Optimal Operation of A Hvac System With A Optimal Operation of A Hvac System With A Tthermal Storage Water Tank Tthermal Storage Water Tank
Optimal Operation of A Hvac System With A Optimal Operation of A Hvac System With A Tthermal Storage Water Tank Tthermal Storage Water Tank
Optimal Operation of A Hvac System With A Optimal Operation of A Hvac System With A Tthermal Storage Water Tank Tthermal Storage Water Tank
Control Optimization 2
- 1249 -
from a real building and the load predicted are used block of thermal load
prediction
additionally to demonstrate the feasibility of our
To predict the following day's load utiliz-
method. block of thermal ing past loads, room temperatures and
load prediction weather forecast information.
IMPROVEMENT OF OPTIMIZATION
initial calculation of operation hour tope
ALGORITHM
block of optimal
operation
Several improvements were added to the previous
optimizing algorithm in order to stabilize calculation, to find optimal chilled water tem-
optimal calculation of θ set perature by applying nonlinear least
avoid local minimum occurrence and reduce (child water temperature of square method to minimize system
a chiller) objective function
computational time by applying more rationale
constraints and more precise model for water circulation.
pw ( n+ 1) > pw (n)
1) Improvement in determining required thermal storage
Yes
The required thermal storage for a following day is
No
defined as follows.
elongation of operation hour determining optimal value of
of refrigerator tope and θ set
Qd = Q p + Qc + Q l − Qs (1)
Where,
Q p : predicted building load block of system
simulation
Qc : generated heat by circulation pumps for chilled
determining electricity con-
water sumption of the total system actual load
Ql : heat loss through storage tank walls and temperature profile within measurement
Qs : stored heat in a tank the tank
- 1250 -
Table 1 Reduction rate for three objective functions from the reference operation
reduction rate [%]
load type control method
electricity
electricity cost CO2 emission
consumption
optimal electricity consumption 41.6 34.0 41.7
light load optimal electricity cost 41.7 34.2 41.6
optimal CO2 emission 41.1 33.6 41.7
optimal electricity consumption 24.9 16.1 25.4
medium load optimal electricity cost 24.5 18.2 24.9
optimal CO2 emission 24.8 15.5 25.5
optimal electricity consumption 11.7 3.1 11.7
heavy load optimal electricity cost 10.7 6.9 11.4
optimal CO2 emission 11.6 4.8 11.8
[kWh]
5000
incorporated to make the simulation model realistic. The 4000
actual load
0
For a basic investigation the storage tank capacity is Jun. 3 Jun. 24 Jul. 15 Aug. 5 Aug. 26 Sep. 16 Oct. 7 Oct. 28
date
assumed large enough to store whole thermal energy Figure 2 Air-conditioning load taken from a real
required for air-conditioning on the following days. building and the predicted load
Although this assumption is not realistic in common
building systems the investigation is useful to
understand the basic performance and characteristics functions is very small. The reasons of this result are as
of the present operation method. follows.
1) To reduce electricity cost daytime electricity usage
1) Comparison of Objective Functions with Periodic should be minimized because daytime price is higher.
Load Decreasing in chilled water temperature is the most
To investigate the effect brought by the deferent effective way to achieve this because water circulation
objective functions which correspond to minimizing rate during daytime air-conditioning can be reduced and
electricity consumption, electricity cost and CO2 as a result electricity used for pumping is reduced.
emission simulations were carried out using three However decreasing the temperature requires more
standard and periodic AC loads; heavy, medium and electricity due to COP drop in chiller operation. Due to
light load. For the simulations the following conditions these contradictory effects the temperature level defers
are used. The current electricity prices in the Tokyo from that of the operation for electricity consumption
region are 6 JPY/kWh for the nighttime (22:00 - 8:00), 20 optimization.
