DST4600A
DST4600A
DST4600A
Operating
Manual
DOCUMENT N EAAM0020I rev. 10
FILE:
Date:
Issued by:
Checked by:
EAAM002010I.doc
24/10/03
Andrea Rizzon
Walter Caielli
This document is owned by SICES s.r.l.. All rights reserved.SICES s.r.l. reserves the right to modify this
document without prior notice.
The disclosure by any means of this document to third parties is not allowed.
EAAM002010I.doc
Revision
Revision
Date
Pages
Notes
00
18/04/01
49
01
15/06/01
58
02
13/07/01
57
03
10/09/01
66
04
14/02/02
76
05
30/04/02
82
2.2, 2.2.1.2, 5.1, 5.1.15, 5.1.19, 5.1.20, 5.1.21, 5.2, 5.5, 6.1,
6.2.7, 6.2.8, 6.4.2, 6.4.11.1, 7.1.3.1, 7.1.3.2, 10.1, 10.2, 10.7,
10.7.1, 10.7.2, 10.7.3, 10.7.4, 10.7.4.1, 10.7.4.2, 10.7.5, 11,
11.2, 11.3, 11.4, 11.5, 11.6, A6, A.6.1, A.6.2, A7
07
07/01/03
78
2.1.7 - 2.1.8 - 2.2.1.1 - 2.2.1.2 - 2.2.2 - 3 - 5.1 -5.1.1 - 5.1.2 5.1.6 - 5.1.7 - 5.1.10 - 5.1.11 - 5.1.15 - 5.1.19 - 5.1.20 - 5.1.22
- 5.1.23 - 5.5 - 6.1 - 6.4.11.2 - 6.4.12 - 7.1.3.2 - 10.1 - 10.5,
10.6 - 10.7.1 - 10.8.4 - 10.9 - 11.4
08
04/02/03
80
2.2.1.2, 2.2.2, 4.2.1, 5.1, 5.1.14, 5.1.15, 5.1.23, 5.5, 6.1, 6.2.9,
6.4.1.12, 10.5, 10.6, 10.6.1, 10.6.2, 10.8.4, A5
09
18/03/03
81
10
24/10/03
85
1.1, 2.1.5, 2.2.2, 5.1, 5.1.6, 5.1.24, 6.1, 6.2.1.1, 6.2.1.2, 6.2.7,
6.3.1, 6.3.2, 6.4.4.1, 6.4.4.2, 6.4.7, 6.4.8, 6.4.9, 6.4.10.2,
6.4.14, 6.4.16, 6.4.17, 6.4.20, 7.3.1, 7.3.2, 7.4, 7.4.1, 7.4.2,
7.4.6, 7.4.9, 7.5, 10.8.4, 10.9, 10.11
EAAM002010I.doc
CONTENTS
FILE:
EAAM002010I.DOC ................................................................................................................................ I
REVISION ............................................................................................................................................................... II
1.
GENERAL INFORMATION......................................................................................................................... 1
1.1
1.2
1.3
2.
DEFINITIONS ................................................................................................................................................. 1
SYMBOLS...................................................................................................................................................... 1
DOCUMENT VALIDITY.................................................................................................................................... 1
2.2.2
2.2.3
Operating area.......................................................................................................................................... 8
Functions Area ........................................................................................................................................10
3.
START INITIALIZATION.......................................................................................................................... 16
4.
5.
PROGRAMMING PROCEDURE............................................................................................................... 19
5.1 TABLE OF DESCRIPTION OF THE DST4600A PARAMETERS. ........................................................................... 19
5.1.1
Parameter P16.................................................................................................................................. 24
5.1.2
Parameter P17.................................................................................................................................. 24
5.1.3
Parameter P37.................................................................................................................................. 25
5.1.4
Parameter P39.................................................................................................................................. 25
5.1.5
Parameter P45.................................................................................................................................. 25
5.1.6
Parameter P46.................................................................................................................................. 25
5.1.7
Parameter P47.................................................................................................................................. 26
5.1.8
Parameter P48.................................................................................................................................. 26
5.1.9
Parameter P49.................................................................................................................................. 26
5.1.10
Parameter P50 ............................................................................................................................. 27
5.1.11
Parameter P51 ............................................................................................................................. 27
5.1.12
Parameter P52 and P53. .............................................................................................................. 27
5.1.13
Parameter P55 ............................................................................................................................. 28
5.1.14
Parameters P56-P60 .................................................................................................................... 28
5.1.15
Parameter P61 ............................................................................................................................. 28
EAAM002010I.doc
5.1.16
Parameter P62 ............................................................................................................................. 29
5.1.17
Parameter P63 ............................................................................................................................. 29
5.1.18
Parameter P64 ............................................................................................................................. 29
5.1.19
Parameters P68 and P69.............................................................................................................. 29
5.1.20
Parameters P70, P71 and P73...................................................................................................... 30
5.1.21
Parameters P72 and P74.............................................................................................................. 30
5.1.22
Parameter P76 ............................................................................................................................. 30
5.1.23
Parameter P77 ............................................................................................................................. 31
5.1.24
Parameter P79 ............................................................................................................................. 31
5.2 ACTIVATION OF THE PROGRAMMING PROCEDURE ................................................................................... 32
5.3 QUITTING THE PROGRAMMING PROCEDURE ............................................................................................ 32
5.4 SELECTING A PARAMETER ........................................................................................................................... 32
5.5 SETTING A PARAMETER ............................................................................................................................... 32
5.6 LOADING THE DEFAULT VALUES .................................................................................................................. 33
5.7 WORK SEQUENCE DURING THE PROGRAMMING. ............................................................................................ 33
5.8 LAMP TEST DURING THE PROGRAMMING PROCEDURE. .................................................................................. 33
6.
FAULTS........................................................................................................................................................ 35
6.1 LIST OF FXX CODES ..................................................................................................................................... 36
6.2 ALARMS ..................................................................................................................................................... 36
6.2.1
Low oil pressure................................................................................................................................ 36
6.2.1.1
6.2.1.2
6.2.2
6.2.2.1
6.2.2.2
6.2.3
6.2.4
6.2.4.1
6.2.4.2
6.2.5
6.2.5.1
6.2.5.2
6.2.6
Auxiliary Alarm ................................................................................................................................ 38
6.2.7
KR close failure ................................................................................................................................ 38
6.2.8
KG close failure................................................................................................................................ 38
6.2.9
Max power........................................................................................................................................ 38
6.3 DEACTIVATIONS.......................................................................................................................................... 38
6.3.1
Generators Voltage Under Minimum Threshold (UNDERVOLTAGE).......................................... 38
6.3.2
Generators Frequency Under the Minimum Threshold (UNDERFREQUENCY) .......................... 39
6.4 BLOCKS ...................................................................................................................................................... 39
6.4.1
Emergency STOP.............................................................................................................................. 39
6.4.2
Manual Stop in AUTO ...................................................................................................................... 39
6.4.3
Fuel END ......................................................................................................................................... 39
6.4.3.1
6.4.3.2
6.4.4
6.4.4.1
6.4.4.2
6.4.5
6.4.5.1
6.4.5.2
6.4.6
6.4.7
6.4.8
6.4.9
6.4.10
Digital input............................................................................................................................................39
From Analogue Input...............................................................................................................................39
EAAM002010I.doc
6.4.10.1
6.4.10.2
6.4.11
6.4.11.1
6.4.11.2
6.4.12
6.4.13
6.4.14
6.4.15
6.4.16
6.4.17
6.4.18
6.4.19
6.4.20
7.
Overload ...................................................................................................................................... 41
From Digital Input (OVERLOAD) .......................................................................................................41
From Current (OVERCURRENT)........................................................................................................42
OPERATING SEQUENCE.......................................................................................................................... 44
7.1 DEFINITIONS ............................................................................................................................................... 44
7.1.1
Mains Voltages Status....................................................................................................................... 44
7.1.2
Generators Voltages Status.............................................................................................................. 45
7.1.3
Engine Status.................................................................................................................................... 46
7.1.3.1
7.1.3.2
7.1.3.3
7.1.3.4
POWER MEASUREMENT......................................................................................................................... 53
8.1
8.2
8.3
8.4
8.5
8.6
9.
SERIAL COMMUNICATION..................................................................................................................... 56
9.1 HARDWARE CONNECTIONS .......................................................................................................................... 56
9.1.1
Direct Connection to a PC................................................................................................................ 56
9.1.2
Connection to an analogue modem ................................................................................................... 56
9.1.3
Connection to a GSM modem............................................................................................................ 56
9.1.4
Connection to a RS-485 network ....................................................................................................... 57
9.2 SOFTWARE PROTOCOLS ............................................................................................................................... 57
EAAM002010I.doc
9.2.1
9.2.2
9.2.3
10.
10.1
AUTOMATIC RECOVERY FROM KR CLOSE FAILURE.................................................................................... 58
10.2
AUTOMATIC PERIODICAL TEST ................................................................................................................ 59
10.3
FUEL PUMP............................................................................................................................................. 59
10.4
REMOTE TEST ........................................................................................................................................ 59
10.5
REMOTE SIGNALS ................................................................................................................................... 59
10.6
LOW POWER OR MAX POWER SIGNALING ......................................................................................... 60
10.6.1
Low load status signal. ................................................................................................................. 61
10.6.2
Maximum power. .......................................................................................................................... 61
10.7
REAL TIME CLOCK OPTION ...................................................................................................................... 63
10.7.1
How to display Time and Date of RTC.......................................................................................... 63
10.7.2
Setting time and date.................................................................................................................... 63
10.7.3
Storing time/date into Data Record databases.............................................................................. 64
10.7.4
Automatic Periodical Test ............................................................................................................ 64
10.7.4.1
10.7.4.2
10.7.5
Generator set Time Lock function................................................................................................. 64
10.8
DATA RECORD ........................................................................................................................................ 66
10.8.1
Databases .................................................................................................................................... 66
10.8.2
Memory device............................................................................................................................. 66
10.8.3
Time and date............................................................................................................................... 67
10.8.4
Event database ............................................................................................................................. 67
10.8.5
Analogue data database ............................................................................................................... 71
10.8.6
Databases lock ............................................................................................................................. 72
10.9
DATA CALL AND SMS FUNCTIONS........................................................................................................... 73
10.9.1
Setup ............................................................................................................................................ 73
10.9.2
Data Call Function Enable........................................................................................................... 73
10.9.3
Description .................................................................................................................................. 73
10.9.4
PC SW procedure ......................................................................................................................... 74
10.10 DIFFERENCES BETWEEN DST4600A AND DST4600A/P ........................................................................... 75
10.10.1
ALARM2 input for PARALLEL FAULT ........................................................................................ 75
10.10.2
KR management ........................................................................................................................... 75
10.10.3
KG management in test operation ................................................................................................ 75
10.10.4
MAINS SIMULATION delay time ............................................................................................. 75
10.11 DIFFERENCES WITH DST4600A/P FOR ASYNCHRONOUS ENGINES.............................................................. 75
10.11.1
Generator frequency and voltages................................................................................................ 75
10.11.2
Terminal 8 function ...................................................................................................................... 75
10.11.3
Terminal 10 function .................................................................................................................... 75
10.11.4
Engine not in threshold with KG closed alarm ......................................................................... 76
11.
