Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

GE Mark V Overview

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

Improved methods of implementing the triple-modular redundant system center on

SIFT technology and result in a more robust control. SIFT involves exchanging
information on the voter link directly between <R>, <S>, <T> and <C> controllers.
Each control processor measures all of its input sensors so that each sensor signal is
represented by a number in the controller. The sensor numbers to be voted are gathered
in a table of values. The basic SIFT concept brings one sensor of each kind into each of
<R>, <S> and <T>. If a sensor fails, the controller with the failed transducer initially
has a bad value. But it exchanges data with the other processors and when the voting
takes place, the bad value is rejected. Therefore, a SIFT-based system can tolerate one
failed transducer of each kind. In previous systems, one failed transducer was likely to
cause one processor to vote to trip.
A failure of a different kind of transducer on another controller could cause a turbine
trip. This does not happen with SIFT because the input data is exchanged and voted.
<C> is also connected to the voter link. It eavesdrops while all three sets of variables
are transmitted by the control processors and calculates the voted values for itself. If
there are any significant disagreements, <C> reports them to <I> for operator attention
and maintenance action. If one of the transducers has failed, its output will not be
correct and there will be a disagreement with the two correct values. <C> will then
diagnose that the transducer or parts immediately associated with it have failed and will
post an alarm to <I>.
Operator Interface Function:
- Unit control
- Generator control (load control)
- Alarm management
- Manual control
a. Preselect load set point
b. Inlet guide vane control
c. Isochronous control
d. Fuel stroke reference
e. Auxiliary control
f. Water wash
g. Mechanical over speed test
Data
a. Exhaust temperature
b. Lube oil temperature
c. Wheel space temperature
d. Generator temperature
e. Vibration
f. Timers and event counter
g. Emission control data
h. Logical status
2.2 Mark V Data Communication Networks

Figure 1. Mark V Network Communication


Information is communicated, shared, and acted upon in the Mark V Control System via three separate
networks :
- The one external network, the Stage Link, is the primary means of communication between the
Operator Interface (<I>) and the common data processor (<C>) of the control panel.
- The data exchange network (DENET) is an ARCNET type communication network internal to the
Mark V control panel. The function of the DENET is to provide a communication link between the
internal processors of the control panel.

You might also like