SCREW AIR COMPRESSOR CONTROLLER

MAM-KY02SVF( B) -( VF-Ⅲ)
(Monitor-200)

USER

MANUAL

Shenzhen Plot Electronic Co., Ltd


Address:4-5F,5 Bldg,Highstar Industry Park,Gangtou Community,
Bantian,Longgang District,Shenzhen City,China
Telephone:(+86 0755)83173599 / 83172822 Postal code:518034
Fax:(+86 0755)83172966 E-mail:plt@pltsz.com
Web site:www.pltsz.com
1
VOTE OF THANKS
Thank you for your trustworthy and select of PLOT air compressor controller !

Shenzhen Plot Electronic Co., Ltd specializes on the manufacture and R&D of air

compressor controller. We are devoted to win customer trust through our high

quality products and service.

We try our best to ensure the completeness and correctness of the manual, but

PLOT Company shall reserve the rights for continuous research and improvement on

its products and assume no obligation for the modification and improvement on the

previously delivered products. The design of products is subject to the change

without notice.

Please feel free to contact our after-sale service center if you encounter any

problem with our product.

You are always welcome to make suggestions and advices!

2
NOTICE

Please read all the operation manual before operating the set and keep this manual for further
reference.

Installation of MAM—KY** compressor controller can be performed only by professional technicians.

Installation position shall be considered carefully in order to ensure good ventilation and reduce
electromagnetic interference.

Wiring shall be performed respectively according to regulations for heavy and weak current to reduce
electromagnetic interference.

RC snubber must be connected to the two terminals of coil (such as AC contactor ,valve, etc),which
are controlled by relay output.

Port connection shall be inspected carefully before power on.

Correct ground connection (the third ground)can help increase product capacity of resisting signal
interference.

Set rated current of motor: the max current of motor/1.2.

Features:
● Chinese / English display.
● Integrate PID calculation and control , adjust load rate automatically based on air pressure and inverter
operation frequency
● current open phase, current overload, current unbalance protection for motor
● On-off control and running control of motor.
● Prevention for air compressor reversal
● Temperature measurement , control and protection
● High integration , high reliability ,high cost performance.
● Remote control/Local control.
● Block mode/Independent mode.
● RS-485 communication function, one for inverter and the other for block control or external communication

3
Contents
1,Basic Operation..................................................................................................................................................... 5
1.1, Button Explanation................................................................................................................................... 5
1.2, Status Display and Operation .................................................................................................................. 6
2, Contoller Function and Technical Parameter ................................................................................................. 12
3,Model and Specification ..................................................................................................................................... 13
3.2, Power specification sheet for corresponding motor. ............................................................................ 13
4, Inverter Communication................................................................................................................................... 14
4.1,Communication Function..................................................................................................................... 14
4.2,Communication Set .............................................................................................................................. 14
4.3,Inverter Upgrade Explanation ....................................................................................................... 14
5, Installation.......................................................................................................................................................... 16
5.1, Mechanical Installation .......................................................................................................................... 16
5.2, Electrical Connections............................................................................................................................ 18
6, Alarm Function .................................................................................................................................................. 18
6. 1、Monitor Indication............................................................................................................................... 18
6.2,Controller indicator................................................................................................................................. 19
7, Controller Protection......................................................................................................................................... 19
8, Troubleshooting ................................................................................................................................................. 20
8.1、This Fault Review ................................................................................................................................. 20
8.2、Common Failures and Causes:............................................................................................................ 21
9, Schematic Diagram:........................................................................................................................................ 23

4
1,Basic Operation
1.1, Button Explanation

Picture 1

I——Start Button:
1,When compressor is at stop status, press this button to start the compressor.
2,When compressor is set as master ( No.1 ) in block mode ,press this button to start the compressor
and activate block mode function at the same time.

O——Stop Button:
1,When the compressor is at running status, press this button to stop the compressor;
2,When compressor is set as master (No.1 ) in block mode ,press this button to stop compressor and
block mode function as well.

——Load / unload Button:


When the compressor is at running status ,press this button to load or unload ;

S——Set Button:
1. When modifying data, press this button after modification to save and confirm the modified data.
2. When the compressor is at password setting status ,press this button to save and confirm the
password

——Move up button/Increasing button:


1,when viewing the menu, press this button to move upward the cursor ;
2,When modifying data, press this button to increase the data at current position .