11.1
11.2
11.3
11.4
12.
REFERENCES......................................................................................................................................... 77
SMS PROTOCOL FOR BOARDS DST4600A AND REMOTE SIGNALS...................................................... 77
DTS4600-PC COMMUNICATION PROTOCOL ............................................................................................ 77
MODBUS PROTOCOL IMPLEMENTATION FOR SICES EQUIPMENT ................................................................ 77
REMOTE SIGNAL OPERATING MANUAL ...................................................................................................... 77
ANNEXES ................................................................................................................................................ 78
EAAM002010I.doc
A5
A6
A7
A8
EAAM002010I.doc
1. General Information
The board DST4600A, included into a special electric switchboard, is able to control the
automatic intervention of a generator set, to monitor it during the operation and to keep it in
the best possible conditions while inactive, in order to assure a quick and safe intervention
in the event of power failure. It works with both three- and single-phase systems.
1.1
Definitions
Throughout this document the word BLOCK is used to indicate an alarm that makes
generation function impossible and causes the automatic generator shutdown with the
emergency procedure (without cooling cycle).
The word DEACTIVATION is used to indicate an alarm that makes generation function
impossible and causes the automatic generator shutdown with the normal procedure (with
cooling cycle).
The word ALARM is used to indicate a warning that requires an operator action but doesnt
require the automatic generator shutdown.
Throughout this document the words SOFTWARE and FIRMWARE are used as
synonymous if they are referred to the board firmware.
Software code is reported in short format on the board back panel. It is in the form xx.yy.uu,
where xx is the firmware short identified code, yy is the major version number and uu is the
minor version number.
The complete SW identification number for the standard DST4600A is EB0220008yyuu
reported in back panel as (for example) 8.00.22.
The complete SW identification number for the DST4600A/P is EB0220012yyuu reported in
back panel as (for example) 12.05.22.
The complete SW identification number for the DST4600A for asynchronous engines is
EB0220029yyuu reported in back panel as (for example) 29.07.39.
The minor version is consistent between the two types of software (uu field is kept aligned).
The major version for the DST4600A/P is increased by 5 respect the standard version.
The major version for the DST4600A for asynchronous engines is increased by 7 respect
the standard version.
Thus the SWs 08.00.39, 12.05.39 and 29.07.39 share the same main features and
functions.
1.2
Symbols
In this document a vertical bar on the right margin or a gray background indicates that the
chapter or the paragraph has been amended with respect to the last documents version.
1.3
Document validity
This manual is valid starting from SW 00.38 release; for previous SW release, please check
manual version 09 or previous. Otherwise use this version very carefully checking
document version notes on page ii.
If the SW version number is greater than this, this manual maybe nevertheless consistent;
please in case check for new document release.
EAAM002010I.doc
Back Panel
The back panel includes all the terminal strips to connect the board DST4600A to the
electric switchboard. There are nine terminal strips (called JA...JL) and the serial connector.
Here follows a short description.
Conn.
Term. Description
ALARM 1
JA
01
ALARM 2
JA
02
EMERGENCY STOP
JA
03
JA
04
JA
05
FUEL END
JA
06
OIL P. ALARM
JA
07
OIL WARNING
JA
08
WATER ALARM
JA
09
EAAM002010I.doc
Name
Conn.
Term. Description
WATER WARNING
JA
10
OVERLOAD
JA
11
Overload block
INPUT C (OVERSPEED)
JA
12
INPUT B
JB
13
INPUT A
JB
14
MAINS SIMULATION
JC
24
REMOTE TEST
JE
46
Conn.
Term. Description
AUX OUTPUT 1
(PREHEAT OUTPUT)
JB
15
ALARM OUTPUT
JB
16
AUX OUTPUT 2
(FUEL PUMP)
JC
17
STOP SOLENOID
JC
18
START
JC
20
Starter control
FUEL SOLENOID
JC
22
Conn.
Term. Description
ENGINE RUNNING
JD
25
Engine running
GENERAL ALARM
JD
26
TRIP ALARM
JD
27
FUEL ALARM
JD
28
EAAM002010I.doc
Name
Conn.
Term. Description
ENGINE ALARM
JD
29
SPEED ALARM
JD
30
GENERATOR ALARM
JD
31
OFF-PROG-MAN
JD
32
OFF SELECTION
JD
33
Name
Conn.
Term. Description
EXC. D+ 12V
JE
35
EXC. D+ 24V
JE
38
OUTPUT 1
JE
37
OUTPUT 2
JE
36
Name
Conn.
Term. Description
D+WL
JE
39/40
NEGATIVE REF
JE
41
OIL PRESSURE
JE
42
TEMPERATURE
JE
43
ANALOG REF
JE
44
Not used
FUEL LEVEL
JE
45
EAAM002010I.doc
Name
Conn.
Term. Description
+24
JF
47
-V Batt. (Ground)
JF
48
+12
JF
49
Conn.
Term. Description
C.T. 1
JH
50/51
TA phase L1
C.T. 2
JH
52/53
TA phase L2
C.T. 3
JH
54/55
TA phase L3
WARNING: if the board has the POWER MEASUREMENT OPTION, be sure that all the TA
share the same phase connected to ground and check for the correct phase connection.
Otherwise the board will issue a reverse power alarm or a wrong power measurement (see
par. 8.6).
Conn.
Term. Description
N.O. GEN
JI
57
C. GEN
JI
58
N.C. GEN
JI
59
Name
Conn.
Term. Description
N.O. MAINS
JI
60
C. MAINS
JI
61
N.C. MAINS
JI
62
controlling
the
The command for the closing of the mains contactor must be taken from terminals 61 / 62
(normally closed) while the command for the closing of the generator set contactor must be
taken from the terminals 57 / 58 (normally open). This is to assure the mains power the
users when the DST4600A is not powered (both contactors commands open). For SW type
EAAM002010I.doc
12, the mains contactor is not used for this function: it is used as a remote signal of the
mains presence status (if the mains is connected to the board).
Conn.
Term. Description
L1
JL
63
L2
JL
65
L3
JL
67
Name
Conn.
Term. Description
JL
70
JL
72
JL
74
EAAM002010I.doc
2.2
Front Panel
EAAM002010I.doc
The front part of the board is made by a polycarbonate panel, oil- and solvent-resistant with
the identifying symbols and inscriptions. There are two slightly different front panels. The
DST4600A front panel is the standard one. The DST4600A/P front panel is used mainly for
switchboard for parallel application; the boards with the DST4600A/P panel have different
part number.
/P version assigns a special meaning to the followings signals:
Substantially, the panel is divided into the three operational areas as described below.
2.2.1.1
Operating area
It corresponds to the right bottom part of the front panel. It groups all the available control
units. It includes:
A button (START) for the manual starting of the generator set engine. The manual
start can be executed only with the key selector on MAN. This button, alone or
combined with the others, can also take other meanings during some particular
procedures not directly related with the management of the generator set (programming,
calibration, etc.).
A button (STOP) for the manual shutdown of the generator set engine. The manual
shutdown can be executed only with the key selector on MAN. By pressing this button
with the key selector in other working positions (AUTO or TEST) the engine shutdown
will be executed through the emergency procedure (see the faults management). This
button, alone or combined with the others, can also take other meanings during some
particular procedures not directly related with the management of the generator set
(programming, calibration, etc.).
A button (bearing the symbol of a siren, from now on called MODE / ACK) for the
faults acknowledgement and the consequent muting of the audible alarm and to reset
the alarms, too. This button, alone or combined with other buttons, can also have other
meanings.
Two buttons (bearing the symbols of two arrows, from now on called F1 and F2) used
to select what to show on the display MULTIFUNCTION (see par.2.2.1.2). These
buttons, alone or combined with other buttons, can also have other meanings.
A key selector allowing to select the boards controlling mode of the generator sets
operation: OFF/RESET - PROGRAMMING - MANUAL - AUTOMATIC TEST. The key
can be extracted only in the positions OFF/RESET and AUTOMATIC. Here follows a
short description of the operating modes:
a) OFF/RESET: in this mode the board is on, but all the functions for the control
and the running of the generator set are disabled. It is used in all the cases in
which the intervention of the generator set is not required (i.e. in order to prevent
unnecessary automatic interventions during the closing periods of a factory etc.)
and above all as a safety position during the maintenance. Actually, when the
selector is on OFF/RESET, the control device is completely disabled and
therefore the generator set cannot intervene in the event of mains voltage
EAAM002010I.doc
failure. The mains contactor is forced at work therefore the users are powered by
the mains (if its present). The monitoring of the mains status, of the engine and
of the generator are anyway enabled and the indicators belonging to the
functional status and measurements area mirror such conditions.
By switching the selector to OFF/RESET the following operations are
executed:
1) Activation of the engine shutdown sequence
2) Forced control of mains power supply
3) Reset of any stored fault causing the generator set shutdown
When the board is in the OFF/RESET mode the direct current consumption is
reduced to a minimum since the displays show only a central dash, while all the
signals are off except the indicator KR (turned on, only for SW type 08) as
well as the indicators ENGINE RUNNING, GENERATOR LIVE and MAINS
LIVE showing respectively the engine, the generator and the mains status
(normally only the indicator MAINS LIVE is turned on).
b) PROG. (PROGRAMMING): in this mode the board behaves exactly as in the
OFF/RESET mode but with the opportunity to view and/or change the value of
the parameters configuring the operating sequences of the generator set (see
par.5 for the programming procedure and par. 7 for the operating sequence).
c) MAN. (MANUAL): in this mode the board is set to manage the manual running of
the generator set. In short:
1) The procedures for the manual starting and shutdown of the engine are
enabled, while those for the automatic starting and shutdown of the engine
are disabled (therefore the board will never automatically start the engine).
2) It is possible to manual operate the power changeover on the generator set
through an explicit command of the operator (if the generator is ready to
supply, of course). In MAN, the board will never execute such switching
automatically.
When the selector is switched on MAN, the engine keeps its status
(running/dead).
d) AUTO (AUTOMATIC): this is the normal operating mode of the board. In this
mode the engine is automatically started/stopped in case of mains failure or at
regular intervals to keep it efficient. In the same way, the power changeover is
automatically switched on mains or on the generator according to their status.
Warning: when the selector is on this mode any maintenance of the
generator set and/or on the electric switchboard is forbidden.
e) TEST: this mode allows starting the generator set keeping all the functions for
the management of the changeover as in the AUTOMATIC mode. By switching
the selector on TEST, a series of starting attempts will be executed
(automatically, the operator will not have to press START), independently
from the mains status. In the same way, by quitting the TEST mode (for the
AUTOMATIC mode), if the mains is present the engine will stop (with the usual
cooling cycle). Normally, in the TEST mode the users are switched on the mains.
They can be switched on the generator set (if it is ready to supply) only in the
following two cases:
EAAM002010I.doc
1) Mains failure
2) Explicit command of the operator (in order to test the entire system, not only
the generator set).
For the SW version 12 (/P boards), KG is activated in the TEST mode if the
generator is ready to supply power. It can be deactivated by manual command.
