SGP Assignment Questions & Answers (Unit-5)
SGP Assignment Questions & Answers (Unit-5)
UNIT-V
1. (a) Distinguish the valve type and zinc oxide lighting arresters.
Valve type lightning arrester (Non Linear Surge Diverter):
(i) The spark gap is a multiple assembly consisting of a number of identical spark
gaps inseries. Each gap consists of two electrodes with fixed gap spacing. The
voltage distributionacross the gaps is linearised by means of additional resistance
elements (called gradingresistors) across the gaps. The spacing of the series gaps is
such that it will withstand thenormal circuit voltage. However, an overvoltage will
cause the gap to breakdown, causingthe surge current to ground via the non-linear
resistors.
(ii) The non-linear resistor discs are made of an inorganic compound such as
Thyrite or Metrosil.These discs are connected in series. The non-linear resistors
have the property of offeringa high resistance to current flow when normal system
voltage is applied, but a low resistanceto the flow of high-surge currents. In other
words, the resistance of these non-linearelements decreases with the increase in
current through them and vice-versa.
Advantages:
(i) They provide very effective protection (especially for transformers and cables)
against surges.
(ii) They operate very rapidly taking less than a second.
(iii) The impulse ratio is practically unity.
Breakdown Voltage under surge conditions
Impulse ratio =
Breakdown Voltage under low frequency conditions
1|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
Limitations:
(i) They may fail to check the surges of very steep wave front from reaching the
terminal apparatus. This calls for additional steps to check steep-fronted waves.
(ii) Their performance is adversely affected by the entry of moisture into the
enclosure. This necessitates effective sealing of the enclosure at all times.
Applications:
According to their application, the valve type arresters are classified as (i)
station type and (ii) line type. The station type arresters are generally used for the
protection of important equipment in power stations operating onvoltages upto 220
kV or higher. The line type arresters are also used for stations handling voltages
upto 66 kV.
Metal oxide surge arrester (MOA):The metal oxide surge arrester abbreviated
as MOA is a recently developed ideal surge arrester. It is a revolutionary advanced
surge protective device for power systems. It is constructed by a series connection
of zinc oxide (ZnO) elements having a highly non- linear resistance. The excellent
non-linear characteristic of zinc oxide element has enabled to make surge arresters
without series connected spark gaps, space i.e., fully solid-state arresters suitable
for system protection upto the highest voltages.
The main constituent of the ceramic material is zinc oxide, the non-
linear resistor made of this material is popularly known as zinc oxide element and
surge arresters made of zinc oxide elements are called metal oxide surge arresters.
Such material can be used to make resistors with a much higher degree of non-
linearity over a large current range. With such resistors, one can design arresters
having voltage-current characteristics very close to ideal. Because of the high
degree of non-linearity, this material allows considerable simplification in arrester
(diverter) design.
2|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
The metal oxide surge arrester has the following advantages over conventional
arrester.
Curve A is the volt-time curve of the protective device and curve B is the
volt-time curve of the equipment to be protected. Form volt-time curves A and B of
FIG. it is clear that any insulation having a voltage withstanding strength in excess
3|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
2. What are the causes of over voltages arising in a power system? Why
is it necessary to protect the lines and other equipment of the power
system against over voltages?
The normal operating voltages of the system do not stress the insulation.
But the voltage stresses due to over voltages can be high that they may become
dangerous to both the lines as well as the connected equipment and may cause
damage, unless some protective measures against these over voltages are taken.
Over voltages arising on a power system can be generally classified into two main
categories as follows.
Atmospheric disturbances, mainly due to lightning are the main reasons for over
voltages. These over voltages take the form of unidirectional impulse (surge) whose
amplitude is independent of the operating voltage of the system. These are caused
due to:
These overvoltages are caused due to switching operation or fault condition. These
overvoltages are generally oscillatory and take the form of a damped sinusoidal.
The frequency of these overvoltages may vary from few hundred Hz to few kHz and
it is governed by the inherent capacitances and inductances of the circuit like
switching of HV reactors and switching of a transformer at no load.
4|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
Overvoltage factor is defined as the ratio of the peak overvoltage to the rated peak
system frequency phase voltage. This is also termed as amplitude factor.
INSULATION COORDINATION:
Curve A is the volt-time curve of the protective device and curve B is the
volt-time curve of the equipment to be protected. Form volt-time curves A and B of
FIG. it is clear that any insulation having a voltage withstanding strength in excess
of the insulation strength of curve B will be protected by the protective device of
curve A.
VOLT-TIME CURVE:
5|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
voltage. The volt-time curve is a graph of the crust flashover voltages plotted
against time to flashover for a series of impulse applications of a given wave shape.
The construction of the volt-time curve and the terminology associated with
impulse voltage testing are shown in fig.