5
——Move down button / Decreasing button:
1, When viewing the menu, press this button to move downward the cursor;
2,When modifying data, press this button to decrease the data at current position.

——Shift button /Enter button:


1,When modifying data, press this button to move to the next data bit;
2,when select menu, press this button to switch to submenu. If no submenu available, the controller
will shift to data setting mode.

C——Return button / Reset button:


1, When modifying data, press this button to exist data setting mode;
2, When viewing the menu, press this button to return to previous-menu;
3, When the controller is at failure stop status, long press this button to reset.

1.2, Status Display and Operation


The display screen will show as below after power on::
WELCOME

SCREW COMPRESSOR

After 5 seconds, the menu will switch as below:


DISC T:20℃ FREQ:50HZ
AIR P:0.60Mpa SPEED:1234RPM
LOADING FAN START
FREQ:123.1KW VOLT:381V C01

Press “” to enter into Selection Menu:

RUN PARAMETER
CALENDAR
CUSTOMER PARAMETER
FACTORY PARAMETER

1.2.1, Operating Parameter and Menu

Press“” or“” to move the cursor to “RUN PARAMETER”, then press“” to switch to secondary
menu:
MOTOR、FAN CURR
VSD PARAMETER
TOTAL RUN TIME
THIS RUN TIME

Move the cursor to “MOTOR,FAN CURR” ,press“” to switch to secondary menu:

CURR(A):R S T
6
MOTOR: 56.1 56.2 56.0
FAN: 4.1 4.1 4.1
Press “RT”, to return to the previous menu or the main menu. If no operation at the current menu for 120
seconds , controller will automatically return to the main menu and turn off the back light simultaneously.

According to above method, use move down “” ,move up button“”, enter button“”and return button “C” to
check TOTAL RUN TIME,THIS RUN TIME,VSD PARAMETER,MAINTENANCE PARA,FAULT
RECORD, PROD.DATE、SERIAL,THIS FAULT and return to previous menu.
1.2.2, Calendar
Check and set time of controller

TIME
2004-2-22
WEEK0
12:46:59

1.2.3, Customer Parameter


A, Customer parameter view and modification
It is not allowed to modify CUSTOMER PARAMETER and FACTORY PARAMETER in running status and
STOP DELAY

The check and modification of CUSTOMER PARAMETER is similar with RUN PARAMETER. Take
UNLOAD P as example: Move “”or“”to CUSTOMER PARAMETER and then press “”to switch to below
menu

SET P、T、VSD PARAMETER


SET TIME
OPERATION MODE
BLOCK PARAMETER SET

press“” to switch to below menu

LOAD P:00.65MPa
UNLD P:00.80MPa
FAN START T:0080℃
FAN STOP T:0070℃

Move the cursor to item LOAD P, then press “” to switch to the following menu which requires a user
password input.
INPUT PASSWORD
****

7
Note: User password can be modified in customer parameter and FACTORY PARAMETER
is fixed as

In this menu, the first data bit of password starts blinking,press “”or“” to modify the first bit of
password,Press “” to move the cursor to the next data bit, modify the second data of password in
accordance with the above , and modify the third and fourth data of password in sequence. Press“S” to
confirm the input data and the menu will switch to the following menu after verification:

LOAD P:00.65MPa “*”in the right up corner


UNLD P:00.80MPa indicates that the data is at a
FAN START T:0080℃ setting status
FAN STOP T:0070℃

In the menu above , press “”, the first data of LOAD P starts blinking ,user can press “”or“”to
modify the present data in accordance with the above method .Press“” to move to next data and modify the
target data in sequence. When finished, press “S” to confirm and save the data.