2.2.1.2
Functions Area
In this area is located a digital display (called display MULTIFUNCTION) showing the
measurements of various quantities that can be selected through the buttons F1 and F2
and indicated to the operator through the corresponding indicators.
The available quantities are:
DATA HOURS COUNT / START COUNTER: by selecting this function the display
MULTIFUNCTION normally shows the number of operating hours of the generator set
engine. The hours count doesnt consider if the users are connected to the generator
but the condition of engine running only. By keeping pressed the button MODE / ACK,
you can view the number of starts of the engine (the number refers to the performed
starts, not to the start attempts). As soon as MODE / ACK is released the engines
operating
hours
can
be
viewed
again.
The corresponding indicator is turned on when the display shows the engines operating
hours, while it flashes when the number of starting attempts is viewed.
If the number of starts of the operating hours exceeds 999, the number is divided by 10
and
displayed
with
a
decimal
point
on
the
right
digit.
It is possible to program (through the parameter P50) a number of operating hours for
the engine after which maintenance has to be carried out. When the hour-counter
reaches or exceeds such parameter (NB: it is set by tens of hours) in order to signal the
maintenance request the number of operating hours will flash alternatively to the
message SER (with the selector on MAN, AUTO and TEST the function to view the
operating hours is automatically selected after 60 seconds without pressing any button).
This condition stays until the hour-counter is reset or until the value of the Parameter
P50 is changed (by increasing it or by forcing it to 0). Both the counters are reset with a
common operation (they cannot be reset separately):
By pressing the F1 and F2 select the DATA HOURS COUNT / START
COUNTER function
Switch the key selector to OFF_RESET.
Press at the same time MODE / ACK and STOP for 5 seconds. After 5
seconds the counters will be reset. The display does not indicate the reset in any
way; therefore the operator has to count the 5 seconds.
There is another hour counter. It cannot be cleared in any way. Its value is not shown
on the DST4600A front panel, but can be read by the serial port.
EAAM002010I.doc
SIMULATION (terminal 24) is enabled, the indicator MAINS VOLTAGE (Vac) /
REACTIVE POWER (kvar) flashes.
If the board is supplied with the power measurement option and if the displays V and
A are showing the active power and the power factor (POWER DISPLAY
FUNCTION), the display MULTIFUNCTION shows the reactive power (in this case,
the measure could blink if at least one of the current measure circuits of the board is
saturated, that means that the current is higher than the TA nominal value).
OIL PRESSURE (bar): when this function is selected, the display MULTIFUNCTION
shows the engines oil pressure measured on the analogue sensor (terminal 42) (in
Bars with a decimal). If the sensor isnt configured (P47=0), the display will show three
dashes (---).
FUEL LEVEL (%): when this function is selected, the display MULTIFUNCTION
shows the fuel level in the tank measured on the analogue sensor (terminal 45)
(percentage). If the sensor isnt configured (P48=0), the display will show three dashes
(---).
Under particular conditions, during the operation the display MULTIFUNCTION can show
messages having no relation with the selected function. In this situation, all indicators
related to display MULTIFUNCTION are turned off. In detail, the messages are the
following:
STA during a starting attempt, that is when the output START (terminal 20) is
activated.
PRE during the preheating phase preceding the starting attempt in diesel engines,
that is when the PREHEAT OUTPUT (AUX OUTPUT 1, terminal 15) is activated.
SER signals that the generator set requires field service maintenance.
F01 in presence of the deactivation for generators voltage under the minimum
threshold (UNDERVOLTAGE).
F02 in presence of the block for generators voltage over the maximum threshold
(OVERVOLTAGE).
F03 in presence of the deactivation for generators frequency under the minimum
threshold (UNDERFREQUENCY).
F04 in presence of the block for generators frequency over the maximum threshold
(OVERFREQUENCY).
F07 in presence of block for STOP pressed in the AUTOMATIC or in the TEST
mode.
EAAM002010I.doc
F40 if the engine in threshold signal is missing while KR is closed (for asynchronous
engine version only)
During the shutdown cycle the display MULTIFUNCTION alternates, every two seconds,
the message STO with the message it would display if the shutdown cycle was not in
progress.
Indicators KG and KR (green): indicate the status of the contactors managing the
power changeover. The indicator KR is not present for SW type 12 (/P boards). If the
green indicator is turned on the corresponding external connected contactor is closed.
The external connected contactors can never be both closed, while they can be both
open
during
the
switching.
The default configuration shows the KG and KR command status, not the actual status.
However it is possible to configure the board to use two inputs to monitor the status:
Flashing at 50% duty cycle: the contactor is open but the command is on
Flashing at 90% ON: the contactor is closed but the command is off
Indicator ENGINE RUNNING (green): it indicates the status of the engine of the
generator set. It takes the following meanings:
Turned off: engine shut down
Flashing: engine cooling (this condition occurs only in the AUTOMATIC mode).
Turned on: engine running
EAAM002010I.doc
Indicator GENERATOR LIVE (green): it indicates the status of the generator set. It
takes the following meanings:
Turned off: the generator doesnt produce any voltage.
Flashing: The generator is living but some of the parameters (voltages on one or
more phases or frequency) are not within the programmed tolerance limits,
therefore the users cannot be switched on it.
Turned on: The generator is living and all its parameters are within the
programmed tolerance limits, therefore it is possible to switch the users on it.
MAINS LIVE indicator (green): It indicates the mains status. It takes the following
meanings:
Turned of: mains failure.
Flashing: the mains is present but the voltage on one or more phases is not within
the limits of the programmed tolerance thresholds, therefore if the users are
currently switched on the generator, they will have to stay on it.
Turned on: the mains is present and within the programmed tolerance limits,
therefore the users can be switched on it.
NB: the board has an input (MAINS SIMULATION, terminal 24) that can be used to
inhibit the automatic operation of the genset. If this digital input is activated,
independently from what has been acquired with the mains sensor, the engine is not
automatically started.
Furthermore, there are two digital displays (each of them having 3 digits) to show the
electric quantities measured on the generator. The left display (called display V) shows
the generators voltages (phase-to-phase for three-phase systems, phase-to-neutral for
single-phase systems) Volts. The right one (called display A) shows the phase currents
in Amperes. The view format changes according to the set TA ratio (P17):
P17 < 10: the currents are displayed with two decimals
P17 >=10 and <100: the currents are displayed with one decimal
P17 >=100: the currents are displayed without any decimal. If the current
measurement exceeds 999 Ampere, it is displayed divided by 10 and the indicator
X10 (yellow), located over the display A turns on.
If the current measured (in the board side of TA) is higher then 5 Amperes, the display A
blinks to indicate lower measure precision.
If the board is supplied with the power measurement option it is possible to view the power
factor (indicated by POWER FACTOR (cos )) on the display V and the active power
(indicated by ACTIVE POWER (kW)) on the display A (POWER DISPLAY FUNCTION).
Furthermore, it is possible to view the energy meter (kWh on the display A and MWh on
the display V). All these measures will blink if at least one of the current measurement
circuits of the board is saturated (see description at the previous paragraph).
Three yellow indicators (called L1/L2, L2/L3 and L3/L1) located between the two
displays are also present. They indicate to which phase the measurements displayed in any
moment refer. On single-phase systems the voltage and the current of the only present
phase are always displayed, therefore the indicator L1/L2 is always turned on, while the
L2/L3 and L3/L1 are always off. On three-phase systems, the three phases are
periodically alternated every 4 seconds on the displays and the indicators L1/L2, L2/L3
and L3/L1 show the current phase. However, it is possible to force the display of one
EAAM002010I.doc
phase only even on three-phase systems by pressing at the same time the buttons F1 and
F2 when the displays show the quantities relating to the phase one intends to force: the
phases scanning will be interrupted and will start again when the two buttons F1 and F2
will be pressed at the same time again.
Indicator TEMPERATURE (red): it indicates the alarm or block status due to the high
cooling water temperature. The indicator flashes at a different speed to indicate an
alarm (more quickly) or a block (more slowly, as for all other blocks). It can be acquired
from:
Digital input WATER WARNING (terminal 10)
Digital input WATER. ALARM (terminal 09)
Analogue input TEMPERATURE (terminal 43)
Indicator LOW OIL PRESSURE (red): it indicates the alarm or block status due to the
low oil pressure of the engine. The indicator flashes at a different speed to indicate an
alarm (more quickly) or a block (more slowly, as for all other blocks). It can be acquired
from:
Digital input OIL WARNING (terminal 08)
Digital input OIL P. ALARM (terminal 07)
Analogue input OIL PRESSURE (terminal 42)
Indicator MAX LEVEL (yellow): It indicates the alarm status due to the maximum fuel
level in the tank. It can be acquired from:
Digital input HIGH LEVEL FUEL (terminal 04)
Analogue input FUEL LEVEL (terminal 45)
Indicator OVERCRANK (red): It indicates the block status due to a failure in the
automatic start of the engine. It is produced by the operating sequence in the
AUTOMATIC mode.
Indicator DISCHARGED (yellow) it indicates the alarm status due to the charge level
of the starting battery of the generator set. Such battery also powers the board
DST4600A. The alarm is produced if the battery voltage exceeds the tolerance limits:
11.8 15 V (for nominal voltage of 12 V battery)
23.2 30 V (for nominal voltage of 24 V battery)
Indicator MIN LEVEL (yellow): it indicates the alarm status due to the minimum fuel
level in the tank. It can be acquired from:
Digital input LOW LEVEL FUEL (terminal 05)
Analogue input FUEL LEVEL (terminal 45)
EAAM002010I.doc
Indicator ALARM2 (AUX. ALARM) (red): it indicates the masked generic block status.
It can be acquired from:
Digital input ALARM 2 (terminal 02)
Indicator OVERSPEED (red): it indicates that the engine is running too fast and it
could damage the alternator or the engine itself. It can be acquired from:
Digital input OVERSPEED (INPUT C terminal 12)
Generators frequency exceeding the set threshold (parameter P21)
Indicator NO FUEL (red): it indicates the block due to the end of the fuel in the tank. It
can be acquired from:
Digital input FUEL END (terminal 06)
Analogue input FUEL LEVEL (terminal 45)
Indicator EMERGENCY STOP (red): it indicates the block that follows the pressing of
the emergency button. It can be acquired from:
Digital input EMERGENCY STOP (terminal 03). NB: the block is enabled when
the digital input is not activated.
EAAM002010I.doc
3. Start Initialization
As soon as the board is powered it executes the following operations:
Lamp Test: during this phase it turns on all the indicators in the front panel and it shows
888 (with the decimal points turned on) on the three displays. This operation lasts two
seconds and allows the identification of any failure in the front panel that could involve
visual signaling of a fault.
Display the software level. The display MULTIFUNCTION shows the message REL
(release). The display V shows the main version; the display A shows the secondary
version. For instance, for a software level 1.23 the display V will indicate 1 and the
display A will indicate 23. In this phase all the indicators on the front panel are
turned off. This phase lasts one second.
In the event of data errors in the non-volatile memory, the display MULTIFUNCTION
shows, in place of REL the message:
After the execution of the above-mentioned operations, the board starts executing the work
sequences, according to the position of the key selector.
