Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Fcu Piping

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20
At a glance
Powered by AI
The document describes piping components and diagrams for fan coil units.

The document describes components like control valves, ball valves, unions, strainers, test ports and more.

Unions are used to provide a means of quickly disconnecting and reconnecting piping without cutting or unsoldering joints.

For Models

HL, VF and VH
Fan Coil Units
FCU PIPING PACKAGES CONTENTS

ITEM PAGE

VALVE / PIPING PACKAGE CODE DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

PIPING PACKAGE FEATURES AND OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

ISOLATION VALVE ONLY PACKAGES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2-WAY CONTROL DIAGRAMS


Model HL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Models VF and VH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

3-WAY CONTROL DIAGRAMS Models HL, VF and VH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

3-WAY CONTROL (with Balance Valve in Bypass) DIAGRAMS


Models HL, VF and VH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

GLOSSARY (Component Descriptions and Specifications)


Manual Ball Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Memory Stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Typical 2-Way Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Typical 3-Way Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Automatic Fixed Flow Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Manual Circuit Setter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Balancing Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Unions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Y Strainer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Y Strainer with Cleanout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Optional Pressure/Temperature Test Port Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Aqua-Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Drawings in this catalog are subject to change without notice.


Visit the ENVIRO-TEC website at www.enviro-tec.com for current submittal drawings.

2 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DESCRIPTIONS FCU PIPING PACKAGES

VALVE / PIPING PACKAGE CODE DESCRIPTIONS

## L 0 1 0 A 0
Package Package Union PT Port Y Strainer Actuator Flow
Number Size Option Option + Cleanout Voltage Rate1

01 to 59 L = 1/2" 0=None 0=None 0=None 0= None 0 = None


H = /4"
3
1= Yes 1= Yes 1=Yes A= 24VAC A = 0.5
B= 120VAC B = 1.0
C= 208VAC C = 1.5
D= 230VAC D = 2.0
E= 277VAC E = 2.5
F = 3.0
G = 3.5
H = 4.0
J = 5.0
K = 6.0
L = 7.0
M= 8.0
N = 9.0
P = 10.0
Q = 11.0
R = 12.0

1. Flow Rate code required for fixed flow control regulator only.
2. Valve packages ship loose on all models except VH.
3. Some unit models and installations may require field piping to connect valve package to coil inlet and outlet.
4. Do not install valve package with control valve actuator below horizontal plane.
5. Valve package assembly length may extend beyond factory auxiliary drip pan.
6. Some valve package components may interfere with factory auxiliary drip pan.
7. Some valve packages may require field furnished and installed insulation.
8. 2-Way control valve may be located in the outlet piping on some models.

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 3
FCU PIPING PACKAGES DESCRIPTIONS

GENERAL NOTES

Control valves are piped normally closed to the coil as standard.


3-way valves are installed as mixing valves as standard.
Transformer option required with 24 volt control valves unless field furnished.
Memory stop serves as a balancing valve and is provided as an attachment to one of the ball stop iso-
lation valves in the piping package.
Unions are installed at the water coil.
P/T test ports are located in the piping package to monitor pressure and temperature across the coil.
Automatic fixed flow control increments are as follows: 0.5 to 4.0 GPM - 0.5 GPM; 5.0 to 9.0 GPM -
1.0 GPM. Specify GPM when ordering.
Maximum close-off pressure for 2-way control valves is 30 PSI, 3-way is 13 PSI. Contact factory when
higher close-off pressures are required.
A piping package diagram or detail must be submitted if accessories are required in locations other
than indicated in the notes above. Additional engineering charges will apply and in some cases, alter-
nate piping accessory locations may not be available due to dimensional or application constraints.
See Valve Piping Package catalog (Stock ID CAT-FCU-PIPING). Contact factory for special pricing and
authorization number prior to quoting.

VH Notes
A minimum of a manual piping package per coil is required on all VH units.
Some restrictions may apply to the Y strainer with cleanout. Contact factory prior to quoting.

VF and HL Notes
Piping packages are factory assembled and shipped loose for field installation to the fan coil unit.
Piping packages are not available on DX or steam coils.
Recommended water flow for 1/2" piping packages is 6.0 GPM with 25 PSIG close-off pressure maxi-
mum; 3/4" is 12.5 GPM and 10 PSIG maximum. If water flow exceeds 12.5 GPM, contact factory for
special pricing.
208/230/277 volt piping packages have extended lead times. Contact factory for ship cycle.
Circuit setter is designed for full shut-off and replaces one ball stop isolation valve.
Y strainer not available on Model HLE horizontal cabinet, or with auxiliary drip pans.

