Lighting design and engineering professionals are facing the challenge and
demand for energy conservation in buildings. Mandatory energy codes
requires lighting control in new buildings
Effective lighting control saves energy, reduces operating costs, and helps
maintain a safe and productive environment for occupants. Well designed and
installed, lighting control also provides convenience for occupants and
enhances productivity.
Designing an optimal lighting control system may often incorporate several
types of controls as well as different control strategies to achieve an integrated,
total-facility approach
1.
Applications needed
2.
3.
4.
5.
What application
Installation
Control strategy
Documentation
Product selection
The starting point for any project is the need to understand the motivation,
reasons, and characteristics of the application involved.
Energy conservation
Many building owners and facility managers want to reduce operating costs by
minimizing energy expenses as much as possible while ensuring the comfort and
safety of facility occupants.
Occupant convenience and preference
Ensuring that occupants have a convenient and accessible personal control over
local lighting which enhances occupant satisfaction and productivity.
Safety and security
Ensuring that facility lighting always is safe and secure for occupants and visitors.
Maintenance and administration
Providing the facilities management staff with the necessary controls and tools to
effectively manage the facility.
1.3 Step 2
Appropriate control
strategies -
At this point, designers should select the appropriate control strategy that best
fits with the applications needs. Since most buildings contain numerous spaces
housing different activities, multiple strategies may be desirable to meet the
specific needs of all the different space types.
Some applications may need only a single product implementing a simple
strategy, such as a time switch providing timed ON/OFF control. In other
applications, designers may combine several control methods. For instance, office
spaces may benefit from time-based ON/OFF control during regular work hours,
supplemented by occupancy-based control after hours.
Step 2 Appropriate
control strategies (cont)
1.4 Step 3
Selecting control
products
These guidelines can help designers match up the best product for
achieving a specific control strategy.
Scheduler
controls relays to turn lighting off according to a programmed schedule.
Recommended applications:
Applications where it is desirable to keep lighting on during hours of
normal business or space usage.
Lobbies, corridors, public spaces, retail sales floor, some open offices.
Time switch
Wall switches turn on manually and then turn off automatically after a preset
interval.
Recommended applications:
Spaces with infrequent activities or where occupancy sensors may not
be able to perform consistently
Store rooms, mechanical and electrical rooms, supply closets, janitorial
spaces.
Step 3 Selecting
control products
cont
Manual switches
These are available in a variety of types and technologies:
Line voltage switches control power directly to fixtures.
Low voltage or bus switches, signal occupancy sensors
Wall switch occupancy sensors (P.I.R.) combine occupancy based shutoff with
manual ON/OFF and preset control
Time switch combines timed shutoff with manual ON/OFF
Manual switches work in conjunction with shutoff, day lighting and other control
strategies.
Step 3 Selecting
control products
cont
Once the product selection is complete, the designer will lay out the control
devices on the general lighting plan drawings.
Different lighting control products require specific design details. For instance,
with occupancy sensors, plans should include placement location of individual
sensors as well as the coverage area of each. For switches, plans should indicate
location and control assignment. For day lighting controls, plans should include
photocell placement as well as the desired lux settings for each covered area.
When lighting control panels are used, designers should prepare riser diagrams
and control schedules. This documentation will assist the designer in preparing a
specification that unifies the entire plan.
10
2 Lighting
We see things every day, from the moment we get up in the morning
until we go to sleep at night. We look at everything around us using
light. We appreciate fine oil paintings, swirling computer graphics,
gorgeous sunsets. But did you ever stop to think that what we see is
light-- light that somehow left objects far or near and reached our eyes.
Light is all our eyes can really see.
The other way that we encounter light is in devices that produce light -incandescent bulbs, fluorescent tubes, lasers, lightning bugs, the
sun. Each one uses a different technique to generate light.
Lighting includes both artificial light sources such as lamps and
natural illumination of interiors from daylight. Lighting represents a
major component of energy consumption, accounting for a significant
part of all energy consumed worldwide. Proper lighting can enhance
task performance or aesthetics, while there can be energy wastage and
adverse health effects of lighting. Indoor lighting is a form of fixture or
furnishing, and a key part of interior design. Lighting can also be an
intrinsic component of landscaping.
11
2.1 Color
temperature
1850 K: Candle
4100 K: Moonlight
5000 K: Daylight
6500 K: Daylight
12
2.2 Comparission
Fluorescent vs
Incandescent
Effiiciency
100 %
20 %
Life span
15x1000 h
13
15000 h
2.4 Lumen
The lumen (symbol: lm) is the SI unit of luminous flux, a measure of the
perceived power of light
2.5 Lux
14
Illumenance is measured in lux, one lux is one lumen per square meter.