B, Customer Parameter Sheet and Function

First menu Second menu Preset Data Function


1,In AUTO load mode , compressor will load if
pressure is below this set data
LOAD P 00.65MPa
2,In STANDBY mode, compressor will start if the
pressure is below this set data
1,Compressor will unload automatically if air
pressure is above this set data
UNLD P 00.80MPa
2.This data should be set above LOAD P ,also
should be set below UNLD P LIM
SET P 、 T、 VSD FAN START T 0080℃ Fan will start if DISC T is above this set data
PARAMETER FAN STOP T 0070℃ Fan will stop if DISC T is below this set data
Set AIR P for VSD compressor to keep running
stable, when pressure is fluctuated around this
VSD P 00.70MPa
data, controller will adjust operation frequency of
inverter to control the pressure close to this data
MOTOR RAT Set RATED POWER in order to calculate actual
022.0KW
POWER power
MOTOR RAT Set RATED SPEED at 50HZ in order to calculate
2600RPM
SPEED the actual speed in variable frequency
Set the MOTOR START TIME. Record time
SET TIME MOTOR START when motor is activated, controller will not start
0008S
TIME overload protection during this time to avoid
impulse starting current stopping the motor.
Set the FAN START TIME. Record time when fan
FAN START is activated, controller will not start overload
0003S
TIME protection during this time to avoid impulse
starting current stopping the fan.
STAR DELAY
0006S Interval time from star start to delta start.
TIME

8
LOAD DELAY
0002S Unloading in this set time after enter delta running
TIME
When unloading continuously, compressor will
STANDBY
0600S automatically stop and enter to standby status if
DELAY
over this set time
For NORMAL STOP operation, compressor will
STOP DELAY 0010S
stop after it continuously unloads over this set time
RE-START Machine can start only over this set time at any
0100S
DELAY case(after normal stop, standby or alarm &stop)
Restrict PID calculations in case the frequency
VSD UP SPEED 0010 increasing too fast which cause motor speeding up
too fast
Restrict PID calculations in case the frequency
VSD DN SPEED 0010 decreasing too fast which cause motor slowing
down too fast
LOCAL :only the button on the controller can turn
on and turn off the machine.
LOCAL/
START MODE REMOTE: both the button on the controller and
REMOTE
the remote control button can turn on and turn off
the machine;
MANUAL : only when the pressure is above
UNLD P, compressor will
AUTOMATI unload automatically .For any other case ,the
LOAD MODE CAL/MANU Load/Unload function can only be executed by
AL pressing “load/unload” key.
OPERATION
AUTOMATICAL: the load/unload function can be
MODE
executed by the fluctuation of AIR P automatically
DISABLE: communication function is not
activated.
DISABLE/
COMPUTER: compressor can communicate with
COM MODE BLOCK/
computer or DCS as slave according to
COMPUTER
MODBUS-RTU.
BLOCK: compressors can work in a net
Set the communication address in COMPUTER or
COM ADD 0001 BLOCK mode. This address is unique for every
controller in net

1.When service as master in BLOCK, master


controls slave; the COM ADD should be set as
MASTER/
BLOCK STATUS No.1
SLAVE
2.When service as slave in BLOCK, slave is
controlled by master
ORDER/
BLOCK ON/OFF
ALONG
When master pressure is between BLOCK
LOAD P and BLOCK UNLD P, master
BLOCK TURN TIME 0002H
determines slave to work alternatively after
PARAMETER
working over this set time
SET
BLOCK
0002 Number of air compressors in block net
NUMBER
In BLOCK mode, one compressor will start or
BLOCK LOAD P 00.63MPa
load when master AIR P is below this set data
In BLOCK mode, one compressor will stop or
BLOCK UNLD P 00.78MPa unload when master AIR P is above this set
data
In BLOCK mode, when master sends two
BLOCK DELAY 0020S commands continuously, second command
signal delays for this set data

