SCREW AIR COMPRESSOR CONTROLLER

MAM-KY02SVF B - VF-
Monitor-100

USER
MANUAL

Shenzhen Plot Electronic Co., Ltd


Address4-5F,5 Bldg,Highstar Industry Park,Gangtou Community,
Bantian,Longgang District,Shenzhen CityChina
Telephone+86 075583173599 / 83172822 Postal code518034
Fax+86 075583172966
E-mailplt@pltsz.com
Web sitewww.pltsz.com

VOTE OF THANKS
Thank you for your trustworthy and select of PLOT air compressor controller !
Shenzhen Plot Electronic Co., Ltd specializes on the manufacture and R&D of air
compressor controller. We are devoted to win customer trust through our high
quality products and service.
We try our best to ensure the completeness and correctness of the manual, but
PLOT Company shall reserve the rights for continuous research and improvement on
its products and assume no obligation for the modification and improvement on the
previously delivered products. The design of products is subject to the change
without notice.
Please feel free to contact our after-sale service center if you encounter any
problem with our product.
You are always welcome to make suggestions and advices!

NOTICE

Please read all the operation manual before operating the set and keep this manual for further
reference.

Installation of MAMKY** compressor controller can be performed only by professional technicians.

Installation position shall be considered carefully in order to ensure good ventilation and reduce
electromagnetic interference.
Wiring shall be performed respectively according to regulations for heavy and weak current to reduce
electromagnetic interference.
RC snubber must be connected to the two terminals of coil (such as AC contactor ,valve, etc),which
are controlled by relay output.
Port connection shall be inspected carefully before power on.
Correct ground connection (the third ground)can help increase product capacity of resisting signal
interference.
Set rated current of motor: the max current of motor/1.2.

Features
Chinese / English display.
Integrate PID calculation and control , adjust load rate automatically based on air pressure and inverter
operation frequency
current open phase, current overload, current unbalance protection for motor
On-off control and running control of motor.
Prevention for air compressor reversal
Temperature measurement , control and protection
High integration , high reliability ,high cost performance.
Remote control/Local control.
Block mode/Independent mode.
RS-485 communication function, one for inverter and the other for block control or external communication

Contents
1,Basic Operation..................................................................................................................................................... 5
1.1, Button Explanation................................................................................................................................... 5
1.2, Status Display and Operation .................................................................................................................. 6
2, Contoller Function and Technical Parameter ................................................................................................. 12
3,Model and Specification ..................................................................................................................................... 13
3.2, Power specification sheet for corresponding motor. ............................................................................ 14
4, Inverter Communication................................................................................................................................... 14
4.1Communication Function..................................................................................................................... 14
4.2Communication Set .............................................................................................................................. 14
4.3Inverter Upgrade Explanation ....................................................................................................... 15
5, Installation.......................................................................................................................................................... 16
5.1, Mechanical Installation .......................................................................................................................... 16
5.2, Electrical Connections............................................................................................................................ 18
6, Alarm Function .................................................................................................................................................. 19
6. 1Monitor Indication............................................................................................................................... 19
6.2,Controller indicator................................................................................................................................. 19
7, Controller Protection......................................................................................................................................... 20
8, Troubleshooting ................................................................................................................................................. 21
8.1This Fault Review ................................................................................................................................. 21
8.2Common Failures and Causes:............................................................................................................ 21
9, Schematic Diagram........................................................................................................................................ 23

1,Basic Operation
1.1, Button Explanation

Picture 1
ONStart Button:
1,When compressor is at stop status, press this button to start the compressor.
2,When compressor is set as master ( No.1 ) in block mode ,press this button to start the compressor
and activate block mode function at the same time.
OFFStop Button
1, When the compressor is at running status, press this button to stop the compressor;
2, When compressor is set as master (No.1 ) in block mode ,press this button to stop compressor and
block mode function as well;
3, When compressor is at stop status, long press this button to display software edition.
M Set Button:
1. When modifying data, press this button after modification to save and confirm the modified data.
2. When the compressor is at password setting status ,press this button to save and confirm the
password

Move up button/Increasing button:


5

1,when viewing the menu, press this button to move upward the cursor ;
2,When modifying data, press this button to increase the data at current position .

