Fcu Piping
Fcu Piping
Fcu Piping
HL, VF and VH
Fan Coil Units
FCU PIPING PACKAGES CONTENTS
ITEM PAGE
2 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DESCRIPTIONS FCU PIPING PACKAGES
## L 0 1 0 A 0
Package Package Union PT Port Y Strainer Actuator Flow
Number Size Option Option + Cleanout Voltage Rate1
1. Flow Rate code required for fixed flow control regulator only.
2. Valve packages ship loose on all models except VH.
3. Some unit models and installations may require field piping to connect valve package to coil inlet and outlet.
4. Do not install valve package with control valve actuator below horizontal plane.
5. Valve package assembly length may extend beyond factory auxiliary drip pan.
6. Some valve package components may interfere with factory auxiliary drip pan.
7. Some valve packages may require field furnished and installed insulation.
8. 2-Way control valve may be located in the outlet piping on some models.
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 3
FCU PIPING PACKAGES DESCRIPTIONS
GENERAL NOTES
VH Notes
A minimum of a manual piping package per coil is required on all VH units.
Some restrictions may apply to the Y strainer with cleanout. Contact factory prior to quoting.
VF and HL Notes
Piping packages are factory assembled and shipped loose for field installation to the fan coil unit.
Piping packages are not available on DX or steam coils.
Recommended water flow for 1/2" piping packages is 6.0 GPM with 25 PSIG close-off pressure maxi-
mum; 3/4" is 12.5 GPM and 10 PSIG maximum. If water flow exceeds 12.5 GPM, contact factory for
special pricing.
208/230/277 volt piping packages have extended lead times. Contact factory for ship cycle.
Circuit setter is designed for full shut-off and replaces one ball stop isolation valve.
Y strainer not available on Model HLE horizontal cabinet, or with auxiliary drip pans.
4 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES
PIPING PACKAGE FEATURES AND OPTIONS
COIL COIL
M
COIL COIL
M
OPTIONAL PRESSURE-
TYPICAL 3-WAY CONTROL VALVE TEMPERATURE TEST
PACKAGE WITH AQUA-THERMOSTAT PORTS TYPICAL AT
COIL INLET AND OUTLET
COIL
OPTIONAL Y-STRAINER
WITH CLEANOUT
LEGEND:
M
3-WAY CONTROL VALVE MAN. BALL VALVE W/MEM STOP ADJUST. FLOW SETTER
M
2-WAY CONTROL VALVE FIXED FLOW CONTROL VALVE FC PRESSURE-TEMPERATURE
TEST PORT
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 5
FCU PIPING PACKAGES AVAILABILITY
LEGEND Available x
Not Available
BV Manual Ball Valve(s)
MS Add Memory Stop to One Ball Valve
Y-STR Y Strainer
FC Fixed Flow Control
AFS Adjustable Flow Circuit Setter
PT Pressure/Temperature Test Port
Y CO Y Strainer with Cleanout
6 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES
CODE - 01 CODE - 02
COIL COIL
CODE - 03 CODE - 04
COIL COIL
03- - 00 04- - 00
CODE - 05 CODE - 06
FC
COIL COIL
TWO BALL VALVES & FIXED FLOW CONTROL ONE BALL VALVE & ADJUST. FLOW SETTER
CODE - 07 CODE - 08
FC
COIL COIL
TWO BALL VALVES, FIXED FLOW CONTROL, ONE BALL VALVE, ADJUST. FLOW SETTER,
& Y-STRAINER & Y-STRAINER
07- - 0 08- - 00
NOTES:
1. All drawings subject to change without prior
notice.
2. This diagram shows component position in
relation to fluid flow. Actual valve package
configuration varies with unit type, hand
connection, and pipe size.
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 7
FCU PIPING PACKAGES AVAILABILITY
LEGEND Available x
Not Available
BV Manual Ball Valve(s)
MS Add Memory Stop to One Ball Valve
2W CV 2-Way Control Valve
Y-STR Y Strainer
FC Fixed Flow Control
AFS Adjustable Flow Circuit Setter
PT Pressure/Temperature Test Port
Y CO Y Strainer with Cleanout
C/O B/L Changeover Bleed Line
(On 2-way piping packages, a bleed line is required to ensure water circulation when valve is
closed. Not required on 3-way piping packages).