9
Record total running time of oil filter. If
OIL FILTER 0000H changing new oil filter, the data should be reset
by manual operation.
Record total running time of O/A separator. If
O/A
0000H changing new O/A separator, the data should
SEPERATOR
be reset by manual operation
CLR
Record total running time of air filter .If
MAINTENANCE
AIR FILTER 0000H changing new air filter, the data should be reset
TIME
by manual operation
Record total running time of lubricant. If
LUBE 0000H changing new lubricant, the data should be
reset by manual operation
Record total running time of grease. If
GREASE 0000H changing new grease, the data should be reset
by manual operation
1, Alarm prompt when total running time of oil
filter is above the set data .
OIL FILTER 2000H
2,Set this data to “0000” , alarm function for
oil filter running time is not activated
1, Alarm prompt when total running time of
O/A O/A separator is above the set data.
2000H
SEPERATOR 2,Set this data to “0000” ,alarm function for
O/A separator running time is not activated
1, Alarm prompt when total running time of air
MAX LIFE TIME filter is above the set data.
AIR FILTER 2000H
2,Set this data to “0000” , alarm function for
air filter running time is not activated
1, Alarm prompt when total running time of
lubricant is above the set data.
LUBE 2000H
2, Set this data to “0000”, alarm function for
lubricant running time is not activated.
1, Alarm prompt when total running time of
grease is above the set data.
GREASE 2000H
2,Set this data to “0” , alarm function for
grease running time is not activated
CHINESE/ ENGLISH: Displays in English
LANGUAGE ENGLISH
ENGLISH CHINESE: Displays in Chinese
ENABLE/ Enable: PHASE PRO function is activated
PHASE PRO
DISABLE Disable: PHASE PRO function is not activated
NEW USER User could modify the user password by old
**** ****
PASSWORD user password or factory password

1.2.4,Factory Parameter
The view and modification of factory parameter requires a factory password, The modification step is
same as customer parameter modification. Main function is as below:

Initial Data Function


PARAMETER
When the current of motor is more than 1.2 times of the
MOTOR RATED Maximum motor overload
set data , the unit will stop for overload feature. (see
CURR data /1.2
table2.1.1)
FAN RATED Maximum fan overload When the current of fan is more than 1.2 times than the
CURR data/1.2 set data , the unit will stop for overload feature.
When discharge temperature reaches this set data,
ALARM DISC T 105℃
compressor will alarm
When the discharge temperature reaches this set
STOP DISC T 110℃
data, compressor will alarm and stop
STOP AIR P 00.90MPa When pressure reaches this set data ,compressor will
10
alarm and stop
This data is the maximum of UNLD P. The UNLD P in
UNLD P LIM 0.85MPa the customer parameter must be set no higher than this
data.
TOTAL LOAD
000095 H Modify the TOTAL LOAD TIME
TIME
TOTAL RUN
000100 H Modify the TOTAL RUN TIME
TIME
FAULT Input”8888”and press “set“ button to clear all the history
****
RECORD RESET fault record.
When MAX -MIN CURRENT >=(1+ SET
DATA*MIN CURRENT/10 ),the unbalance
CURR protection is activated ,compressor will alarm and stop,
0006
UNBALANCE reporting MOTOR CURR UNBAL
If the set data ≥ 15, the unbalance protection will not be
activated.
OPEN PHASE If OPEN PHASE protection ≥20 seconds, OPEN
002.0S
PROT PHASE protection is not activated
Set inverter model.Controller will read inverter running
parameter based on the model set.
ATV61: Schneider 61/71 inverter。
ATV31:Schneider 31 inverter。
7200GS:TECO 7200GS inverter。
SINE303:CINEE inverter。
ATV61/ATV31/7200GS V5-H:V&T inverter。
SINE303/V5-H/CIMR-F7B/ CIMR-F7B:YASKAWA inverter。
INVERTER SHF/MD320/SB60/SB61/
MD320:Henchman inverter。
MODEL LB60G/POWTRAIN/HOLP/
MEGMEET/ACS550 、 SHF:SANKEN inverter
510/MM440 SB60/SB61:SENLAN inverter
LB60G:LEEPER inverter
POWTRAIN:POWTRAN inverter
HOLP:HOLIP inverter
MEGMEET:MEGMEET inverter
ACS550、510:ABB inverter
MM440: Siemens 440 inverter
PROD.DATE 9999-99-99 Production date set by manufacturer
SERIAL NO. 9999999999 Serial No. set by manufacturer
(PID TARGET P - INTEGRAL SCALE)< detected
MOTOR INT AIR P < (PID TARGET P + INTEGRAL
00.20MPa
SCALE
SCALE),INTEGRAL GAIN works
When detected AIR P<(PID TARGET P -INTEGRAL
SCALE)or
MOTOR INT
INITIAL
0020 Detected AIR P> ( PID TARGET P +INTEGRAL
SCALE)
Integral calculation is based on this data
MOTOR PROP Track speed of PID TARGET P , the bigger the data, the
0010
GAIN faster the track; the smaller the data, the slower the track
Track the speed of PID TARGET P and STEADY
STATE ERROR, the bigger the data ,the faster the track
MOTOR INT
0012 and smaller the STEADY-STATE ERRORS; the
GAIN
smaller the data ,the slower the track and bigger the
STEADY-STATE ERRORS
MOTOR DIFF Track the hysteresis system(such as temperature) ,it is
0000
GAIN not used very often and normally set as “0000”
COIL STOP T 000℃ Spare
11
In the process of adjustment, The minimum operating
MOTOR MIN
040.0HZ frequency when pressure is over the LOAD P pressure
FREQ
and not reach the UNLD P
MOTOR UNLD
0030.0HZ Permitted operating frequency in UNLD MODE
FREQ
MOTOR MAX
180.0HZ The maximum operating frequency in loading status
FREQ
PF: Star-delta wll run
RUN MODE VSD/PF VSD:inverter will run
(refer to schematic diagram and operation control)
Choose operation power frequency.(This parameter
influences the sample current value. When this data is set
FREQ SEL 50Hz/60Hz
incorrectly, the actual current is 1.2 times different from
displayed current value)
When set as VSD mode and AIR P is detected higher
than set DESCEND P, DESCEND FREQ works.( This
DESCEND P 00.72MPa data is only available in MOTOR VSD or MOTOR/FAN
VSD mode)
Suggest: this set data = VSD P+0.02(MPa)
In VSD mode ,when the AIR P is detected higher than
the set DESCEND P ,sent the data (CONTROL
FREQUENCY based on the PID OPERATING
REQUENCY- SET DESCEND FREQUENCY) to
DESCEND FREQ 005.0HZ
inverter to avoid AIR P over PID TARGET PRESS too
far which may cause the compressor loading and
unloading frequently.
Suggest: this set data <=Motor max frequency×1% (Hz)
SLOW: When compressor receives stop command,
INLET VALVE terminals will open and MOTOR
INVERTER RUN terminal will open. The compressor
MOTOR STOP will stop according to STOP DELAY set.
SLOW/FREE
MODE FREE: When compressor receives stop command, Inlet
valve will open. MOTOR INVERTER RUN terminal
will keep closed to control inverter frequency decreasing
and it will open until 1 S before STOP DELAY finishes