Move down button / Decreasing button:


1, When viewing the menu, press this button to move downward the cursor;
2,When modifying data, press this button to decrease the data at current position.
Shift button /Enter button:
1,When modifying data, press this button to move to the next data bit;
2,when select menu, press this button to switch to submenu. If no submenu available, the controller
will shift to data setting mode.
RTReturn button / Reset button:
1, When modifying data, press this button to exist data setting mode;
2, When viewing the menu, press this button to return to previous-menu;
3, When the controller is at failure stop status, long press this button to reset.

1.2, Status Display and Operation


The display screen will show as below after power on:
WELCOME

SCREW COMPRESSOR

After 5 seconds, the menu will switch as below:


DISC T20 FREQ:50HZ
AIR P0.60Mpa SPEED:1234RPM
LOADING
FAN START
FREQ:123.1KW
VOLT:381V C01
Press to enter into Selection Menu:
RUN PARAMETER
CALENDAR
CUSTOMER PARAMETER
FACTORY PARAMETER
1.2.1, Operating Parameter and Menu
Press or to move the cursor to RUN PARAMETER, then press to switch to secondary
menu:
MOTORFAN CURR
VSD PARAMETER
TOTAL RUN TIME
THIS RUN6 TIME

Move the cursor to MOTOR,FAN CURR ,press to switch to secondary menu:

CURR(A)R
S
T
MOTOR 56.1 56.2 56.0
FAN 4.1 4.1
4.1
Press RT to return to the previous menu or the main menu. If no operation at the current menu for 120
seconds , controller will automatically return to the main menu and turn off the back light simultaneously.
According to above method, use move down ,move up button, enter buttonand return button RT
to check TOTAL RUN TIME,THIS RUN TIME,VSD PARAMETER,MAINTENANCE PARA,FAULT
RECORD, PROD.DATESERIAL,THIS FAULT and return to previous menu.
1.2.2, Calendar
Check and set time of controller
TIME
2004-2-22
WEEK0
12:46:59

1.2.3, Customer Parameter


A, Customer parameter view and modification
It is not allowed to modify CUSTOMER PARAMETER and FACTORY PARAMETER in running status and
STOP DELAY
The check and modification of CUSTOMER PARAMETER is similar with RUN PARAMETER. Take
UNLOAD P as example: Move orto CUSTOMER PARAMETER and then press to switch to below
menu
SET PTVSD PARAMETER
SET TIME
OPERATION MODE
BLOCK PARAMETER SET
press to switch to below menu
LOAD P00.65MPa
UNLD P00.80MPa
FAN START T0080
FAN STOP T0070

Move the cursor to item LOAD P, then press to switch to the following menu which requires a user

password input.
INPUT PASSWORD
****

Note: User password can be modified in customer parameter and FACTORY PARAMETER
is fixed as
In this menu, the first data bit of password starts blinkingpress or to modify the first bit of
passwordPress to move the cursor to the next data bit, modify the second data of password in
accordance with the above , and modify the third and fourth data of password in sequence. PressM to
confirm the input data and the menu will switch to the following menu after verification:

LOAD P00.65MPa
UNLD P00.80MPa
FAN START T0080
FAN STOP T0070

*in the right up corner


indicates that the data is at a
setting status

In the menu above , press , the first data of LOAD P starts blinking ,user can press orto
modify the present data in accordance with the above method .Press to move to next data and modify the
target data in sequence. When finished, press M to confirm and save the data.
B, Customer Parameter Sheet and Function

First menu

SET P T VSD
PARAMETER

Second menu

Preset Data

LOAD P

00.65MPa

UNLD P

00.80MPa

FAN START T
FAN STOP T

0080
0070

VSD P

00.70MPa

MOTOR
POWER
MOTOR
SPEED

RAT
RAT

Function
1,In AUTO load mode , compressor will load if
pressure is below this set data
2,In STANDBY mode, compressor will start if the
pressure is below this set data
1,Compressor will unload automatically if air
pressure is above this set data
2.This data should be set above LOAD P ,also
should be set below UNLD P LIM
Fan will start if DISC T is above this set data
Fan will stop if DISC T is below this set data
Set AIR P for VSD compressor to keep running
stable, when pressure is fluctuated around this
data, controller will adjust operation frequency of
inverter to control the pressure close to this data
Set RATED POWER in order to calculate actual
power
Set RATED SPEED at 50HZ in order to calculate
the actual speed in variable frequency

