the tripping time (with reference to the curve,
T1 affects the entire curve by shifting it as a whole along the y-axis).
Time t1 IMPORTANT:
The protection limits the tripping time to 1 second in two cases:
• if, according to the calculation, the time is less than 1 second.
• If the fault current is greater than 12 In.
Example (with I1 set to 400 A): the protection is activated for currents between 420 A and
(1)
480 A.
With the modules Ekip T&P or Ekip Bluetooth and with the Ekip Connect software, it is possible to activate
the function Thermal Memory, and adjust the threshold of Pre-alarm. See page 25.
20 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 2 - Protections
ABB | SACE Emax 2
NOTE: the protection is available for LSI and LSIG versions of the trip unit.
When the activation threshold is exceeded, the protection trips within a fixed or dynamic time (the time
t I2 S decreases as the current reading increases).
Parameters
t2 All the parameters that can be modified by the user affect the response curve, and related tripping times.
Parameter Description
I Enable By setting the threshold dip-switches to the Off position, the protection is disabled.
It determines the dynamic of the curve and the tripping time, fixed or dynamic
according to the selection:
Type of curve
NOTE: calculation of the tripping time of the inverse time curve is based on a
mathematical expression. The details are provided in the table on page 26.
It defines the current value that activates the protection when exceeded (with
reference to the curve, it is the part parallel to the y-axis).
IMPORTANT:
Threshold I2
• The I2 threshold set must be higher than the I1 threshold. An
incorrect configuration returns an alarm signal.
• The delay is interrupted if the current drops below the activation
threshold.
The selected function determines the contribution of t2:
• Fixed time: t2 is the delay time between exceeding the I2 threshold and sending
the opening command.
• Dynamic time: t2 contributes in calculating the tripping time (with reference to the
curve, t2 affects the entire curve, shifting it as a whole along the vertical axis).
Time t2
IMPORTANT:
• The minimum tripping time of the protection is t2. If, according to
the calculation, the tripping time is less, it is automatically limited to t2.
• For all the UL versions, the maximum time allowed by the trip unit
is 0.4 s. If a higher value is set, the trip unit signals the error and forces
the parameter to 0.4 s.
With the modules Ekip T&P or Ekip Bluetooth and with the Ekip Connect software, it is possible to activate
the function Thermal Memory. See page 25.
21 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 2 - Protections
ABB | SACE Emax 2
Parameters
t I3 I The user can set the intervention threshold.
Parameter Description
t3 Enable By setting the threshold dip-switches to the Off position, the protection is disabled.
It defines the current value that activates the protection when exceeded (with
reference to the curve, it is the part parallel to the y-axis).
I Threshold I3
IMPORTANT: The I3 threshold set must be higher than the I2
threshold. An incorrect configuration returns an alarm signal.
22 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 2 - Protections
ABB | SACE Emax 2
NOTE: the protection is available for the LSIG version of the trip unit.
When the activation threshold is exceeded, the protection trips within a fixed or dynamic time (the time
t I4 G decreases as the current reading increases).
Parameters
t4 All the parameters that can be modified by the user affect the response curve, and related tripping times.
Parameter Description
I By setting the dip-switches of the threshold in one of the available combinations
other than Off, the protection is enabled.
If enabled, the protection is inhibited automatically by the trip unit under two
conditions:
• Disconnection of one or more current sensors.
• Current measured on one of the phases higher than a maximum value.
Enable
IMPORTANT: the maximum current value that deactivates G protection
varies according to the threshold set:
• 8 In (with I4 ≥ 0.8 In)
• 6 In (with 0.5 In ≤ I4 < 0.8 In)
• 4 In (with 0.2 In ≤ I4 < 0.5 In)
• 2 In (with I4 < 0.2 In)
It determines the dynamic of the curve and the tripping time, fixed or dynamic
according to the selection:
Type of curve
NOTE: calculation of the tripping time of the inverse time curve is based on a
mathematical expression. The details are provided in the table on page 26.
It defines the current value that activates the protection when exceeded (with
reference to the curve, it is the part parallel to the y-axis).
IMPORTANT:
Threshold I4 • The delay is interrupted if the current drops below the tripping
threshold.
• For all the UL versions the maximum threshold allowed by the trip
unit is 1200 A. If a higher value is set, the trip unit signals the error and
forces the parameter to 1200 A.
The selected function determines the contribution of t4:
• Fixed time: t4 is the delay time between the exceeding of the I4 threshold and the
sending of the opening command.
• Dynamic time: t4 contributes in calculating the tripping time (with reference to the
curve, t4 affects the entire curve, shifting it as a whole along the y-axis).
Time t4
IMPORTANT:
• The minimum tripping time of the protection is t4. If, according to
the calculation, the tripping time is less, it is automatically limited to t4.
• For all the UL versions, the maximum time allowed by the trip unit is
0.4s. If a higher value is set, the trip unit signals the error and forces the
parameter to 0.4 s.
With the Ekip T&P or Ekip Bluetooth modules and with the Ekip Connect software, it is possible to adjust the
threshold of Pre-alarm. See page 25.
23 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 2 - Protections
ABB | SACE Emax 2
Neutral and frequency Adjusting of the neutral setting is used to customize the L, S and I protections on the Neutral pole with a
control factor different from the other phases.
NOTE: use the adjustment of the neutral setting only with four-pole or three-pole circuit-
breakers with external neutral: with three-pole circuit-breakers and neutral protection active,
the trip unit signals the absence of the current sensor.
The adjustment of the frequency is used in order to set the installation frequency (between 50 and 60 Hz).
Neutral parameters
The user can activate the protection and set the percentage for calculation of the protection thresholds.
Parameter Description
By setting the threshold dip-switches to the Off position, the protection on the
Enable
Neutral is disabled.
Represented as a percentage; it defines the multiplication factor applied to the
tripping thresholds of the protections:
Threshold InN • 50%: trip threshold of the neutral current lower than other phases.
• 100%: same trip thresholds for all poles.
• 200%: trip threshold of the neutral current higher than other phases.
Limitations
The adjustment of the Neutral threshold to value of 200 % must be performed considering the following
formula: (I1 * InN) ≤ Iu.
I1 indicates the threshold of L protection in Amperes (example: In = 1000 A; I1 = 0.45 In = 450 A), InN is the
neutral threshold expressed as a multiplication factor (example: 2), Iu indicates the size of the circuit-breaker
(example: 1000 A).
24 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 2 - Protections
ABB | SACE Emax 2
Additional protections The Ekip T&P and Ekip Bluetooth modules, and the Ekip Connect software, allow you to set some protections
not available via dip-switch:
• Thermal Memory
• T Protection
• Prealarm threshold
• Hardware Trip
Thermal Memory
This function, available for protections L and S, reduces the tripping time of the protection based on the time
elapsed between multiple trips caused by heating of the cables.
NOTE: for correct calculation of the time between the various trips, the trip unit must have
been powered for at least one 1 second.
IMPORTANT: for the S protection the function can be activated if the selected curve
is time-dependent.
T Protection
T protection protects the circuit-breaker against abnormal temperatures recorded by the protection trip unit.
T protection is always active; via Ekip Connect it is possible to enable tripping, which takes place for
temperatures t < -25 °C or t > 85 °C.
Pre-alarm
The purpose of the pre-alarm, available for L and G protections, is to signal that the measured current is near
the activation threshold of the protection itself.
It is possible to set the pre-alarm threshold in order to establish the pre-alarm activation values; the pre-alarm
threshold is expressed as a percentage in relation to the protection thresholds (I1 and I4) and is adjustable
between 50% and 90% (default value).
Example: with I1 = 0.6 In and pre-alarm threshold L=50 %, the pre-alarm is activated for currents greater
than 0.3 In
The pre-alarm condition is activated for currents higher than the threshold set, and is deactivated for:
• Current less than the pre-alarm threshold.
• Current greater than the activation threshold of protection.
Hardware Trip
Hardware Trip protection protects against internal disconnections of the circuit-breaker. Via Ekip Connect
it is possible to enable the trip command, which is sent if one or more of the following events is detected:
• Current sensors disconnected (internal or external if enabled).
• Rating Plug disconnected.
• Trip Coil disconnected.
• Internal problems with the protection trip unit.
IMPORTANT: the protection trips if the error conditions persist for more than 1 second.
25 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 2 - Protections
ABB | SACE Emax 2
(1)
See the serigraph for the available combinations.
(2)
t t calculation is valid for If values that have exceeded the trip threshold of the protection. Use fault current and threshold values expressed in In to
calculate t t, as shown in the example.
(3)
Tolerances valid with trip unit energized in service conditions or with the auxiliary; tripping time ≥ 100 ms, temperature and currents within operating
limits. If these conditions are not guaranteed, the tolerances in the table shown below apply.
(4)
In the presence of auxiliary power supply, you can select all the thresholds. In self-supply mode the minimum threshold is limited to: 0.3 In (with In
= 100 A), 0.25 In (with In = 400 A) or 0.2 In (for all other sizes).
(5)
ANSI / IEEE C37-2 encoding.
Key
• (t=k) - Fixed time curve
• (t=k/I2) - Dynamic time curve
• tt - Tripping time
• If - Primary fault current
Tolerances in particular cases
If the conditions defined in point (3)
of the above table are not guaranteed, the following tolerances apply:
Protection Tolerance threshold Tolerance t t
L Activation for If in the range (1.05...1.2) x I1 ± 20 %
S ± 10 % ± 20 %
I ± 15 % ≤ 60 ms
G ± 15 % ± 20 %
26 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 2 - Protections
ABB | SACE Emax 2
3 - Measurements
Introduction Measurements The Ekip Dip trip unit records various items of information, useful for analysis and consultation:
• Instantaneous measurements of phase currents
• Measurement of the maximum and minimum currents recorded with an adjustable interval
• Trip Log
• List of events, changes of state and alarms recorded by the trip unit
• Contact Wear value
• Number of mechanical and electrical operations.
NOTE: all the information is available with Ekip T&P and Ekip Bluetooth modules and with
the Ekip Connect software. The instantaneous measurements are also available with the Ekip
Multimeter switchgear unit.
Instantaneous currents The following table summarises the measurements of the instantaneous currents:
NOTE: the precisions specified in the table refer to the range of normal operation
Maximum and minimum The trip unit is able to record the maximum and minimum current, measured inside an interval that can be
currents programmed by the user.
Every measurement recorded is accompanied by the following information:
• Recording interval.
• Phase and value of maximum and minimum current measured.
• Date and time of the recording (referring to the internal clock).
NOTE: in the case of the minimum current, if the value drops below the 0.03 In threshold, it
will be recorded and represented by the symbol “…” in the measurement field.
Trips The trip unit is able to record the last 30 openings of the circuit-breaker caused by protection functions (trips).
The trips include useful information:
• The protection that caused the trip
• The progressive number of the opening
• The date and time of the opening (referring to the internal clock)
• The measurements associated to the trip protection.
Contact Wear Contact wear indicates the state of deterioration of the main contacts of the circuit-breaker.
The value is expressed as a percentage, and is 0 % in the case of no wear, and 100 % in the case of total
wear.
The contact wear is calculated automatically by the trip unit at every opening for protection or, in the presence
of an auxiliary power supply, also at every manual opening of the circuit-breaker.
Number of operations In the presence of auxiliary power, the trip unit records a series information relating to the openings of the
circuit-breaker:
• Number of manual operations
• Total number of operations (manual + trips)
27 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 3 - Measurements
ABB | SACE Emax 2
4 - Test
Presentation The Ekip TT, Ekip T&P and Ekip Bluetooth modules connected to the Ekip Dip trip unit allow you to perform
various tests:
• Trip unit LED test
• Check on the presence of the internal battery
• Circuit-breaker opening test (trip test)
• Protection test.
LED test The LED test can be performed directly on Ekip Dip:
Phase Operation
1 Connect a module to the front test connector of frontal test.
2 Press the iTest pushbutton for at least 6 seconds, but less than 9 seconds.
3 When the protection LEDs light up, trip unit the iTest pushbutton.
Check the following switch-on sequence:
• S, I, G LEDs on fixed
4
• Led pre-alarm L and alarm L that alternate three times
• All the protection LEDs off
Battery test The battery check is integrated in the LED test procedure, except for the battery error signal:
• If the battery is absent or not working, after iTest is pressed the error is signalled by five flashes of the
pre-alarm LED L.
• If the battery is present and working, the LED test proceeds as in the normal procedure.
Protection test In order to perform the protection test, follow the instructions below:
Phase Operation
1 Make sure that the circuit-breaker is closed and that there are no primary currents.
2 Connect Ekip T&P or Ekip Bluetooth to the front test connector.
3 Start the communication with Ekip Connect.
4 Open the Information page and select the Test command, which opens the protection test page.
5 Set up the test as required and verify that the trip unit functions properly.
Opening test The opening test can be performed directly on the trip unit or from Ekip Connect.
To perform the test from the trip unit:
Phase Operation
1 Make sure that the circuit-breaker is closed and that there are no primary currents.
2 Connect a module to the front test connector of frontal test.
3 Press the iTest pushbutton for at least 9 seconds.
4 Check that the circuit-breaker opens and that the TU Reset button comes out
28 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 4 - Test
ABB | SACE Emax 2
LED view The Ekip Dip trip unit continuously monitors its own operating condition and that of all the devices to which
it is connected. All the signals are available with the front LEDs.
The protection LEDs provide information with various combinations of lighting and flashing, while the power-
on LED, as described on page 19, indicates the power-on conditions of the trip unit.
Figure 3
NOTE: the number of LEDs depends on the version of the trip unit (LI, LSI, LSIG).
29 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 5 - List of alarms and signals
ABB | SACE Emax 2
(1)
The temperature alarm is signalled by lighting of the protection L and I red LEDs.
(2)
The last trip can also be displayed with trip unit off, by pressing the iTest key.
(3)
The Hardware Trip is signalled by lighting of the pre-alarm L yellow LED and the protection I red led.
(4)
Five flashes when self-test is started up
(5)
Error present with one of the three flashing options displayed alongside.
NOTE: for further details refer to the table listing the components of the interface, available on page 18.
30 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 5 - List of alarms and signals
Continued from the previous page ABB | SACE Emax 2
HELP
Some LED signals indicate connection errors or operational errors that require corrective or maintenance
operations. The following are the suggestions for checking with reference to the preceding LED table:
HELP
Operation
note
A Contact ABB and give details about the state of the LEDs on the unit.
Check the connections between trip unit and accessories (Rating Plug, trip coil, sensors,
B
etc).
C Normal operation/signalling provided by the trip unit.
Error in setting of the dip-switches. Check and correct the following conditions:
• All the dip-switches of L are in the ON position
• I1 ≥ I2 or I2 ≥ I3.
• Iu < (2 * In * I1) in the case where InN = 200 %.
D • I4 < 0.3 In (con In = 100 A), 0.25 In (con In = 400 A) or 0.2 In (for all other sizes), in the
absence of auxiliary power supply.
• t2 > 0.4s (in the case of UL circuit-breaker)
• t4 > 0.4s (in the case of UL circuit-breaker)
• I4 > 1200 A (in case of UL circuit-breaker)
E Carry out installation.
F Connect via Ekip Connect in order to set the Local Bus or to confirm maintenance.
G Contact ABB to restore software compatibility between Ekip Dip and Mainboard.
H Replace the battery.
31 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 5 - List of alarms and signals
ABB | SACE Emax 2
Presentation Ekip T&P, Ekip Programming and Ekip Bluetooth allow the protection trip unit to be connected to Ekip
Connect software and to access parameters and commands that cannot be accessed directly from the front
interface: a description of the various functions is given below.
The additional protections available via Ekip Connect are described on page 25.
Maintenance The Maintenance function allows signalling to the user, via LED, that:
• One year has passed since the last maintenance.
• Contact wear has increased by more than 10% compared with the value at the last maintenance.
Via Ekip Connect there are two selections available:
• Activation: it allows to the maintenance function to be activated.
• Reset: it allows confirmation of maintenance on the trip unit; the present date and contact wear values
are recorded, and the signal is reset.
The reference date is that of the internal clock, and the elapsed time is calculated both with the trip unit on
and off (provided that the internal battery is working).
NOTE: manual modification of the date can cause variations in the calculation of the time
elapsed, and therefore in the date of the next maintenance.
NOTE: the maintenance signal due to increased contact wear is active for values higher than
20 %.
Local Bus In order to activate communication on the Local Bus with the Ekip Link, Ekip Multimeter or Ekip Signalling
10K modules, the Local Bus parameter must be enabled.
NOTE: communication with the modules is active if the auxiliary power supply is present.
Date and time The Ekip Dip trip unit has a user-adjustable internal clock.
Setting the date can be useful for some functions such as the recording of trips and minimum and maximum
currents, and maintenance.
The clock is active if the internal battery of the trip unit is working.
32 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 6 - Ekip Dip: additional functions
ABB | SACE Emax 2
Programmable States There are sixteen independent programmable states identified by the letters A, B, C, D, E, F, G, H, I, L, M, N,
O, P, Q, R, offering different solutions for event control.
The value of each programmable state can be either "True" or "False". Different configuration parameters are
available:
• Trigger: event or combination of more events of state activation (up to 24, in AND or OR logic configuration).
• On Delay: state activation delay calculated from trigger presence onwards.
• Off Delay: state de-activation delay calculated from trigger absence onwards.
NOTE: the state become activate if the trigger is present for longer than the On delay setting
and become inactive if the trigger is absent for longer than the Off delay setting.
Trigger State
Delay ON
Delay OFF
Delay ON Delay OFF
Programmable State
TRUE
FALSE
The states can be used with the external Ekip Signalling 10K module, on Link Bus or with the programmable
functions, to transfer the desired signalling combination on contacts.
Programmable Functions Ekip Dip allows you to program five commands so that they are automatically activated according to the
signalling state or the events selected by the user. The commands are:
• Trip
• Reset of the trip signal.
• Reset signalling contacts of the Ekip Signalling 10K module.
• Opening coil command (YO).
• Closing coil command (YC).
Each command provides two programming parameters:
• Activation function: event or events (up to eight, in logical AND or OR configuration) that activate the
command.
• Delay: command sending delay, calculated starting from the occurrence of the activation event.
NOTE: the command is sent if the event is present for a time greater than the delay that has
been set.
NOTE: the YO and YC commands are possible only if the coils and Ekip Actuator are present,
and if all the operating conditions exist (see page 118).
33 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 6 - Ekip Dip: additional functions
ABB | SACE Emax 2
Circuit-breaker label and user Labels that can be configured by the user so as to facilitate remote identification of the trip unit; in detail the
Data CB label, the trip unit model and the communication address form the identifier used by Ekip Connect for
the devices connected.
Info Page Additional information page that can be activated and customized by the user. If activated, it can be accessed
on the display by pressing the iTest button twice from the main page.
NOTE: the pages can be configured with all the trip units for SACE Emax 2 circuit-breakers,
but they can only be displayed via Ekip Touch.
Load Profile Timers SACE Emax 2 has 4 counters which display how long the maximum current measured has remained in each
percentage band.
The counters are expressed in seconds and the bands are: 0-49%In, 50-79%In, 80-89%In, >90%In.
Energy Store Time The counter indicates the time that has elapsed since the last energy metering reset.
It is active and updated in the presence of at least one of the following: auxiliary supply, supply by Ekip T&P
or supply by Ekip Measuring.
Led Alive The parameter allows the behaviour of the power-on LED indicator of the trip unit and of all modules that can
be connected to Ekip Supply to be changed. If activated:
• Trip unit: it comes on at a frequency of 0.5 Hz.
• Modules connected to Ekip Supply: if there are no communication errors, they synchronize with the flashes
of the trip unit LED.
If deactivated, the power-on leds on the respective devices come on with a steady light.
Open/Close Remote Direct The parameter controls two different command packages for remote circuit-breaker opening and closing:
Command • Enabled: commands 7 and 8 are valid (direct commands for CB Open and CB Close).
• Disabled: commands 7 and 8 are not valid.
IMPORTANT: in this case, remote circuit-breaker opening and closing can still be
obtained using the programmable YC COMMAND and YO COMMAND functions and
the Request circuit-breaker opening (28) and Request circuit-breaker closing (29)
commands.
Modules network settings It allows the communication parameters of the circuit-breaker to be controlled if the trip unit is replaced:
retention • Overwrite: the parameters of the new trip unit are valid, so it is advisable to make sure that the communication
parameter settings suit the communication network.
• Keep module data: the new trip unit updates its communication parameters with the ones in the Ekip
Com modules of the circuit-breaker, used up to that moment in the various communication networks.
The trip units are supplied with the parameter set as Overwrite.
Wink The command allows the power-on LED on the protection trip unit to flash at 3 Hz so as to physically identify
a trip unit that would not be identifiable in other ways.
3 Hz flashing is disabled by sending another Wink command or by switching off the trip unit.
Glitch The commands of Glitch 16 to 23 activate the respective glitch registers, which can be used for customizing
programmable functions or output contacts.
34 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 6 - Ekip Dip: additional functions
ABB | SACE Emax 2
7 - Operating features
Primary operating currents The Ekip Dip trip unit can be powered directly by the internal current sensors, with clearly defined primary
currents.
The operating conditions for proper operation are listed below:
Parameter Operating limits
> 80 A (E1.2-E2.2-E4.2)
Minimum three-phase turn-on current
> 160 A (E6.2)
Rated frequency 50 / 60 Hz ± 10 %
Harmonic distortion Conforming to 60947-2
Auxiliary power supply The Ekip Dip trip unit can be connected to an external auxiliary power source, useful for activating some
functions such as communication on the Local Bus or recording of manual operations.
The auxiliary power can be supplied by the modules of the Ekip Supply range (for further functional details,
see page 208), or with direct connection to a terminal box.
The direct connection must be made guaranteeing the following operating conditions:
Parameter Operating limits
Voltage 24 V DC galvanically isolated
Tolerance ± 10 %
Maximum ripple ±5%
Maximum inrush current @ 24 V 10 A per 5 ms
Maximum rated power @ 24 V 4W
Insulated with a two-pole shielded cable (Belden
Connection cable
3105A type or equivalent)
35 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 7 - Operating features
ABB | SACE Emax 2
8 - Default parameters
The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front DIPs
(protections, Frequency, Neutral), other via front bus.
Protection/Parameter Value
L 1 In; 144 s
S (1) Off; 0.1 s
I 4 In
G (1) Off; 0.1 s
Frequency 50 Hz (IEC) / 60 Hz (UL)
Off (for three-pole circuit breakers).
Neutral
50 % (for four-pole circuit-breaker)
Hardware Trip Disabled
Monitor time 5 minutes
Local Bus Disabled
Alive LED Disabled (Power-on LED fixed)
Maintenance Off
(1)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.
36 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Dip protection trip unit | 8 - Default parameters
ABB | SACE Emax 2
Functions of the interface The operator interface for Ekip Touch trip units allows to:
• Dislpay signals and measurements related to the functions in progress, or recorded events.
• Configure the circuit-breaker, and the installation parameters.
• Set the parameters for available protections and for other functions of the trip unit.
• Set parameters for the connected accessory modules.
• Perform tests.
• Display information on the circuit-breaker, trip unit, and connected accessory modules.
Components of the interface The operator interface for the Ekip Touch trip units appears as follows:
B
C
03:55 D
528.9A
E
L1
95.3V
U12 F
U12 U23 U31 L1 L2 L3 Ne
Figure 4
The following table provides a description of the parts of the interface:
Pos. Description
A Touchscreen display.
B Power LED, green.
C LED Warning, yellow.
D LED Alarm, red.
E The HOME key accesses the main page, or the initial page.
iTEST key. If the main page or a level 2 page is displayed (see below), whenever you press on it
the following pages are displayed in succession:
• List of Alarms, if there are any messages.
• Protection unit, with information on Mainboard and trip unit.
F
• Circuit-breaker, with information on the circuit-breaker.
• Last opening, with information on the last opening.
If the Trip Test item has been selected in the Test menu, it will execute the opening command
when pressed and held for at least 7 seconds.
G Test connector.
37 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 1 - Layout of the interface
ABB | SACE Emax 2
Signallings The following table provides a description of the signals of the interface:
LEDs Description
The possible states are:
• Off: power supply absent.
Green • On, fixed or flashing: power supply present, and trip unit on.
NOTE: if the trip unit is off and no opening has taken place, if you press the iTEST key
the LED comes on for 6 s.
The possible states are:
• Off: no warning or error.
• On, blinking rapidly: absence of communication between trip unit and Mainboard, or
Yellow installation error (of the Rating Plug, or the Ekip Measuring module, or Ekip Measuring Pro).
• On, flashing slowly: internal error.
• On, with two quick flashes every 0.5 s: parametrization error.
• On, fixed: prealarm of protection L, or circuit-breaker state error.
The possible states are:
• Off: no alarm or error.
• On, blinking rapidly: absence of communication between trip unit and Mainboard, or trip coil
Red disconnected, or current sensor disconnected, or delay active.
• On, with two quick flashes every 2 s: rating plug error.
• On, flashing slowly: internal error.
• On, fixed: tripping signal.
Structure of the pages The following table shows how the pages shown on the display are structured:
NOTE: the level 3 pages are not graphical pages, and are dealt with in chapter “6 - Menu”
on page 46.
38 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 1 - Layout of the interface
ABB | SACE Emax 2
Diagnosis bar The diagnosis bar is present on the main page and on level 2 pages, along the lower side of the display.
The bar appears as follows:
TC disconnected
Figure 5
The following table provides a description of the various areas of the bar:
Pos. Description
It shows the type of message:
• Alarm
• Active timing
B It displays the active messages one by one in a loop.
C ABB logo.
Figure 6
The following table provides a description of the various areas of the page:
Pos. Function
A It opens the Histograms page.
B It opens the Menu page.
C It opens the Measuring instruments page.
D It opens the Measurements page.
E In the presence of messages, it opens the Alarm List page.
39 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 1 - Layout of the interface
ABB | SACE Emax 2
Start page To open the page, press the HOME key until the page is displayed.
The system returns automatically to this page after some minute of inactivity.
The default start page is the Histograms page.
Any graphical level 2 page (accessible from the main page) can be set as the start page, except for the
pages Alarm List and Menu.
To set a page as the start page, you need to:
1. Open the page
2. Keep the HOME key pressed for at least 5 seconds.
3. Select Yes in the confirmation window that appears on the display.
Navigation The following table shows how to access the pages through the keys:
(1)
The Info page displays five lines of twenty characters each containing alphanumeric data that the customer
can insert through the Ekip Connect software (see the chapter "17 - Other accessories", and the paragraph "
Ekip Connect software" on page 288). To be displayed, it must be enabled (see the chapter "6 - Menu", and
the paragraph "Settings Menu" on page 49).
40 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 1 - Layout of the interface
ABB | SACE Emax 2
Description The page Alarm List shows the list of messages present.
The Alarm page is available:
• By touching the diagnosis bar, in the message display area.
• By pressing the key iTEST.
NOTE: when the menus, or the pages that can be accessed from them are displayed, the
key iTEST doesn't open the page Alarm List.
The page orientation (horizontal by default) can be changed from the Settings menu, by selecting System -
View (see the chapter "6 - Menu", and the paragraph "Settings Menu" on page 49).
Alarm List
TC disconnected
RatingPlug
C
RatingPlug installation
CB undefined
Figure 7
The following table provides a description of the various areas of the page:
Pos. Function
A It opens the page displayed previously
B It shows the name of the page
It shows the list of messages of:
• Alarm
• Active timing
41 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 2 - Alarm List Page
ABB | SACE Emax 2
3 - Histograms Page
I
Figure 8
The following table provides a description of the various areas of the page:
Pos. Description
Y-axis of the histogram, with the measurements expressed as percentage of the nominal values
A
set.
Bars that represent the measurements of phase-to-phase voltages U12 U23 U31, and of the
phase currents L1 L2 L3 and of the neutral Ne:
• In blue: no alarm.
• In yellow: voltage or current in prealarm, compared with the thresholds set (see the chapter "
B
9 - Touch protections" from page 61, and the chapter "10 - Measuring Pro protections" from page
75).
• In red: voltage or current in alarm, compared with the thresholds set (see the chapter "9 - Touch
protections" from page 61, and the chapter "10 - Measuring Pro protections" from page 75).
X-axis of the histogram.
C NOTE:
• The voltage histograms are shown with the Ekip Measuring accessory module.
• The Ne current histogram is shown with circuit-breaker configured with neutral.
42 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 3 - Histograms Page
Continued from the previous page ABB | SACE Emax 2
Pos. Description
Signalling and functions in progress:
• Remote connection, visible with auxiliary voltage and Ekip Com accessory
modules.
D
• o Auxiliary voltage or Test connection.
• or If the Dual Set function is enabled (see Settings menu), the letter
identifies the activated configuration.
E Current time.
• Measurement of the maximum phase current, as an absolute value (Ampere).
F
• Phase to which the measurement refers.
Displayed with the Ekip Measuring module:
G • Measurement of the maximum phase-to-phase voltage, as an absolute value (Volt).
• Concatenated to which the measurement refers.
Viewed with the Ekip Measuring module, it indicates the presence of several pages,
H that you can scroll through by touching the sides of the display, and in which of these
pages you are.
I Diagnosis bar.
Possible operations If Ekip Measuring or Ekip Measuring Pro are installed, access the histogram page and press the sides of the
display to access a page containing a summary of the main measurements (maximum phase current, line-to-
line overvoltage, power factor, active, reactive and apparent power). If Ekip Synchrocheck is also available,
there is a further page with a summary of the main measurements associated with the module (Int and Ext
voltages and frequencies, phase difference, synchronism state).
Both pages can be set as main page by pressing and holding down the HOME key.
43 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 3 - Histograms Page
ABB | SACE Emax 2
Description The Measuring instruments pages show an indicator of the maximum phase current, or the maximum line-
to-line voltage, or the active, reactive or apparent power.
The page orientation (horizontal by default) can be changed from the Settings menu, by selecting System -
View (see the chapter "6 - Menu", and the paragraph "Settings Menu" on page 49).
A
.... B
528.9
....
A C
L3
Figure 9
The following table provides a description of the various areas of the pages:
Pos. Description
Type of indicator:
• A: ammeter, with measurement of the maximum phase current.
• V: ammeter, with measurement of the maximum phase-to-phase voltage.
• kW: measurement of the active power.
A • kVAR: measurement of the reactive power.
• kVA: measurement of the apparent power.
NOTE: all the indicators except the ammeter are available with the Ekip Measuring
module.
B Measurement expressed as a percentage of the nominal value set.
C Measurement as an absolute value (A, V, kW, kVA).
D Phase current or phase-to-phase voltage, to which the measurement refers.
E Diagnosis bar.
44 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 4 - Measuring instruments pages
ABB | SACE Emax 2
5 - Measurements pages
Description The pages Measurements display a list of real-time measurements of currents, voltages, active/reactive/
apparent power, or relavant to the energy counters, or to the Power Controller function.
NOTE: the voltage and power measurements, and the measurements related to the energy
counters and the Power Controller function, are available with the Ekip Measuring module.
A B C
Voltage D
E
F
Figure 10
The following table provides a description of the various areas of the pages:
Pos. Description
Viewed with the Ekip Measuring module, it indicates the presence of several pages, that you
A
can scroll through by touching the sides of the display, and in which of these pages you are.
B Signalling and functions in progress (see the Histograms page)
C Current time.
D Unit in which the measurements are displayed.
E Real time measurements.
F Diagnosis bar.
45 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 5 - Measurements pages
ABB | SACE Emax 2
6 - Menu
A B C
D G E F
Figure 11
The following table provides a description of the various areas of the page:
Pos. Function
A It opens the Protections menu.
B It opens the Advanced menu.
C It opens the Measurements menu.
D It opens the Settings menu.
E It opens the Test menu.
F It opens the About menu.
G In the presence of messages, it opens the Alarm List page.
46 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
ABB | SACE Emax 2
A B C
Advanced D
S(V) Protection
Current-Voltage Protection (51V)
S(V) Protection
Current-Voltage Protection (51V)
Protection MCR
Short circuit
D Protection
Directional (67)
IU Protection
Current unbalance (46) D
Figure 12
The following table provides a description of the various areas of the menus:
Pos. Function
A It opens the higher level menu, or if there is no higher level, the Menu page.
B It displays the name of the menu.
• It displays a list of the available submenus, the parameters that can be set, and the
commands that can be performed
C
• Depending on the selection, it opens a submenu, the Modify Parameters page, or an
information page, or performs a command.
D Scroll the list
NOTE: in the menus, the description and the ANSI code are indicated under each protection,
and the current value is shown under each parameter.
Protections Menu The following table shows the submenus and the protections associated to the menu Protections, and the
relevant Ekip Touch trip units.
IMPORTANT:
• Selecting a protection opens the list of the parameters that can be set for the
selected protection.
• With Hi-Touch and G Hi-Touch trip units, and the Dual Set function enabled (see
the Settings menu), the protections can be set according to two configurations (Set
A and Set B), of which the default configuration can be selected.
Protections
Trip units
L Protection
Touch G-Touch
S Protection
S2 Protection - -
• Set A (1)
I Protection Hi-Touch G Hi-Touch
• Set B (1) Touch G-Touch
2I Protection
G Protection Touch (2) G-Touch (2)
(1)
Submenus available with Hi-Touch and G Hi-Touch trip units, and the Dual Set function enabled (see the
Settings menu).
(2)
With Touch and G Touch trip units, alternative protection to Gext, therefore available only without S.G.R.
toroid (see the menu Settings, Circuit Breaker, Ground protection).
(3)
Protection available with S.G.R. toroid (see the menu Settings, Circuit Breaker, Ground protection), and
alternative to RC protection (see the Advanced menu).
47 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
ABB | SACE Emax 2
Advanced menus The following table shows the submenus and the protections associated to the menu Advanced, and the
relevant Ekip Touch trip units.
IMPORTANT:
• Selecting a protection opens the list of the parameters that can be set for the
selected protection.
• With Hi-Touch and G Hi-Touch trip units, and the Dual Set function enabled (see
the Settings menu), the protections can be set according to two configurations (Set
A and Set B), from which the default configuration can be selected.
Trip units
Advanced
S(V) Protection - - G-Touch
S2(V) Protection - - -
MCR Protection Touch G-Touch
D Protection - -
IU Protection
Touch
Rc Protection (2) G-Touch
Hi-Touch
UV Protection Touch (3)
UV2 Protection - -
OV Protection Touch (3) G-Touch
OV2 Protection - -
RV Protection - -
VU Protection Touch (3) G-Touch
• Set A (1)
UF Protection Touch (3)
• Set B (1)
UF2 Protection - Hi-Touch -
G Hi-Touch
OF Protection Touch (3) G-Touch
OF2 Protection - -
ROCOF Protection - - -
RP Protection Touch (3) Hi-Touch
RQ ProtectioN - -
OP Protection - -
OQ Protection - -
UP Protection - -
Synchrocheck (4) Touch (3) G-Touch
Alarms Touch (3)
Current thresholds
Hi-Touch
External Trip (5)
Touch
• Functions Trip RESET (6)
Switch On SET B (7)
(1)
Submenus available with Hi-Touch and G Hi-Touch trip units, and the Dual Set function enabled (see the
Settings menu).
(2)
Protection available with Rating Plug Rc and Ekip Measuring Pro modules, and toroid Rc (see the menu
Settings, Circuit Breaker, Ground protection), and alternative to the Gext protection (see the Protections menu).
(3)
Protection available with Ekip Measuring Pro module.
(4)
Protection available with the Ekip Synchrocheck module.
(5)
It opens a list of the parameters that can be set for programming the opening of the circuit-breaker.
(6)
It opens a list of the parameters that can be set for programming the reset of the tripping signal.
(7)
It opens a list of the parameters that can be set for programming the switching of the protection configuration
from A to B.
48 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
ABB | SACE Emax 2
Settings Menu This menu allows you to configure more settings in addition to those of the protections and of the advanced
protections and functions.
The following table shows the submenus and the parameters associated to the menu Settings, up to Level
3 (if present). The options corresponding to parameters and commands are underlined, to distinguish from
those corresponding to submenus.
Options
Settings
• Configuration: available with a three-pole circuit-breaker, it opens a list of the
possible configurations of the circuit-breaker neutral.
• Hardware Trip: it opens the Modify Parameters page, to enable/disable tripping in
the case of hardware problem of the trip unit.
• T Protection: it opens a list of the parameters that can be set for the
Circuit Breaker overtemperature protection.
• Neutral Protection: available with a configuration with neutral, it opens a list of the
parameters that can be set.
• Ground protection: it opens a list of the parameters that can be set.
• Installation: displayed if a Rating Plug or Ekip Measuring or Ekip Measuring Pro
module is not installed. It opens a list of the modules to be installed.
Main frequency It opens the Modify Parameters page, to set the Line frequency.
Phase Sequence It opens the Modify Parameters page, to set the phase sequence.
• Local/Remote: it opens the Modify Parameters page, to set the local or remote
connection.
• Local Bus: it opens the Modify Parameters page, to enable/disable the Local Bus
• Ekip Measuring, Ekip Synchrocheck, etc: these open a list of the parameters that
Modules (1) can be the set for the electronic accessories.
• Functions: it allows the access to the menus in order to program Switch On
LOCAL, Signalling RESET, YO Command, and YC Command actions (see the
chapter "20 - Operating features", and the paragraph "Functional characteristics", on
page 124).
It opens the Modify Parameters page, to set the waiting time between the acquisition
Monitor time
of one measurement and the next.
• Enable: it opens the Modify Parameters page, to enable/disable the function.
• Load Operating Mode: available with Power Controller enabled, it opens a list of the
Power
loads, to be enabled/disabled.
Controller
• Power Limits: available with Power Controller enabled, it opens a list of the power
thresholds to be set.
• Enable: it opens the Modify Parameters page, to enable/disable the function.
• I Harm Analysis: available with Network Analyzer enabled, it opens the Modify
Parameters page to enable/disable the calculation of the harmonics for currents.
• V Harm Analysis: available with Network Analyzer enabled, it opens the Modify
Parameters page to enable/disable the calculation of the harmonics for voltages.
• V Threshold Low, V Threshold High, Umbalance Th, V microinterr. Th, V Spike Threshold:
Network
available with Network Analyzer enabled, they open the Modify Parameters page,
Analyzer
to set the parameters (for details on the parameters, see the chapter "17 - Hi-Touch
measurements", and the paragraph "Network Analyzer", on page 114).
• Sags: available with Network Analyzer enabled, it opens a list of the parameters that
can be set for monitoring voltage drops.
• Swells: available with Network Analyzer enabled, it opens a list of the parameters
that can be set for monitoring voltage swells.
• Enable: available if the function is not running, it opens the Modify Parameters page
to enable/disable the function.
• Num. of Datalogger: available with Datalogger enabled, it opens the Modify
Parameters page, in order to set the number of records.
• Sampling frequency: available with Datalogger enabled, it opens the Modify
Parameters page, to set the frequency of data logging.
Datalogger (2)
• Datalogger 1: available with Datalogger enabled, opens a list of the parameters that
can be set and the commands of the function.
• Datalogger 2: available with the second Datalogger enabled, it opens a list of the
parameters that can be set and the commands of the function.
• Restart all: available with the second Datalogger enabled, it starts both recordings.
• Stop all: available with the second Datalogger enabled, it stops both recordings.
49 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
Continued from the previous page ABB | SACE Emax 2
Options
Settings
• Enable: it opens the Modify Parameters page, to enable/disable dual configuration
of the protections.
Dual Set
• Default Set: available with Dual Set enabled, it opens the Modify Parameters page,
to set the default configuration.
• Date: it opens the Modify Parameters page, to set the date.
• Time: it opens the Modify Parameters page, to set the time
System
• Language: it opens the Modify Parameters page, to set the language.
• New Password: it opens the page for insertion of the password.
• TFT orientation: it opens the Modify Parameters page to set the orientation of
the Alarm List and Measuring instruments pages, and with a summary of the
measurements accessible from the Histograms page.
• Ammeter Phase: it opens the Modify Parameters page to set the current the
View measurement of which is to be displayed in the Measuring instruments page.
• Voltmeter phase: it opens the Modify Parameters page to set the phase-to-phase
voltage the measurement of which is to be displayed in the Measuring instruments
page.
• Clients page: it opens the Modify Parameters page, to enable the Info (4) page.
• YO Command: opens the list of parameters that can be set for programming the coil
opening command.
Functions
• YC Command: opens the list of parameters that can be set for programming the coil
closing command.
• Signals: it opens the Modify Parameters page, in order to enable/disable the
Maintenance maintenance required signal, after a year from the last maintenance, or with contact
wear of at least 20 % and an increase of 10 % compared to the last maintenance.
(1)
The options in the Modules submenu change according to the electronic accessories connected.
(2)
Function available with the trip unit energized with auxiliary voltage.
(3)
Setting available with Hi-Touch and G Hi-Touch trip units.
(4)
If enabled, the Info page can be accessed by pressing the iTEST key until it appears; it displays five lines of
twenty characters each containing alphanumeric data that the customer can insert through the Ekip Connect
software (see the chapter "17 - Other accessories", and the paragraph "Ekip Connect software" on page 288).
Test Menu This menu allows you to access the commands in order to perform the tests.
The following table shows the submenus and the commands associated to the menus Test, up to Level
3 (if present). The options corresponding to commands are underlined, to distinguish them from those
corresponding to submenus.
Option
Test
Rc Test (1) Test protection Rc.
Auto Test It performs a test on the display and LEDs of the interface.
Trip Test it enables the opening command.
• Close CB: it commands the closing of the circuit-breaker.
Test CB
• Open CB: it commands the opening of the circuit-breaker.
Ekip Signalling 2K (2) • Auto Test
Ekip Signalling 4K (2) • Auto Test
• S Protection: opens a list of the test commands of the Zone Selectivity
function for S protection.
Zone selectivity (68)
• G Protection: it opens a list of the test commands of the Zone Selectivity
function for G protection.
(1)
Test available with Rating Plug Rc and Ekip Measuring Pro modules, and toroid Rc (see Settings - Circuit
Breaker - Earth protection menu).
(2)
These menus are available if the relevant modules are connected.
50 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
ABB | SACE Emax 2
Function
Information
It displays:
Protection unit • Information on Mainboard and trip unit.
• Date and time.
Circuit Breaker Displays information on the circuit-breaker.
Modules It displays a list of the electronic accessories connected.
• Load input status: shows the Open/Closed state of the loads
Power Controller (1)
• Load Active: shows the Active/Inactive state of the loads.
(1)
Menus available with the Power Controller function enabled (see the Settings Menu- Power Controller).
51 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
Continued from the previous page ABB | SACE Emax 2
(1)
Measurements available with Ekip Measuring or Ekip Measuring Pro modules.
(2)
Measurements available with Ekip Synchrocheck module.
(3)
Measurements available with the Network Analyzer function enabled (see the menu Settings - Network
Analyzer).
Last Trip measurements To open the page, from the menu Measurements, you need to select Historicals - Tripping, and a trip from
the list.
Alternatively, if the main page or a level 2 page is displayed (see the chapter “1 - Layout of the interface", and
the paragraph "Structure of the pages”, on page 38), you can open the page relating to the last opening by
pressing the iTEST key until the page is displayed.
NOTE: when a trip occurs, the page relating to the last trip is opened automatically.
Last Trip
14:07:13:406 Mar 04, 2013
D L Protection n°01 E
L1 Ne .... F
L2 1885.5A
L3 1903.1A
Figure 13
The following table provides a description of the various areas of the page:
Pos. Description
A Name of the page.
B Time at which the selected trip occurred (time set on the trip unit at the moment of the trip)
C Date at which the selected trip occurred (date set on the trip unit at the moment of the trip)
D The protection that tripped.
Number of the selected trip.
E
NOTE: every new trip is associated to an incremental number
52 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
ABB | SACE Emax 2
Measurements history To open the page, from the menu Measurements, you need to select Historicals - Measurements, and an
item in the list.
I max 5min
Figure 14
The following table provides a description of the various areas of the page:
Pos. Description
A It cancels the operation, and opens the Measurements list.
B Item selected in the Measurements list.
Time interval between the selected measurement (see flashing bar) and the previous one.
C
Value 0 indicates the first measurement after a unit shutdown.
D Measurement of the bar that is flashing in the histogram.
E Date of the selected measurement.
F Time of the selected measurement (see flashing bar).
Histogram y-axis, with the measurements expressed as percentages of the nominal value
G
set.
H Bars that represent the measurements of the dimension in position D.
In this page, you can do the following:
• Touch the sides of the display to scroll along the time axis, and select the bar before or after the flashing bar.
• Return to the list Measurements.
53 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
ABB | SACE Emax 2
Waveforms To open the page, from the menu Measurements, you need to select Network Analyzer - Waveforms, and
an item from the list.
Voltage 12 95,3V
Refresh Harmonics
E F
Figure 15
The following table provides a description of the various areas of the page:
Pos. Description
A It cancels the operation, and opens the Waveforms list.
B Item (measurement) selected in the Waveforms list.
C Measurement value at the moment of selection.
D Waveform at the time of selection.
E Refresh key: performs a new acquisition.
Harmonics key: available if the measurement of harmonics is enabled (see the menu
F
Settings, Network Analyzer), open the Harmonic Measurements page.
54 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
ABB | SACE Emax 2
Harmonics Measurement To open the page, from the page with the waveform, press the key Harmonics.
The page shows the measurements performed for the harmonics of the selected item, in the form of a
histogram.
NOTE: to view measurement of the harmonics, measuring must be enabled from the Settings
- Network Analyzer menu, selecting I Harm Analysis to enable measurement of the harmonics
of the currents, and V Harm Analysis to enable measurement of voltage harmonics.
The page appears as follow:
A B C D
Harmonics Voltage 12
G
Figure 16
The following table provides a description of the various areas of the page:
Pos. Description
A It cancels the operation, and opens the Waveforms list.
B Name of the page.
C Quantity of which the harmonics are displayed.
D The harmonic to which the flashing bar in the histogram corresponds.
E Measurement of the flashing bar in the histogram in numerical form.
Histogram y-axis, with the measurements expressed as a percentage of the fundamental
F
component.
G Bars that represent the measurements of the harmonics of dimension in position C.
In this page, you can do the following:
• Touch the sides of the display to scroll through the harmonics, and select the bar before or after the
flashing bar.
• Return to the list Waveforms.
55 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 6 - Menu
ABB | SACE Emax 2
Function The purpose of the password of Ekip Touch is to prevent unintentional parameter settings made via the
display.
However, the parameters can still be changed using Ekip Connect via the front connector to Ekip T&P, Ekip
Programming or Ekip Bluetooth.
If the trip unit is connected to Ekip Com modules and configured as Remote, the parameters can also be
changed via the relative bus.