4 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES
PIPING PACKAGE FEATURES AND OPTIONS

COIL COIL
M

TYPICAL 2-WAY CONTROL VALVE OPTIONAL UNION


PACKAGE WITH 1/4" BLEED BYPASS TYPICAL LOCATION
LINE AND AQUA-THERMOSTAT
M

COIL COIL
M

OPTIONAL PRESSURE-
TYPICAL 3-WAY CONTROL VALVE TEMPERATURE TEST
PACKAGE WITH AQUA-THERMOSTAT PORTS TYPICAL AT
COIL INLET AND OUTLET

COIL

OPTIONAL Y-STRAINER
WITH CLEANOUT

NOTES: 3. 1/4" BLEED LINE IS FURNISHED ON 2-PIPE


1. ALL DRAWINGS SUBJECT TO CHANGE WITHOUT COOL & HEAT AUTO CHANGEOVER SYSTEMS.
PRIOR NOTICE.
2. THIS DIAGRAM SHOWS COMPONENT POSITION
IN RELATION TO FLUID FLOW. ACTUAL VALVE
PACKAGE CONFIGURATION VARIES WITH UNIT
TYPE, HAND CONNECTION, AND PIPE SIZE.

LEGEND:

Y-STRAINER Y-STRAINER W/CLEANOUT UNION

M
3-WAY CONTROL VALVE MAN. BALL VALVE W/MEM STOP ADJUST. FLOW SETTER

M
2-WAY CONTROL VALVE FIXED FLOW CONTROL VALVE FC PRESSURE-TEMPERATURE
TEST PORT

MANUAL BALL VALVE BALANCE VALVE AQUA-THERMOSTAT

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 5
FCU PIPING PACKAGES AVAILABILITY

MANUAL PIPING PACKAGES


PACKAGE COMPONENTS OPTIONS PRODUCTS
CODE BV MS Y-STR FC AFS UNION PT Y CO HLF/HLP HLE VF VH
01 x x x x x x x
02 x x x x x x x x
03 x x x x x x x
04 x x x x x x x x
05 x x x x x x x x
06 x x x x x x x
07 x x x x x x x x
08 x x x x x x x

LEGEND Available x
Not Available
BV Manual Ball Valve(s)
MS Add Memory Stop to One Ball Valve
Y-STR Y Strainer
FC Fixed Flow Control
AFS Adjustable Flow Circuit Setter
PT Pressure/Temperature Test Port
Y CO Y Strainer with Cleanout

6 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES

MANUAL BALL VALVES ONLY

CODE - 01 CODE - 02

COIL COIL

TWO BALL VALVES TWO BALL VALVES ADD MEM. STOP

01- - 000 02- - 000

CODE - 03 CODE - 04

COIL COIL

TWO BALL VALVES ADD MEM. STOP


TWO BALL VALVES Y-STRAINER
& Y-STRAINER

03- - 00 04- - 00

CODE - 05 CODE - 06
FC

COIL COIL

TWO BALL VALVES & FIXED FLOW CONTROL ONE BALL VALVE & ADJUST. FLOW SETTER

05- - 00 06- - 000

CODE - 07 CODE - 08
FC

COIL COIL

TWO BALL VALVES, FIXED FLOW CONTROL, ONE BALL VALVE, ADJUST. FLOW SETTER,
& Y-STRAINER & Y-STRAINER

07- - 0 08- - 00

NOTES:
1. All drawings subject to change without prior
notice.
2. This diagram shows component position in
relation to fluid flow. Actual valve package
configuration varies with unit type, hand
connection, and pipe size.