022.0KW
2600RPM

SET TIME

MOTOR START
TIME

0008S

FAN
TIME

START

0003S

STAR
TIME
LOAD
TIME

DELAY
DELAY

0006S

Interval time from star start to delta start.

0002S

Unloading in this set time after enter delta running

STANDBY
DELAY

0600S

STOP DELAY

0010S

RE-START
DELAY

0100S

VSD UP SPEED

0010

VSD DN SPEED

0010

START MODE

LOCAL/
REMOTE

LOAD MODE

AUTOMATI
CAL/MANU
AL

COM MODE

DISABLE/
BLOCK/
COMPUTER

COM ADD

0001

OPERATION
MODE

BLOCK
PARAMETER
SET

Set the MOTOR START TIME. Record time


when motor is activated, controller will not start
overload protection during this time to avoid
impulse starting current stopping the motor.
Set the FAN START TIME. Record time when fan
is activated, controller will not start overload
protection during this time to avoid impulse
starting current stopping the fan.

BLOCK STATUS

MASTER/
SLAVE

BLOCK ON/OFF

ORDER/
ALONG

TURN TIME

When unloading continuously, compressor will


automatically stop and enter to standby status if
over this set time
For NORMAL STOP operation, compressor will
stop after it continuously unloads over this set time
Machine can start only over this set time at any
case(after normal stop, standby or alarm &stop)
Restrict PID calculations in case the frequency
increasing too fast which cause motor speeding up
too fast
Restrict PID calculations in case the frequency
decreasing too fast which cause motor slowing
down too fast
LOCAL :only the button on the controller can turn
on and turn off the machine.
REMOTE: both the button on the controller and
the remote control button can turn on and turn off
the machine;
MANUAL : only when the pressure is above
UNLD P, compressor will
unload automatically .For any other case ,the
Load/Unload function can only be executed by
pressing load/unload key.
AUTOMATICAL: the load/unload function can be
executed by the fluctuation of AIR P automatically
DISABLE: communication function is not
activated.
COMPUTER: compressor can communicate with
computer or DCS as slave according to
MODBUS-RTU.
BLOCK: compressors can work in a net
Set the communication address in COMPUTER or
BLOCK mode. This address is unique for every
controller in net
1.When service as master in BLOCK, master
controls slave; the COM ADD should be set as
No.1
2.When service as slave in BLOCK, slave is
controlled by master

When master pressure is between BLOCK


LOAD P and BLOCK UNLD P, master
determines slave to work alternatively after
working over this set time