2.6 Illuminance
Light Level or Illuminance, is the amount of light measured in a plane. The work
plane is where the most important tasks in the room or
space are performed.
Earlier it was common with light levels in the range 100 - 300 lux for normal
activities. Today the light level is more common in the range
500 - 1000 lux - depending on activity. For precision and detailed works, the
light level may even approach 1500 - 2000 lux.
15
16
Incandescent lamp
Halogen lamp
Halogen lamps are high pressure, incandescent lamps that contain halogen
gases such as iodine and bromine that allow filaments to work at higher
temperatures and higher efficiencies. Halogen lamps consist of a tungsten
filament inside a quartz envelope that is filled with halogen gas. In halogen
lamps, the quartz envelope is closer to the filament than the glass used in
conventional light bulbs. Heating the filament to a high temperature causes
the tungsten atoms to evaporate and combine with the halogen gas. These
heavier molecules are then deposited back on the filament surface. This
recycling process increases the life of the tungsten filament and enables the
halogen lamp to produce more light per units of energy.
17
Compact
fluorescent lamp
Fluorescent tube
A fluorescent tube is a gas-discharge lamp that uses electricity to excite
mercury vapor in argon or neon gas, resulting in a plasma that produces
short-wave ultraviolet light. This light then causes a phosphor to fluoresce,
producing visible light.
Unlike incandescent lamps, fluorescent lamps always require a ballast to
regulate the flow of power through the lamp. In common tube fixtures
(typically 4 ft (120 cm) or 8 ft (240 cm) in length), the ballast is enclosed in
the fixture. Compact fluorescent light bulbs may have a conventional ballast
located in the fixture or they may have ballasts integrated in the bulbs,
allowing them to be used in lampholders normally used for incandescent
lamps.
Compact fluorescents may fail to operate at low temperatures. Light output
drops at low temperatures, and they may not light at all below zero
degrees C0 They also suffer shortened life when switched on and off
frequently. Incandescent bulbs operate well with no loss of brightness at
extremely low or high temperatures and can better withstand frequent
turning on and off, as in security light applications. Manufacturers of compact
fluorescents warn against using ordinary CFLs to replace incandescent bulbs
in enclosed fixtures or those which are controlled by dimmers. Dimming
fluorescent lamps requires lamp ballasts designed for dimming.
18
19
White SON
A variation of the high pressure sodium, the White SON, introduced in
1986, has a higher pressure than the typical HPS lamp, producing a color
temperature of around 2700K, with a CRI of 85; greatly resembling the color
of incandescent light. These are often indoors in cafes and restuarants to
create a certain atmosphere. However, these lamps come at the cost of higher
purchase cost, shorter life, and lower light efficiency.
All gas discharge lamps, including fluorescent lamps, require a control gear
to operate. The control gear provides a high initial voltage to initiate the
discharge, then rapidly limits the lamp current to safely sustain the discharge.
Necessity for current limiting
Control gears are most commonly needed when an electrical circuit or device
presents a negative resistance to the supply. Examples of such negativeresistance devices are gas discharge tubes and lamps. If such a device
were connected to a constant-voltage power supply, it would draw an everincreasing amount of current until it was destroyed or caused the power
supply to fail. To prevent this, a ballast provides a positive resistance or
reactance that limits the ultimate flow of current to an appropriate level.
20
Transformers
Magnetic transformers are made with an iron or ferrite core and multiwound coil system; commonly called a coil-core transformer. These devices
transform the voltage in a predictable way using magnetic coupling.
Electronic transformers are generally made of an inverter and a smaller
transformer. Due to the design and manufacturing of electronic transformers,
the characteristics and performance can not always be predicted
3.3 Dimming
Principles
Shaded area
lights OFF
Shaded area
lights OFF
21
Universal dimmers
Adaptive Dimmers solves all the load compatibility problems inherent in loads
controlled by both triac and transistor dimmers.In universal dimmer, both
the voltage and the current are monitored, and this is linked into the CPU
which controls the dimmers operating parameters. When the adaptive source
controller sees an inductive load, it adopts a leading edge dimmingmode. In
case of overload the device is automatically switched off.
3.4 Special
requirement at
switching and
dimming
Fluorescent lights
switching
Fluorescent lights
dimming
Fluorescent lamps can also be dimmed when used with a dimming ballast.