2, Contoller Function and Technical Parameter


2.1,Digital input &output:8 points of digital input,10 points of digital relay output
2.2,Analog input& output:1 points of Pt100 temperature input,1 points of 4~20mA pressure signal input,2
groups of three phases current input (CT provided);
2.3,Input voltage of phases:three phase 380V;
2.4,Controller operation power:220V、50/60Hz、12VA(Recommond20VA);
2.5,Measurement :
2.5.1Oil temperature:—20~150℃;Accuracy:±1℃
2.5.2Discharge temperature:—20~150℃;Accuracy:±1℃
2.5.3Running time:0~999999H
2.5.4Current:0~999.9A
2.5.5Pressure:0~1.60MPa Accuracy:0.01Mpa
2.6,Phase protection: When compressor is at stop mode and detects open phase, response time≤2s;
2.7,Motor protection: This controller provides open phase, unbalance and overload protection to motor and
fan.

12
2.7.1Open phase protection:When any phase opens, the response time equals to set time;This function is not
activated when OPEN PHASE PROTECTION time is set over 20s
2.7.2Unbalance protection: when MAX-MIN current >= SET DATA *MIN current/10 ,respond time is
5s;
2.7.3Protection features of overload (time unit: second),please see following table(table 2.1.1)for your

reference. Multiple=Iactual/Iset ,response time is shown in following table (table 2.1.1) according to

overload multiples from 1.2 times and 3.0 times .

Iactual/Iset
Time parameter ≥1.2 ≥1.3 ≥1.5 ≥1.6 ≥2.0 ≥3.0

Response time(S) 60 48 24 8 5 1

Table 2 curve table for protection of motor


2.8, Temperature protection: when actual temperature measured is higher than temperature set; response
time≤2s
2.9, Contact capacity of output relay: 250V,5A;Contact endurance :500000 times;
2.10, Current error is less than 1.0%.;
2.11,RS—485communication, one for inverter and the other for block control or external communication

3,Model and Specification

3.1, Model explanation

MAM—KY02SVF(40)(B)(T)—III
Control mode III
T:RS—485communication
B:Pressure transmitter;K:pressure switch
Motor max operating current
V:Vane compressor;S:Screw compressor
02 controller(LCD display)
Model

3.2, Power specification sheet for corresponding motor.


