MAM100 User Manual
MAM100 User Manual
MAM100 User Manual
MAM-KY02SVF B - VF-
Monitor-100
USER
MANUAL
VOTE OF THANKS
Thank you for your trustworthy and select of PLOT air compressor controller !
Shenzhen Plot Electronic Co., Ltd specializes on the manufacture and R&D of air
compressor controller. We are devoted to win customer trust through our high
quality products and service.
We try our best to ensure the completeness and correctness of the manual, but
PLOT Company shall reserve the rights for continuous research and improvement on
its products and assume no obligation for the modification and improvement on the
previously delivered products. The design of products is subject to the change
without notice.
Please feel free to contact our after-sale service center if you encounter any
problem with our product.
You are always welcome to make suggestions and advices!
NOTICE
Please read all the operation manual before operating the set and keep this manual for further
reference.
Installation position shall be considered carefully in order to ensure good ventilation and reduce
electromagnetic interference.
Wiring shall be performed respectively according to regulations for heavy and weak current to reduce
electromagnetic interference.
RC snubber must be connected to the two terminals of coil (such as AC contactor ,valve, etc),which
are controlled by relay output.
Port connection shall be inspected carefully before power on.
Correct ground connection (the third ground)can help increase product capacity of resisting signal
interference.
Set rated current of motor: the max current of motor/1.2.
Features
Chinese / English display.
Integrate PID calculation and control , adjust load rate automatically based on air pressure and inverter
operation frequency
current open phase, current overload, current unbalance protection for motor
On-off control and running control of motor.
Prevention for air compressor reversal
Temperature measurement , control and protection
High integration , high reliability ,high cost performance.
Remote control/Local control.
Block mode/Independent mode.
RS-485 communication function, one for inverter and the other for block control or external communication
Contents
1,Basic Operation..................................................................................................................................................... 5
1.1, Button Explanation................................................................................................................................... 5
1.2, Status Display and Operation .................................................................................................................. 6
2, Contoller Function and Technical Parameter ................................................................................................. 12
3,Model and Specification ..................................................................................................................................... 13
3.2, Power specification sheet for corresponding motor. ............................................................................ 14
4, Inverter Communication................................................................................................................................... 14
4.1Communication Function..................................................................................................................... 14
4.2Communication Set .............................................................................................................................. 14
4.3Inverter Upgrade Explanation ....................................................................................................... 15
5, Installation.......................................................................................................................................................... 16
5.1, Mechanical Installation .......................................................................................................................... 16
5.2, Electrical Connections............................................................................................................................ 18
6, Alarm Function .................................................................................................................................................. 19
6. 1Monitor Indication............................................................................................................................... 19
6.2,Controller indicator................................................................................................................................. 19
7, Controller Protection......................................................................................................................................... 20
8, Troubleshooting ................................................................................................................................................. 21
8.1This Fault Review ................................................................................................................................. 21
8.2Common Failures and Causes:............................................................................................................ 21
9, Schematic Diagram........................................................................................................................................ 23
1,Basic Operation
1.1, Button Explanation
Picture 1
ONStart Button:
1,When compressor is at stop status, press this button to start the compressor.
2,When compressor is set as master ( No.1 ) in block mode ,press this button to start the compressor
and activate block mode function at the same time.
OFFStop Button
1, When the compressor is at running status, press this button to stop the compressor;
2, When compressor is set as master (No.1 ) in block mode ,press this button to stop compressor and
block mode function as well;
3, When compressor is at stop status, long press this button to display software edition.
M Set Button:
1. When modifying data, press this button after modification to save and confirm the modified data.
2. When the compressor is at password setting status ,press this button to save and confirm the
password
1,when viewing the menu, press this button to move upward the cursor ;
2,When modifying data, press this button to increase the data at current position .
SCREW COMPRESSOR
CURR(A)R
S
T
MOTOR 56.1 56.2 56.0
FAN 4.1 4.1
4.1
Press RT to return to the previous menu or the main menu. If no operation at the current menu for 120
seconds , controller will automatically return to the main menu and turn off the back light simultaneously.