Not all ballasts are dimmable, but all can be switched. Digital controlled
ballast are becoming more available on the market. There are a few
different protocols from several different manufacturers. DALI or Digitally
Addressable Lighting Interface, DSI, LON, DMX512, and KNX are a few of
the digital control methods. Some devices can only be dimmed to a certain
level and also require a minimum turn on level. The minimum turn on level
is determined by the ballast. Turning it on or dimming below this level can
cause flickering and premature lamp failure. Consult the manufacturer
to determine the dimming performance of any ballast used in a dimming
system.
It is not recommended to mix different loads on a dimmer like incandescent
with magnetic or electronic ballasts. There is an increased possibility of bad
performance, along with more complicated trouble shooting. There should
be a positive disconnection from power when the dimmer is off to prevent
a voltage leaking to the ballast. Ballast manufacturers recommend this
practice for maximum safety. It is recommended that a circuit with ballasts
not exceed 80% capacity. It is standard practice to derate the dimmer to
80% or less. If the dimmer is rated at 500W, then the connected fluorescent
load should be 400W or less.
22
Transformers
switching on/off
Transformers
Dimming
23
4 Applications
Occupancy Control
Scheduling
Constant Light Control
Dali Dimming Control
Shutter Control
24
4.1 Introduction
Reducing the connected load (wattage) of the lighting system represents only
half of the potential for maximizing energy savings. The other half is minimizing
the use of that load through automatic controls. Automatic controls switch or dim
lighting based on time, occupancy, lighting-level strategies, or a combination of
all three. In situations where lighting may be on longer than needed, left on in
unoccupied areas, or used when sufficient daylight exists, you should consider
installing automatic controls as a supplement or replacement for manual controls.
Controls can be hard-wired or wireless. Most hard-wired controls rely on lowvoltage bus wiring for signal transmission. However, there are a few products
on the market that transmit signals over standard wiring (and therefore require
no additional wiring). Some systems are plug and play while other systems typically ones that provide the most flexibility - require design and programming
by the installer. Central lighting control systems can be zoned to provide
pre-programmed lighting levels (often called scenes) for different situations.
Examples of modes that may be preprogrammed are use of video-beamer in
conference rooms.
A manual-on occupancy sensor is a wall switch that will allow regular on and
off switching of lights and can be used as an electronic occupancy sensor, as
well. The occupancy sensor operates on low frequency sound waves or infrared
signals that can sense movement in an area. After a prescribed time delay of six
to fifteen minutes, dependent upon manufacturer or local preset, the sensor will
turn off the light if movement has not been detected.
25
Dimmer switches can allow one fixture to serve several lighting functions, such
as task lighting at full ballast and decorative or safety lighting on a lower setting.
Dimming increases lamp life and saves energy - a light that is dimmed by 25%
uses about 20% less energy while lamp life is increased fourfold.
Lighting in a commercial office building often accounts for at least 40% of the
total electricity used. Simply switching off lighting when it is not required results
in substantial energy savings. Regardless of the amount of automation used for
lighting control in a given application, the ability to manually override lighting is
often an important element in the overall design. =S= controls offer a variety of
choices for manual override of lighting in systems including simple low voltage
wall switches and networked button stations
26
4.2 Occupancy
Control
Occupancy sensors provide effective lighting control for smaller areas within the
building that are occasionally utilized. They can also be used to provide automatic
override of schedules for after-hours usage by occupants or cleaning crews.
Using occupancy sensors as part of a system allows independent sensing zones
to be functionally linked or separated as appropriate based on the time of day.
The occupancy sensors may also simply be deactivated during normal business
hours and reserved for after-hours override operation. Further, when sensors are
used as part of the LON system, occupancy status can be easily shared with the
Building Automation System to direct HVAC and other non-lighting functions.
Open Office Area
Scheduled Zone Control
General illumination for open office areas is controlled by the system on a
zone basis. Lighting automatically comes on in the morning to greet arriving
employees, in areas where light level is sufficient and no occupancy registered
the lights will turn off after a delay until occupancy is registered . At the end of
the workday, if no occupancy registered, lighting is automatically switched off.
The potentially harmful effects of inrush generated by switching large fluorescent
loads is nullified by the =S= control systems zero-cross switching technology.
Manual Zone Control
Manually switching on lighting in the morning, and when no occupancy
registered, the light is switcht off maximizes energy savings and eliminates the
need to program holidays into the schedule. To prevent tampering, the switch is
disabled during normal work hours. Later in the evening, the cleaning crew uses
the same switch to turn on lighting for a programmed period of time.