WARNING! the user is responsible for security against unauthorized access and
modifications in all the cases mentioned above.
Description The page where the password is entered is open, if a parameter to be entered, or the Test menu have been
selected, or if the password must be changed.
NOTE: insertion of the password is requested, if:
56 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 7 - Insertion of the password
ABB | SACE Emax 2
Password
0 * * * * D
Confirm
E
Figure 17
The following table provides a description of the various areas of the page:
Pos. Function
A Cancels the operation, and opens the start menu.
B It shows the name of the page
C Keys to increase and decrease the corresponding digit.
D It displays the digits of the password.
Confirm key:
• Confirmation after inserting a digit in a position from 1 to 4 will automatically bring you to the
E next digit.
• When the fifth digit is confirmed, the entire password is confirmed and the selected page is
opened.
NOTE:
• If you are changing the password, after the first confirmation of the new password, the page
opens again for the reconfirmation.
• In the case of an incorrect password, the message “Wrong Password” appears for approximately
3 seconds, and the page for insertion of the password opens again.
• There is no limit to the number of incorrect passwords that you can insert.
• If the password is lost, see the document 1SDH001501R0002 or contact ABB
57 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 7 - Insertion of the password
ABB | SACE Emax 2
Modifying a parameter To set a parameter, you need to select it. Selecting a parameter opens the page Modify Parameter.
There are two possible types of Modify Parameter page:
• By option: it consists of a list of the values that can be assigned to the parameter (see page 59).
• By value: graphical page with a bar for assigning the parameter a numerical value within a range. (see
page 59).
In both the cases, in order to set the parameter, you need to select the desired value.
Programming the trip unit When a parameter is modified, the new value is indicated in the Start menu, and the parameter is associated
to a tick symbol.
If available, when going up to the higher level menus, the submenus of which parameters have been modified
are also associated to a tick symbol.
The menu with submenus and parameters with ticks appears as follows:
S(V) Protection
Enable
On
Trip enable
On
Function
Step mode
I20 Threshold
0.60In (240A)
Ul Threshold
100% Un (100V)
Figure 18
The following table provides a description of the changes made to the menu:
Pos. Description
A Modified submenu or parameter. If it is a parameter, the new value assigned is shown.
B Tick symbol, that indicates the submenus and parameters modified.
The ticks indicate that the changes are not effective. In order make a change effective, the trip unit must be
programmed. To program the trip unit, you need to press the key HOME, that opens the page Programming.
Alternatively, you can go up to the higher level menus until the page is displayed.
In the page Programming:
• A list of the changes made is displayed.
• You are asked to confirm, cancel, or modify the settings.
NOTE: before confirming a change in the page Programming, other changes can be made
both in the same menu and in higher or lower level menus. In fact, the changes are stored
unless they are cancelled in the page Programming, and the confirmation or the cancellation
refers to all the changes made up to that moment but still not confirmed.
58 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 8 - Setting the parameters
ABB | SACE Emax 2
Edit Parameters page by option NOTE: In the case of Edit Parameters by option, the selection of a value brings you automatically
back to the previous Menu.
A Modify Parameter E
Frequency
50 Hz
60 Hz
E
Figure 19
The following table provides a description of the various areas of the page:
Pos. Description
A Cancels the operation, and opens the start menu.
B Name of the page.
C Name of the parameter to be set.
D List of the selectable values.
E Scroll the list
Edit Parameters page by value NOTE: In the case of Edit Parameters by value, in order to complete the setting and return
to the previous menu, you need to confirm the selected value.
Modify Parameter
I20 Threshold
Confirm
Figure 20
59 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 8 - Setting the parameters
Continued from the previous page ABB | SACE Emax 2
The following table provides a description of the various areas of the page:
Pos. Description
A Cancels the operation, and opens the start menu.
B Name of the page.
C Name of the parameter to be set.
D Value selected for the parameter.
E Bar: graphic representation of the range of selectable values.
F Cursor: graphic representation of the selected value.
• MIN key: selects the minimum value.
G
• MAX key: selects the maximum value.
H - and + keys: allow you to increase and decrease the value selected.
I Confirm key: confirms the selected value.
Programming
S(V) Protection
B
S(V) Protection
Figure 21
The following table provides a description of the various areas of the page:
Pos. Description
A Name of the page.
B List of changes made.
C Confirm key: confirms the changes (programs the trip unit), and opens the Menus page.
D Cancel key: cancels the changes, and opens the Menus page.
E Modify key: it keeps the changes and opens the menu with ticks, for further modifications.
60 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 8 - Setting the parameters
ABB | SACE Emax 2
9 - Touch protections
Presentation Touch protections are available in all models of trip units of the Ekip Touch range.
The presence of each single protection depends on the version of the trip unit, as specified in the following
paragraphs.
List of protections
Touch protections:
Symbol Protection against
L Overload with inverse long-time delay
S Selective short-circuit
I Instantaneous short-circuit
G Earth fault with adjustable delay
2I Programmable instantaneous short-circuit
MCR Instantaneous short-circuit on closing of the circuit-breaker
IU Current unbalance
Hardware Trip Circuit-breaker internal connection error
Harmonic Distortion Distorted waveforms
Current thresholds Programmable signal thresholds
T Temperature outside range
Neutral Neutral protection
The trip units of SACE Emax 2 series also guarantee a non-adjustable fixed protection against instantaneous
short-circuit at high currents, called Iinst.
Operating principle
The protections have a series of parameters available allowing the user to adjust the activation thresholds and
the opening times of the circuit-breaker.
The operating principle of all the protections is similar: if the current exceeds the set protection threshold, the
specific protection will enter the alarm condition and will begin to delay.
The duration of the delay depends on the threshold and time parameters set, and depending on the dynamic
of the current two behavoiurs are possible:
• If the alarm condition persists, the trip unit opens the circuit-breaker.
• If the current drops below the protection threshold, the trip unit exits from the alarm condition, interrupts
the delay and does not make the circuit-breaker open.
The protection thresholds refer to the rated current of the Rating Plug (In).
IMPORTANT:
• To manage the circuit-breaker tripping with a specific protection, the protection itself
must be enabled and, if supported, must have the Trip Enable parameter activated.
• All the protections have a default configuration: if enabled, check the parameters and
make the necessary changes according to the requirements of your installation.
61 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
L Protection
Path
Main page - Menus - Protections
t
I1 L Function
L protection protects against overloads
NOTE: the protection is available and active for all the versions of the trip unit. You can disable
the protection by configuring the trip unit with Rating Plug L = Off.
t1
When the activation threshold is exceeded, the protection trips in a time that decreases as the current read
increases.
I
Parameters
Here is a list of the available parameters:
Parameter Description
It determines the dynamic of the curve and the calculation of the tripping time,
conforming to various reference standards:
• t = k / I 2 according to IEC 60947-2.
• IEC 60255-151 SI
• IEC 60255-151 VI
• IEC 60255-151 EI
Curve • t = k / I 4 according to IEC 60255-151
Each function corresponds to a mathematical expression that allows the tripping
time to be calculated. The details of the expressions are provided in the table on
page 73.
Time t1 IMPORTANT:
The protection limits the tripping time to 1 second in two cases:
• if, according to the calculation, the time is less than 1 second.
• If the fault current is greater than 12 In.
The prealarm of L allows notification that the measured current is near the activation
threshold of the protection.
The prealarm state is activated for currents higher than a threshold that can be set
I1 Prealarm by the user, and is deactivated in two cases:
• Current lower than the prealarm threshold.
• Current higher than the protection activation threshold.
A value within the 50 % ... 90 % range can be entered, with 1 % steps.
62 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
S Protection
Path
Main page - Menus - Protections
t
I2 S Function
S protection protects against selective short circuit.
NOTE: the protection is available for LSI and LSIG versions of the trip unit.
t2 When the activation threshold is exceeded, the protection trips within a fixed or dynamic time (the time
decreases as the current reading increases).
I Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It determines the dynamic of the curve and the tripping time, fixed or dynamic
according to the selection:
• t = k (ANSI 50TD): fixed time trip.
Curve
• t = k / I 2 (ANSI 51): inverse time dynamic tripping.
The calculation of the tripping time of the inverse time curve is based on a
mathematical expression. The details are provided in the table on page 73.
It defines the current value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to the
y-axis).
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug).
Threshold I2
IMPORTANT: The I2 threshold set must be higher than the I1
threshold. An incorrect configuration gives an error on the display and
the programming session doesn’t conclude, with consequent rejection
of the changes made to the parameters.
The selected function determines the contribution of t2:
• t = k: t2 is the delay time between the exceeding of the I2 threshold and the
sending of the opening command.
• t = k / I 2: t2 contributes in calculating the tripping time (with reference to the
Time t2 above curve, t2 affects the curve, shifting it along the vertical axis).
S protection has Trip Enable, Thermal Memory, Zone Selectivity, Startup Enable, see page 71.
Via Ekip Connect it is also possible to access the blocking functions, see page 72.
63 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
I Protection
Path
Main page - Menus - Protections
t
I3 I Function
I protection protects against instantaneous short circuit.
When the activation threshold is exceeded, the protection trips within a fixed time. The user can set the
intervention threshold.
Parameters
It defines the current value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to the
y-axis).
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug).
Threshold I3
IMPORTANT: The I3 threshold set must be higher than the I2
threshold. An incorrect configuration gives an error on the display and
the programming session doesn’t conclude, with consequent rejection
of the changes made to the parameters.
64 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
G Protection
Path
Main page - Menus - Protections
t
I4 G Function
G protection protects against a ground fault.
NOTE:
t4 • The protection is available for the LSIG version of the trip unit.
• With toroid S.G.R. enabled and Ekip Touch and Ekip G Touch trip units, protection G is replaced
by Gext. Both protections, G and Gext, are available with Ekip Hi-Touch and G Hi-Touch trip
units.
I When the activation threshold is exceeded, the protection trips within a fixed or dynamic time (the time
decreases as the current reading increases).
Parameters
Here is a list of the available parameters:
Parameter Description
To activate/deactivate the protection.
If enabled, the protection is inhibited automatically by the trip unit under two
conditions:
• Disconnection of one or more current sensors.
• Current measured on one of the phases higher than a maximum value.
Enable
IMPORTANT: the maximum current value that deactivates G protection
varies according to the threshold set:
• 8 In (with I4 ≥ 0.8 In)
• 6 In (with 0.5 In ≤ I4 < 0.8 In)
• 4 In (with 0.2 In ≤ I4 < 0.5 In)
• 2 In (with I4 < 0.2 In)
It determines the dynamic of the curve and the tripping time, fixed or dynamic
according to the selection:
• t = k (ANSI 50NTD): fixed time trip.
Curve
• t = k / I 2 (ANSI 51N): inverse time dynamic tripping.
The calculation of the tripping time of the inverse time curve is based on a
mathematical expression. The details are provided in the table on page 73.
The value I4 contributes in calculating the tripping time, and also defines the current
value that, if exceeded, activates the protection (with reference to the figure above,
Threshold I4 the threshold is the part of the curve parallel to the y-axis).
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug).
The selected function determines the contribution of t4:
• t = k: t4 is the delay time between the exceeding of the I4 threshold and the
sending of the opening command.
• t = k / I 2: t4 contributes in calculating the tripping time (with reference to the
Time t4 above curve, t4 affects the curve, shifting it along the vertical axis).
G protection has Trip Enable, Zone Selectivity, Startup Enable, see page 71.
Via Ekip Connect it is also possible to access the blocking functions, see page 72.
65 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
2I Protection
Path
Main page - Menu - Advanced
t
I31 2I Function
2I protection, like I protection, protects against instantaneous short circuit.
The main difference between the two protections is that 2I requires an activation event (or command), that
can be programmed by the user.
If 2I protection is active and the set threshold is exceeded, the protection trips within a fixed time. The user
can set the threshold and select three different activation modes.
I
Parameters
The following is a description of the protection parameters:
Parameter Description
Enable To enable/disable the protection and access the programmable parameters.
It defines the current value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to the
Threshold I31
y-axis). It is represented both as an absolute value (Ampere) and as a relative value
(In, nominal value defined by the Rating Plug).
Protection enabling allows access to menu 2I Menu (available following the path Advanced - Functions), to
program the protection activation event.
Parameter Description
Two alternative modes are available:
• Dependent function: the protection is active if the programmed activation event
occurs.
Activation • Active: the protection is always active.
NOTE: if you select Dependent function the access to the Function and Delay
parameters is activated in order to program the activation event.
Protection activation event:
• On the display, it is possible to choose between the state of the input contacts
of the Ekip Signalling 4K and Ekip Signalling 2K modules, the states of the circuit-
Function breaker, and the Custom function.
• Via Ekip Connect, it is possible to customize the Custom function, that allows up
to eight states to be combined with the activation event configured using AND or OR
logical operators.
Protection activation delay, calculated according to the presence of the activation
event.
Delay
NOTE: the protection is active if the event is present for a time greater than the
set delay.
Remote activation
Two remote commands are available for the temporary activation/deactivation of the protection:
• 2I Mode ON: activates the protection.
• 2I Mode OFF: deactivates the protection.
NOTE: if the protection has been activated by the 2I Mode ON command, it will be
deactivated automatically when the solid-state trip unit is turned off.
Signallings
With 2I protection active, the message “2I active” appears in the diagnosis bar and in the Alarm List page,
and the alarm LED remains lit (red).
66 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
Protection MCR
Path
Main page - Menu - Advanced
t
I3 MCR Function
MCR protection has the same characteristics as I protection, with some variations:
• It acts only within an interval that starts from the closing of the circuit-breaker.
• It only works with auxiliary power supply or Ekip Measuring Pro module (with voltage sockets energized).
When the activation threshold is exceeded, the protection trips within a fixed non-adjustable time. The user
can set the tripping threshold.
I Parameters
Here is a list of the available parameters:
Parameter Description
To activate/deactivate the protection.
Enable
IMPORTANT: it can be only activated if the protection is deactivated.
It defines the current value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to the
Threshold I3 y-axis).
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug).
It defines the time interval during which the protection is active, starting from the
Monitor time
closing of the circuit-breaker.
Via Ekip Connect it is also possible to access the blocking functions, see page 72.
67 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
IU Protection
Path
Main page - Menu - Advanced
t
I6 IU Function
IU protection protects against an unbalance between the currents of the individual phases protected by the
circuit-breaker.
When the activation threshold is exceeded, the protection trips within a fixed time.
t6 Unbalance, expressed in percentage value, is calculated in the following way: % Sbil = 100 * (Imax-Imin) / Imax,
where Imax is the maximum and Imin the minimum.
NOTE: The protection is automatically self-excluding in two cases:
I • when at least one phase current exceeds 6 * In.
• when the maximum phase current is less than 0.3 * In.
Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the current value that activates the protection when exceeded (with reference to
Threshold I6 the figure above, the threshold is the part of the curve parallel to the y-axis).
It is represented as a percentage value of 1 In.
The delay time between the exceeding of the I6 threshold and the sending of the opening
Time t6 command (with reference to the curve, it affects the entire curve, shifting it along the
vertical axis).
Hardware Trip
Path
Main page - Menus - Settings - Circuit-breaker
Function
Hardware Trip protection protects against internal disconnections of the circuit-breaker.
If enabled, the fault is signalled and an opening command is sent when one or more of the following events
is detected:
• Current sensors disconnected (phase or external if enabled).
• Rating Plug disconnected.
• Trip coil disconnected (only signalling).
• Incompatibility between protection trip unit and mainboard.
• Internal problems with the trip unit.
IMPORTANT: the protection trips if the error conditions persist for more than 1 second.
Harmonic distortion
Path
Main page - Menus - Measurements
Function
The Harmonic Distortion protection allows a control alarm to be activated for a distorted waveforms.
If enabled, an alarm is activated for peak factors higher than 2.1.
68 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
Current thresholds
Path
Main page - Menu - Advanced
Function
The Current Thresholds allow controls to be set on the current lines, to be connected to the programmable
contacts of the Ekip Signalling modules (in all versions). Two pairs of contacts are available:
• Threshold 1 I1 and Threshold 2 I1, with control referring to I1.
• Threshold Iw1 and Threshold Iw2, with control referring to In.
IMPORTANT:
• The current thresholds do not manage the trip, but only the signal.
• The function is active if the trip unit is energized by an auxiliary power supply or Ekip
Measuring Pro.
Parameters
Here is a list of the available parameters:
Parameter Description
It is possible to do the following:
Threshold 1 I1 • Enable the function.
• Set the activation percentage value
It is possible to do the following:
Threshold 2 I1 • Enable the function.
• Set the activation percentage value
It is possible to do the following:
• Enable the function.
Threshold Iw1 • Set the threshold.
• Set activation to obtain the signal when current is higher (up) or lower (down) than
the threshold value. See the following graph.
It is possible to do the following:
• Enable the function.
Threshold Iw2 • Set the threshold.
• Set activation to obtain the signal when current is higher (up) or lower (down) than
the threshold value. See the following graph.
NOTE: the thresholds Iw1 and Iw2 are expressed both as an absolute value (Ampere) and a
relative value (In, nominal value defined by Rating Plug).
State
State
69 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
T Protection
Path
Main page - Menus - Settings - Circuit-breaker
Function
T protection protects the circuit-breaker against abnormal temperatures recorded by the trip unit.
It is always active, and has two states, according to the temperature read:
State Temperature Range Trip unit actions
Warning -25 < t < -20 or 70 < t < 85 Display off; Warning LED on @ 0.5Hz.
Display off; Alarm and Warning LEDs on @2Hz;
Alarm t < -25 o t > 85
Circuit beaker opening command.
IMPORTANT: the opening command is sent only if the parameter Trip Enable is ON.
Neutral
Path
Main page - Menus - Settings - Circuit-breaker
Function
The purpose of the neutral protection is to characterize the protections L, S and I on the Neutral pole with a
control factor different from the other phases.
IMPORTANT: the protection is available with four-pole circuit-breakers or three-pole
circuit-breakers with external neutral.
Parameters
Here is a list of the available parameters:
Parameter Description
This parameter is available with three-pole circuit-breakers and makes it possible
Configuration to activate (3 P + N setting) or deactivate (3 P setting) the presence of the external
neutral.
To activate/deactivate the protection.
Limitations
The adjustment of the neutral threshold to values of 200% and 150% must be performed considering the
following formula: (I1 x InN) ≤ Iu
I1 indicates the threshold of L protection in Amperes (example: In = 1000 A; I1 = 0.45 In = 450 A), InN is the
neutral threshold expressed as a multiplication factor (example: 2), Iu indicates the size of the circuit-breaker
(example: 1000 A).
70 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
Iinst The purpose of this protection is to maintain the integrity of the circuit-breaker and installation in the case
of particularly high current values requiring shorter reaction times than those provided by the instantaneous
short-circuit-protection.
The protection cannot be disabled, and the tripping threshold and time are defined by ABB.
Additional functions
Functions
For some protections there are functions available that extend the functionality:
Protection L S I G MCR IU T
Thermal memory x x
Trip Enable x x x x
Zone Selectivity x x
StartUp enable x x x
Blocks x x x x
Thermal Memory
This function reduces the tripping time of the protection based on the time elapsed between multiple trips
caused by heating of the cables.
IMPORTANT: the parameter can be activated if the function of the selected protection
is t = k / I 2.
Trip enable
It disables the opening command in order to use the protection as an alarm signal, without opening commands.
Zone Selectivity
The function allows multiple circuit-breakers in the same installation to be connected together, in order to
coordinate the trip units and to reduce the tripping times in the case of S and G protections.
The function allows circuit-breakers to be coordinated so that, in the event of a failure:
• The circuit-breaker closest to the fault trips.
• The other circuit-breakers are locked for a programmable time.
For further information see the chapter "1 - Zone Selectivity" on page 156.
StartUp enable
The function allows you to modify the threshold of the protection for a period that can be set by the user. The
period is activated when a threshold is exceeded (startup threshold), which can be programmed by the user
via Ekip Connect software.
IMPORTANT:
71 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
Continued from the previous page ABB | SACE Emax 2
Protection blocks
With Ekip Connect software six blocks are available for some protections, useful for deactivating the protection
based on programmable events.
In particular, four blocks are associated with the programmable states A, B, C and D:
• BlockOnProgStatusA
• BlockOnProgStatusB
• BlockOnProgStatusC
• BlockOnProgStatusD
One block is associated to the startup (present for protections that have a StartUp function):
• BlockOnStartUp
and one block, not present for frequency protections, is associated with the checking of the measured
frequency:
• BlockOnOutOfFrequency
Each block is independent and has its own activation command (Block On).
The protection is deactivated for a time equal to the duration of the event itself:
• If the programmed event occurs (true), in the case of state-based blocks.
• If the StartUp function is active and the startup threshold is exceeded (block active for the startup time
that has been set), in the case of blocking from StartUp.
• If at least one frequency measured is outside the range 30…80 Hz, in the case of a frequency-based block.
IMPORTANT: the blocks can cause:
• Increase of the tripping times of the protections (max: + 30 ms), due to the occurrence
of the event in question (example: frequency check).
• undesired deactivation of the protection, if the block is associated to states or signals
from modules on the local bus and the auxiliary power supply is absent. In this case,
it can be useful to program the event also taking account of the state of the auxiliary
power supply (Supply from Vaux).
• undesired deactivation of the protection, if the block is associated to frequency
measurements, and the voltage is less than the minimum calculation threshold (30 or
60 V, see page 288).
IMPORTANT: during startup, if the function is activated, the blocks are deactivated.
72 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
73 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
Continued from the previous page
The following are the details of the protections according to standard IEC 60255-151:
Protection Curve parameters Calculation formula t t (3) Calculation example t t (3)
L a = 0.02; b = 0.15873; tt = t t = 4.78 s with:
(60255-151 SI) k = 0.16 (t1 x k x b) / ((If / I1) a -1) I1 = 0.4 In; t1 = 3 s; If = 0.8 In
L a = 1; b = 0.148148; tt = t t = 6 s with:
(60255-151 VI) k = 13.7 (t1 x k x b) / ((If / I1) a -1) I1 = 0.4 In; t1 = 3 s; If = 0.8 In
L a = 2; b = 0.1; tt = t t = 8 s with:
(60255-151 EI) k = 82 (t1 x k x b) / ((If / I1) a -1) I1 = 0.4 In; t1 = 3 s; If = 0.8 In
L a = 4; b = 1; tt = t t = 16 s with:
(60255-151 I 4) k = 82 (t1 x k x b) / ((If / I1) a -1) I1 = 0.4 In; t1 = 3 s; If = 0.8 In
NOTES
(1)
ANSI / IEEE C37-2 encoding.
(2)
t t calculation is valid for If values exceeding the trip threshold of the protection. Use fault current and threshold values expressed in In to calculate t
t
, as shown in the example.
(3)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tolerances in the table that following these notes are valid.
(4)
In the presence of auxiliary power supply, you can select all the thresholds. In self-supply mode the minimum threshold is limited to: 0.3 In (with In
= 100 A), 0.25 In (with In = 400 A) or 0.2 In (for all other sizes).
(5)
The MCR time is the time for which the protection remains active after circuit-breaker closing. Tripping time, not adjustable, as for protection I.
(6)
Startup can be activated only with the function set to fixed time.
(7)
For the startup functions, the specified time is the period during which the protection with the different threshold remains active, calculated from
the moment the startup threshold is exceeded.
(8)
With t4 = Instantaneous, the maximum tolerance is 50 ms.
Protection Tolerance threshold Tolerance t t
L Activation for If in the range 1.05...1.2 I1 ± 20 %
S ± 10 % ± 20 %
I ± 15 % ≤ 60 ms
G ± 15 % ± 20 % (60 ms with t4 = instantaneous)
2I ± 15 % ≤ 60 ms
Other - ± 20 %
74 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 9 - Touch protections
ABB | SACE Emax 2
Presentation The Measuring Pro protections are available in all versions of trip units of the Touch range equipped with Ekip
Measuring Pro module.
List of protections
The following is a list of the Measuring Pro protections:
Symbol Protection against
UV Minimum voltage
OV Maximum voltage
VU Voltage unbalance
UF Minimum frequency
OF Maximum frequency
RP Reverse active power
Phase Sequence Phase sequence error
Cos φ Power factor error
If the Ekip Measuring Pro module and the Ekip Synchrocheck module are present, a further selection is
activated:
Symbol Function
Synchronism between two independent power
Synchrocheck
supply systems
Operating principle
The protections have a series of parameters available allowing the user to adjust the activation thresholds and
the opening times of the circuit-breaker.
The operating principle of all the protections is similar: if the voltage, frequency or power signal exceeds the
set protection threshold, the specific protection will enter the alarm condition and will begin to delay.
The duration of the delay depends on the threshold and time parameters set, and depending on the dynamic
of the signal we can have two behaviours:
• If the alarm condition persists, the trip unit opens the circuit-breaker.
• If the signal drops below the protection threshold, the trip unit exits from the alarm condition, interrupts
the delay and doesn't open the circuit-breaker.
The protection thresholds are distinguished by type:
• The voltage protections are related to the rated size of the voltage line-to-line set on the trip unit (Un).
• The frequency protections are related to the frequency set on the trip unit (fn).
• The power protections refer to the product of current and rated voltage (Sn = √3 * In * Un).
IMPORTANT:
• To manage the circuit-breaker tripping with a specific protection, the protection itself
must be enabled and, if supported, must have the Trip Enable parameter activated.
• All the protections have a default configuration: if enabled, check the parameters and
make the necessary changes according to the requirements of your installation.
75 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 10 - Measuring Pro protections
ABB | SACE Emax 2
UV Protection
Path
Main page - Menu - Advanced
t
UV Function
U8 UV protection trips when the phase-to-phase voltage drops below the set threshold.
If at least one line-to-line voltage drops below the activation threshold, the protection trips within a fixed time
set by the user.
t8
Parameters
v Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the voltage value below which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold U8 the y-axis).
It is represented both as an absolute value (Volts) and a relative value (Un,
nominal value defined on the trip unit).
The delay time between the exceeding of the U8 threshold and the sending of
Time t8 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
OV Protection
Path
Main page - Menu - Advanced
t
U9 OV Function
OV protection trips when the phase-to-phase voltage rises above the set threshold.
If at least one line-to-line voltage rises above the activation threshold, the protection trips within a fixed time
set by the user.
t9
Parameters
Here is a list of the available parameters:
V
Parameter Description
Enable To activate/deactivate the protection.
It defines the voltage value above which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold U9 the y-axis).
It is represented both as an absolute value (Volts) and a relative value (Un,
nominal value defined on the trip unit).
The delay time between the exceeding of the U9 threshold and the sending of
Time t9 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
76 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 10 - Measuring Pro protections
ABB | SACE Emax 2
VU Protection
Path
Main page - Menu - Advanced
t
U14 VU Function
VU protection protects against an unbalance between the phase-to-phase voltages protected by the circuit-
breaker.
The unbalance, expressed as a percentage, is calculated as follows: % Sbil = 100 * dmax Umi / Umi, where
t14 dmax Umi is the maximum deviation of the three of calculated by comparing each line-to-line voltage with the
average value, and Umi is the average value of the line-to-line voltages.
When the activation threshold is exceeded, the protection trips within a fixed time, set by the user.
V NOTE: the protection is not active if the highest of the voltages measured is in any case less
than 30% of the Un.
Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the voltage value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold U14
the y-axis).
It is represented as a percentage value of Un.
The delay time between the exceeding of the U14 threshold and the sending of
Time t14 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
UF Protection
Path
Main page - Menu - Advanced
t
UF Function
f12 UF protection trips when line frequency drops below the set threshold.
If the line frequency drops below the activation threshold, the protection trips within a fixed time set by the
user.
t12
NOTE: the protection is not active for voltages <30V.
f Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the frequency value below which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold f12 the y-axis).
It is represented both as an absolute value (Hertz) and a relative value (fn,
nominal value defined on the trip unit).
The delay time between the exceeding of the f12 threshold and the sending of
Time t12 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
77 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 10 - Measuring Pro protections
ABB | SACE Emax 2
OF Protection
Path
Main page - Menu - Advanced
t
f13 OF Function
OF protection trips when the line frequency rises above the set threshold.
If the line frequency rises above the activation threshold, the protection trips within a fixed time set by the
user.
t13 NOTE: the protection is not active for voltages <30V.
f Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the frequency value above which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold f13 the y-axis).
It is represented both as an absolute value (Hertz) and a relative value (fn,
nominal value defined on the trip unit).
The delay time between the exceeding of the f13 threshold and the sending of
Time t13 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
RP Protection
Path
Main page - Menu - Advanced
t
RP P11 Function
RP protection trips when the total reverse active power exceeds the reverse active power threshold set.
When the total reverse active power rises above the set threshold, the protection delays for the set time t11
and then opens.
t11
Parameters
78 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 10 - Measuring Pro protections
ABB | SACE Emax 2
Phase Sequence
Path
Main page - Menu - Settings (Threshold)
Main page - Menus - Advanced - Alarms (enabling)
Function
The phase Sequence protection trips when the sequence of the voltages is not aligned with the sequence
set by the user.
Parameters
The following is a description of the parameters in the various menus:
Parameter Description
Enable To activate/deactivate the protection.
Threshold It defines the voltage control sequence.
Cos φ
Path
Main page - Menus - Advanced - Alarms
Function
The protection Cos φ trips when the total cos φ value drops below the threshold set.
NOTE: total cos φ is calculated as the ratio between Total active power and Total apparent
power.
Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
Threshold It defines the value of cos φ below which the protection is activated.
Synchrocheck
Path
Main page - Menu - Advanced
Function
The Synchrocheck module recognizes and signals if the synchronism conditions exist between two
independent voltage sources (example: generator + network) for closing of the interconnection circuit-breaker.
NOTE:
• Synchrocheck functions are activated only if the Ekip Synchrocheck module is present.
• All the operating specifications are described in the paragraph that describes the Synchrocheck
module, on page 216.
79 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 10 - Measuring Pro protections
ABB | SACE Emax 2
Calculation
Tolerance
ABB ANSI (3) Threshold Time formula Tolerance t t (2)
threshold
t t (1)
The better of the two
values:
U8 = 0,05….0,98 Un t8 = 0.05…120 s
UV 27 ±2% t t = t8 ± 10 % or ± 40 ms (for a
step = 0.001 Un step = 0.01 s
time set < 5 s) / ± 100 ms
(for a time set ≥ 5 s)
The better of the two
values:
U9 = 1….1,5 Un t9 = 0.05…120 s
OV 59 ±2% t t = t9 ± 10 % or ± 40 ms (for a
step = 0.001 Un step = 0.01 s
time set < 5 s) / ± 100 ms
(for a time set ≥ 5 s)
The better of the two
values:
U14 = 2…90 % t14 = 0.5…60 s
VU 47 ±5% t t = t14 ± 10 % or ± 40 ms (for a
step = 1 % step = 0.5 s
time set < 5 s) / ± 100 ms
(for a time set ≥ 5 s)
The better of the two
values:
f12 = 0,9….1 fn t12 = 0,06…300 s
UF 81L ± 1 % (4) t t = t12 ± 10 % or ± 40 ms (for a
step = 0.001 fn step = 0.01 s
time set < 5 s) / ± 100 ms
(for a time set ≥ 5 s)
The better of the two
values:
f13 = 1….1,1 fn t13 = 0,06…300 s
OF 81H ± 1 % (4) t t = t13 ± 10 % or ± 40 ms (for a
step = 0.001 fn step = 0.01 s
time set < 5 s) / ± 100 ms
(for a time set ≥ 5 s)
The better of the two
values:
P11 = -1…-0.05 Sn t11 = 0.5…100 s
RP 32R ± 10 % t t = t11 ± 10 % or ± 40 ms (for a
step = 0.001 Sn step = 0.1 s
time set < 5 s) / ± 100 ms
(for a time set ≥ 5 s)
Ulive = 0.5…1.1 Un; step = 0.001 Un
∆U = 0.02…0.12 Un; step = 0.001 Un
tref = 0.1…30 s
Synchrocheck 25 ∆f = 0.1…1 Hz; step = 0.1 Hz ± 10 % - -
step = 1 ms
∆Cos φ = 5…50° elt; step = 5° elt
tsyn = 0.1…3 s; step = 0.1 s
Cyclic
direction of 47 1-2-3 or 3-2-1 - - - -
the phases
Cos φ = 0.5…0.95
Cos φ 78 - - - -
step = 0.01
(1)
Calculation of t t is valid for values exceeding the tripping threshold of the protection.
(2)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tripping time tolerance of ± 10 % will become ± 20%.
(3)
ANSI / IEEE C37-2 encoding.
(4)
Valid tolerance for frequencies in the range: fn ± 2 %. For frequency outside the range a tolerance of ± 5 % applies.
80 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 10 - Measuring Pro protections
ABB | SACE Emax 2
11 - Hi-Touch protections
Presentation Hi-Touch protections are available for Ekip Hi-Touch and Ekip G Hi-Touch trip units.
List of protections
The following is a list of the Hi-Touch protections:
Symbol Protection against
S2 Short-circuit with adjustable delay
D Directional short-circuit with adjustable delay
UV2 Minimum voltage
OV2 Maximum voltage
UF2 Minimum frequency
OF2 Maximum frequency
Set A-B Double configuration of the protections
Operating principle
The protections have a series of parameters available allowing the user to adjust the activation thresholds and
the opening times of the circuit-breaker.
The operating principle of all the protections is similar: if the current, voltage or frequency signal exceeds the
set protection threshold, the specific protection will enter the alarm condition and will begin to delay.
The duration of the delay depends on the threshold and time parameters set, and depending on the dynamic
of the signal we can have two behaviours:
• If the alarm condition persists, the trip unit opens the circuit-breaker.
• If the signal drops below the protection threshold, the trip unit exits from the alarm condition, interrupts
the delay and doesn't open the circuit-breaker.
The protection thresholds are distinguished by type:
• The current protections are related to the rated size of the Rating Plug (In).
• The voltage protections are related to the rated size of the voltage line-to-line set on the trip unit (Un).
• The frequency protections are related to the frequency set on the trip unit (fn).
IMPORTANT:
• To manage the circuit-breaker tripping with a specific protection, the protection itself
must be enabled and, if supported, must have the Trip Enable parameter activated.
• All the protections have a default configuration: if enabled, check the parameters and
make the necessary changes according to the requirements of your installation.
81 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
S2 Protection
Path
Main page - Menus - Protections
t
I5 S2 Function
S2 protection:
• It protects against a selective short circuit, as the S function.
• It is independent from S protection: it is therefore possible to program thresholds and functions of the two
protections in order to have different installation solutions (for example: signalling with S and trip with S2,
t5 or vice versa, or S and S2 both for signalling or trip).
When the activation threshold is exceeded, the protection trips within a fixed time. The user can set the
threshold and the tripping time.
I
Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the current value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to
the y-axis).
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug).
Threshold I5
IMPORTANT: The I5 threshold set must be higher than the I1
threshold. An incorrect configuration gives an error on the display
and the programming session doesn’t conclude, with consequent
rejection of the changes made to the parameters.
This is the delay time between the exceeding of the I5 threshold and the
Time t5
sending of the opening command.
S2 protection has Trip Enable, Zone Selectivity, Startup Enable, see page 88.
Via Ekip Connect it is also possible to access the blocking functions, see page 72.
82 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
D Protection
Path
Main page - Menu - Advanced
t
I7 D Function
D protection protects against selective directional short circuit.
t7bw Once the activation threshold has been exceeded, the protection trips within a fixed time determined by the
direction of the fault, t7fw in the case of forward direction and T7bw in the case of backward direction.
t7fw NOTE: the protection does not detect the direction of fault current for < 5 V voltages.
I Operating principle
The direction of the fault current detected is compared with the reference direction for the fault
current (forward direction).
This reference direction matches the set power flow value in nominal conditions, provided that the phase
sequence has been set correctly (cyclic direction of the phases).
Reference direction for
Cyclic direction of the Cyclic direction of
Power flow the fault current (forward
phases (Set) the phases (Real)
direction).
123 Top -> Bottom 123 Top -> Bottom
123 Bottom -> Top 123 Bottom -> Top
123 Top -> Bottom 321 Bottom -> Top
123 Bottom -> Top 321 Top -> Bottom
321 Top -> Bottom 123 Bottom -> Top
321 Bottom -> Top 123 Top -> Bottom
321 Top -> Bottom 321 Top -> Bottom
321 Bottom -> Top 321 Bottom -> Top
NOTE: The flow of power parameter is described under the Ekip Measuring Pro module, on
page 210, while the phase sequence on page 79.
Parameters
It is possible to modify various parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the current value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to the
Threshold I7 Bw y-axis), in the case of forward direction.
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug)
It defines the current value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to the
Threshold I7 Fw y-axis), in the case of backward direction.
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug)
This is the delay time between the exceeding of the I7 threshold and the sending of
Time t7 Fw
the opening command, in the case of forward direction.
This is the delay time between the exceeding of the I7 threshold and the sending of
Time t7 Bw
the opening command, in the case of backward direction.
The direction of the fault is calculated by the trip unit according to the phase
difference angle between the reactive and apparent powers measured: when the
phase-difference becomes greater than the parameter Min Angle Direction set, the
Direction Min
trip unit considers the direction of the fault to have been identified.
Angle
NOTE: There are 15 preset values available, in a range from 3.6° to 69.6°.
83 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
Continued from the previous page ABB | SACE Emax 2
D protection has Trip Enable, Directional Zone Selectivity, Startup Enable, see page 88.
Via Ekip Connect it is possible to access further parameters:
• Blocking functions, see page 72 for operation details.
• Trip only Forward: if it is activated, protection D manages opening commands only if forward direction
is detected
• Trip only Backward: if it is activated, protection D manages opening commands only if backward
direction is detected
Notes
By activating the directional D protection, the alarm that checks the phase sequence is automatically set
(it can however also be bypassed and activated manually): note that in the event of a cyclical sequence of
phases different from the set value, the directional protection inverts the reference direction in the case of a
fault whenever different from the expected one.
NOTE: the details of the phase sequence protection are available on page 79.
The behavior of the directional protection is influenced in the case of small overloads by the load type: in the
case of a capacitive load, to avoid the possibility of incorrect identification of the fault current direction, this
protection should be adjusted in relation to real fault conditions and not to overloads.
WARNING! Parameters and application notes are valid with protection trip units
updated to SW version 2.00 (or later versions).
t
UV2 Function
U15 UV2 protection:
• It trips when the line-to-line voltage drops below the set threshold, like the UV protection.
• It is independent from UV protection: it is therefore possible to program thresholds and functions of the
two protections in order to have different installation solutions (for example: signalling with UV and trip
t15 with UV2, or vice versa, or UV and UV2 both for signalling or trip).
If at least one line-to-line voltage drops below the activation threshold, the protection trips within a fixed time
set by the user.
v
Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the voltage value below which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold U15 the y-axis).
It is represented both as an absolute value (Volts) and a relative value (Un,
nominal value defined on the trip unit).
The delay time between the exceeding of the U15 threshold and the sending of
Time t15 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
84 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
t
Function
U16 OV2
OV2 protection:
• It trips when the line-to-line voltage rises above the set threshold, like the OV protection.
• It is independent from OV protection: it is therefore possible to program thresholds and functions of the
two protections in order to have different installation solutions (for example: signalling with OV and trip
t16 with OV2, or vice versa, or OV and OV2 both for signalling or trip).
If at least one line-to-line voltage rises above the activation threshold, the protection trips within a fixed time
set by the user.
V Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the voltage value above which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold U16 the y-axis).
It is represented both as an absolute value (Volts) and a relative value (Un,
nominal value defined on the trip unit).
The delay time between the exceeding of the U16 threshold and the sending of
Time t16 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
Function
t
UF2 UF protection:
• It trips when the line frequency drops below the set threshold, like UF protection.
f17 • It is independent from UF protection: it is therefore possible to program thresholds and functions of the
two protections in order to have different installation solutions (for example: signalling with UF and trip
with UF2, or vice versa, or UF and UF2 both for signalling or trip).
t17 If the line frequency drops below the activation threshold, the protection trips within a fixed time set by the
user.
NOTE: the protection is not active for voltages <30V.
f
Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the frequency value below which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold f17 the y-axis).
It is represented both as an absolute value (Hertz) and a relative value (fn,
nominal value defined on the trip unit).
The delay time between the exceeding of the f17 threshold and the sending of
Time t17 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
85 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
OF2 Protection
Path
Main page - Menu - Advanced
t
f18 OF2 Function
OF2 protection:
• It trips when the line frequency rises above the set threshold, like the OF protection.
• It is independent from OF protection: it is therefore possible to program thresholds and functions of the
two protections in order to have different installation solutions (for example: signalling with OF and trip
t18 with OF2, or vice versa, or OF and OF2 both for signalling or trip).
If the line frequency rises above the activation threshold, the protection trips within a fixed time set by the
user.
f NOTE: the protection is not active for voltages <30V.
Parameters
Here is a list of the available parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the frequency value above which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold f18 the y-axis).
It is represented both as an absolute value (Hertz) and a relative value (fn,
nominal value defined on the trip unit).
The delay time between the exceeding of the f18 threshold and the sending of
Time t18 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
86 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
Set A-B
Path
Main page - Menu - Settings - Double Set (Enabling)
Main page - Menus - Protections - Advanced - Functions - Turn on SET B (Activation event)
Function
Enabling the function Set A-B makes it possible to activate two different protection configurations, alternatives
to each other, on the basis of certain programmable events.
Enabling
The following parameters are available:
Parameter Description
To activate/deactivate the protection.
Activation events
The following parameters are available:
Parameter Description
It allows you to choose the event or the state that activates the secondary protection set.
Function
NOTE: with SW Ekip Connect it is possible to program the “Custom” setting (for
further details see the Ekip Connect User Manual).
This is the minimum time of presence of an event/state necessary to activate the
Delay
parameter change.
87 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
Trip enable
It disables the opening command in order to use the protection as an alarm signal, without opening commands.
Zone Selectivity
The function allows multiple circuit-breakers in the same installation to be connected together, in order to
coordinate the trip units and to reduce the tripping times in the case of S2 protection.
The function allows circuit-breakers to be coordinated so that, in the event of a failure:
• The circuit-breaker closest to the fault trips.
• The other circuit-breakers are locked for a programmable time.
For further details see the chapter "Specific applications" on page 156.
Startup enable
The function allows you to modify the threshold of the protection for a period that can be set by the user. The
period is activated when a threshold is exceeded (startup threshold), which can be programmed by the user
via Ekip Connect software.
NOTE: for protection D the startup thresholds are available for both forward and backward
direction.
88 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
Tolerance Calculation
ABB ANSI (4) Threshold Time Tolerance t t (2)
threshold formula t t (1)
± 7 % If ≤ 6 In
I5 = 0.6...10 In t5 = 0.05...0.8 s The better of the two values:
S2 50 TD ± 10 % If > t t = t5
step = 0.1 In step = 0.01 s ± 10 % or ± 40 ms
6 In
± 7 % If ≤ 6 In
I7 Fw/Bw = 0.6...10 In t7 Fw/Bw = 0.1...0.8 s The better of the two values:
D 67 ± 10 % If > t t = t7
step = 0.1 In step = 0.01 s ± 10 % or ± 40 ms
6 In
The better of the two values:
U15= 0,05….0,98 Un t15 = 0.05…120 s ± 10 % or ± 40 ms (for a time
UV2 27 ±2% t t = t15
step = 0.001 Un step = 0.01 s set < 5 s) / ± 100 ms (for a time
set > 5 s)
The better of the two values:
U16= 1….1,5 Un t16 = 0.05…120 s ± 10 % or ± 40 ms (for a time
OV2 59 ±2% t t = t16
step = 0.001 Un step = 0.01 s set < 5 s) / ± 100 ms (for a time
set > 5 s)
The better of the two values:
f17= 0,9….1 fn t17 = 0,06…300 s ± 10 % (min=30ms) or ± 40 ms
UF2 81L ± 1 % (5) t t = t17
step = 0.001 fn step = 0.01 s (for a time set < 5 s) / ± 100 ms
(for a time set > 5 s)
The better of the two values:
f18= 1….1,1 fn t18 = 0,06…300 s ± 10 % or ± 40 ms (for a time
OF2 81H ± 1 % (5) t t = t18
step = 0.001 fn step = 0.01 s set < 5 s) / ± 100 ms (for a time
set > 5 s)
(1)
Calculation of t t is valid for values exceeding the tripping threshold of the protection.
(2)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tripping time tolerance of ± 10 % will become ± 20%.
(3)
For the startup functions, the specified time is the period during which the protection with the different threshold remains active, calculated from the
moment the startup threshold is exceeded.
(4)
ANSI / IEEE C37-2 encoding.
(5)
Valid tolerance for frequencies in the range: fn ± 2 %. For frequency outside the range a tolerance of ± 5 % applies.
89 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
12 - G Touch protections
Presentation G Touch protections are available in all the versions of trip units of the Generators range (Ekip G Touch and
Ekip G Hi-Touch).
List of protections
The following is a list of the G Touch protections:
Symbol Protection against
S(V) Voltage control short-circuit
RV Residual voltage
RQ Reverse reactive power
OQ Maximum reactive power
OP Maximum active power
UP Minimum active power
Operating principle
The protections have a series of parameters available allowing the user to adjust the activation thresholds and
the opening times of the circuit-breaker.
The operating principle of all the protections is similar: if the voltage or power signal exceeds the set protection
threshold, the specific protection will enter the alarm condition and will begin to delay.
The duration of the delay depends on the threshold and time parameters set, and depending on the dynamic
of the signal we can have two behaviours:
• If the alarm condition persists, the trip unit opens the circuit-breaker.
• If the signal drops below the protection threshold, the trip unit exits from the alarm condition, interrupts
the delay and doesn't open the circuit-breaker.
The protection thresholds are distinguished by type:
• The voltage protections are related to the rated size of the voltage line-to-line set on the trip unit (Un).
• The power protections refer to the product of current and rated voltage (Sn = √3 * In * Un).
IMPORTANT:
• To manage the circuit-breaker tripping with a specific protection, the protection itself
must be enabled and, if supported, must have the Trip Enable parameter activated.
• All the protections have a default configuration: if enabled, check the parameters and
make the necessary changes according to the requirements of your installation.
90 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 12 - G Touch protections
ABB | SACE Emax 2
S(V) Protection
Path
Main page - Menu - Advanced
t
I20 S(V) Function
S(V) protection protects against short circuits, with a threshold sensitive to the value of the voltage.
Following a voltage drop, the I20 threshold varies according to two different modes:
• Step Mode provides for variation in steps according to the Ul parameter.
t20 • Linear Mode provides for dynamic variation base on Ul and Uh parameters.