0002H

CLR
MAINTENANCE
TIME

MAX LIFE TIME

LANGUAGE

BLOCK
NUMBER

0002

BLOCK LOAD P

00.63MPa

BLOCK UNLD P

00.78MPa

BLOCK DELAY

0020S

OIL FILTER

0000H

O/A
SEPERATOR

0000H

AIR FILTER

0000H

LUBE

0000H

GREASE

0000H

OIL FILTER

2000H

O/A
SEPERATOR

2000H

AIR FILTER

2000H

LUBE

2000H

GREASE

2000H

CHINESE/
ENGLISH

ENGLISH
ENABLE/
DISABLE

PHASE PRO
NEW
USER
PASSWORD

Number of air compressors in block net

****

****

In BLOCK mode, one compressor will start or


load when master AIR P is below this set data
In BLOCK mode, one compressor will stop or
unload when master AIR P is above this set
data
In BLOCK mode, when master sends two
commands continuously, second command
signal delays for this set data
Record total running time of oil filter. If
changing new oil filter, the data should be reset
by manual operation.
Record total running time of O/A separator. If
changing new O/A separator, the data should
be reset by manual operation
Record total running time of air filter .If
changing new air filter, the data should be reset
by manual operation
Record total running time of lubricant. If
changing new lubricant, the data should be
reset by manual operation
Record total running time of grease. If
changing new grease, the data should be reset
by manual operation
1, Alarm prompt when total running time of oil
filter is above the set data .
2,Set this data to 0000 , alarm function for
oil filter running time is not activated
1, Alarm prompt when total running time of
O/A separator is above the set data.
2,Set this data to 0000 ,alarm function for
O/A separator running time is not activated
1, Alarm prompt when total running time of air
filter is above the set data.
2,Set this data to 0000 , alarm function for
air filter running time is not activated
1, Alarm prompt when total running time of
lubricant is above the set data.
2, Set this data to 0000, alarm function for
lubricant running time is not activated.
1, Alarm prompt when total running time of
grease is above the set data.
2,Set this data to 0 , alarm function for
grease running time is not activated
ENGLISH: Displays in English
CHINESE: Displays in Chinese
Enable: PHASE PRO function is activated
Disable: PHASE PRO function is not activated
User could modify the user password by old
user password or factory password

1.2.4,Factory Parameter
The view and modification of factory parameter requires a factory password, The modification step is
same as customer parameter modification. Main function is as below:
PARAMETER

Initial Data

Function
10

MOTOR RATED
CURR

Maximum motor overload


data /1.2

FAN
CURR

Maximum fan overload


data/1.2

RATED

ALARM DISC T

105

STOP DISC T

110

STOP AIR P

00.90MPa

UNLD P LIM

0.85MPa

TOTAL LOAD
TIME
TOTAL
RUN
TIME
FAULT
RECORD RESET

000095 H

Modify the TOTAL LOAD TIME

000100 H

Modify the TOTAL RUN TIME

****

Input8888and press set button to clear all the history


fault record.

When MAX -MIN CURRENT >=1+ SET


DATA*MIN CURRENT/10 ,the unbalance

CURR
UNBALANCE

0006

OPEN
PROT

002.0S

PHASE

INVERTER
MODEL

ATV61/ATV31/7200GS
SINE303/V5-H/CIMR-F7B/
SHF/MD320/SB60/SB61/
LB60G/POWTRAIN/HOLP/
MEGMEET/ACS550

510/MM440

PROD.DATE
SERIAL NO.

9999-99-99
9999999999

MOTOR
SCALE

INT

MOTOR
INITIAL

INT

When the current of motor is more than 1.2 times of the


set data , the unit will stop for overload feature. (see
table2.1.1)
When the current of fan is more than 1.2 times than the
set data , the unit will stop for overload feature.
When discharge temperature reaches this set data,
compressor will alarm
When the discharge temperature reaches this set
data, compressor will alarm and stop
When pressure reaches this set data ,compressor will
alarm and stop
This data is the maximum of UNLD P. The UNLD P in
the customer parameter must be set no higher than this
data.

00.20MPa

0020

protection is activated ,compressor will alarm and stop,


reporting MOTOR CURR UNBAL
If the set data 15, the unbalance protection will not be
activated.
If OPEN PHASE protection 20 seconds, OPEN
PHASE protection is not activated
Set inverter model.Controller will read inverter running
parameter based on the model set.
ATV61 Schneider 61/71 inverter
ATV31Schneider 31 inverter
7200GSTECO 7200GS inverter
SINE303CINEE inverter
V5-HV&T inverter
CIMR-F7BYASKAWA inverter
MD320Henchman inverter
SHFSANKEN inverter
SB60/SB61SENLAN inverter
LB60GLEEPER inverter
POWTRAINPOWTRAN inverter
HOLPHOLIP inverter
MEGMEETMEGMEET inverter
ACS550510:ABB inverter
MM440: Siemens 440 inverter
Production date set by manufacturer
Serial No. set by manufacturer
(PID TARGET P - INTEGRAL SCALE)< detected
AIR P < (PID TARGET P + INTEGRAL
SCALE,INTEGRAL GAIN works
When detected AIR P<PID TARGET P -INTEGRAL
SCALEor
Detected AIR P> PID TARGET P +INTEGRAL
SCALE
Integral calculation is based on this data
11