EAAM002010I.doc
4. Calibration Procedure
The calibration procedure is carried out by the producer and not by the user. Such
procedure requires particular instruments and working conditions. The only function
requiring a users calibration is that of the level sensor.
The user will strictly follow the instructions given in this paragraph; otherwise, he could alter
the calibration factors and would have to return the DST4600A board to SICES S.R.L. for a
new calibration.
4.1
4.2
The indicator L1/L2 turns off and L2/L3 flashes. The display V shows a 0 value
while the display A shows the level value calculated according to the actual
parameters.
EAAM002010I.doc
2.
Place the level sensor at the minimum level it can reach within the tank. Then wait
until the value on the display A gets stable (it can take a lot of seconds). Then you
can change the value showed on the display V to associate any percentage to the
current physical level in the tank. Normally with the sensor at the minimum level the
system should indicate 0% but there may be situations in which you need it indicates
10%, for instance. To change the percentage use the buttons F1 and F2, for which
the AUTOREPEAT function is enabled.
3.
When the display V shows the percentage you want to associate to the minimum
level and the valued indicated by the display A is stable, by pressing MODE / ACK
you will pass to the next stage
4.
The indicator L1/L2 stays off and L2/L3 keeps flashing. The display V shows a
100 value while the display A shows the level value calculated according the actual
parameters.
5.
Place the sensor at the maximum level it can reach within the tank. Then wait until the
value showed on the display A gets stable. Now you can change the value showed
on the display V to associate any percentage to the current physical level in the
tank. Normally with the sensor at the maximum level the system should indicate 100%
but there may be situations in which you need it indicates 90% or 110%, for instance.
To change the percentage use the buttons F1 and F2, for which the
AUTOREPEAT function is enabled.
6.
When the display V shows the percentage you want to associate to the maximum
level and the valued indicated by the display A is stable, by pressing the MODE /
ACK button you will pass to the next stage
7.
Then the system calculates the parameters it has to use to obtain the level, it turns the
indicator L2/L3 off and L1/L2 on and shows the level calculated according to the
new parameters The new parameters are immediately stored in the non-volatile
memory.
EAAM002010I.doc
5. Programming Procedure
With this procedure it is possible to configure all the parameters controlling the boards
operation. Those parameters can be thresholds or times, but also operating options or
hardware configuration. The parameters are stored in the non-volatile memory. When the
board is turned off a consistency test is carried out on such parameters and in the event of
an error the alarm F09 is produced and the default values are loaded.
Some parameters are bit-managed. Each 1 bit enables a function and each 0 bit disables a
function. Each bit corresponds to a value. The parameter must be set with the result
obtained by summing the values associated to the bits you wish to put at 1. 8 bits are
available. A table like the following one explains the bit-managed parameters:
5.1
Bit Value
Description
Enable function 1
Enable function 2
Enable function 3
Enable function 4
16
Enable function 5
32
Enable function 6
64
Enable function 7
128
Enable function 8
If its required to disable all functions set the value 0 for the parameter.
If its required to enable all functions, set 255 (1+2+4+8+16+32+64+128) for the
parameter.
If its required to enable only selected functions, values of the selected are to be
summed (for example, to enable only the functions 3, 4, 6 and 8, the value 4+8+32+128
= 172 is to be set for the parameter).
Description
From
Level
Min
Value
Max
Value
Default
Value
Unit of
measure
Disable
Value
P01
0.00
999
320
P02
0.00
20
10
P03
Generators voltage
presence recognition
threshold
0.00
999
80
P04
0.00
999
EAAM002010I.doc
Cod
e
Description
From
Level
Min
Value
Max
Value
Default
Value
Unit of
measure
Disable
Value
P05
0.00
999
30
P06
0.00
999
P07
0.00
999
45
P08
0.00
20
P09
0.00
300
20
P10
Number of starting
attempts of the generator
set
0.00
15
P11
0.00
10
60
45
Hz
Min
P12
0.00
52
99
55
Hz
Max
P13
0.00
10
999
300
Min
P14
0.00
100
999
450
Max
P15
0.00
100
999
440
P16
0.00
100
Min
P17
TA Ratio
0.00
6000
/5A
P18
0.00
999
Ore
Min
P19
0.00
60
Min.
Min
P20
0.00
99
Min
P21
0.00
55
99
60
Hz
Max
P22
0.00
30
EAAM002010I.doc
Cod
e
Description
From
Level
Min
Value
Max
Value
Default
Value
Unit of
measure
Disable
Value
P23
0.00
20
P24
0.00
20
P25
0.00
0.0
9.9
0.0
Bar
Min
P26
0.00
199
199
Max
P27
0.00
100
100
Max
P28
0.00
100
Max
P29
0.00
100
Max
P30
0.00
100
Max
P31
0.03
120
15
P32
0.03
999
30
P33
0.03
100
Min
P34
0.03
9.9
0.0
Bar
Min
P35
0.03
199
Min
P37
0.03
247
P38
0.03
99
P39
Enable mask 1
0.03
255
127
P40
0.03
0.5
10.0
0.5
P41
0.03
15
P42
0.03
20
10
Hz
EAAM002010I.doc
Cod
e
Description
From
Level
Min
Value
Max
Value
Default
Value
Unit of
measure
Disable
Value
P43
0.03
10
Hz
P45
0.03
P46
0.03
11
P47
0.03
11
P48
0.03
P49
Enable mask 2
0.03
255
191
P50
Next maintenance
occurrence
0.03
999
Tenths of
Hours
P51
Type of serial
communication
0.03
11
P52
0.05
999
kW
Min
P53
0.05
999
P54
0.05
999
60
Max=
always
0=never
P55
0.05
199
Min
P56
0.12
9999
kW
Min
0.12
999
0.12
9999
kW
Min
0.12
999
P60
0.12
999
P61
Enable mask 3
0.12
255
128
P62
0.12
192
96
Bps/100
P57
P58
P59
0.37
0.37
0.37
0.37
EAAM002010I.doc
Cod
e
Description
From
Level
Min
Value
Max
Value
Default
Value
Unit of
measure
Disable
Value
P63
0.12
P64
0.18
3600
60
P65
0.22
999
1-STD
180-/P
P66
0.22
999
2-STD
0- /P
P67
0.22
999
P68
Generator Secondary
winding Primary winding
turns ratio
0.23
1000
1000
Thousandth
P69
0.23
1000
1000
Thousandth
P70
0.24
00.00
23.59
00.00
Hour.Min
P71
0.24
00.00
23.59
00.00
Hour.Min
P72
0.24
127
127
P73
0.24
00.00
23.59
00.00
Hour.Min
P74
0.24
127
127
P75
0.24
60
Min
P76
0.33
999
P77
0.33
100
999
500
P76=0
P78
Delay for
protection
0.37
0.0
3.0
0.1
P79
Enable mask 4
0.38
255
16STD
20- /P
short
circuit
EAAM002010I.doc
Parameters P52, P53, P56, P57, P58, P59 and P60 are displayed only if the board is
equipped by power measurement option.
Parameters P70, P71, P72, P73 and P74 are displayed only if the board is equipped by
Real Time Clock option.
Default values are referred to 400V-50Hz generator set system.
The following table outline the main parameters change depending on generator set
configuration.
Code
Description
230 V
400 V
440 V
50 Hz
60 Hz
P01
150
320
360
P03
80
80
80
P11
45
55
P12
55
65
P13
130
300
330
P14
280
450
490
P15
270
440
480
P21
60
70
EAAM002010I.doc
Available values:
0
10
15
20
25
30
35
40
50
60
70
75
80
100
120
125
150
200
250
300
400
500
600
700
750
800
1000
1200
1250
1500
1600
2000
2500
3000
4000
5000
6000
Description
16
32
64
128
EAAM002010I.doc
This parameter allows the configuration of the temperature sensor. The available values
are:
Value
Trademark
Scale
Characteristics
No
VDO
40..150 C
288..10 Ohm
BORLETTI
40..150 C
1185..39 Ohm
10
MTU
0..120 C
0..10 V
11
SCANIA
40..120 C
10 V PWM
Trademark
Scale
Characteristics
No
VDO
BORLETTI
0..8 Bar
300.20 Ohm
VDO
0..5 Bar
10..180 Ohm
10
MTU
11
SCANIA
0..7 Bar
10 V PWM
Trademark
Scale
Characteristics
No
VDO
0..100 %
180..10 Ohm
Description
16
32
64
EAAM002010I.doc
Bit Value
Description
128
EAAM002010I.doc
the generator set (even in manual). Both parameters are not displayed if the board doesnt
have the power measurement option.
Description
16
Enable generator set Time Lock function (only if Real Time Clock option is
installed)
32
64
128
Select the function related to parameters P56-P60. If set, the max power
protection function is selected, if not set the low power signaling function is
selected.
The bit 3 of this parameter enables some special functions related to Volvo engines. These
functions are available from SW 08.00.21. These functions are:
The stop in excitation command duration is fixed to two seconds. The time set in
parameter P09 is used again for activation of F21 block (engine not stopped)
The block OVER-SPEED (from terminal 12) can be activated only if engine is running
(it is ignored if engine is stopped).
EAAM002010I.doc
5.1.16 Parameter P62
P62 is used to configure the serial port baud rate. This setting is valid for all the selected
protocol.
It is possible to select the following values:
300 bps
600 bps
12
1200 bps
24
2400 bps
48
4800 bps
96
9600 bps
192
19200 bps
EAAM002010I.doc
Value for P68 and/or P69 id ((440 / 690) * 1000) 638
If Power Option equips your board, be caution in transformer choice. In this case
care that the phase lag introduced will be negligible.
For best performance use measure transformer or at lest 30VA transformer designed for the
nominal voltage at no-load. Thats should minimize also harmonic distortion.
Description
Sunday
Monday
Tuesday
Wednesday
16
Thursday
32
Friday
64
Saturday
128
Reserved
Days related to Values used to obtain the programmed parameter have the specific function
(Generator set periodic test and Generator set Time Lock) enabled.
These parameters are valid only if the Real Time Clock option is installed and
according to bit 4 of P61.
EAAM002010I.doc
The implemented function is known as Extremely Inverse I2t.
Intervention time
1000
100
10
0,1
1
10
Multiple of I
The graphic shows the trend of the intervention time related to multiples of over-current
threshold, with P76 set to 60 seconds.
Description
EAAM002010I.doc
5.2
Bit Value
Description
If set, when switching from AUTO or TEST to MAN the load is connected
to KR (or, for /P, the KG breaker is opened)
If set, the board sends SMS or makes data calls when mains become
present.
16
32
64
128
5.3
5.4
Selecting a Parameter
To select a parameter use F1 e F2. Through F1 you go to the next parameter, through
F2 you go to the previous one. The management of these buttons supports the
AUTOREPEAT function, that is if you press and soon release one of the buttons F1 or
F2 you move of only one position in the parameters list, while if you keep it pressed you
move of one position as soon as you press the button and after 1 second you move of one
position every 0.1 seconds. The parameters are displayed cyclically, that is by pressing F1
you move from the last to the first and vice versa.