Occupancy-Based Override
Occupancy sensors provide automatic override of lighting during after-hours
periods, eliminating the need for manual override by employees or the cleaning
crew. Sensor operation is automatically limited to after-hours operation by =S=
controls. Adjacent sensor zones are logically linked for simultaneous operation to
eliminate the discomfort of a lone employee working in a small pool of light.
Private Office
Distributed Personal Control
Desk lamps are used and controlled by the occupant as task lighting. The general
lighting is controlled by a sensitive presence detector which covers the whole
office area and will automatically shut off, or in case of dimming, dim the lighting
to a un-occupancy level. All stations for an entire floor share a single network
wire. Since the signals for the dimming ballasts and the local relay packs are
provided directly by the station, no additional home run wiring is required.
27
Occupancy Reporting
Energy savings in small areas like offices is maximized through the use of
occupancy sensors. Lighting is automatically turned off when the occupant leaves
the office for an extended length of time. Since the =S= control system has
visibility of the occupancy status, it can be passed on to the HVAC controls via
the LonTalk protocol.
Infrequently used spaces
Occupancy sensors are ideal in infrequently used spaces like bins, toilets, and
corridors. Lighting is automatically turned on when the occupant enters the
space. Adjacent sensor zones are logically linked for simultaneous operation to
eliminate dark spots in wider areas.
About Occupancy Sensing
Occupancy-based strategies are best suited to spaces that have highly variable
and unpredictable occupancy patterns. Occupancy or motion sensors are used
to detect occupant motion, lighting the space only when it is occupied. For both
initial and sustained success in using occupancy sensors, the sensor must be able
to see the range of motion in the entire space while avoiding either on or off false
triggering. This requires proper product selection, positioning, and testing.
Occupancy sensors should first be selected based on the range of body motion
expected to occur throughout the entire lighted space.
Controls for hallways, for example, need only be sensitive to a person walking
down a narrow area, while sensors for offices need to detect smaller upper body
motion, such as typing or reaching for a telephone. Once sensitivity and coverage
area is established, sensors are selected from two predominant technology types.
Passive infrared sensors detect the motion of heat between vertical and
horizontal fan pattern detection zones. This technology requires a direct line of
sight and is more sensitive to lateral motion, but it requires larger motion as
distance from the sensor increases. The coverage pattern and field of view can
also be precisely controlled. It typically finds its best application in smaller spaces
with a direct line of sight, warehouses, and aisles.
28
Application description
Occupancy controlled general lighting with time based override possibilities.
Single-occupant office. Primary activities are computer work, reading and
meetings.
Control needs
ON/OFF control with light level sensing. The sensor should be able to detect small
movements such as typing.
29
4.3 Scheduling
30
About Scheduling
The most basic controlling strategies involve time-based controls, best suited
for spaces where lighting needs are predictable and predetermined. Time-based
controls can be used in both indoor and outdoor situations. Common outdoor
applications include automatically switching parking lot or security lighting based
on the sunset and sunrise times. Typical indoor situations include switching
lighting in production, manufacturing, and retail facilities that operate on fixed,
predefined operating schedules. Time-based control systems for indoor lighting
typically include a manual override option for situations when lighting is needed
beyond the scheduled period.
31
Application description
Control of general lighting in spaces which has a predetermined usage.
For security reasons some areas may need to have a decreased light
level. Time-based control can be used both inside and outside.
Control needs
ON/OFF and/or dimming control with manual or automatic override
possibilities
32
The TAC Xenta 511 is a web based presentation system for LONWORKS networks.
Using a standard web browser, the operator can easily view and control the
devices in the LON network via Internet or a local intranet. One TAC Xenta 511
can present a small LON network or be one of several local presentation devices
in a larger network. Time schedules and trend logs are easily accessed. For
setting see data sheet
33
34
Application description
Control of general lighting with an automatic control that replaces or
accompanies occupant control, in order to conserve energy, by switching off
or dimming the electric lights when full output is not needed.
Control needs
ON/OFF and/or dimming control with manual override possibilities
35
Introduction
4.5 Dimming
Control
36
37
The versatile meeting room can be divided into three spaces with movable walls,
each space having its own set of pushbuttons to allow individual control. When
partition walls are open and the space is used for larger meetings all pushbuttons
work in parallel. One side of the space has large windows allowing daylight
harvesting.