I20 I20
I I20 I20
Ks x I20 Ks x I20
UI Uh
Ul V V
Figure 22
Parameters
It is possible to modify various parameters:
Parameter Description
Enable To activate/deactivate the protection.
Allows you to choose the variation dynamic of the current threshold, as represented
Curve
in the two diagrams above.
It defines the current value that activates the protection when exceeded (with
reference to the curve, it is the part parallel to the y-axis).
Threshold I20
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug).
With the curve in step mode, it is the threshold that determines the variation in the
level of I20:
UI Threshold • With voltage ≥ Ul, the tripping threshold is I20.
(Step) • With voltage < Ul, the tripping threshold is Ks * I20.
It is represented both as an absolute value (Volts) and as a percentage (%Un, with
Un nominal value defined on the trip unit).
With the curve in linear mode, it is the threshold that determines the variation in the
level of I20:
• With voltage ≥ Uh, the tripping threshold is I20.
Threshold Uh e Ul
• With voltage < Uh and > Ul, the tripping threshold changes gradually.
(Linear)
• With voltage ≤ Ul, the tripping threshold is Ks * I20
It is represented both as an absolute value (Volts) and as a percentage (%Un, with
Un nominal value defined on the trip unit).
Constant for calculation of the variation of the I20 threshold. To be applied in
Ks threshold
different ways according to the type curve selected.
This is the delay time between the exceeding of the I20 threshold (determined by the
Time t20 voltage value read) and the sending of the opening command (with reference to the
curve, t20 affects the entire curve, shifting it along the y-axis).
91 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 12 - G Touch protections
ABB | SACE Emax 2
RV Protection
Path
Main page - Menu - Advanced
t
U22 RV Function
RV protection protects against loss of insulation (residual voltage). The residual voltage U 0 is calculated by
the vectorial sum of the phase voltages.
NOTE: the protection is activated and available for:
t22 • Four-pole circuit-breakers
• Three-pole circuit-breakers configured with external neutral voltage (parameter Neutral
connection= Present, available in the menu of the Ekip Measuring module).
V When the residual voltage exceeds the activation threshold U22, the protection trips within a fixed time t22.
Parameters
It is possible to modify various parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the voltage value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold U22 the y-axis).
It is represented both as an absolute value (Volts) and a relative value (Un,
nominal value defined on the trip unit).
This is the delay time between the exceeding of the U22 threshold (determined
Time t22 by the voltage value read) and the sending of the opening command (in
reference to the curve, t22 affects the entire curve, shifting it along the y-axis).
RQ Protection
Path
Main page - Menu - Advanced
RQ t
Function
Q24; Kq RQ protection protects against reversal of reactive power, with an adjustable threshold according to the
parameter Sn (= √3 x Un x In).
When the reverse reactive power drops below the activation threshold Q24, the protection trips within a fixed
t24 time t24.
Adjustment of the constant Kq allows you to vary the tripping threshold of the protection: with Kq = 0 the
threshold is constant, while with Kq different from 0 the threshold has a slope, as illustrated in the following
figure.
Q24; Kq
Q Q
kq
P
P
Q24 kq=0 Q24 TRIP
TRIP
Figure 23 Figure 24
92 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 12 - G Touch protections
Continued from the previous page ABB | SACE Emax 2
Parameters
It is possible to modify various parameters:
Parameter Description
Enable To activate/deactivate the protection.
Threshold Kq It defines the slope of the protection function.
It defines the starting point on the Q axis of the protection curve.
It is represented both as an absolute value (kVAR) and a relative value (Sn,
referring to the rated voltage set on the trip unit).
Threshold Q24
NOTES: the threshold expressed in Sn is preceded by the sign “- “ in
order to indicate that it refers to reverse power.
This is the delay time between the exceeding of the tripping threshold and the
Time t24
sending of the opening command
It is the minimum voltage for activation of the protection. If a there is at least
Threshold Vmin one line-to-line voltage present below the Vmin threshold, the protection is not
active.
OQ Protection
Path
Main page - Menu - Advanced
t
Q27 OQ Function
OQ protection trips when the power supplied rises above the set threshold.
If the reactive power rises above the activation threshold, the protection trips within a fixed time set by the
user.
t27
Parameters
93 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 12 - G Touch protections
ABB | SACE Emax 2
OP Protection
Path
Main page - Menu - Advanced
t
P26 OP Function
OP protection trips when the active supplied rises above the set threshold.
If the active power rises above the activation threshold, the protection trips within a fixed time set by the user.
t26
Parameters
It is possible to modify various parameters:
P Parameter Description
Enable To activate/deactivate the protection.
It defines the active power value above which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold P26 the y-axis).
It is represented both as an absolute value (kW) and a relative value (Sn,
referring to the rated voltage set on the trip unit).
The delay time between the exceeding of the P26 threshold and the sending of
Time t26 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
UP Protection
Path
Main page - Menu - Advanced
t
UP Function
P23 UP protection trips when the power supplied drops below the set threshold.
If the active power drops below the activation threshold, the protection trips within a fixed time set by the
user.
t23 NOTE:
• The protection is not active for voltages <30V and if the circuit-breaker is open.
• The protection is active also for negative (reverse) active power, but is independent from the RP
P protection (protection against reverse active power).
Parameters
It is possible to modify various parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the active power value below which the protection is activated (with
reference to the figure above, the threshold is the part of the curve parallel to
Threshold P23 the y-axis).
It is represented both as an absolute value (kW) and a relative value (Sn,
nominal value defined on the trip unit).
The delay time between the exceeding of the P23 threshold and the sending of
Time t23 the opening command (with reference to the figure above, the threshold is the
part of the curve parallel to the x-axis).
UP protection has Trip Enable and Startup Enable , see page 71.
Via Ekip Connect it is also possible to access the blocking functions, see page 72.
94 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 12 - G Touch protections
ABB | SACE Emax 2
Tolerance Calculation
ABB ANSI (5) Threshold Tripping time Tolerance t t (2)
threshold formula t t (1)
The better of the two
I20 = 0.6...10 In; step = 0.1 In (6) values:
S(V) t20 = 0.05…30 s
51V Ul = 0.2…1 Un; step = 0.01 Un ± 10 % t t = t20 ± 10 % or ± 40 ms (for
(Step) step = 0.01 s
Ks = 0.1…1; step = 0.01 (6) a time set < 5 s) / ± 100
ms (for a time set > 5 s)
The better of the two
I20 = 0.6...10 In; step = 0.1 In (6)
values:
S(V) (3)
Ul = 0.2…1 Un; step = 0.01 Un (7) t20 = 0.05…30 s
51V ± 10 % t t = t20 ± 10 % or ± 40 ms (for
(Linear) Uh = 0.2…1 Un; step = 0.01 Un (7) step = 0.01 s
a time set < 5 s) / ± 100
Ks = 0.1…1; step = 0.01 (6)
ms (for a time set > 5 s)
The better of the two
values:
U22 = 0.05….0.5 Un t22 = 0.05…120 s
RV 59N ±5% t t = t22 ± 10 % or ± 40 ms (for
step = 0.001 Un step = 0.01 s
a time set < 5 s) / ± 100
ms (for a time set > 5 s)
The better of the two
Q24 = -1…-0.1 Sn; step = 0.001 Sn values:
t24 = 0.5…100 s
RQ 40/32R Kq = -2…2; step = 0.01 ± 10 % t t = t24 ± 10 % or ± 40 ms (for
step = 0.1 s
Vmin = 0.5...1.2 Un; step = 0.01 a time set < 5 s) / ± 100
ms (for a time set > 5 s)
The better of the two
values:
P26 = 0.4…2 Sn t26 = 0.5…100 s
OP 32OF ± 10 % t t = t26 ± 10 % or ± 40 ms (for
step = 0.001 Sn step = 0.5 s
a time set < 5 s) / ± 100
ms (for a time set > 5 s)
The better of the two
values:
Q27 = 0.4…2 Sn t27 = 0.5…100 s
OQ 32OF ± 10 % t t = t27 ± 10 % or ± 40 ms (for
step = 0.001 Sn step = 0.5 s
a time set < 5 s) / ± 100
ms (for a time set > 5 s)
The better of the two
values:
P23 = 0.1...1 Sn t23 = 0.5…100 s
UP 32LF ± 10 % t t = t23 ± 10 % or ± 40 ms (for
step = 0.001 Sn step = 0.5 s
a time set < 5 s) / ± 100
ms (for a time set > 5 s)
(1)
Calculation of t t is valid for values exceeding the tripping threshold of the protection.
(2)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tripping time tolerance of ± 10 % will become ± 20%.
(3)
The tripping threshold of the current for voltage values between Ul and Uh is calculated by performing the linear interpolation between the
thresholds Uh and I20 (first point on the line) and Ul and Ks * I20 (second point on the line). Ithreshold = [I20 * (1 - ks) * (Umeasured - Uh)] / (Uh - Ul) + I20.
(4)
The startup of protection UP is to be considered as the temporary deactivation time of the protection, starting from the exceeding of the startup
threshold.
(5)
ANSI / IEEE C37-2 encoding.
(6)
The setting of the Ks threshold must guarantee the following constraint: Ks * I20 ≥ 0.6 In.
(7)
The setting of thresholds Uh and Ul must guarantee the following constraint: Uh > Ul.
95 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 12 - G Touch protections
ABB | SACE Emax 2
13 - G Hi-Touch protections
Presentation The G Hi-Touch protections are available with the Ekip G Hi-Touch trip unit.
List of protections
The following is a list of the G Hi-Touch protections:
Symbol Protection against
ROCOF Rate of change of frequency
S2(V) Voltage control short-circuit
RQ2 Reverse reactive power
Operating principle
The protections have a series of parameters available allowing the user to adjust the activation thresholds and
the opening times of the circuit-breaker.
The operating principle of all the protections is similar: if the frequency or power signal exceeds the set
protection threshold, the specific protection will enter the alarm condition and will begin to delay.
The duration of the delay depends on the threshold and time parameters set, and depending on the dynamic
of the signal we can have two behaviours:
• If the alarm condition persists, the trip unit opens the circuit-breaker.
• If the signal drops below the protection threshold, the trip unit exits from the alarm condition, interrupts
the delay and doesn't open the circuit-breaker.
The protection thresholds are distinguished by type:
• The frequency protections are related to the rated size of the frequency set on the trip unit (Un).
• The power protections refer to the product of current and rated voltage (Sn = √3 * In * Un).
IMPORTANT:
• To manage the circuit-breaker tripping with a specific protection, the protection itself
must be enabled and, if supported, must have the Trip Enable parameter activated.
• All the protections have a default configuration: if enabled, check the parameters and
make the necessary changes according to the requirements of your installation.
96 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 13 - G Hi-Touch protections
ABB | SACE Emax 2
ROCOF Protection
Path
Main page - Menu - Advanced
t
f28 ROCOF Function
ROCOF protection protects against rapid frequency variations.
When the frequency change exceeds the control threshold f28 over time, the protection trips within a fixed
time t28.
t28 It is also possible to characterize the protection according to the way in which frequency varies (increase or
decrease), or to consider both conditions.
Hz/s f(Hz)
frequency
after failure
failure
50/60 Hz
frequency
after failure
Time
Figure 25
Parameters
It is possible to modify various parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the maximum allowed frequency variation rate over time, above which
Threshold f28 the protection will be activated.
It is represented as an absolute value (Hertz / second).
It defines whether the protection monitors increases, decreases, or both
Trip Direction
variations.
This is the delay time between the exceeding of the f28 threshold and the
Time t28
sending of the opening command
97 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 13 - G Hi-Touch protections
ABB | SACE Emax 2
S(V) Protection
Path
Main page - Menu - Advanced
t
I21 S2(V) Function
S2(V) protection:
• It protects against short circuits, with a threshold sensitive to the value of the voltage.
• It is independent from S(V) protection: it is therefore possible to program thresholds and functions of the
two protections in order to have different installation solutions (for example: signalling with S(V) and trip
t21 with S(V)2, or vice versa, or S(V) and S(V)2 both for signalling or trip).
When the activation threshold I21 is exceeded, the protection trips within a fixed time t21.
Following a voltage drop, the I21 threshold varies according to two different modes:
I • Step Mode provides for variation in steps according to the Ul2 parameter.
• Linear Mode provides for dynamic variation base on the parameters Ul2 and Uh2.
I21 I21
I21 I21
Parameters
It is possible to modify various parameters:
Parameter Description
Enable To activate/deactivate the protection.
It defines the variation dynamic of the current threshold, as represented in the two
Curve
diagrams above.
It defines the current value that activates the protection when exceeded (with
reference to the curve, it is the part parallel to the y-axis).
Threshold I21
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug).
With the curve in step mode, it is the threshold that determines the variation of the
level of I21:
Threshold Ul2 • With voltage ≥ Ul2, the tripping threshold is I21.
(Step) • With voltage < Ul2, the tripping threshold is Ks2 * I21.
It is represented both as an absolute value (Volts) and as a percentage (of Un,
nominal value defined on the trip unit).
With the curve in linear mode, it is the threshold that determines the variation of the
level of I21:
• With voltage ≥ Uh2, the tripping threshold is I21.
Threshold Uh2 e
• With voltage < Uh2 and > Ul2, the tripping threshold changes gradually.
Ul2 (Linear)
• With voltage ≤ Ul2, the tripping threshold is Ks2 * I21.
It is represented both as an absolute value (Volts) and as a percentage (of Un,
nominal value defined on the trip unit).
Constant for calculation of the variation of the I21 threshold. To be applied in
Threshold Ks2
different ways according to the type curve selected.
This is the delay time between the exceeding of the I21 threshold (determined by the
Time t21 voltage value read) and the sending of the opening command (in reference to the
curve, t21 affects the entire curve, shifting it along the y-axis).
98 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 13 - G Hi-Touch protections
ABB | SACE Emax 2
RQ2 Protection
Path
Main page - Menu - Advanced
t
RQ2 Function
RQ2 protection:
Q24; Q25; Kq; Kq2
• It protects against the reversal of reactive power, with an adjustable threshold according to the active
power value.
t24 • It is a variant of the RQ protection available with Ekip G Hi-Touch trip units.
When the reverse reactive power drops below activation threshold, the protection trips within a fixed time t24.
The parameters Q24 and Q25, with the respective constants Kq and Kq2, allow you to characterize the
Q24; Q25; Kq; Kq2 response curve with a dynamic behavior.
In particular, the adjustment of the constants Kq and Kq2 allows you to vary the tripping threshold of the
protection: with Kq and Kq2 = 0 the threshold is constant, while with Kq and Kq2 different to 0 the threshold
has a slope, as illustrated in the following image.
NOTE: The trip unit accepts parameters in accordance with the following limitations: Q24 <
Q25 e Kq < Kq2 (slope).
Q Q
kq2 kq
P P
Q24 kq=0
Q24
Q25 kq2=0 TRIP
Q25
TRIP
Figure 27 Figure 28
Parameters
It is possible to modify various parameters:
Parameter Description
Enable To activate/deactivate the protection.
Threshold Kq It defines the slope of the protection function.
Threshold Kq2 It defines the slope of the protection function.
It defines the reactive power value for which the protection is activated.
It is represented both as an absolute value (kVAR) and a relative value (Sn,
referring to the rated voltage set on the trip unit).
Threshold Q24
NOTE: the threshold expressed in Sn is preceded by the sign “- “ in
order to indicate that it refers to reverse power.
It defines the reactive power value for which the protection is activated.
It is represented both as an absolute value (kVAR) and a relative value (Sn,
referring to the rated voltage set on the trip unit).
Threshold Q25
NOTE: the threshold expressed in Sn is preceded by the sign “- “ in
order to indicate that it refers to reverse power.
This is the delay time between the exceeding of the tripping threshold and the
Time t24
sending of the opening command
It is the minimum voltage for activation of the protection. If a there is at least
Threshold Vmin one line-to-line voltage present below the Vmin threshold, the protection is not
active.
99 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 13 - G Hi-Touch protections
ABB | SACE Emax 2
Tolerance Calculation
ABB ANSI (1) Threshold Tripping time Tolerance t t (3)
threshold formula t t (2)
The better of the two
I21 = 0.6...10 In; step = 0.1 In (4) values:
S2(V) t21 = 0.05…30 s
51V Ul2 = 0.2…1 Un; step = 0.01 Un ± 10 % t t = t21 ± 10 % or ± 40 ms (for
(Step) step = 0.01 s
Ks2 = 0.1…1; step = 0.01 (4) a time set < 5 s) / ± 100
ms (for a time set > 5 s)
The better of the two
I21 = 0.6...10 In; step = 0.1 In (4)
values:
S2(V) Ul2 = 0.2…1 Un; step = 0.01 Un (7) t21 = 0.05…30 s
51V ± 10 % t t = t21 ± 10 % or ± 40 ms (for
(Linear) (5) Uh2 = 0.2…1 Un; step = 0.01 Un (7) step = 0.01 s
a time set < 5 s) / ± 100
Ks2 = 0.1…1; step = 0.01 (4)
ms (for a time set > 5 s)
Q24 = -1…-0.1 Sn; step = 0.001 Sn The better of the two
Q25 = -1…-0.1 Sn; step = 0.001 Sn values:
t24 = 0.5…100s
RQ2 (6) 40/32R Kq = -2…2; step = 0.01; ± 10 % t t = t24 ± 10 % or ± 40 ms (for
step = 0.1 s
Kq2 = -2…2; step = 0.01 a time set < 5 s) / ± 100
Vmin = 0.5...1.2 Un; step = 0.01 ms (for a time set > 5 s)
The better of the two
f28 = 0.4…10 Hz / s t28 = 0.5...10 s
ROCOF 81R ± 10 % (8) t t = t28 values:
step = 0.2 Hz / s step = 0.01 s
± 20 % o 200 ms
(1)
ANSI / IEEE C37-2 encoding.
(2)
Calculation of t t is valid for values exceeding the tripping threshold of the protection.
(3)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tripping time tolerance of ± 10 % will become ± 20%.
(4)
The trip unit accepts the I21 and Ks2 parameters provided that their product is greater than or equal to 0.6 Hz / s: Ks2 * I21 >= 0.6 Hz / s.
(5)
The tripping threshold of the current for voltage values between Ul2 and Uh2 is calculated by performing the linear interpolation between the
thresholds Uh2 and I21 (first point on the line) and Ul2 and Ks2 * I20 (second point on the line). Ithreshold = [I10 * (1 - ks2) * (Umeasured - Uh2)] / (Uh2 -
Ul2) + I21.
(6)
The tripping threshold of protection RQ2 is calculated by the intersection of the 2 straight lines formed by Q24 and Kq (Pthreshold = Qmeasured * Kq +
Q24) and from Q25 and Kq2 (Pthreshold = Qmeasured * Kq2 + Q25). If the constants Kq and Kq2 are set to 0, the highest threshold will apply (see the
sample graph in the chapter on the RQ protection).
(7)
The setting of thresholds Uh2 and Ul2 must guarantee the following constraint: Uh2 > Ul2.
(8)
± 20 % for the threshold 0.4 Hz / s.
100 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 13 - G Hi-Touch protections
ABB | SACE Emax 2
Presentation The presence of SGR external toroids and Rc allows the use of Gext and Rc protections respectively.
External toroids can be connected to all versions of the protection trip units of the Touch range.
NOTE: the Rc protection RC requires the presence of an Rc Rating Plug and an Ekip Measuring
Pro module.
List of protections
Operating principle
The protections have a series of parameters available allowing the user to adjust the activation thresholds and
the opening times of the circuit-breaker.
The operating principle of all the protections is similar: if the current exceeds the protection threshold that has
been set, the specific protection enters the alarm condition and starts timing.
The duration of the delay depends on the threshold and time parameters set, and two cases can be
distinguished according to the dynamics of the current:
• If the alarm condition persists, the trip unit opens the circuit-breaker.
• If the current drops below the protection threshold, the trip unit exits from the alarm condition, interrupts
the delay and does not make the circuit-breaker open.
For the Gext protection the protection threshold is related to the size of the current of the of the SGR external
toroid and, for the Rc protection, to of preset current values.
IMPORTANT:
• To manage the circuit-breaker tripping with a specific protection, the protection itself
must be enabled and, if supported, must have the Trip Enable parameter activated.
• All the protections have a default configuration: in the event of activation, check the
parameters and make changes according to the requirements of your installation.
Gext Protection
Path
Main page - Menus - Settings - Circuit Breaker - Ground protection (enabling the presence of the external
toroid)
t Main page - Menus - Protections (protection parameters)
I4 Gext NOTE: the menu containing the Gext protection parameters is activated if the presence of
the SGR external toroid was previously enabled in the appropriate menu.
t4 Function
Gext protection protects against external earth faults, detecting the fault current with the appropriate SGR
external toroid
I NOTE:
When the activation threshold is exceeded, the protection trips within a fixed or dynamic time (the time
decreases as the current reading increases).
Availability
Protection G is an alternative to protection Gext on Ekip Touch and Ekip G Touch type releases (by enabling
the presence of external toroid S.G.R. so as to display the Gext protection), while both protections are
available with trip units Ekip Hi-Touch and Ekip G Hi-Touch.
Enabling parameters
Parameters to enable the external toroid presence in the relevant menu:
Parameter Description
External
It allows the presence of the SGR external toroid to be activated
Toroid
It allows you to select the reference current of the protection among four available sizes.
NOTE: the menu is available after the presence of the SGR external toroid has been
enabled
Toroid size
IMPORTANT: the current selected from the menu must be consistent with
the size of the SGR external toroid connected to the protection trip unit.
Protection parameters
The following is a description of the protection parameters:
Parameter Description
To activate/deactivate the protection.
Enable IMPORTANT: the protection is inhibited automatically by the protection trip
unit if the absence of the SGR external toroid is detected
It determines the dynamic of the curve and the tripping time, fixed or dynamic according
to the selection:
• t = k (ANSI 50GTD): fixed time trip.
Curve
• t = k / I 2 (ANSI 51G): inverse time tripping.
The calculation of the tripping time of the inverse time curve is based on a mathematical
expression. The details provided in the table on page 104.
The value I41 contributes to calculate the tripping time, and also defines the current value
that, if exceeded, activates the protection.
Threshold I41
It is represented both as an absolute value (Amperes) and as a relative value (In, nominal
value defined by the size of the SGR external toroid).
The selected function determines the contribution of t41:
• t = k: t41 is the delay time between the exceeding of the I41 threshold and the sending
Time t41
of the opening command.
• t = k / I 2: t41 contributes to calculate the tripping time.
The prealarm of the Gext protection indicates that the current measured is close to the
tripping threshold of the protection.
The prealarm state is activated for currents higher than a threshold that can be set by the
I41 Prealarm
user, and is deactivated in two cases:
Threshold
• Detected current lower than the prealarm threshold.
• Detected current higher than the protection tripping threshold.
A value within the 50 % ... 90 % range can be entered, with 1 % steps.
Additional functions
Gext protection has Trip Enable, Zone Selectivity, StartUp Enable, see page 72.
Via Ekip Connect it is also possible to access the blocking functions, see page 72.
102 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 14 - External toroid protections
ABB | SACE Emax 2
RC Protection
Path
Main page - Menus - Settings - Circuit Breaker - Ground protection (reading of the external toroid setting)
Main page - Menus - Advanced (protection parameters)
t
Idn Rc
NOTE: the menu with the parameters of Rc protection is activated if Rc type Rating Plug and
Ekip Measuring Pro modules are present and correctly installed.
Function
tdn
Rc protection protects against the residual current earth faults by detecting the fault current with the
appropriate external Rc toroid.
I
When the activation threshold is exceeded, the protection trips within a fixed time. The user can set the
threshold and the tripping time of the protection.
Availability
protection G is an alternative to protection Rc on Ekip Touch and Ekip G Touch type releases (by enabling the
presence of external toroid Rc so as to display the Rc protection), while both protections are available with
trip units Ekip Hi-Touch and Ekip G Hi-Touch.
Parameters
Here is a list of the available parameters:
Parameter Description
It defines the current value that activates the protection when exceeded.
Threshold Idn
It is represented as an absolute value (Ampere).
This is the delay time between the exceeding of the Idn threshold and the sending of
Time tdN
the opening command
103 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 14 - External toroid protections
ABB | SACE Emax 2
Continued from the previous page
Threshold
Calculation Calculation
ABB ANSI (1) Threshold toleran- Time Tolerance t t (3)
formula t t (2) example t t (2)
ce (3)
The better of the
I41 = 0.1...1 In toroid t41 = 0.1…1 s
Gext (t = k) 50GTD ±7% t t = t41 - two values: ± 10 %
step = 0.001 In step = 0.05 s (6)
or ± 40 ms
t t = 0.32 s with:
I41 = 0.1...1 In toroid t41 = 0.1…1 s t t = 2 / (If /
Gext (t = k / I 2) 51G ±7% I41 = 0.8 In; t41 = ± 15 %
step = 0.001 In step = 0.05 s (6) I41) 2
0.2 s; If = 2 In
tdn = 0.06 - 01
Idn = 3 - 5 - 7 - 10 - 140 ms @ 0.06 s (7)
Rc 64 50NTD -20 % ÷ 0 - 0.2 - 0.3 - 0.4 t t = tdn -
20 - 30 A 950 ms @ 0.8 s (7)
- 0.5 - 0.8 s
Threshold Calculation
ABB ANSI (1) Threshold Time (5) Tolerance t t (3)
tolerance (3) formula t t (3)
The better of the two
I41 startup = 0.1...1 In toroid t41 startup = 0.1…30 s
Gext (Startup) (4) - ±7% t t = t41 values: ± 10 % or ±
step = 0.02 In toroid step = 0.01 s
40 ms
t41 sdz= 0.04…0.2 s
Gext (SdZ) 68 ±7% t t = 2 / (If / I41) 2 -
step = 0.01 s
(1)
ANSI / IEEE C37-2 encoding.
(2)
t t calculation is valid for If values that have exceeded the trip threshold of the protection. Use fault current and threshold values expressed in In to
calculate t t, as shown in the example.
(3)
Tolerances valid with trip unit energized in service conditions or with auxiliary power supply, tripping time ≥ 100 ms, temperature and currents within
operating limits. If these conditions are not guaranteed, the threshold tolerance becomes: ± 15 % and tolerance tt becomes: ± 20 %.
(4)
Startup can be activated only with the function set to fixed time.
(5)
For the startup functions, the specified time is the period during which the protection with the different threshold remains active, calculated from
the moment the startup threshold is exceeded.
(6)
The maximum time permitted by the trip unit for type UL circuit-breakers is 0.4 s. If a higher value is entered, the protection trip unit will signal error
and force the parameter to 0.4 s.
(7)
Maximum tripping time.
104 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 14 - External toroid protections
ABB | SACE Emax 2
15 - Touch measurements
Presentation Touch measurements are available in all the models of trip units of the Ekip Touch range.
The following is a list of the available measurements:
Measurements Description
Instantaneous currents Real Time measurements of the currents
Trip List of the trip for basic protections
Events List of events, changes of state, alarms recorded by the trip unit
Maximum current History of the maximum currents recorded with an interval that can be set
Minimum current History of the minimum currents recorded with an interval that can be set
Peak factor Real time measurement of the peak factor of the currents
Contact Wear Calculation of the wear of the contacts
Datalogger Recording of the waveform of the currents and the digital states
Operation counters Number of mechanical and electrical operations
Instantaneous currents
Description
Instantaneous currents are real time measurements of earth fault and phase currents, expressed as r.m.s.
value.
• The measurement of the earth fault current is available only with LSIG versions of trip units.
• The measurements in Amperes are available from a minimum value of 0.03 In for the phase
currents, and 0.08 In the for earth fault current. For lower currents “…” is displayed.
• In the Histograms page, the graphical representation of the currents is in relation to 1 In, with
a maximum value of 1.25 In
Tripping
Path
Main page - Menu - Measurements - Historicals
Description
The trip unit is able to record the last 30 openings of the circuit-breaker caused by protection trips (trips).
The trips are associated to the following information:
• The protection that tripped.
• The progressive number.
• The date and time of the opening (referring to the internal clock)
• The measurements associated to the trip protection.
NOTE:
• Each trip is associated to a progressive number that is increased with every trip.
• If the trip unit has exceeded the threshold of the 30 openings, the oldest ones are progressively
overwritten.
105 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 15 - Touch measurements
Continued from the previous page ABB | SACE Emax 2
Correlated measurements
The type of protection involved determines the measurements recorded at the moment of tripping:
Protection
Measurements recorded at the moment of the tripping
against
Phase currents L1, L2, L3, Ne, Ig, Ige, Irc.
NOTE:
• Ne is available with four-pole or three-pole circuit brakers with external Neutral
Current • Ig is available with a trip unit in the LSIG version, in the case of trip due G
protection.
• Ige is available with a trip unit with a SGR toroid, in the case of trip due Gext
protection.
• Irc is available with a trip unit with a Rc toroid.
Phase currents L1, L2, L3, Ne.
Temperature
NOTE:
the temperature cannot be viewed from the display.
Events
Path
Main page - Menu - Measurements - Historicals
Description
The trip unit can record the last 200 events, referring mainly to variations in state and operation.
Specifically, the recorded events can supply information on:
• Trip unit: configuration status of the bus, operating mode, active set, auxiliary power supply.
• Protections: delay in action or alarm.
• Connection states and connection alarms: circuit-breaker, current sensors, trip coil, Rating Plug.
• Tripping: state of the opening command, or signal of tripping due to protection.
NOTE: in the list of the events, the first available is the most recent one. If the trip unit has
exceeded the threshold of 200 events, the oldest ones are progressively overwritten.
106 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 15 - Touch measurements
Continued from the previous page ABB | SACE Emax 2
Correlated information
All events are correlated with the following information:
• Icon that identifies the type.
• Name
• Date and time.
There are 4 icons that identify the type of event:
Icon Description
Event reported for information purposes.
Description
The maximum and minimum currents are the recordings of the measurements of the maximum and minimum
phase currents performed by the trip unit, and that can be displayed by selecting I Max and I Min in the
menu Historicals - Measurements.
The interval between one measurement and the other can be set through the parameter Monitor time,
available in the menu Settings.
The recordings can be reset through the command Reset measurements, available in the menu Historicals
- Measurements.
Correlated information
Al measurements are correlated with the following information:
• The time interval since the previous measurement.
• The phase to which it refers, and value in Amperes.
• The date and time (referring to the internal clock).
• Graphical representation in the form of a histogram on a time axis.
NOTE:
• If the value is less than 0,03 In, “…” is shown instead of the value in Amperes.
• The graphical representation is referred to 1 In, with a maximum value of 1.25 In
• When the parameter “Monitor time” is modified, the trip unit performs an immediate recording.
Peak factor
Path
Main page - Menus - Measurements
Description
The selection of Peak factor in the menu Measurements allows you to display real time measurements of
the peak factors of the phase currents.
The measurements are expressed as a ratio between the peak values and RMS values, for each individual
phase.
107 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 15 - Touch measurements
ABB | SACE Emax 2
Contact Wear
Path
Main page - Menu - Measurement - Maintenance
Description
Contact wear gives an estimation of the conditions of the circuit-breaker's main contacts.
The value is expressed as a percentage, and is 0 % in the case of no wear, and 100 % in the case of total
wear.
The contact wear is calculated automatically by the trip unit at every opening for protection or, in the presence
of an auxiliary power supply, also at every manual opening of the circuit-breaker.
NOTE:
Datalogger
Path
Main page - Menus - Settings
Description
The datalogger it is a function that allows the recording of data associated to a trigger event.
The data recorded are:
• Analog measurements: phase currents and line-to-line voltages (if the Ekip Measuring or Ekip Measuring
Pro module is present).
• Digital events: protection alarms, circuit-breaker state signals, tripping of protections.
When the datalogger is activated, the protection trip unit continuously acquires data, by filling and emptying
an internal buffer. If a trigger event occurs, the trip unit inhibits acquisition (either immediately or with a time-
lag that can be adjusted by the user) and stores the data, which can then be downloaded to a PC for reading
and analysis.
IMPORTANT: the function is available with trip unit energized with auxiliary voltage.
Figure 29
Pos. Description
A Trigger event
Data samples
B
NOTE: the set sampling frequency establishes the number of samples acquired per
second.
C Time delay before stopping of recording
Recording window
D
NOTE: the window changes, depending on the set sampling frequency.
108 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 15 - Touch measurements
Continued from the previous page ABB | SACE Emax 2
Parameters that can be the set and the commands of the function are:
Parameter Description
It selects the number of recordings (1 or 2).
Number of
dataloggers NOTE: the recordings are independent, but they share the sampling
frequency and the type of memory.
It determines the number of data logs recorded. There are four options available:
1200, 2400, 4800, 9600 Hz.
Sampling
frequency IMPORTANT:
• A high frequency allows a more accurate analysis of the data.
• The higher the frequency, the shorter the recording.
It allows the user to set the parameters and to manually command recording number
1.
• Stop Source: it selects the trigger event, on the occurrence of which the recording
is to be stopped.
• Stop Delay: it sets the delay after the trigger event after which recording is to be
Datalogger 1 stopped
• Restart command: it starts recording.
• Stop command: it stops the recording and saves it in memory.
With Ekip Connect software it is possible to select the parameter Memory Type, not available on the display.
Such parameter allows to choose whether to keep the recording also with the trip unit off (non-volatile) or to
delete it if the auxiliary power disappears (volatile).
NOTE: the parameter is configured by default as non-volatile.
• If Memory Type = Non volatile, the life of the internal battery of Ekip Touch may be sensibly lower
than the declared value in case a recording is stored but auxiliary power supply is not present.
• If the Memory Type is Volatile and the auxiliary supply is lost, the datalogger will rerun the
recording when re-powered and the previously memorized data will be lost.
Operation counters
Path
Main page - Menu - About - Circuit-breaker
Description
In the presence of auxiliary power, the trip unit records a series information relating to the openings of the
circuit-breaker:
• The number of manual openings.
• The total number of operations (manual + trips).
By activating the communication with the trip unit, the following counters are also available:
• The number of openings due to tripping of protections.
• The number of openings due tripping of failed protections.
• The number of opening tests performed.
Summary table of basic The following table summarises the basic measurements:
measurements
Normal operating
Quantities measured Monitor time Accuracy
range
Phase currents (I1, I2, I3, Ine) 0.03…16 In 0.2…1.2 In 1%
Earth fault current (Ig) 0.08…4 In 0.2…1.2 In 2%
NOTE: the accuracies refer to normal operating ranges, as established by IEC 61557-12.
109 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 15 - Touch measurements
ABB | SACE Emax 2
Presentation These measurements are available in all the models of trip units of the Ekip TOUCH range supplied with Ekip
Measuring module or Ekip Measuring Pro.
The following is a list of the available measurements:
Measurements Description
Instantaneous voltages Real Time measurements of the voltages
Instantaneous power Real Time measurements of the active, reactive, apparent power
Trips List of the trips due to voltage, frequency, power
Maximum voltage History of the maximum voltages recorded with an interval that can be set
Minimum voltage History of the minimum voltages recorded with an interval that can be set
Maximum power History of the maximum active powers recorded with an interval that can be set
Average power History of the average active powers recorded with an interval that can be set
Power factor Real time measurement of the power factor
Instantaneous
Measurement of the line frequency
frequency
Energy counters Measurement of active, reactive, apparent energy
With the Ekip Measuring Pro module and Ekip Synchrocheck, a further set of measurements is activated:
Measurements Description
Measurements related to the function of synchronism between two
Synchrocheck
independent power supply systems
Power references
Displayed operating ranges and maximum values of power described in this chapter are given in absolute
value or in relation to:
• Pn for the total power (Sn = In * Un * √3).
• Pn for the phase power (Pn = In * Un / √3).
Instantaneous voltages
Description
Instantaneous voltages are measurements in real time of the line-to-line and phase voltages.
NOTE: the measurements of the phase voltages are available with four-pole or three-pole
circuit-breakers configured with external neutral.
• "..." is displayed, for voltage values lower than 5 V, "> 1.25 Un" is displayed for voltage values
greater than 1.25Un (example: with Un = 100 V, "> 125 V" is displayed).
• In the Histograms page, the graphical representation of the voltages relates to 1 Un, with a
maximum value of 1.25
110 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 16 - Ekip Measuring Measurements
ABB | SACE Emax 2
Instantaneous power
Description
Instantaneous power values are real time measurements of the total and phase power
NOTE: phase power measurements are available with four-pole circuit-breakers or three-pole
circuit-breakers with external neutral.
The measurements in kW or kVAR are available with minimum voltages of 5 V and minimum currents of 0.03
In The maximum measurable power value is 1.25 Pn (phase power) / 1,25 Sn ( total power).
NOTE: with voltages or currents lower than the minimum values, or power higher than 1.25
Pn / 1,25 Sn, the indication “…” is shown.
Tripping
Path
Main page - Menu - Measurements - Historicals
Description
The presence of the Ekip Measuring Pro module introduces other types of trips, relating to the protections
active with Measuring Pro.
The ways to access theses pages and the information contained are similar to those for the trips of the Basic
protections.
Correlated measurements
The type of protection involved determines the measurements recorded at the moment of tripping:
Protection against Measurements recorded at the moment of the tripping
Phase currents (L1, L2, L3, Of), and line-to-line voltages (U12, U23, U31).
Voltage
NOTE: if protection RV trips, U0 is also recorded.
Frequency Phase currents (L1, L2, L3, Of), and line frequency.
Phase currents (L1, L2, L3, Of), and total power (active or apparent depending
Power
on the protection tripped).
111 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 16 - Ekip Measuring Measurements
ABB | SACE Emax 2
Description
The Maximum and Minimum Voltages are recordings of the measurements of maximum and minimum phase-
to-phase voltages made by the trip unit, and that can be displayed by selecting U Max and U Min in the
menu Historicals - Measurements.
The interval between one measurement and the other can be set through the parameter Monitor time,
available in the menu Historicals.
The recordings can be reset through the command Reset measurements, available in the menu Historicals
- Measurements.
Correlated information
Al measurements are correlated with the following information:
• The time interval since the previous measurement.
• The phase-to-phase voltage to which it refers, and value in Volt.
• The date and time (of the internal clock).
• Graphical representation in the form of a histogram on a time axis.
NOTE:
• If the value is less than 5 V, “…” is shown instead of the Volt values.
• The graphical representation is in reference to 1 Un, with a maximum value of 1.25 Un
• When the parameter Monitor time is modified , the trip unit performs an immediate recording.
Description
The maximum and minumun power are the recordings of the measurements of total maximum and minumun
active power made by the trip unit, and that can be displayed by selecting P Max and P Min in the menu
Historicals - Measurements.
The interval between one measurement and the other can be set through the parameter Monitor time,
available in the menu Historicals.
The recordings can be reset through the command Reset measurements, available in the menu Historicals
- Measurements.
NOTE: with external communication, recordings of total, maximum and average reactive and
apparent power measurements are also available.
Correlated information
Al measurements are correlated with the following information:
• The time interval since the previous measurement.
• The value in kW.
• The date and time (referring to the internal clock).
• Graphical representation in the form of a histogram on a time axis.
NOTE:
• If current and voltage are lower than the minimum measurable values, the power measurement
indicates “…” instead of the value in kW.
• The graphical representation is related to 1 Sn, with maximum value of 1.25 Sn.
• If the value is negative, the corresponding bar is represented with different color from those
with positive value.
• When the parameter Monitor time is modified , the trip unit performs an immediate recording.
112 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 16 - Ekip Measuring Measurements
ABB | SACE Emax 2
Power factor
Path
Main page - Menus - Measurements
Description
The power factor is the real time measurement of the ratio of total active power and total apparent power,
expressed as Cos φ.
The trip unit signals with an alarm if Cos φ drops below a control threshold, preset to 0.95. The threshold can
be modified via Ekip Connect software (from 0.5 to 0.95).
Energy counters
Path
Main page - Menus - Measurements - Energy - Energy counters
NOTE: for details on the pages, see the chapter Menu pages and menus, and the
paragraph Measurement history, beginning from page 45.
Description
The energy counters are the measurements of the total reactive and apparent active energy, updated every
minute.
The measurements can be reset through the command Reset counters, available in the menu Energy.
Instantaneous frequency
Path
Main page - Menus - Measurements
Description
The Instantaneous frequency is the real-time measurement of the line frequency, expressed in Hertz.
NOTE: measurement of the line frequency is available for voltages greater than 30 V (with
Un < 277 V) or 60 V (with Un > 277 V), and if the installation frequency is in the range 30...80
Hz.
Synchrocheck
Path
Main page - Menus - Measurements - Ekip Synchrocheck
Description
The Synchrocheck measurements relating to the function of synchronism between two independent power
source, are described in the dedicated section on accessories, in the paragraph dedicated to the Ekip
Synchrocheck module.
Summary table of Ekip The following table summarises the basic measurements:
Measuring measurements
Quantities measured Monitor time Normal operating range Accuracy
Line-to-line and phase 50…400 V (phase)
5 V…1.25 Un 0.5 %
voltages 100…690 V (phase-to-phase)
45…55 Hz (Frequency set = 50 Hz)
Line frequency 30…80 Hz 0.1 %
54…66 Hz (Frequency set = 60 Hz)
Active, reactive, and
-(16 In * 1.25 Un)… -1.2…-0.3 Sn / 0.3…1.2 Sn (total)
apparent power (total 2%
(16 In * 1.25 Un) -1.2…-0.3 Pn / 0.3…1.2 Pn (phase)
and phase)
Power factor -1…1 - 2%
Total apparent active, 1 kWh … 2 TWh
reactive, and apparent 1 kVAh … 2 TVARh - 2%
energy 1 kVARh … 2 TVAh
NOTE:
113 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 16 - Ekip Measuring Measurements
ABB | SACE Emax 2
17 - Hi-Touch measurements
Presentation Hi-Touch measurements are available for Ekip Hi-Touch and Ekip G Hi-Touch trip units.
IMPORTANT: the measurements are available with trip units equipped with auxiliary
power supply.
Waveforms
Path
Main page - Menu - Measurement - Network Analyzer - Waveforms
Description
The selection of one of the listed quantities opens the representation of the waveform of the selected quantity
acquired at the moment of selection.
The quantities with which the waveform can be displayed are:
• Phase currents L1, L2, L3, Of.
• Line-to-line voltages V12, V23, V31.
NOTE:
• The Ne phase current is available with four-pole or three-pole circuit-breakers with external neutral.
• For details on the pages, see the chapter “Menu Page and menus”, and the paragraph “Measurements
Menu”, on page 51.
ed2e9062-6939-4f67-a6c8-0b5f14228e92
Harmonics
Path
Main page - Menu - Measurement - Network Analyzer - Waveforms
Description
In the above mentioned page, the Harmonics key opens a representation in the form of a histogram of the
measurements of the harmonics constituting the waveform, and related to the frequency set in the menu
Settings.
In order to display the harmonics, you need to enable the calculation of the harmonics through the parameter
Harmonic, available in the menu Measurements.
NOTE: For details on the pages, see the chapter “Menu Page and menus”, and the paragraph
“Measurements Menu”, on page 51.
Network Analyzer
Path
Main page - Menu - Measurements - Network Analyzer (for the measurements and the counters)
Main page - Menu - Settings - Network Analyzer (for the control parameters)
Description
The Network Analyzer function allows you to set voltage and current controls over a long period, in order to
analyze your system.
To this purpose, voltages and currents are monitored, so as to find:
• Voltage sequences.
• Short voltage sags or interruptions.
• Short voltage increases.
• Slow voltage sags.
• Slow voltage increases.
• Unbalances between the voltages.
• Harmonic distortion of voltages and currents.
114 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 17 - Hi-Touch measurements
Continued from the previous page ABB | SACE Emax 2
Each monitoring is associated with control parameters set by the user and updated each time the set control
conditions occur.
NOTE:
• On the display the cumulative counter and the counter relevant to the last 24 hours of activity
(two counters for each monitoring operation) are available.
• With external communication, the cumulative counter and the counters relevant to the last
seven days of activity (eight counters for each monitoring) are available.
The general parameters available on the display are:
• Enable: to activate the Network Analyzer function and to modify the control parameters
• I Harm Analysis: to activate the analysis of the current harmonics.
• V Harm Analysis: to activate the analysis of the voltage harmonics.
Voltage sequences
There are three alarm counters:
• Over voltages: it records the number of times that the average value of the positive sequence (with the
rotation direction of the phases set: 1-2-3) or negative sequence (with the rotation direction of the phases
set: 3-2-1) calculated in the set interval exceeds a certain threshold.
• Under voltages: it records the number of times that the average value of the positive sequence (with the
rotation direction of the phases set: 1-2-3) or negative sequence (with the rotation direction of the phases
set: 3-2-1) calculated in the set interval drops below a threshold.
• Unbalance: it counts the number of times that the average value of the ratio between positive on negative
sequence (with the rotation direction 3-2-1) and negative on positive sequence (1-2-3) calculated in the
set interval rises above a certain threshold.
Parameters that can be set for the check are:
Parameter Description
It defines the upper alarm threshold for the Overvoltage counter.
V Threshold High
It is expressed as % Un.
It defines the lower alarm threshold for the Undervoltage counter.
V Threshold Low
It is expressed as % Un.
It defines the alarm threshold for the Unbalance counter, expressed as a % (0
Unbalance Th
% = symmetric and balanced system).
In the settings menu you can set the Monitor time parameter, which defines the time interval between
subsequent measurements.
NOTE: the monitor time is the same parameter available for the maximum current and voltage
measurements.
The positive and negative sequence counters are available on the display.
The checking is completed by these available measurements:
• Positive sequence relating to the period in progress (V pos seq).
• Negative sequence relating to the period in progress (V neg seq).
• Positive sequence calculated on the last period (Last V pos seq).
• Negative sequence calculated on the last period (Last V neg seq).
• Positive sequence calculated in last the 3 seconds (V pos seq).
• Negative sequence calculated in last the 3 seconds (V neg seq).
• Unbalance.
NOTE: The measurements of the sequences are available following the path: Main page -
Menus - Measurements - Network Analyzer- V Sequences - V 3s Sequences.
NOTE: the unbalance value measured by the protection trip unit stops when it reaches 200
%.
115 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 17 - Hi-Touch measurements
Continued from the previous page ABB | SACE Emax 2
t t
The alarm threshold available in the menu, V microinterr. Th, is expressed as %Un.
The cumulative (V microinterr.) and last day counters are available in the corresponding menus.
t t
The alarm threshold available in the menu, V Spike Threshold, is expressed as %Un.
The cumulative (Peaks) and last-day counters are available in the corresponding menus.
116 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 17 - Hi-Touch measurements
Continued from the previous page ABB | SACE Emax 2
NOTE:
• The trip unit accepts the parameters in accordance with the following limitation: V dur short <=
V dur middle <= V dur long.