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 7
FCU PIPING PACKAGES AVAILABILITY

2-WAY PIPING PACKAGES HL


PACKAGE COMPONENTS OPTIONS PRODUCTS
CODE BV MS 2W CV Y-STR FC AFS UNION PT Y CO C/O B/L HLF/HLP HLE VF VH
09 x x x x x x x
10 x x x x x x x x
11 x x x x x x x x
12 x x x x x x x x
13 x x x x x x x x x
14 x x x x x x x x x
15 x x x x x x x
16 x x x x x x x x
NON-CATALOGUED PACKAGES (Contact Factory)
17 x x x x x x
18 x x x x x x x
19 x x x x x x
20 x x x x x x x
21 x x x x x x x x
22 x x x x x x x

LEGEND Available x
Not Available
BV Manual Ball Valve(s)
MS Add Memory Stop to One Ball Valve
2W CV 2-Way Control Valve
Y-STR Y Strainer
FC Fixed Flow Control
AFS Adjustable Flow Circuit Setter
PT Pressure/Temperature Test Port
Y CO Y Strainer with Cleanout
C/O B/L Changeover Bleed Line
(On 2-way piping packages, a bleed line is required to ensure water circulation when valve is
closed. Not required on 3-way piping packages).

8 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES

2-WAY CONTROL VALVE MODEL HL


CODE - 09 CODE - 10 CODE - 11
FC

COIL M COIL M COIL M

2-WAY CONTROL VALVE 2-WAY CONTROL VALVE W/BALL VALVES, 2-WAY CONTROL VALVE W/BALL VALVES &
W/BALL VALVES ADD MEMORY STOP FIXED FLOW CONTROL

09- - 0 0 10- - 0 0 11- - 0

CODE - 12 CODE - 13 CODE - 14


FC

COIL M COIL M COIL M

2-WAY CONTROL VALVE W/BALL VALVES, 2-WAY CONTROL VALVE W/BALL VALVES,
2-WAY CONTROL VALVE W/BALL
ADD MEMORY STOP, FIXED FLOW
VALVES & Y-STRAINER
& Y-STRAINER CONTROL, & Y-STRAINER

12- - 0 13- - 0 14- -

CODE - 15 CODE - 16

COIL M COIL M

2-WAY CONTROL VALVE W/BALL VALVE & 2-WAY CONTROL VALVE W/BALL VALVE,
ADJUST. FLOW SETTER ADJUST. FLOW SETTER, & Y-STRAINER

15- - 0 0 16- - 0

CODE - 17(4) CODE - 18(4) CODE - 19(4)


FC

COIL M COIL M COIL M

2-WAY CONTROL VALVE W/FIXED 2-WAY CONTROL VALVE W/ADJUST.


2-WAY CONTROL VALVE ONLY
FLOW CONTROL FLOW SETTER

17- - 0 0 18- - 0 19- - 0 0

(4) (4) (4)


CODE - 20 CODE - 21 CODE - 22
FC

COIL M COIL M COIL M

2-WAY CONTROL VALVE 2-WAY CONTROL VALVE W/FIXED FLOW 2-WAY CONTROL VALVE W/ADJUST. FLOW
W/Y-STRAINER CONTROL & Y-STRAINER SETTER & Y-STRAINER

20- - 0 21- - 22- - 0

NOTES:
1. ALL DRAWINGS SUBJECT TO CHANGE WITHOUT 3. 1/4" BLEED LINE IS FURNISHED ON 2-PIPE
PRIOR NOTICE. COOL & HEAT AUTO CHANGEOVER SYSTEMS.
2. THIS DIAGRAM SHOWS COMPONENT POSITION 4. NON-CATALOGED VALVE PACKAGE. CONTACT
IN RELATION TO FLUID FLOW. ACTUAL VALVE FACTORY.
PACKAGE CONFIGURATION VARIES WITH UNIT
TYPE, HAND CONNECTION, AND PIPE SIZE.

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 9
FCU PIPING PACKAGES AVAILABILITY

2-WAY PIPING PACKAGES VF & VH


PACKAGE COMPONENTS OPTIONS PRODUCTS
CODE BV MS 2W CV Y-STR FC AFS UNION PT Y CO C/O B/L HLF/HLP HLE VF VH
23 x x x x x x x
24 x x x x x x x x
25 x x x x x x x x
26 x x x x x x x x
27 x x x x x x x x x
28 x x x x x x x x x
29 x x x x x x
30 x x x x x x
31 x x x x x x x x
NON-CATALOGUED PACKAGES (Contact Factory)
32 x x x x x
33 x x x x x
34 x x x x x x

LEGEND Available x
Not Available
BV Manual Ball Valve(s)
MS Add Memory Stop to One Ball Valve
2W CV 2-Way Control Valve
Y-STR Y Strainer
FC Fixed Flow Control
AFS Adjustable Flow Circuit Setter
PT Pressure/Temperature Test Port
Y CO Y Strainer with Cleanout
C/O B/L Changeover Bleed Line
(On 2-way piping packages, a bleed line is required to ensure water circulation when valve is
closed. Not required on 3-way piping packages).