Corresponding
Current
Specification main motor Remark Description
range (A)
power (KW)
MAM—KY02SVF(20) 8~20 Below 11 Fan has three
MAM—KY02SVF(40) 16~40 11-18.5 levels of current,
MAM—KY02SVF(100) 100 22-45 such as 0.2-2.5A,

13
MAM—KY02SVF(200) 200 55-90 1-5A and 4-10A,
MAM—KY02SVF(400) 400 110 determined-by
MAM—KY02SVF(600/5) 600/5 200-250 With CT current of motor

4, Inverter Communication
4.1,Communication Function

Controller can read relevant information such inverter operation frequency, output current, output voltage,
motor speed and inverter fault and so on through the second RS 485 communication port A2 (485+)、B2
(485-)(see detail in picture 4.1.1).In the main interface, it can display inverter operation frequency, motor
power, motor speed, output voltage and so on. For more parameter, please check VSD PARAMETER in the
RUN PARAMETER. To avoid communication interference, it is necessary to ground connect controller shell
when controller communicates with inverter. Also, please use the cable with shielded covering to connect with
controller. There will be an information to indicate if communication between controller and inverter is
interrupted, in this way, please check the communication cable and the inverter parameter set.

RS485 RS485
24+ 24- A1 B1 A2 B2

Picture 4.1.1
4.2,Communication Set
①、Inverter set
When controller communicates with inverter,the Baud rate is 9600Bps,1 start bit,8 data bit,1 stop bit,
No parity check bit and inverter communication address is 001.User can set relevant communication
parameter through inverter menu,(See inverter communication set for detail).It is require to power off and
reset after communication parameter is set
Note: To avoid communication interference, it is necessary to ground connect controller shell when
controller communicates with inverter
②、Controller Set
Set the INVERTER NAME in FACTORY PARAMETER(Different inverter share different data
address register. Controller read inverter RUN PARAMETER through the INVERTER NAME set
here).After set,enter USER PARAMETER and set RATED POWER and SPEED at 50HZ. based on this
set ,calculate the actual power and speed for user reference.

4.3,Inverter Upgrade Explanation


①This software edition adapts to all inverter supporting MODBUS RTU (Inverter has to read output current,
output voltage, output frequency and output power)
②Controller supports 38 different inverters communication protocol. Beyond these models, you can also set
the communication parameter according to below step:
 Enter FACTORY PARAMETER, move down cursor to INVERTER NAME and set it as
SELF-DEF
 Return to the main menu, move the cursor to FACTORY PARAMETER, and press password 2688
to enter INVERTER SET like picture below.

14
VOLT ADDRESS:FFFF Set the voltage
CURR ADDRESS:FFFF address .hexadecimal
FREQ ADDRESS:FFFF
POWR ADDRESS:FFFF

In this menu, please set the MODBUS address of output voltage, output current, output frequency
and output power. After set, move down to check data calculation menu like below picture.

V=REC*FFFF÷FFFF
I=REC*FFFF÷FFFF
Use percentage power ,please select SET,
F=REC*FFFF÷FFFF
Use real power, please select 1

P=REC*SET/1 *FFFF÷FFFF
Set the data format to
COM FORM:8N1-NONE
communicate with inverter
VSD ADD:0001

Set communication
Example: MODBUS address
A customer wants to use SB70 inverter, SB70 communication protocol is not set in the inverter yet
and the information in the inverter manual is as below
Output current address:1202H,digits 0.01A
Output voltage address:1204H,digits 0.1V
Output frequency address:1200H,digits 0.01HZ
Output power address:1208H,digits 0.1KW
To communicate with SB70,please set as below:
Factory parameter
FAULT RECORD RESET:9999 Set:SELF-DEFF
CURR UNBALANCE:0008
OPEN PHASE PROT:00.30S
INVERTER NAME:SELF-DEFF

 Return to the main menu, move the cursor to FACTORY PARAMETER, and press password 2688
to enter INVERTER SET like picture below.