• Since an event may belong to more typologies, only the counter corresponding to the longest
duration is incremented (long > middle > short).
Cumulative counters (Short sags, Medium sags, Long sags) and those of the last-day counters are available
in the respective menus.
NOTE:
• The trip unit accepts the parameters in accordance with the following limitation: V dur short <=
V dur long.
• Since an event may belong to more typologies, only the counter corresponding to the longest
duration is incremented (long > short).
Cumulative counters (Short sags, Long sags) and those of the last-day counters are available in the respective
menus.
Harmonic distortion
The Harmonic Distortion check regards line-to-line voltages and the phase currents, and is of two types:
• If the single harmonic components (different from the fundamental ones) have an amplitude greater than
the set value, an alarm is activated and displayed (Harmonic V Over Th / Harmonic I Over Th).
• If the total distortion is greater than the set value an alarm is activated and displayed (THD V Over Th /
THD I Over Th), and the THD meter is incremented by the total minutes during which the threshold was
exceeded.
NOTE: The counter stops at 65535 minutes.
The cumulative and last-day counters (THD Voltage and THD Current) are available in the corresponding
menus.
117 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 17 - Hi-Touch measurements
ABB | SACE Emax 2
18 - Test
Presentation All the trip units of the Ekip Touch range allow you to carry out various checks directly from the display:
• Autotest, for the check on the display and the LEDs.
• Trip Test, for the check on the circuit breaker opening command.
• Test CB, for the check on the controls of the circuit-breaker opening and closing coils
• Zone Selectivity, for the check on Zone Selectivity inputs and outputs.
In the presence of auxiliary power supply and contact type modules, the dedicated sections are enabled:
• Ekip Signalling 4K allows module contacts and leds to be checked.
• Ekip Signalling 2K-1, 2K-2, 2K-3 allows module contacts and leds to be checked.
• Ekip Signalling 10K-1, 10K-2, 10K-3 allows leds to be checked and contact closing commands to be sent.
In the presence of an Rc type trip unit and auxiliary power supply, the dedicated test section is enabled:
• Rc Test allows the connection and correct operation of the Rc toroid to be checked.
NOTE: access to the Test Menu requires the insertion of the password.
Using the Ekip T&P and Ekip Bluetooth test accessories it is also possible to check the operation of the
electronic protections from a PC, by simulating various installation conditions.
Autotest The automatic sequence of the display and the LED is activated by selecting the command Autotest.
The sequence includes the following test phases:
Phase Operation
1 Screen with message “www.abb.com”
2 Darkening of the display
3 Color sequence with red, green, blue bands, with gradual increase of backlighting
4 Warning and Alarm LEDs switched on for 1 second
Trip Test Selecting the command Trip test opens a dedicated page that requests confirmation for performing the test
by pressing the iTest key.
An opening command is transmitted to the trip coil when the key is released.
IMPORTANT: the opening command is performed with circuit-breaker closed and
absence of circulating currents.
NOTE: to reset the trip signal, go back to the HOME page and press the iTest key or transmit
a TRIP RESET command (via Ekip Connect or remotely).
Test CB Selecting the command Test CB opens a submenu containing the commands Open CB and Close CB.
The commands allow you to activate coil opening and closing respectively: the correct sending of the
command is confirmed by a window with the message “Test Executed”.
The correct operation of the entire command system (trip unit, Ekip Com Actuator and opening and closing
coils) is verified through the opening and/or the closing of the circuit-breaker.
118 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 18 - Test
Continued from the previous page ABB | SACE Emax 2
IMPORTANT:
• The coil opening and closing commands work only with the trip unit powered by
auxiliary power supply.
• Make sure that the coils are connected to the power supply source.
• The commands verify the operation of the trip unit: any possible faults on Ekip COM
Actuator or the coils are not found by the test.
Zone Selectivity The command Zone Selectivity allows you to select the line you want to check: S Protection or G
Protection.
The following are available for each command:
• Input, to check the state of the Zone Selectivity input.
• Force output, in order to force the state of the Zone Selectivity output to high.
• Force Output, to trip unit the override on the Zone Selectivity output.
IMPORTANT: the Zone Selectivity commands work with:
Ekip Signalling The submenus for testing the Ekip Signalling modules in the various versions 4K, 2K-1, 2K-2, 2K-3 allow you
to send the command Autotest.
The command activates an automatic sequence of test for the LEDs and contacts:
Phase Operation
1 Reset LEDs and output contacts
Switch-on in sequence of all LEDs and closing in sequence of all the associated output
2
contacts
3 Reset initial conditions
NOTE: with Ekip Signalling modules 2K-1, 2K-2, 2K-3, the sequence includes testing of the
LEDs of the inputs.
IMPORTANT: the autotest sequence involves the closing of the output contacts: the
check on the correct closing is the user's responsibility.
Rc Test Submenus for the test of the Rc toroid involve the command Autotest that allows you to send the command
to the toroid to check correct operation.
NOTE: the test is available only with the toroid correctly connected, the trip unit in Rc
configuration, auxiliary power supply present.
Protection test
To perform the protection command test, follow this procedure:
Phase Operation
1 Make sure that the circuit-breaker is closed and that there are no currents circulating
2 Connect Ekip T&P or Ekip Bluetooth
3 Start the communication with Ekip Connect
4 Open the Information page and select the Test command, which opens the protection test page
5 Set up the test as required and verify that the trip unit functions properly
119 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 18 - Test
ABB | SACE Emax 2
19 - Self-diagnosis
Self-diagnosis Ekip Touch continuously monitors its own operating state and that of all connected devices.
In the event of an error, the detected fault is reported:
Signal Description
With Vaux present and local Bus enabled: no module detected on terminal
box by trip unit (with alarm icon) or loss of communication for more than 5
Local Bus
seconds between trip unit and previously detected module (with prealarm
icon)
TC disconnected Trip coil not connected
L1 Sensor
L2 Sensor
Current sensor not connected
L3 Sensor
Ne Sensor
Gext Sensor Toroid S.G.R. not connected
Make sure that one of the following conditions is present:
• Rating plug not connected
• Invalid value
Rating Plug
• Rating Plug Rc inserted but Ekip Measuring not present
• Upon replacing the rating plug I4 becomes > 1200 A (in the case of UL
circuit-breaker)
Internal Error Internal error
Invalid Date Date not set
CB status CB state incorrect (esample: current present but CB in open state)
Rating Plug Installation Rating Plug not installed
Battery low Battery low or absent
Measuring Installation Ekip Measuring module not installed
Measuring Error Ekip Measuring module in error
The Mainboard and Ekip Touch software versions are not compatible with
each other: editing of all parameters is inhibited by the display.
Software Not
The protections L, I and Iinst are active and working with the parameters set in
Compatible
the previous protection trip unit.
To restore compatibility please contact ABB.
Make sure that one of the following conditions is present:
• I4 < 0.3 In (con In = 100 A), 0.25 In (con In = 400 A) or 0.2 In (for all other
sizes), in the absence of auxiliary power supply
Configuration • Iu < (2 * In * I1) if InN = 200 %
• t2 or t4 or t5 or t41 > 0.4 s (in case of UL circuit-breaker)
• I4 > 1200 A (in case of UL circuit-breaker)
• Protection curve L different from t=k/i 2 (in case of UL circuit-breaker)
Ekip Link Bus Loss of connection with one or more actors
PC Power exceed The average power limit setting of the Power Controller has been exceeded
IEEE1588 synch Synchronization problem of IEEE 1588 synchronization reference module
Maintenance Maintenane alarm
Zone Selectivity Diag Error in zone selectivity connections (Hardware Selectivity)
CB undefined CB state contacts error
SNTP error Synchronization problem of SNTP synchronization reference module
120 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 19 - Self-diagnosis
Continued from the previous page ABB | SACE Emax 2
Signal Description
Ethernet disconnected no external cable on one or more modules without Ethernet connection
Problem of Ekip Com Hub module with: certificates, connected devices,
Ekip Com Hub missing Com modules (RTU or with Ethernet connection), API TLS device,
Hub events, parsar configuration
TFTP server enabled / configuration session open in one or more modules
Configuration Session
between: Ekip Com IEC 61850 or Ekip Hub
Alarm for connection of one or more analog inputs to the Ekip Signalling
Ekip Signalling 3T
3T module
Ekip Installattion Installation error between HMI and mainboard. Contact ABB
MAC Address Module detected with incorrect / not allowed MAC address
Numeric alarm (e.g. 30002) Internal error. Contact ABB
NOTE: for resolution of the signals see section Fault resolution on page 312.
Protections and Measurements In the event of protection or measurement alarms, the associated signals are reported:
121 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 19 - Self-diagnosis
ABB | SACE Emax 2
Programming errors If during the programming of the parameters an attempt is made to violate certain limitations, the trip unit
blocks the saving procedure and signals the error:
Type of error Error description
L Th ≥ S Th Errors in the adjustment of the protection thresholds
S Th ≥ I Th Errors in the adjustment of the protection thresholds
L Th ≥ S2 Th Errors in the adjustment of the protection thresholds
S2 Th ≥ I Th Errors in the adjustment of the protection thresholds
L Th ≥ D Th Errors in the adjustment of the protection thresholds
D Th ≥ I Th Errors in the adjustment of the protection thresholds
Activation of Zone Selectivity with protections S, S2,
D Zone Sel = On while S / S2/ G / Rc = On
G or Rc enabled
S(V) t20 and S(V) I20 error Incorrect configuration of S(V) protection
RQ Q24 > Q25 Incorrect configuration of RQ protection
Error in the parameters of the Ekip Synchrocheck
SYNCHRO parameters error
module
ROCOF t28 error Incorrect configuration of ROCOF protection
And the MCR enabled together Simultaneous enabling of the protections I and MCR
Protection and delay alarms present during
High priority alarm
programming
Attempt to activate the Rc toroid without Ekip
Rc toroid error
Measuring or Rating Plug of the Rc type
It tries to set the internal neutral setting with a value
Internal neutral config error
that is not allowed
Change of datalogger number with datalogger not Change datalogger parameters with datalogger
stopped active
Change of the parameter "pole order" with a half
Error Reverse pole order
size circuit-breaker.
Programming Session Timeout Timeout for saving data
122 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 19 - Self-diagnosis
ABB | SACE Emax 2
20 - Operating features
Electrical characteristics
Operating currents and voltages
The correct operation of Ekip Touch trip unit is guaranteed with primary currents with clearly defined
characteristics.
In addition, Ekip Touch trip unit can be powered directly by the internal current sensors or, in the presence of
the Ekip Measuring Pro module, by the installation voltage.
The following are the specifications:
Parameter Operating limits
> 80 A (E1.2-E2.2-E4.2)
Minimum three-phase turn-on current
> 160 A (E6.2)
Rated frequency 50 / 60 Hz ± 10 %
Peak factor Complying with standard IEC 60947-2
Minimum three-phase turn-on voltage > 80 V
123 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 20 - Operating features
ABB | SACE Emax 2
Functional characteristics The Ekip Touch trip unit, in addition to the protection and measurement menus, also allows various operating
and configuration parameters to be set on the screen:
• Line frequency, to set the installation frequency.
• Remote / Local Mode, to set the operating mode and enable editing of parameters and sending remote
commands.
• Local Bus, to enable communication with the terminal modules and communication on the Local Bus.
• Harmonics, to enable the calculation of current and voltage harmonics.
• Power controller, to enable the function Ekip Power Controller.
• Programmable functions, to combine the modification of parameters and configurations to the
programmable inputs of Ekip Signalling modules.
• System, to modify system data such as date, time, language and password.
• Maintenance, to optimize maintenance operations on the circuit-breaker.
Line frequency The adjustment of the frequency setting is used to set the installation frequency.
In the menu Settings - Main frequency two configurations are available: 50 and 60 Hz.
NOTE: the measurements of voltages and currents are performed according to the grid
frequency set. A wrong setting could cause protection and measurement anomalies.
Local/Remote In the menu Settings - Modules - Local/Remote you can enable the modification of the parameters and
sending of certain commands remotely, via Ekip Com communication modules.
Enabling Remote Configuration inhibits changing of parameters from display, with the exception of the
parameter Local / Remote.
NOTE: in Remote configuration the inhibition of changes is active if:
Local Bus In the menu Settings - Modules - Local Bus you can enable the Local Bus line to allow communication with
all modules mounted on the terminal block or switchgear.
NOTE: the Local Bus alarm is signalled if the trip unit is powered by Ekip Supply, but no
module is connected and the Local Bus parameter is enabled.
Harmonics Hi-Touch and G Hi-Touch trip unit versions, in the menu Measurements - Harmonic allow you to enable the
check on the current and voltage harmonics.
The harmonics are essential for:
• Network Analyzer function.
• Waveform measurement.
Power Controller The description of Ekip Power Controller function is available beginning from page 131.
124 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 21 - Additional Ekip Touch functions
ABB | SACE Emax 2
Programmable functions It is possible to program eight commands, with automatic activation based on signals or events.
The commands are:
Command type Path
Trip Advanced - Functions
Change protection set (from Set A to Set B) Advanced - Functions
Change configuration (from Remote to Local) Settings - Modules - Functions
Reset the contacts of the signalling modules Settings - Modules - Functions
Opening coil command (YO). Settings - Functions
Closing coil command (YC). Settings - Functions
Reset energy counters Measurements - Energies - Function
Reset of the trip signal Advanced - Functions
NOTE: the YO and YC commands are possible only if the coils are present and if all the
operating conditions exist (circuit-breaker open).
System In the menu Settings - System some system parameters are available:
Date, to set the current date.
Time, to set the current time
Language, to set the language of the menus.
Password, in order to reconfigure the password.
NOTE: the date and time are maintained thanks to an internal battery in the trip unit. In the
event of date and time fault, you are advised to follow the procedure for replacement of the
battery.
Maintenance The Maintenance function allows the user to be alerted by a Warning alarm that:
• One year has passed since the last maintenance.
• Contact wear has increased by more than 10% compared with the value at the last maintenance.
There are two areas available on the display:
• Activation area (Main page - Menus - Settings - Maintenance): it allows the maintenance function to be
activated.
• Measurements and reset area (Main page - Menus - Measurements - Maintenance): it appears only if the
maintenance function is activated; it provides information related to maintenance (contact wear and dates)
and the command for confirming that maintenance has been carried out (by confirming, the current date
and contact wear values are recorded, and the alarm signal is reset).
The reference date is that of the internal clock, and the elapsed time is calculated both with the trip unit on
and off (provided that the internal battery is working).
NOTE: manual modification of the date can cause variations in the calculation of the time
elapsed, and therefore in the date of the next maintenance.
NOTE: the maintenance signal due to increased contact wear is active for values higher than
20 %.
125 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 21 - Additional Ekip Touch functions
ABB | SACE Emax 2
Additional options via remote / Ekip T&P, Ekip Programming and Ekip Bluetooth allow the protection trip unit to be connected to Ekip
front control Connect software and to access parameters and commands that cannot be accessed directly from the front
interface.
Parameters, measurements and commands are also available when communication is activated via Ekip Com
modules.
Programmable States There are sixteen independent programmable states identified by the letters A, B, C, D, E, F, G, H, I, L, M, N,
O, P, Q, R, offering different solutions for event control.
The value of each programmable state can be either "True" or "False". Different configuration parameters are
available:
• Trigger: event or combination of more events of state activation (up to 24, in AND or OR logic configuration).
• On Delay: state activation delay calculated from trigger presence onwards.
• Off Delay: state de-activation delay calculated from trigger absence onwards.
NOTE: the state become activate if the trigger is present for longer than the On delay setting
and become inactive if the trigger is absent for longer than the Off delay setting.
State
Trigger
Delay ON
Delay OFF
Delay ON Delay OFF
State
Programmable
TRUE
FALSE
The states can be used with the external Ekip Signalling 10K module, on Link Bus or with the programmable
functions, to transfer the desired signalling combination on contacts.
Circuit-breaker label and user Labels that can be configured by the user so as to facilitate remote identification of the trip unit; in detail the
Data CB label, the trip unit model and the communication address form the identifier used by Ekip Connect for
the devices connected.
Info Page Additional information page that can be activated and customized by the user. If activated, it can be accessed
on the display by pressing the iTest button twice from the main page.
NOTE: the pages can be configured with all the trip units for SACE Emax 2 circuit-breakers,
but they can only be displayed via Ekip Touch.
126 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 21 - Additional Ekip Touch functions
ABB | SACE Emax 2
Load Profile Timers SACE Emax 2 has 4 counters which display how long the maximum current measured has remained in each
percentage band.
The counters are expressed in seconds and the bands are: 0-49%In, 50-79%In, 80-89%In, >90%In.
Energy Store Time The counter indicates the time that has elapsed since the last energy metering reset.
It is active and updated in the presence of at least one of the following: auxiliary supply, supply by Ekip T&P
or supply by Ekip Measuring.
Led Alive The parameter allows the behaviour of the power-on LED indicator of the trip unit and of all modules that can
be connected to Ekip Supply to be changed. If activated:
• Trip unit: it comes on at a frequency of 0.5 Hz.
• Modules connected to Ekip Supply: if there are no communication errors, they synchronize with the flashes
of the trip unit LED.
If deactivated, the power-on leds on the respective devices come on with a steady light.
Open/Close Remote Direct The parameter controls two different command packages for remote circuit-breaker opening and closing:
Command • Enabled: commands 7 and 8 are valid (direct commands for CB Open and CB Close).
• Disabled: commands 7 and 8 are not valid.
IMPORTANT: in this case, remote circuit-breaker opening and closing can still be
obtained using the programmable YC COMMAND and YO COMMAND functions and
the Request circuit-breaker opening (28) and Request circuit-breaker closing (29)
commands.
Modules network settings It allows the communication parameters of the circuit-breaker to be controlled if the trip unit is replaced:
retention • Overwrite: the parameters of the new trip unit are valid, so it is advisable to make sure that the communication
parameter settings suit the communication network.
• Keep module data: the new trip unit updates its communication parameters with the ones in the Ekip
Com modules of the circuit-breaker, used up to that moment in the various communication networks.
The trip units are supplied with the parameter set as Overwrite.
Change Double Set of If activated, it allows the modification of the parameter set even when delay alarms are in progress. Disabled
parameters always by default.
Repeat zone selectivity S/G HW If Enabled, the propagation logic of HW signals for zone selectivity applies in accordance with the table
in the Technical Application Paper QT1. 1SDC007100G0205; if Disabled the HW selectivity signal is not
propagated by the protection trip unit.
Zone selectivity input functions The zone selectivity inputs and some outputs can be configured in this section:
• Standard: input or output operation as per standard zone selectivity logic (see 1SDC007100G0205 or
1SDC007401G0201); all selectivity functions have the Standard setting.
• Customized: the event that activates the zone selectivity input or output can be selected.
IMPORTANT: in the Customized configuration, the only zone selectivity activation
event is the one set and therefore standard selectivity operation is not active
(modification should only be performed by expert technical personnel).
127 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 21 - Additional Ekip Touch functions
ABB | SACE Emax 2
Wink The command allows the power-on LED on the protection trip unit to flash at 3 Hz so as to physically identify
a trip unit that would not be identifiable in other ways.
3 Hz flashing is disabled by sending another Wink command or by switching off the trip unit.
Glitch The commands of Glitch 16 to 23 activate the respective glitch registers, which can be used for customizing
programmable functions or output contacts.
Wizard Reset Reset Wizard: the Wizard window appears the first time the trip unit comes on and can be used to enter
some of the trip unit and circuit-breaker parameters.
128 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 21 - Additional Ekip Touch functions
ABB | SACE Emax 2
22 - Default parameters
Ekip Touch default parameters The Ekip Touch trip units are supplied with the following default parameters:
(1)
Thermal memory, startup, Zone Selectivity set to Off.
(2)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.
(3)
Protections available if the respective toroids (S.G.R. or Rc) are present.
(4)
Protection activated on request when purchasing the trip unit.
The protections activated by the presence of the Ekip Measuring Pro module, have the following default
parameters:
Protection/Parameter Value
VU Off; 50%; 5 s
UV Off; 0.9 Un; 5 s
OV Off; 1.05 Un; 5 s
UF Off; 0.9 fn; 3 s
OF Off; 1.1 fn; 3 s
RP Off; 0.1 Sn; 10 s
Phase Sequence 1-2-3
Cos φ Off; 0.95
129 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 22 - Default parameters
Continued from the previous page ABB | SACE Emax 2
The Ekip Hi-Touch and Ekip G Hi-Touch trip units have additional protections, provided with the following
default parameters:
Protection/Parameter Value (1)
S2 Off; 2 In; 50 ms; Curve: t = k
D Off; 2 In; 200 ms
UV2 Off; 0.9 Un; 5 s
OV2 Off; 1.05 Un; 5 s
UF2 Off; 0.9 fn; 3 s
OF2 Off; 1.1 fn; 3 s
Network Analyzer Off
Harmonic calculation Off
Set A-B Off
The Ekip G Touch and Ekip G Hi-Touch trip units have additional protections, provided with the following
default parameters:
Protection/Parameter Value (1)
S(V) Off; type = step; 1 In; UI = 1 Un; Ks = 0.6; t20 = 1 s
RV Off; 0.15 Un; 15 s
RQ Off; Kq = -2; Q24 = 0.1 An
OQ Off; 1 Sn; 1 s
OP Off; 1 Sn; 1 s
UP Off; 1 Sn; 1 s
The Ekip G Hi-Touch trip units has additional protections, provided with the following default parameters:
Protection/Parameter Value
ROCOF Off; 0.6 Hz; 500 ms
S2(V) Off; type = step; 1 In; UI2 = 1 Un; Ks2 = 0.6; t21 = 1 s
RQ2 Off; Kq = -2; Kq2 = 2; Q24 = 0.1 Sn; Q25 = 0.11 Sn; Vmin = 0.5 Un; 100 s
130 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 22 - Default parameters
ABB | SACE Emax 2
Presentation The Ekip Power Controller function allows you to manage the load of an installation according to the power
input, in order to contain consumption and to optimize energy efficiency.
The various parameters related to this function can be configured using a dedicated tool in the Ekip Connect
software.
For further information see the chapter "2 - Load control" on page 159.
trip units The function Power Controller can be activated for all the trip units of the Ekip TOUCH range, and allows you
to do the following via display:
• Modify some parameters of the function.
• Display some measurements of the function.
• View the state of the loads.
NOTE: the Power Controller function is available if requested when ordering the CB or the
protection trip unit.
Parameters on the display The parameters available following the path Main page - Menu page - Settings - Power Controller are:
Parameter Description
Enable It allows you to enable/disable the Power Controller function.
Load Operating It allows you to set the configuration of each of the 15 programmable loads
Mode Automatic or Manual configurations available.
Power limits It allows you to set the four power limits (from 0 to 10000 kW, step 10kW).
NOTE: for the characterization of all the parameters of the function you are advised to configure
the parameters via Ekip Connect first, and only subsequently to operate on the trip unit in
order to enable or to modify loads and power limits.
Measurements on the display The measurements are available by following the path Main page - Measurements page - Power Controller
page, they are:
Measurement Description
Ea Expected energy
DT Time elapsed inside of the evaluation range
LOADS Number of loads monitored
LOADS Shed Number of shed loads
Sp Shed priority set
T Evaluation window
Information displayed Information about the state of the loads is available by following the path Main page - Menu page - Information
- Power Controller.
131 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Ekip Touch protection trip unit | 23 - Ekip Power Controller
ABB | SACE Emax 2
Protection curves
1 - Introduction
This chapter illustrates the trip curves of the available protections with all the protection trip units for SACE
Emax 2 circuit-breakers, represented in various dot diagrams.
Some notes for reading the diagrams:
• The curves are illustrated considering the minimum and maximum values and of the parameters of each
protection.
• Protections that have multiple functions (for example: G protection), are represented with multiple diagrams.
• The curves do not take account of the effects of special parameters such as thermal memory, startup or
presence of the Rating Plug L=OFF.
• Where not present, the curves are valid for both the IEC version and the UL version.
NOTE: for calculation of the tripping time, it is recommended to always use the mathematical
function provided in the protection summary table.
2 - DIP protections
The following are the trip curves of the protections available with Ekip Dip trip units.
1000
3 .. 144
100
10
1,5..15
0,1
0,01
0,1 1 10 x In
133 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 2 - DIP protections
ABB | SACE Emax 2
1000
3 ..144
100
0,6..10
10
0,1..0,8
1,5..15
0,1
0,01
0,1 1 10 x In
Version UL
t [s] L
0,4..1
1000
3 ..144
100
0,6..10
10
0,1..0,4
1,5..15
0,1
0,01
0,1 1 10 x In
134 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 2 - DIP protections
ABB | SACE Emax 2
1000
3 .. 144
100
0,6..10
10
1,5..15
0,1..0,8
S
0,1
0,01
0,1 1 10 x In
Version UL
t [s] L 0,4..1
1000
3 .. 144
100
0,6..10
10
1,5..15
0,1..0,4
S
0,1
0,01
0,1 1 10 x In
135 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 2 - DIP protections
ABB | SACE Emax 2
t [ s] 10
0.1...1
0.1...1
0,1
0,01
0,01 0,1 1 10
x In
Version UL
t [ s] 10
0.1...1
0.1...0.4
0,1
0,01
0,01 0,1 1 10
x In
136 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 2 - DIP protections
ABB | SACE Emax 2
t [s] 10
G
0.1...1
0.1...1
0,1
0,01
0,01 0,1 1 10
x In
Version UL
t [s] 10
G
0.1...1
0.1...0.4
0,1
0,01
0,01 0,1 1 10
x In
137 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 2 - DIP protections
ABB | SACE Emax 2
3 - Touch protections
The following are the trip curves of the protections available with Ekip Touch trip units.
NOTE: protections I, MCR and 2I share the same curve. For graphical convenience only
protection I is included.
1000
3 .. 144
100
10
1,5..15
0,1
0,01
0,1 1 10 x In
138 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 3 - Touch protections
ABB | SACE Emax 2
1000
3 ..144
100
0,6..10
10
0,1
0,01
0,1 1 10 x In
Version UL
t [s] L
0,4..1
1000
3 ..144
100
0,6..10
10
0,05..0,4
1,5..15
0,1
0,01
0,1 1 10 x In
139 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 3 - Touch protections
ABB | SACE Emax 2
1000
3 .. 144
100
0,6..10
10
0,05..0,8
1,5..15
0,1
S
0,01
0,1 1 10 x In
Version UL
t [s] L 0,4..1
1000
3 .. 144
100
0,6..10
10
1,5..15
0,05..0,4
0,1
S
0,01
0,1 1 10 x In
140 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 3 - Touch protections
ABB | SACE Emax 2
t [s] 10000
0,4..1
1000
100
3 .. 144
10
0,1
0,1 1 10
x In
Version VI
t [s] 10000
0,4..1
1000
100
3 .. 144
10
0,1
0,1 1 10
x In
141 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 3 - Touch protections
Continued from the previous page ABB | SACE Emax 2
Version EI
t [s]
10000
0,4..1
1000
100
3 .. 144
10
0,1
0,1 1 10
x In
Version I4
t [s] 100000
0,4..1
10000
1000
3 .. 144
100
10
0,1
0,1 1 10
x In
142 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 3 - Touch protections
ABB | SACE Emax 2
t [ s] 10
0.1...1
0.1...1
0,1
0,01
0,01 0,1 1 10
x In
Version UL
t [s] 10
0.1...1
0.1...0.4
0,1
0,01
0,01 0,1 1 10
x In
143 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 3 - Touch protections
ABB | SACE Emax 2
t [s] 10
G
0.1...1
0.1...1
0,1
0,01
0,01 0,1 1 10
x In
Version UL
t [s] 10
G
0.1...1
0.1...0.4
0,1
0,01
0,01 0,1 1 10
x In
144 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 3 - Touch protections
ABB | SACE Emax 2
100
2%...90%
10 0.5...60
IU
0,1
1 10 100
%1In
145 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 3 - Touch protections
ABB | SACE Emax 2
UV
0.5...0.98
100
10
0.05...120
0,1
0,01
0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,1
x Un
OV
1.02..1.5
100
10
0.05...120
0,1
0,01
0,9 1 1,1 1,2 1,3 1,4 1,5 1,6 1,7
x Un
146 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 4 - Measuring Pro protections
ABB | SACE Emax 2
2%..90%
10
0.5...60
1
0,1
1 10 100
%Un
UF
0.9..0.999
100
10 0.15...300
0,1
0,01
0,8 0,85 0,9 0,95 1 1,05 1,1
Fn
147 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 4 - Measuring Pro protections
ABB | SACE Emax 2
OF
1.001..1.1
100
10
0.15...300
0,1
0,01
0,95 1 1,05 1,1 1,15 1,2
x fn
RP
-1 .. -0.05
100
10
0.5...100
0,1
-1,2 -1 -0,8 -0,6 -0,4 -0,2 0
x Sn
148 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 4 - Measuring Pro protections
ABB | SACE Emax 2
5 - Hi-Touch protections
The following are the trip curves of the protections available with Ekip Hi-Touch and Ekip G Hi-Touch trip
units.
NOTE: the protections S with S2, OV with OV2, UV with UV2, UF with UF2 and OF with OF2
share the same calculation algorithm. For graphical convenience only one curve is shown for
each protection (S, OV, UV, UF, OF in the previous chapters).
t [s] 10
0.6...10
D
0.1...0.8
0,1
0,01
0,1 1 10 100
x In
149 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 5 - Hi-Touch protections
ABB | SACE Emax 2
6 - G Touch protections
The following are the trip curves of the protections available with Ekip G-Touch and Ekip G Hi-Touch trip units.
0.6...10
10
0.05...30
0,1
0,01
0,1 1 10
In
RV
0.05..0.5
100
10
0.05...120
0,1
0,01
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7
x Un
150 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 6 - G Touch protections
ABB | SACE Emax 2
RQ
-1 .. -0.1
100
10
0.5...100
0,1
-1,2 -1 -0,8 -0,6 -0,4 -0,2 0
x Sn
t [s]
OQ
100 0.4...2
10
0.5...100
0,1
0,1 1 10
x Sn
151 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 6 - G Touch protections
ABB | SACE Emax 2
t [s]
OP
0.4...2
100
10
0.5...100
0,1
0,1 1 10
x Sn
t [s]
UP
0.1..1
100
10 0.5...100
0,1
0,01 0,1 1
x Sn
152 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 6 - G Touch protections
ABB | SACE Emax 2
7 - G Hi-Touch protections
The following are the trip curves of the protections available with Ekip G Hi-Touch trip units.
NOTE: the protections S(V) with S2(V), and RQ with RQ2, share the same calculation algorithm.
For graphical convenience only one curve is shown for each protection (S(V) and RQ in the
previous chapters).
ROCOF
0.4..10
10
0.5..10
0,1
0,1 1 10 100
Hz/s
153 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 7 - G Hi-Touch protections
ABB | SACE Emax 2
3...30
1
0,06...0,8
0,1
0,01
1 10 100
(A)
154 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Protection curves | 8 - External toroid protections
ABB | SACE Emax 2
System Interface
Documents For correct use of Ekip Com communication modules, two documents are available in the ABB library:
Document Description
Guidelines with details for putting communication modules into
1SDH001140R0001
service.
Table with the references of all the registers for the parameters,
1SDH001140R0001_CSI_Emax2
commands, measurements, etc.
The .zip file contains the files for integrating Emax 2 in the available communication networks. The specific
Ekip Com module contains an IMPORTANT file with notes on how to use the files.
NOTE: consult the ABB library for the most recent version of the .zip file.
155 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B System Interface | 8 - External toroid protections
ABB | SACE Emax 2
Specific applications
1 - Zone Selectivity
Description Zone Selectivity is an evolution of time selectivity (see chapter "2 - Selectivity between ABB SACE circuit-
breakers"), in which a dialog is created between the trip units through input and output blocking signals: an
active input blocking signal means that the circuit-breaker must remain closed.
Specifically, if a trip unit with the function enabled detects a fault current higher than the threshold set for a
particular protection, it activates the output blocking signal for the protection and, before opening, checks
the corresponding input blocking signal:
• If the input is not active, the trip unit opens with a delay equal to the selectivity time set for the protection
(which must be lower than the protection tripping time).
• If the input is active, it opens only if the fault persists and with a delay equal to the tripping time of the
protection.
Zone Selectivity can be enabled via cabling (Hardware Selectivity) with ABB SACE circuit-breakers, not
Emax 2, where available.
Besides Hardware Selectivity, SACE Emax 2 circuit-breakers allow Logic Selectivity to be configured using
the communication via Link Bus between releases equipped with Ekip Link module. For further details,
consult paragraph “Zone Selectivity with SACE Emax 2 circuit-breakers".
Zone Selectivity with ABB SACE With electronic trip units not for ABB SACE Emax 2:
circuit-breakers • Zone selectivity can be implemented only for protections S G and D (Directional).
• If the function is available, the circuit-breaker is equipped with two blocking outputs and two blocking
inputs that is, one output and one input for each S and G protection), or as an alternative two outputs
and two inputs for protection D (one output and one input per direction).
• Since only two blocking outputs and two blocking inputs are available, Zone Selectivity for protections S
and G and Directional Zone Selectivity are mutually excluding (to implement Directional Zone Selectivity,
the S and G protections must be disabled, and vice versa).
• To actuate Zone Selectivity, the releases must be equipped with auxiliary voltage to activate the outputs.
• Each S G and D protection has two selectivity parameters: the function enabling parameter and selectivity
time, meaning the opening time of the circuit-breaker if the selectivity input is not active.
• The blocking outputs and inputs are considered active if the level is high (equal to the auxiliary voltage).
• For protection D, the selectivity time to be set is the same for both directions.
To obtain Zone Selectivity, the protections must be set, and the blocking outputs and must be wired, so that
only those circuit-breakers capable of isolating the overload or fault without the rest of the installation being
de-energized open. Regarding this:
• For each type of selectivity, definitions, operating principles, application fields, advantages and disadvantages,
requirements, indications for setting the protections and examples are provided in the Technical Application
Paper QT1 1SDC007100G0205 "Low voltage selectivity with ABB circuit-breakers".
• For Directional Selectivity, application examples are available in the White Paper 1SDC007401G0201
“Directional protection and directional zone selectivity”.
156 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 1 - Zone Selectivity
ABB | SACE Emax 2
Zone Selectivity with SACE With SACE Emax 2 circuit-breakers, Zone Selectivity can be implemented:
Emax 2 circuit-breakers • If the circuit-breakers are equipped with Ekip LCD or Touch trip units (including Hi-, G, and G Hi- trip units).
• For protections S, G, D, S2, Gext (availability depends on the trip unit model).
Hardware Selectivity operation is the same as that described in the previous section for SACE circuit-breakers
other than Emax2, except for the addition of S2 and Gext in the list of protections supported.
NOTE: S2 and Gext share the same selectivity inputs/outputs of S and G, respectively. If
several protections are active with the same channels (e.g.: S and S2) the trip unit controls
the inputs and outputs with OR logic: configure the parameters with care to avoid undesired
signals or actions.
Logic Selectivity, which is available in the presence of Ekip Link modules, has different advantages:
• Each protection is independent. There are no cases of shared or exclusive channels/bits (example: selectivity
D can be actuated without disabling protections S and G).
• Each device connected to Link Bus can be customized with many propagation parameters, mask, diagnosis.
Use of both types of selectivity or just logic selectivity can be selected on trip unit for each protection.
NOTE: for details on how to associate trip units connected to the same Link Bus, see the
chapter "14 - Ekip Link module”.
NOTE: the S/D-Forward (G/D-Backward) hardware output is activated only if the protections
S or D-Forward (G or D-Backward) are in alarm, and the S/D-Forward (G/D-Backward)
hardware input acts as a block only for the protections S and D-Forward (G and D-Backward),
regardless of whether hardware-only or mixed selectivity is selected.
157 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 1 - Zone Selectivity
Continued from the previous page ABB | SACE Emax 2
• Remote Programmable States A and B are also included in the selectivity masks: these 2 parameters,
which are available in the Ekip Link configuration page, enable the event (or combination of several
events) and reference actor that activate the selectivity input of the trip unit to be selected. 2 further states
are available, C and D, but they cannot be configured for Zone Selectivity. All 4 programmable states are
used for the Programmable Logic function described in chapter "14 - Ekip Link module".
NOTE: The Programmable Logic function is different from that of Zone Selectivity.
Then:
• A check is performed on the hardware inputs at regular intervals.
• If, on the trip unit, the input of an actor is configured for diagnosis (e.g. input S of actor 3) and this input
is not active when the test is performed, the actor stimulates its output (e.g. actor 3 activates output S)
for a short time: the trip unit considers the test result to be positive if it receives the signal correctly at its
input, otherwise it will signal error.
• the diagnosis check will not be performed if the hw input is active.
• if the input configured for diagnosis is active when the test is performed, diagnosis check will not be
performed and the Detection state in the Ekip Link state page will indicate: Unknown.
• A line inconsistency (independently of diagnostics) is indicative of a possible configuration error (for example:
a hardware input of the trip unit is connected to the hardware output of a trip unit not associated via Link
Bus, or to an actor for which the function has not been enabled).
• Therefore, to avoid a line inconsistency being reported, the trip units whose hardware outputs are connected
to the hardware inputs of the trip unit must also be connected to the Link Bus and associated to the trip
unit (see the chapter "14 - Ekip Link module") while it is not necessary (it is not necessary for the value
“True” to be assigned to the Selectivity Actor parameter).
158 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 1 - Zone Selectivity
ABB | SACE Emax 2
2 - Load control
General description Load control is possible through the Ekip Power Controller, which is a new patented ABB function, available
only on SACE Emax 2 circuit-breakers equipped with any Ekip LCD or Touch (including Hi-, G, and G Hi- trip
units).
The purpose of the function is to to prevent a defined limit of power absorption from being exceeded in the
installation, through:
• The cumulative measurement of the energy consumed by the installation over time.
• An estimate of the energy consumed at the end of the monitoring periods in which the electrical energy
billing cycle is divided.
• Automatic load control, that is to say the temporary disconnection of lower priority loads if the estimate of
the energy exceeds the product of the power limit set and the duration of the monitoring periods.
• Recognition of the instant the monitoring periods start with reset and restart of energy meters at the beginning
of each period on the basis of the internal clock of the release or of an external synchronization signal.
NOTE: if the trip unit where the function resides is equipped with an Ekip Link module and
the clock and synchronization signals in accordance with the IEEE 1588 protocol are available
on the Link Bus, synchronization can be performed by the trip unit on the basis of this signal.
For details, see the chapter “14 - Ekip Link module".
Ekip Power Controller enables you to:
• do not exceed the contracted power limits established with the users and increase the contracted power
and fixed costs without incurring penalties in the case of peaks in energy consumption.
• oversize the installation to prevent overload protections from tripping.
• ensure smart real time management of the loads on the basis of real plant consumption needs at any instant.
NOTE: load control based on measuring the energy rather than the instantaneous power
allows power peaks above the contractual limit to be tolerated if the duration of the peaks is
such that the average power during the monitoring period does not exceed the contractual
limit. This is useful, because billing and any penalties from the public utility company are
calculated on the basis of the average power measured in predefined time intervals, specifically
on the basis of the average highest power reached during the billing period.
Further information on the potential of the function is available in the White Paper 1SDC007410G0202 “Load
management with Ekip Power Controller for SACE Emax 2”.
Operating details To enable the function, this just needs to be available on an Ekip LCD or Ekip Touch trip unit equipped with an
auxiliary power supply, and with the possibility to measure the total energy consumed (for example: installed
on the main circuit-breaker of the system). Therefore, the energy can be measured if the trip unit is equipped
with an Ekip Measuring module (see the chapter “2 - Ekip Measuring modules”).
NOTE: Ekip Measuring module is supplied as standard with Ekip Hi-, G, G Hi-Touch and Ekip
Hi-, G, G Hi-LCD trip units, whereas it has to be ordered in case an Ekip LCD or Touch are
used.
The circuit-breaker performing the function is indicated as the master, while the devices located upstream
the power supply circuits and controlled by the master are indicated as slaves.
The slaves can be real loads, or they can be generators. The generators are controlled in the opposite way
to loads, that is, they are connected in the event of high consumption (to activate additional energy sources)
and disconnected in the event of reduced consumption.
159 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 2 - Load control
Continued from the previous page ABB | SACE Emax 2
Within the monitoring period, the estimate of the energy consumed at the end of the period is performed by
the master at regular intervals. Then, after every interval:
• If the estimate is in the high consumption range, a load is disconnected (or a generator is connected)
• If the estimate is in the low consumption range, a load is connected (or a generator is disconnected)
• If the estimate is in the acceptable consumption range, no loads or generators are disconnected or connected.
Load monitoring is still performed by the master, in accordance with these rules:
• The maximum number of loads that can be controlled is 15 (including the generators).
• The order in which the loads are disconnected and connected depends on the priority level assigned: the
lower the priority level, the less important the load. Therefore a load with lower priority will be disconnected
before and connected after the one with higher priority.
• It is possible to assign the same priority level to different loads.
• If the same level of priority is assigned to more loads, the master will disconnect (connect) the load that
has been connected (disconnected) for the longest time.
• To avoid damage or due to operating requirements, it is possible that once a load has been disconnected
(connected) it can only be reconnected (disconnected) only after a certain minimum time (the minimum
times for which a load must remain disconnected and connected can be different). Furthermore, a load
cannot remain disconnected beyond a certain maximum time. This information can be inserted in the
master (separately for each load), and the master will disconnect (connect) each load only after its minimum
time has elapsed, and will reconnect before its maximum time has elapsed, regardless of its priority level.
• If a load to be disconnected is already disconnected (for example: due to tripping of a protection of a
supply-side trip unit, or manual opening), the load is classified as not available and is excluded by the
function until it becomes available again.
NOTE: in the text that follows, the term “load” is used for both real loads and generators.
NOTE:
• Communication via Link Bus is possible only with Ekip Dip, LCD, and Touch trip units equipped
with an Ekip Link module. Then the circuit-breakers equipped with Ekip Dip trip units can only
act as slaves, while the circuit-breakers equipped with LCD or Touch trip units can act both as
masters and as slaves.
• For details on how to associate trip units connected to the same Link Bus with each other,
see the chapter “14 - Ekip Link module". For details on how to associate a trip unit and a 10K
module connected to the same Link Bus, see the manual 1SDH001318R0002 of the 10K
modules.
160 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 2 - Load control
Continued from the previous page ABB | SACE Emax 2
For these signals, the inputs and outputs of the signalling modules connected to the master can be used
(Ekip Signalling 4K mounted on the trip unit, or 2K or 10K modules connected to the trip unit via Local Bus,
see the chapters “4 - Ekip Signalling 4K module" and "5 - Ekip Signalling 2K modules“ and the manual
1SDH001318R0002 for 10K modules). Thus, if the slaves are circuit-breakers, the maximum number of loads
that can be controlled through wiring is:
• Two, if the master is an E1.2 and 2K modules are used (4k modules cannot be installed on E1.2 circuit
breakers, and a maximum of two 2k modules can be connected).
• Five, if the master is an E2.2, an E4.2 or an E6.2, and 4K and 2K modules are used.
• 15, if 10K modules are used.
More information on the connections, the equipment of the master and of every type of slave (for example:
air , molded-case, miniature circuit-breakers), and examples of applications are provided in the White Paper
1SDC007410G0202 “Load management with Ekip Power Controller for SACE Emax 2”.
NOTE: unlike the 10K modules connected to the trip unit via Local Bus (with which the
programming of inputs and outputs must be performed via Ekip Connect, by connecting to
the trip unit), the programming of the inputs and outputs of 10K modules configured to
communicate via Link Bus must be performed via Ekip Connect, connecting the module. For
details, see the manual 1SDH001318R0002 of the 10K modules.
Load control via Link Bus is useful if the loads are located in different switchboards and the connection
distances are long. And it is possible by setting up one or more Ethernet switches, with an adequate number
of outputs for the connection of all the trip units equipped with Ekip Link modules and Ekip Signalling 10K
modules configured to communicate via the Link Bus of the installation.
More information on the connections, the equipment of the master and of every type of slave (for example:
air , molded-case, miniature circuit-breakers), and examples of applications are provided in the White Paper
1SDC007410G0202 “Load management with Ekip Power Controller for SACE Emax 2”.
161 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 2 - Load control
ABB | SACE Emax 2
NOTE: the parameters for setting the function are available only if the trip unit is equipped
with an Ekip Measuring module. In this case, the Advanced Power Controller menu on Ekip
Connect is activated, under which the following pages can be selected.
The function must be enabled in the Basic settings and information page of the master.
The following items must be entered in the Advanced settings and information page of the master:
• If, on start up, the loads must be considered available, they can be both closed and open, or must be
closed, or if they must in any case be considered unavailable until the manual alarm deletion command
has been selected in the Basic settings and information page.
• During the monitoring period (5 minutes by default. Can be set in the Unit configuration page of the
general configuration of the release and installation), after how much time the function must be executed
(energy at end of period must be estimated and loads must be controlled).
• In relation to this time, the percentage of delay with which loads can be disconnected and connected.
• In the presence of an external time synchronization signal, the master signalling input to which it is
connected (input of the Ekip Signalling 4K module installed on the trip unit, or the 2K or 10K modules
connected to the trip unit via Local Bus). For more information on synchronization, see the White Paper
1SDC007410G0202 "Load management with Ekip Power Controller for SACE Emax 2".
• Up to ten power limits, of which at least the first one must be set.
• For each day of the week, up to a maximum of four time bands (which must cover a total twenty four
hours), and for each time band one of the above-mentioned ten power limits.
The load parameters are set in the Load parameters pages of the master (separately for each load):
• If the load has to be disconnected and connected manually, or automatically by the master.
• The priority level, from 1 to 15 (the higher the level, for example 15, the more important the load. The lower
the level, for example 1, the less important the load).
• The load type, in other words whether it is a real load or a generator.
• The number (from 0 to 2) and type of information on the state of the slaves on the supply side of the load
(open/closed, not available, in tripped position).
• The type of inputs, in other words, how the above state information is supplied (through physical connection
of inputs, or via Link Bus using one of the 15 Ekip Link modules that can be associated with the master).
• In case of physical inputs, to which signalling inputs of the master the above state signals are connected.
• The minimum time for which the load must remain connected.
• The minimum time for which the load must remain disconnected.
• The maximum time for which the load can remain disconnected.
• The start time and end time of a possible time slot in the day during which the load cannot be disconnected.
NOTE: if the non-availability signal of a load is active, the load cannot be disconnected and
connected, and therefore it cannot be used for the function until it becomes available again.