According to above method, use move down ,move up button, enter buttonand return button RT
to check TOTAL RUN TIME,THIS RUN TIME,VSD PARAMETER,MAINTENANCE PARA,FAULT
RECORD, PROD.DATESERIAL,THIS FAULT and return to previous menu.
1.2.2, Calendar
Check and set time of controller
TIME
2004-2-22
WEEK0
12:46:59
Move the cursor to item LOAD P, then press to switch to the following menu which requires a user
password input.
INPUT PASSWORD
****
Note: User password can be modified in customer parameter and FACTORY PARAMETER
is fixed as
In this menu, the first data bit of password starts blinkingpress or to modify the first bit of
passwordPress to move the cursor to the next data bit, modify the second data of password in
accordance with the above , and modify the third and fourth data of password in sequence. PressM to
confirm the input data and the menu will switch to the following menu after verification:
LOAD P00.65MPa
UNLD P00.80MPa
FAN START T0080
FAN STOP T0070
In the menu above , press , the first data of LOAD P starts blinking ,user can press orto
modify the present data in accordance with the above method .Press to move to next data and modify the
target data in sequence. When finished, press M to confirm and save the data.
B, Customer Parameter Sheet and Function
First menu
SET P T VSD
PARAMETER
Second menu
Preset Data
LOAD P
00.65MPa
UNLD P
00.80MPa
FAN START T
FAN STOP T
0080
0070
VSD P
00.70MPa
MOTOR
POWER
MOTOR
SPEED
RAT
RAT
Function
1,In AUTO load mode , compressor will load if
pressure is below this set data
2,In STANDBY mode, compressor will start if the
pressure is below this set data
1,Compressor will unload automatically if air
pressure is above this set data
2.This data should be set above LOAD P ,also
should be set below UNLD P LIM
Fan will start if DISC T is above this set data
Fan will stop if DISC T is below this set data
Set AIR P for VSD compressor to keep running
stable, when pressure is fluctuated around this
data, controller will adjust operation frequency of
inverter to control the pressure close to this data
Set RATED POWER in order to calculate actual
power
Set RATED SPEED at 50HZ in order to calculate
the actual speed in variable frequency
022.0KW
2600RPM
SET TIME
MOTOR START
TIME
0008S
FAN
TIME
START
0003S
STAR
TIME
LOAD
TIME
DELAY
DELAY
0006S
0002S
STANDBY
DELAY
0600S
STOP DELAY
0010S
RE-START
DELAY
0100S
VSD UP SPEED
0010
VSD DN SPEED
0010
START MODE
LOCAL/
REMOTE
LOAD MODE
AUTOMATI
CAL/MANU
AL
COM MODE
DISABLE/
BLOCK/
COMPUTER
COM ADD
0001
OPERATION
MODE
BLOCK
PARAMETER
SET
BLOCK STATUS
MASTER/
SLAVE
BLOCK ON/OFF
ORDER/
ALONG
TURN TIME
0002H
CLR
MAINTENANCE
TIME
LANGUAGE
BLOCK
NUMBER
0002
BLOCK LOAD P
00.63MPa
BLOCK UNLD P
00.78MPa
BLOCK DELAY
0020S
OIL FILTER
0000H
O/A
SEPERATOR
0000H
AIR FILTER
0000H
LUBE
0000H
GREASE
0000H
OIL FILTER
2000H
O/A
SEPERATOR
2000H
AIR FILTER
2000H
LUBE
2000H
GREASE
2000H
CHINESE/
ENGLISH
ENGLISH
ENABLE/
DISABLE
PHASE PRO
NEW
USER
PASSWORD
****
****
1.2.4,Factory Parameter
The view and modification of factory parameter requires a factory password, The modification step is
same as customer parameter modification. Main function is as below:
PARAMETER
Initial Data
Function
10
MOTOR RATED
CURR
FAN
CURR
RATED
ALARM DISC T
105
STOP DISC T
110
STOP AIR P
00.90MPa
UNLD P LIM
0.85MPa
TOTAL LOAD
TIME
TOTAL
RUN
TIME
FAULT
RECORD RESET
000095 H
000100 H
****
CURR
UNBALANCE
0006
OPEN
PROT
002.0S
PHASE
INVERTER
MODEL
ATV61/ATV31/7200GS
SINE303/V5-H/CIMR-F7B/
SHF/MD320/SB60/SB61/
LB60G/POWTRAIN/HOLP/
MEGMEET/ACS550
510/MM440
PROD.DATE
SERIAL NO.
