Manual de Servicio LB-B6020CL
Manual de Servicio LB-B6020CL
Manual de Servicio LB-B6020CL
Air Conditioner
SERVICE MANUAL
MODEL: LB-D1820HL
LB-D2420CL
LB-B6020CL
Contents
Functions
Dimensions
Wiring Diagram
10
Operation Details
13
16
Test Running
27
3-way Valve
29
34
35
38
Schematic Diagram
39
41
Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature sensor. (Thermistor)
Room temperature control
Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
Indoor fan is delayed for 5 seconds at the starting.
Time Delay Safety Control
Restarting is inhibited for approx. 3 minutes.
Indoor Fan Speed Control
High, Med, Low
Soft Dry Operation Mode
Intermittent operation of fan at low speed.
Auto Operation
The setting temperature, indoor fan speed and desired operation mode are automatically set.
Deice (defrost) control (Heating)
Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating)
The indoor fan stops until the evaporator piping temperature will be reached at 28.
Remote Controller
Operation ON/OFF
(Cooling
(Cooling & Heating
model only)
model)
)
)
LO (Low)
MED (Med)
HI (High)
Down to 18C
Up to 30C,
Heating
Down to 16C
Up to 30C,
Set
LB-D1820HL
LB-D2420CL
LB-B6020CL
Unit
Cooling Capacity
Btu/h(kcal/h)
18,000(4,536)
24,000(6,048)
60,000(15,000)
Heating Capacity
Btu/h(kcal/h)
18,000(4,536)
Moisture Removal
l/h
3.5
3.5
7.5
, V, Hz
1, 220V~, 60Hz
1, 220V~, 60Hz
1, 220V~, 60Hz
18.5
18.5
56
49
49
105
2,000
2,800
7,100
1,850
9.2
13
32
8.3
8.57
7.06
42
42
70
60
60
90
1,600
1,840
4,000
L.C.D
L.C.D
L.C.D
Liquid
1/4" (6.35)
3/8" (9.52)
1/2" (12.7)
Gas
5/8" (15.88)
5/8" (15.88)
3/4" (19.05)
Power Source
Air Circulation
Indoor
m3/min
Outdoor
Input
Cooling
Heating
Running Current
Cooling
Heating
E.E.R.
Dimensions
(WHD)
Net. Weight
Btu/h-W
Indoor
mm
Outdoor
Indoor
kg
Outdoor
Refrigerant (R-22)
Remocon Type
Service Valve &
Connecting Tube
Drain Hose
Connecting Wire
0.75mm2
0.75mm2
1.25mm2
2.5mm2
3.5mm2
8mm2
Soft Dry
24Hrs
24Hrs
24Hrs
Dimensions
(1) MODEL: LB-D1820HL/ LB-D2420CL
Indoor Unit
880
575
281
Outdoor Unit
320
870
655
1230
760
370
Outdoor Unit
370
900
1200
OUTDOOR UNIT
CAPILLARY TUBE
LIQUID SIDE
CHECK VALVE
HEAT
EXCHANGER
HEAT
EXCHANGER
GAS SIDE
REVERSING
VALVE
COOLING
HEATING
COMPRESSOR
Pipe size(Diameter: )
Piping length(m)
Elevation(m)
MODEL
LB-D1820HL
(
Gas
Liquid
Rated
Max.
Rated
Max.
5/8"
1/4"
15
For installation over rated distance, 40g of refrigerant should be added for each meter.
ex) When installed at a distance of 15m, 400g of refrigerant should be added.
(15-5) x 40g = 400g
Additional
refrigerant
(g/m)
40
OUTDOOR UNIT
LIQUID SIDE
HEAT
EXCHANGER
(EVAPORATOR)
HEAT
EXCHANGER
(CONDENSER)
COMPRESSOR
GAS SIDE
Pipe size(Diameter: )
Piping length(m)
Elevation(m)
MODEL
Additional
refrigerant
(g/m)
Gas
Liquid
Rated
Max.
Rated
Max.
LB-D2420CL
5/8"
3/8"
15
60
LB-B6020CL
3/4"
1/2"
30
30
70
For installation over rated distance, 70g of refrigerant should be added for each meter.
ex) When installed at a distance of 15m, 700g of refrigerant should be added.
