Pem735 D00084 D Xxen
Pem735 D00084 D Xxen
Pem735 D00084 D Xxen
PEM735
PEM735_D00084_00_D_XXEN/06.2014
class
Product description
The digital universal measuring device PEM735 is suited for measuring and displaying
electrical quantities of electricity networks. The device measures currents and voltages,
energy consumption and power, and displays the individual current/voltage harmonics
for assessment of the power quality in accordance with DIN EN 50160. The accuracy of
active energy measurements corresponds to class 0.2 S in accordance with DIN EN
62053-22 (VDE 0418 part 3-22). The current inputs are connected via external /1 A or
/5 A measuring current transformers.
Typical application
Continuous monitoring of the voltage quality in accordance with DIN EN 50160
PEM735
Device features
Class A power analyser, certified according to DIN EN 61000-4-30
Monitoring the quality of the voltage in
accordance with DIN EN 50160
A
ccuracy class according to IEC 62053-22:
0.2 S
TFT colour display (640x480) 5.7
Modbus/RTU and Modbus/TCP
4 current inputs
5 voltage inputs
1 GB internal memory
Panel mounting 144x144
Integrated web server
Data export via FTP: comtrade, PQDIF
Flicker measurement
Detection and recording of transients (40 s)
Description of function
Sampling rate of the measuring channels: 25.6 kHz
Calculation of the total harmonic distortion THDU/THDI: harmonics up to the 63rd harmonic
Individual current/voltage harmonics
Password protection
History memory for minimum and maximum values of current, voltage, energy, power
rating etc. for each month.
Inputs and outputs:
6 digital outputs, 8 digital inputs (1 kHz sampling rate)
24 adjustable parameter setpoints
System protocol: 1024 events, setup changes, setpoint alarming, DI status changes,
DO switching operations
Communication:
Galvanically isolated RS-485 interface (1.200 to 19.200 bit/s)
Modbus/RTU protocol
Modbus/TCP (10/100 MBit/s)
Standards
The universal measuring device for Power Quality and Energy Measurement/PEM735 was
developed in accordance with the following standards: IEC 62053-22(VDE 0418 Part 3-22),
DIN EN 61557-12 (VDE 0413-12), DIN EN 50160, DIN EN 61000-4-30 (VDE 0847-4-30), DIN
EN 61000-4-7 (VDE 0847-4-7), DIN EN 61000-4-15 (VDE 0847-4-15)
IEC 61850
2 PEM735_D00084_00_D_XXEN/06.2014
Operating elements
1
PEM735
LINETRAXX
kWh
3 - Display
4 - " " button: Selection (in the menu)
5 - " " button: Up (in the menu)
6 - " " button: Down (in the menu)
ENTER
ESC
PEM7xx
PEM7xx
Ethernet
Datenbank
Modbus/TCP
Modbus/TCP
NSHV
L
PEN
CP700
PE
PAS
BMS
PEM5xx
PEM5xx
Modbus/TCP
RCMS
I
112
Modbus/TCP
Modbus/RTU
L
N
PE
Modbus/
RTU
Modbus/RTU
UV1
UV2
PEM3xx
Modbus/RTU
RCMS
PEM3xx
112
U
I
Modbus/RTU
PEM735_D00084_00_D_XXEN/06.2014 3
Wiring diagram
US
2
DO1+
DO1-
DO2+
DO2-
AC 400 V/230 V
AC 690V/400 V
DI1
DI2
DI3
DI4
DI5
DI7
DI6
DIC
DI8
L1
NC
L1
SH
D+
L4
L2
DSH
L3
DIC
RO13
DI1
RO14
DI2
RO23
DI3
RO24
DI4
RO33
DI5
RO34
DI6
RO43
DI7
RO44
NC
NC
D-
P1(RS-485)
D+
PEM
Three-phase 3-wire system
The PEM can be used in three-phase 3-wire systems.
