Resistance in Circuit Breakers: Discussion
Resistance in Circuit Breakers: Discussion
Resistance in Circuit Breakers: Discussion
Warren C. Garber
NETA Test Technician, Infraspection Level III Thermographer
Industrial Electric Testing, Inc.
11321 West Distribution Avenue
Jacksonville, FL 32256
Ph: 904-260-8378
www.industrialelectrictesting.com
Abstract
As thermographers, we see many thermal anomalies in switchgear and panelboards.
However, finding the actual root cause of what appears to be high contact resistance is
not as straightforward as you may think. Circuit breakers have many internal
mechanical connections, all of which can radiate heat under load.
Misdiagnosing thermal anomalies can result in added time, wasted money and
unnecessary damage to critical equipment. Additionally, there is the frustration involved
with finding that same problem during the follow-up inspection, and then having to
explain to the customer or your boss why the money that was spent to tighten the
connection problem didnt rectify the problem.
In this presentation I will discuss the parts of circuit breakers and the ways that those
parts can cause thermal anomalies commonly called connection problems. I will
show, using a primary injection test set, how different connections within the breakers
will produce thermal anomalies and I will then demonstrate a voltage drop technique to
determine the location of the abnormal resistance.
Discussion
Low Voltage Circuit Breakers
Low voltage (less than 600 VAC) circuit breaker types common in domestic, commercial
and industrial applications include:
Heavy-Duty Power Circuit Breakers - rated current from 400 to 5000A with
interrupting capacities of up to 85ka. Heavy-duty power circuit breakers
employ spring operated, stored energy
mechanisms for quick-make and quick-break
manual or electric operation. Generally, these
breakers have draw-out features whereby
individual breakers can be de-energized for
maintenance purposes. The manually stored
energy breakers are charged and closed by
use of an operating handle. The electrically
operated breakers are operated by a motor or
a solenoid.
Static-Trip Devices - Static-trip devices are completely static; that is, there
are no moving parts. These devices use semiconductor-based integrated
circuits, capacitors, transformers, and other electronic components. Statictrip devices operate to open the circuit breaker when the current time
relationship exceeds a preselected value. The energy required to trip the
breaker is obtained from the circuit being protected. No external power, such
as DC batteries, is required. The complete static-trip system is comprised of:
1. Primary circuit current transformers, sensors are a toroidal type
mounted one per phase on the primary studs of the circuit breaker.
These transformers provide a signal to the static trip device
proportional to the primary current.
2. Static logic box, receives the signal from the primary current
transformers. It monitors the signal, senses overloads or faults, and
executes the required action in accordance with preselected settings.
3. Tripping actuator, a magnetically held latch device that receives the
output signal from the static logic box, and in turn causes the circuit
breaker to open.
The power supply for the static logic boxes and the tripping actuator is
supplied from a separate set of sensors mounted in the breaker studs. In
addition to the phase overcurrent logic boxes, a ground fault sensing feature
may be provided. New design advances are continually being made in the
development of static-trip devices.
Electrical Resistance
The electrical resistance of an object is a measure of its opposition to the passage of a
steady electric current. An object of uniform cross section will have a resistance
proportional to its length and inversely proportional to its cross-sectional area, and
proportional to the resistivity of the material. Discovered by Georg Ohm in the late
1820s, electrical resistance shares some conceptual parallels with the mechanical
notion of friction. The measurement unit of electrical resistance is the ohm, symbol .
The resistance of an object determines the amount of current through the object for a
given potential difference across the object, in accordance with Ohm's law:
Primary Contacts
& Arcing Contacts
rise should not be used. Thermography can be used to locate these problems but
additional testing is needed to determine the severity and the cause of the heat.
Because the breakers may be stacked in the panel or switchgear it may be difficult to
get line of sight to the side of the breaker, where the breaker body material is thinnest,
to see a temperature rise on the breaker body. The heat is sometimes also located in
the space between two breakers. While conducting the inspection, it is important to
move around because the heat may be seen reflecting off the back of the panel or bus
behind the breaker.
The thermal images above show the results of a breaker with internal heating. The heating
cannot be seen on the breaker body but as a reflection on the back of the panel.
When these types of thermal anomalies are located it is important to know the load of all
phases of the breaker. If the load is balanced then a simple Milli-volt drop test can be
conducted. A Milli-volt drop test can disclose several abnormal conditions inside a
breaker such as eroded contacts, contaminated contacts, or loose internal connections.
This test is conducted while the circuit is energized and under load. One lead of a volt
meter is placed on the load side with the other on the line side of the breaker. The
reading is the voltage drop through the breaker internal connections. These readings
can then be compared to one another to determine if the problem is internal to the
breaker. If the load is not balanced, the voltage drop readings are collected using a volt
meter. Then Ohms law can be used to calculate the resistance of each phase. After
the calculated resistance is found for each phase the values can then be compared to
each other to determine if the problem is internal to the breaker.
Conclusion
While conducting an infrared inspection of an electrical system it is important to think
outside the box. A building electrical system consists of many integral parts that all
must operate together to be a safe and efficient system. Thermography is an important
tool in finding problems within the system; however, there must be other tools in the
box. If, during an inspection, problems with the circuit breakers are found it should be
noted correctly in the written report with all needed information and the customer
notified. Then, a qualified electrical testing company can perform electrical tests on
these circuit breakers to determine the proper corrective action.
References
1. Robert Friedel and Paul Israel, Edison's Electric Light: Biography of an Invention,
Rutgers University Press, New Brunswick, New Jersey USA, 1986
ISBN 0-8135-1118-6 pp. 65-66
2. B. M. Weedy, Electric Power Systems Second Edition, John Wiley and Sons,
London, 1972, ISBN 0471924458 pp. 428-430
3. http://bonle.en.alibaba.com/product/50348671/51680889/Switch/MCB_MCCB.html
4. http://www3.interscience.wiley.com/journal/113307491/abstract?CRETRY=1&
SRETRY=0 Electrical Engineering in Japan, vol. 157 issue 4 pp. 13-23
5. United States Department of the Interior Bureau of Reclamation. Denver, Colorado,
Facilities Instructions, Standards and Techniques, Volume 3-16, Maintenance of
Power Circuit Breakers, Internet Version of this Manual Created December 1999,
Hydroelectric Research and Technical Services Group