5.5
Setting a Parameter
When the display MULTIFUNCTION shows the wanted parameter (PXX) to change it you
need to follow the instructions below:
EAAM002010I.doc
1.
Press MODE / ACK. The indicator L1/L2 turns off and L2/L3 flashes.
2.
Use F1 and F2 to change the value. Through F1 you increase the value, through
F2 you decrease it. The management of these buttons supports the
AUTOREPEAT function, that is if you press and soon release one of the buttons
F1 or F2 you move of only one position in the parameters list, while if you keep it
pressed you move of one position as soon as you press the button and after 1 second
you move of one position every 0.1 seconds. If you keep pressed the button for other
five seconds, the AUTOREPEAT function will add 5 to the value. Again, elapsed
other 5 second with the button pressed, it will be added 50 to the value.
The parameters are displayed cyclically, that is by pressing F1 you move from the
last to the first and vice versa.
3.
If you wish to cancel the setting in progress press STOP. The original value of the
parameter is displayed. The indicator L2/L3 is turned off, while L1/L2 one is turned
on. You are again at point 1.
4.
If you wish to store the set value press MODE / ACK. The indicator L1/L2 turns on
and L2/L3 turns off. The new value is immediately stored in the non-volatile
memory. You are again at point 1.
The instructions at point 2 refer to all parameters except P17 (TA ratio) and P62.
Some parameters can have values over 999. In those cases, until SW version 08.00.23, the
value is displayed divided by 10 (therefore you lose the possibility to set the units) and the
indicator x10 is turned on. Starting from version 08.00.24, the indicator x10 is no more
used (in programming mode) and values are shown on the two displays V and A.
The parameters P25, P34 and P40 are displayed with a decimal. The parameters P70, P71
and P73 are displayed with two decimals.
5.6
5.7
5.8
EAAM002010I.doc
The Lamp Test procedure (testing of all the indicators and displays of the panel and of the
board) is not carried out during the programming procedure but when the board is powered.
To give the operator the opportunity of executing the test without disconnecting the board, it
is possible to execute such test during the programming procedure, but only by a command.
Actually, you need to enter the programming procedure in the view mode and then press
STOP. Until you keep the button pressed all the indicators and displays will turn on.
EAAM002010I.doc
6. Faults
During the operation of the generator set (but even when it is not running) some faults may
occur. The faults can be divided into three categories according to the way the affect the
generator set:
Alarms: faults that are not immediately dangerous for the generator set and for its load,
and that therefore allow the generator set to keep on working. They require an
operators intervention otherwise they could cause a more dangerous fault.
Deactivations: these faults are more dangerous for the load that needs to be switched
immediately on the mains (even if theres a mains failure) but they arent immediately
dangerous for the generator set and/or for the operator: the generator set will have to be
stopped in any case but it can be stopped with the standard procedure (cooling cycle,
etc.).
Blocks: these faults can damage the generator set and sometimes the load, too. When
they are activated, the load is immediately switched on the mains (even if theres a
mains failure) and the engine is stopped through the emergency procedure (without the
cooling cycle).
Any fault can be activated only if the key selector is on MAN, AUTO or TEST.
The alarms can always be activated. There may be more than one alarm at the same time.
The deactivation can be activated if in the moment the cause occurs no deactivation or
block is present, while one or more alarms can be present. There cannot be two
deactivation at the same time.
The blocks can be activated only if in the moment the cause occurs no other block is
present, while deactivation and/or alarms can be present. As a principle, there cannot be
two blocks at the same time, but actually, the blocks NO FUEL, EMERGENCY STOP
and MANUAL STOP IN AUTO are an exception since they can be activated even in
presence of other blocks
When a fault occurs, whatever be its category, the audible alarm is activated (ALARM
OUTPUT, terminal 16) as well as the corresponding visual signal. Such signal can be an
indicator on the front panel (fault area) or a message FXX on the display
MULTIFUNCTION. In the case of an indicator it flashes.
The audible alarm stays active for the time programmed through the parameter P54 than it
turns off automatically (if P54 is equal to 999 the siren does never turn off automatically, if
P54 is equal to 0 the siren never turns on), while the visual signal keeps on flashing until the
operator doesnt recognize it.
The recognition involves the pressing of MODE / ACK. As a consequence, the signal
stops flashing and stays turned on and the audible alarm (if still active) is disabled.
Once the operator has recognized the alarms, they are automatically cancelled by
DST4600A when the corresponding cause ceases to exist. If the alarm is cancelled, the
visual signal turns off, too.
While the blocks and deactivation can be cancelled only by switching the key selector to
OFF/RESET.
EAAM002010I.doc
6.1
6.2
Description
F01
F02
F03
F04
F05
F06
F07
F08
F09
F10
F11
F12
F13
F14
F16
Short-circuit
F21
F40
F49
F50
Alarms
6.2.1.2
EAAM002010I.doc
Conditions to activate it Engine running from the time set through the parameter P31
Pressure detected by the analogue input OIL PRESSURE
(terminal 42) lower or equal to the threshold set through the
parameter P25
Fuel solenoid activated.
Filter time
2 seconds
Visual signal
Quick flashing of the indicator LOW OIL PRESSURE
Filter time
Visual signal
6.2.2.2
Filter time
Visual signal
Filter time
Visual signal
6.2.4.2
EAAM002010I.doc
Conditions for its
activation
Filter time
Visual signal
6.2.5.2
6.3
Deactivations
Parameter P13 = 0
EAAM002010I.doc
Conditions for its
activation
Filter time
Visual signal
No deactivation
No block
Engine running
Generator already in the operating window from starting.
Shutdown cycle not in progress
Fuel solenoid activated
With selector on MAN, generator set contactor closed
Generators voltage under the threshold set through the
parameter P13 at least on one phase
Not existent in asynchronous engine version
Time set through the parameter P24
Message F01 on the display MULTIFUNCTION
Filter time
Visual signal
6.4
Parameter P11 = 0
No deactivation
No block
Engine running
Generator already in the window from starting.
Shutdown cycle not in progress
Fuel solenoid activated
With selector on MAN, generator set contactor closed
Generators frequency under the threshold set through the
parameter P11
Not existent in asynchronous engine version
Time set through the parameter P23
Message F03 on the display MULTIFUNCTION
Blocks
Cannot be disabled
EMERGENCY STOP input, terminal 03 open
0.5 seconds
Indicator EMERGENCY STOP slowly flashing
Cannot be disabled
Key selector on AUTO or TEST
STOP button pressed o external STOP command
0 seconds (immediate)
Message F07 on the display MULTIFUNCTION
Digital input
Disabling
Conditions for its
activation
Filter time
Visual signal
6.4.3.2
EAAM002010I.doc
Visual signal
Filter time
Visual signal
6.4.4.2
Filter time
Visual signal
Filter time
Visual signal
6.4.5.2
Filter time
Visual signal
EAAM002010I.doc
Conditions for its
activation
Filter time
Visual signal
No block
Engine running from the time set through the Parameter P31
Fuel solenoid activated
ALARM 2 digital input (terminal 02) shorted to ground
Starting from SW version 08.00.22 this value is set by
parameter P.65.
In the old version this time was set through the parameter
P40
ALARM 2 (AUX ALARM) indicator slowly flashing
Filter time
Visual signal
Filter time
Visual signal
Disabling
Conditions for its
activation
Filter time
Visual signal
6.4.10.2
From Frequency
Disabling
Conditions for its
activation
Filter time
Visual signal
6.4.11 Overload
6.4.11.1
Disabling
EAAM002010I.doc
Conditions for its
activation
Filter time
No block
OVERLOAD digital input (terminal 11) shorted to ground
Time set through the parameter P40. Starting from 08.00.23
version, a fixed time of 1.5 second is added to the set value.
Visual signal
OVERLOAD indicator slowly flashing
Starting from revision 08.00.38, this block may be configured as a deactivation by using bit
0 of parameter P79.
6.4.11.2
Disabling
Conditions for its
activation
Filter time
Visual signal
Filter time
Visual signal
Cannot be disabled
No block
Selector on AUTO or TEST
Engine running
Fuel solenoid activated
The generator doesnt get in operating window (for two
seconds) within the time limit set through the parameter P32
from the engine start.
Immediate
Message F08 on the display MULTIFUNCTION
6.4.15 OVERCRANK
Disabling
Cannot be disabled
EAAM002010I.doc
Conditions for its
activation
Filter time
Visual signal
No block
Selector on AUTO or TEST
Engine not running after P10 starting attempts
Immediate
OVERCRANK indicator slowly flashing
Cannot be disabled.
No block
Detected hardware fault on generator voltage measurement.
Immediate
Message F50 on the display MULTIFUNCTION
Filter time
Visual signal
Cannot be disabled
Inhibition activated by serial line or SMS
Immediate
Message F12 on the display MULTIFUNCTION
Filter time
Visual signal
Cannot be disabled
No block
Engine running
Fuel solenoid activated
Shutdown cycle not in progress
KG closed
Engine in threshold input not active for at least 0.5 sec.
Immediate
Message F40 on the display MULTIFUNCTION
EAAM002010I.doc
7. Operating Sequence
7.1
Definitions
P04: generator set intervention delay for mains voltage failure (s)
P05: Mains restoration delay (closing mains contactor from mains present) (s)
Mains is considered alive if the voltage on all the existing phases is over of the alive
mains threshold. It is considered dead if the voltage on at least one phase is under the
dead mains threshold. If no phase is under the dead mains threshold but at least one of
them is under the alive mains threshold, the mains keeps the dead/alive status it
previously had (hysteresis). If the voltage on at least one phase is over the
OVERVOLTAGE threshold, the mains is considered alive out of window. Of course the
parameter P15 must be over the alive mains threshold.
In addition, there is the digital input MAINS SIMULATION (terminal 24). When such input
is enabled, the board wait for time T2 is elapsed before mains is considered present.
Furthermore, if the board is set to work with an external mains sensor (using only the
MAINS SIMULATION input and ignoring the mains voltages), when the input MAINS
SIMULATION is not enabled the mains is immediately considered absent. Depending on
the SW versions, the delay times related to this input are different.
Starting from SW version 08.00.22 the parameters P66 and P67 are used to set the
Generator set intervention and shutdown on MAIN SIMULATION deactivation and
activation
Starting from SW version 08.00.09 to SW revision 08.00.21 the same parameters used
for the delay of the mains control are used (P.04 and P05).
Before 08.00.09 version there were no delay time related to this function.
Absent:
EAAM002010I.doc
Restoring:
Present:
Outgoing:
The T1 and T2 times change according to the position of the key selector and if the engine
is running or dead:
SELECTOR
ENGINE
T1
T2
AUTO-TEST
Dead
P04
P05 1
MAN-PROG-OFF
Dead
P04
0s
AUTO-TEST
P05
MAN 2
0s
As you can see, the transitional mains failure is cancelled (2 seconds) with the engine
running. In such conditions, as soon as a mains failure occurs, if the selector is on AUTO
the users are switched on the generator.
In the same way, the transitional mains restoring is cancelled (0 seconds) only if the selector
is in OFF-PROG-MAN, to avoid the engine starting or the users switching on the generator
set if going back to AUTO during the mains restoring.