MOTOR
GAIN

PROP

MOTOR
GAIN

INT

Track speed of PID TARGET P , the bigger the data, the


faster the track; the smaller the data, the slower the track
Track the speed of PID TARGET P and STEADY
STATE ERROR, the bigger the data ,the faster the track
and smaller the STEADY-STATE ERRORS; the
smaller the data ,the slower the track and bigger the

0010

0012

STEADY-STATE ERRORS
MOTOR
DIFF
GAIN
COIL STOP T
MOTOR
FREQ

MIN

MOTOR
FREQ
MOTOR
FREQ

UNLD
MAX

0000
000
040.0HZ
0030.0HZ

Permitted operating frequency in UNLD MODE

180.0HZ

The maximum operating frequency in loading status

RUN MODE

VSD/PF

FREQ SEL

50Hz/60Hz

DESCEND P

00.72MPa

DESCEND FREQ

005.0HZ

MOTOR
MODE

SLOW/FREE

STOP

Track the hysteresis system(such as temperature) ,it is


not used very often and normally set as 0000
Spare
In the process of adjustment, The minimum operating
frequency when pressure is over the LOAD P pressure
and not reach the UNLD P

PF: Star-delta wll run


VSD:inverter will run
(refer to schematic diagram and operation control
Choose operation power frequency.(This parameter
influences the sample current value. When this data is set
incorrectly, the actual current is 1.2 times different from
displayed current value)
When set as VSD mode and AIR P is detected higher
than set DESCEND P, DESCEND FREQ works.( This
data is only available in MOTOR VSD or MOTOR/FAN
VSD mode)
Suggest: this set data = VSD P+0.02(MPa)
In VSD mode ,when the AIR P is detected higher than
the set DESCEND P ,sent the data (CONTROL
FREQUENCY based on the PID OPERATING
REQUENCY- SET DESCEND FREQUENCY) to
inverter to avoid AIR P over PID TARGET PRESS too
far which may cause the compressor loading and
unloading frequently.
Suggest: this set data <=Motor max frequency1% (Hz)
SLOW: When compressor receives stop command,
INLET VALVE terminals will open and MOTOR
INVERTER RUN terminal will open. The compressor
will stop according to STOP DELAY set.
FREE: When compressor receives stop command, Inlet
valve will open. MOTOR INVERTER RUN terminal
will keep closed to control inverter frequency decreasing
and it will open until 1 S before STOP DELAY finishes

2, Contoller Function and Technical Parameter


2.1,Digital input &output8 points of digital input10 points of digital relay output
2.2,Analog input& output1 points of Pt100 temperature input1 points of 420mA pressure signal input,2
groups of three phases current input (CT provided
2.3,Input voltage of phasesthree phase 380V
2.4,Controller operation power220V50/60Hz12VARecommond20VA
2.5,Measurement :
12

2.5.1Oil temperature20150Accuracy1
2.5.2Discharge temperature20150Accuracy1
2.5.3Running time0999999H
2.5.4Current0999.9A
2.5.5Pressure01.60MPa
Accuracy:0.01Mpa
2.6,Phase protection: When compressor is at stop mode and detects open phase, response time2s
2.7,Motor protection: This controller provides open phase, unbalance and overload protection to motor and
fan.
2.7.1Open phase protectionWhen any phase opens, the response time equals to set timeThis function is not
activated when OPEN PHASE PROTECTION time is set over 20s
2.7.2Unbalance protection: when MAX-MIN current >= SET DATA *MIN current/10 ,respond time is
5s
2.7.3Protection features of overload (time unit: second)please see following tabletable 2.1.1for your
reference. MultipleIactualIset ,response time is shown in following table (table 2.1.1) according to
overload multiples from 1.2 times and 3.0 times .