JPY/kWh for the daytime (8:00 - 14:00, 16:00 - 22:00) and 2) Hourly CO2 emission rates in unit electricity usage
22 JPY/kWh for peak hour (14:00 - 16:00). The larger the do not differ so significantly that much difference
percentage of generation by nuclear power plants is, between two objective functions; electricity
the less the CO 2 emission rate by unit electricity consumption and CO2 emission, does not occur.
consumption is because nuclear power is believed to If we evaluate the total effectiveness of incorporating
emit less CO 2. In the present research hourly CO 2 the optimal operation based on the medium load
emission rates reported by Tokyo Electric Company are condition, about 25% in electricity consumption and
used. For the comparison of the results the reference CO2 emission and 16% in electricity cost can be reduced.
operation is defined; namely non-optimal operation that
corresponds to chilled water temperature of 7 0C (design 2) Simulation using Real Air-Conditioning Loads
value) and full storage without load prediction function. To verify the feasibility and the stability of the present
The reduction rates from the reference vale are shown method simulation using real air-conditioning loads
in Table-1. measured at a real building was performed. The record
It can be seen that the reduction of all the three optimal of the integrated loads in daily basis is shown by the
operations is substantial. This says incorporating solid line of Figure 2. The period of air-conditioning is
optimal operation is very beneficial. However the from June 3 to October 31 and the daily air-conditioning
deference between the reduction rates of three objective period is from 9:00 to 18:00. The dotted line in Figure 2 is
- 1251 -
Table 2 Results of perfect prediction case for total period
in average power consumption [MWh]
o
operation hour [h] set temperature [ C] total refregirator secondary pump others
maximum storage operation 5.4 7.0 96.8 73.7 5.0 18.1
optimal operation 3.5 15.2 67.3 49.1 6.4 11.8
the predicted load by the method of the previous report a day is defined as an insufficient storage day. In the
4)
. The prediction error is 7.32% (a0) of the maximum present study the number of such days was 17. Table-4
load. The a 0 is defined as EEP (Expected Error shows the results and it can be seen that the reduction
Percentage) value. rate (36%) excluding the insufficient storage days is
similar to that of the perfect prediction case (32%). But
2-1) Simulation with Perfect Prediction the existence of 17 days of insufficient air-conditioning
Load prediction is not perfect in a real situation; would be a serious problem to building users.
however, basic investigation was made assuming Furthermore it was found that inadequate temperature
perfection. The results for the whole period of simulation disturbance in the tank is produced and this causes
are shown in Table-2 compared with the reference unstable air-conditioning operation.
operation defined at the previous investigation. It is
found that substantial conservation 33.1MWh (=96.8 - 3) Simulation Considering Prediction Error
63.7MWh) can be attained, that corresponds to 31% Two points are considered in the investigation of
reduction. This is mainly due to chiller COP increase prediction error; the effect of prediction error EEP level
with high chilled water temperature of 15.2 0C in average. and the effect of a margin of safety to reduce occurrence
Table-3 shows monthly results. It can be found that the of faulty air-conditioning days.
reduction rates are larger in intermittent season. This is
why in heavy load period the temperature must be low 3-1) EEP level of prediction error
to manage large AC load and as a result COP decreases. The EEP level of prediction error of the present
example is 7.32% as shown previously, however,
2-2) Simulation with Prediction Error according to the benchmark trials operated by SHASE
Taking the real situation into account simulation with (The Society of Heating, Air-Conditioning and Sanitary
load prediction error was carried out. Namely thermal Engineering of Japan) the average EEP level of the best
storage operation is performed based on the predicted methods was around 5%. Therefore in the present
load and consumption of the thermal energy or air- investigation predicted loads with three levels of EEP,
conditioning operation is achieved based on real loads. namely 5% (average), 10% (2 times) and 20% (4 times),
As mentioned previously the EEP value of the present were generated by the following method and the
example is 7.32%. Therefore due to the existence of the simulation using them was performed.