Refer to the inverter manual,


VOLT ADDRESS:1204
and set voltage MODBUS
CURR ADDRESS:1202
register address
FREQ ADDRESS:1200
POWR ADDRESS:1208
After read voltage
successfully, the voltage will
V=REC*0001÷0001 transfer to a one digit number
I=REC*0001÷0010
F=REC*0001÷0010 After read frequency successfully, the
frequency will transfer to a one digit
number.SB70 frequency is with two
15
digits, to transfer to one digits, it should
be divided by 10
P=REC* 1 *0001÷0001
COM FORM:8N1-NONE
VSD ADD:0001
SB70 support MODBUS RTU
protocol,the data format can set as:
8N1no parity bit

5, Installation
5.1, Mechanical Installation
5.1.1, CT Installation
The CT shall be installed at a place where the current of motor cable can be measured, thus, controller can
be set according to instructions on motor nameplate, and the detailed dimension is shown as below:

Picture1、CT1 Structural dimension of CT1(ф36 hole) Picture2、CT1 Installation dimension

A
B

Picture 3、Structural dimension of CT2(ф10 hole) Picture


4、CT2 Installation dimension

5.1.2,Controller Installation
When install the controller, room should be left around
controller for wiring. The specific dimension is shown as below:

16
1、Indicator(IN):
The corresponding digital input terminal of 00、01、02、03、04、05、06、07 is 20、 19、18、
17、16、15、14、13.
2、Indicator(OUT)
The corresponding digital input terminal of 00、01、02、03、04、05、06、07、08、09 is 27、28、 29、30、
31、35、36、37、38、39
3、Power Indicator:PWR
4、Run indicator:RUN
5、Error indicator:ERR

Picture 5、Controller structure dimension


5.1.3,Panel Function and Installation Panel Structure 165╳102╳50(mm)

250
50

I
排气温度:80C
供压:0.80MPa
后油 运行状态:设备已停止 O

138
150
冷冷
却却
0秒 本地
器器

S 14 22

Picture 6,Panel Dimension

Picture 7, Hole dimension

17
5.2, Electrical Connections

Picture 8、Terminal arrangement diagram

Monitor connection terminal:


There are five connection cables and a communication cable which are used for display connection , RS-485
communication ,24V power supply.
Controller connection terminal:
Communication cable is used to connect monitor and controller
1.2.3 CT1:Motor current 4.5.6 CT2:Fan current 7、9 Discharge temperature
transformer transformer input
23、24、25 Phase input 27 Motor contactor(PF) 28 Star contactor(PF)
29 Delta contactor 30 Inlet valve 31 Fan
32 Output relay COM1 34 Control inverter(VSD) 35 Control VSD Fan
37 Run indicator 38 Error indicator 39 Alarm indicator
40 Communication port 2 42 GND(analog) 43,44 220V

* Note : Electromagnetism coil shall be connected nearest with RC snubber during wiring, Dotted line is

for extra function

6, Alarm Function
6. 1、Monitor Indication
6.1.1, Air Filter Alarm

①. Air filter block check.


The monitor displays AIR BLOCK by checking pressure differential switch close.
②. Air filter running time alarm

18
The text displays AIR TIME END when running time of the air filter is exhausted.

6.1.2, Oil Filter Alarm

①. Oil filter block check.


The monitor displays OIL BLOCK by checking pressure differential switch close.
②. Oil filter running time alarm
The text displays OILTIME END when running time of the oil filter is exhausted.

6.1.3, O/A Separator Alarm

①. O/A separator block check.


The monitor displays O/A BLOCK by checking pressure differential switch close.
②. O/A filter running time alarm
The text displays O/A TIME END when running time of the oil filter is exhausted.

6.1.4, Lubricant Alarm

The text displays LUBE TIME END when running time of the lubricant is exhausted.

6.1.5, Grease Alarm

The text displays GREASE TIME END when running time of the grease is exhausted.

6.1.6, Discharge Temperature High Alarm


The text displays DISC T HIGH when DISC T is higher than ALARM DISC T set in FACTORY
PARAMETER.