Unusual case: in AUTO mode the engine is dead during the transitional mains restoration only in the event of starting
failure.
EAAM002010I.doc
The generator is considered alive if the voltage on all the existing phases is over the
alive generator threshold. It is considered dead if the voltage on at least one of the
phases is under the dead generator threshold. If no phase is under the dead generator
threshold but at least one phase is under the alive generator threshold, the generator
keeps the previous dead/alive status (hysteresis).
If the voltage on at least one of the phases is over the OVERVOLTAGE threshold, the
generator is considered alive out of window. Of course, the parameter P14 must be set in
order to be over the alive mains threshold.
If the voltage on at least one of the phases is under the UNDERVOLTAGE threshold, the
generator is considered alive out of window. Of course, the P13 parameter must be set in
order to be over the alive mains threshold and over the parameter P14.
If the generators frequency is over the OVERFREQUENCY threshold, the generator is
considered alive out of window.
If the generator is alive but its frequency is under the UNDERFREQUENCY threshold, the
generator is considered alive out of window. Of course, the parameter P11 must be under
the parameter P12.
4 status are defined in the generator management:
Absent:
Restoring:
Present:
Outgoing:
7.1.3.2
Generators frequency over the threshold specified through the parameter P42 (only if
enabled with bit 6 of the parameter P49)
Voltage on all the generators phases less than 80 V (not configurable). Starting from
version 08.00.23, is used the value of P03 (the default value is changed to 80V).
Voltage at the D+WL input (terminals 39..40) over the threshold (10 or 20 V according
to the nominal voltage of the battery), only if enabled with bit 4 of the parameter P39.
On the DST4600A board this time act only if the generator set contactor is open. If it is closed, wait until the alarms
management starts the F01.F04 alarm and then execute the emergency stop cycle.
EAAM002010I.doc
7.1.3.3
Generators frequency under the threshold specified by the parameter P43 (only if
enabled with bit 6 of the parameter P49)
Voltage on at least one generators phases less than 80 V (not configurable). Starting
from version 08.00.23, is used the value of P03 (the default value is changed to 80V).
Voltage at the D+WL input (terminals 39..40) under the threshold (3 or 6 V according to
the nominal voltage of the battery), only if enabled with bit 4 of the parameter P39.
Starting Request
It is a series of many conditions. The most important one is the absence of any block or
deactivation. The remaining conditions depend on the key selector status:
MAN
a) START button pressed.
AUTO
a) Mains status Absent (and no MAINS SIMULATION)
b) REMOTE TEST digital input (terminal 46) enabled
c) Periodical Test (if configured through the parameters P18 and P19)
d) Starting command from RS232 serial line
TEST
a)
7.1.3.4
Stop Requests
The immediate stop request is given by at least one of the following conditions:
a) STOP button
b) Presence of any block.
c) Selector on OFF or on PROG
d) Request from serial line or SMS.
The request of stop with cooling cycle is given by at least one of the following conditions:
a) Selector on AUTO and no starting request
b) Selector on AUTO or TEST and presence of a deactivation
7.2
Shutdown System
The control board can be set to work with engines equipped with an excitation shutdown
system (usually electromagnet with control on the engine stop lever or electro-valve
interrupting the fuel supply), or dropout shutdown ones (standard versions - usually N.C. fuel
supply electro-valve or electro-magnet unlocking the engine stopping condition).
In the first case (EXCITATION SHUTDOWN), the stopping control STOP SOLENOID
(terminal 18) is activated for the time set with the parameter P09. If the VOLVO engine EDC
EAAM002010I.doc
function is enabled (bit 3 of P.61) is enabled, the STOP SOLENOID is driven for a fixed
time of 2 seconds. The command is activated at the beginning of the shutdown phase, stays
active for all the set duration and is disabled at the end of the same period.
In the second case (DROP-OUT SHUTDOWN), the stopping command takes the meaning
of permission to the engines running, FUEL SOLENOID (terminal 22) is activated with the
engine starting command and stays active until the beginning of the stopping command.
7.3
Keeping of the contactors status. From revision 00.00.39, it is possible to configure the
board for switch to mains (bit 2 of P79 parameter).
If the engine is cooling, such phase is cancelled and the engine is kept running.
EAAM002010I.doc
simply press it for a second and the board execute a complete shutdown cycle. That is, it
disables the FUEL SOLENOID output and it enables the STOP SOLENOID one (terminal
18) for the time set with the parameter P09 (if it is enabled the VOLVO engine EDC this
time is fixed and of 2 seconds).
The MANUAL mode doesnt foresee any shutdown failure block, except for the automatic
shutdown cycles following blocks or deactivation.
7.4
EAAM002010I.doc
2. The STOP SOLENOID output (terminal 18), used for the excitation shutdown, is
disabled (it should already be disabled unless the starting request occurs during a stop
cycle). If the engine is already running, the procedure stops here.
3. If the preheat function for diesel engines is enabled the AUX OUTPUT 1 (terminal 15)
is enabled for the time set with the parameter P20 (if such time is equal to 0 the preheat
function is disabled). In this phase the display MULTIFUNCTION shows the message
PRE. At the end of this phase the output is disabled passing to phase 2.
4. The START output (terminal 20) controlling the generator set starter, is enabled. The
output is kept for the time set with the parameter P08 or until the engine running
recognition. In this phase the display MULTIFUNCTION shows the message STA. If
the engine gets started phase 6 will follow, otherwise phase 5 will follow (unless the
starting attempts have ended,
5. The START output is disabled and theres a wait for with the duration set with the
parameter P38 During this phase the preheat function for diesel engines is enabled, as
well as the AUX OUTPUT 1 (terminal15) and the display MULTIFUNCTION shows
the message PRE.
6. Engine running.
The activation sequence is always: FUEL SOLENOID (terminal 22), AUX OUTPUT 1
(PREHEAT OUTPUT) (terminal 15) and then START (terminal 20). Thus, it is possible to
use this feature to drive an auxiliary output that requires to be activated before the actual
start command (use parameter P38 to configure the delay time).
Starting from SW version 08.00.12, the activation sequence is always: FUEL SOLENOID
(terminal 22), AUX OUTPUT 1 (PREHEAT OUTPUT) (terminal 15) and then START
(terminal 20). Thus, it is possible to use this feature to drive an auxiliary output that requires
to be activated before the actual start command (use parameter P38 to configure the delay
time). This sequence is valid also in manual mode.
Starting from SW version 08.00.38, the activation sequence is subjected to the engine
stopped or the shut down cycle completed conditions.
After the time set with the parameter P06 has passed since the generator is in window.
If the temperature analogue sensor exists, if a minimum threshold for the supply
permission has been set (P55 different from 0) and if the temperature is over such
threshold.
In this phase the blocks and deactivations F01, F02, F03 and F04 are enabled, while the
block F08 is disabled.
EAAM002010I.doc
Please, consider that the status of each contactor cannot be inverted from the prior
command before the time set through the parameter P41 is elapsed from the last command.
Please, consider that the status of each contactor cannot be inverted from the prior
command before the time set through the parameter P41 is lapsed from the last command.
STOP SOLENOID output (terminal 18) disabled. If the VOLVO engine EDC function is
enabled (bit 3 of P61), the solenoid is driven only for two seconds but the board waits in
any case until P09 is elapsed.
At the end of the cycle, if the engine is still running, the shutdown failure block (F21) is
activated (anyway the STOP SOLENOID output will not be enabled).
Up to revision 08.00.38, the automatic shut down cycle could be aborted if a new start
request arises. In some situations, this caused a false F01 or F03 blocks. So, from revision
08.00.39 a new start request can be processed only when the engine is stopped or when the
shutdown cycle is terminated.
7.5
The engine is started in any case, independently from the start requests.
The users switching normally is executed only in case of mains failure. The operator
can force it with the same procedure used in the MANUAL mode.
The engine is never stopped automatically, except for blocks and/or deactivations.
EAAM002010I.doc
Therefore, the TEST mode can be used to test accurately the generator set without
disconnecting the users from the mains, but at the same time assuring the users power
supply from the generator set in case of mains failure.
EAAM002010I.doc
8. Power Measurement
The board is able (optionally) to execute the true r.m.s measurements on the generator
voltages and currents as well as the active, reactive, apparent power and power factor
measurements of the system when it is powered by the generator. In addition, it manages
an energy meter for the power supplied by the generator set.
If the option is present, the generator voltages and currents true r.m.s. are displayed in the
place of the corresponding values measured in the standard version, that is on the displays
V and A.
To view the powers press at the same time MODE / ACK and F2 (this combination is
highlighted on the front panel of the board with the indication MODE + F2: POWER
DISPLAY). In this conditions the L1/L2, L2/L3 L3/L1 are all of them turned on and the
display V shows the power factor, while the display A shows the active power. Further, if
through the buttons F1 and F2 you choose the MAINS VOLTAGE (Vac) / REACTIVE
POWER (kvar) function, the display MULTIFUNCTION shows the reactive power, if you
choose the BATTERY VOLTAGE (V) / APPARENT POWER (kVA) function, it shows the
apparent power.
By pressing again the buttons F2 and MODE / ACK at the same time, youll go back to
the indications of the generator and mains voltages and of the generator current.
8.1
Power Factor
The value indicated by the display V is the systems total power factor. It cannot be
viewed for each single phase. It is displayed with two decimals.
The eventual negative sign associated to this quantity indicates the energy inversion status.
This status also refers to the whole system: if one of the phases was in energy inversion,
probably it wouldnt be indicated since globally the system would still supply (NB: actually, it
never occurs: if theres an energy inversion, it is present on all the phases).
Further, through the power factor some information on the type of load, inductive or
capacitive is given to the operator. This information is provided using the decimal point of
the least significant digit of the power factor: when is turned on the load is a capacitive one.
In the place of the power factor are displayed three dashes when its value makes no sense,
that is in the absence of any current (dead engine or frequency not in window). Furthermore,
if the total active power is too low (under 10% of the systems maximum power), the power
factor is forced to one, since its measurement for low current value gets too imprecise.
8.2
Active Power
The active power (the systems total one) is displayed in kW on the display A (message
ACTIVE POWER (kW) over the display. If less than 100 kW is displayed with a decimal, if
over 1000 kW is displayed in tens of kW, with the indicator X10 turned on. It is always
displayed in module: its sign (that would provide the true information of energy inversion) is
associated to the power factor for display problems: if it was displayed associated to the
active power one resolution digit would be lost, while by displaying it associated to the power
factor it replaces the initial zero (actually the power factor is never 1.00 but always 0.xx).
This introduces only a small rounding of the power factor: if it was 1.00 in energy inversion,
instead of 1.00 it was displayed as .99.
EAAM002010I.doc
8.3
Reactive Power
The reactive power (the systems total one) is displayed in kvar on the display
MULTIFUNCTION if the MAINS VOLTAGE (Vac) / REACTIVE POWER (kvar) function is
selected. If under 100 kvar it is displayed with a decimal, if over 1000 kvar it is displayed in
tens of kvar, by turning on the decimal point of the less significant digit to indicate that the
value has to be multiplied by 10. It is displayed with its sign, replacing the most significant
digit.