162 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 2 - Load control
Continued from the previous page ABB | SACE Emax 2
NOTE: by default, all the actors are set as slaves, therefore the trip unit for which the Ekip
Link is being set is the master of the function (which is, however, not activate unless it is
enabled on the Advanced Information and Settings page).
Wizard
To facilitate the setting of the function, under the heading "Tools" in the menu, the Ekip Connect software
provides the Power Controller wizard, which guides the user step by step and automatically creates
configurations based on the choices made by the operator.
Access from the display For the parameters to be set and the information regarding the function available on the display, see the
chapter “23 - Ekip Power Controller".
163 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 2 - Load control
ABB | SACE Emax 2
3 - Generator protection
Description
Specific protections and functions have been integrated into SACE Emax 2 circuit-breakers equipped with
Ekip LCD or Touch trip units (with Ekip Measuring Pro module), or Ekip Hi- or G or G Hi- (LCD or Touch)
trip units to protect low voltage synchronous generators against typical fault conditions and to connect the
generators to the installation. This ensures solutions that are compact and simple to install, with no need to
turn to indirect solutions.
Available information
More information is available in the White Paper 1SDC007409G0202 “Generator protections: Ekip G trip unit
for SACE Emax 2”, which provides:
• A list of the available protections and functions giving both the ABB name and the ANSI codes (example:
protection RQ, with ANSI codes 40 and 32R).
• For each protection, the fault conditions to which it is applied (example: for protection RQ, the inversion
of the sign of the reactive power, positive if outgoing from the generator).
• A description of the malfunctions that can lead to the above fault conditions (example: for reactive power
reversal, the loss of excitation and the consequent loss of the electromotive force, with reactive power
absorption from the network by the generator).
• The types of generator or installation in which such mulfunctions are most likely to take place (for example:
reversal of reactive power, smooth rotor generators).
• The consequences to which they may lead if the trip unit does not trip (example: for reversal of reactive
power, a voltage drop, if the network is not able to supply the required reactive power with the consequent
loss of system stability, and in any case an increase in temperature on the generator windings).
• If the protection can be duplicated using the Hi- version of the trip unit, with the possibility of setting the
two protections independently, and therefore with the possibility of adding redundancy to increase reliability,
or to fine tune the adjustment of the protection.
• For each protection, the parameters to be set, the trip curves and the criteria for the setting of parameters.
• For each of the above parameters, the values that can be assigned.
• For each protection, an application example.
• The description of the synchronism function, which can be implemented with the Ekip Synchrocheck
module (see the chapter “3 - Ekip Synchrocheck module”), that permits the parallel connection of two
independent power supply systems.
For a summary of the fault conditions to which the protections are applied and of the parameters to be set,
see the chapters “9 - Touch protections” “10 - Measuring Pro protections” “12 - G Touch protections” and “
13 - G Hi-Touch protections”.
Compatibility
The protections may already be available in Ekip LCD and Ekip Touch trip units (with Ekip Measuring Pro
module, see the chapter “2 - Ekip Measuring modules”) or Ekip Hi- (LCD and Touch) trip units, or only Ekip
G or G Hi- trip units (LCD and Touch). To identify the trip units in which the protections are available, see the
chapter “1 - Presentation” and the paragraph “Families and functionality", and the chapter "6 - Menu” and
the paragraph “Advanced menus".
164 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Specific applications | 3 - Generator protection
ABB | SACE Emax 2
Mechanical characteristics
1 - E1.2 description
Description of circuit-breaker Emax E1.2 circuit-breakers consist of a structure containing the poles, the operating mechanism and the
auxiliary parts. Each pole, enclosed in a plastic box, consists of a breaking part and a current transformer.
The structure of the breaking part differs between selective or current-limiting circuit-breaker.
The circuit-breaker is available in two types:
• fixed version
• withdrawable
The circuit-breaker in fixed version (see Figure 30) has its own terminals for connection to the power circuit.
The withdrawable circuit breaker consists of a mobile part (see Figure 31 for IEC and Figure 32 for UL) and
of a fixed part (see Figure 33 for IEC and Figure 34 for UL) for connection through its own terminals to the
power circuit.
The coupling between the mobile part and the fixed part is via disconnection contacts mounted on the fixed
part.
Figure 30 Figure 31
Figure 32 Figure 33
Figure 34
165 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 1 - E1.2 description
ABB | SACE Emax 2
1 2 3
8 4
7
6 5
Figure 35
Pos. Description
1 Lever for manually charging the closing springs
2 SACE Ekip protection trip unit
3 Name of the circuit-breaker
4 CB open (O) / closed (I) indicator
5 Closing pushbutton
6 Opening pushbutton
7 Mechanical signalling of tripped TU
8 Springs charged-discharged signalling device
9 Electrical data plate
11
10 5
9
8
7
6 Uimp 12Kv 12
Figure 36
Pos. Description
1 Type of circuit-breaker
2 Utilization category
3 Device type: Circuit-breaker or switch-disconnector
4 Rated current
5 Rated operating frequency
6 Admissible rated short-time current
7 Rated duty short-circuit breaking capacity
8 Rated ultimate short-circuit breaking capacity
9 Rated service voltage
10 Standards
11 Circuit-breaker serial number
12 Impulse voltage
166 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 1 - E1.2 description
ABB | SACE Emax 2
Figure 37
Pos. Description
1 Type of circuit-breaker
2 Rated current
3 Rated operating frequency
4 Admissible rated short-time current
5 Rated short-circuit breaking capacity
6 Rated service voltage
7 Standards
8 Circuit-breaker serial number
167 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 1 - E1.2 description
ABB | SACE Emax 2
Manual operations for opening The following is the sequence of steps for closing and opening the circuit-breaker:
and closing the circuit-breaker 1. Check that the circuit-breaker is open (open / closed indicator "O - OPEN"), and check that the springs
are discharged (spring signalling device "white - DISCHARGED SPRING") as indicated in Figure 38.
2. Charging the springs - Pull the lever [A] downwards several times until the springs charged signalling
device [B] is “yellow - CHARGED SPRING” as indicated in Figure 39.
A B
Figure 38 Figure 39
3. Check that the circuit-breaker is open (open/closed signalling device “O - OPEN”), and check that the
springs are charged (springs signalling device “yellow - CHARGED SPRING”) as indicated in Figure 40.
4. Closing - Press the closing pushbutton “I - Push ON” as indicated in Figure 41.
Figure 40 Figure 41
5. Check that the circuit-breaker is closed (open/closed indicator "I - CLOSED"), and check that the
springs are discharged (spring signalling device "white - DISCHARGED SPRING" as indicated in
Figure 42.
6. Opening - Press the opening pushbutton “O - Push OFF” as indicated in Figure 43.
Figure 42 Figure 43
168 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 1 - E1.2 description
Continued from the previous page ABB | SACE Emax 2
7. Check that the circuit-breaker is open (open / closed indicator "O - OPEN"), and check that the springs
are discharged (spring signalling device "white - DISCHARGED SPRING") as indicated in Figure 44.
Figure 44
Mechanical status indicators The following are the possible states in which you can find the circuit-breaker:
1. Circuit-breaker open with springs discharged (see Figure 45).
2. Circuit-breaker open with springs charged (see Figure 46).
3. Circuit-breaker closed with springs discharged (see Figure 47).
4. Circuit-breaker closed with springs charged (see Figure 48). This state occurs when after closing (see
step 4 - Figure 48) the springs are recharged manually or automatically by the gearmotor (if provided).
Figure 48
169 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 1 - E1.2 description
ABB | SACE Emax 2
Circuit breaker racking-in/ The following is the procedure for the insertion of the moving part in the fixed part:
racking-out operations
WARNING!
“CLICK”
Figure 49
2. Make sure that signalling device on the fixed part indicates the DISCONNECT position. See Figure
50.
Figure 50
3. Position the moving part in the fixed part and push until it comes to a stop. See Figure 51 and Figure
52.
Figure 51 Figure 52
170 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 1 - E1.2 description
Continued from the previous page ABB | SACE Emax 2
4. Extract the disconnection crank from its housing See Figure 53.
5. Press the lock pushbutton and insert the crank in the moving part. In this phase the moving part is still
in DISCONNECT position. See Figure 54.
Figure 53 Figure 54
6. Turn the crank clockwise until the pushbutton comes out and the indicator shows that the circuit-
breaker is in TEST position. See Figure 55.
Figure 55
7. Press the lock button and then rotate the crank clockwise until the button comes out and the indicator
shows that the circuit-breaker is in the CONNECT position. See Figure 56.
Figure 56
171 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 1 - E1.2 description
Continued from the previous page ABB | SACE Emax 2
Figure 57 Figure 58
To extract the moving part from the fixed part, perform the same steps indicated for insertion in reverse order.
After extraction, in order to remove the moving part, unlock the safety lock. See Figure 59.
2
Figure 59
Mechanical position indicators The following are the possible positions where you can find the mobile part of a withdrawable circuit-breaker
during its use:
• circuit breaker in DISCONNECT position (see Figure 60).
• circuit-breaker in test position (see Figure 61).
• circuit-breaker in CONNECT position (see Figure 62).
172 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 1 - E1.2 description
ABB | SACE Emax 2
2 - E2.2-E4.2-E6.2 description
Description of circuit-breaker The Emax E2.2-E4.2-E6.2 circuit-breakers consist of a steel structure in which the operating mechanism, the
poles and the auxiliary parts are located.
Each pole, isolated from the others, contains the breaking parts and the current transformer of its own phase.
The structure of the poles differs between selective or current-limiting circuit-breaker.
The circuit-breaker is available in two types:
• fixed version
• withdrawable
The circuit-breaker in fixed version (see Figure 63) has its own terminals for connection to the power circuit.
The withdrawable circuit breaker consists of a mobile part (see Figure 64) and of a fixed part (see Figure 65
for IEC and Figure 66 for UL) for connection through its own terminals to the power circuit.
The coupling between the mobile part and the fixed part is via disconnection contacts mounted on the fixed
part.
Figure 63 Figure 64
Figure 65 Figure 66
173 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
ABB | SACE Emax 2
Description of the circuit- The following are the main components of the circuit-breaker:
breaker front panel
1 2 3
4
5
6
7
8
9
Figure 67
Pos. Description
1 Lever for manually charging the closing springs
2 Ekip protection trip unit
3 Name of the circuit-breaker
4 CB open (O) / closed (I) indicator
5 Opening pushbutton
6 Mechanical signalling of tripped TU
7 Closing pushbutton
8 Springs charged-discharged signalling device
9 Electrical data plate
12
11 5
10
9
8
7
Uimp 12Kv 13
Figure 68
Pos. Description
1 Type of circuit-breaker
2 Utilization category
3 Device type: Circuit-breaker or switch-disconnector
4 Rated current
5 Rated operating frequency
6 Rated voltage of accessories
7 Admissible rated short-time current
8 Rated duty short-circuit breaking capacity
9 Rated ultimate short-circuit breaking capacity
10 Rated service voltage
11 Standards
12 Circuit-breaker serial number
13 Impulse voltage
174 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
ABB | SACE Emax 2
5 Accessories
A UX 4Q 3A 400V A C YO 220V - 250V A C/DC
4 A UX 6Q YO2
RTC YC 220V - 250V A C/DC
YR YC2
M 220V - 250V A C/DCYU
Figure 69
Pos. Description
1 Type of circuit-breaker
2 Rated current
3 Rated operating frequency
4 Rated voltage of accessories
5 Rated short-circuit breaking capacity
6 Rated service voltage
7 Standards
8 Circuit-breaker serial number
175 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
ABB | SACE Emax 2
Manual operations for opening The following is the sequence of steps for closing and opening the circuit-breaker:
and closing the circuit-breaker 1. Check that the circuit-breaker is open (open / closed indicator "O - OPEN"), and check that the springs
are discharged (spring signalling device "white - DISCHARGED SPRING") as indicated in Figure 70.
2. Charging the springs - Pull the lever [A] downwards several times until the springs charged signalling
device [B] is “yellow - CHARGED SPRING” as indicated in Figure 71.
A
B
Figure 70 Figure 71
3. Check that the circuit-breaker is open (open/closed signalling device “O - OPEN”), and check that the
springs are charged (springs signalling device “yellow - CHARGED SPRING”) as indicated in Figure 72.
4. Closing - Press the closing pushbutton “I - Push ON” as indicated in Figure 73.
Figure 72 Figure 73
5. Check that the circuit-breaker is closed (open/closed indicator "I - CLOSED"), and check that the
springs are discharged (spring signalling device "white - DISCHARGED SPRING" as indicated in
Figure 74.
6. Opening - Press the opening pushbutton “O - Push OFF” as indicated in Figure 75.
Figure 74 Figure 75
176 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
Continued from the previous page ABB | SACE Emax 2
7. Check that the circuit-breaker is open (open / closed indicator "O - OPEN"), and check that the springs
are discharged (spring signalling device "white - DISCHARGED SPRING") as indicated in Figure 76.
Figure 76
Mechanical status indicators The following are the possible states in which you can find the circuit-breaker:
1. Circuit-breaker open with springs discharged (see Figure 77).
2. Circuit-breaker open with springs charged (see Figure 78).
3. Circuit-breaker closed with springs discharged (see Figure 79).
4. Circuit-breaker closed with springs charged and not ready to close (see Figure 80). This state occurs
when after closing (see step 4 - Manual operations for opening and closing the circuit-breaker) the
springs are recharged manually or automatically by the gearmotor (if provided).
5. Circuit-breaker open with springs charged and not ready to close (see Figure 81). This state occurs
in the following cases:
• The circuit-breaker is open due to tripping of protection trip units and the Reset signal has not been
reset. To close the circuit-breaker press the TU Reset pushbutton on the front of the circuit-breaker.
• The key lock or padlock is active in the open position.
• The undervoltage coil is de-energized
• The opening coil is permanently energized.
• The closing coil is permanently energized.
• The pushbutton for enabling the insertion/extraction crank of a withdrawable circuit-breaker is pres-
sed.
Figure 80 Figure 81
177 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
ABB | SACE Emax 2
Circuit breaker racking-in/ The following is the procedure for the insertion of the moving part in the fixed part:
racking-out operations
WARNING!
1 2 “CLICK” 3
Figure 1
2. Position the lifting plates on the mobile part making sure that the tongue of the plates is latched
properly. See Figure 82.
1 2 3
Figure 82
3. Extract the guides of the fixed part using the appropriate levers. See Figure 83.
4. Position the moving part on the guides of the fixed part. Latch by inserting the hollow part of the side
in the latch of the guide of the fixed part See Figure 84.
1
2
Figure 83 Figure 84
178 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
Continued from the previous page ABB | SACE Emax 2
5. Unlatch the tongue and remove the lifting plates from the moving part. See Figure 85.
1 2 3
Figure 85
6. Make sure that the signalling device indicates the DISCONNECT position. See Figure 86.
Figure 86
7. Grip the guide levers of the fixed part and push them until the moving part stops. See Figure 87.
Figure 87
179 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
Continued from the previous page ABB | SACE Emax 2
8. Extract the disconnection crank from its housing See Figure 88.
9. Press the lock pushbutton and insert the crank in the moving part. In this phase the moving part is still
in DISCONNECT position. See Figure 89.
Figure 88 Figure 89
10. Turn the crank clockwise until the pushbutton comes out and the indicator shows that the circuit-
breaker is in TEST position. See Figure 90.
Figure 90
11. Press the lock button and rotate the crank clockwise until it comes out and the indicator shows that
the circuit-breaker is in CONNECT position. See Figure 91.
1
Figure 91
180 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
Continued from the previous page ABB | SACE Emax 2
Figure 92 Figure 93
To extract the moving part from the fixed part, perform the same steps indicated for insertion in reverse order.
Figure 94
181 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
Continued from the previous page ABB | SACE Emax 2
Always use both levers of the guides on the fixed part when racking out the circuit-breaker. See Figure 94.
= =
OK
NO!
Figure 95
WARNING! When withdrawing the moving part, make sure that both guides on the
fixed part travel to the same extent, thereby keeping the moving part parallel to the
fixed part. See Figure 95.
Mechanical position indicators The following are the possible positions where you can find the mobile part of a withdrawable circuit-breaker
during its use:
• circuit breaker in DISCONNECT position (see Figure 96)
• circuit-breaker in test position (see Figure 97)
• circuit-breaker in CONNECT position (see Figure 98)
182 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 2 - E2.2-E4.2-E6.2 description
ABB | SACE Emax 2
3 - Environmental conditions
Installation environment Install the circuit-breaker in a dry environment, without dust or corrosive acids, and so that it is not subject
to shock or vibration.
If this is not possible, mount the circuit-breaker in a compartment protecting it adequately.
For the dimensions to be considered for installation, see the chapter "4 - Installation" on page 185 where the
references for following information can be found:
• minimum installation volumes of the circuit-breakers and derived versions in a cell
• overall dimensions of the circuit-breakers and the fixed parts
• drilling of mounting holes
• drilling of the cell door
Temperatures of the installation The mechanical and electrical characteristics are guaranteed between -25 ° C and +70 ° C, -13 °F e +158 °F.
environment
Particular weather conditions The circuit breaker is designed to operate in particularly difficult industrial environments.
It was tested according to:
• IEC 60068-2-1: endurance at low temperatures
• IEC 60068-2-2: hot dry climate
• IEC 60068-2-30: hot humid climate
• IEC 60068-2-52 severity 2: saline mist atmosphere
• IEC 60947 (pollution level ≤ 3)
• IEC60721-3-6 class 6C3
• IEC60721-3-3 class 3C2
NOTE: the circuit-breaker is suitable for installation in environments with saline concentrations
no higher than 10 mg/m3.
Dusty environments It is recommended to install the circuit breaker in suitably ventilated switchgear where penetration by dust is
minimized.
In case of dusty environments (dust> 1 mg/m3) second level maintenance procedures must be followed.
Vibration The circuit-breaker is insensitive to mechanical or electromagnetic vibrations that meet the following
standards:
• IEC 60068-2-6 a) From 1 to 13 Hz with movement equal to 1 mm - 0.04 in b) From 13 to 100 Hz with
constant acceleration equal to 0.7 g - 0.025 lbs
• Shipping Registers' specifications: RINA, BV, GL, ABS, LRs, DNV
183 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 3 - Environmental conditions
ABB | SACE Emax 2
Altitude The circuit breaker maintains its rated operating characteristics up to 2000 m above sea level.
Once this altitude is passed, you need to consider reduction of dielectric strength and reduced cooling
capacity of the air.
The following are the corrections expressed as a percentage to be applied to the parameters according to
altitude:
2000 m / 3000 m / 4000 m / 5000 m /
Altitude
6600 ft 9900 ft 13200 ft 16500 ft
Rated service voltage (V) Ue 100% 88% 78% 68%
Rated current (A) at 40°C 100% 98% 93% 90%
Electromagnetic compatibility The use of specific devices in industrial installations may cause electromagnetic interference in the electrical
system.
The SACE Emax 2 circuit-breakers were developed and tested in an EMC environment in accordance with
IEC 60947-2, Annex J and F.
Storage Environment Store the circuit breaker in a dry, dust-free environment free of harsh chemicals.
The storage ambient temperature must be:
• Circuit-breaker in the original packaging, without protection trip unit or Ekip Dip trip unit, between -40 °
C and +85 ° C, -40 °F e +185 °F.
• Circuit-breaker in the original packaging, with Ekip Touch protection trip unit, between -25°C and + 85°C,
-22°F e +185°F.
NOTE: the storage conditions may differ from the usage conditions.
184 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 3 - Environmental conditions
ABB | SACE Emax 2
4 - Installation
Positioning anchor plates E1.2 The following diagram shows the distance for positioning the first anchor plate for E1.2 circuit-breakers
according to the peak current:
500/
19.69
450/ L L
17.72
400/
15.75
350/
13.78
L L
300/
11.81
250/
9.84
200/
7.87
150/
5.91
L L
100/
3.94
40 60 80 100 120 140 160
Figure 99
(1): distance of the first anchor plate from the circuit-breaker terminals
(2): peak current
Positioning anchor plates E2.2- The following diagram shows the distance for positioning the first anchor plate for E2.2-E4.2-E6.2 circuit-
E4.2-E6.2 breakers according to the peak current:
500/
19.69
400/
15.75
350/
13.78
300/
11.81
250/
9.84 L
200/
(1)
7.87
L [mm]
150/
5.91
100/
3.94
40 60 80 100 120 140 160 180 200 220 240 260 280 300
Figure 100
(1): distance of the first anchor plate from the circuit-breaker terminals
(2): peak current
30mm max.
Figure 101
>690V version circuit-breakers Insulating protections must be assembled for >690V circuit-breakers as indicated in the figure.
Withdrawable protec-
Circuit-breaker Voltage Version Fixed protection
tion
F X -
E2.2/E9 800V/900V
W - -
F X -
E2.2/E 1000V/1150V
W - X
F X -
E4.2/E9 800V/900V
W - -
F X -
E4.2/E 1000V/1150V
W - X
F X -
E6.2/E9 800V/900V
W - -
F X -
E6.2/E 1000V/1150V
W - X
Earthing (solo E2.2-E4.2-E6.2) The circuit-breakers in fixed version and the fixed part of withdrawable circuit-breakers are equipped with a
screw for the ground connection.
The connection must be implemented by means of a conductor of suitable cross-section according to the
IEC 61439-1 Standard.
Clean and degrease the area around the screw before making the connection.
After assembly of the conductor, tighten the screw with a torque of 2 Nm - 17.7 lb in.
Phase separators (for E2.2- Phase separators are available on request. Alternatively, it is possible to position the insulation barriers to
E4.2-E6.2 only) segregate live parts.In addition, the phase separators are mandatory:
• If, between two phases, the minimum distance between the screws that fix the circuit-breaker terminals
to the connection bars is less than 14 mm - 0.55".
• For circuit breakers version >690V.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheet 1SDH001000R0810.
Connection to the power circuit The connection of a circuit-breaker to the power circuit is performed using the connection busbars of the
electric switchgear fixed to the terminals of the circuit-breaker. The sizing of the busbars is specified by the
designer of the electrical switchgear.
IMPORTANT: before proceeding with the connection between terminals and connection
busbars:
• Make sure that the contact surfaces of the busbars are free of burrs, dents, traces of
rusting, dust or traces of grease.
• Make sure, if aluminium busbars are used, than they are tin plated in the contact areas.
• Make sure that the busbars do not exert forces in any direction on the terminal.
• Tightening: for E1.2 use M10 screws with resistance class 8.8 equipped with spring
washers and lock them with a torque of 45 Nm - 398.3 lb in
• Tightening: for E2.2-E4.2-E6.2 use M12 screws with resistance class 8.8 equipped with
spring washers and lock them with a torque of 70 Nm - 619.5 lb in
IMPORTANT: it is possible to obtain different capacities for the connections by altering
the thickness and number of busbars in parallel.
http://new.abb.com/low-voltage/products/circuit-breakers/emax2.
The connection for the E1.2 circuit-breaker is shown below as swell as the tables with some examples of the
amount and sizes of the connections that can be used for each type of circuit-breaker:
The connection for the E2.2-E4.2-E6.2 circuit-breakers is shown below as swell as the tables with some
examples of the amount and sizes of the connections that can be used for each type of circuit-breaker:
(1)
values for spread terminals
Dimension of Horizontal Vertical ter-
circuit-breaker UL 1066 Iu (A)
busbars terminals minals
3x1/4x2 - yes
4x1/4x2 yes -
1600
3x1/4x2.5 yes -
E2.2-A
2x1/4x3 - yes
4x1/4x2 - yes
2000
4x1/4x2.5 yes -
4x1/4x2 - yes
2000
4x1/4x2.5 yes -
E4.2-A 3x1/4x4 - yes
2500
4x1/4x4 yes -
3200 4x1/4x4 - yes
4000 4x1/4x5 yes yes
E6.2-A 6x1/4x5 - yes
5000
8x1/4x5 yes -
NO
OK
Figure 108
OK
NO
Figure 109
OK
NO
= = ≠ ≠
Figure 110
OK NO
OK NO
Figure 111
5 - Technical characteristics
Protection degree SACE Emax 2 circuit-breakers guarantee the following protection degrees:
• IP20 for circuit-breakers in fixed or withdrawable versions, excluding the terminals
• IP30 for the front parts of the circuit-breaker when it is installed in a switchboard with IP30 flange mounted
on the door
• IP54 in circuit-breakers equipped with an optional IP54 transparent flange fitted to the front door of the
switchboard.
Dissipated power To guarantee the performance of the switchgear in terms of uninterrupted rated capacity, the design of the
switchgear must take into account the power dissipated by switchgear and controlgear and by the installed
live parts. Dissipated powers are calculated according to the standard IEC 60947. The values indicated in
the table refer to the total power for each three-phase circuit-breaker with balanced loads with a current flow
equal to the rated uninterrupted current Iu. These power dissipations are measured according to the standard
IEC 60947. The values indicated in the table refer to the total power of the circuit-breakers in three-pole and
four-pole versions with balanced loads and a current flow equal to the rated uninterrupted current Iu at 50/60
Hz.
Dissipated power [W]
Iu E1.2 B/C/N E2.2 B/N/S/H E4.2 N/S/H/V E6.2 H/V/X
F (1) W (2) F (1) W (2) F (1) W (2) F (1) W (2)
630A 31 62
800A 50 100 34 72
1000A 78 156 53 113
1250A 122 244 83 176
1600A 201 400 136 288
2000A 212 450
2500A 267 550
3200A 425 743
4000A 465 900 309 544
5000A 483 850
6300A 767 1350
(1)
Fisso - Fixed - Fest - Fixe - Fijo
(2)
Estraibile - Withdrawable - Ausfahrbarer - Débrochable - Extraíble
192 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 5 - Technical characteristics
ABB | SACE Emax 2
Derating due to temperature In certain installations, the circuit-breakers could end up operating at a temperature above the reference
temperature (40 °C). In such cases the rated capacity of the circuit-breaker may be reduced. To find out the
percentage of reduction to be applied to the capacity consult the following table:
Emax 2 E1.2 Temperature [°C]
< 40 45 50 55 60 65 70
E1.2 250 100% 100% 100% 100% 100% 100% 100%
E1.2 630 100% 100% 100% 100% 100% 100% 100%
E1.2 800 100% 100% 100% 100% 100% 100% 100%
E1.2 1000 100% 100% 100% 100% 100% 100% 100%
E1.2 1250 100% 100% 100% 100% 100% 100% 100%
E1.2 1600 100% 100% 100% 98% 95% 93% 90%
193 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 5 - Technical characteristics
ABB | SACE Emax 2
Current limiting curve SACE Emax 2 series offer current-limiting circuit-breakers in E1.2 size up to 1600 A. These circuit-breakers
are characterized from the constructional point of view by the following features:
• Dedicated stored energy operating mechanism that reduces opening times.
• Specific main contacts that, by exploiting the electrodynamic forces generated by the short-circuit,
accelerate the opening of the main contacts.
These features enable rapid breaking and consequently reduce the electromechanical and thermal stress
suffered by the installation during a short-circuit. The Current-limiting circuit-breakers are characterized by
short-time withstand currents that are not particularly high and are therefore not suitable for applications
where selectivity towards more downstream devices is required or in case of devices with high inrush currents
in the start-up phase.
194 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical characteristics | 5 - Technical characteristics
ABB | SACE Emax 2
Accessories
1 - Preliminary considerations
Introduction All the circuit-breakers have a series of electrical and mechanical accessories that can be applied according
to the circuit-breaker type, and a series of electronic accessories that can be applied according to the type
of Ekip trip unit equipping the circuit-breaker.
Accessory combination tables The following table shows the possible combinations of the electrical and mechanical accessories for E1.2:
Switch-
Type of accessory Accessory Circuit-breakers
disconnectors
AUX 4Q S R
AUX 15Q R R
Ekip AUP (1) R R
Electrical signalling
Ekip RTC R R
S51 S -
S33 M/2 R R
YO (4) - YC R R
YO2 (4) R R
Electrical control YU (2)(4) R R
M R R
YR R -
KLC - PLC R R
KLP - PLP (1) R R
SL (1) S S
Security mechanical DLC R R
Anti-insertion lock S S
MOC R R
FAIL SAFE (3) R R
PBC R R
IP54 R R
Protection mechanical
HTC-LTC R R
PB R R
Interlocks MI R R
S: Standard. R: on request.
(1)
For withdrawable version only.
(2)
Incompatible with FAIL SAFE. Can be ordered for UL on request
(3)
Incompatible with YU; standard for UL version.
(4)
A maximum of two accessories are available for YO and YU.
The following table shows the possible combinations of the electrical and mechanical accessories for E2.2-
E4.2-E6.2:
S: Standard. R: on request.
(1)
For withdrawable version only.
(2)
Incompatible with FAIL SAFE. Can be ordered for UL on request
(3)
Incompatible with YU; standard for UL version.
(4)
A maximum of two accessories are available for YO and YU.
(5)
Not available for withdrawable circuit-breakers with lateral fastening.
(6)
Incompatible with YR
The following table shows the possible combinations of the electronic accessories:
Trip units
Type of accessory Accessory Ekip Ekip Ekip G Ekip G
Ekip Dip
Touch Hi-Touch Touch Hi-Touch
Power supply Ekip Supply R R R R R
Ekip Com - R R R R
Ekip Com Redundant - R R R R
Ekip Com Actuator R R R R R
Connectivity Ekip Link R R R R R
Ekip Bluetooth R R R R R
Ekip Signalling Modbus
R R R R R
TCP
Ekip Signalling 2K - R R R R
Ekip Signalling 3T - R R R R
Signal
Ekip Signalling 4K - R R R R
Ekip Signalling 10K R R R R R
Ekip Measuring - R - - -
Ekip Measuring Pro - R S S S
Ekip Synchrocheck - R R R R
Measurement and
Rating Plug R R R R R
Protection
Toroid S.G.R. - R R R R
Rc Toroid - R R R R
External neutral sensor R R R R R
Ekip Multimeter R R R R R
Display and Supervision
Ekip Control Panel R R R R R
Ekip TT R S S S S
Testing and
Ekip T&P R R R R R
Programming
Ekip Programming R R R R R
S: Standard. R: on request.
NOTE: Ekip Signalling 4K module available for E2.2-E4.2-E6.2 circuit-breakers.
Disassembly operations for To dismantle the accessories, the following parts must be removed from the circuit-breaker:
circuit breakers E1.2 • Front cover (A) and protection (F) by removing the screws (B and C).
• For 4-p circuit-breakers, the lateral protection (D) by fixing the screws (C and E).
D B
C
Figure 112 - Removing the front cover and protections
After reassembling the accessories, the parts previously dismantled must be reassembled as indicated:
• Front cover (A) and protection (F) by screwing the fixing screws (B and C) with tightening torque 0.8 Nm
- 7 lb in (B) and 1.5 Nm - 13 lb in (C).
• For 4-p circuit-breakers, the lateral protection (D) by fixing the screws (C and E) with tightening torque
1.5 Nm - 13 lb in.
D B
C
Disassembly operations for To dismantle the accessories, the following parts must be removed from the circuit-breaker:
circuit breakers E2.2-E4.2-E6.2 • Transparent flange (A) of the trip unit, by turning the screws (B).
• Front cover of the circuit-breaker (C), by removing the mounting screws (D).
1
2
C 2
1
90°
A
B
D
Figure 114 - Removing the flange and front cover
After reassembling the accessories, the parts previously dismantled must be reassembled as indicated:
• Front cover of the circuit-breaker (C), by screwing in the mounting screws (D) with tightening torque 1.1
Nm - 9.74 lb in.
• Transparent flange (A) of the trip unit, by turning the screws (B).
C 2
1
2
1
90°
A
B
D
Figure 115 - Assembly of flange and front cover
2 - Wiring diagrams
General wiring diagrams The following is the wiring diagram of the circuit-breaker 1SDM000091R0001, also available on the website
http://www.abb.com/abblibrary/DownloadCenter/.
N L1 L2 L3
K51
XK1
1
Q
XK1
T11 13 >
YO1
TI/L1 T12 14
2
T21 11 >>
TI/L2 T22 12
XK3
T31 9 7
TI/L3 T32 10 >>
A1 T41 7 Q/26
TI/N T42 8 >>
> 8
XK3
XK1
T13 21
>> 9
UI/L1 T14 22
Q/27
T23 19
UI/L2 10
T24 20 EKIP DIP
EKIP TOUCH
T33 17 XK3
UI/L3 EKIP HI-TOUCH 5
T34 18
EKIP G TOUCH
T43 15 EKIP G HI-TOUCH
UI/N T44 16 RTC EKIP
6
* C)
* H)
• Circuit-breaker in withdrawable version (also valid for fixed version), open and connected.
• Circuits de-energized.
• Trip units not tripped.
• Motor operator with discharged springs.
The following is the wiring diagram of the switch-disconnector:
B
N L1 L2 L3
A1 Q
The wiring diagram of the circuit breaker is illustrated without any indication of the auxiliary power supply of
the Ekip trip unit. If the circuit-breaker is equipped with the Ekip Supply module, for information see page 208.
If the circuit-breaker is not equipped with the Ekip Supply module, for the connection of the auxiliary power
supply of the Ekip trip unit see the direct power supply diagram below:
31
* P)
-
Uaux.
+
A4 24VDC
* N)
X K1 K2
XV K1 K2
K1
K2
A1 K51
EKIP
W3
W4
XV W3 W4
X W3 W4
A4 * Q)
(A) (B)
W2 (LOCAL BUS)
* A)
Diagram 31 - Direct auxiliary power supply
Circuit-breaker terminal box The circuit-breaker is equipped with a terminal box for the wiring of the accessories, different according to
the type of circuit-breaker:
• Terminal box for circuit-breakers in fixed version.
• Terminal box for circuit-breakers in withdrawable version.
The following is a view of the terminal box of E1.2 circuit-breakers in both fixed and withdrawable versions
with the differences highlighted:
EKIP Supply TU YU YC
S51 S33 M YR Trip Unit I/O Module Module I/O RTC YO2 YO Q1 Q2 Q3 Q4
Figure 116
The following is a view of the terminal box of E2.2-E4.2-E6.2 circuit-breakers in both fixed and withdrawable
versions with the differences highlighted:
61 71 81 91 01 45
51 HC H1 H2 H3 H4 95 35 R1 V3 Vn Ge+ Szi Ne- K2 W4 D1 C1 C11 C21 11 21 31 41
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo Ne+ K1 W3 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04 98 38
54
HC K7 K8 K9 K10 U2 V1 Gzo Szc Gzi Rca 48 D2 C2 C12 C22 14 24 34 44
S51 S33 Trip Unit I/O EKIP Supply Module Module Module YU YC YO YC2 Q1 Q2
RTC YO2 Q3 Q4
Q5..Q10/EKIP Signalling 4K M YR
71 81 91 01
51 61HC H1 H2 H3 H4 95 35 R1 V3 Vn Ge+ Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
62 72 82 92 02
52 HC K3 K4 K5 K6 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne+ 46 C3 C13 12 22 32 42
64 74 84 94 04 V1 Gzo Szc Gzi
54
HC K7 K8 K9 K10 98 38 U2 W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
Figure 117
NOTE: for the details of the wiring diagram of each single accessory, please refer to the pages
describing that specific accessory.
In addition, the terminal box of the Emax E1.2 circuit-breaker has two differences compared to the terminal
box for Emax E2.2-E4.2-E6.2 circuit-breakers:
• Module compartments: Emax E1.2 can house three modules (one Ekip Supply + two other modules),
whereas E2.2-E4.2-E6.2 can house four modules (one Ekip Supply + three other odules).
• Ekip Signalling 4K: Emax E1.2 does not have the connections for Q5...Q10 / Ekip Signalling 4K.
In the following chapters, the terminal box considered is always that one of E2.2-E4.2-E6.2 circuit-breakers.
Q4
41
42
44
32
Q/3 34
31
81
Q3
31
32
34
22
Q/2 24
21
Q2
21
22
24
12
Q/1 14
11
YO YC2 Q1
12
14
11
C21
YC2
79
C1 C11 C21
C2 C12 C22
C22
C11
C11
YO
K51
76
C3 C13
75 C13
YO
C12 YO C12
C1
C1
RTC YU YC
YC
K51
77 78
YC
C3
C2 YC C2
YO2
D1
D2
D1 73 D1
YO2
YU
72 D2 74 D2
45
46
48
46
RTC
71 48
45
K51
Ne+
Ne+
Rca
Ne-
I/O
TU
27 Ne-
K51/..
W3
LOCAL BUS
K1
K2
31
EKIP Supply
W4
K1
32 ALIM. AUS. +/L
W3
W4
AUX. SUPPLY -/N K2
41 K51/SIGN H12
K51/SIGN K12 K51/SYNC KS1 48 44 K51/TEMP
O 12
I 12 I 44 H44
K14 XSC KS2
Hc6
K51/SYNC H
K51/SIGN H11
O 11
Module
HC1 I 11 VS2 Hc5
K13 H
I 42 H42
H Hc4
42 K51/SIGN H22
K51/SIGN K22 K51/COM 51 I 42 H41
O 22
K51/SIGN H21
O 21
Module
HC2 I 21 K23 H54
I 54
58 H
HC9
I 53 H53
43 K51/SIGN H32
K51/SIGN K32 K51/COM 61 H
HC8
O 32
I 32 K34 W..R ..
O ORTA COMUNIC.
COMMUN. O ORT
I 52 H52
RIDONDANTE
REDUNDANT
K51/SIGN H31 H
O 31
HC7
K51/SIGN K31 ..
Module
I 31 I 52 H51
HC3 K33
66 4-20 mA
K51
Szi
Rct Ge- Szo
Gzo
25 Rca
24 Ge+
Ge-
Szc
Vn
K51/MEAS K51/MEAS
VN K51/MEAS
21 VN
20 V1
V3
V2
22 23 V2
V3
N L1 L2 L3 L1 L2 L3
YR
R1
R2
R1
YR
14 R2
F1
U1
U2
S33M/1 U1
M
M
13 U2
S51 S33
36
35
36
38
S33M/2
12 38
35
96
95
96
98
S51
11 98
95
H4
K6
K10
K51/SIGN K6 02
K51/SIGN Q/10
EKIP Signalling 4K
H4
01
02
04
O 04 04
I 04
K10
01
H3
K5
K9
K51/SIGN K5 92
K51/SIGN H3 Q/9
91
92
94
O 03 94
I 03
K9
91
K51/SIGN
H2
K4
K8
K4 82
K51/SIGN H2 Q/8
O 02 84
81
82
84
I 02
K8
81
K51/SIGN
H1
K3
K7
K3 72
K51/SIGN H1 Q/7
I 01
O 01 74
71
72
74
K7
71
HC
HC
HC
62
Q5..Q10
HC Q/6 64
61
62
64
61
52
Q/5
51
52
54
54
51
N 2 1
Symbol Description
* See the note indicated by the letter
A1 Applications located on the mobile part of the circuit-breaker
A3 Applications located on the fixed part of the circuit-breaker
Indicative device and connections for control and signalling, outside the
A4
circuit-breaker
BUS1 Serial interface with external bus
D Electronic time-lag device of YU undervoltage coil, outside the circuit-breaker
F1 Time-delayed trip fuse
GZi(DBi) Zone Selectivity input for G protection or input in “reverse” direction for D protection
Zone Selectivity output for G protection or output in “reverse” direction for D
GZo(DBo)
protection
I 01…32 Up to 10 programmable digital inputs of the Ekip trip unit
K51 Overcurrent protection solid-state trip unit
K51 / COM Communication module
K51 / MEAS Measurement module
K51 / SIGN Signalling module
K51 / SUPPLY Optional auxiliary power supply module (24-48Vdc and 110-220Vac / dc)
K51 / SYNC Synchronization module
K51 / YC Closing control from the Ekip protection trip unit
K51 / YO Opening control from the Ekip protection trip unit
M Motor for loading closing springs
O 01...32 Up to 10 programmable digital inputs of the Ekip trip unit
O SC Contact for synchronism control
Q Circuit-breaker
Q / 1...Q / 27 Auxiliary open/closed contacts of the circuit-breaker
Rc Rc Toroid
RTC EKIP Auxiliary ready to close contact of the circuit-breaker, used internally by the trip unit
RTC Contact for signalling circuit-breaker is ready to close
S33M / 1…2 Limit contacts of spring loading motor
S43 Switch for setting remote/local control
S51 Trip signalling contact
S51/2 Trip signalling contact
Contacts for signalling circuit-breaker in disconnected position
S75E / 1…4 (1)
(only with withdrawable circuit-breakers)
Contacts for signalling circuit-breaker in connected position
S75I / 1…4 (1)
(only with withdrawable circuit-breakers)
Contacts for signalling circuit-breaker in test position
S75T / 1…4 (1)
(only with withdrawable circuit-breakers)
SC Pushbutton or contact for closing the circuit-breaker
SO Pushbutton or contact for immediate opening of the circuit-breaker
SO1 Pushbutton or contact for opening the circuit-breaker with time-delayed trip
SR Push-button or contact for electrical restting of opening contacts S51 and S51/2
Input for Zone Selectivity for S protection or input in “direct” direction for D
SZi(DFi)
protection
Output for Zone Selectivity for S protection or output in “direct” direction for D
SZo(DFo)
protection
TI / L1 Current transformer phase L1
TI / L2 Current transformer phase L2
TI / L3 Current transformer phase L3
TI / N Current transformer on neutral
TU1…TU2 Insulation voltage transformer (outside circuit-breaker)
Uaux Auxiliary supply voltage
UI / L1 Current sensor phase L1
YU2 (2) Second undervoltage coil
(1)
There are up to 6 S75 contacts for E1.2 and 10 for E2.2-E4.2-E6.2.
(2)
Only for E2.2-E4.2-E6.2.
The explanatory key to the numbering used in the circuit diagrams is given below:
Symbol Description
[81] Open/close auxiliary contacts of the circuit-breaker (first set)
[79] Second closing coil
[75][76] First opening coil
[77][78] First closing coil
[72] Second opening coil
[73][74] Undervoltage coil
[71] Contact ready to close
[27] Input of current sensor on the external neutral
[31][32] Auxiliary power supply and Local Bus
[41][42][43] Signalling modules
[44][45] Temperature monitoring modules
[48] Ekip Synchrocheck
[51][...][...][58] Communication modules
[61][...][...][66] Redundant communication modules
[26] Zone selectivity
[25] Input of the TRAFO star centre sensor
[24] Input of the residual-current protection RC sensor
Note Description
For the zone selectivity and Local bus functions an auxiliary power supply is required (see
A)
diagram 1SDM000091R0001, figures 31-32).
When there are mixed auxiliary contacts, Q1 and Q2 are 400V, while Q3 and Q4 are 24V. Then
B)
Q5, Q6 and Q7 are 400V while Q8, Q9 and Q10 are 24V.
C) Always supplied with Ekip Com module.
D) Always supplied with the motor for loading the closing springs in Figure 13.
Voltage transformer, mandatory in the case of external outlet sockets. External outlet sockets,
E) mandatory for systems with rated voltage greater than 690 V. The maximum secondary rated
voltage admitted is 230V.
The connections between the residual-current protection RC sensor and the poles of connector
F) X (or XV) of the circuit-breaker must be implemented with a screened four-pole cable with paired
braided conductors (BELDEN 9696 paired type or equivalent), no more than 10m in length.
With all the electronic protection trip units equipped with a display interface with LSIG
protections, protection against ground faults (Gext) is available through a current sensor
positioned on the star centre of the MV/LV transformer. The connection between terminals 1
G)
and 2 of the UI/O current transformer and the Ge+ and Ge- poles of connector X (or XV) must
be implemented with two-pole shielded stranded cable (BELDEN 9841 type or equivalent) no
more than 15 m in length.
Make the connection using the ABB cable supplied. There must be no break in the cable. Use
of other cables or extensions using intermediate terminal boxes is not allowed. With a three-pole
H)
circuit-breaker, poles Ne+ and Ne- of connector X (or XV) are short-circuited (unless the external
neutral is present): realize short-circuit connection if absent.
I) Obligatory in the case of presence of any Ekip module.
In the presence of Fig. 32, for circuit-breakers E2.2, E4.2 and E6.2, up to three applications can
be supplied between Fig. 41…58 taken only one; for E1.2 circuit-breakers, instead, up to two
L)
applications can be supplied between Fig. 41…58 taken only once. In addition it is possible to
duplicate an Ekip Com module that may be selected choosing between Fig. 61…66.
Opening and closing commands via the Ekip Actuator module can be obtained with coils YC
M)
and YO, with 110-120VDC and 240-250VAC maximum voltage values.
N) Use cable type Belden 3105A or equivalent.
In the presence of several Ekip Com modules with withdrawable version circuit-breakers, the
O)
contact S75I/5 should be connected only once to a single module.
The auxiliary voltage Uaux allows all the functions of the Ekip electronic protection trip units to
P) be activated "Galvanically separated converters" conforming to standard IEC 60950 (UL 1950)
or the equivalent standards.
Q) Belden type 3105A or equivalent cables must be used, with a maximum length of 15m.
R) Suggested RJ45 cable: CAT6 STP
For the EIA RS485 serial interface connection, see the "Technical Application Handbook - vol.
S)
9: Communication with ABB circuit-breakers via BUS”
T) Short circuit the 120 Ω on terminals if you wish to insert a terminating resistor on the Local Bus.
Use Belden type 3105A or equivalent cables. For further details see the White Paper
U)
1SDC007412G0201 "Communication with SACE Emax 2 circuit-breakers".
Use Belden type 3084A or equivalent cables. For further details see the White Paper
V)
1SDC007412G0201 "Communication with SACE Emax 2 circuit-breakers".
Z) Ekip Supply cannot be used to supply the electronic trip unit via terminals K1 and K2.
AA) For W3 and W4 connection see figure 31 or 32
Use a twisted pair shielded and stranded cable type BELDEN 8762/8772 or equivalent. The
AB) shield must be earthed on the selectivity input side (for zone selectivity) or on both sides (for
others applications).
AC) The maximum secondary rated voltage admitted is 120V.
Use insulated cables for thermcouples such as PENTRONIC TEC/SITW-24F (Type TX) or
AD)
similar. Maximum length 3 meters.
Use suitable cables up to 3 meters in length compatible with the workplace in which the
AE)
4-20mA current sensor is used.
(1)
Only for E2.2-E4.2-E6.2.