(15-5) x 70g = 700g
Wiring Diagram
(1) MODEL: LB-D1820HL
Indoor Unit
Outdoor Unit
10
FAN
MOTOR
Outdoor Unit
11
Outdoor Unit
12
Operation Details
(1) The function of main control
1. Time Delay safety Control
3min The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
30sec The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode while compress is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by Micom Control.
INDOOR FAN
COMPRESSOR
More than
More than
3 minutes
3 minutes
Selecting
fan speed
Low
Selecting
fan speed
Low
Selecting
fan speed
ON
OFF
ON
OFF
ON
13
minimum 3min
Setting temp.+3C
(Compressor OFF)
A
Setting temp.
(Compressor ON)
INDOOR FAN
COMPRESSOR
1min
Hot Start
Low
Selecting
Fan Speed
ON
minimum
minimum
minimum
10sec.
1min.
10sec.
Low
OFF
Low
OFF
Selecting fan
speed
ON
Low
OFF
OFF
A point; While the indoor Heat-Exchanger temperature is higher than 35C fan operates at low speed, when
it becomes lower than 35C fan stops.
B point; When the indoor Heat-Exchanger temperature is higher than 35C, fan operates at seleted fan
speed, when it becomes lower than 35C, the fan operates at low speed for 10sec, after 10sec, it
operates at seleted fan speed.
5. Hot-Start Control
The indoor fan stops until the evaporator piping temperature will be reached to 28C.
The operation diagram is as following.
PIPING
TEMPERATURE
28C
1min
26C
INDOOR FAN
ON
COMPRESSOR
: Selected Fan
: Low Fan
14
: Fan Stop
6. Defrost Control
Defrost operation is controlled by timer and sensing the outdoor piping temperature.
The defrost starts only when the outdoor pipe temperature falls below -6C after 60 minutes passed from starting
of heating operation.
Defrost ends after 9 minutes 30 seconds passed from starting of defrost operation or when the outdoor pipe
temperature rises over 12C even if before 12 minutes.
Within
12minutes
Defrost
Defrost
-6C
(Defrost ON)
HOTSTART
Indoor Fan
ON
OFF
ON
OFF
Compressor
ON
ON
ON
ON
4-Way Valve
ON
OFF
ON
OFF
7. Self-Diagnosis Function
'CHECK' will flash in the remote controller display when a problem occurs. Then please contact your dealer.
Correct the accident point as shown in the table below before restarting operation.
During the normal operation 'CHECK' won't be displayed in the remote controller.
Accident Point
F1
F2
F3
15
1) Indoor unit
(unit: mm)
Select location
Install the air conditioner in the location that satisfies the following conditions.
The place shall easily bear a load exceeding four
times the indoor units weight.
The place shall be able to inspect the unit as the
figure.
The place where the unit shall be leveled.
The place shall allow easy water drainage.(Suitable dimension H is necessary to get a slope to
drain as figure.)
The place shall easily connect with the outdoor
unit.
The place where the unit is not affected by an
electrical noise.
The place where air circulation in the room will be
good .
There should not be any heat source or steam
near the unit.
Inspection hole
(600X600)
1000
Control box
600
600
Front
Front view
2) Outdoor unit
Su
nro
of
More than
30cm
Fe
ob nce
sta or
cle
s
16
More than
30cm
More than
70cm
Indoor unit
Gas
Liquid
Standard
Max.
Standard
Max.
* Additional
refrigerant
(g/m)
18K BTU
5/8"
1/4"
15
40
24K BTU
5/8"
3/8"
15
60
60K BTU
3/4"
1/2"
30
30
70
MODEL
Length A(m)
Elevation B(m)
A
B
Outdoor unit
NOTE:
Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the
fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water
drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it
may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
17
CASE 1
C
E
880
466
54
574
1230
650.5
54
760
Dimension
1~3mm
Capacity
Drainage hole
CASE 2
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can
support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.
M10 Nut
X4
(Local
M10 SP. washer X 4 supply)
M10 washer
X4
M10 washer
X4
(Local
M10 SP. washer X 4 supply)
M10 Nut
X4
18
Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on
the ceiling.