Iactual/Iset
Time parameter

1.2

1.3

1.5

1.6

2.0

3.0

Response timeS

60

48

24

Table 2 curve table for protection of motor


2.8, Temperature protection: when actual temperature measured is higher than temperature set; response
time2s
2.9, Contact capacity of output relay: 250V,5AContact endurance :500000 times
2.10, Current error is less than 1.0%.
2.11,RS485communication, one for inverter and the other for block control or external communication

3,Model and Specification


3.1, Model explanation

MAMKY02SVF40BTIII
Control mode III
TRS485communication
BPressure transmitterKpressure switch
Motor max operating current
VVane compressorSScrew compressor
02 controllerLCD display
Model

13

3.2, Power specification sheet for corresponding motor.


Corresponding
Current
Specification
main motor
range (A)
power (KW)
Below 11
MAMKY02SVF20
820
11-18.5
MAMKY02SVF40
1640
100
22-45
MAMKY02SVF100
200
55-90
MAMKY02SVF200
400
110
MAMKY02SVF400
600/5
200-250
MAMKY02SVF600/5

Remark

Description

With CT

Fan has three


levels of current,
such as 0.2-2.5A,
1-5A and 4-10A,
determined-by
current of motor

4, Inverter Communication
4.1Communication Function
Controller can read relevant information such inverter operation frequency, output current, output voltage,
motor speed and inverter fault and so on through the second RS 485 communication port A2 (485+)B2
(485-)(see detail in picture 4.1.1).In the main interface, it can display inverter operation frequency, motor
power, motor speed, output voltage and so on. For more parameter, please check VSD PARAMETER in the
RUN PARAMETER. To avoid communication interference, it is necessary to ground connect controller shell
when controller communicates with inverter. Also, please use the cable with shielded covering to connect with
controller. There will be an information to indicate if communication between controller and inverter is
interrupted, in this way, please check the communication cable and the inverter parameter set.

RS485
24+

24-

RS485

A1 B1 A2 B2

Picture 4.1.1
4.2Communication Set
Inverter set
When controller communicates with inverter,the Baud rate is 9600Bps,1 start bit,8 data bit,1 stop bit,
No parity check bit and inverter communication address is 001.User can set relevant communication
parameter through inverter menu,(See inverter communication set for detail).It is require to power off and
reset after communication parameter is set
Note: To avoid communication interference, it is necessary to ground connect controller shell when
controller communicates with inverter
Controller Set
Set the INVERTER NAME in FACTORY PARAMETER(Different inverter share different data
address register. Controller read inverter RUN PARAMETER through the INVERTER NAME set
here).After set,enter USER PARAMETER and set RATED POWER and SPEED at 50HZ. based on this
set ,calculate the actual power and speed for user reference.
14

4.3Inverter Upgrade Explanation


This software edition adapts to all inverter supporting MODBUS RTU (Inverter has to read output current,
output voltage, output frequency and output power)
Controller supports 38 different inverters communication protocol. Beyond these models, you can also set
the communication parameter according to below step
Enter FACTORY PARAMETER, move down cursor to INVERTER NAME and set it as
SELF-DEF
Return to the main menu, move the cursor to FACTORY PARAMETER, and press password 2688
to enter INVERTER SET like picture below
In this menu, please set the MODBUS address of output voltage, output current, output frequency
and output power. After set, move down to check data calculation menu like below picture.

VOLT
CURR
FREQ
POWR

ADDRESSFFFF
ADDRESSFFFF
ADDRESSFFFF
ADDRESSFFFF

Set
the
voltage
address .hexadecimal

V=REC*FFFFFFFF
I=REC*FFFFFFFF
F=REC*FFFFFFFF

Use percentage power ,please select SET


Use real power, please select 1

P=REC*SET/1 *FFFFFFFF
COM FORM8N1-NONE
VSD ADD0001

Set the data format to


communicate with inverter
Set communication
MODBUS address

Example
A customer wants to use SB70 inverter, SB70 communication protocol is not set in the inverter yet
and the information in the inverter manual is as below
Output current address1202Hdigits
.01A
Output voltage address1204Hdigits
.1V
Output frequency address1200Hdigits
.01HZ
Output power address1208Hdigits .1KW
To communicate with SB70,please set as below
Factory parameter
FAULT RECORD RESET9999
CURR UNBALANCE0008
OPEN PHASE PROT00.30S
INVERTER NAMESELF-DEFF