6|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
1) Earthing screen
2) Overhead ground wires
3) Lightning arresters or Surge diverters
7|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
When the direct lightning stroke occurs on the transmission line, it will
be taken up by the ground wires. The heavy lightning current (10 kA to 50 kA) from
the ground wire flows to the ground, thus protecting the line from the harmful
effects of lightning. It may be mentioned here that the degree of protection provided
by the ground wires depends upon the footing resistance of the tower. Suppose, for
example, tower-footing resistance is R1 ohms and that the lightning current from
tower to ground is I1 amperes. Then the tower *rises to a potential Vt given by:
Vt = I1R1
Advantages:
Disadvantages:
3) Lightning Arresters:
The earthing screen and ground wires can well protect the electrical
system against direct lightning strokes but they fail to provide protection against
travelling waves which may reach the terminal apparatus. The lightning arresters
or surge diverters provide protection against such surges.
8|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
Fig.(i) shows the basic form of a surge diverter. It consists of a spark gap in series
with a non-linear resistor. One end of the diverter is connected to the terminal of
the equipment to be protected and the other end is effectively grounded. The length
of the gap is so set that normal line voltage is not enough to cause an arc across
the gap but a dangerously highvoltage will break down the air insulation and form
an arc. The property of the non-linear resistance is that its resistance decreases as
the voltage (or current) increases and vice-versa. This is clear from the *volt/amp
characteristic of the resistor shown in Fig (ii).
(i) Under normal operation, the lightning arrester is off the line i.e. it conducts no
current to earth or the gap is non- conducting.
(ii) On the occurrence of overvoltage, the air insulation across the gap breaks down
and an arc is formed, providing a low resistance path for the surge to the ground.
In this way, the excess charge on the line due to the surge is harmlessly conducted
through the arrester to the ground instead of being sent back over the line.
(iii) It is worthwhile to mention the function of non-linear resistor in the operation of
arrester. As the gap sparks over due to overvoltage, the arc would be a short-circuit
on the power system and may cause power-follow current in the arrester. Since the
characteristic of the resistor is to offer high resistance to high voltage (or current),
it prevents the effect of short-circuit. After the surge is over, the resistor offers high
resistance to make the gap non-conducting. Two things must be taken care of in
the design of a lightning arrester. Firstly, when the surge is over, the arc in gap
should cease. If the arc does not go out, the current would continue to flow through
the resistor and both resistor and gap may be destroyed. Secondly, I R drop (where
I is the surge current) across the arrester when carrying surge current should not
exceed the breakdown strength of the insulation of the equipment to be protected.
(i) The spark gap is a multiple assembly consisting of a number of identical spark
gaps inseries. Each gap consists of two electrodes with fixed gap spacing. The
voltage distributionacross the gaps is linearised by means of additional resistance
elements (called gradingresistors) across the gaps. The spacing of the series gaps is
such that it will withstand thenormal circuit voltage. However, an overvoltage will
cause the gap to breakdown, causingthe surge current to ground via the non-linear
resistors.
9|Page
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
(ii) The non-linear resistor discs are made of an inorganic compound such as
Thyrite or Metrosil.These discs are connected in series. The non-linear resistors
have the property of offeringa high resistance to current flow when normal system
voltage is applied, but a low resistanceto the flow of high-surge currents. In other
words, the resistance of these non-linearelements decreases with the increase in
current through them and vice-versa.
The main function of the surge diverter is the protection of the insulation against
dangerously high over voltages and for this reason the breakdown voltage of the
diverter at system frequency is made greater than 1.8 times the normal value.
Advantages:
(iv) They provide very effective protection (especially for transformers and cables)
against surges.
(v) They operate very rapidly taking less than a second.
(vi) The impulse ratio is practically unity.
Breakdown Voltage under surge conditions
Impulse ratio =
Breakdown Voltage under low frequency conditions
Limitations:
(iii) They may fail to check the surges of very steep wave front from reaching the
terminal apparatus. This calls for additional steps to check steep-fronted waves.
(iv) Their performance is adversely affected by the entry of moisture into the enclosure.
This necessitates effective sealing of the enclosure at all times.
10 | P a g e
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
Applications:
According to their application, the valve type arresters are classified as (i)
station type and (ii) line type. The station type arresters are generally used for the
protection of important equipment in power stations operating onvoltages upto 220
kV or higher. The line type arresters are also used for stations handling voltages
upto 66 kV.
A sudden rise in voltage for a very short duration on the power system is
known as a voltage surge or transient voltage.