10 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES

2-WAY CONTROL VALVE MODELS VF & VH


CODE - 23 M
CODE - 24 M
CODE - 25 M

FC

COIL COIL COIL

2-WAY CONTROL VALVE 2-WAY CONTROL VALVE W/BALL VALVES, 2-WAY CONTROL VALVE W/BALL VALVES &
W/BALL VALVES ADD MEMORY STOP FIXED FLOW CONTROL

23- - 0 0 24- - 0 0 25- - 0

CODE - 26 M
CODE - 27 M
CODE - 28 M

FC

COIL COIL COIL

2-WAY CONTROL VALVE W/BALL 2-WAY CONTROL VALVE 2-WAY CONTROL VALVE W/BALL VALVES,
VALVES & Y-STRAINER W/BALL VALVES, ADD MEMORY FIXED FLOW CONTROL,
STOP, & Y-STRAINER & Y-STRAINER
26- - 0
27- - 0 28- -

CODE - 29 M
CODE - 30 M
CODE - 31 M

COIL COIL COIL

2-WAY CONTROL VALVE W/BALL VALVES,


2-WAY CONTROL VALVE W/BALL 2-WAY CONTROL VALVE W/BALL VALVES & ADJUST. FLOW SETTER,
VALVE & ADJUST. FLOW SETTER ADJUST. FLOW SETTER & Y-STRAINER

29- - 0 0 30- - 0 0 31- - 0


(MODEL "VF" ONLY) (MODEL "VH" ONLY)

(4) (4) (4)


CODE - 32 CODE - 33 CODE - 34
M M M

FC

COIL COIL COIL

2-WAY CONTROL VALVE & 2-WAY CONTROL VALVE W/FIXED


2-WAY CONTROL VALVE ONLY
ADJUST. FLOW SETTER FLOW CONTROL

32- - 0 0 33- - 0 0 34- - 0

NOTES: 3. 1/4" BLEED LINE IS FURNISHED ON 2-PIPE


1. ALL DRAWINGS SUBJECT TO CHANGE WITHOUT COOL & HEAT AUTO CHANGEOVER SYSTEMS.
PRIOR NOTICE.
2. THIS DIAGRAM SHOWS COMPONENT POSITION 4. NON-CATALOGED VALVE PACKAGE. CONTACT
IN RELATION TO FLUID FLOW. ACTUAL VALVE FACTORY.
PACKAGE CONFIGURATION VARIES WITH UNIT
TYPE, HAND CONNECTION, AND PIPE SIZE.

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 11
FCU PIPING PACKAGES AVAILABILITY

3-WAY PIPING PACKAGES


PACKAGE COMPONENTS OPTIONS PRODUCTS
CODE BV MS 3W CV Y-STR FC AFS UNION PT Y CO HLF/HLP HLE VF VH
35 x x x x x x x x
36 x x x x x x x x x
37 x x x x x x x x x
38 x x x x x x x x
39 x x x x x x x x x
40 x x x x x x x x x
41 x x x x x x x x
42 x x x x x x x x
NON-CATALOGUED PACKAGES (Contact Factory)
43 x x x x x x
44 x x x x x x x
45 x x x x x x
46 x x x x x x
47 x x x x x x x
48 x x x x x x

LEGEND Available x
Not Available
BV Manual Ball Valve(s) FC Fixed Flow Control
MS Add Memory Stop AFS Adjustable Flow Circuit Setter
to One Ball Valve PT Pressure/Temperature Test Port
3W CV 3-Way Control Valve Y CO Y Strainer with Cleanout
Y-STR Y Strainer

12 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES

3-WAY CONTROL VALVE MODELS HL, VF & VH


CODE - 35 CODE - 36 CODE - 37

M
FC

M
COIL COIL COIL

3-WAY CONTROL VALVE 3-WAY CONTROL VALVE W/BALL VALVES, 3-WAY CONTROL VALVE W/BALL VALVES &
W/BALL VALVES ADD MEMORY STOP FIXED FLOW CONTROL