8 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES
2-WAY CONTROL VALVE 2-WAY CONTROL VALVE W/BALL VALVES, 2-WAY CONTROL VALVE W/BALL VALVES &
W/BALL VALVES ADD MEMORY STOP FIXED FLOW CONTROL
2-WAY CONTROL VALVE W/BALL VALVES, 2-WAY CONTROL VALVE W/BALL VALVES,
2-WAY CONTROL VALVE W/BALL
ADD MEMORY STOP, FIXED FLOW
VALVES & Y-STRAINER
& Y-STRAINER CONTROL, & Y-STRAINER
CODE - 15 CODE - 16
COIL M COIL M
2-WAY CONTROL VALVE W/BALL VALVE & 2-WAY CONTROL VALVE W/BALL VALVE,
ADJUST. FLOW SETTER ADJUST. FLOW SETTER, & Y-STRAINER
15- - 0 0 16- - 0
2-WAY CONTROL VALVE 2-WAY CONTROL VALVE W/FIXED FLOW 2-WAY CONTROL VALVE W/ADJUST. FLOW
W/Y-STRAINER CONTROL & Y-STRAINER SETTER & Y-STRAINER
NOTES:
1. ALL DRAWINGS SUBJECT TO CHANGE WITHOUT 3. 1/4" BLEED LINE IS FURNISHED ON 2-PIPE
PRIOR NOTICE. COOL & HEAT AUTO CHANGEOVER SYSTEMS.
2. THIS DIAGRAM SHOWS COMPONENT POSITION 4. NON-CATALOGED VALVE PACKAGE. CONTACT
IN RELATION TO FLUID FLOW. ACTUAL VALVE FACTORY.
PACKAGE CONFIGURATION VARIES WITH UNIT
TYPE, HAND CONNECTION, AND PIPE SIZE.
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 9
FCU PIPING PACKAGES AVAILABILITY
LEGEND Available x
Not Available
BV Manual Ball Valve(s)
MS Add Memory Stop to One Ball Valve
2W CV 2-Way Control Valve
Y-STR Y Strainer
FC Fixed Flow Control
AFS Adjustable Flow Circuit Setter
PT Pressure/Temperature Test Port
Y CO Y Strainer with Cleanout
C/O B/L Changeover Bleed Line
(On 2-way piping packages, a bleed line is required to ensure water circulation when valve is
closed. Not required on 3-way piping packages).
10 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES
FC
2-WAY CONTROL VALVE 2-WAY CONTROL VALVE W/BALL VALVES, 2-WAY CONTROL VALVE W/BALL VALVES &
W/BALL VALVES ADD MEMORY STOP FIXED FLOW CONTROL
CODE - 26 M
CODE - 27 M
CODE - 28 M
FC
2-WAY CONTROL VALVE W/BALL 2-WAY CONTROL VALVE 2-WAY CONTROL VALVE W/BALL VALVES,
VALVES & Y-STRAINER W/BALL VALVES, ADD MEMORY FIXED FLOW CONTROL,
STOP, & Y-STRAINER & Y-STRAINER
26- - 0
27- - 0 28- -
CODE - 29 M
CODE - 30 M
CODE - 31 M
FC
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 11
FCU PIPING PACKAGES AVAILABILITY
LEGEND Available x
Not Available
BV Manual Ball Valve(s) FC Fixed Flow Control
MS Add Memory Stop AFS Adjustable Flow Circuit Setter
to One Ball Valve PT Pressure/Temperature Test Port
3W CV 3-Way Control Valve Y CO Y Strainer with Cleanout
Y-STR Y Strainer
12 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES
M
FC
M
COIL COIL COIL
3-WAY CONTROL VALVE 3-WAY CONTROL VALVE W/BALL VALVES, 3-WAY CONTROL VALVE W/BALL VALVES &
W/BALL VALVES ADD MEMORY STOP FIXED FLOW CONTROL
FC
M
M
M
COIL COIL COIL
3-WAY CONTROL VALVE W/BALL 3-WAY CONTROL VALVE W/BALL VALVES, ADD 3-WAY CONTROL VALVE W/BALL VALVES, FIXED
VALVES & Y-STRAINER MEMORY STOP & Y-STRAINER FLOW CONTROL, & Y-STRAINER
CODE - 41 CODE - 42
M
M
COIL COIL
3-WAY CONTROL VALVE, W/BALL VALVE 3-WAY CONTROL VALVE W/BALL VALVES,
& ADJUST. FLOW SETTER ADJUST. FLOW SETTER, & Y-STRAINER
41- - 0 0 42- - 0
(3) (3)
CODE - 43 CODE - 44 (3) CODE - 45
FC
M
M
COIL COIL COIL
3-WAY CONTROL 3-WAY CONTROL VALVE W/FIXED 3-WAY CONTROL VALVE W/ADJUST.
VALVE ONLY FLOW CONTROL FLOW SETTER
FC
M
3-WAY CONTROL VALVE ONLY 3-WAY CONTROL VALVE W/FIXED FLOW 3-WAY CONTROL VALVE W/ADJUST.
W/Y-STRAINER CONTROL & Y-STRAINER FLOW SETTER & Y-STRAINER
NOTES:
1. ALL DRAWINGS SUBJECT TO CHANGE WITHOUT 3. NON-CATALOGED VALVE PACKAGE. CONTACT
PRIOR NOTICE. FACTORY.