Link
AC 690 V
DO1+
DO1DO2+
A1/+
Power
I32
l42
AC 400 V
10/100M
Ethernet
P3
l31
l41
l22
l21
Act
LED
l11
I12
DI8
L3
Ri
P2(RS-485)
L2
DO2-
A2/-
2
L1
I12
I22
I32
I21
I11
I31
I42
L2
L3
Ri
I41
L1
PEM
L2
L3
N
5
L1
L2
L3
L1
Ri
7 - Connection Ethernet
8 - Relay output
4 PEM735_D00084_00_D_XXEN/06.2014
PEM
L2
L3
Technical data
Insulation co-ordination
Interface
Measuring circuit
Rated insulation voltage
Overvoltage category
Pollution degree
Supply circuit
Rated insulation voltage
Overvoltage category
Pollution degree
Interface/protocol
Baud rate
Cable length
Shielded cable ((shield connected to PE on one side)
600 V
III
2
300 V
II
2
Supply voltage
Rated supply voltage US
Frequency range of US
Power consumption
95250 V
DC, 44440 Hz
11 VA
Measuring circuit
Measuring voltage inputs
UL1-N,L2-N,L3-N
400 V
UL1-L2,L2-L3,L3-L1
690 V
Measuring range
10 120 % Un
Rated frequency
4258 Hz
Internal resistance (L-N)
> 500 k
Measuring current inputs
External measuring current transformer,
should at least comply with accuracy class 0.2 S
Burden
n.A., internal current transformers
Measuring range
0.1 120 % IN
CT transformation ratio, secondary
15 A
CT transformation ratio, primary
130000 A
Accuracies (of measured value/of full scale value)
Phase voltage UL1-N, UL2-N, UL3-N
0.1 % of the measured value.
Current
0.1 % of measured value + 0.05 % of full scale value.
Frequency
0.005 Hz
Phase position
1
Active energy measurement acc. to
DIN EN 62053-22 (VDE 0418 Part 3-22)
R.m.s. voltage measurements acc. to
DIN EN 61557-12 (VDE 0413-12), chapter 4.7.6
R.ms. phase current measurements acc. to
DIN EN 61557-12 (VDE 0413-12), chapter 4.7.5
Frequency measurements acc. to
DIN EN 61557-12 (VDE 0413-12), chapter. 4.7.4
Measurement of the harmonics acc. to
DIN EN 61000-4-7 class A
2 x RS-485, Modbus/RTU
1.219.2 kbits / s
01200 m
recommended: J-Y(St)Y min. 2x0.8
InterfaceEthernet
Protocol
FTP, Modbus/TCP, IEC 61850
Baud rate
100 MBit/s
Switching elements
Outputs (RO)
4 x N/O contacts
Operating principle N/O operation
Rated operational voltage AC 230 V DC 24 V AC 110 V DC 12 V
Rated operational current
5A
5A
6A
5A
Minimum contact rating
1 mA at AC/DC 10 V
Inputs
8 electrically separated digital inputs
Imin
2.4 mA
UDI
DC 24 V
2 electronic outputs (DO)
max. 80 V
Imax 50 mA
Environment/EMC
EMC
Operating temperature
Climatic class acc. to DIN EN 60721
stationary use
Classification of mechanical conditions acc. to IEC 60721
stationary use
DIN EN 61326-1
-25+ 55 C
3K5
3M4
Connection
Connection
screw-type terminals
Other
Degree of protection, installation
Degree of protection, front
Documentation number
Weight
IP20
IP52
D00084
1100 g
PEM735_D00084_00_D_XXEN/06.2014 5
Ordering information
Nominal system voltage
3(N)AC
100690 V
Current input
Type
Art. No.
5A
PEM735
B 9310 0735
Dimension diagram
Panel cut-out
Dimensions in mm
Dimensions in mm
145
125
138
144
16
109
20
138
144
164
BENDERGroup
PEM735_D00084_00_D_XXEN / 06.2014 / pdf / Schw / Bender GmbH & Co. KG, Germany Subject to change! The specified standards take into account the current edition at the time of going to press.
140
144
14