Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Resistance in Circuit Breakers: Discussion

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Resistance in Circuit Breakers

Warren C. Garber
NETA Test Technician, Infraspection Level III Thermographer
Industrial Electric Testing, Inc.
11321 West Distribution Avenue
Jacksonville, FL 32256
Ph: 904-260-8378
www.industrialelectrictesting.com

Abstract
As thermographers, we see many thermal anomalies in switchgear and panelboards.
However, finding the actual root cause of what appears to be high contact resistance is
not as straightforward as you may think. Circuit breakers have many internal
mechanical connections, all of which can radiate heat under load.
Misdiagnosing thermal anomalies can result in added time, wasted money and
unnecessary damage to critical equipment. Additionally, there is the frustration involved
with finding that same problem during the follow-up inspection, and then having to
explain to the customer or your boss why the money that was spent to tighten the
connection problem didnt rectify the problem.
In this presentation I will discuss the parts of circuit breakers and the ways that those
parts can cause thermal anomalies commonly called connection problems. I will
show, using a primary injection test set, how different connections within the breakers
will produce thermal anomalies and I will then demonstrate a voltage drop technique to
determine the location of the abnormal resistance.

Discussion
Low Voltage Circuit Breakers
Low voltage (less than 600 VAC) circuit breaker types common in domestic, commercial
and industrial applications include:

Molded Case Circuit Breaker - rated current up to 1000A. Are generally


used for low-current, low-energy power circuits. Molded case circuit breakers
have self-contained overcurrent trip elements.
Conventional thermal
magnetic circuit breakers employ a thermal bimetallic element that has
inverse time-current characteristics for overload protection and a magnetic
1

trip element for short-circuit protection. Many


manufacturers are now switching over from
bimetallic elements to power sensor (solid
state) type trip elements. Magnetic trip only
breakers have no thermal element. These
breakers are principally used only for short
circuit protection.
Nonautomatic circuit
breakers have no overload or short-circuit
protection.
They are primarily used for
manual switching.

Insulated-Case Circuit Breakers - rated current up to 5000A with


interrupting capacities through 200ka.
Insulated case circuit breakers are molded
case circuit breakers using glass-reinforced
insulating materials for increased dielectric
strength. They have push to open buttons
with rotary operated low torque handles with
independent spring charged mechanisms.
This type of mechanism provides for quickmake and quick-break protection. Wide
choices of automatic trip units are available
for these breakers.

Heavy-Duty Power Circuit Breakers - rated current from 400 to 5000A with
interrupting capacities of up to 85ka. Heavy-duty power circuit breakers
employ spring operated, stored energy
mechanisms for quick-make and quick-break
manual or electric operation. Generally, these
breakers have draw-out features whereby
individual breakers can be de-energized for
maintenance purposes. The manually stored
energy breakers are charged and closed by
use of an operating handle. The electrically
operated breakers are operated by a motor or
a solenoid.

Overcurrent Protective Devices


The low voltage protective devices are direct-acting trip, and static trip.

Direct-acting Trip Devices - use a solenoid (electromagnet) whose pulling


force increases with the current. The circuit breaker contacts are held closed
by a latch. As the current in the solenoid increases beyond the rating of the
circuit breaker, the solenoid's pull releases the latch which then allows the
2

contacts to open by spring action. Ambient temperature affects the time


delay but does not affect the current rating of a magnetic breaker. Thermal
magnetic circuit breakers, which are the type found in most distribution
boards, incorporate both techniques with the electromagnet responding
instantaneously to large surges in current (short circuits) and the bimetallic
strip responding to less extreme but longer-term over-current conditions.
Direct-acting trips on insulated-case and heavy-duty power circuit breakers
are of the electromagnetic type. Four trip devices are available: (1) Long
Time Delay (LT), (2) Short Time Delay (ST), (3) Instantaneous (INST) and
(4) Ground Fault (GF). Any combination of the four functions are available to
provide protection for overcurrents. A trip device is installed on each phase of
the electrical circuit. The LTD, STD, INST, and GF trip devices are available
in adjustable time bands to facilitate the coordination of various trip devices in
series. All these units have adjustable settings.

Static-Trip Devices - Static-trip devices are completely static; that is, there
are no moving parts. These devices use semiconductor-based integrated
circuits, capacitors, transformers, and other electronic components. Statictrip devices operate to open the circuit breaker when the current time
relationship exceeds a preselected value. The energy required to trip the
breaker is obtained from the circuit being protected. No external power, such
as DC batteries, is required. The complete static-trip system is comprised of:
1. Primary circuit current transformers, sensors are a toroidal type
mounted one per phase on the primary studs of the circuit breaker.
These transformers provide a signal to the static trip device
proportional to the primary current.
2. Static logic box, receives the signal from the primary current
transformers. It monitors the signal, senses overloads or faults, and
executes the required action in accordance with preselected settings.
3. Tripping actuator, a magnetically held latch device that receives the
output signal from the static logic box, and in turn causes the circuit
breaker to open.
The power supply for the static logic boxes and the tripping actuator is
supplied from a separate set of sensors mounted in the breaker studs. In
addition to the phase overcurrent logic boxes, a ground fault sensing feature
may be provided. New design advances are continually being made in the
development of static-trip devices.