6.2,Controller indicator

Indicator Meaning and function Indicator status

Power Controller power on PWR indicator on


Run Controller run RUN indicator on
Error Failure and stop ERR indicator blink
IN00~08corresponding indicator on. Indicator
Digital input Terminal 26~18 digital input
will not be illuminated if input has no function

Terminal 39、40、41、42、43、46、
Digital output OUT00~09 corresponding indicator on
47、49、50、51digital output

Data storage Data and time set PWR blink once

7, Controller Protection
19
7.1, Motor protection
MAM—KY02SVF compressor controller provide short circuit ,block, overload, lack phase, unbalance
protection to motor.

Electronic
Failure display Reason
failure
Short circuit Display “Motor/FAN OVER LOAD” Short circuit or wrong current set
Overload, bearing wear and other mechanica
Current Block Display “Motor/FAN BLOCK”
l failure
Overload, bearing wear and other mechanica
Overload Display “Motor/FAN OVERLOAD”
l failure
Power supply, contactor and open phase of
Lack phase Display “Motor/FAN *LACK PHASE”
motor
Poor contact of contactor, inside open-loop of
Unbalance Display “Motor/FAN UNBALANCE”
motor

7.2, Protection of Discharge Temperature High


When DISC T is above the STOP DISC T, the controller will alarm and stop the machine. THIS FAULT
displays DISC T HIGH

7.3, Protection of Air Compressor anti-reversal


When compressor is at stop status and three phases sequence is not in order, THIS FAULT displays PHASE
WRONG1, and the controller cannot start the motor. Change the position of any arbitrary two phase power
lines and check the rotation of motor.

7.4, Protection of Air Pressure High


When the AIR P is above the MAX LIM P, the controller will alarm and stop the machine. THIS FAULT
displays HIGH P.

7.5, Protection of Sensor Fault


When pressure sensor or temperature sensor is disconnected, the controller will alarm and stop the machine.
THIS FAULT displays **SENSOR FAULT.

7.6, Protection of Air Compressor Open Phase


When compressor is at stop status and open phase is detected, THIS FAULT displays PHASE WRONG2,
and the controller cannot start the compressor. Check the three phase.

7.7,Protection of VSD Fan


When VSD fan is failure, controller will stop

7.8, Protection of Inverter


When inverter is failure, controller will stop

8, Troubleshooting
8.1、This Fault Review

20
Alarm and stop caused by the external parts of controllers may be removed by checking THIS FAULT or
FAULT RECORD, method is shown as below:

Press“” to move the cursor to “RUN PARAMETER” menu, then press“”,the secondary menu will show as
below:
MOTOR FAN CURR
VSD PARA
TOTAL RUN TIME
THIS RUN TIME

MAINTENANCE PARAMETER
FAULT RECORD
PROD.DATE、SERIAL
THIS FAULT

Move the cursor to “THIS FAULT” menu Then press“”to switch to the following menu(display failure):

STOP: DISC T SENSOR


FAULT
170℃

User can reset fault according to the information prompted

8.2、Common Failures and Causes:

Failure Reason Solution

High discharge Bad vent condition, Oil shortage Check the vent condition and lubricant amount
temperature etc. etc.
Temperature Sensor
Cable broken or PT100 failure Check the wiring and PT100
Failure
Pressure too high or the pressure
High Pressure Check the pressure and the pressure sensor
sensor failure
Cable broken, Sensor failure or
Pressure Sensor Failure Check the wiring and pressure transmitter
the cables connect reversely

Lack water Water pressure switch failure Check water pressure switch

Power open phase or the contactor


Open Phase Check the power and contactors
failure
Voltage too low, tubes block,
bearing wear off or other Check the set data, voltage, bearings, tubes and
Overload
mechanical failure or wrong set other mechanical system.
data etc.
Current unbalance, contactor
Unbalance failure or the internal open loop of Check the power, contactor and the motor
the motor
21
Phase sequence reversal or open
Wrong Phase Sequence Check the wiring
phase
Fan failure, contactor failure,no
Fan fail to run Check wiring
control output
Motor overload during Master start time set to less than Reset the master start time longer than star
start the star delta delay time delay + 2 seconds
The emergency stop button is
Main Contactor shakes Check if the coil of contactor connects with
loose or controller is reset by
frequently RC snubber or not
interference

22
9, Schematic Diagram:

23