Mount the suspension bolts to the set anchor
firmly.
Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
Old building
New building
1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
Local supply
Set anchor
Plate washer
Spring washer
Nut
Suspension bolt
CAUTION
Tighten the nut and bolt to prevent unit falling
19
- M10
- M10
- W3/8 or M10
- W3/8 or M10
el
ow
er
pa
rt
Remote control
box body
Lever carefully
the box open
using a screw
driver, etc.
Cord clamp
(accessory)
Under plate
Screw (accessory)
ELECTRICAL WIRING
Remote controller
(Main board)
CN REMO
20
1(L)
2(N)
POWER INPUT
24K Btu
3(L) 4(N) 5
3(L) 4(N) 5
POWER
INPUT
18K Btu
3(L) 4(N)
3(L) 4(N)
POWER
INPUT
CAUTION
The power cord connected to the outdoor unit should be
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA).
NORMAL
CROSS-SECTIONAL
AREA 2.5mm2 (18K/24K)
8mm2 (60K)
GN
/YL
NORMAL
CROSS-SECTIONAL
AREA 0.75mm2 (18K/24K)
1.25mm2 (60K)
GN
/YL
20
20
mm
mm
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the
manufacturer of its service agent.
WARNING
Make sure that the screws of the terminal are free from looseness.
2) Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly.
For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic
clamp to the other boss of the control panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle
of live pin on the power plug should be over 1.8m.
21
ELECTRICAL WIRING
Circuit Breaker
Use a 25A(18K/24K),
50A(60K) circuit breaker
or time delay fuse.
Main
power source
Switch box
Outdoor
Indoor
WIRING CONNECTION
Control terminal board
INDOOR UNIT
Control box
A view
Remove the control box cover for electrical connection between the indoor and outdoor
unit.(Remove two screws .)
Use the cord clamper to fix the cord.
Remote
control cord
Cord clamper
Connection
cord between
the indoor unit
and the
outdoor unit
OUTDOOR UNIT
Main terminal board
Please check !!
Cover control
22
Copper
tube
90
Pipe
Reamer
2) Burrs removal
Point down
3) Putting nut on
Flare nut
Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having
completed burr removal.
(Not possible to put them on after flaring work)
Copper tube
4) Flaring work
Carry out flaring work using flaring tool as shown
below.
Capacity
60K BTU
Outside Diameter
Gas
Liquid
3/4"
1/2"
"A"
Gas
Liquid
Handle
1.0~1.3 0.5~0.8
24K BTU
5/8"
3/8"
0.8~1.0 0.5~0.8
18K BTU
5/8"
1/4"
0.8~1.0 0.5~0.8
Bar
Bar
"A"
Yoke
Cone
Copper pipe
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
Clamp handle
5) Check
Smooth all round
= Improper flaring =
Even length
all round
23
Piping Connection
1. Form the piping according to its routing. Avoid
bending and bending back the same piping point
more than three times. (This will result in hardening the pipe.)
2. After deforming the piping, align centers of the
union fitting of the indoor unit and the piping, and
tighten them firmly with wrenches.
3. Connect pipe to the service valve or ball valve
which is located below the outdoor unit.
4. After completing the piping connection, be sure
to check if there is gas leakage in indoor and
outdoor connection.
Liquid side
Indoor
unit
Outdoor
unit
Flare connection
Gas side
Flare connection
Vacuum drying
After completing the piping connection, execute
vacuum drying for the connecting piping and the
indoor unit.
The vacuum drying must be carried out using the
service ports of both the liquid and gas side valves.
Model
LB-D1820HL
1/4"
5/8"
LB-D2420CL
3/8"
5/8"
LB-B6020HL
1/2"
3/4"
CAUTION
Use two wrenches and tighten with regular torque.
Pipe size
Liquid Side
Gas Side
Union
Torque
1/4"
1.8kg.m
3/8"
4.2kg.m
1/2"
5.5kg.m
5/8"
6.6kg.m
3/4"
6.6kg.m
24
CAUTION
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.
Front of view
The unit must be horizontal or declined to the drain hose connected when finished installation.