In this simple scenario, five (5) lighting schemes were defined and programmed
at installation (although sixteen schemes are possible):
38
Scheme 1: Constant light control (use of daylight) for meetings. Groups 1-9 are
programmed for varying light levels.
Scheme 2: Evening activities. Groups 1-9 are programmed at 100% light levels.
Scheme 3: Stage lighting for presentations Group 10 only is programmed.
Scheme 4: Lighting for cleaning Groups 1-9 are programmed at 50% light levels.
Scheme 5: Security lighting. One light from each Group 1-9 is programmed at
10%.
To achieve this, four groups were defined and programmed as follows:
- Groups 1-3, groups 4-6 and groups 7-9 are arranged in parallel to the windows
in order to create ideal conditions for daylight control. - Group 10 is wired
separately to highlight the stage on special occasions.
If these groupings needed to be changed, the fixtures would simple be
reassigned to new groups via remote control or PC - no ladders, no pulling wires,
complete flexibility!
Shutters and blinds not only protect us from the sun, creating pleasant lighting
conditions, they can also help make a significant contribution to saving energy
costs for heating, cooling and artificial lighting.
=S= control systems includes shutter actuators in different functional versions
for the control of shutters, interior blinds, awnings or motorized curtains
Types and operation
Wind Control - Retracts external blinds if the wind speed exceeds a pre-set level.
Timer Control - a daily or weekly timer to operate the blinds at preset times. It
is usually used to extend the blinds in the morning and retract them at night.
Where blinds or shutters are used for insulation it can be used to lower them at
night for heat retention.
Light level control - for non-retractable blinds has three lux level control and
allows the slats to adjust to maintain light levels within a selected band width.
Master or Building Control - allows override of the system from one central point
with the option of an interface with the fire alarm system to retract the blinds.
Individual control - allows override of the automatic system by a switch local to
each blind.
Infra-red control - operation by means of an infra-red transmitter that activates
the sensor that is normally mounted on the wall beside the blind.
Radio remote control - control by a hand held transmitter is usually used for
shutters or garage doors. It is suited when direct line of sight to the sensor is not
possible.
39
Application description
Control of shutters and blinds with an automatic control that replaces or
accompanies occupant control, in order to ensure that external blinds are
retracted in windy conditions or extended at sunny conditions following the data
from the BA system.
Control needs
Automatic UP / Down and slats control with manual override possibilities
40
5 Application practice
41
42
Software Description
The application serves the dimming and switching of fluorescent lamps via
electronic ballasts with an interface 1 V...10 V, or of NV halogen lamps via
transformers with an interface 1 V...10 V.
With the aid of a brightness sensor, constant light control can be achieved.
Furthermore, it is possible to save lighting scene settings and to retrieve
them when required. Certain lighting moods can hereby be quickly reestablished through one click on a button. The information from the
presence detector can be used to switch off the light completely or to dim it
to a particular level.
In the LON I/O module, the following LONMARK objects are available: Lamp
Actuator (3040), Constant Light Controller (3050), Scene Controller (3251)
and Occupancy Controller (3071).
43
For the SVEA LON Bus Coupling Unit UP there is a very flexible software
application that can be configured for almost every planned application. It
is based on the LonMark profiles Switch (3200), Scene Panel (3250) and
Occupancy Sensor (1600).
The applications for the switching or dimming of luminaires and for the
sending of scene setting values are described in the following examples.
Application Manually Dimming Lights
44
3. Through operating a switch on the bus connector, the dimming value, and
thus the brightness of the lamps, can be altered. As long as the switch is
pressed, messages are distributed via nvoSWswitch in which the value-part is
gradually enlarged or reduced, according to the dimming direction. The size
of the dimming stages can be set in a configuration variable.
4. The dimming actuator reports its current status to the LON network via
the feedback variable, nvoLAlampValueFb. This value must be bound to the
input variable nviSWswitchFb of the bus connection because it is only from
the current dimming value that brightening or dimming occurs.
45
3. During active control, the actual value of the brightness, which should be
present at nviCLluxLevel, is compared with the programmed setpoint value
(nviCLLuxSetpoint or SCPTluxSetpoint). If the two values differ from each
other, an output value (value-part of the SNVT_switch-Variable) is calculated
in order to dim the connected luminaire. Via a configuration variable, the
value to be sent first can be defined after switching on the control. If the
control is switched off, a switch-off message is also sent to the dimmer
actuator. It is possible to switch off the light automatically to save energy
as long as the actual value lies above a definable value due to outside light.