8.4
Apparent Power
The apparent power (the systems total one) is displayed in kVA on the display
MULTIFUNCTION, if the function BATTERY VOLTAGE (V) / APPARENT POWER (kVA)
is selected. If less than 100 kVA it is displayed with a decimal, if over 1000 kVA it is
displayed in tens of kVA, by turning on the indicator X10. It is, by definition, always
positive, therefore theres no problem for the display of its sign.
8.5
Energy Meter
The energy meter managed by DST4600A counts the energy supplied by the generator set.
It has an internal resolution under 100 Wh but it is displayed in kWh. It is updated every
second. It is displayed alternatively to the powers by pressing MODE / ACK (this procedure
is indicated on the front panel of the board with the indication POWER DISPLAY + MODE:
ACTIVE ENERGY). It uses the displays as follows:
If the energy counter exceeds 8 digits (100 GWh), it is saturated to 99.999.999 but is
displayed with the decimal point of the less significant digit turned on, to indicate the
saturation condition.
The energy counter can be reset. The reset procedure is the following one:
By pressing the F1 and F2 select the DATA HOURS COUNT / START
COUNTER function
Switch the key selector to OFF_RESET.
Press at the same time MODE / ACK and START for 5 seconds. After 5
seconds the counters will be reset. The display does not indicate the reset in any
way; therefore the operator has to count the 5 seconds.
The procedure is similar to the other counter reset procedure. The only difference is in the
used pushbutton: START instead of STOP. Until the SW version 08.00.11 the energy
meter counter were cleared only together with the hour-counter and with the start-counter.
8.6
Connection caution
Be sure that all the TA share the same phase connected to ground and check for the correct
phase connection. Otherwise the power measures will be wrong and itll possible that the
board will issue a reverse power alarm.
As a rule, connect terminal 50, 52 and 54 to ground and check that all the TA has the same
phase connected to the ground. Then, if the measured power factor is negative, reverse all
the TA connection.
EAAM002010I.doc
Moreover, be sure that TA connections meet the generator phases connection (i.e. TA1
must measures L1 current etc.). Otherwise the power measurement will be wrong.
There is no problem about phase rotation direction. The board will recognize if it is
clockwise or counter clockwise and will automatically set-up for correct power measurement.
EAAM002010I.doc
9. Serial Communication
The board DST4600A has a serial connector, which can be used to dialog with the board to
get all the parameters, the status and the quantities to give the commands.
9.1
Hardware Connections
9.1.2
EAAM002010I.doc
Indicator
Signal Quality
TEMPERATURE (C)
9.2
Software Protocols
Using the parameter P51 you can configure the DST4600A to use one of the protocols
described in this paragraph for the serial communications, with no regard to the type of
hardware connection.
EAAM002010I.doc
Connect to INPUT C (terminal 12) a signal from KR that will be close to GROUND
when KR is close.
Enable F13 alarm (warning) setting a value greater than 0 for P75.
Working with this configuration, if the board doesnt acknowledge KR closed, after P75 time,
issues a F13 alarm.
If bit 5 of P61 is set, the board interrupts cooling down sequence or, if engine is not running,
starts the engine and make the Generator set supplying users.
At this point the board doesnt connect the load to the mains (even if its acknowledged) until
operator performs an appropriate action:
From software release 08.00.26 this operation consists in setting the MAN mode,
manually make the mains supplying users and then set the AUTO mode again.
After these operations, if the board doesnt acknowledge KR closed, the alarm F13 is
issued again and the procedure is repeated.
Starting from SW release 08.00.35, the function has been modified in order to inhibit the
engine start (caused by this alarm) if the input MAINS SIMULATION (terminal 24) is active
and if the board is configured to use the internal mains sensor. If this case, in fact, the
MAINS SIMULATION is used as inhibition for automatic intervention: thus, even this
automatic intervention have to be inhibited. If the board doesnt measures the mains, this
input is used as an external mains sensor and so it cannot inhibit this automatic intervention
(because it is in case of mains presence that the alarm F13 causes the engine to start).
Starting from revision 08.00.38, this block may be masked if mains is not present, by using
bit 1 of parameter P79. This mask is useful in plants where the mains breaker is powered by
the mains itself. In this situation, when the mains become unavailable, the board
immediately acquires the breaker open status. The board needs a lot of seconds in order to
start the engine and to close the load on the genset, and so the condition of breaker open
while the command is for closure remains for a lot of time. This condition causes the alarm
F13 to be raised. But if the alarm is masked when mains is not present, this false alarm is
not raised.
EAAM002010I.doc
The function is enabled if the parameters P29, P30 and P48 are all different from 0 and P29
is lower than P30
ENGINE RUNNING (terminal 25): this output is enabled when the engine is running.
GENERAL ALARM (terminal 26): this output is enabled if at least one alarm is present.
TRIP ALARM (terminal 27): this output is enabled if at least a deactivation or a block
is present.
FUEL ALARM (terminal 28): this output is enabled if at least one fuel failure is present:
ENGINE ALARM (terminal 29): this output is enabled if at least one fault in the engine
is present:
-
EAAM002010I.doc
Emergency stop
Belt break
SPEED ALARM (terminal 30): this output is enabled if at least one fault relating to the
engines speed is present:
-
GENERATOR ALARM (terminal 31): this output is enabled if at least one fault
regarding the generator is present:
-
OFF-PROG-MAN (terminal 32): this output is enabled only if the key selector is on
AUTO or on TEST
OFF SELECTION (terminal 33): this output is enabled only if the key selector is on
MAN, AUTO or TEST
Further, you can send the remote signals of the single blocks, deactivations and alarms
through the serial interface with the RS 232C device.
From the software release 08.00.25 is it possible to order as option the second serial port of
DST4600A board. It is then possible to connect to this serial port one expansion board
provided with 32 digital outputs or 16 outputs and 16 inputs. The outputs can be used as
additional remote signals. See document EAAN0022, release 03 or successive.
P56 = 0
P58 = 0
EAAM002010I.doc
To select an action, you have to operate with the bit 7 of parameter P61. If not set, the
board will signal the low power status, if set the board will signal the maximum power status.
This is true from revision EB02200080037, for the previous revisions the only action was the
low power signaling.
The signal is performed by a digital output (OUTPUT 1, terminal 37). The next two
paragraphs describe the available actions in details.
Input INPUT A (terminal 14) must be configured to acquire the KG actual status (bit 1
parameter P61=1).
Parameters P56 and P58 must have values greater than 0 and P58 must be greater
than P56.
This function uses also the parameter P60, in addition to those described in the previous
paragraph.
Operational procedure:
1.
Generator set not supplying: OUTPUT 1 is not activated (floating, open circuit). On
INPUT A (KG status) activation (ground shorted) becomes step 2.
2.
Until P60 time is elapsed, OUTPUT 1 is still not activated. During P60 time, on
INPUT A deactivation the procedure returns toward step 1, otherwise, at the end,
switches to step 3.
3.
Supplied active power less than P56 threshold throughout P57 time:
OUTPUT 1 is activated.
b)
Supplied active power greater than P58 threshold throughout P59 time:
OUTPUT 1 is deactivated.
c)
If the supplied power value is in the range between P56 and P58 values,
OUTPUT 1 status is not changed from the actual status.
EAAM002010I.doc
If the active power is lower than P56 threshold consecutively for the P57 time, the
maximum power status is reset and so the OUTPUT 1 output and the F49 warning are
deactivated (the F49 warning is still present on the DST4600A panel if not acknowledged).
If the active power is between the P56 and P58 thresholds, the maximum power status and
the OUTPUT 1 output and the F49 warning are not modified.
The OUTPUT 1 output can be connected to a circuit breaker for automatically disconnect
the less important loads. If it is connected to a changeover circuit, the board automatically
re-connect the less important loads when the active power back into its nominal range.
Comparing the maximum power signal function to the low power signal function, there are
the following differences:
The genset breaker status is not used (and so is not necessary to connect it).
The OUTPUT 1 output is controlled in the opposite way than in low load function: it
is activated if power is greater than P58, while in the low power function it is
activated if the power is lower then P56.
EAAM002010I.doc
Automatic periodical test of generator set at preset time and days of the week.
Time Lock of Generator set operation at preset time and days of the week.
Display F:
hours (00-23)
Display V:
minutes (00-59)
Display A:
seconds (00-59)
Display F:
day (01-31)
Display V:
month (01-12)
Display A:
year (00-99)
This mode is outlined by the light on of the dot at the least significant digit of the displays.
Pressing again F1 and F2 the mode will revert to hour.
Pressing STOP again the RTC display mode is exit.
From SW release 08.00.35, the displays are blinking if the RTC date/time is not reliable
(and so is required that the operator set the correct date/time).
SEC:
MIN:
HOU:
DAT:
EAAM002010I.doc
DAY:
MON:
YEA:
10.7.4.1
Set P74, configuring the day of the week when carry out the test (see par. 5.1.21)
If P74 is greater than zero (RTC periodical test enabled), the standard periodical test mode
is disabled even if P18 is greater than zero.
10.7.4.2
The parameter P18 determines the cyclical starting period of the generator set.
The parameter P19 determines the duration of the test operation of the generator set.
If during the programming you change the value P18 the period count will restart from zero
in the moment in which youll exit the PROGRAMMING procedure.
The automatic periodical test is disabled if at least one of the two parameters is equal to
zero or if RTC based periodical test is enabled.
If RTC option is not installed it is possible to use only Standard mode periodical test
procedure.
EAAM002010I.doc
This function let you prevent the start of the engine when emergency supply is not required;
otherwise you can use this function to start and stop the Generator set at needed time.
Three parameters are to be set to enable this function:
It is possible to configure only one set of enable time and one set of enable days.
If P70 is equal to P71 the Generator set will be enabled 24 hours at day but only during the
days enabled by P72.
When the system is in Time Lock, the display V and A together will show the message
DISABL.
EAAM002010I.doc
10.8.1 Databases
There are two main types of databases: event databases and analogue data databases.
The first type of databases stores the information related to the events that may arise. They
can be anomalies, status changes or operator commands or other.
When such event arises, the DST4600A board stores the board status alongside the time at
which the event occurs.
The second type of database, stores the analogue data; they are normally stored on regular
time rate.
The databases can store a finite number of records, but they have a circular buffer
structure: the oldest record is discarded and overwritten by the more recent record. The
record index one is always assigned to the oldest record in memory
The number of the implemented databases is four; three of them are of the analogue data
type, the last one records the events.
Fast analogue data: the time rate is programmable by the operator with a resolution of
one second. The database can store 30 records. This database has the purpose to
supply the trend near the event time point. By default, the time rate is 60 seconds,
yielding a database time length of 30 minutes.
Slow analogue data: the time rate of this database is 30 times more slowly than the fast
database. Actually, a new record is written when the fast analogue database is
completely rewritten (thus every 30 fast records).
It can stores 48 records and has the purpose to supply the slow trend over a greater
time window than fast database. By default, it can store two days data.
Analogue data linked to event: this data database store analogue data every time that a
new event is stored into the event database. The records are linked across the two
databases by means time occurrence.
It can store 15 records (16 if RTC option is installed).