3 - Standard accessories
Accessories for fixed circuit- Fixed version SACE Emax 2 circuit-breakers and switch-disconnectors are always supplied with the following
breakers accessories as standard:
• IP30 protection for the switchgear door
• lifting plates for E2.2-E4.2-E6.2 circuit-breakers
• front terminals for E1.2 circuit-breakers
• orientable rear terminals for E2.2-E4.2-E6.2 circuit-breakers, mounted in HR – HR position
• screws for mounting in switchboards
In addition, for automatic circuit-breakers only, the following accessories are always supplied:
• four standard open/closed auxiliary contacts - AUX 4Q
• four terminals for the auxiliary connections
• mechanical signalling for protection trip unit tripping - Ekip TU Reset
• Ekip TT power supply and test unit, when a protection unit is present on display
• Ekip protection trip unit tripping signalling contact S51
Accessories for withdrawable Withdrawable version SACE Emax 2 circuit-breakers and switch-disconnectors are always supplied with the
circuit-breakers following accessories as standard:
• anti-extraction locking mechanism with the circuit-breaker closed
• lifting plates for E2.2-E4.2-E6.2 circuit-breakers
• racking-in/racking-out lever
• anti-insertion lock
In addition, for automatic circuit-breakers only, the following accessories are always supplied:
• four standard open/closed auxiliary contacts - AUX 4Q
• four terminals for the auxiliary connections
• mechanical signalling for protection trip unit tripping - Ekip TU Reset
• Ekip TT power supply and test unit, when a protection unit is present on display
The fixed parts of the withdrawable versions are always supplied with:
• IP30 protection for the switchgear door
• anti-insertion lock
• standard shutter lock - SL
• screws for floor mounting
• orientable rear terminals
Electronic accessories
1 - Introduction
Operating conditions The Ekip Synchrocheck, Ekip Com and Ekip Signalling modules function correctly:
• In the presence of auxiliary power supply.
• With the circuit-breaker in racked-in position (if the model is withdrawable).
Ekip Signalling 2K
Module\ Ekip
Ekip Com Ekip Signalling 3T Ekip Signalling 4K
Condition Synchrocheck
Ekip Signalling 10K
CB in Test (1)(2) Synchronism: Communication: Inputs and output Inputs and output
position not available (4) active contacts: available contacts: available
(1)
The description refers to the module when correctly on and with the CB in the indicated position.
(2)
In the Test position, the trip unit is connected to the modules and all information is available on the display or
via external communication.
(3)
In the DISCONNECTED position, the connection between trip unit and modules is interrupted.
(4)
Owing to internal voltage not connected to the Ekip Measuring Pro module.
(5)
See the document 1SDH001140R0001 (Communication System Interface Emax 2), section INFORMATION
WITH PROTECTION TRIP UNIT DISCONNECTED.
(6)
Outputs only function correctly if configured as: input state (of module itself) or non-communication with trip
unit. For all other configurations, the module forces the Outputs as per Contact Type parameter (NO, NC).
Compatibility The modules can be installed combined with Ekip Dip, Ekip Touch, Ekip Hi‐Touch, Ekip G Touch, and Ekip G
Hi‐Touch trip units.
Electrical characteristics The following table lists the electrical characteristics of the modules:
(1)
Trip unit with Ekip Supply only
208 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 1 - Ekip Supply modules
ABB | SACE Emax 2
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0511.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K 2
Module Module Module I/O
32
A4 Uaux.
110-240VAC/DC * Q)
24-48VDC
K1 K2 W3 W4
X K1 K2 W3 W4
XV K1 K2 W3 W4
W3
W4
K1
K2
A1
K51
EKIP
* A) * I)
Diagram 32
For external wiring, AWG 22-16 cables with a maximum external diameter of 1.4 mm must be used.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
A • Off: power supply absent.
• On fixed: power supply present.
209 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 1 - Ekip Supply modules
ABB | SACE Emax 2
Description The Ekip Measuring is an accessory module for measurement of voltage, power and energy.
Specifically:
• It measures the r.m.s. value and frequency of the voltages of the three-phase system on the internal
contacts of the circuit-breaker, or on the external sockets. From these measurements, the trip unit obtains
the power and energy ones, which therefore become available.
• Combined with the Ekip Synchrocheck module, Ekip Measuring makes it possible to recognise whether
the synchronism conditions exist between the internal contacts (or external sockets) and external contacts
necessary for closing the circuit-breaker.
Two types are available:
• Ekip Measuring, equipped with the measuring function only.
• Ekip Measuring Pro, with a measuring function, possibility of powering the trip unit, and activation of the
Measuring protections.
With the Ekip Measuring Pro module, the power supply of the trip unit is guaranteed, if at least one value of
the line-to-line voltages is greater than or equal to 80 V AC.
Compatibility and power supply The Ekip Touch trip unit can be equipped with the Ekip Measuring and the Ekip Measuring Pro modules, the
former if you only wish to implement the measurement function and the latter if you also wish to implement
the power supply function and activate the Measuring protections. With Ekip Hi-Touch, G Touch, and G Hi-
Touch trip units, Ekip Measuring Pro is provided as standard.
Ekip Measuring requires the trip unit to be also supplied with auxiliary voltage (example: provided by an Ekip
Supply module). Auxiliary supply is not necessary with Ekip Measuring Pro.
Electrical characteristics The following table lists the electrical characteristics of the modules:
Component Characteristics
Phase-to-phase input voltage 0…760 V AC
Input frequency 30…80 Hz
Isolation transformer If the input phase-to-phase voltage supplied to the modules is greater than 690 V AC rated voltage (maximum
760 V AC), external sockets must be used.
In the presence of external sockets, the use of an isolation transformer is mandatory.
IMPORTANT: the maximum secondary rated voltage admitted in the case of external
outlet sockets is 230V.
NOTE: for the primary and secondary voltages of the transformer, see the configuration
parameters of the module, paragraph "Access from the display".
210 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 2 - Ekip Measuring modules
ABB | SACE Emax 2
Measurements The following table lists the measurement accuracy for the modules:
(1)
With phase-to-phase voltage V greater than 690 V AC rated voltage (maximum 760 V AC), in the presence of
external sockets and an isolation transformer.
(2)
The measurement of the frequency is available with a a phase-to-phase voltage value ≥ 36 V AC, and is
unavailable with a phase-to-phase voltage value ≤ 32 V AC.
(3)
In the absence of harmonic distortion.
Connections The modules must be mounted directly on the Mainboard, to the right of the trip unit. In parallel they are
connected to a connector, to which the phase and neutral voltages arrive either on the internal contacts of
the circuit-breaker, or on the external sockets.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0505.
IMPORTANT: in the case of dielectric tests, you need to disconnect the modules as
illustrated in the assembly diagram, and to disconnect the external sockets from the
terminal box. It is not necessary to remove the modules.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K10
S51 S33 M YR Trip Unit I/O TU YU YC
RTC YO2 YO YC2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O
Module Module Module EKIP Supply
20 21 22 23
N PE N L1L2 L3 TU1
L1 L2 L3 A1 a1
B1 b1
A2 a2
GS B2 b2
A4 3~
A3 a3
B3 b3
* E)
* AB)
X VN V3 V2 V1 VN V3 V2 V1 VN V3 V2 V1 VN V3 V2 V1
XV VN V3 V2 V1 VN V3 V2 V1 VN V3 V2 V1 VN V3 V2 V1
N L1 L2 L3 L1 L2 L3 L1L2 L3
A1
Ekip Measuring Pro
Ekip Measuring
Ekip Measuring
XV
X
A4
Diagrams 20 - 21 - 22 - 23
211 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 2 - Ekip Measuring modules
ABB | SACE Emax 2
Access from the display With the trip unit energized, the presence of the modules activates the following on the display:
• Additional graphical pages, that display measurements.
• Additional menus.
The additional graphical pages are:
• A summary of the measurements in progress (maximum phase current, maximum phase-to-phase voltage,
power factor, and the active, reactive and apparent power), accessible from the page Histograms (see
page 42).
• The indicators of the maximum phase-to-phase voltage, and of the active, reactive and apparent power,
accessible by selecting the pages Measuring instruments (see page 44).
• The measurements of the phase and phase-to-phase voltages, and of the active, reactive and apparent
power, as well as the energy counters, accessible by selecting the pages Measurements (see page 45).
• The historicals of the minimum and maximum phase-to-phase voltages and maximum and mean power,
accessible from the menu Measurements.
• The waveforms and the harmonics of the phase-to-phase voltages, accessible from the menu Measurements.
The additional menus allow you to:
• Configure the protections activated by Ekip Measuring Pro.
• Configure the modules.
• Display the measurements associated to the modules (in addition to those displayed in the graphical pages).
• Display information on the modules.
The following table shows the path from the display to access the configuration parameters of the protections
activated by the Ekip Measuring Pro module:
…
IU Protection
Rc Protection (1)
UV Protection
UV2 Protection
OV Protection
OV2 Protection
RV Protection
VU Protection
UF Protection
UF2 Protection
OF Protection
Advanced OF2 Protection
ROCOF Protection
RP Protection
RQ Protection
OP Protection
OQ Protection
UP Protection
Synchrocheck
Phase Sequence
Signallings
Cos φ
Current thresholds
…
(1)
Protection available with Rating Plug Rc and Ekip Measuring Pro, and toroid Rc (see the menu Settings -
Circuit Breaker - Ground protection), and alternative to the Gext protection (see the Protections menu).
212 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 2 - Ekip Measuring modules
Continued from the previous page ABB | SACE Emax 2
NOTE: selecting a protection opens the list of parameters that can be set for the selected
protection. For details on the protections, see chapters “10 - Measuring Pro protections”
on page 75, and the chapter "11 - Hi-Touch protections” on page 81.
The following table shows the path from the display for viewing the measurements and commands activated
by the modules and accessible from the menus:
…
Events
…
I Max
U Min
U Max
Historicals
P Max
Measurements P Mean
Q Max
Q Mean
S Max
S Mean
Reset measures
Power factor
Frequency
Energy counters
Measurement
Energy Reset counters
RESET Energy
Peak factor
Harmonic dist.
Ekip Synchrocheck
…
Counters
…
Network Analyzer
Ne
Waveforms Voltage 12
Voltage 23
Voltage 31
Maintenance
213 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 2 - Ekip Measuring modules
Continued from the previous page ABB | SACE Emax 2
The following table shows the measurements and commands accessible from the menus:
Measurement or
Description
control
It shows the history of the minimum line-to-line voltage measurements in the form
U Min
of a histogram (see page 53).
It shows the history of the maximum line-to-line voltage measurements in the
U Max
form of a histogram (see page 53).
It shows the history of the maximum active power measurements in the form of a
P Max
histogram (see page 53).
It shows the history of the mean active power measurements in the form of a
P Mean
histogram (see page 53).
It shows the history of the maximum reactive power measurements in the form of
Q Max
a histogram (see page 53).
It shows the history of the mean active power measurements in the form of a
Q Mean
histogram (see page 53).
It shows the history of the maximum apparent power measurements in the form
S Max
of a histogram (see page 53).
It shows the history of the mean apparent power measurements in the form of a
S Mean
histogram (see page 53).
Power factor Shows the value of the power factor.
Energy counters Shows the values of active, reactive and apparent energy.
Reset counters It resets the energy counters.
It opens a list of the parameters for programming the resetting of the energy
RESET Energy
counters (see page 51).
Shows the waveform of the phase-to-phase voltage U12, acquired at the
Voltage 12
moment of selection (see page 54).
Shows the waveform of the phase-to-phase voltage U23, acquired at the
Voltage 23
moment of selection (see page 54).
Shows the waveform of the phase-to-phase voltage U31, acquired at the
Voltage 31
moment of selection (see page 54).
The following table shows the path for accessing the configuration parameters of the modules from the
display:
…
Main frequency
Phase Sequence
Local/Remote
Local bus
…
Voltage Transf.
Settings Rated voltage
Modules Primary voltage
Ekip Measuring
Secondary voltage
Power flow
Neutral connection
…
Functions
Monitor time
Power Controller
…
214 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 2 - Ekip Measuring modules
Continued from the previous page ABB | SACE Emax 2
The following table shows the configuration parameters of the modules:
Parameter Values Default Description
• Absent = Isolation transformer on
the supply side of the inputs of the
Voltage module is absent.
Absent, Present Absent
Transf. • Present = Isolation transformer on
the supply side of the inputs of the
module is present.
100 V, 115 V, 120 V, 190 V, 208 V,
Displayed with "Voltage Transf." set
220 V, 230 V, 240 V, 277 V, 347 V,
Rated voltage 400 V as absent: the rated voltage of the
380 V, 400 V, 415 V, 440 V, 480 V,
installation.
500 V, 550 V, 600 V, 660 V, 690 V
100 V, 115 V, 120 V, 190 V, 208 V,
220 V, 230 V, 240 V, 277 V, 347 V, Displayed with "Voltage Transf." set
Primary
380 V, 400 V, 415 V, 440 V, 480 V, 400 V as present: the primary voltage of
voltage
500 V, 550 V, 600 V, 660 V, 690 V, the isolation transformer.
910 V, 950 V, 1000 V, 1150 V
Displayed with "Voltage Transf." set
Secondary 100 V, 110 V, 115 V, 120 V, 200 V,
100 V as present: the secondary voltage of
voltage 230 V
the isolation transformer.
• Bottom->Top = Flow of power
from the low terminals to the high
terminals of the circuit-breaker (load
connected to top).
Power flow Bottom->Top, Top->Bottom Low->High
• Top->Bottom = Flow of power
from the high terminals to the low
terminals the circuit-breaker (load
connected to bottom).
• Present = It enables measurement
of the phase voltages.
Neutral • Absent = It disables measurement
Absent, Present Present
connection (1) of the phase voltages (only it
enables measurement of line-to-line
voltages).
(1)
Available with 3P configuration.
The following table shows the path from the display to get information on the modules:
Protection Unit
Circuit-breaker
…
About
Modules Ekip Measuring
…
Power Controller
The items of information on the modules that can be displayed are the serial number and the version ("Basic"
in the case of Ekip Measuring, "Pro" in the case of Ekip Measuring Pro).
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power status LED, green; present only on the Ekip Measuring Pro. The possible states are:
A
A • Off: the power supplied by the Ekip Measuring Pro to the trip unit is absent.
• On fixed: the power supplied by the Ekip Measuring Pro to the trip unit is present.
215 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 2 - Ekip Measuring modules
ABB | SACE Emax 2
Description The Ekip Synchrocheck is an accessory module that, combined with the Ekip Measuring or Ekip Measuring
Pro module serves to recognize whether the synchronism conditions exist between the internal and external
contacts of the circuit-breaker, necessary for closing the circuit-breaker.
Ekip Synchrocheck measures the voltage on the external contacts (external voltage) while Ekip Measuring or
Ekip Measuring Pro measures it on the internal contacts (internal voltage). With a generator, and the circuit-
breaker in "Standard" configuration, the external voltage is that of the grid while the internal voltage is that
of the generator.
There are two types of operation:
• With busbar live, if the external voltage is other than zero.
• With a dead bus, if one of the voltages is nil (external with "Standard" configuration, internal with "Reverse"
configuration).
With live busbar:
• The search for the synchronism is started if the external voltage is greater than or equal to a minimum (0.5
Un by default), for a minimum time (1 s by default).
• Synchronism is considered to be reached if the differences between the RMS values of the frequency and
the voltage phases are less than or equal to a maximum (0.12 Un, 0.1 Hz and 50 ° by default).
Instead, with a dead bus and "Normal" configuration:
• The search for the synchronism is started if the internal voltage is greater than or equal to a minimum (0.5
Un by default), for a minimum time (1 s by default).
• The synchronism is considered to be achieved if the external voltage is less than or equal to a maximum
(0.2 by default) for a minimum time (1 s by default).
With a dead bus and "Reverse" configuration, the roles of the internal and external voltages are reversed.
To the above-mentioned synchronism conditions, we can add that of circuit-breaker open (by enabling the
condition “Evaluate CB status”, disabled by default).
The frequency and phase controls can be disabled.
IMPORTANT: to disable frequency and phase controls, make sure that the
correspondence of the desired frequency and phase already exists between external
and internal contacts.
The synchronism signal is activated when the synchronism is achieved and is kept active for at least 200 ms.
After 200 ms, it is kept active while the synchronism is present, and deactivated when the synchronism falls,
or the circuit-breaker is open (with condition "Evaluate CB status" enabled), or the communication with the
trip unit is interrupted.
Lastly, the Ekip Synchrocheck module makes the pins of a contact (K S1 and K S2) available on the terminal
box. Depending on how the module is configured, this contact is either normally open or closed, and changes
status when the synchronism is achieved.
IMPORTANT: only one Ekip Synchrocheck can be installed on each circuit-breaker.
Compatibility and power supply The module can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
requires the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
216 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 3 - Ekip Synchrocheck module
ABB | SACE Emax 2
Electrical characteristics The following table lists the electrical characteristics of the module:
Component Characteristics
Input voltage 0...120 V AC rated
Input frequency 30…80 Hz
• Maximum switching voltage (1): 150 V DC / 250 V AC.
• Breaking capacity (1): 2 A @ 30 V DC, 0.8 A @ 50 V DC, 0.2 A @ 150 V DC,
4A @ 250 V AC.
Output contact
• Dielectric strength between open contacts: 1000 V AC (1 minute @ 50 Hz).
• Dielectric strength between each contact and coil: 1000 V AC (1 minute @
50 Hz).
(1)
Data related to a resistive load.
Isolation transformer Between the external contacts of the circuit-breaker and the inputs of the module, an isolation transformer
must always be installed having the following characteristics:
Characteristics Description
• Mounting: EN 50022 DIN43880 guide.
• Material: self-extinguishing thermoplastic.
Mechanical
• Protection degree: IP30.
• Electrostatic protection: with shield to be connected to ground.
• Accuracy class: ≤ 0.5.
• Performance: ≥ 5 VA.
• Overload: 20 % permanent.
Electrical
• Insulation: 4 kV between inputs and outputs, 4 kV between shield and
outputs, 4 kV between shield and inputs.
• Frequency: 45…66 Hz.
NOTE: for the primary and secondary voltages of the transformer, see the configuration
parameters of the module, paragraph "Access from the display" on page 220).
Measurements The following table lists the measurement accuracy for the module:
(1)
With live busbar.
(2)
With a live busbar, the frequency measurement is available with a voltage measured ≥ 36 V AC, and is
unavailable with a voltage measured ≤ 32 V AC.
(3)
In the absence of harmonic distortion.
(4)
The phase measurement refers to the phase difference between internal and external voltage.
217 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 3 - Ekip Synchrocheck module
ABB | SACE Emax 2
Connections The module must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0513.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
48
TU2
L1 L2
A a
B b
A4
*AB)
*AC)
KS2
A4
* L)
Diagram 48
For external wiring, AWG 22-16 cables with a maximum external diameter of 1.4 mm must be used.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
218 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 3 - Ekip Synchrocheck module
ABB | SACE Emax 2
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
• Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip unit with
the Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip unit):
A
power supply and communication with trip unit present (with a trip unit with the Alive LED
option enabled).
• On, with two quick flashes per second (not synchronized with those of the green LED on
the trip unit): power supply present, and communication with trip unit absent (for example:
because of Local Bus disabled).
LED O SC, green. The possible states are:
• Off: contact K open (with contact normally open, synchronization KO; with contact normally
B closed, synchronization OK) (1).
B A
• On fixed: contact K closed (with contact normally open, synchronization OK; with contact
normally closed, synchronization KO) (1).
(1)
Consult the Settings menu of the module in order to configure the contact.
219 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 3 - Ekip Synchrocheck module
ABB | SACE Emax 2
Access from the display With the module energized, and the Local Bus enabled, the presence of the module itself on the terminal box
activates additional menus on the display:
• To configure the synchronism function.
• To display the measurements related to the function (voltage, frequency, and phase).
• To configure the module.
• To display information on the module and synchronism status.
The presence of the module also activates a graphic summary page with the measurements of the synchronism
function and synchronism state. This page can be accessed from the Main page by touching the sides of the
display until it appears. Further information is available on page 222.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The configuration parameters of the synchronism function are different depending on whether the dead
busbar option is enabled or not.
The following table shows the path from the display to access the configuration parameters of the function,
and the parameters available with dead busbar disabled:
…
UP Protection
Activate
Dead busbar option (Off)
Ulive Threshold
Stability Time
Delta Voltage
Delta Frequency
Advanced
Synchrocheck Delta Phase
Auto Live-dead detect
Auto Deadbar detect
Primary voltage
Secondary voltage
Concatenated Ref
Contact type
Signallings
…
The following table shows the path from the display to access the configuration parameters of the function,
and the parameters available with dead busbar enabled:
…
UP Protection
Activate
Dead busbar option (On)
Udead Threshold
Ulive Threshold
Stability Time
Contact Delay
Advanced
Synchrocheck Dead bar configuration
Auto Live-dead detect
Auto Deadbar detect
Primary voltage
Secondary voltage
Concatenated Ref
Contact type
Signallings
…
NOTE: the module can also be configured through the Ekip Connect software (see the chapter
"17 - Other accessories", and the paragraph "Ekip Connect software" on page 288).
220 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 3 - Ekip Synchrocheck module
ABB | SACE Emax 2
Continued from the previous page
The following table shows the configuration parameters of the synchronism function:
Parameter Values Default Description
• Off = Function disabled.
Activate Off, On Off
• On = Function enabled
• Off = busbar live.
Dead busbar option Off, On Off
• On = busbar dead.
0,02...0,20 Un With a dead bus and "Standard" configuration, 1 st synchronism condition:
Udead Threshold 0.2 Un
steps of 0.001 Un maximum external voltage (2).
Minimum voltage in order to start up monitoring of the voltages (3):
0.5...1.1 Un
Ulive Threshold 0.5 Un • With busbar live, external undervoltage.
steps of 0.001 Un
• With a dead bus and "Standard" configuration, minimum internal voltage (2).
100...30000 ms With live bus, minimum time during which the “Ulive Threshold” condition must
Stability Time 1000 ms
steps of 1 ms be obtained in order to activate voltage monitoring
With busbar dead, and generator:
• Reversed = Ekip Synchrocheck/external contacts connected to the generator
Dead bar configuration Reversed, Standard Standard (1)
.
• Standard = Ekip Synchrocheck/external contacts connected to the network.
0.02...0,12 Un With live busbar, 1 st synchronism condition: maximum difference between
Delta Voltage 0.12 Un
steps of 0.001 Un internal and external voltage (1).
0.1...1.0 Hz With live busbar, 2 nd synchronism condition: maximum difference between
Delta Frequency 0.1 Hz
steps of 0.1 Hz internal and external frequency.
5…50 ° With live busbar, 3 rd synchronism condition: maximum difference between
Delta Phase 50 °
steps of 5 ° internal and external phase.
100 V, 115 V, 120 V,
190 V, 208 V, 220 V,
230 V, 240 V, 277 V,
347 V, 380 V, 400 V,
Primary voltage 400 V Primary voltage of the isolation transformer.
415 V, 440 V, 480 V,
500 V, 550 V, 600 V,
660 V, 690 V, 910 V,
950 V, 1000 V, 1150 V
100 V, 110 V, 115 V,
Secondary voltage 100 V Secondary voltage of the isolation transformer.
120 V
Concatenated Ref V12, V23, V31 V12 Input line-to-line voltage to the module.
Status of the contact:
Contact type NC, NO NO • NC = Normally closed.
• NO = Normally open.
With busbar live, “Delta Frequency” condition:
Frequency check (4) (5)
ON, OFF ON • OFF = Disabled.
• ON = Enabled.
With busbar live, “Delta Phase” condition:
Phase check (4) (5)
ON, OFF ON • OFF = Disabled.
• ON = Enabled.
Circuit-breaker open condition (with live busbar 4 th synchronism condition, With
dead busbar 2 nd synchronism condition):
Evaluate CB status (4) NO, YES NO
• NO = Disabled.
• YES = Enabled.
• Manual = with dead bus, manual selection of the "Standard" or "Reverse"
configuration by means of the "Dead bus configuration" parameter.
Auto Live-dead detect (4) Manual, Automatic Manual • Automatic = with dead bus, automatic selection of the "Standard" or
"Reverse" configuration on the basis of the voltages measured (the "Dead bus
configuration" paremeter is ignored).
• Manual = with dead bus, manual selection of the "Standard" or "Reverse"
configuration by means of the "Dead bus configuration" parameter.
Auto Deadbar detect (4) Manual, Automatic Manual • Automatic = with dead bus, automatic selection of the "Standard" or
"Reverse" configuration on the basis of the voltages measured (the "Dead bus
configuration" paremeter is ignored).
With live bus, minimum time in which the “Phase Delta” condition must be met:
it is not a synchronism function but a parameter allowing a discrimination to be
Minimum matching 100...3000 ms made between correct and incorrect combinations of the “Frequency Delta”
100 ms
time (4) steps of 10 ms and “Phase Delta” conditions. Owing to latencies in the worst case, the time
that effectively elapses before synchronism is recognized may be longer than
the set time (approx. 20 ms).
221 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 3 - Ekip Synchrocheck module
Continued from the previous page ABB | SACE Emax 2
(1)
The precision of measurement of the voltage difference is ± 10%, except with the value of parameter equal
to 0.02 Un, with which the precision is ± 20%.
(2)
With a dead bus and "Reverse" configuration, the roles of the internal and external voltages are reversed.
(3)
On the condition of minimum voltage, a hysteresis of 10 % is applied: once reached, the condition is lost if
the voltage drops below 90 % of the set limit.
(4)
Parameter available only with the Ekip Connect.
(5)
If the Frequency Check is disabled (OFF), the Phase Check is also Off, but not vice versa.
The following table shows the path from the display get the measurements related to the synchronism
function:
…
Harmonic dist.
Measurements
Ekip Synchrocheck
Network Analyzer
…
The page containing a summary of the measurements of the Ekip Synchrocheck module can also be accessed
from the Histograms page. The measurements in this page are:
• Green if the relative synchronism condition has been achieved.
• Red if the relative synchronism condition has not been achieved or the function is disabled.
• White if the measurements are not available.
The measurement summary page can be set as HOME.
The following table shows the measurements related to the synchronism function:
Measurement Description
• Ok = Synchronism conditions met.
Module
• Not Ok = Synchronism conditions not met or synchronism function disabled.
• Ok = Synchronism condition regarding frequencies met.
• Not Ok = Synchronism condition regarding frequencies not met, or synchronism
Frequency function disabled, or frequencies out of the measuring range limits.
• --- = Synchronism condition regarding frequencies not available (example: owing
to operation with dead bus).
• Ok = Synchronism condition regarding voltages met.
Voltage • Not Ok = Synchronism conditions regarding voltages not met or synchronism
function disabled.
• Ok = Synchronism condition regarding phase difference met.
• Not Ok = Synchronism condition regarding phase difference not met, or
Phase synchronism function disabled, or frequencies out of the measuring range limits.
• --- = Synchronism condition regarding phase difference not available (example:
owing to operation with dead bus).
222 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 3 - Ekip Synchrocheck module
Continued from the previous page ABB | SACE Emax 2
Measurement Description
Voltage measured by Ekip Synchrocheck (1). The dots "...." indicate that the
measurement is continuous or less than 1 V, while the dashes "---" indicate that
Ext Side Voltage
the measurement is not available (example: because the synchronism function is
disabled).
Voltage measured by Ekip Measuring (2). The dots "...." indicate that the
Int Side Voltage
measurement is continuous or less than 1 V.
Frequency measured by Ekip Synchrocheck (1). The dots "...." indicate that the
Ext Side Frequency measurement is not available (example: owing to synchronism function disabled, or
operation with dead bus, or frequencies out of the measuring range limits).
Frequency measured by Ekip Measuring (2). The dots "...." indicate that the
Int Side Frequency measurement is not available (example: owing to operation with dead bus, or
frequencies out of the measuring range limits).
Phase difference among voltages (1). The dots "...." indicate that the measurement is
Phase difference not available (example: owing to synchronism function disabled, or operation with
dead bus, or frequencies out of the measuring range limits).
• Live bar = With automatic detection of operating mode, operation with live bus or
synchronism function not enabled.
Auto detection • Dead bar = With automatic detection of operating mode, operation with dead bus.
• --- = Measurement not available (example: owing to manual detection of operation
mode).
• Vint<=Vext = Internal voltage lower than or equal to external voltage.
• Vin>Vext = Internal voltage higher than external voltage.
Voltage relation
• --- = Measurement not available (example: because the synchronism function is
disabled, or voltages less than 1 V or continuous).
• fint<=fext = Internal frequency lower than or equal to external frequency.
• fin>fext = Internal frequency higher than external frequency.
Frequency relation • --- = Measurement not available (example: owing to synchronism function
disabled, or operation with dead bus, or frequencies out of the measuring range
limits).
(2)
For the characteristics of the voltage and frequency (internal) measurements of Ekip Measuring, refer to
those of the Ekip Measuring module (see page 211).
The following table shows the path from the display to view information on the module and synchronism
status:
Protection Unit
Circuit-breaker
About …
Modules Ekip Synchrocheck
…
Power Controller
The information on the modules that can be displayed includes the serial number and the software version.
223 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 3 - Ekip Synchrocheck module
ABB | SACE Emax 2
To switch the state of an input, a short circuit must be created between the input, and a reference available
on the same terminal box. In parallel, the information on the state of the inputs is transmitted by the module
to the trip unit, that can be programmed so that the activation of an input corresponds to an action on the
part of the trip unit.
The closing or the opening of the contacts is commanded by the trip unit, which can be programmed so that
the closing/opening corresponds to the occurrence of a desired event or combination of events.
The signalling LEDs light up in the presence of the short circuit for the inputs, or by closing the contact for
the outputs.
Compatibility and power supply The module can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
requires the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
NOTE: the Ekip Signalling 4K module can be ordered only if the circuit-breaker is not equipped
with AUX 6Q contacts.
Electrical characteristics The following table lists the electrical characteristics of the outputs of the module:
Component Characteristics
• Maximum switching voltage (1): 150 V DC / 250 V AC.
• Breaking capacity (1): 2 A @ 30 V DC, 0.8 A @ 50 V DC, 0.2 A @ 150 V DC, 4A @ 250
Output contacts V AC.
• Dielectric strength between open contacts: 1000 V AC (1 minute @ 50 Hz).
• Dielectric strength between each contact and coil: 1000 V AC (1 minute @ 50 Hz).
(1)
Data relating to a resistive load.
224 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 4 - Ekip Signalling 4K module
ABB | SACE Emax 2
Connections The module must be mounted directly on the Mainboard, to the left of the trip unit. The outputs and inputs of
the module are therefore accessible from the terminal box of the circuit-breaker.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0516.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The wiring diagram for the module is shown below:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 13 23 33 43
HC K7 K8 K9 K10
S51 S33 M YR Trip Unit I/O EKIP Supply TU YU YC
RTC YO2 YO YC2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O
Module Module Module
A4
X K3 K4 K5 K6 H1 H2 H3 H4
XV K3 K4 K5 K6 H1 H2 H3 H4
H1
H2
H3
K6
H4
K3
K5
K4
I 01 I 02 I 03 I 04
Ekip Signalling 4K
A1
K51 O 01 O 02 O 03 O 04
SIGN K10
HC
HC
HC
K9
K7
K8
XV K7 K8 K9 K10 HC HC HC
X K7 K8 K9 K10 HC HC HC
A4
Diagram 2
225 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 4 - Ekip Signalling 4K module
ABB | SACE Emax 2
Access from the display To configure the module the trip unit must be on.
Then, the presence of the module activates the additional menus on the display:
• In order to configure the input and output contacts.
• To display information on the module and the state of inputs and outputs.
The following table shows the path for accessing the configuration parameters of the module from the display:
…
Main frequency
Local/Remote
Local Bus
…
Polarity
I 01
Delay
I 02 (1)
I 03 (1)
I 04 (1)
O 03 (2)
O 04 (2)
…
Functions
Power Controller
…
(1)
As the menu I 01.
(2)
As the menu O 01.
NOTE: the module can also be configured through the Ekip Connect software (see the chapter
"17 - Other accessories", and the paragraph "Ekip Connect software" on page 288).
The following table shows the configuration parameters of the inputs:
Parameter Selectable values Default Description
• Active open = To be considered active,
the input must be floating.
Active
Polarity Active open, Active closed • Active closed = To be considered
closed
active, the input must be connected to its
reference.
Delay time after the input is activated
before the change of state is recognized
(if the input is reset before a time equal to
0.00…100.00 s
Delay 0.1 s the delay has elapsed, the change of state
steps of 0.01 s
is not recognized). If 0.00 s is selected,
the value 300 μs is assigned to the
parameter.
226 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 4 - Ekip Signalling 4K module
Continued from the previous page ABB | SACE Emax 2
The following table shows the configuration parameters of the outputs:
Parameter Selectable values Default Description
• None
• Prealarm L
• Delay L
• Delay S
• Opening L
• Opening S
• Opening G
The event that activates the outputs, so as to make
• Opening I
the contact:
Signal source • Every opening None
• Closed, if set as NO.
• Every delay
• Open, if set as NC.
• Threshold1 I1 (1)
• Threshold2 I1 (1)
• CB Open
• CB Close
• Local Bus Not
Active
• Custom (2)
Standby time after the selected event has occurred,
and before the output is activated (if the event
0.00…100.00 s
Delay 0.00 s disappears before a time equal to the delay elapsed,
steps of 0.01 s
the output is not activated). If 0.00 s is selected, the
value 300 μs is assigned to the parameter.
• NO = Contact normally open.
Contact type (3) NO, NC NO
• NC = Contact normally closed.
• Off = The output is deactivated when the event
disappears.
• On = When the event disappears, the output is
kept active for the minimum time selected.
Self-latching (3) Off, On Off
IMPORTANT: if the output is used for the
Power Controller function, self-latching
must not be enabled.
The "Pulse Mode" value can only be selected if the
output is used for the Power Controller function (see
chapter "23 - Ekip Power Controller", on page 131).
Then the output is maintained active for a fixed time
pertaining to the function itself, regardless of whether
the event that activated it persists or not.
Min activation 0 ms, 100 ms, 200 On the contrary, with self-latching enabled, the
0 ms
time ms, Pulse Mode minimum time in which the output is kept active (once
the selected time has elapsed, the output is kept
active as long as the event that activated it persists).
(1)
For the sources Threshold1 I1 and Threshold2 I1, see the chapter "9 - Touch protections", and the
paragraph "Current thresholds”, on page 69.
(2)
The Custom source is a combination of default events that can be modified using the Ekip Connect software
so as to make the closing/opening of the contact correspond to a wide range of combinations of the status
bits of the trip unit.
(3)
If self-latching is configured as On and the contact Type must be changed (e.g. from NO to NC), after the
parameters have been changed a signaling reset command must be transmitted (by pressing and holding the
iTEST push-button for at least 4 s or by transmitting the Reset signals command from Ekip Connect.
227 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 4 - Ekip Signalling 4K module
Continued from the previous page ABB | SACE Emax 2
The following table shows the path from the display for accessing information on the module:
Protection Unit
Circuit-breaker
About …
Modules Ekip Signalling 4K
…
Power Controller
Information that can be displayed on the module:
• The logical state of the inputs (“Off” if not active, “On” if active).
• The state of the output contacts (“Open” if open, “Closed” if closed).
The following tables illustrate the paths from the display to access the pages for programming the actions you
wish the trip unit to perform in the event of an input being activated.
NOTE: the selection of an action opens a list of the programming parameters, that is, a list
of the events for which the action can be performed, and the related delay. For details on the
parameters, see the chapter “20 - Operating features", and the paragraph "Functional
characteristics" on page 124.
…
Advanced Current thresholds
External Trip
Functions (1)
Trip RESET
(1)
Menus available with the Double Set function disabled (see the chapter "6 - Menu", and the paragraph "
Settings Menu" on page 49.
Set A
Set B
Advanced
External Trip
Functions (1)
Trip RESET
Turn on SET B
(1)
Menus available with the Double Set function enabled (see the chapter "6 - Menu", and the paragraph "
Settings Menu" on page 49.
…
Frequency
Energy counters
Measurements
Energy (1) Reset counters
RESET Energy
Peak factor
…
(1)
Menu available with Ekip Measuring or Ekip Measuring Pro modules.
228 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 4 - Ekip Signalling 4K module
Continued from the previous page ABB | SACE Emax 2
…
Circuit-breaker Ground protection
Installation
Main frequency
…
Modules Switch On LOCAL
Settings Functions
Signalling RESET
Power Controller
…
System
YO Command
Functions
YC Command
Maintenance
The following table describes the programmable actions on the trip unit:
Action Description
Trip RESET Resetting of the trip signal.
Resetting of the energy counters (see the chapter "16 - Ekip Measuring
RESET Energy
Measurements", and the paragraph "Energy counters", on page 113).
Opening of the circuit-breaker (see the chapter "6 - Menu", and the paragraph
External Trip
"Advanced menus", on page 48).
Switching of the connection from remote to local (see the chapter "6 - Menu",
Switch On LOCAL
and the paragraph "Settings Menu", on page 49).
Signalling RESET Resetting of the signals.
Opening coil command (see the chapter "6 - Menu", and the paragraph "
YO Command
Settings Menu", on page 49).
Closing coil command (see the chapter "6 - Menu", and the paragraph "
YC Command
Settings Menu", on page 49).
Switching the protections from configuration A to configuration B (see the
Turn on SET B chapter "11 - Hi-Touch protections", and the paragraph "Set A-B", on page
87).
The following table shows the path for accessing the Test command of the module:
…
Test CB
Test
Ekip Signalling 2K (1)
Ekip Signalling 4K Auto Test
Zone selectivity (68)
(1)
Menu available with module Ekip signalling 2K.
229 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 4 - Ekip Signalling 4K module
ABB | SACE Emax 2
Signallings The following table shows the possible signals, and their meaning:
NOTE: for the references of contacts and inputs, see the paragraph “Connections”, on page
225.
A
Pos. Name Description
Power LED, green. The possible states are:
B A - • Off: power supply absent.
C
• On fixed: power supply present.
D
E LED for signalling the state of contact the K3 - K7, green. The possible states are:
F B O 01 • Off: contact open.
G • On fixed: contact closed.
H LED for signalling the state of contact the K4 - K8, green. The possible states are:
I C O 02 • Off: contact open.
• On fixed: contact closed.
LED for signalling the state of the contact K5 - K9, green. The possible states are:
D O 03 • Off: contact open.
• On fixed: contact closed.
LED for signalling the state of the contact K6 - K10, green. The possible states are:
E O 04 • Off: contact open.
• On fixed: contact closed.
LED for signalling the physical state of the input H1, green (1). The possible states are:
F I 01 • Off: floating input.
• On fixed: input short-circuited on HC.
LED for signalling the physical state of the input H2, green (1). The possible states are:
H I 02 • Off: floating input.
• On fixed: input short-circuited on HC.
LED for signalling the physical state of the input H3, green (1). The possible states are:
G I 03 • Off: floating input.
• On fixed: input short-circuited on HC.
LED for signalling the physical state of the input H4, green (1). The possible states are:
I I 04 • Off: floating input.
• On fixed: input short-circuited on HC.
(1)
The LED turns on and off according to the physical state of the input, without taking any account of how the
Delay parameter is set.
230 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 4 - Ekip Signalling 4K module
ABB | SACE Emax 2
To switch the state of an input, a short circuit must be created between the input and a reference available on
the same connector. In parallel, the information on the state of the inputs is transmitted by the module to the
trip unit, that can be programmed so that the activation of an input corresponds to an action of the trip unit.
The closing or the opening of the contacts is commanded by the trip unit, which can be programmed so that
the closing/opening corresponds to the occurrence of a desired event or combination of events.
The signalling LEDs light up in the presence of the short circuit for the inputs, or by closing the contact for
the outputs.
IMPORTANT: on each circuit-breaker, a maximum of two (for E1.2 circuit-breakers)
or three (for E2.2-E4.2-E6.2 circuit breakers) Ekip Signalling 2K modules can be
installed: one 2K-1, one 2K-2, and one 2K-3 (for E2.2-E4.2-E6.2 circuit breakers only).
These modules differ in name and label, and have distinct wirings, but they are
identical as regards their characteristics and installation.
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
require the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
Electrical characteristics The following table lists the electrical characteristics of the modules:
Component Characteristics
• Maximum switching voltage (1): 150 V DC / 250 V AC.
• Breaking capacity (1): 2 A @ 30 V DC, 0.8 A @ 50 V DC, 0.2 A @ 150 V DC, 4A @
Output contacts 250 V AC.
• Dielectric strength between open contacts: 1000 V AC (1 minute @ 50 Hz).
• Dielectric strength between each contact and coil: 1000 V AC (1 minute @ 50 Hz).
(1)
Data relating to a resistive load.
231 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 5 - Ekip Signalling 2K modules
ABB | SACE Emax 2
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0524.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
41 42 43
A4
K11 K13 H11 H12 HC1 K21 K23 H21 H22 HC2 K31 K33 H31 H32 HC3
I 11 I 12 I 21 I 22 I 31 I 32
Ekip Signalling 2K-1
A4
Diagrams 41 - 42 - 43
For external wiring, AWG 22-16 cables with a maximum external diameter of 1.4 mm must be used.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
232 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 5 - Ekip Signalling 2K modules
ABB | SACE Emax 2
Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display:
With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display.
• In order to configure the input and output contacts.
• To display information on the modules and the state of inputs and outputs.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path for accessing the configuration parameters of the modules from the
display:
…
Main frequency
Local/Remote
Local Bus
…
Signal source
I 01
Delay
I 02 (1)
Signal source
Ekip Signalling Delay
Settings 2K-1 Contact type
Modules O 01
Self-latching
Min activation time
O 02 (2)
(1)
As menu I 01.
(2)
As menu O 01.
(3)
As menu Signalling 2K-1.
NOTE: the modules can also be configured with the Ekip Connect software (see the chapter
“17 - Other accessories", and the paragraph "Ekip Connect software" on page 288).
NOTE: Ekip Signalling 2K-3 module menu available with E2.2-E4.2-E6.2 circuit-breakers.
233 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 5 - Ekip Signalling 2K modules
Continued from the previous page ABB | SACE Emax 2
The following table shows the configuration parameters of the outputs:
Parameter Selectable values Default Description
• None
• Prealarm L
• Delay L
• Delay S
• Opening L
• Opening S
• Opening G
The event that activates the outputs, so as to make
• Opening I
the contact:
Signal source • Every opening None
• Closed, if set as NO.
• Every delay
• Open, if set as NC.
• Threshold1 I1 (1)
• Threshold2 I1 (1)
• CB Open
• CB Close
• Local Bus Not
Active
• Custom (2)
Standby time after the selected event has occurred,
and before the output is activated (if the event
0.00…100.00 s
Delay 0.00 s disappears before a time equal to the delay elapsed,
steps of 0.01 s
the output is not activated). If 0.00 s is selected, the
value 300 μs is assigned to the parameter.
• NO = Contact normally open.
Contact type (3) NO, NC NO
• NC = Contact normally closed.
• Off = The output is deactivated when the event
disappears.
• On = When the event disappears, the output is
kept active for the minimum time selected.
Self-latching (3) Off, On Off
IMPORTANT: if the output is used for the
Power Controller function, self-latching
must not be enabled.
The "Pulse Mode" value can only be selected if the
output is used for the Power Controller function (see
chapter "23 - Ekip Power Controller", on page 131).
Then the output is maintained active for a fixed time
pertaining to the function itself, regardless of whether
the event that activated it persists or not.
Min activation 0 ms, 100 ms, 200 On the contrary, with self-latching enabled, the
0 ms
time ms, Pulse Mode minimum time in which the output is kept active (once
the selected time has elapsed, the output is kept
active as long as the event that activated it persists).
(1)
For the sources Threshold1 I1 and Threshold2 I1, see the chapter "9 - Touch protections", and the
paragraph "Current thresholds”, on page 69.
(2)
The Custom source is a combination of default events that can be modified using the Ekip Connect software
so as to make the closing/opening of the contact correspond to a wide range of combinations of the status
bits of the trip unit.
(3)
If self-latching is configured as On and the contact Type must be changed (e.g. from NO to NC), after the
parameters have been changed a signaling reset command must be transmitted (by pressing and holding the
iTEST push-button for at least 4 s or by transmitting the Reset signals command from Ekip Connect.
234 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 5 - Ekip Signalling 2K modules
Continued from the previous page ABB | SACE Emax 2
The following table shows the configuration parameters of the inputs:
Parame-
Selectable values Default Description
ter
• Active open = To be considered active, the input
Active open, Active Active must be floating.
Polarity
closed closed • Active closed = To be considered active, the input
must be connected to its reference.
Delay time after the input is activated before the
change of state is recognized (if the input is reset
0.00…100.00 s
Delay 0.1 s before a time equal to the delay has elapsed, the
steps of 0.01 s
change of state is not recognized). If 0.00 s is selected,
the value 300 μs is assigned to the parameter.
IMPORTANT: if the trip unit is disconnected for at least 8 s, the outputs are deactivated,
except those programmed to be activated in case of disconnection. Normal operation
is restored at reconnection.
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
…
About Ekip Signalling 2K-1
Modules Ekip Signalling 2K-2
Ekip Signalling 2K-3
…
Power Controller
235 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 5 - Ekip Signalling 2K modules
Continued from the previous page ABB | SACE Emax 2
The following tables illustrate the paths from the display to access the pages for programming the actions you
wish the trip unit to perform in the event of an input being activated.
NOTE: the selection of an action opens a list of the programming parameters, that is, a list
of the events for which the action can be performed, and the related delay. For details on the
parameters, see the chapter “20 - Operating features", and the paragraph "Functional
characteristics" on page 124.
…
Advanced Current thresholds
External Trip
Functions (1)
Trip RESET
(1)
Menus available with the Double Set function disabled (see the chapter "6 - Menu", and the paragraph "
Settings Menu" on page 49.
Set A
Advanced Set B
External Trip
Functions (1) Trip RESET
Turn on SET B
(1)
Menus available with the Double Set function enabled (see the chapter "6 - Menu", and the paragraph "
Settings Menu" on page 49.
…
Frequency
Energy counters
Measurements
Energy (1) Reset counters
RESET Energy
Peak factor
…
(1)
Menu available with Ekip Measuring or Ekip Measuring Pro modules.
…
Circuit-breaker Ground protection
Installation
Main frequency
…
Modules Switch On LOCAL
Settings Functions
Signalling RESET
Power Controller
…
System
YO Command
Functions
YC Command
Maintenance
236 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 5 - Ekip Signalling 2K modules
Continued from the previous page ABB | SACE Emax 2
The following table describes the programmable actions on the trip unit:
Action Description
Trip RESET Resetting of the trip signal.
Resetting of the energy counters (see the chapter "16 - Ekip Measuring
RESET Energy
Measurements", and the paragraph "Energy counters", on page 113).
Opening of the circuit-breaker (see the chapter "6 - Menu", and the
External Trip
paragraph "Advanced menus", on page 48).