SetSELF-DEFF
15

Return to the main menu, move the cursor to FACTORY PARAMETER, and press password 2688
to enter INVERTER SET like picture below.
VOLT
CURR
FREQ
POWR

Refer to the inverter manual,


and set voltage MODBUS
register address

ADDRESS1204
ADDRESS1202
ADDRESS1200
ADDRESS1208

After
read
voltage
successfully, the voltage will
transfer to a one digit number

V=REC*00010001
I=REC*00010010
F=REC*00010010

After read frequency successfully, the


frequency will transfer to a one digit
number.SB70 frequency is with two
digits, to transfer to one digits, it should
be divided by 10

P=REC* 1 *00010001
COM FORM8N1-NONE
VSD ADD0001

SB70
support
MODBUS
RTU
protocolthe data format can set as
8N1no parity bit

5, Installation
5.1, Mechanical Installation
5.1.1, CT Installation
The CT shall be installed at a place where the current of motor cable can be measured, thus, controller can
be set according to instructions on motor nameplate, and the detailed dimension is shown as below:

Picture1CT1 Structural dimension of CT136 hole


16

Picture2CT1 Installation dimension

A
B

Picture 3Structural dimension of CT210 hole

Picture 4CT2 Installation dimension

5.1.2,Controller Installation
When install the controller, room should be left around controller for wiring. The specific dimension is
shown as below:
1IndicatorIN
The corresponding digital input terminal of 0001020304
050607 is 20 1918
1716151413.
2IndicatorOUT
The corresponding digital input terminal of 0001020304
0506070809 is 2728 293031353637
3839
3Power IndicatorPWR
4Run indicatorRUN
5Error indicatorERR
Picture 5Controller structure dimension
5.1.3,Panel Function and Installation Panel Structure 16510250mm
164

49

80C
8.5MPa

ON

91.5

RT

Picture 6,Panel Dimension

17

Picture 7, Hole dimension

5.2, Electrical Connections

Picture 8Terminal arrangement diagram


Monitor connection terminal
There are five connection cables and a communication cable which are used for display connection , RS-485
communication ,24V power supply.
Controller connection terminal
Communication cable is used to connect monitor and controller
1.2.3
CT1:Motor
current 4.5.6
CT2:Fan
current 79
Discharge temperature
transformer
transformer
input
Phase
input
27
28
232425
Motor contactorPF
Star contactorPF
29
Delta contactor
30
Inlet valve
31
Fan
32
Output relay COM1
34
Control inverter(VSD) 35
Control VSD Fan
37
Run indicator
38
Error indicator
39
Alarm indicator
40
Communication port 2 42
GND(analog)
43,44
220V
18

Note : Electromagnetism coil shall be connected nearest with RC snubber during wiring, Dotted line is
for extra function

6, Alarm Function
6. 1Monitor Indication
6.1.1, Air Filter Alarm
. Air filter block check.
The monitor displays AIR BLOCK by checking pressure differential switch close.
. Air filter running time alarm
The text displays AIR TIME END when running time of the air filter is exhausted.

6.1.2, Oil Filter Alarm


. Oil filter block check.
The monitor displays OIL BLOCK by checking pressure differential switch close.
. Oil filter running time alarm
The text displays OILTIME END when running time of the oil filter is exhausted.

6.1.3, O/A Separator Alarm


. O/A separator block check.
The monitor displays O/A BLOCK by checking pressure differential switch close.
. O/A filter running time alarm
The text displays O/A TIME END when running time of the oil filter is exhausted.

6.1.4, Lubricant Alarm


The text displays LUBE TIME END when running time of the lubricant is exhausted.

6.1.5, Grease Alarm


The text displays GREASE TIME END when running time of the grease is exhausted.
6.1.6, Discharge Temperature High Alarm
The text displays DISC T HIGH when DISC T is higher than ALARM DISC T set in FACTORY
PARAMETER.