9999-99-99
9999999999
MOTOR
SCALE
INT
MOTOR
INITIAL
INT
00.20MPa
0020
MOTOR
GAIN
PROP
MOTOR
GAIN
INT
0010
0012
STEADY-STATE ERRORS
MOTOR
DIFF
GAIN
COIL STOP T
MOTOR
FREQ
MIN
MOTOR
FREQ
MOTOR
FREQ
UNLD
MAX
0000
000
040.0HZ
0030.0HZ
180.0HZ
RUN MODE
VSD/PF
FREQ SEL
50Hz/60Hz
DESCEND P
00.72MPa
DESCEND FREQ
005.0HZ
MOTOR
MODE
SLOW/FREE
STOP
2.5.1Oil temperature20150Accuracy1
2.5.2Discharge temperature20150Accuracy1
2.5.3Running time0999999H
2.5.4Current0999.9A
2.5.5Pressure01.60MPa
Accuracy:0.01Mpa
2.6,Phase protection: When compressor is at stop mode and detects open phase, response time2s
2.7,Motor protection: This controller provides open phase, unbalance and overload protection to motor and
fan.
2.7.1Open phase protectionWhen any phase opens, the response time equals to set timeThis function is not
activated when OPEN PHASE PROTECTION time is set over 20s
2.7.2Unbalance protection: when MAX-MIN current >= SET DATA *MIN current/10 ,respond time is
5s
2.7.3Protection features of overload (time unit: second)please see following tabletable 2.1.1for your
reference. MultipleIactualIset ,response time is shown in following table (table 2.1.1) according to
overload multiples from 1.2 times and 3.0 times .
Iactual/Iset
Time parameter
1.2
1.3
1.5
1.6
2.0
3.0
Response timeS
60
48
24
MAMKY02SVF40BTIII
Control mode III
TRS485communication
BPressure transmitterKpressure switch
Motor max operating current
VVane compressorSScrew compressor
02 controllerLCD display
Model
13
Remark
Description
With CT
4, Inverter Communication
4.1Communication Function
Controller can read relevant information such inverter operation frequency, output current, output voltage,
motor speed and inverter fault and so on through the second RS 485 communication port A2 (485+)B2
(485-)(see detail in picture 4.1.1).In the main interface, it can display inverter operation frequency, motor
power, motor speed, output voltage and so on. For more parameter, please check VSD PARAMETER in the
RUN PARAMETER. To avoid communication interference, it is necessary to ground connect controller shell
when controller communicates with inverter. Also, please use the cable with shielded covering to connect with
controller. There will be an information to indicate if communication between controller and inverter is
interrupted, in this way, please check the communication cable and the inverter parameter set.
RS485
24+
24-
RS485
A1 B1 A2 B2
Picture 4.1.1
4.2Communication Set
Inverter set
When controller communicates with inverter,the Baud rate is 9600Bps,1 start bit,8 data bit,1 stop bit,
No parity check bit and inverter communication address is 001.User can set relevant communication
parameter through inverter menu,(See inverter communication set for detail).It is require to power off and
reset after communication parameter is set
Note: To avoid communication interference, it is necessary to ground connect controller shell when
controller communicates with inverter
Controller Set
Set the INVERTER NAME in FACTORY PARAMETER(Different inverter share different data
address register. Controller read inverter RUN PARAMETER through the INVERTER NAME set
here).After set,enter USER PARAMETER and set RATED POWER and SPEED at 50HZ. based on this
set ,calculate the actual power and speed for user reference.