Switching of the connection from remote to local (see the chapter "6 -
Switch On LOCAL
Menu", and the paragraph "Settings Menu", on page 49).
Signalling RESET Resetting of the signals.
Opening coil command (see the chapter "6 - Menu", and the paragraph "
YO Command
Settings Menu", on page 49).
Closing coil command (see the chapter "6 - Menu", and the paragraph "
YC Command
Settings Menu", on page 49).
Switching the protections from configuration A to configuration B (see the
Turn on SET B chapter "11 - Hi-Touch protections", and the paragraph "Set A-B", on page
87).
The following table shows the path for accessing the Test command of the module:
…
Test CB
Test
Ekip Signalling 2K Auto Test
Ekip Signalling 4K (1)
(1)
Menu available with module Ekip signalling 4K.
237 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 5 - Ekip Signalling 2K modules
ABB | SACE Emax 2
Signals and inputs/outputs The following table shows all the signals, inputs and outputs of the module:
(1)
The absence of communication is signalled immediately by the power LED, unlike the outputs which (except
for those programmed to be activated in the case of disconnection) are deactivated if the condition persists for
at least 8 s.
(2)
With x = 1, 2, or 3.
(3)
The LED turns on and off according to the physical state of the input, without taking any account of how the
Delay parameter is set.
238 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 5 - Ekip Signalling 2K modules
ABB | SACE Emax 2
Description Ekip Signalling 3T is a signaling accessory which enables the connection of:
• 3 analog inputs for PT1000 temperature sensors (2 wires).
• 1 analog input for 4-20mA current loop.
The measurements supplied by the module can be associated with different control threshold, useful for
configuring alarm signals, states and programmable commands.
The module can be installed on all Emax 2 circuit-breakers in the presence of trip units Ekip Touch, Hi-Touch,
G Touch, G Hi-Touch (of the equivalent Ekip LCD models) with firmware version 2.23 or higher.
Models Emax 2 can be configured with 2 different 3T modules: Ekip Signalling 3T-1 and Ekip Signalling 3T-2.
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE: if different indications are not given, the information in the next chapter is valid for
both models.
The two modules can be installed at the same time on the same circuit-breaker so as to extend the
opportunities for measuring and monitoring the installation.
IMPORTANT: each circuit-breaker can only be fitted with one module per type. The
configuration with two modules of the same model is not allowed (example: two Ekip
Signalling 3T-1 modules).
(1)
Accuracy values refer to 3T module without sensors. For complete accuracy, consider the characteristics of
the sensors and cabling used.
(2)
Accuracy valid in -25 to 250°C range; in complete range it is: ± 0.5°C.
(3)
The measurement is expressed as a percentage, where: 0% = 4 mA and 100% = 20 mA.
(4)
Accuracy values refer to full scale: 0.5% = 0.1 mA.
Power supply Ekip Signalling 3T is supplied directly by the Ekip Supply module to which it is connected.
• no auxiliary supply
• withdrawable circuit-breaker momentarily in withdrawn position.
communication between trip unit and module is interrupted and the information supplied
(state and measurement of the inputs) is not valid.
239 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 6 - Ekip Signalling 3T modules
ABB | SACE Emax 2
Connections - Module The module must be installed on the terminal box of the circuit-breaker (in the fixed version), or on the fixed
part (in the withdrawable version), in the first slot after the Ekip Supply module.
Further details about assembly of module 3T on Emax 2 circuit-breakers are available at http://www.abb.
com/abblibrary/DownloadCenter/, especially in the kit sheet 1SDH001000R0527.
There are two examples alongside, with circuit-breaker E2.2 in the fixed and withdrawable versions.
Connection of each input (H41, H42, H43, H44 for model 3T-1, H51, H52, H53, H54 for model 3T-2) must
be performed with reference to the respective common contacts (HC), as indicated in the circuit diagram:
44 45
A4
*AD) *AD) *AD) *AE) *AD) *AD) *AD) *AE)
H44 HC6 H43 HC5 H42 HC4 H41 H54 HC9 H53 HC8 H52 HC7 H51
I 44 I 43 I 42 I 41 I 54 I 53 I 52 I 51
A4
Diagrams 44 - 45
Connections - Inputs For PT1000 sensors, use insulated cables for thermistors such as PENTRONIC TEC/SITW-24F (Type TX) or
similar. Maximum length 3 meters
For the 4-20mA Current Loop sensor, use suitable cables up to 3 meters in length compatible with the
workplace in which the 4-20mA current sensor is used.
IMPORTANT: the inputs are not insulated: regardless of plant voltage, the customer
must ensure there is insulation between each input and between the inputs and
power supply of the Ekip Supply module on the basis of the customer's own application
and network. For applications in low voltage installations ABB suggests use of the
dedicated isolated external sensor PT1000, which can be ordered by code
1SDA085695R1, is equippped with a nut and screw for use on busbars and is compatible
with the dielectric withstand and insulation levels established by standard IEC 60947-
2 (Ui= 1000 V, Uimp= 12 kV).
240 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 6 - Ekip Signalling 3T modules
ABB | SACE Emax 2
LEDs Description
Signals the on state and correct communication with the trip unit:
• Off: module off.
• On steady or flashing synchronized with the trip unit Power led: module on and
Power
communication with trip unit present.
• Flashing not synchronized with trip unit Power led (2 fast flashes per second): module on
and communication with trip unit absent.
Indicate the state of the input contacts:
I 41, I 42, • Off: input disabled.
I 43, I 44 • On steady: input enabled, sensor connected and measurement valid.
• Flashing: input enabled, sensor not connected and measurement not valid.
Access from the display Local bus activation, which is essential for starting the communication between module and trip unit, is
available in the Settings Menuon page 49.
The following areas are activated on the trip unit if the Ekip Signalling 3T is detected correctly:
• Measurements page, accessible from the Home page by pressing at the sides of the display, containing
the measurements of all the PT1000 and Current Loop 4-20mA inputs of both modules 3T-1 and 3T-2.
• Information submenus in the Information-Modules menu containing: serial number, module version and
state of sensors (Present/Alarm).
IMPORTANT:
• If one or more sensors are in the alarm state, the signal on the diagnosis bar will be: Ekip
Signalling 3T.
• If a sensor is not enabled, the state indicated is: Present
Enabling and measurements The individual inputs of the module: PT1000 1, PT1000 2, PT1000 3 and Current Loop 4-20mA can be
enabled in the Ekip Signalling 3T page.
Parameter Description Default
Enables the specific input and relative alarm state and signaling controls
Enable Enabled
to be activated
The state alarms and the measurement detected for each input are also available in the page.
241 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 6 - Ekip Signalling 3T modules
ABB | SACE Emax 2
Alarm signals In the Protection parameters - Other parameters A (and B, if dual set is activated) page, up to three alarm
thresholds, independent of each other: THR 1, THR2, TH3, can be activated and configured for each input.
Each alarm threshold has the following configuration parameters:
NOTE: the table lists the parameters of threshold 1 of input PT1000 1; the names and
references of all the other thresholds and inputs change.
States and alarms The state of all control thresholds can be checked in the Warnings/Alarms page.
242 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 6 - Ekip Signalling 3T modules
ABB | SACE Emax 2
Description Ekip Com Modbus RTU is a communication accessory module which integrates the circuit-breaker into a
remote industrial supervision and monitoring network in two different modes, master and slave.
It can be connected to a RS-485 network with a Modbus RTU communication protocol, and allows you to:
• Connect the trip units to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker from remote.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If mounted on a circuit-breaker in withdrawable version, detect the connected/disconnected position.
For more details about how to access information and transmit commands to the trip unit via the module,
consult chapter "System Interface" on page 155.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker is equipped
with an Ekip Com Actuator module (see page 286).
For applications in which a high network reliability is necessary, the module can be installed along with the
corresponding Redundant module.
The Redundant module is identical in terms of characteristics and installation, but its wiring is different from
the non-Redundant model.
IMPORTANT: on each circuit-breaker, only one Ekip Com Modbus RTU, and only one
Ekip Com Modbus RTU Redundant can be installed.
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
require the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
Termination resistor A 120 Ω termination resistance can be linked to bus RS-485, thereby configuring the dip-switches Rterm
located on the side of the modules in the on position. In the case of bus termination, a 220 Ω pull-up or
pull-down resistor must also be installed on the lines by setting dip-switches Rpoll to the on position. These
options must be selected before the installation of the modules.
Consult the next figure for the on and off positions of the dip-switches.
ON
1 2 3 4
Figure 118
243 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 7 - Ekip Com Modbus RTU modules
ABB | SACE Emax 2
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0512.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
51 61
A4
*O)
S75I/5
193
194
XK7 1 XK7 2
A3
Modbus RTU
K51 K51
COM COM
W1 W2 W1R W2R
A4
*S) *S)
* L) * L)
Diagrams 51 - 61
For the communication lines (A) and (B), Belden type 3105A or equivalent cables must be used.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
244 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 7 - Ekip Com Modbus RTU modules
ABB | SACE Emax 2
Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path for accessing the configuration parameters of the modules from the
display:
…
Main frequency
Local/Remote
Local Bus
…
Serial address
Settings Baudrate
Modules Ekip Com Modbus RTU
Physical
protocol
Ekip Com Modbus RTU *R (1)
…
Functions
Power Controller
…
(1)
As Ekip Com Modbus RTU.
NOTE: the modules can also be configured with the Ekip Connect software (see the chapter
“17 - Other accessories", and the paragraph "Ekip Connect software" on page 288).
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
…
About
Ekip Com Modbus RTU
Modules
Ekip Com Modbus RTU *R
…
Power Controller
The information on the modules that can be displayed includes the serial number and the software version.
245 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 7 - Ekip Com Modbus RTU modules
ABB | SACE Emax 2
Remote configurations The operating configuration can be changed from slave to master via the service connector (via Ekip Connect)
or via a system bus communication as as to integrate the module into an interactive data exchange network
(see description of Ekip Com Hub).
IMPORTANT:
• In the Master configuration, the module does not allow data exchange as in the normal
Slave function.
• The presence of several masters in the same network can cause faulty operation.
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
• Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip unit with the
Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip unit):
A
power supply and communication with trip unit present (with a trip unit with the Alive LED
option enabled).
• On, with two quick flashes per second (not synchronized with those of the green LED on the
trip unit): power supply present, and communication with trip unit absent (for example: because
of Local Bus disabled).
RX and TX LEDs, green. The possible states are:
B • Off: Modbus RTU communication not active.
B
A • On, flashing rapidly: Modbus RTU communication active.
246 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 7 - Ekip Com Modbus RTU modules
ABB | SACE Emax 2
Description The Ekip Com Profibus DB is a communication accessory module that integrates the circuit-breaker in an
industrial remote supervision and control network.
It can be connected to a RS-485 network with a Profibus communication protocol, and allows of:
• Connect the trip units as slaves to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker from remote.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If mounted on a circuit-breaker in withdrawable version, detect the connected/disconnected position.
For more details about how to access information and transmit commands to the trip unit via the module,
consult chapter "System Interface" on page 155.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker is equipped
with an Ekip Com Actuator module (see page 286).
For applications in which a high network reliability is necessary, the module can be installed along with the
corresponding Redundant module.
The Redundant module is identical in terms of characteristics and installation, but its wiring is different from
the non-Redundant model.
IMPORTANT: on each circuit-breaker, only one Ekip Com Profibus DP, and only one
Ekip Com Profibus DP Redundant can be installed.
IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unit
is disconnected from the module: in this condition, the only valid information
transmitted is:
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
require the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
247 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 8 - Ekip Com Profibus DP modules
ABB | SACE Emax 2
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0512.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
53 63
A4
O)
*
S75I/5
193
194
XK7 1 XK7 2
A3
Profibus DP
K51 K51
COM COM
W5 W6 W5R W6R
A4
U) U)
* *
(data+) B A (data-) (data+) B A (data-)
BUS 1 BUS 2
*L) *L)
Diagrams 53 - 63
For the communication lines (A) and (B), Belden type 3079A or equivalent cables must be used.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
248 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 8 - Ekip Com Profibus DP modules
ABB | SACE Emax 2
Termination resistors The modules provide the possibility to insert a 220 Ω termination resistor on the RS-485 bus, by setting the
dip-switches Rterm on the side of the modules, in position on.
In the event of termination of the bus, a 390 Ω pull-up or pull-down resistor must also be inserted on the lines,
by setting the dip-switches Rpoll, in position on.
These options must be selected before the installation of the modules.
For the positions on and off of the dip-switches, see the following figure.
ON
1 2 3 4
Figure 119
Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path for accessing the configuration parameters of the modules from the
display:
…
Main frequency
Local/Remote
Local Bus
…
Settings
Modules Ekip Com Profibus DP Serial address
Ekip Com Profibus DP *R Serial address
…
Functions
Power Controller
…
NOTE: the modules can also be configured with the Ekip Connect software (see the chapter
“17 - Other accessories", and the paragraph "Ekip Connect software" on page 288).
The default serial address is 125 for Ekip Com Profibus DP, and 124 for Ekip Com Profibus DP Redundant,
and can be changed to a value between 1 and 125.
IMPORTANT: devices connected to the same network must have different addresses.
249 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 8 - Ekip Com Profibus DP modules
Continued from the previous page ABB | SACE Emax 2
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
…
About
Ekip Com Profibus DP
Modules
Ekip Com Profibus DP *R
…
Power Controller
The information on the modules that can be displayed includes the serial number and the software version.
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
• Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip unit with
the Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip unit):
A
power supply and communication with trip unit present (with a trip unit with the Alive LED
option enabled).
• On, with two quick flashes per second (not synchronized with those of the green LED on
the trip unit): power supply present, and communication with trip unit absent (for example:
because of Local Bus disabled).
RX LED, green. The possible states are:
B • Off: communication between master and trip unit not active.
B C • On fixed: communication between master and trip unit active.
A
TX LED, green. The possible states are:
C • Off: communication between master and trip unit not active.
• On flashing: communication between master and trip unit active.
250 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 8 - Ekip Com Profibus DP modules
ABB | SACE Emax 2
Description The Ekip Com DeviceNet™ is a communication accessory module that integrates the circuit-breaker in an
industrial remote supervision and control network.
It can be connected to a CAN network with a DeviceNet™ communication protocol, and allows you to:
• Connect the trip units as slaves to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker from remote.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If mounted on a circuit-breaker in withdrawable version, detect the connected/disconnected position.
For more details about how to access information and transmit commands to the trip unit via the module,
consult chapter "System Interface" on page 155.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker is equipped
with an Ekip Com Actuator module (see page 286).
For applications in which a high network reliability is necessary, the module can be installed along with the
corresponding Redundant module.
The Redundant module is identical in terms of characteristics and installation, but its wiring is different from
the non-Redundant model.
IMPORTANT: on each circuit-breaker, only one Ekip Com DeviceNet™, and only one
Ekip Com Redundant DeviceNet™ can be installed.
IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unit
is disconnected from the module: in this condition, the only valid information
transmitted is:
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
require the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
251 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 9 - Ekip Com DeviceNet modules™
ABB | SACE Emax 2
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0512.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
55 65
A4
* O)
S75I/5
193
194
XK7 1 XK7 2
TM
DeviceNet TM
K51 K51
COM COM
V+ W7 W8 V- V+ W7R W8R V-
A4 * V) *V)
V+ (H) (L) V- V+ (H) (L) V-
BUS 1 BUS 2
* L) * L)
Diagrams 55 - 65
For the communication buses BUS1 and BUS2, Belden type 3084A or equivalent cables must be used.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
252 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 9 - Ekip Com DeviceNet modules™
ABB | SACE Emax 2
Termination resistor The modules provide the possibility to insert a 120 Ω termination resistor on the CAN bus, by setting the dip-
switches Rterm on the side of the modules, in position on. This option must be selected before the modules
are installed.
For the positions on and off of the dip-switches Rterm, see the following figure (on DeviceNet™
communication modules, the remaining dip-switches are not used).
IMPORTANT:
• The termination resistors must never be included in the nodes. The inclusion of this
capability could easily lead to a network with improper termination (impedance too
high or too low), potentially causing a failure. For example, the removal of a node,
which includes a termination resistor, could result in a network failure.
• The termination resistors must not be installed at the end of a branch (drop line), but
only at the two ends of the main backbone (trunk line).
ON
1 2 3 4
Figure 120
Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display.
To enable the Local Bus, you need to select "On" in the menu Settings, Modules, Local Bus.
The following table shows the path for accessing the configuration parameters of the modules from the
display:
…
Main frequency
Local/Remote
Local Bus
…
Settings MAC Address
Modules Ekip Com DeviceNet™
Baudrate
MAC Address
Ekip Com DeviceNet™*R
Baudrate
…
Functions
Power Controller
…
253 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 9 - Ekip Com DeviceNet modules™
Continued from the previous page ABB | SACE Emax 2
The following table shows the configuration parameters of the modules:
Parameter Values Default Description
Address to be assigned to the modules.
• Ekip Com DeviceNet™: 65
MAC
1…63 • Ekip Com Redundant IMPORTANT: devices connected
Address
DeviceNet™: 64 to the same network must have
different addresses.
125 kbit/s, 250
Baudrate 125 kbit/s Data transmission speed
kbit/s, 500 kbit/s
NOTE: the modules can also be configured with the Ekip Connect software (see the chapter
“17 - Other accessories", and the paragraph "Ekip Connect software" on page 288).
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
…
About
Ekip DeviceNet™
Modules
Ekip DeviceNet™ *R
…
Power Controller
The information on the modules that can be displayed includes the serial number and the software version.
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Class ID Defines the addressing class of the module, either 8 or 16 bits. 8-bit Class ID
Defines the behavior of the module following loss of
communication (Bus-Off), with a choice between Standard (supply DeviceNet
Bus-Off behavior
reset is awaited if the communication is lost) and Advanced (the standard
module attempts to reset and detects the error state).
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
• Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip unit with
the Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip unit):
A
power supply and communication with trip unit present (with a trip unit with the Alive LED
option enabled).
• On, with two quick flashes per second (not synchronized with those of the green LED on
the trip unit): power supply present, and communication with trip unit absent (for example:
because of Local Bus disabled).
LED, green. The possible states are:
• Off: device off line (with red LED off) (1), or in error conditions (with red LED on).
B
B C A • On fixed: device on line, and allocated on a master (operating condition).
• On flashing: device on line, but not allocated on a master (device ready for communication).
LED, red. The possible states are:
• Off: no error.
C
• On fixed: device in bus off, or Network Power absent.
• On flashing: I/O connection (cyclic data) in timeout.
(1)
The device has not yet sent Duplicate ID sequence on line.
254 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 9 - Ekip Com DeviceNet modules™
ABB | SACE Emax 2
Description Ekip Com Modbus TCP is an accessory module that can function as a communication module integrating the
circuit-breaker in an industrial remote supervision and control network or as an HTTP Server.
As communication module, it can be connected to an Ethernet network with Modbus TCP communication,
and allows to:
• Connect the trip units to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker from remote.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If mounted on a circuit-breaker in withdrawable version, detect the connected/disconnected position.
For more details about how to access information and transmit commands to the trip unit via the module,
consult chapter "System Interface" on page 155.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker is equipped
with an Ekip Com Actuator module (see page 286).
As HTTP Server, connected to an Ethernet network, this module allows read-only access to the information
of the trip unit. This access is possible through a browser, inserting the IP address of the module. Once the
trip unit has been found, a login page is opened that asks for the user password to be inserted, which is the
same password to be inserted in the display to modify the parameters.
For applications in which a high network reliability is necessary, the module can be installed along with the
corresponding Redundant module.
The Redundant module is identical in terms of characteristics and installation, but its wiring is different from
the non-Redundant model.
IMPORTANT: on each circuit-breaker, only one Ekip Com Modbus TCP, and only one
Ekip Com Modbus TCP Redundant can be installed.
IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unit
is disconnected from the module: in this condition, the only valid information
transmitted is:
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
255 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 10 - Ekip Com Modbus TCP modules
ABB | SACE Emax 2
Safety and cyber security Since the module allows the circuit-breaker and access to the data in the trip unit to be checked, it can
only be connected to networks equipped with all the necessary safety and prevention measures against
unauthorized access (for example, the network of the control system of an installation).
IMPORTANT:
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
require the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
256 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 10 - Ekip Com Modbus TCP modules
ABB | SACE Emax 2
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0514.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2/E4.2/E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
52 62
A4
O)
*
S75I/5
193
194
XK7 1 XK7 2
A3
Modbus TCP
K51 K51
COM COM
RJ45
RJ45
W9
W9R
n n
A4
R) R)
* *
BUS 1 BUS 2
* L) * L)
Diagrams 52 - 62
For the communication bus, a cable of type Cat.6 S/FTP must be used (Cat.6 with S/FTP double shielding).
If the circuit-breaker is in withdrawable version, the use of cables fitted with a RJ45 socket with output at 90°
is recommended.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
257 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 10 - Ekip Com Modbus TCP modules
ABB | SACE Emax 2
Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display:
• For setting the function and addressing of the modules.
• In order to display information on the modules.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path from the display, for setting the function and addressing of the modules:
…
Main
frequency
Local/Remote
Local Bus
…
Function
Settings Force Static IP address
Modules Ekip Com Modbus TCP Static IP Address
Static Network Mask
Static Gateway addr
Ekip Com Modbus TCP *R (1)
…
Functions
Power
Controller
…
(1)
As Ekip Com Modbus TCP menu.
The following table shows the parameters for setting the function and the addressing of the modules. For
further information, see the table on page 259.
Selectable
Parameter Default Description
values
• HTTP Server = HTTP Server operating mode.
HTTP Server,
Function Modbus TCP • Modbus TCP = Communication module operating
Modbus TCP
mode.
Force Static IP • Off = Dynamic IP address.
Off, On Off
address • On = Static IP address.
Static IP Displayed with static IP Address enabled, it must be selected in order to insert the IP
Address Address of the modules.
Static Network Displayed with static IP Address enabled, it must be selected in order to insert the subnet
Mask mask of the modules.
Displayed with static IP Address enabled, it must be selected in the presence of
Static Gateway
multiple subnets, in order to insert the IP Address of the node to which the modules are
addr
connected.
258 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 10 - Ekip Com Modbus TCP modules
Continued from the previous page ABB | SACE Emax 2
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
…
About
Ekip Com Modbus TCP
Modules
Ekip Com Modbus TCP *R
…
Power Controller
(1)
Organizationally Unique Identifier, formed by the first three bytes of a MAC address, and which uniquely
identifies the manufacturer of an Ethernet device.
259 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 10 - Ekip Com Modbus TCP modules
ABB | SACE Emax 2
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive
data exchange network (see chapter "15 - Ekip Com Hub modules"
Client/Server on page 282). Server only
(1)
Enable IEEE 1558 and Enable SNTP client must not be enabled at the same time.
(2)
The parameter can only be changed by system bus in the remote configuration.
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW version General module information
Flash CRC status e result Information about the correctness of the SW in the module
Stato Ekip Link Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronisation State of synchronism with SNTP server
Valid with Master IEEE 1588 = ON, notifies the presence (Slave or PTP
IEEE 1558 status Master Active) or absence (PTP Master but Passive) of the higher level
master
260 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 10 - Ekip Com Modbus TCP modules
ABB | SACE Emax 2
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
C B • Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip unit with the
Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip unit):
A
power supply and communication with trip unit present (with a trip unit with the Alive LED
option enabled).
• On, with two quick flashes per second (not synchronized with those of the green LED on the
trip unit): power supply present, and communication with trip unit absent (for example: because
of Local Bus disabled).
Link LED, green. The possible states are:
B • Off: connection error (signal absent).
• On fixed: correct connection.
A
Activity LED, yellow. The possible states are:
C • Off: no activity on the line.
• On flashing: activity on the line (in reception and/or transmission).
261 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 10 - Ekip Com Modbus TCP modules
ABB | SACE Emax 2
Description The Ekip Com Profinet is a communication accessory module, that integrates the circuit-breaker in an
industrial remote supervision and control network.
It can be connected to an Ethernet network with a Profinet communication protocol, and allows you to:
• Connect the trip units to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker from remote.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If mounted on a circuit-breaker in withdrawable version, detect the connected/disconnected position.
For more details about how to access information and transmit commands to the trip unit via the module,
consult chapter "System Interface" on page 155.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker is equipped
with an Ekip Com Actuator module (see page 286).
The following table shows the ports used by the module:
Ethertype Port Service Notes
0x88CC. - LLDP Link Layer Discovery Protocol
Specific for real time
0x8892 (Profinet). - Profinet IO
communications (RT)
0x0800. 34964/udp Profinet-cm (Context Manager) DCE/RPC
For applications in which a high network reliability is necessary, the module can be installed along with the
corresponding Redundant module.
The Redundant module is identical in terms of characteristics and installation, but its wiring is different from
the non-Redundant model.
IMPORTANT: on each circuit-breaker, only one Ekip Com Profinet, and only one Ekip
Com Profinet Redundant can be installed.
IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unit
is disconnected from the module: in this condition, the only valid information
transmitted is:
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
Safety and cyber security Since the module allows the circuit-breaker and access to the data in the trip unit to be checked, it can
only be connected to networks equipped with all the necessary safety and prevention measures against
unauthorized access (for example, the network of the control system of an installation).
IMPORTANT:
262 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 11 - Ekip Com Profinet modules
ABB | SACE Emax 2
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
require the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0514.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
54 64
A4
O)
*
S75I/5
193
194
XK7 1 XK7 2
K51 K51
Profinet
COM COM
RJ45
RJ45
W10
W10R
n n
A4 R) R)
* *
BUS 1 BUS 2
* L) * L)
Diagrams 54 - 64
For the communication bus, a cable of type Cat.6 S/FTP must be used (Cat.6 with S/FTP double shielding).
If the circuit-breaker is in withdrawable version, the use of cables fitted with a RJ45 socket with output at 90°
is recommended.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
263 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 11 - Ekip Com Profinet modules
ABB | SACE Emax 2
Access from the display With the modules energized and Local Bus enabled, the modules can be viewed on the display.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
…
About
Ekip Com Profinet
Modules
Ekip Com Profinet *R
…
Power Controller
Information that can be displayed on the modules:
• The serial number and the software version.
• The MAC address, assigned by ABB and with an OUI equal to ac:d3:64 (Organizationally Unique Identifier,
formed of the first three bytes of a MAC address; the OUI uniquely identifies the manufacturer of an
Ethernet device).
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
C B • Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip unit with
the Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip unit):
A
power supply and communication with trip unit present (with a trip unit with the Alive LED
option enabled).
• On, with two quick flashes per second (not synchronized with those of the green LED on
the trip unit): power supply present, and communication with trip unit absent (for example:
because of Local Bus disabled).
Link LED, green. The possible states are:
B • Off: connection error (signal absent).
• On fixed: correct connection.
A
Activity LED, yellow. The possible states are:
C • Off: no activity on the line.
• On flashing: activity on the line (in reception and/or transmission).
264 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 11 - Ekip Com Profinet modules
ABB | SACE Emax 2
Description Ekip Com EtherNet/IP™ is an accessory module that can act as a communication module integrating the
circuit-breaker in an industrial remote supervision and control network.
It can be connected to an Ethernet network with EtherNet/IP™ communication protocol, and allows you to:
• Connect the trip units to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker from remote.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If mounted on a circuit-breaker in withdrawable version, detect the connected/disconnected position.
For more details about how to access information and transmit commands to the trip unit via the module,
consult chapter "System Interface" on page 155.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker is equipped
with an Ekip Com Actuator module (see page 286).
The following table shows the ports used by the module:
Port Protocol Notes
Encapsulation Protocol (example: ListIdentity, UCMM, CIP
44818 TCP
Transport Class 3)
44818 UDP Encapsulation Protocol (example: ListIdentity)
2222 UDP CIP Transport Class 0 or 1
DHCP Client enabled as an alternative to “Static Address =
68/udp DHCP Client
On”
For applications in which a high network reliability is necessary, the module can be installed along with the
corresponding Redundant module.
The Redundant module is identical in terms of characteristics and installation, but its wiring is different from
the non-Redundant model.
IMPORTANT: on each circuit-breaker, only one Ekip Com EtherNet/IP™, and only one
Ekip Com Redundant EtherNet/IP™ can be installed.
IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unit
is disconnected from the module: in this condition, the only valid information
transmitted is:
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
Safety and cyber security Since the module allows the circuit-breaker and access to the data in the trip unit to be checked, it can
only be connected to networks equipped with all the necessary safety and prevention measures against
unauthorized access (for example, the network of the control system of an installation).
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between Ekip ComEtherNet/IP™ and customer network or any other
network (as the case may be). The plant manager must establish and maintain
appropriate measures (such as but not limited to the installation of firewalls, application
of authentication measures, encryption of data, installation of antivirus programs, etc.)
to protect the product, the network, the customer system and interface against any
kind of security breaches, unauthorized access, interference, intrusion, loss and/or
theft of data or information. ABB and its affiliates are not liable for damages and/
or losses related to such security breaches, unauthorized accesses, interference,
intrusion, loss and/or theft of data or information.
• The module cannot be connected directly to the Internet. Only connect to dedicated
Ethernet networks with EtherNet/IP™ communication protocol.
265 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 12 - Ekip Com EtherNet/IP™ modules
ABB | SACE Emax 2
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
require the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0514.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
56 66
A4
O)
*
S75I/5
193
194
XK7 1 XK7 2
TM
Ekip Com EtherNet IP
K51 K51
COM COM
RJ45
RJ45
W11 W11R
n n
A4
R) R)
* *
BUS 1 BUS 2
*L ) *L)
Diagrams 56 - 66
For the communication bus, a cable of type Cat.6 S/FTP must be used (Cat.6 with S/FTP double shielding).
If the circuit-breaker is in withdrawable version, the use of cables fitted with a RJ45 socket with output at 90°
is recommended.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
266 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 12 - Ekip Com EtherNet/IP™ modules
ABB | SACE Emax 2
Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display:
• To set the addressing of the modules.
• In order to display information on the modules.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path from the display, for setting the function and addressing of the modules:
…
Main frequency
Local/Remote
Local Bus
…
Force Static IP address
Settings Static IP Address
Modules Ekip Com EtherNet/IP™
Static Network Mask
Static Gateway addr
Ekip Com EtherNet/IP™ *R (1)
…
Functions
Power Controller
…
(1)
As Ekip Com EtherNet/IP™.
The following table shows the parameters for setting the function and the addressing of the modules. For
further information, see the table on page 259.
Parameter Selectable values Default Description
Force Static IP • Off = Dynamic IP address.
Off, On Off
address • On = Static IP address.
Displayed with static IP Address enabled, it must be selected in order to insert the IP
Static IP Address
Address of the modules.
Static Network Displayed with static IP Address enabled, it must be selected in order to insert the
Mask subnet mask of the modules.
Displayed with static IP Address enabled, it must be selected in the presence of
Static Gateway
multiple subnets, in order to insert the IP Address of the node to which the modules
addr
are connected.
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
…
About
Ekip Com EtherNet/IP™
Modules
Ekip Com EtherNet/IP™ *R
…
Power Controller
267 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 12 - Ekip Com EtherNet/IP™ modules
Continued from the previous page ABB | SACE Emax 2
(1)
Organizationally Unique Identifier, formed by the first three bytes of a MAC address, and which uniquely
identifies the manufacturer of an Ethernet device.
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Enables the IEEE 1588 protocol for distribution of the clock and
IEEE 1558 enable OFF
synchronization signal to be enabled (1).
Enables the module to be set up as a master in the the network
Master IEEE 1588 OFF
segment to which it belongs (synchronization clock).
IEEE 1588 delay Enables the data exchange mode between module and master,
End-to-End
mechanism between Peer-to-Peer and End-to-End to be selected.
Enables the SNTP protocol for distribution of the clock and
SNTP Client enable OFF
synchronization signal to be enabled (1).
Force Static IP Address Enables the network server that supplies the SNTP to be set. 0.0.0.0
Time zone Defines the time zone to be used for synchronism. +00:00
Used to select whether daylight saving time is present (ON) or not
Daylight Saving Time OFF
(OFF) in the country to which the synchronization time refers.
(1)
Enable IEEE 1558 and Enable SNTP client must not be enabled at the same time.
268 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 12 - Ekip Com EtherNet/IP™ modules
ABB | SACE Emax 2
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW
general module information
version
Flash CRC status e
Information about the correctness of the SW in the module
result
Stato Ekip Link Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server
State of synchronism with SNTP server
Synchronisation
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP Master Active)
IEEE 1558 status
or absence (PTP Master but Passive) of the higher level master
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
C B • Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip
unit with the Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip
A
unit): power supply and communication with trip unit present (with a trip unit with the
Alive LED option enabled).
• On, with two quick flashes per second (not synchronized with those of the green
LED on the trip unit): power supply present, and communication with trip unit absent
(for example: because of Local Bus disabled).
Link LED, green. The possible states are:
B • Off: connection error (signal absent).
• On fixed: correct connection.
A
Activity LED, yellow. The possible states are:
C • Off: no activity on the line.
• On flashing: activity on the line (in reception and/or transmission).
269 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 12 - Ekip Com EtherNet/IP™ modules
ABB | SACE Emax 2
Description Ekip Com IEC 61850 is an accessory module that can function as a communication module by integrating
the circuit-breaker in an industrial remote supervision and control network.
It can be connected to an Ethernet network with an IEC 61850 communication protocol, and allows you to:
• Connect the trip units to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker from remote.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If mounted on a circuit-breaker in withdrawable version, detect the connected/disconnected position.
• Provide vertical communication (report) towards higher-level supervision systems (SCADA) with states and
measurements (re-transmitted whenever, and only if, they change with respect to the previous report).
• Provide horizontal communication (GOOSE output) towards other circuit-breakers (non-Emax 2, e.g.
medium voltage circuit-breakers), with all the information about state and measurements normally shared
by Emax 2 communication modules on busbars.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker is equipped
with an Ekip Com Actuator module (see page 286).
The configuration for the IEC 61850 protocol to assign the Technical Name, and, where necessary, to enable
the GOOSE (by setting the corresponding MAC addresses), is carried out by loading a configuration file in
the module. For further information, see the chapter "System Interface" on page 155, and in particular the
document 1SDH001140R0001 referenced in the chapter
The following table shows the ports used by the module:
Ethertype Port Protocol
0x0800 - IP. 102 ISO Transport Service on top of the TCP (RFC 1006)
0x88B8. - GOOSE Messages
0x0800 - IP. 123 UDP NTP - Network Time Protocol
0x0800 - IP. 69 UDP TFTP - Trivial File Transfer Protocol
For applications in which a high network reliability is necessary, the module can be installed along with the
corresponding Redundant module.
The Redundant module is identical in terms of characteristics and installation, but its wiring is different from
the non-Redundant model.
IMPORTANT: on each circuit-breaker, only one Ekip Com IEC 61850, and only one
Ekip Com IEC 61850 Redundant can be installed.
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
Safety and cyber security Since the module allows the circuit-breaker and access to the data in the trip unit to be checked, it can
only be connected to networks equipped with all the necessary safety and prevention measures against
unauthorized access (for example, the network of the control system of an installation).
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between Ekip Com IEC 61850 and customer network or any other network
(as the case may be). The plant manager must establish and maintain appropriate
measures (such as but not limited to the installation of firewalls, application of
authentication measures, encryption of data, installation of antivirus programs, etc.) to
protect the product, the network, the customer system and interface against any kind
of security breaches, unauthorized access, interference, intrusion, loss and/or theft
of data or information. ABB and its affiliates are not liable for damages and/or losses
related to such security breaches, unauthorized accesses, interference, intrusion, loss
and/or theft of data or information.
• The module cannot be connected directly to the Internet. Only connect to dedicated
Ethernet networks with IEC 61850 communication protocol.
270 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 13 - Ekip Com IEC 61850 modules
ABB | SACE Emax 2
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip unit since
version 2.0 software, and require the presence of an Ekip Supply module in the first slot of the circuit-breaker
terminal box.
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0514.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
57 67
A4
O)
*
S75I/5
193
194
XK7 1 XK7 2
K51
Ekip Com
K51
COM COM
RJ45
RJ45
W12 W12R
n n
A4
R) R)
* *
BUS 1 BUS 2
*L ) L)
Diagrams 57 - 67
For the communication bus, a cable of type Cat.6 S/FTP must be used (Cat.6 with S/FTP double shielding).
If the circuit-breaker is in withdrawable version, the use of cables fitted with a RJ45 socket with output at 90°
is recommended.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
271 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 13 - Ekip Com IEC 61850 modules
ABB | SACE Emax 2
Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
activates additional menus on the display:
• To set the modules.
• In order to display information on the modules.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path from the display, for setting the function and addressing of the modules:
…
Main frequency
Local/Remote
Local Bus
…
Force Static IP address
SNTP Client Enabled
Settings Static IP Address
Modules Ekip Com IEC 61850
Static Network Mask
Static Gateway addr
SNTP Server Address
Ekip Com IEC 61850 *R (1)
…
Functions
Power Controller
…
(1)
As Ekip Com IEC 61850.
The following table shows the parameters for setting the modules. For further information, see the table on
page 273.
Selectable
Parameter Default Description
values
Force Static IP • Off = Dynamic IP address.
Off, On Off
address • On = Static IP address.
• Off = Synchronism with the SNTP clock signal
SNTP Client
Off, On Off disabled.
Enabled
• On = Synchronism with the SNTP clock signal enabled.
Static IP Displayed with static IP Address enabled, it must be selected in order to insert the IP
Address Address of the modules.
Static Network Displayed with static IP Address enabled, it must be selected in order to insert the subnet
Mask mask of the modules.
Displayed with static IP Address enabled, it must be selected in the presence of
Static
multiple subnets, in order to insert the IP Address of the node to which the modules are
Gateway addr
connected.
SNTP Server Displayed with SNTP client enabled. "On" has to be selected to insert the IP address of
Address the server with whose SNTP clock signal the modules are to be synchronised.
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
…
About
Ekip Com IEC 61850
Modules
Ekip Com IEC 61850 *R
…
Power Controller
272 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 13 - Ekip Com IEC 61850 modules
Continued from the previous page ABB | SACE Emax 2
(1)
Organizationally Unique Identifier, formed by the first three bytes of a MAC address, and which uniquely
identifies the manufacturer of an Ethernet device.
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Preferred If several configuration files are present, allows file hierarchy
.cid
configuration file between .cid and .iid to be defined
Enables the IEEE 1588 protocol for distribution of the clock and
IEEE 1558 enable OFF
synchronization signal to be enabled (1).
Enables the module to be set up as a master in the the network
Master IEEE 1588 OFF
segment to which it belongs (synchronization clock).
IEEE 1588 delay Enables the data exchange mode between module and master,
End-to-End
mechanism between Peer-to-Peer and End-to-End to be selected.
Time zone Defines the time zone to be used for synchronism. +00:00
Used to select whether daylight saving time is present (ON) or
Daylight Saving Time OFF
not (OFF) in the country to which the synchronization time refers.
Defines the file loading procedure:
• TFTP always On= port open, loading always possible.
• TFTP enable required= port normally closed. To start loading,
TFTP Security level TFTP always On
Enable TFTP must be run at the start of the procedure and the
disable TFTP must be run at the end of the procedure (disable
not necessary, security command).
Defines the limitations to remote opening and closing command
execution:
• Standard commands= standard commands (unrestricted)
CB Open/CB Close activated. Standard
command • CB operate request= standard commands not activated. Use commands
programmable functions YC COMMAND and YO COMMAND
and Request breaker opening (28) and Request breaker closing
(29) commands.
Flag word hex Sets a filter on the selectivity states. 0
(1)
Enable IEEE 1558 and Enable SNTP client must not be enabled at the same time.
273 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 13 - Ekip Com IEC 61850 modules
ABB | SACE Emax 2
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW version General module information
Flash CRC status e result Information about the correctness of the SW in the module
Stato Ekip Link Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronisation State of synchronism with SNTP server
Valid with Master IEEE 1588 = ON, notifies the presence (Slave
IEEE 1558 status or PTP Master Active) or absence (PTP Master but Passive) of
the higher level master
Missing GOOSE Signals that an expected GOOSE has not been received
Configure Mismatch
Decode Error A GOOSE received does not conform to the expected structure
Sequence number error
Remote programmable states (from E to Condition (true/false) of the programmable states and
R) information on selectivity arising from logic defined in the
Remote inputs of zone selectivity configuration files loaded in module IEC 61850
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
C B • Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip unit with the
Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip unit):
A
power supply and communication with trip unit present (with a trip unit with the Alive LED
option enabled).
• On, with two quick flashes per second (not synchronized with those of the green LED on the
trip unit): power supply present, and communication with trip unit absent (for example: because
of Local Bus disabled).
Link LED, green. The possible states are:
B • Off: connection error (signal absent).
• On fixed: correct connection.
A
Activity LED, yellow. The possible states are:
C • Off: no activity on the line.
• On flashing: activity on the line (in reception and/or transmission).
274 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 13 - Ekip Com IEC 61850 modules
ABB | SACE Emax 2
Description Ekip Link is a communication accessory module that integrates the circuit-breaker in an internal Ethernet
network with an ABB proprietary protocol.
The network to which the module is to be connected must be dedicated and comprising only Ekip Link and
Ethernet switches that declare support for level L2 multicast on the datasheet. In this case the Ethernet
switches do not require any configuration. If, instead, the network also includes routers, multicast must be
enabled and configured on all L3 Layer VLAN interfaces.
IMPORTANT: the module can be connected only to Ethernet networks inside one or
more switchboards, to which trip units or ABB Emax 2 accessories are connected.
It is the installer's responsibility to ensure that all the necessary security measures
are adopted for all the connected devices (for example, the necessary access
authorizations, and so on). The module cannot be connected to other Ethernet
networks (for example, with the purpose of monitoring the system, or the office), or
to the Internet.
The module is necessary if you wish to implement the following functions:
• Power Controller
• Zone Selectivity
• Programmable Logic
For these functions, the trip units of the system that are involved must be equipped with an Ekip Link, and for
each of them the IP addresses of the Ekip Link modules of the other trip units must be inserted.
The Ekip Link modules must be connected to a dedicated network that includes only Ekip Link modules and
Ethernet switches that declare support for level L2 multicast in their data sheets. In this case, the Ethernet
switches do not require any configuration. If instead the network also includes routers, multicast must be
enabled and configured on all L3 Layer VLAN interfaces.
For each Ekip Link, every other trip unit connected to the network is considered as an actor. In addition, each
Ekip Link can be interfaced with a maximum of 15 actors, of which a maximum of 12 for the Zone Selectivity
function.
With the Power Controller function, every trip unit can:
• Acquire the state of the loads from remote and monitor them.
• Play the role of Master, and collect the energy measurements of the trip units selected as Energy Meter.
• Supply energy measurements to the trip units inserted as master.
The state of the loads can be acquired by checking the state of the inputs of the signalling modules connected
to the trip units whose IP address has been entered, while the loads can be monitored by programming their
outputs.
Remote acquisition of the state of the loads and monitoring of the loads can also be implemented with Ekip
Signalling 10K modules connected to the network.
For further information about the Power Controller function see the chapter "23 - Ekip Power Controller" on
page 131, and "2 - Load control" on page 159.
With the Zone Selectivity function:
• The IP addresses inserted refer to the trip units with the role of interlock.
• For every interlock trip unit inserted, the protections for which selectivity is to be implemented must
be selected by setting a mask. The function set in this way is indicated hereafter as logical, in order to
distinguish it from the standard function, hereafter referred to as hardware.
• The protections selected in this manner are added to the hardware protections S G D-Backward and
D-Forward.
• It is possible to choose between hardware-only selectivity and both hardware and logical selectivity.
• It is possible to set diagnostics to check for each interlock trip unit whether there is consistency between
the hardware and logical selectivity information.
• It is possible to set a mask that identifies the protections from which the received information about
selectivity is to be retransmitted, regardless of whether the trip unit is in alarm conditions. The information
to which the mask is applicable regards only logical selectivity.
For further information about Zone Selectivity function see the chapter "1 - Zone Selectivity" on page 156.
With the Programmable Logic function, it is possible to program the activation of the Ekip Link up to 4 bits,
each bit according to any combination of the status bits of a trip unit whose IP Address has been inserted.
These four bits are indicated as states A, B, C and D remotely programmable, and their value is transmitted
to the trip unit to which the Ekip Link module is connected.
Exclusively with Ekip Dip trip units: the module can also be used with a function similar to that of the Ekip Com
Modbus TCP module, but only with the possibility to communicate with the ABB master (e.g.: Ekip Connect,
or Ekip Control Panel).
The following table shows the ports used by the module:
Port Service Notes
502/tcp Modbus TCP When the module is used as a Modbus TCP communication module.
18/udp ABB proprietary In case of exchange of fast information between ABB devices.
319/udp When IEEE protocol 1588 is enabled (see paragraph "Remote
IEEE 1588
320/udp configurations", on page 279).
68/udp DHCP Client DHCP Client enabled as an alternative to “Static Address = On”
If connected to a withdrawable version of the circuit-breaker, the module allows the connected/disconnected
position to be detected.
IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unit
is disconnected from the module: in this condition, the only valid information
transmitted is:
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
Compatibility and power supply The module can be installed combined with Ekip Dip, Touch, Hi-Touch, G Touch, and G Hi-Touch trip units,
and requires the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
276 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 14 - Ekip Link module
ABB | SACE Emax 2
Connections The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0514.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
58
A4
*O)
S75I/5193
XK7 1 XK7194 2
A3 Ekip Link
K51
COM
RJ45
W13
A4
*R)
LINK BUS
*L)
Diagram 58
For the communication bus, a cable of type Cat.6 S/FTP must be used (Cat.6 with S/FTP double shielding).
If the circuit-breaker is in withdrawable version, the use of cables fitted with a RJ45 socket with output at 90°
is recommended.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
277 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 14 - Ekip Link module
ABB | SACE Emax 2
Access from the display With the module energized, and the Local Bus enabled, the presence of the module itself on the terminal box
activates additional menus on the display:
• To set the addressing of the module.
• To display information on the module.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path from the display to set the addressing of the module:
…
Main frequency
Local/Remote
Local Bus
…
Settings Force Static IP address
Modules Static IP Address
Ekip Link
Static Network Mask
Static Gateway addr
…
Functions
Power Controller
…
The following table shows the configuration parameters for the addressing of the module: For further
information, see the table on page 279.
Parameter Selectable values Default Description
Force Static IP • Off = Dynamic IP address.
Off, On Off
address • On = Static IP address.
Displayed with static IP Address enabled, it must be selected in order to insert the
Static IP Address
IP Address of the module.
Displayed with static IP Address enabled, it must be selected in order to insert the
Static Network Mask
subnet mask of the module.