prediction error the stored thermal energy is not
necessarily sufficient to manage air-conditioning for a ed ( n ) = Q r , d ( n ) − Q p , d ( n ) (2)
whole day on certain days. The shortage of thermal
energy results in the increase of stored chilled water (aL a0 ) ⋅ ed (n) − Qr , d ( n)
k ( n) = (3)
temperature, and consequently room air temperature Q p , d ( n)
becomes higher than the set point for some hours. Such
- 1252 -
q p , L ( n , j ) = k ( n ) ⋅ q p ( n, j ) (4) maximum load condition. This implies maximizing the
duration of chiller operation and consequently
minimizing chiller capacity. In other words the tank
where,
capacity is designed so as to store a half of the maximum
ed (n) : prediction error in day total
Qr ,d : day total load, although this does not necessarily ensure
actual load in day total
Qp,d : optimal size. When daytime storage operation takes place
predicted load in day total
q p, L : the conditions concerning optimal operation become
predicted hourly load
more sophisticated. On a day when total air-conditioning
n : indication of day
load is less than the tank capacity nighttime operation
j : indication of hour
meets the requirement and the operation strategy can
aL : EEP level ( a1 : 5%, a2 : 10%, a3 : 20%)
be the same as explained for the totally nighttime
operation. However when total load exceeds the tank
As shown in Table-5 the optimal chilled water
capacity optimal operation becomes more complex
temperature decreases and the number of days of
because other variables such as operation schedule of
insufficient storage or unsatisfactory air-conditioning
chillers in addition to the chilled water temperature must
increases substantially with EEP, although electricity
be considered. In the present study four conditions are
consumption does not increase significantly. When EEP
analyzed with different levels as listed in Table-7. They
level is 10% 20 days out of 122 days or 16% of cooling
are chiller operation schedule, chilled water temperature
season days will have unsatisfactory air-conditioning.
set point, reference tank temperature, and a margin of
This figure will not be acceptable by buildings users.
safety for storage. Eleven scenarios (S1 -- S7, S11 -- S14
shown in Table-8) based on different combinations of
3-2) Operation with a margin of safety
the four conditions and levels were investigated as
Increasing the stored thermal energy by a margin of
potential optimal strategies. For example each scenario
safety for the predicted load can decrease the number
is abbreviated such as S1( σ ), if the scenario is S1 and
of unsatisfactory air-conditioning days. To investigate
the safety margin is σ . Simulation was carried out by
the effect of margin level simulation was performed with
taking electric power consumption as the objective
five levels; 0%, σ (=7.32%), 2 σ , 4 σ and 8 σ . As shown
function and daytime chilled water temperature was
in Table-6 no unsatisfactory air-conditioning day occurs
optimized. To evaluate the results of the scenarios the
by applying the margin level greater than 4 σ ,
performance of non-optimal operation is taken as the
nevertheless the electricity consumption increases very
reference, that is, the chilled water temperature in the
little (3%).
nighttime is set at 7 oC and the temperature of the last
tank is maintained between 8 and 9 oC by on-off control
PARTLLY DAYTIME STORAGE of chillers. The reduction rates shown in Table-9 mean
OPERATION the reduction from the reference value. As seen they
range from 11 to 18 % with 15 % in average.
According to a design guide a standard storage tank
should be sized so that chillers are operated for 10 hours 1) Daytime chiller operation schedule
both in the nighttime and the daytime on the day of To evaluate the schedule of daytime chiller operation
- 1253 -
the performance of early time operation (OE) and late mostly in the daytime. The differences between S1, S4
time operation (OL) were compared. The OE means that and S5 are not significant, but comparing three aspects
chillers are operated without break after nighttime of power consumption, cost and CO2 emission the
operation, namely, operated in the morning. On the S4(2 σ ) would be decided as an optimal scenario and
contrary OL is reverse or operation in the afternoon. reductions of 12.9% in power consumption, 6.8% in cost
Heat loss is reduced by OL operation but the possibility and 12.4% in CO2 emission can be attained.
of the occurrence of thermal energy shortage is higher.
Although the difference between the two strategies is 3) Reference temperature change with month
negligible as shown in S1(0) for OE and S2(0) for OL of As investigated previously by changing the tank
Table-9. reference temperatures with month the system efficiency
will increase. To investigate this effect simulation S6
2) Chilled water temperature in the nighttime and S7 were performed. By comparing with the best
In the nighttime chillers are operated at maximum given result S4(2 σ ) it can be found that additional
capacity in partially daytime storage operation. To reductions of 3.5% in power consumption, 2.5% in cost
investigate the effect of the chiller temperature set point and 3.2% in CO2 emission is possible.
in the nighttime operation, simulations were performed
at three levels of set point; namely 7, 9 and 11 oC. They 4) Difference in objective function
are abbreviated as S1, S4 and S5 respectively and the The objective function of the above studies is the
effect of three levels of safety margin for load prediction electric power consumption. To investigate the effect
is analyzed together. Fundamentally the set point of applying different objective functions simulations
should be the design value of 7 oC to store maximum through S11 to S14 were performed. It can be seen that
thermal energy during night, however, it can be set higher the effect is very little, therefore taking the electric power
in real operation. In this case the stored energy will be consumption as the objective function is acceptable.