Electrical Resistance
The electrical resistance of an object is a measure of its opposition to the passage of a
steady electric current. An object of uniform cross section will have a resistance
proportional to its length and inversely proportional to its cross-sectional area, and
proportional to the resistivity of the material. Discovered by Georg Ohm in the late
1820s, electrical resistance shares some conceptual parallels with the mechanical
notion of friction. The measurement unit of electrical resistance is the ohm, symbol .
The resistance of an object determines the amount of current through the object for a
given potential difference across the object, in accordance with Ohm's law:

R is the resistance of the object, measured in ohms


V is the potential difference across the object, measured in volts
I is the current through the object, measured in amperes

The resistance of an object can be defined as the ratio of voltage to current:

Resistivity, and therefore Resistance, is temperature dependent. For most materials as


the temperature increases the resistance also increases. As the resistance increases
due to temperature the ratio of voltage-to-current will also rise, often resulting in a drop
of utilization voltage and current.

Parts of the Circuit Breaker


The internal parts of a circuit breaker consist of
many contact points and mechanical connections all
of which can generate heat under load. The picture
below shows a cutaway of a single pole 20 amp
circuit breaker.
1. Actuator lever - used to manually trip and
reset the circuit breaker. Also indicates the
status of the circuit breaker (On or
Off/tripped). Most breakers are designed so
they can still trip even if the lever is held or
locked in the "on" position.
This is
sometimes referred to as "free trip" or
"positive trip" operation.
4

2. Actuator mechanism - forces the contacts together or apart.


3. Contacts - Allows current when touching and breaks the current when moved
apart.
4. Terminals
5. Bimetallic strip
6. Calibration screw - allows the manufacturer to precisely adjust the trip
current of the device after assembly.
7. Solenoid
8. Arc divider / extinguisher
As you can see, there is a lot more to a circuit breaker than just a line and a load side
conductor connection. Poor contact on any one of these internal connections can
cause heating within the breaker. The problem is there is enough thermal mass in the
breaker body to hide the true cause of the heat. Think of the internal parts of the circuit
breaker as a fused disconnect that you can only see the line and load side connections
of. Many of the same parts are there, contacts and mechanical connections, with the
addition of the removable trip unit on some styles of breakers.
Solid State Trip Unit

Primary Contacts
& Arcing Contacts

Trip Unit Connection


Above is a molded case circuit breaker with a solid state trip unit installed.
The breaker cover has been removed to show the internal parts

Locating and Confirming these Internal Problems


It is very important to note that electricity is very dangerous. Only qualified technicians
should conduct these types of inspections. This test requires that a volt meter be used
to determine the voltage drop on live electrical circuits. When conducting an electrical
infrared inspection all covers and dead fronts must first be removed by a qualified
person.
Breaker internal problems appear thermally to be connection problems and sometimes
even look as if to be load imbalance issues. These anomalies in most cases do not
have very large temperature rises and can be easily overlooked. Because the heat
found in these situations is indirect, the result of a much higher temperature within the
breaker that can not be seen directly, normal recommendations based on temperature

rise should not be used. Thermography can be used to locate these problems but
additional testing is needed to determine the severity and the cause of the heat.
Because the breakers may be stacked in the panel or switchgear it may be difficult to
get line of sight to the side of the breaker, where the breaker body material is thinnest,
to see a temperature rise on the breaker body. The heat is sometimes also located in
the space between two breakers. While conducting the inspection, it is important to
move around because the heat may be seen reflecting off the back of the panel or bus
behind the breaker.

The thermal images above show the results of a breaker with internal heating. The heating
cannot be seen on the breaker body but as a reflection on the back of the panel.

When these types of thermal anomalies are located it is important to know the load of all
phases of the breaker. If the load is balanced then a simple Milli-volt drop test can be
conducted. A Milli-volt drop test can disclose several abnormal conditions inside a
breaker such as eroded contacts, contaminated contacts, or loose internal connections.
This test is conducted while the circuit is energized and under load. One lead of a volt
meter is placed on the load side with the other on the line side of the breaker. The
reading is the voltage drop through the breaker internal connections. These readings
can then be compared to one another to determine if the problem is internal to the
breaker. If the load is not balanced, the voltage drop readings are collected using a volt
meter. Then Ohms law can be used to calculate the resistance of each phase. After
the calculated resistance is found for each phase the values can then be compared to
each other to determine if the problem is internal to the breaker.

Conclusion
While conducting an infrared inspection of an electrical system it is important to think
outside the box. A building electrical system consists of many integral parts that all
must operate together to be a safe and efficient system. Thermography is an important
tool in finding problems within the system; however, there must be other tools in the
box. If, during an inspection, problems with the circuit breakers are found it should be
noted correctly in the written report with all needed information and the customer
notified. Then, a qualified electrical testing company can perform electrical tests on
these circuit breakers to determine the proper corrective action.

References
1. Robert Friedel and Paul Israel, Edison's Electric Light: Biography of an Invention,
Rutgers University Press, New Brunswick, New Jersey USA, 1986
ISBN 0-8135-1118-6 pp. 65-66
2. B. M. Weedy, Electric Power Systems Second Edition, John Wiley and Sons,
London, 1972, ISBN 0471924458 pp. 428-430
3. http://bonle.en.alibaba.com/product/50348671/51680889/Switch/MCB_MCCB.html
4. http://www3.interscience.wiley.com/journal/113307491/abstract?CRETRY=1&
SRETRY=0 Electrical Engineering in Japan, vol. 157 issue 4 pp. 13-23
5. United States Department of the Interior Bureau of Reclamation. Denver, Colorado,
Facilities Instructions, Standards and Techniques, Volume 3-16, Maintenance of
Power Circuit Breakers, Internet Version of this Manual Created December 1999,
Hydroelectric Research and Technical Services Group

You might also like