Displayed with static IP Address enabled, it must be selected in the presence
Static Gateway addr of multiple subnets, in order to insert the IP Address of the node to which the
module is connected.
The following table shows the path from the display for accessing information on the module:
Protection Unit
Circuit-breaker
About …
Modules Ekip Link
…
Power Controller
278 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 14 - Ekip Link module
Continued from the previous page ABB | SACE Emax 2
(1)
Organizationally Unique Identifier, formed by the first three bytes of a MAC address, and which uniquely
identifies the manufacturer of an Ethernet device.
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive data
exchange network (see Ekip Com Hub on page 154).
Client/Server Server only
IMPORTANT:: if Client/Server, the module allows data
exchange like a normal Server function.
Enables the IEEE 1588 protocol for distribution of the clock and
IEEE 1558 enable OFF
synchronization signal to be enabled (1).
Enables the module to be set up as a master in the the network
Master IEEE 1588 OFF
segment to which it belongs (synchronization clock).
IEEE 1588 delay Enables the data exchange mode between module and master,
End-to-End
mechanism between Peer-to-Peer and End-to-End to be selected.
SNTP Client Enables the SNTP protocol for distribution of the clock and
OFF
enable synchronization signal to be enabled (1).
Force Static IP
Enables the network server that supplies the SNTP to be set. 0.0.0.0
Address
Time zone Defines the time zone to be used for synchronism. +00:00
Daylight Saving Used to select whether daylight saving time is present (ON) or not
OFF
Time (OFF) in the country to which the synchronization time refers.
Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
Disabilita Gratuitos
message, used by Ekip Connect to rapidly find the modules via ARP Enabled
ARP
Ethernet scan without knowing the IP address beforehand.
Access protected Enables the writing operations performed by the network to be Standard
by password protected by a password (Password request). mode
Password Modbus With access protected by enabled password, is the password to use
Local access
TCP before each writing session (2).
(1)
Enable IEEE 1558 and Enable SNTP client must not be enabled at the same time.
(2)
The parameter can only be changed by system bus in the remote configuration.
279 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 14 - Ekip Link module
ABB | SACE Emax 2
Remote Link configurations Regarding the Link functions, the following further parameters are available:
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW version General module information
Flash CRC status e result Information about the correctness of the SW in the module
Stato Ekip Link Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronisation State of synchronism with SNTP server
Valid with Master IEEE 1588 = ON, notifies the presence (Slave or PTP
IEEE 1558 status Master Active) or absence (PTP Master but Passive) of the higher level
master
Remote Link information Regarding the Link functions, the following further parameters are available:
Information Description
Information about the state and inconsistency of HW and logic selectivity
Line Congruency detection
(state and type of selectivity inconsistent)
Remote programmable
state (true/false) of remote programmable states A, B, C and D
states
Remote programmable Word
value of remote programmable Words A, B, C, D
state
Zone logic selectivity Logic selectivity states (inputs and outputs)
280 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 14 - Ekip Link module
ABB | SACE Emax 2
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Power LED, green. The possible states are:
C B • Off: power supply absent.
• On fixed: power supply and communication with the trip unit present (with a trip unit with the
Alive LED option disabled).
• On, with one flash per second (synchronized with that of the green LED on the trip unit):
A
power supply and communication with trip unit present (with a trip unit with the Alive LED
option enabled).
• On, with two quick flashes per second (not synchronized with those of the green LED on the
trip unit): power supply present, and communication with trip unit absent (for example: because
of Local Bus disabled).
Link LED, green. The possible states are:
B • Off: connection error (signal absent).
• On fixed: correct connection.
A
Activity LED, yellow. The possible states are:
• Off: no activity on the line.
C
• On, fixed or flashing: activity present on the line (in reception and/or transmission).
When it is on, it may be fixed or flashing (communication is active in both cases).
281 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 14 - Ekip Link module
ABB | SACE Emax 2
Description Ekip Com Hub is a communication accessory that enables the data and measurements of Ekip Touch and
other devices connected to the same installation to be gathered and then made available on the server
through an Ethernet network.
The configuration of the module is available via Ekip Connect or with the System Interface document, which
contains all the details.
The ports used by the module are:
Port Service Notes
67/udp 68/udp DHCP client Client DHCP enabled as an alternative to Static address = On
443/tcp HTTPS always active when module is enabled
123/udp SNTP active with SNTP client enabled
53/udp DNS always active
The Ekip Com Modbus RTU and Ekip Com Modbus TCP modules can be configured to support Ekip Com
Hub in the collection of data to send to Cloud. See Getting Started 1SDC200063B0201
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "17 - Other
accessories" on page 287).
Safety and cyber security The module uses the HTTPS protocol and can be connected to the Internet
Compatibility and power supply The modules can be installed on Emax 2 circuit-breakers configured with trip units Ekip Touch, Hi-Touch, G
Touch, G Hi-Touch (firmware version 2.20 or higher) and Ekip Supply module fitted into the first slot of the
terminal box of the circuit-breaker.
NOTE: the communication is interrupted in the absence of auxiliary power supply.
282 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 15 - Ekip Com Hub modules
ABB | SACE Emax 2
Connections The module must be installed on the terminal box of the circuit-breaker, or on the fixed part of withdrawable
circuit-breakers, in the first slot after the Ekip Supply module.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0514.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring diagram:
61 71 81 91 01
51 95 35 R1 V3 Vn Ge Szi Ne- 45 D1 C1 C11 C21 11 21 31 41
HC H1 H2 H3 H4
62 72 82 92 02
52 96 36 U1 R2 V2 Rct Ge- Szo W3 K1 Ne 46 C3 C13 12 22 32 42
HC K3 K4 K5 K6
64 74 84 94 04
54 98 38 U2 V1 Gzo Szc Gzi W4 K2 Rca 48 D2 C2 C12 C22 14 24 34 44
HC K7 K8 K9 K1 0
S51 S33 M YR Trip Unit I/O Module Module Module EKIP Supply TU YU YC
RT C YO YO YC 2 Q1 Q2 Q3 Q4
Q5..Q10 EKIP Signalling 4K I/O 2
59
A4
* O)
S75I/5
193
194
XK7 1 XK7 2
A3
Ekip Com HUB
K51
COM
W14
RJ45
A4
* R)
BUS 1
* L)
Diagram 69
For the communication bus, a cable of type Cat.6 S/FTP must be used (Cat.6 with S/FTP double shielding).
If the circuit-breaker is in withdrawable version, the use of cables fitted with a RJ45 socket with output at 90°
is recommended.
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
283 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 15 - Ekip Com Hub modules
ABB | SACE Emax 2
Access from the display Local bus activation, which is essential for starting the communication between module and trip unit, is
available in the menu Settings Menu on page 49
The following communication parameters can be configured if the module has been correctly detected by the
trip unit in the Settings-Modules menu:
Parameter Description Default
Enable Switch communication between module and server on/off.
Defines whether the module has the dynamic (Off) or static (On) IP
Force Static IP Address address. OFF
Se = On all the associated parameters are enabled.
Static IP Address Enables the static IP to be selected. 0.0.0.0
Network Mask Static Enables the subnet mask to be selected. 0.0.0.0
When there are several subnets, enables the IP address of the
Static Gateway addr 0.0.0.0
node to which the module is connected to be selected.
Enables the SNTP protocol for distribution of the clock and
SNTP Client Enabled OFF
synchronization signal to be enabled.
SNTP Server Address Enables the network server that supplies the SNTP to be set. 0.0.0.0
Password code required to register module on Cloud. ---
Enables the firmware of the module to be updated. Two
parameters are available: OFF
Remote firmware update
• Enable, to configure firmware download. Automatic
• Automatic, to automate module update.
The following information will be available if the module is detected correctly by Ekip UP in the Information-
Modules menu:
Information Description
SN and version Identifier and SW version of the module.
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be
xset via the menu in the event of a static IP.
IP Address
NOTE: without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the modules
Network Mask
belong and enables modules to be searched for within a defined set of recipients.
IP address of the node to which the module is connected, in the presence of several
Gateway Address
subnets.
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC Address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device.
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Allows the CRL (Certificate Revocation List) to be used to ascertain
CRL Enable
whether the server certificate is valid
Clock update
hardening Enables control of the time reference transmitted by the SNTP server
enable
SNTP Server Enables the position of the SNTP server to be set in relation to the
Location network in which the module is installed
SNTP Time
Defines the time zone to be used for synchronism +00:00
zone
SNTP Daylight Used to select whether daylight saving time is present (ON) or not
OFF
Saving Time (OFF) in the country to which the synchronization time refers
Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
Disabilita
message, used by Ekip Connect to rapidly find the modules via ARP Enabled
Gratuitos ARP
Ethernet scan without knowing the IP address beforehand
284 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 15 - Ekip Com Hub modules
ABB | SACE Emax 2
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW version General module information
Flash CRC status e result Information about the correctness of the SW in the module
Publish enable configuration State of enabling in Security File
Name of the file dedicated to the information to transmit (measurements,
Configuration file
etc.)
Name of the file dedicated to the information requested by the module for
Security file
transmission purposes (addresses, certificates, etc.)
Certificate Revocation List Name of the file containing the revoked certificates
Executable file Name of the executable firmware update file
Configuration error Module configuration error state
Sample time Period of data acquisition from the connected devices
Log time Period within which the acquired data are saved in the log
Upload time Period (calculated by the module) between each data transmission
Configured device Number of modules involved in the network with Hub module
Polling period API events Period in which the module communicates with the API device
Connection client Address of modbus TCP client connected to the module
Recordings of the latest saving operations and percentage of resources
Statistics
being used
Status plant side Information about the quality of the communication with the other devices
State of the errors concerning the TLS session established between
Status Cloud side
module and server
Application status Operation progress indicators
General indicators of the module: SNTP state, flash, cable connection,
Status
FW availability, file errors, etc.
Signallings The following table shows the possible signals, and their meaning:
Pos. Description
Signals the on state and correct communication with the trip unit:
C B • Off: module off.
• On steady or flashing synchronized with the trip unit Power led: module on and
A
communication with trip unit present.
• Flashing not synchronized with trip unit Power led (2 fast flashes per second): module on and
communication with trip unit absent.
Indicates the communication state:
B • Off: incorrect connection, signal absent.
• On fixed: correct connection.
Indicates the communication state:
C • Off: no activity on the line.
• Flashing: activity on line present (receiving and/or transmitting).
A
285 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 15 - Ekip Com Hub modules
ABB | SACE Emax 2
Description Ekip Com Actuator is an accessory module that allows SACE Emax 2 circuit-breakers to be opened and
closed from remote.
Connections Ekip Com Actuator is installed on the front of the circuit-breaker in the accessories area.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH000999R0501 and 1SDH001000R0501.
Wiring diagrams of the module are provided below:
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
78 76
+ +
~ ~
A4
SC S43 SO S43
C11
C13
C1
C3
C2 C12 XK7 9 K51 XK7 7 K51
A1 XK7 10 XK7 8
XB3 1 XB4 1
YC YO
XB3 2 XB4 2
C12
C2
XV C2 C12
X C2 C12
A4
- -
~ ~
*M) *M)
Diagrams 78 - 76
Compatibility Ekip Com Actuator module is supplied on request and is compatible with all Ekip trip units equipped with
Ekip Com or Ekip Link modules.
286 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 16 - Ekip Com Actuator module
ABB | SACE Emax 2
17 - Other accessories
Ekip LCD The LCD version of the protection trip unit can be requested for installations in particularly aggressive
environments (low temperatures, high degree of humidity, dust or chemical substances). The LCD version
differs from the version with touchscreen display in:
• Black and white LCD display.
• Menu navigation by buttons.
• The HOME button provides direct access to the page Menu. The Measurements pages can be accessed
using the ARROW UP and ARROW DOWN buttons from the page Histograms. (Main Page and Measuring
Instruments area are not available).
All the protection, measurement and accessory options are the same as those of the touchscreen version.
Rating Plug The Rating Plug defines the rated current In necessary to set the current protections on the trip unit, since
these refer to In.
It is supplied with all Ekip trip units, mounted on a front connector dedicated and accessible to the user, and
can be replaced with trip unit off and circuit breaker open.
IMPORTANT: the replacement of the Rating Plug with trip unit on or circuit breaker
closed may cause malfunction of the trip unit, or unwanted opening of the circuit-
breaker.
NOTE: a trip unit can be equipped with any Rating Plug with a maximum rated current equal
to Iu, i.e. the rated uninterrupted current of the circuit-breaker (indicated on the rating plate
of the circuit-breaker).
The trip unit continuously checks for the presence of the Rating Plug, signalling its absence or any assembly
or installation errors.
Once mounted, when the trip unit is energized, its installation is requested.
To activate the residual current protection on the Touch, Hi-Touch, G Touch and G Hi-Touch trip units, it is
necessary to mount a Rating Plug Rc. Rating Plug L = OFF, which allow you to deactivate the protection L
are also available.
Further details about assembly and the Rating Plug installation procedure are available on the website http://
www.abb.com/abblibrary/DownloadCenter/, in particular in the kit sheet 1SDH001000R0510.
Toroid S.G.R. S.G.R., or Source Ground Return, is the external homopolar current sensor that can be installed with the
following trip units: Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch, LSIG version.
Its presence should be selected when the release is programmed (see menu Settings - Circuit-breaker -
Earth protection), which activates earth fault protection Gext (see Advanced menu) .
IMPORTANT: the S.G.R. Toroid can be selected as an alternative to the Rc type.
Therefore Gext and Rc protections are alternatives.
Further information on the connection of the S.G.R. toroid is available on the website http://www.abb.com/
abblibrary/DownloadCenter/, in particular in kit sheet 1SDH001000R0507.
Rc Toroid Rc is the external residual current sensor, that can be installed with Ekip Touch, Hi‐Touch, G Touch, and G
Hi-Touch trip units equipped with Rating Plug Rc, Ekip Measuring Pro and Ekip Supply modules.
Its presence should be selected when the release is programmed (see menu Settings - Circuit-breaker -
Earth protection), which activates residual current Rc protection Gext (see Advanced menu) .
IMPORTANT: the Rc toroid can be selected as an alternative to the S.G.R type.
Therefore the Rc and Gext protections are alternatives.
Further information on the connection of the Rc toroid is available on the website http://www.abb.com/
abblibrary/DownloadCenter/, in particular in kit sheet 1SDH001000R0521.
287 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 17 - Other accessories
ABB | SACE Emax 2
Ekip Connect software Ekip Connect is the free software for communication and testing of ABB low voltage circuit-breakers equipped
with compatible trip units, in particular of Ekip series.
Ekip Connect must be installed on PCs equipped with the Microsoft Windows® operating system by
downloading it from the site http://www.abb.com/abblibrary/DownloadCenter.
Through its communication function, it allows you to:
• Monitor the state of the connected circuit-breakers and record information.
• Execute the switching, reset, signalling commands, etc…
• Configure the protection trip units with customized parameters.
• Configure the electronic accessories, connected to the trip unit via Local Bus.
• Download information from the trip units equipped with Datalogger.
• Create communication reports.
• Reset configurations.
Through the test function, and Ekip T&P module (see page 289), it allows you to:
• Simulate fault conditions by performing manual or automatic tests.
• Perform trip tests.
• Create test reports.
Further information on the Ekip Connect application is available on the website http://www.abb.com/
abblibrary/DownloadCenter/, in particular in the manual 1SDH000891R0002.
Ekip Bluetooth module The Ekip Bluetooth allows connection via Bluetooth between the Ekip trip units, and a support (PC, tablet, or
smart phone) with the Ekip Connect software installed (see previous paragraph).
IMPORTANT: the Ekip Bluetooth module can be connected to the trip units also when
in service.
NOTE: Ekip Bluetooth powers the trip unit only. Therefore, in order to set and to display
information on any electronic accessories connected to the terminal box, these must be
powered by an Ekip Supply module (see page 208).
It draws its power from a rechargeable lithium-polymer battery delivered with the unit. It is connected directly
to the front test connector of the trip unit, and allows a trip unit without auxiliary voltage to be powered.
It is switched on by pressing the power button on the side, and is equipped with two LEDs:
• The first LED in green when the device is on and the battery charged, red with the device turned on and
low battery.
• The second LED flashing blue with active Bluetooth communication.
NOTE: the red flashing LED indicates that the battery is completely drained, an error condition,
or malfunction of the module.
The battery charging is performed by connecting the module to the USB ports of a PC with the supplied
cable. Connection to a PC automatically switches the module on, and charging in progress is indicated by
the flashing green LED, with increasing frequency as the level of charging rises. Completion of charging is
indicated by the green LED on (fixed).
NOTE: during recharging, the module must be kept energized.
288 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 17 - Other accessories
ABB | SACE Emax 2
Ekip T&P module The Ekip T&P module is part of the Ekip T&P programming and test kit for Ekip trip units, and allows you to:
• Supply the trip unit in the absence of auxiliary voltage.
• Access the information, the pages for programming the trip unit and activate the test pages, through the
Ekip Connect software (see page 288).
IMPORTANT: Ekip T&P can also be connected to the trip units when in service. In
case of connection to trip units in service, it is not possible to perform a trip test.
NOTE: Ekip T&P only powers the trip unit. Therefore, in order to set and to display information
on any electronic accessories connected to the terminal box, these must be powered with
an Ekip Supply module (see page 208).
It draws its power from the PC, and connects one side directly to the test connector at the front of the trip
unit, and on the other to the USB ports of the PC through the cable supplied.
It turns on after connecting to the PC, and is equipped with two LEDs, a green one indicating that the module
is on, and a yellow one indicating active communication.
NOTE: Ekip Programming powers the trip unit only. Therefore, to set and display the information
for any electronic accessories connected to the terminal box, those accessories must be
powered with an Ekip Supply module (see page 208).
It draws its power from the PC, and connects one side directly to the test connector at the front of the trip
unit, and on the other to the USB ports of the PC through the cable supplied.
It turns on after connecting to the PC, and is equipped with two LEDs, a green one indicating that the module
is on, and a yellow one indicating active communication.
Ekip TT module
Ekip TT is supplied as standard with Emax 2 circuit-breakers if they are equipped with an Ekip Touch, Ekip
Hi-Touch, Ekip G Touch or Ekip G Hi-Touch protection trip unit, and with all loose trip units (ordered as spare
parts). Ekip TT allows you to:
• Check that the opening mechanism of the circuit-breaker functions properly by commanding an opening
according to the test procedure (see page 28)
• Power the trip unit so that you can see which protection tripped either on the display or through the lighting
of the corresponding LEDs in the absence of auxiliary voltage and where the circuit breaker is open due
to a protection tripping
• Power the Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units in order to set the protections in the
absence of auxiliary voltage
IMPORTANT: Ekip TT can be connected to the trip units also when in service. In case
of connection to trip units in service, it is not possible to perform a trip test.
NOTE: Ekip TT powers the trip unit only. Therefore, in order to set and to display information
on any electronic accessories connected to the terminal box, these must be powered through
an Ekip Supply module (see page 208).
Ekip TT draws its power from three AA alkaline batteries 1.5V, connects to the test connector at the front of
the trip unit through the supplied cable, and is turned on by setting the side switch to ON.
It includes a LED that is green when the device is energized and the batteries are charged, and red when the
batteries are drained and need to be replaced.
Further information on Ekip TT is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0519, and in the Ekip Connect software manual 1SDH000891R0002.
289 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 17 - Other accessories
ABB | SACE Emax 2
Ekip Signalling 10K modules The Ekip Signalling 10K is an accessory module for external signaling that can be installed on a standard 35
mm DIN rail (DIN EN 50022 type TS 35x15 mm).
This module has:
• Ten programmable output contacts.
• Ten or eleven programmable digital inputs.
• A power-on LED, and twenty or twenty-one signalling LEDs (one for each output/input).
The module can be set-up in four different configurations:
• One in case of connection to a Link bus network.
• Three configurations in case of connection via Local Bus (to allow up to three modules to be connected
to the same trip unit).
Ekip Signalling Modbus TCP The Ekip Signalling Modbus TCP is an external accessory module that can be installed on a standard 35 mm
DIN rail (DIN EN 50022 type TS 35 x 15 mm).
Its function is to share, via an Ethernet network with Modbus TCP communication protocol, information about
the state of circuit-breakers that may even be without the capability to provide such information via Ethernet,
and to allow these circuit-breakers to be operated via remote control.
The module has 11 digital inputs and 10 output contacts:
• The inputs allow the state of the circuit-breakers and other information to be monitored.
• The outputs allow the circuit-breakers to be operated.
Each input and output is associated with a state LED.
Free I/O The inputs and outputs can be fully configured by the user.
Further details about Ekip Signalling Modbus TCP are available on the website http://www.abb.com/
abblibrary/ DownloadCenter/, in particular in the manual 1SDH001456R0002.
290 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 17 - Other accessories
ABB | SACE Emax 2
Ekip Multimeter module The Ekip Multimeter is a remote displaying unit on the front of the switchgear and is equipped with a
touchscreen display.
It can be installed in combination with Ekip Dip, Touch, Hi‐Touch, G Touch, and G Hi‐Touch trip units, with
which it communicates via Local Bus. It must be powered independently of the trip units to which it is
connected and can be powered in AC at 105...265 V AC/DC, or DC at 21.5...53 V DC.
IMPORTANT: AC and DC power supplies cannot be present at the same time.
One trip unit can communicate with a maximum of four Ekip Multimeters. On the other hand, the module can
be connected to only one trip unit.
In addition, the module makes available an auxiliary voltage of 24 V DC, which can be used to power the
trip unit. If the trip unit is powered through Ekip Multimeter, the power supply must be applied directly on the
terminal box of the circuit-breaker: in fact the Ekip Multimeter is sized in order to supply only the trip unit,
and therefore it is may be unable to deliver enough power to supply an Ekip Supply module and any other
electronic accessories connected to the terminal box.
In case of connection to an Ekip Touch, Hi-Touch, G-Touch, and G Hi-Touch trip unit, as well as displaying the
measurements, the module also allows you to set parameters and protection thresholds.
For the Local Bus (communication lines W3 and W4) and the auxiliary output power (24Vout L+ and - signals),
Belden 3105A or equivalent cables must be used with a maximum length of 15 m. The shield of the cables
must be connected to ground on both sides of the connection.
Further information on Ekip Multimeter is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular in the kit sheet 1SDH001000R0520.
External neutral This is a current sensor for the neutral pole outside the circuit-breaker.
It is provided only for three-pole circuit breakers. It allows protection of the neutral to be implemented through
the connection to the Ekip trip unit. It is supplied on request.
Further information on the connection of the external neutral is available on the website http://www.abb.com/
abblibrary/DownloadCenter/, in particular in the kit sheets:
• 1SDH001000R0506 for circuit breakers E2.2.
• 1SDH001000R0515 for circuit breakers E4.2 and E6.2.
Contacts Ekip AUP The communication modules are always supplied with dedicated Ekip AUP auxiliary position contacts. In
case of a withdrawable circuit-breaker, the Ekip AUP contacts give the signal of moving part racked-in/out
from the fixed part.
The assembly assures that the position signalling is given also with the moving part withdrawn.
IMPORTANT: in case of multiple communication modules, only one can be connected
to the Ekip AUP contacts.
Further information on assembling Ekip AUP modules and contacts is available on the web site http://www.
abb.com/abblibrary/DownloadCenter/, in particular in the kit sheet 1SDH001000R0811.
Ekip RTC contact The communication modules are always supplied with an Ekip RTC auxiliary contact, which gives to the trip
unit the signal indicating that the circuit-breaker is ready to receive a close command.
Further information on the assembly of the Ekip RTC contact is available on the website http://www.abb.
com/abblibrary/DownloadCenter/, in particular in the kit sheets:
• 1SDH000999R0604 for circuit breakers E1.2.
• 1SDH001000R0604 for circuit breakers E2.2, E4.2 and E6.2.
291 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electronic accessories | 17 - Other accessories
ABB | SACE Emax 2
Electrical accessories
YO-YC-YO2-YC2 (1): Opening The opening coils, YO and YO2, and the closing coil, YC and YC2 (1), allow the circuit-breaker to be controlled
and closing coil remotely.
The opening of the circuit-breaker is always possible with the circuit-breaker closed, while closing is possible
with the circuit-breaker open and the closing springs charged.
The opening and closing coils can operate in two different modes:
• instantaneous service (the minimum duration of the command impulse must be 100 ms).
• service with permanent power supply.
D1 C1 C11
C3 C13
D2 C2 C12
YU
YO 2 YC YO
D1 C1 C11 C21
C3 C13
D2 C2 C12 C22
YU
YO 2 YC YO YC 2
NOTE: the second opening coil YO2 is alternative to the undervoltage coil YU.
IMPORTANT:
• If the closing coil is permanently energized and the opening coil trips, after opening,
the closing coil must be momentarily de-energized so that it can be reused for the next
closing operation.
• If instead the opening coil trips, it is necessary, after having de-energized it, to wait at
least 100 ms before operating the closing coil.
Available voltages and characteristics
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un) General characteristics YO-YO2 YC-YC2 (1)
24 V AC/DC Operating limits 70...110 %Un 85...110 %Un
30 V AC/DC Inrush power (Ps) 300 VA/W
48 V AC/DC Continuous power (Pc) 3.5 VA/W
60 V AC/DC Maximum opening time 35 ms -
110…120 V AC/DC Maximum closing time - 50 ms
220…240 V AC/DC
240...250 V AC/DC
277 V AC/DC
380…400 V AC
415…440 V AC
480…500 V AC
500…550 V AC
(1)
YC2 not available for E1.2
292 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 1 - Electrical control accessories
Continued from the previous page ABB | SACE Emax 2
YU: Undervoltage coil The undervoltage coil YU controls the value of the voltage in the circuit to which it is connected.
The coil opens the circuit-breaker when its energizing voltage drops below a value between 35...70%Un
The circuit-breaker can be reclosed when the coil energizing voltage is between 85...110% Un.
The undervoltage coil YU can in addition be used for the following purposes:
• Trip unit the circuit-breaker remotely using pushbuttons of the normally closed type.
• Activate the lock when the circuit-breaker is closed (the closing of the circuit-breaker is allowed only with
the undervoltage coil energized).
IMPORTANT:
• The undervoltage coil YU is incompatible with the presence of the Fail Safe device (UL
circuit-breakers).
• The undervoltage coil YU is a emergency trip unit. For service operations use the
opening coil.
NOTE: the power supply of the coil must be drawn on the supply side of the circuit-breaker
or from an independent source.
If the undervoltage coil trips, it is necessary, after having reset it, to wait at least 100 ms
before operating the closing coil.
D1
D2
YU
YO 2
YU for E1.2
D1
D2
YU
YO 2
293 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 1 - Electrical control accessories
Continued from the previous page ABB | SACE Emax 2
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un) General characteristics YU
24 V AC/DC Inrush power (Ps) 300 VA/W
30 V AC/DC Continuous power (Pc) 3.5 VA/W
48 V AC/DC Opening time 50 ms
60 V AC/DC
110…120 V AC/DC
220…240 V AC/DC
240...250 V AC/DC
277 V AC/DC
380…400 V AC
415…440 V AC
480…500 V AC
YU: Connections
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999R0504 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000R0504.
R1
R2
YR
YR for E1.2
R1
R2
YR
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un) General characteristics
24 V AC (1) 24 V DC (1) Operating limits 90...110 %Un
110 V AC (1) 110 V DC (1) (2)
220 V AC (1) 220 V DC (1) (2)
(1)
The coil must be activated by a pulse lasting at least 20ms.
(2)
The coil must be activated by a pulse lasting max 50ms.
YR: Connections
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999R0606 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000R0606.
294 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 1 - Electrical control accessories
ABB | SACE Emax 2
M: Motor The motor automatically recharges the closing springs of the circuit-breaker when these are discharged.
The motor is equipped with a limit contact S33 M/1 that interrupts the power supply of the motor after
charging of the springs is completed.
The motor is equipped with a limit contact S33 M/2 that signals the state of the charged springs.For information
on the S33 M/2 limit contact refer to the dedicated paragraph "S33 M/2: springs charged signalling contact"
in this chapter.
U1
U2
M for E1.2
U1
U2
NOTE: The closing springs can in any case be charged manually through the appropriate
front control lever.
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un) General characteristics
24…30 V AC/DC Operating limits 85...110 %Un
48…60 V AC/DC Inrush power (Ps) 500 VA/W
100…130 V AC/DC Power during charge (Pc): 100 VA/W
220…250 V AC/DC Charging time Min 5 s, max 10 s
Available voltages (Un) (1)
380…415 V AC
Available voltages (Un) (2)
277 V AC/DC
380…400 V AC
440…480 V AC
(1)
for E1.2
(2)
for E2.2 - E4.2 - E6.2
M: Connections
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999R0609 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000R0609.
295 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 1 - Electrical control accessories
ABB | SACE Emax 2
AUX 4Q: auxiliary open-closed The AUX 4Q contacts signal the open/closed state of the circuit-breaker.
contacts These are "switching" contacts and are available in three types:
• four standard contacts
• four digital signals (low power)
• two standard contacts (Q1-Q2) + two digital signals (Q3-Q4)
NOTE: The standard AUX 4Q contacts are always included in the circuit-breakers
11 21 31 41
12 22 32 42
14 24 34 44
Q1 Q2 Q3 Q4
11 21 31 41
12 22 32 42
13 23 33 43
Q1 Q2 Q3 Q4
296 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
51 61 71 81 91 01
HC H1 H2 H3 H4
52 62 72 82 92 02
HC K3 K4 K5 K6
54 64 74 84 94 04
HC K7 K8 K9 K10
Q5..Q10 EKI P S ignalling 4K
(1)
Only for E2.2 - E4.2 - E6.2
NOTE: it is possible to order the AUX 6 Q contacts only if the circuit-breaker is not equipped
with a protection trip unit with the Ekip Signalling 4K module.
297 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
298 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
AUP: auxiliary position contacts The AUP contacts are intended for circuit-breakers in withdrawable version.
They electrically signal the position of a moving part (inserted/test/withdrawn) in relation to the fixed part in
which they are inserted.
These are "switching" contacts and are available in the following configurations:
Up to a maximum of six contacts for E1.2:
• six standard contacts
• six digital signals
Up to a maximum of ten contacts for E2.2-E4.2-E6.2:
• five standard contacts
• five digital signals
• five additional standard contacts
• five additional digital signals
AUP: Connections
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999R0603 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000R0603.
299 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
The RTC is a "switching" contact type and is available in the standard version or in the versions for digital
signals.
45
46
48
RT C
45
46
48
RT C
RTC: Connections
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999R0604 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000R0604.
300 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
95
96
98
S51
95
96
98
S5 1
S51: Connections
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999R0605 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000R0605.
301 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
R1
R2
YR
S51: Connections
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet 1SDH001000R0614.
302 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
35
36
38
S33
35
36
38
S33
S33/M2: Connections
Further information is available on page 204, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999R0609 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000R0609.
303 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Electrical accessories | 2 - Electrical signalling accessories
ABB | SACE Emax 2
Mechanical accessories
IP54 protection IP54 protection completely protects the front of the circuit-breaker, to achieve protection class IP54.
It is always equipped with two locks for closing, available in two types:
• lock with different key code numbers (for an individual circuit-breaker)
• lock with the same key code number (for more than one circuit-breaker)
304 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical accessories | 1 - Mechanical Protection accessories
ABB | SACE Emax 2
HTC / LTC (1): Terminal-cover Terminal-covers are applied in order to reduce the risk of direct contact with live parts. They are available in
two types:
• HTC - High terminal-covers
• LTC - Low terminal-covers
(1)
Only for E1.2
Information on assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheets:
• 1SDH000999R0612 for the high terminal-covers
• 1SDH000999R0613 for the low terminal-covers
PB (1): Phase separators The phase separators are applied in order to increase the insulation clearance between two adjacent phases.
(1)
Only for E1.2
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheet 1SDH000999R0608.
305 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical accessories | 1 - Mechanical Protection accessories
ABB | SACE Emax 2
KLC: open position key lock The KLC locks the circuit-breaker in the open position.
It can also be used during maintenance activities on the circuit-breaker after removal of the cover of the
accessory area.
The KLC lock is available with two types of locking:
• lock with different key code numbers (for a single circuit-breaker).
• lock with the same key code number (for more than one circuit-breaker). The maximum number of key
code numbers available is five.
If set up appropriately, the KLC-A lock can work with four other types of locks:
• Ronis
• Profalux
• Kirk
• Castell
NOTE: the supply of Ronis - Profalux - Kirk - Castell locks is at customer's expense.
PLC: padlock The PLC locks the circuit-breaker in the open position.
It is available in two types:
• lock usable with a maximum number of three padlocks with a diameter of 4 mm - 0.16"
• lock usable with a maximum number of two padlocks with a diameter of 8 mm - 0.32"
• lock for a padlock with a diameter of 7 mm - 0.28" or for a latch chain
NOTE: The padlocks are at customer's expenses.
306 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical accessories | 2 - Mechanical safety accessories
ABB | SACE Emax 2
Anti-insertion lock The anti-insertion lock allows the moving part of the circuit-breaker to be inserted only into the corresponding
fixed part.
It is intended for all withdrawable circuit breakers.
L
E1.2 12
10 L
08 .2 12
-N
16
06 E1
B-C12 10
E1.2 10
08 08
06
02 N 06
C-
B- 12 16
.2
E1 10
08
06
02
02 E2.2
08
10 N-B-
LEFT
12 S
16
20
25
08 E2.2
10
12 H
16
20
MATC 25
H
ALSO
THE
RIGH
T
SIDE
MOC: Operation counter The mechanical operation counter displays the number of mechanical operations performed by the circuit-
breaker.
00001 00001
MOC for E1.2 MOC for E2.2 - E4.2 - E6.2
PLP: padlock in connected/ The PLP locks the moving part of a withdrawable circuit-breaker in the fixed part, in one of the following
test/disconnected positions positions:
• connected
• test
• disconnected
Only one type is available that allows you to mount up to three padlocks with a diameter of 8 mm.
NOTE: the PLP lock can also be supplied in the presence of a KLP lock
307 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical accessories | 2 - Mechanical safety accessories
ABB | SACE Emax 2
KLP: key lock for connected/ The KLP lock for connected/test/disconnected position locks the moving part of a withdrawable circuit-
test/disconnected positions breaker in the fixed part, in one of the following positions:
• connected
• test
• disconnected
NOTE: it is possible to lock the moving part in the disconnected position only by using the
additional accessory KLP lock.
The KLP lock for connected/test/disconnected positions is available with two types of lock:
• lock with different key code numbers (for a single circuit-breaker).
• lock with the same key code number (for more than one circuit-breaker). The maximum number of key
code numbers available is five.
Through an appropriate setup, the KLP lock for connected/test/disconnected positions can work with three
other types of lock:
• Ronis
• Profalux
• Kirk
• Castell
The maximum number of locks that can be installed per circuit-breaker is the two, for all types of lock.
NOTE: the supply of Ronis - Profalux - Kirk locks is at customer's expense.
NOTE: the KLP lock can also be supplied in the presence of a PLP lock
KLP lock additional accessory This additional accessory limits the blocking function to the disconnected position only.
308 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical accessories | 2 - Mechanical safety accessories
ABB | SACE Emax 2
SL: shutter lock The SL shutter locks the shutters of the fixed part.
It is possible to lock the upper and lower shutters independently.
This is an accessory available on all the fixed parts and can work with the aid of padlocks with diameters of 4
mm - 0.16", 6 mm - 0.24", 8 mm - 0.32", with a maximum of four padlocks per fixed part (two for the upper
shutters and two for the lower shutters).
NOTE: The padlocks are at customer's expenses.
DLC: Door opening lock with The DLC prevents the following operations from being carried out:
the circuit-breaker in closed • opening the switchgear door with the circuit-breaker closed if the circuit-breaker is in fixed version
position • opening the switchgear door with the circuit-breaker closed and in connected position if the circuit-breaker
is in fixed version
• closing of the circuit-breaker when the switchgear door is open
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999R0712 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000R0712.
309 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical accessories | 2 - Mechanical safety accessories
ABB | SACE Emax 2
DLP (1): door opening lock The DLP lock prevents the switchgear door from being opened when the moving part of the circuit-breaker
with the circuit-breaker in is in the connected or test position.
connected/test position It can be installed alternatively on the right side or the left side of the fixed part.
DLR (1): lock on racking-in/ The DLR lock prevents the moving part from being racked in/out from the fixed part when the switchgear
racking-out of the moving part door is open.
with the door open It is available on request on all fixed parts.
Fail safe The fail safe is a device that prevents the removal of the mobile part of a withdrawable circuit-breaker from
the fixed part if the springs are charged.
It is always supplied with UL circuit-breakers.
IMPORTANT:
• The fail safe device makes undervoltage coil YU unavailable.
• It is, however, possible not to install the fail safe device, in which case the undervoltage
coil YU must be used.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular for E1.2 in the kit sheets
• 1SDH000999R0708 for the Fail Safe, movable part
• 1SDH000999R0711 for the Fail Safe, fixed part
and for E2.2-E4.2-E6.2 in the kit sheet 1SDH001400R0821.
310 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical accessories | 2 - Mechanical safety accessories
ABB | SACE Emax 2
3 - Mechanical Interlocks
Mechanical interlocks determine the opening/closing logic between two or three circuit-breakers.
Four types of interlocks are available, usable in both fixed and withdrawable versions.
Mechanical interlock of type A - The Type A interlock is applicable to two circuit-breakers (normal power supply + emergency power supply).
Two Circuit-breakers It allows you never to have two circuit-breakers in the closed position at the same time.
1 2 Information on assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
O O particular with the kit sheets:
I O • 1SDH000999R0720 for interlock between E1.2circuit-breakers
O I • 1SDH001000R0720 for interlock between E2.2-E4.2-E6.2 circuit-breakers
• 1SDH000999R0721 for interlock between one E1.2 circuit-breaker and one E2.2-E4.2-E6.2 circuit-breaker
Mechanical interlock of type B - The Type B interlock is applicable to three circuit-breakers (two normal power supplies + emergency power
Three Circuit-breakers supply).
1 2 3 It only allows the closing of the two circuit-breakers of the normal power supply if the circuit-breaker of the
O O O emergency power supply is open. The circuit-breaker of the emergency power supply can be closed only if
the others two are open.
I O O
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
O O I
particular with the kit sheet 1SDH001000R0721.
I O I
O I O
Mechanical interlock of type C - The Type C interlock is applicable to three circuit-breakers (two normal power supplies + a bus tie).
Three Circuit-breakers It allows the simultaneous closing of one or two circuit-breakers, resulting in two possible types of power
1 2 3 supply of the half busbars:
O O O • power supply from a single transformer (bus tie closed)
I O O • power supply from both transformers (bus tie open)
O I O
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
O O I
particular with the kit sheet 1SDH001000R0722.
O I I
I I O
I O I
Mechanical interlock of type D - The Type C interlock is applicable to three circuit-breakers (three power supplies on the same bar that must
Three Circuit-breakers not operate in parallel)
1 2 3 It allows only one of the three circuit-breakers to be closed.
O O O Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
I O O particular with the kit sheet 1SDH001000R0723.
O I O
O O I
311 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Mechanical accessories | 3 - Mechanical Interlocks
ABB | SACE Emax 2
Alarms or failures
Introduction The protection trip unit is able to identify some faults and to signal them through LEDs or display; you need to
identify the cause and eliminate it before re-closing the circuit-breaker, both locally and remotely.
WARNING! identification of the faults must be managed only by Skilled Persons in
the electrical field (IEV 195-04-01): person with relevant education and experience
to enable him or her to perceive risks and to avoid hazards which electricity can
create. Indeed, it may be necessary to perform insulation and dielectric tests on part
or all of the installation.
Some failures involve partial operation of the circuit-breaker. Consult the paragraphs “Faults, causes and
remedies” on page 313 and “Faults signalled on the display” on page 316 where the possible causes of the
main faults are listed.
Further information on the Ekip Touch trip unit and on the accessories mentioned in this chapter and which are
not covered in this manual are available on the website http://www.abb.com/abblibrary/DownloadCenter/,
with the Ekip Touch manual 1SDH001316R0002.
312 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Alarms or failures | 1 - Identification of alarms or failures
ABB | SACE Emax 2
Faults, causes and remedies The following is a list of possible fault situations, their possible causes and suggestions for resolving them.
NOTE: Before consulting the table, check the error messages on the display. If the suggestions
indicated fail to resolve the problem, contact the ABB Assistance Service supplying, if possible
supplying the report produced by the Ekip Connect software.
313 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Alarms or failures | 1 - Identification of alarms or failures
Continued from the previous page ABB | SACE Emax 2
314 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Alarms or failures | 1 - Identification of alarms or failures
Continued from the previous page ABB | SACE Emax 2
The display is not backlit (if Current and/or voltages below the
Correct operating condition.
present) display switch-on limit
Current below the minimum
Incorrect current reading Correct operating condition.
threshold that can be displayed
Incorrect connection between Check the connections between
Incorrect voltage, power and isolation transformer and Ekip the isolation transformer and Ekip
cos φ reading Measuring Measuring
Voltage parameter setting error Set the correct parameters
The expected trip does not Correct operating condition. Enable
Trip excluded
occur trip if necessary
No activation of the Voltage
Values outside range Correct operating condition.
unbalance protection (VU)
No auxiliary power supply and/or
Opening data not displayed Correct operating condition.
battery low
Correct operating condition, reset
The password is not The password was disabled or
the password with a value other than
requested already inserted recently
“00000”
Impossible to change any of
Trip unit in alarm condition Correct operating condition.
the parameters
315 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Alarms or failures | 1 - Identification of alarms or failures
ABB | SACE Emax 2
Faults signalled on the display The following is a list of faults that can be detected from the display and the suggestions for resolving them:
Signal Suggestions
No Com on Local Bus Local bus enabled bus but no module present: check connection to
warning terminal box modules (example: Ekip Supply, Com, Contact, ecc...)
Trip coil disconnected Check the connection of the opening solenoid
Contact Wear PreAlarm/
Make sure that the contacts/poles are in good condition.
Alarm
L1/L2/L3/Ne sensor
Check the connection of the current sensor
disconnected
Gext sensor Disconnected Check the connection of the current sensor
Check the connection of the Rating Plug on the front of the trip unit and
Rating Plug Error
verify that the protections do not cause parameter configuration conflicts
Internal Error Contact ABB
Invalid Date Set the date
CB Status Error Check the circuit-breaker status signal contacts
Rating Plug Installation
Install Rating Plug, and in the case of faults check its connection
Warning
Switchboard Actors
Check the configuration and connection of the Ekip Link modules
Communication Error
Battery Low Change the battery on the trip unit (1)
(1)
Further information is available on the website http://www.abb.com/abblibrary/DownloadCenter/, where the
procedure is available 1SDH001000R0509.
Consult the individual chapters describing the modules for fault finding and resolving with regard to Ekip Com
modules.
316 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Alarms or failures | 1 - Identification of alarms or failures
ABB | SACE Emax 2
1 - Presentation
Objectives Routine maintenance has always been considered a good way to maintain a high level of efficiency in the
installation, but it is also a cost item linked to the frequency with which it is performed.
Maintenance work can be promptly organized thanks to application of the new digital technologies and
constant monitoring of the vital parameters of the circuit-breaker during normal daily operation.
The ability to estimate the exact time that maintenance must be performed optimizes all aspects concerning
maintenance itself: plant efficiency, management of costs and investments, continuity of service.
This condition is known as predictive maintenance.
Proposal In ABB low voltage air circuit-breakers, the system that monitors and identifies the moment in which
maintenance is required is made available thanks to Predictive Maintenance in ABB Ability EDCS.
When it is connected to Cloud, the circuit-breaker continuously transmits a set of data which, once organized
and analyzed by algorithms, supply a trend with the state of aging of the circuit-breaker.
Operating principle The main factors that influence circuit-breaker aging are:
• The number of electrical and mechanical openings (switches).
• The interrupted current (%In, short-circuit, overload, etc...).
• Environmental factors such as temperature, humidity, dust, corrosion, ...
Constant evolution of these data and their combination affect circuit-breaker aging, which can be more or
less rapid.
An indication of the condition of the circuit-breaker and, above all, of the date when maintenance should next
be performed can be obtained by monitoring these data by means of Predictive Maintenance in ABB Ability
EDCS.
If something happens to the circuit-breaker during its normal operation, this data item is updated as a
consequence.
317 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Predictive analysis program | 1 - Presentation
ABB | SACE Emax 2
2 - Service offers
LEAP Easy Audit On the basis of the environmental and specific operating conditions of the circuit-breaker in different types of
installation, LEAP AUDIT EASY provides a simple analysis using statistical data for the purpose of obtaining
an estimation of the conditions of the circuit-breaker itself.
LEAP EASY AUDIT can be performed by the actual client, free of charge, after registration in the dedicated
WEB page (link).
Procedure
1. The client registers in the dedicated WEB page (link). (link).
2. Waiting for mail with credentials to access software online and directly enter certain data concerning
use of the circuit-breaker (serial number of circuit-breaker, application, average annual environmental
conditions and number of operations (opening sequences) since installation).
3. Once this general information has been entered, the customer received a report via mail describing
the condition of his circuit-breaker.
The result is an analysis purely based on statistical data in the absence of access to the complete operating
data of the circuit-breaker.
Predictive maintenance in ABB A section dedicated to predictive maintenance can be activated in ABB Ability EDCS and used to supervise
Ability EDCS the conditions of the ABB air circuit-breakers connected in ABB Ability EDCS.
If a maintenance contract has been drawn up with ABB service, evidence of maintenance efficacy will also
be apparent in ABB Ability EDCS.
318 | © 2018 ABB | 1SDH001330R0002 - ECN000086018 - Rev. B Predictive analysis program | 2 - Service offers
ABB | SACE Emax 2
Service
1 - Power Care
Foreword The number of devices that make up an electrical installation varies so greatly that it can be difficult to
manage them, even for a very expert installation manager.
To ensure the availability and reliability of electrification systems, ABB offers PowerCare, a wide range
of service packages tailored to the type of company, with custom support solutions based on customer
requirements.
Description The PowerCare platform is based on a matrix of services that the customer selects, according to his own
needs, when the service contract is activated. The proposed services range from the possibility of having
dedicated access, through a portal PowerCare, to a complete range of support services for each type
switchgear and controlgear.
All the services are supplied by qualified and certified ABB personnel.
Services The PowerCare matrix consists of 20 products subdivided into five service areas and four levels:
Service Area Each service area represents a service offered by ABB technical support:
Levels The levels represent the extent of the service offered: the higher the level the greater the expertise of the
service and of the ABB design engineers put at the disposal of the customer to support him.