14
VOLT
CURR
FREQ
POWR
ADDRESSFFFF
ADDRESSFFFF
ADDRESSFFFF
ADDRESSFFFF
Set
the
voltage
address .hexadecimal
V=REC*FFFFFFFF
I=REC*FFFFFFFF
F=REC*FFFFFFFF
P=REC*SET/1 *FFFFFFFF
COM FORM8N1-NONE
VSD ADD0001
Example
A customer wants to use SB70 inverter, SB70 communication protocol is not set in the inverter yet
and the information in the inverter manual is as below
Output current address1202Hdigits
.01A
Output voltage address1204Hdigits
.1V
Output frequency address1200Hdigits
.01HZ
Output power address1208Hdigits .1KW
To communicate with SB70,please set as below
Factory parameter
FAULT RECORD RESET9999
CURR UNBALANCE0008
OPEN PHASE PROT00.30S
INVERTER NAMESELF-DEFF
SetSELF-DEFF
15
Return to the main menu, move the cursor to FACTORY PARAMETER, and press password 2688
to enter INVERTER SET like picture below.
VOLT
CURR
FREQ
POWR
ADDRESS1204
ADDRESS1202
ADDRESS1200
ADDRESS1208
After
read
voltage
successfully, the voltage will
transfer to a one digit number
V=REC*00010001
I=REC*00010010
F=REC*00010010
P=REC* 1 *00010001
COM FORM8N1-NONE
VSD ADD0001
SB70
support
MODBUS
RTU
protocolthe data format can set as
8N1no parity bit
5, Installation
5.1, Mechanical Installation
5.1.1, CT Installation
The CT shall be installed at a place where the current of motor cable can be measured, thus, controller can
be set according to instructions on motor nameplate, and the detailed dimension is shown as below:
A
B
5.1.2,Controller Installation
When install the controller, room should be left around controller for wiring. The specific dimension is
shown as below:
1IndicatorIN
The corresponding digital input terminal of 0001020304
050607 is 20 1918
1716151413.
2IndicatorOUT
The corresponding digital input terminal of 0001020304
0506070809 is 2728 293031353637
3839
3Power IndicatorPWR
4Run indicatorRUN
5Error indicatorERR
Picture 5Controller structure dimension
5.1.3,Panel Function and Installation Panel Structure 16510250mm
164
49
80C
8.5MPa
ON
91.5
RT
17
Note : Electromagnetism coil shall be connected nearest with RC snubber during wiring, Dotted line is
for extra function
6, Alarm Function
6. 1Monitor Indication
6.1.1, Air Filter Alarm
. Air filter block check.
The monitor displays AIR BLOCK by checking pressure differential switch close.
. Air filter running time alarm
The text displays AIR TIME END when running time of the air filter is exhausted.
6.2,Controller indicator
Indicator
Indicator status
Power
Controller power on
PWR indicator on
Run
Controller run
RUN indicator on
19
Error
Digital input
Digital output
Terminal 394041424346
OUT00~09 corresponding indicator on
47495051digital output
Data storage
7, Controller Protection
7.1, Motor protection
MAMKY02SVF compressor controller provide short circuit ,block, overload, lack phase, unbalance
protection to motor.
Electronic
failure
Failure display
Reason
Short circuit
Current Block
Overload
Lack phase
Unbalance
8, Troubleshooting
8.1This Fault Review
Alarm and stop caused by the external parts of controllers may be removed by checking THIS FAULT or
FAULT RECORD, method is shown as below:
Press to move the cursor to RUN PARAMETER menu, then press,the secondary menu will show as
below:
MOTOR FAN CURR
VSD PARA
TOTAL RUN TIME
THIS RUN TIME
MAINTENANCE PARAMETER
FAULT RECORD
PROD.DATESERIAL
THIS FAULT
Move the cursor to THIS FAULT menu Then pressto switch to the following menudisplay failure
STOP: DISC T SENSOR
FAULT
170
Reason
Solution
High discharge
temperature
Temperature Sensor
Failure
High Pressure
21
Lack water
Open Phase
Overload
Unbalance
Wrong Phase Sequence
Fan fail to run
Motor overload during
start
Main Contactor shakes
frequently
22
9, Schematic Diagram