6.2,Controller indicator
Indicator

Meaning and function

Indicator status

Power

Controller power on

PWR indicator on

Run

Controller run

RUN indicator on
19

Error

Failure and stop

ERR indicator blink

Digital input

Terminal 2618 digital input

IN00~08corresponding indicator on. Indicator


will not be illuminated if input has no function

Digital output

Terminal 394041424346
OUT00~09 corresponding indicator on
47495051digital output

Data storage

Data and time set

PWR blink once

7, Controller Protection
7.1, Motor protection
MAMKY02SVF compressor controller provide short circuit ,block, overload, lack phase, unbalance
protection to motor.
Electronic
failure

Failure display

Reason

Short circuit

Display Motor/FAN OVER LOAD

Short circuit or wrong current set

Current Block

Display Motor/FAN BLOCK

Overload

Display Motor/FAN OVERLOAD

Lack phase

Display Motor/FAN *LACK PHASE

Unbalance

Display Motor/FAN UNBALANCE

Overload, bearing wear and other mechanica


l failure
Overload, bearing wear and other mechanica
l failure
Power supply, contactor and open phase of
motor
Poor contact of contactor, inside open-loop of
motor

7.2, Protection of Discharge Temperature High


When DISC T is above the STOP DISC T, the controller will alarm and stop the machine. THIS FAULT
displays DISC T HIGH

7.3, Protection of Air Compressor anti-reversal


When compressor is at stop status and three phases sequence is not in order, THIS FAULT displays PHASE
WRONG1, and the controller cannot start the motor. Change the position of any arbitrary two phase power
lines and check the rotation of motor.

7.4, Protection of Air Pressure High


When the AIR P is above the MAX LIM P, the controller will alarm and stop the machine. THIS FAULT
displays HIGH P.

7.5, Protection of Sensor Fault


When pressure sensor or temperature sensor is disconnected, the controller will alarm and stop the machine.
THIS FAULT displays **SENSOR FAULT.

7.6, Protection of Air Compressor Open Phase


When compressor is at stop status and open phase is detected, THIS FAULT displays PHASE WRONG2,
and the controller cannot start the compressor. Check the three phase.
20

7.7Protection of VSD Fan


When VSD fan is failure, controller will stop

7.8 Protection of Inverter


When inverter is failure, controller will stop

8, Troubleshooting
8.1This Fault Review
Alarm and stop caused by the external parts of controllers may be removed by checking THIS FAULT or
FAULT RECORD, method is shown as below:
Press to move the cursor to RUN PARAMETER menu, then press,the secondary menu will show as
below:
MOTOR FAN CURR
VSD PARA
TOTAL RUN TIME
THIS RUN TIME

MAINTENANCE PARAMETER
FAULT RECORD
PROD.DATESERIAL
THIS FAULT
Move the cursor to THIS FAULT menu Then pressto switch to the following menudisplay failure
STOP: DISC T SENSOR
FAULT
170

User can reset fault according to the information prompted

8.2Common Failures and Causes:


Failure

Reason

Solution

High discharge
temperature

Bad vent condition, Oil shortage


etc.

Check the vent condition and lubricant amount


etc.

Temperature Sensor
Failure

Cable broken or PT100 failure

Check the wiring and PT100

High Pressure

Pressure too high or the pressure


sensor failure

Check the pressure and the pressure sensor

21

Pressure Sensor Failure

Cable broken, Sensor failure or


the cables connect reversely

Check the wiring and pressure transmitter

Lack water

Water pressure switch failure

Check water pressure switch

Open Phase

Overload

Unbalance
Wrong Phase Sequence
Fan fail to run
Motor overload during
start
Main Contactor shakes
frequently

Power open phase or the contactor


failure
Voltage too low, tubes block,
bearing wear off or other
mechanical failure or wrong set
data etc.
Current unbalance, contactor
failure or the internal open loop of
the motor
Phase sequence reversal or open
phase
Fan failure, contactor failure,no
control output
Master start time set to less than
the star delta delay time
The emergency stop button is
loose or controller is reset by
interference

22

Check the power and contactors


Check the set data, voltage, bearings, tubes and
other mechanical system.

Check the power, contactor and the motor


Check the wiring
Check wiring
Reset the master start time longer than star
delay + 2 seconds
Check if the coil of contactor connects with
RC snubber or not

9, Schematic Diagram