Transients or surges are of temporary nature and exist for a very short
duration (a few hundred µs) but they cause overvoltages on the power system. They
originate from switching and from other causes but by far the most important
transients are those caused by lightning striking a transmission line. When
lightning strikes a line, the surge rushes along the line, just as a flood of water
rushes along a narrow valley when the retaining wall of a reservoir at its head
suddenly gives way. In most of the cases, such surges may cause the line
insulators (near the point where lightning has struck) to flash over and may
also damage the nearby transformers, generators or other equipment connected to
the line if the equipment is not suitably protected.
The voltage build-up is taken along y-axis and the time along x-axis. It may be seen
that lightning introduces a steep-fronted wave. The steeper the wave front, the
more rapid is the build-up of voltage at any point in the network. In most of the
cases, this build-up is comparatively rapid, being of the order of 1-5 µs. Voltage
surges are generally specified in terms of *rise time t1 and the time t2 to decay to
half of the peak value. For example, a 1/50 µs surge is one which reaches its
maximum value in 1µs and decays to half of its peak value is 50 µs.
11 | P a g e
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
dangerous to both the lines as well as the connected equipment and may cause
damage, unless some protective measures against these over voltages are taken.
Over voltages arising on a power system can be generally classified into two main
categories as follows.
Atmospheric disturbances, mainly due to lightning are the main reasons for over
voltages. These over voltages take the form of unidirectional impulse (surge) whose
amplitude is independent of the operating voltage of the system. These are caused
due to:
These overvoltages are caused due to switching operation or fault condition. These
overvoltages are generally oscillatory and take the form of a damped sinusoidal.
The frequency of these overvoltages may vary from few hundred Hz to few kHz and
it is governed by the inherent capacitances and inductances of the circuit like
switching of HV reactors and switching of a transformer at no load.
Overvoltage factor is defined as the ratio of the peak overvoltage to the rated peak
system frequency phase voltage. This is also termed as amplitude factor.
12 | P a g e
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
(i) Solid Grounding: When the neutral point of a 3-phase system (e.g., 3- phase
generator, 3-phase transformer etc.) is directly connected to earth through a wire of
negligible resistance and reactance, it is called solid grounding or effective grounding.
Advantages:
(ii) When earth fault occurs on any phase, the resultant capacitive current I C is in
phase opposition to the fault current IF. The two currents completely cancel each other.
Therefore, no arcing ground or over-voltage conditions can occur.
Fig.10
13 | P a g e
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
(iii) When there is an earth fault on any phase of the system, the phase to earth voltage
of the faulty phase becomes zero.
(iv) It becomes easier to protect the system from earth faults which frequently occur on
the system. When there is an earth fault on any phase of the system, a large fault
current flows between the fault point and the grounded neutral.
Disadvantages:
(i) The solid grounding results in heavy earth fault currents. Since the fault has to be
cleared by the circuit breakers, the heavy earth fault currents may cause the burning
of circuit breaker contacts.
(ii) The increased earth fault current results in greater interference in the neighbouring
communication lines
Applications: Solid grounding is used for voltages upto 33kV with total power capacity
not exceeding 5000kVA.
Resistance Grounding: When the neutral point of a 3-phase system (e.g., 3-phase
generator, 3-phase transformer etc.) is connected to earth through a resistor to limit
the fault current to a safe value, it is called Resistance Grounding.
Fig.11 shows the grounding of neutral point through a resistor R. The value of R should
neither be very low nor very high. If the value
of earthing resistance R is very low, the earth
fault current will be large and the system
becomes similar to the solid grounding system.
If the value of earthing resistance R is very
high, the system conditions become similar to
ungrounded neutral system.
Fig.11
Advantages:
(i) By adjusting the value of R, the arcing grounds can be minimized. Suppose earth
fault occurs in phase B as shown in Fig.12. The capacitive currents IR and IY flow in the
healthy phases R and Y respectively. The fault current IF lags behind the phase voltage
of the faulted phase by a certain angle depending upon the earthing resistance R and
the reactance of the system upto the point of fault. The fault current I F can be resolved
into two components: (a) IF1 in phase with the faulty phase voltage. (b) IF2 lagging
behind the faulty phase voltage by 90°.
14 | P a g e
SWITCHGEAR AND PROTECTION (20A02504a) – ASSIGNMENT QUESTIONS & ANSWERS
F
i
g
.
Fig.12
(ii) The earth fault current is small due to the presence of earthing resistance.
Therefore, interference with communication circuits is reduced.
Disadvantages:
(i) Since the system neutral is displaced during earth faults, the equipment has to be
insulated for higher voltages.
Reactance Grounding: In this system, a reactance is inserted between the neutral and
ground as shown in Fig.13. The purpose of reactance is to limit the earth fault current.
This method of grounding may be used for the
neutral of Synchronous Motors and also for
circuits having large charging currents.
Fig.13
15 | P a g e