1~3mm
Ceiling
INCORRECT
CORRECT
Drainage hole
Drainage hole
Lay the drain hose with a downward inclination
so water will drain out.
Thermal insulator
(Local supply)
Drainage pipe
(Local supply)
Unit
Drainage hole
CORRECT
INCORRECT
25
Indoor
WALL
Outdoor
5~7mm
INSULATION, OTHERS
THERMAL INSULATION
INDOOR UNIT
REFRIGERANT PIPE
Insulate and tape both the gas piping and liquid piping.
Connecting cable
Liquid pipe
Thermal insulator
26
Tape
Gas pipe
Trap
Drain hose
Taping
Connecting
cable
Power supply
cord
Test running
1) PRECAUTIONS IN TEST RUN
The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
For test run, carry out the cooling operation firstly even during heating season. If heating operation
is carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
Caution
Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time.
To cancel the test run, press any button.
M5...196N.cm{20kgf.cm}
M8...588N.cm{60kgf.cm}
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring,
be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and
make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the
wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning,
temperature control, etc.).
28
3-way Valve
1. Pump down
Liquid side
Indoor unit
3-Way
valve
Open
Outdoor unit
Gas side
Closed
3-Way
valve
Lo
CLOSE
CLOSE
Procedure
(6) Operate the air conditioner in cooling mode
and stop it when the gaug e indicates
1kg/cm2g.
(8) Disconnect the charge set, and mount the 2way and 3-way valves stem nuts and the
service port nut.
Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
Be sure to check for gas leakage.
29
1) Re-air purging
(Re-installation)
Liquid side
Indoor unit
3-Way
valve
Closed
Outdoor unit
Gas side
Closed
3-Way
valve
Gas cylinder
Lo
R22
OPEN
CLOSE
Procedure
(6) Disconnect the charge set and the gas
cylinder, and set the 2-way and 3-way valves
to the open position.
Be sure to use a hexagonal wrench to operate
the valve stems.
(1) Confirm that both the liquid side valve and the
gas side valve are set to the closed position.
(2) Connect the charge set and a gas cylinder to
the service port of the 3-way valve.
Leave the valve on the gas cylinder closed.
* CAUTION:
Do not leak the gas in the air during Air
Purging.
30
Liquid side
Indoor unit
Outdoor unit
3-Way
valve
Open
Gas side
3-Way
valve
Open
Lo
OPEN
CLOSE
Procedure
(1) Confirm that both the liquid side and gas side
valves are set to the back seat.
31
2. Evacuation
(All amount of refrigerant leaked)
Liquid side
Indoor unit
Outdoor unit
3-Way
valve
Open
Gas side
3-Way
valve
Open
Vacuum pump
Lo
OPEN
CLOSE
Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
32
3. Gas Charging
(After Evacuation)
Liquid side
Indoor unit
3-Way
valve
Open
Outdoor unit
Gas side
Open
3-Way
valve
Check valve
Charging
cylinder
Lo
(1)
OPEN
CLOSE
Procedure
\
33
Temp. Difference
Operating Current
Temp. difference
Current
: approx. 0C
: less than 80% of
rated current
Temp. difference
Current
: approx. 8C
: less than 80% of
rated current
Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
Temp. difference
Current
: less than 8C
: over the rated
current
Temp. difference
: over 8C
Normal
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure
(Compared with
the normal value)
Temperature
(Compared with
the normal value)
Cause of Trouble
High
Defective compressor
Defective 4-way reverse valve
Current is low
Excessive amount of
refrigerant
Insufficient amount of
refrigerant (Leakage)
Clogging
Current is low
Higher
Normal
Lower
Higher
Description
Current is low
Notice :
1. The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
34
NO
YES
Is the output voltage
of transformer about AC14V?
NO
Is shorted the
transformer output?
YES
YES
NO
NO
YES
Is the output voltage
of IC01D DC12V?
NO
Exchange IC01D
YES
NO
Exchange IC02D
YES
NO
Check the
5V P.C.B pattern.
YES
Exchange MICOM
35
Possible Trouble 2
Is it the HOT
START mode?
YES
It is normal operation.
NO
Is IC01M operated
normally?
NO
Exchange IC01M
YES
Is the each Relay
any problem?