2. THIS DIAGRAM SHOWS COMPONENT POSITION
IN RELATION TO FLUID FLOW. ACTUAL VALVE
PACKAGE CONFIGURATION VARIES WITH UNIT
TYPE, HAND CONNECTION, AND PIPE SIZE.
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 13
FCU PIPING PACKAGES AVAILABILITY
14 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES
M
COIL COIL
49- - 0 0 50- - 0 0
CODE - 51 CODE - 52
M
M
COIL COIL
51- - 0 52- - 0
M
COIL COIL COIL
3-WAY CONTROL VALVE W/BALANCE VALVE IN 3-WAY CONTROL VALVE W/BALANCE VALVE 3-WAY CONTROL VALVE W/BALANCE VALVE IN
BYPASS, ONE BALL VALVE, IN BYPASS, ONE BALL VALVE, BYPASS, TWO BALL VALVES
& ADJUST. FLOW SETTER ADJUST. FLOW SETTER, & Y-STRAINER & ADJUST. FLOW SETTER
COIL COIL
56- - 0 0 57- - 0
COIL COIL
3-WAY CONTROL VALVE W/BALANCE VALVE IN 3-WAY CONTROL VALVE W/BALANCE VALVE IN BYPASS,
BYPASS & ADJUST. FLOW SETTER ADJUST. FLOW SETTER, & Y-STRAINER
58- - 0 0 59- - 0
NOTES:
1. ALL DRAWINGS SUBJECT TO CHANGE WITHOUT 3. NON-CATALOGED VALVE PACKAGE. CONTACT
PRIOR NOTICE. FACTORY.
2. THIS DIAGRAM SHOWS COMPONENT POSITION
IN RELATION TO FLUID FLOW. ACTUAL VALVE
PACKAGE CONFIGURATION VARIES WITH UNIT
TYPE, HAND CONNECTION, AND PIPE SIZE.
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 15
FCU PIPING PACKAGES GLOSSARY
NOTE: Photos are for representation purposes only. Vendors and models subject to change without notice.
16 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
GLOSSARY FCU PIPING PACKAGES
NOTE: Photos are for representation purposes only. Vendors and models subject to change without notice.
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 17
FCU PIPING PACKAGES GLOSSARY
NOTE: Photos are for representation purposes only. Vendors and models subject to change without notice.
Balancing Fitting
A plug type valve designed to balance the waterside of
the fan coil to ensure proper flow through the bypass cir-
cuit of a 3-way control valve. Manual adjustment is required.
No calibration is provided at the valve.
Unions
A fitting used to provide a means of quickly disconnect-
ing and re-connecting valve packages or field piping from
a unit. The large nut on the union can be unscrewed and
the piping can be separated without cutting the pipe or
unsoldering a joint. When ordered, unions are installed
at the coil on the VF and HL Series Fan Coils. Unions are
not mounted on the VH Series Fan Coil.
Y Strainer
Designed to allow water to flow through a built in screen
to filter debris or contaminates from the water system.
With the water system isolated, the plug can be removed
from the blowdown leg of the strainer and the captured
debris removed from the screen. After the plug is
replaced, the system can be put back in operation and
the strainer will continue to filter the units water.
Nominal Size: " & "
Body Material: Bronze
Connection: Sweat
Pressure Rating (psig): 200
Temp. Rating, F: 150
Screen: 20 Mesh Stainless Steel
18 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
GLOSSARY FCU PIPING PACKAGES
NOTE: Photos are for representation purposes only. Vendors and models subject to change without notice.
Optional Pressure/Temperature
Test Port Locations
Designed to allow testing of water pressure, differential
pressure or water temperature without interrupting the
waterside operation of the Fan Coil Unit. Sensor probes
(1/8") are not included.
Aqua Thermostat
Also called an Automatic Seasonal Changeover Switch.
The Aquastat is a line or low voltage changeover switch
designed to switch a thermostat from heating to
cooling based on a change in supply water temperature.
Can be mounted on " or " copper tube. Switching
action is SPDT.
Specifications: Switch on temperature rise, 85 (6)
Switch on temperature fall, 70 (6)
Current Rating:
- 5.8 FLA, 34.8 LRA (inductive); 10 amps (resistive) at 120VAC
- 2.9 FLA, 17.4 LRA (inductive); 5 amps (resistive) at 240VAC
- 3.6 FLA, 21.6 LRA (inductive); 1 amps (resistive) at 277VAC
Agency Approval: UL Listed, CSA Approved
2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 19
Research & Development,
Engineering, and Manufacturing.
6750 Bryan Dairy Rd. Largo, FL 33777 Variable Volume Terminals
www.enviro-tec.com Fan Coil Units
727-541-3531 Air Handling Units
2001 Environmental Technologies, Inc. Blower Coil Units
Stock ID: CAT-FCU-PIPING Grilles, Registers and Diffusers, & Fire Dampers
April, 2001 Part No. PX-00-0018 Electronic Controls