Event: the database can store 15 records (96 if RTC option is installed).
EAAM002010I.doc
If the board is to be disconnected from power supply, it is good practice to move the key
lock switch toward OFF/RESET position before disconnect power supply from the board
(battery voltage).
RTC option non-installed: the board doesnt know the current date and time. For this
reason, in the database, it is not stored the absolute time but the time relative to the
board power-up. The way this time is obtained let the board to continuously work up to
136 years before wraps the counter. It is possible, for a PC, to read the board relative
time, compares it to the proper real time clock and calculates the absolute time of a
record.
RTC option installed: full real date and time information are stored. It is thus possible
store events until 31/12/2063 23:59:59.
New anomalies
Start/Stop commands
Other
If RTC option is not installed, only event of TYPE 1 are stored, if RTC is installed both
TYPE 1 and TYPE 2 events are stored. If event is of TYPE 2*, it is normally not stored, but
can be stored if RTC option is present and by setting bit 6 of P61 (enable execution of data
calls or SMS if mains is missing). If event is of TYPE 2#, it is normally not stored, but can
be stored if RTC option is present and by setting bit 3 of P79 (enable execution of data calls
or SMS if mains become present).
Each type of event has an identifying code.
Code
TYPE Description
EAAM002010I.doc
Code
TYPE Description
10
2*
Mains dead
11
12
2#
13
14
2*
20
Generator dead
21
22
30
31
32
33
35
36
37
38
40
Engine halt
41
Engine cranking
42
Engine start
43
44
50
51
52
EAAM002010I.doc
Code
TYPE Description
53
54
55
56
57
58
59
60
Fuel pump on
61
66
67
Board power up
201
202
203
204
205
206
207
Aux. warning
208
209
210
251
252
Aux. 1 block
253
Aux. 2 block
254
Emergency stop
255
Over crank
256
257
EAAM002010I.doc
Code
TYPE Description
258
259
260
261
262
Over speed
263
Overload
264
265
266
267
268
269
270
271
272
273
Event code
Warning list
EAAM002010I.doc
The analogue data related to the event are not stored in the event database. Sometime they
are meaningful, for such reason they are stored into an analogue data database linked to
the event database. The time field is used to link the two databases.
If negative, the most significant digit will be replaced by the minus sign.
EAAM002010I.doc
Moving the key lock switch to OFF/RESET and then moving it away from this position
(moving the key in OFF/RESET doesnt unlock the databases, they are unlocked when
the key is moved in PROG or MAN or AUTO or TEST from the OFF/RESET position).
The last solution is useful for remote management of the board when the data call function
is used.
In this case, when the block arises, the records are locked, the board calls the remote PC
that downloads the data and then unlocks the databases.
Moreover, it is important, using a remote PC to read the data, that the updating of the
databases will be disabled. It is possible to do that also by means a serial communication
command.
Disabling by remote the updating is important because this function let the PC to read all the
data without the record of new data between the readings of two records.
If the remote call function is not used, the manual board resetting command unlocks the
database and the board can add new records.
EAAM002010I.doc
10.9.1 Setup
The data call function setup can be done by means a special PC SW supplied by SICES
s.r.l. By means this program it is possible to configure:
A plant identification string: this string will be sent in each SMS and will be used by the
PC in order to select the calling plant when answering an incoming call.
Up to six-telephone number organized as two groups, the first of four numbers and the
second of two numbers. The second group exists only from revision 08.00.38.
Choice between data call or SMS sending for the numbers of first group
Number of calls attempt or SMS for the numbers of second group (this exists only from
revision 08.00.38)
Choice between data call or SMS sending for the numbers of second group (this exists
only from revision 08.00.38)
10.9.3 Description
When a new alarm, block or disable arises (from software release 08.00.28 even some
status changes), if the GSM modem is ready, the board sends first as many SMS as
configured to each existent number of the groups configured for SMS. So the SMS are
guarantee for each new event that requires them. However, there is no assurance that a
data call is performed for each new alarm or block. This is because all alarms and blocks
that are activated when a data calls is performed, are considered acquired from PC when
EAAM002010I.doc
the data call ends.
When a new event arises, the board follows this procedure:
1. The boards send first as many SMS as configured to each existent number of the
groups associated with SMS. If no group is associated with SMS or if no number is
configured in the group, this step is skipped. Note that up to revision 08.00.38 there was
only one group and so if it is assigned to SMS, the data calls were disabled.
2. The board searches for the first configured number in the groups related to data calls,
starting from first group. If no number is configured, the procedure ends, otherwise uses
the first found number.
3. Make the first attempt to call the selected number.
4. If it gets an answer and at least one valid data transfer from board to PC takes place
with the selected protocol, the function ends, the communication stay alive until closed
by the PC and the function is ready to wake up at the next event. From revision
08.00.38, the PC has to explicitly acknowledge the data calls in order to stop the
procedure (with an apposite ModBus protocol command).
5. If there isnt answer or it is impossible to get a valid connection and valid data transfer,
then the function searches for another, if present, configured telephone number. If it
found the number, wait for a minute and then start from point 3 of this procedure.
6. If no more number is found or if all the number was already attempted, the function
increases the attempt counter. If this value is less or equal to the programmed call
attempts, then it waits for a minute and then start from point 2 of this procedure.
7. If all the attempts are executed without a successful connection and if the event is
already set (no local reset has taken place), the procedure wait for 5 minute then start
again from point 2 of this procedure. The 5-minute pause has the purpose to let an
incoming call to be answered.
10.9.4 PC SW procedure
The host PC must execute the following operations to assure that a valid connection and
data transaction take place.
1. It must answer to the incoming call.
2. It must require to the DST4600A the plant identification string.
3. On board acknowledgment, it must ask to the board the call reason.
4. It can read, then, the recorded events and data in order to identify the fault. To do that,
it must:
a) Sends a database lock command,
b) Reads all the data,
c) Unlocks the database
d) Manages the acquired data.
e) From revision 08.00.38, it must explicitly acknowledge the data call, in order to stop
the procedure on the board.
EAAM002010I.doc
10.10.1
10.10.2
KR management
Now DST4600A/P boards use KR as status for MAINS ALIVE.
Enabling the internal MAINS VOLTAGE sensor and connecting the GRID line to the R-S-T
input terminal, KR will be deactivated if the MAINS is OK, and otherwise it will be activated.
If the internal MAINS VOLTAGE sensor is disabled, KR will be always in deactivated status.
The MAINS SIMULATION input (terminal 24) will never interfere on KR status.
10.10.3
10.10.4
10.11.1
10.11.2
Terminal 8 function
In the standard version, this terminal acquires the low oil pressure alarm. In this version, it
acquires the engine running status, and so the low oil pressure alarm is disabled.
10.11.3
Terminal 10 function
In the standard version, this terminal acquires the high water temperature alarm. In this
version, it acquires the engine in threshold status, and so the high water temperature
alarm is disabled.
EAAM002010I.doc
10.11.4
EAAM002010I.doc
11. References
11.1 SMS Protocol for Boards DST4600A and REMOTE SIGNALS
Document:
EAAS0015
Revision:
01 or later
EAAS0006
Revision:
01 or later
EAAS0016
Revision:
03 or later
EAAS0022
Revision:
03 or later
EAAM002010I.doc
12. Annexes
NB: these annexes dont have to be provided to the user. It is meant for internal use.
NB: special trained operators must carry out these procedures.
A1
A2
A3
Selector on OFF/RESET: test of the digital inputs and of the buttons of the front
panel.
EAAM002010I.doc
A4
Selector on TEST: test of the indicators and displays of the front panel.
Sending data and verifying the received data, the test software checks both the TX and RX
channels. Whats more, the DTR and DSR signal lines are also checked.
If the serial port is working fine, no messages are displayed on display A, otherwise one of
the following messages are shown:
Er1:
Er2:
Er3:
Er4:
Only one error is shown, the priority is from Er1 toward Er2
In this part of the SELFTEST procedure you test also the digital inputs. Display V shows a
code referring to the active digital input or to the button pressed. For the digital inputs, the
number displayed is that of the corresponding terminal. For the buttons is a number over or
equal to 100, whose meaning can be derived from the following table.
Code
Description
01
02
EAAM002010I.doc
Code
Description
03
04
05
06
07
08
09
10
11
12
13
14
24
46
101
F1 button
102
F2 button
103
104
STOP button
105
START button
NB: the digital input EMERGENCY STOP (terminal 03) is considered active when the
corresponding terminal is not closed on the battery negative (that is when the contact
connected to that terminal is open). This is because normally the emergency buttons has
closed contacts that open when the button is pressed. As a consequence, if you execute this
part of the SELFTEST procedure without connecting anything to the terminal 03, the VOLT
display will show the code of that input, that is 03.
If there are two or more active inputs or buttons at the same time, the priority for the
selection of the code to display is made according to the above table. The first position in
the table has the first priority, while the last one has the minimum priority. Therefore, if for
instance the MAINS SIMULATION input and the F1 button are active at the same time,
the display V will show 24 that is the code corresponding to the MAINS SIMULATION
digital input.
A5
EAAM002010I.doc
Message
M.U.
Fractional
Digits
Description
Fr
Hz
1-2
Volt
2-3
Volt
3-1
Volt
C 1
Ampere
C 2
Ampere
C 3
Ampere
R-S
Volt
S-T
Volt
T-R
Volt
BAT
Volt
S P
Bar
S T
S L
ENG
Volt
voltage
Current value is always displayed in AMPERE units. The format may differ depending on
P17 parameter (TA value).
P17 >= 100: value is displayed without any decimal digits. If the value is greater than
999 A, it is divided for 10 and the x10 lamp is light on.
As already stated, you can use the buttons F1 and F2 to select an analogue input. With
the button F1 you move along the above table downwards, while with the button F2 you
EAAM002010I.doc
move upwards. The management of these buttons supports the AUTOREPEAT function,
that is by pressing and soon releasing the F1 or F2 buttons you move of one position
each time, while by keeping it pressed you move of one position as soon as you press the
button and after one second you move of one position every 0.1 seconds. The scanning of
the positions is cyclic, that is by pressing F2 you move from the last to the first and vice
versa.
In this phase do not use the buttons START, STOP and MODE / ACK. By pressing
them youll view different information from the analogue input value on the display A.
Such information is not relevant for the operator.
A6
A7
EAAM002010I.doc
Code
Description
15
16
17
18
20
22
25
26
27
28
29
30
31
32
33
36
37
57
60
Until SW revision 08.00.23, the tested output was automatically changed at fixed rate of 1
second. Starting from revision 08.00.24 it is up to the operator to change the output in test:
pressing any pushbutton does that.
A8
MODE/ACK pushbutton: all signal lamps and displays will be turned off. Then
each segment of MULTIFUNCTION display will then light in sequence one at time.
STOP pushbutton: all signal lamps and displays will be turned off. Then each
segment of V display will then light in sequence one at time.
EAAM002010I.doc
START pushbutton: all signal lamps and displays will be turned off. Then each
segment of A display will then light in sequence one at time.
F1 pushbutton: all signal lamps and displays will be turned off. Then each signal
lamp will then light in sequence one at time.