consumed excessively in the daytime and the risk of
unsatisfactory air-conditioning or insufficient storage CONCLUSIONS
increases. In addition to the three scenarios the scenario
S3 in which the set point was optimized as a uniform An optimal operation method for a HVAC system
value for day and night was performed. The results are equipped with a water storage tank was proposed by
shown in Table-9. All the scenarios of S3 show good the author’s in the previous work1). In the present report
reduction in power consumption, however, electricity improvement of the methodology is explained and the
cost increases and the number of insufficient storage effect and the feasibility of the method is investigated
days is large. This is because the chiller operation is and evaluated. The evaluation is made in terms of
- 1254 -
electricity consumption, electricity cost and CO2 following scenario is the best; nighttime storage
emission based on the present electricity tariff and operation at 9 oC followed by daytime operation in the
diurnal variations in CO2 emission for unit electricity morning, monthly varied reference temperatures for
usage taking nuclear power generation into account. storage and 10% of a margin of safety for load prediction.
Firstly totally nighttime operation is investigated. This Approximate reduction by this near-optimal operation
is the case that the tank capacity is designed large is 15% in power consumption, 9% in cost and 14% in
enough to store whole energy to satisfy air-conditioning CO2 emission. The effect of different objective function
of a peak day. If air-conditioning load is predicted is also analyzed but not so significant effect is detected.
perfectly the reduction of electric power consumption
from non-optimized operation can be about up to 30%. ACKNOWLEDGEMENT
In reality perfect prediction is not possible and if the
error level is 5% the system encounters 11 days of The authors acknowledge the favor of Tonetsu Co.
unsatisfied air-conditioning or insufficient storage. In in providing measured data from a real building.
general this figure may not be accepted by building
users. Therefore the cases in which predicted load is REFERENCES
increased with a margin of safety are investigated and it
is found that no insufficient storage day occurs with 1) Yoshida.H. and Goto.Y., Development of Optimal
20% of a margin of safety. Nevertheless reduction effect Operation of Thermal Storage Tank and the Validation
remains at about 30%. by Simulation Tool”, Building Simulation ’99 Kyoto,
Secondary more common operational condition is Japan, BS99-088, 1999
investigated, that is, partially daytime storage operation. 2) Yoshida, H. and Goto, Y., Air-Conditioning Load
According to a design guide the tank capacity is sized Prediction for Optimal Operation of Thermal Storage
so that chillers are operated 10 hours both in the Systems”, Summaries of Technical Papers of Annual
nighttime and the daytime on a peak load day. Meeting, The Society of Heating, Air-Conditioning
Consequently the tank is in storing mode only for and Sanitary Engineers of Japan, pp.177-180, 1998
nighttime on the days of light load. On these days the 3) Yoshida, H. and Goto, Y., Validation of Thermal Load
optimal strategy can be the same as for the totally Predicting Algorithm for Thermal Storage Systems
nighttime operation. On the contrary storing operation using Real Building Data”, Transactions of the
must be done during daytime also on the days of heavy Society of Heating, Air-Conditioning and Sanitary
load, then conditions becomes complex. Eleven Engineers of Japan, No.73, pp.101-110, 1999
scenarios are made as feasible combinations of 4) Yoshida, H. and Inooka, T., Rational Operation of a
conditions and they are evaluated. In conclusion the Thermal Storage Tank with Load Prediction Scheme
- 1255 -
by ARX Model Approach”, IBPSA, 2, pp.79-86, 1997
5) Inooka, T. and Suzuki, T. et al, Study on Control
Systems for Energy Conservation of Thermal Storage
Air-conditioning Systems” (Part3), Summaries of
Technical Papers of Annual Meeting, The Society of
Heating, Air-Conditioning and Sanitary Engineers of
Japan, pp.241-224, 1996
6) Mori, S. et al, Thermal Storage System, The Society
of Heating, Air-Conditioning and Sanitary Engineers
of Japan, 1982
7) Ibamoto, T et al, Thermal Storage System-basis and
application, The Society of Heating, Air-Conditioning
and Sanitary Engineers of Japan, 1995
- 1256 -