YES
Exchange Relay
NO
Check the fan motor
and connector.
(CN-MOTOR)
Possible Trouble 3
YES
NO
NO
NO
36
Possible Trouble 4
: Ineffective Heating
Is it Heating Mode?
NO
YES
NO
YES
Is IC01M operated
normally?
NO
Change IC01M.
YES
Is 4way-valve operated?
NO
Check RY-4Way
YES
Check the connector
(CN-OUT, CN-AC1.2)
37
38
Schematic Diagram
Cooling & Heating type
39
40
13
16
11
27
30
25
20
21
12
19
18
15
14
24
10
26
23
22
17
28
31
29
41
PARTS NAME
PART No.
LB-D1820HL
LB-D2420CL
PANEL UPPER
3720A30023
1A
1A
PANEL SIDE-L
3720A30027
1A
1A
PANEL SIDE-R
3720A30028
1A
1A
BARRIER, INDOOR
4790A30003
1A
1A
HOUSING ASSY-L
3661A20003
1A
1A
HOUSING ASSY-R
3661A20003
1B
1B
MOUNT MOTOR
4960A30001
1B
1B
MOTOR ASSY
4681A20005
1D
1D
BLADE ASSY
5833A20001
1G
1G
10
BLADE ASSY
5833A20001
1H
1H
11
BRACKET EVA.-L
4810A30002
1C
1C
12
BRACKET EVA.-R
4810A30003
1C
1C
13
EVAPORATOR ASSY
5421A20008
1C
1C
14
5211A30094
1A
1A
15
5211A30094
1C
1B
16
3086A30001
1C
1C
17
PANEL REAR(E)
3720A30025
1A
1A
18
4994A20001
1A
1A
19
THERMISTOR ASSY
6323AQ2333
1L
1L
20
PWB(PCB) ASSY
6871A20016
1B
1A
21
TRANSFORMER
6171AQ2258
1H
1H
22
REMOTE CONTROLLER
6711AQ2350
1M
1K
23
6871A20009
1H
1G
24
HANGER
4990AP7280
2E
2E
25
HANGER
4990AP7280
2F
2F
26
COVER, CONTROL
3550A30003
2A
2A
27
PANEL REAR(B)
3720A30026
1A
1A
28
FILTER
5230A30001
1B
1B
29
GUIDE FILTER
4974A30016
1A
1A
30
ANGLE ASSY
3001A30004
1A
1A
31
GUIDE FILTER
4974A30016
1B
1B
42
REMARK
16
11
13
31
25
43
21
20
12
18
19
14
15
24
10
27
26
23
28
22
17
32
30
29
2. MODEL: LB-B6020HL
PARTS NAME
PART No.
LB-B6020CL
PANEL UPPER
3720A30021A
PANEL SIDE-L
3720A20012A
PANEL SIDE-R
3720A20013A
BARRIER, INDOOR
4790A30006A
HOUSING ASSY-L
3661A20001A
HOUSING ASSY-R
3661A20001B
MOUNT MOTOR
4960A30002A
MOTOR ASSY
4681A20005A
BLADE ASSY
5833A20001A
10
BLADE ASSY
5833A20001B
11
BRACKET EVA. -L
4810A30002A
12
BRACKET EVA. -R
4810A30003A
13
EVAPORATOR ASSY
5421A20008A
14
5211A30077A
15
5211A30077B
16
3086A30001H
17
PANEL REAR(E)
3720A30022A
18
4994A20001A
19
THERMISTOR ASSY
6323AAQ2333L
20
PWB(PCB) ASSY
6871A20016A
21
TRANSFORMER
6171AQ2258H
22
REMOTE CONTROLLER
6711AQ2350K
23
6871A20009G
24
HANGER
4990AP7280E
25
HANGER
4990AP7280F
26
COVER, CONTROL
3550A30003A
27
PANEL REAR(S)
3720A30020A
28
PANEL REAR(L)
3720A30019A
29
GUIDE FILTER
4974A30016B
30
GUIDE FILTER
4974A30013A
31
ANGLE ASSY
3001A30005A
32
FILTER, AIR
5230A30001A
44
REMARK
24
23
22
20
27
26
13
10
11
12
C S
R
19
15
18
17
14
21
45
PARTS NAME
PART No.
