Untitled
Untitled
Untitled
Professor
In addition, temporary overvoltages are the basis for the
selection of the surge arrester ratings. From both points of
view low temporary overvoltages have to be aimed for. Per
unit values of 1.3 or even less are considered suitable.
Temporary overvoltages may also occur due to resonance
and ferro-resonance phenomena in particular when
energizing transformers via longer lines or de-energizing
inductive voltage transformers. These voltages can last for
more than 10 s. Therefore a sufficient damping of the
oscillation has to be obtained.
B. Slow Front Overvoltages
For UHV systems overvoltages due to earth-fault
initiation and clearance are of predominant importance.
Overvoltages due to earth-fault initiation occur on the
unfaulted phases and may cause a subsequent failure on
these phases. The consequence could be loss of two lines at
one earth-fault.
Overvoltage due to fault clearing occurs on the faulted
phase, when the faulted line is switched off. A subsequent
insulation failure may occur on the part of the system still in
operation.
Both these types of overvoltages should be carefully
investigated for a given system, because they cannot be
avoided by protection means. The amplitude of such
overvoltages are proportional to the earth-fault factor and
may reach 1.5 p.u for earth-fault factors of 1.25 to 1.3.
Overvoltages due to energization and, in particular, reenergization of overhead lines after faults are limited by preinsertion resistors or point-of-wave switching. An especially
severe situation is obtained for three-phase re-energization
due to the trapped charges remaining on the two unfaulted
phases, when the fault is cleared. There are two possibilities
to avoid such trapped charges:
- Single-phase reclosing
A. Technical Parameters
For evolving parameters of the 1200kV System,
simulation studies have been carried out using frequency
dependent line modeling in EMTP and the basic parameters
are given below.[5][10-11] The technical parameters being
considered for 1200kV Transmission Lines are summarized
in Table-I below:
TABLE I
TECHNICAL PARAMETERS CONSIDERED FOR 1200KV
TRANSMISSION LINES
Sr. No.
1
2
3
4
5
6
Parameters
Nominal Voltage
Highest Voltage
Resistance
Reactance
Susceptance
Surge Impedance
Loading
7
Surge Impedance
Base KV: 1200 KV
Value
1150 KV
1200 KV
4.338 x10-7 p.u./km
1.772 x10-5 p.u./km
6.447 x10-2 p.u./km
6030 MW
239 Ohm
Base MVA: 100 MVA
700
1.78
1.58
1.52
Residual Voltage
(kV peak)
1380
1440
1500
1600
1700
= 2x5MJ +35MJ + 10 MJ = 55 MJ
The basic technical parameters considered for designing
insulation coordination are listed in Table-V & the
technical parameter for four column ZnO surge arrester are
listed in Table-VI below.
Parameters
Rated Voltage
Nominal Voltage
Rated Frequency
Fault Current
Lightning
Impulse Voltage
Level
Value
1200 KV
1150 KV
50 Hz.
50 KA
2400 kV
2250 KV
2550 KV
Switching
Impulse Voltage
Level
One Minute
Power Frequency
Voltage
1800 KV
1950 KV
1200 kV
Remarks
Switchyard equipments
Transformers & Reactors
Transformer & Reactor
Bushings
Switchyard Equipments
and Transformers
Bushings
TABLE-VI
TECHNICAL PARAMETERS FOR ZnO SURGE ARRESTER
Parameter
Value
SA Class
Rated Voltage
Continuous Operating
Voltage(COV)
Nominal discharge current
Lightning Impulse Protective
Level(LIPL)
Switching Impulse Protective
Level(SIPL)
Energy level
ZnO disc diameter
5
850 kV rms
723 kV rms
V. CONCLUSIONS
a) For designing Insulation Coordination of UHV Line,
besides the continuous power-frequency voltage,
temporary overvoltages and transient overvoltages like
slow front overvoltage, fast front overvoltage & very
fast front overvoltage have to be considered.
b) For IC, determination of stresses and the assessment of
the strength of the system and the equipment installed is
required & methods of reducing the stress should also be
examined.
c) It is appropriate to use and develop Frequency dependent
Line models for a specific range of frequencies &
various power system elements are modeled using
EMTP.
d) The simulation results of designing 450 KM line indicate
satisfactory per unit limits for switching & temporary
Overvoltages.
e) Finally the selection of Insulation level & the role of
surge arrester is suggested.
20 kA
1700 kV peak at 20
kA
1500 kV peak at 2
kA
55 MJ
136 mm/ 125mm
VI. REFERENCES
[1] R N Naik, Y K Sehgal, Subir sen, Integration of 1200 KV AC
Systems for future Indian Grid (IEC/ CIGRE UHV Symposium
Beijing, 2007)
[2] C.Neumann K.-H. Weck, Planning of UHV systems with respect to
insulation coordination, IEC/CIGRE UHV Symposium Beijing 1821 July 2007.
[3] K.H. Schilling, E.Lerch, A.Luxa, UHV AC Transmission Systems
(IEC / CIGRE UHV Symposium Beijing, 2007)
[4] R. Nayak, M. Krishnakumar, A. Anand, Design of 1200 kV
transmission line (GridTech Conference, New Delhi 2007)
[5] R N Naik, M.C.Bhatnagar, B.N.De.Bhowmick R.K.Tyagi, 1200kV
Transmission System and Status of Development of Substation
Equipment/ Transmission Line Material in India, Second
International Symposium on Standards for UHV Transmission-IEC/
CIGRE UHV Symposium New Delhi, 2009.
[6] Andrew. R. Hileman, Insulation Coordination for power systems,
Taylor & Francis group, LLC, 1999.
[7] Juan. A Martinez- Velasco, Power System Transients- Parameter
Determination, CRC Press- Taylor & Francis Group, Boca Raton,
New York.
[8] Neville Watson, Jos Arrillaga, Power Systems Electromagnetic
Transients Simulation,
The Institution of Engineering &
Technology, London, UK, 2007.
[9] Juan.A Martinez- Velasco, Ferley Castro- Aranda, Modeling of
Overhead Transmission Lines for Lightning Studies, International
Conference on Power Systems Transients (IPST05) in Montreal,
Canada, on June 19-23, 2005 Paper No. IPST05 047.
[10] G.N.Alexandrov, 1100 kV overhead transmission line optimum
design for the increase of its reliability, IEC/CIGRE UHV
Symposium Beijing 18-21 July 2007.
[11] A.Ametani, N. Nagaoka, T.Noda, T.Matsuura, A Simple & Efficient
Method for Including A Frequency-Dependent Effect in A
Transmission Line Transient Analysis.
[12] E. Kuffel, W.S. Zaengl & J. Kuffel, High Voltage Engineering
Fundamentals , Newnes Oxford, Woburn, MA.
[13] A. Haddad & D. Warne, Advances in High Voltage Engineering,
The Institution of Electrical Engineers, London, United Kingdom.
[14] A.P. Sakis Meliopoulos, Power System Grounding and Transients,
Marcel Dekker,Inc.; Newyork and Basel.