LB-D1820HL
LB-D2420CL
BASE W. ASM
3A02084
1V
1G
CONDENSER ASM
5402AR2347
1B
1K
COMP. ASM
2A00713
5416A20003
REMARK
1A
RECIPRO
1D
ROTARY
3A01100
1A
REVERSING VALVE
3A02027
1A
3A02028
1Y
SUPPORT VALVE
2A00921
1C
1C
VALVE SERVICE
2A00392
1E
1E
15.88
VALVE SERVICE
2A00393
1C
9.52
2H02479
1B
1A
10
BARRIER ASM
2H02110
11
MOTOR FAN
4680AP2135
4681A20013
12
MOUNT MOTOR
6.35
1A
1G
1E
4960AP1032
1A
4960AP1361
1A
13
EXTRA FAN
1A00195
1B
1B
14
PANEL REAR
3720AP0003
1D
1D
15
CONTROL PANEL
2A00928
1A
1A
16-1
CAPACITOR
2A00986
1D
1D
16-2
CAPACITOR
2A00986
1W
1W
17
6871A20015
1F
18
POWER RELAY
6920AP3400
1A
1A
19
TERMINAL BLOCK
3A00093
1A
4G00103
1A
20
FRONT PANEL
1A00196
1K
1K
21
COVER CONTROL
3A01919
1B
1B
22
2A00915
1H
1H
23
ORIFICE
4948AP2527
1A
1A
24
GRILLE DISCHARGE
3530AP2289
1X
1X
25
SCREW
4A00637
3B
3B
26
1WSD0800030
27
NUT
1NHA0801206
46
47
27
28
29
25
31
30
24
23
4
3
22
12
34
17
15
35
33
32
40
10
41
38
42
18
20
19
39
37
21
36
16
14
13
11
5
7
26
2. MODEL: LB-B6020CL
PARTS NAME
PART No.
LB-B6020CL
REMARK
3041AP2569D
LEG
4778AP2526A
ELBOW, DRAIN
5212AP3173A
RUBBER, DRAIN
5040AP3178A
SUPPORT, VALVE
4980AP2517B
VALVE SERVICE
2A00499C
( 19.05)
VALVE SERVICE
2H01890G
( 12.7)
COMPRESSOR
2A01094E
(CRN5-0500-PFV)
CONDENSER ASSY
5403AP2378B
11
LINK SHEET
4520AP4095A
12
BRACKET COND.
4810AP3697A
13
MANIFOLD IN ASSY
5211AP3843A
14
5211AP3844A
15
REVERSING VALVE
3A02080B
VH40100
16
CHECK VALVE
3A01020D
VN30100(RANCO)
17
DISCHARGE TUBE
5210AP3841C
18
SUCTION TUBE
5210AP7081A
19
ACCUMULATOR
2A00983C
20
3A01902A
21
H.P SWITCH
3A01100A
22
BAFFLE
4760AP1216A
23
MOUNT
4960AP1214A
24
MOTOR ASSY
4680AP2135N
25
EXTRA FNA
1A00195B
26
PANEL REAR
3720AP1202C
27
PANEL FRONT
3720AP1212B
28
GRILLE DISCHANGE
3530AP1225B
29
TOP COVER
3550AP1213B
30
PANEL COVER
3720AP1215B
31
COVER ASSY
3551AP3925D
32
CONTROL ASSY
6615AP2772C
33
BOARD CONTROL
3500AP1266A
48
Q'TY
No.
PARTS NAME
PART No.
LB-B6020CL
34
MAGNETIC CONTACTOR
2A01031C
35
E. O. C. R
2A00999B
36
SH CAPACITOR
2H00841J
37
COVER DEICER
2H00644A
38
TERMINAL BLOCK
3H00390A
39
3Q10485K
40
TERMINAL BLOCK
3A00493A
41
TERMINAL BLOCK
4G00103A
42
POWER RELAY
3A00261C
49
REMARK
P/No.: 3828A30014E
P/No.: 3828A30014F
March, 1999
Printed
in Korea
March,
1999
Printed in Korea