35- - 0 0 36- - 0 0 37- - 0

CODE - 38 CODE - 39 CODE - 40

FC

M
M

M
COIL COIL COIL

3-WAY CONTROL VALVE W/BALL 3-WAY CONTROL VALVE W/BALL VALVES, ADD 3-WAY CONTROL VALVE W/BALL VALVES, FIXED
VALVES & Y-STRAINER MEMORY STOP & Y-STRAINER FLOW CONTROL, & Y-STRAINER

38- - 0 39- - 0 40- -

CODE - 41 CODE - 42
M

M
COIL COIL

3-WAY CONTROL VALVE, W/BALL VALVE 3-WAY CONTROL VALVE W/BALL VALVES,
& ADJUST. FLOW SETTER ADJUST. FLOW SETTER, & Y-STRAINER

41- - 0 0 42- - 0

(3) (3)
CODE - 43 CODE - 44 (3) CODE - 45

FC
M

M
COIL COIL COIL

3-WAY CONTROL 3-WAY CONTROL VALVE W/FIXED 3-WAY CONTROL VALVE W/ADJUST.
VALVE ONLY FLOW CONTROL FLOW SETTER

43- - 0 0 44- - 0 45- - 0 0

(3) (3) (3)


CODE - 46 CODE - 47 CODE - 48

FC
M

COIL COIL COIL

3-WAY CONTROL VALVE ONLY 3-WAY CONTROL VALVE W/FIXED FLOW 3-WAY CONTROL VALVE W/ADJUST.
W/Y-STRAINER CONTROL & Y-STRAINER FLOW SETTER & Y-STRAINER

46- - 0 47- - 48- - 0

NOTES:
1. ALL DRAWINGS SUBJECT TO CHANGE WITHOUT 3. NON-CATALOGED VALVE PACKAGE. CONTACT
PRIOR NOTICE. FACTORY.
2. THIS DIAGRAM SHOWS COMPONENT POSITION
IN RELATION TO FLUID FLOW. ACTUAL VALVE
PACKAGE CONFIGURATION VARIES WITH UNIT
TYPE, HAND CONNECTION, AND PIPE SIZE.

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 13
FCU PIPING PACKAGES AVAILABILITY

3-WAY PIPING PACKAGE WITH BALANCE BYPASS VALVE


PACKAGE COMPONENTS OPTIONS PRODUCTS
CODE BV MS 3W CV BPBV Y-STR FC AFS UNION PT Y CO HLF/HLP HLE VF VH
49 x x x x x x x x x
50 x x x x x x x x x x
51 x x x x x x x x x
52 x x x x x x x x x x
53 x x x x x x x x
54 x x x x x x x x
55 x x x x x x
NON-CATALOGUED PACKAGES (Contact Factory)
56 x x x x x x x
57 x x x x x x x
58 x x x x x x x
59 x x x x x x x
LEGEND Available x
Not Available
BV Manual Ball Valve(s) Y-STR Y Strainer
MS Add Memory Stop FC Fixed Flow Control
to One Ball Valve AFS Adjustable Flow Circuit Setter
3W CV 3-Way Control Valve PT Pressure/Temperature Test Port
BPBV Bypass Balance Valve Y CO Y Strainer with Cleanout

14 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
DIAGRAMS FCU PIPING PACKAGES

3-WAY CONTROL VALVE WITH BALANCE BYPASS VALVE


MODELS HL, VF & VH
CODE - 49 CODE - 50

M
COIL COIL

3-WAY CONTROL VALVE W/BALANCE


3-WAY CONTROL VALVE W/BALANCE VALVE IN
VALVE IN BYPASS & TWO BALL
BYPASS & TWO BALL VALVES
VALVES, ADD MEMORY STOP

49- - 0 0 50- - 0 0

CODE - 51 CODE - 52
M

M
COIL COIL

3-WAY CONTROL VALVE W/BALANCE VALVE IN BYPASS,


3-WAY CONTROL VALVE W/BALANCE VALVE IN
TWO BALL VALVES, ADD MEMORY STOP,
BYPASS, TWO BALL VALVES, & Y-STRAINER
& Y-STRAINER

51- - 0 52- - 0

CODE - 53 CODE - 54 CODE - 55


M

M
COIL COIL COIL

3-WAY CONTROL VALVE W/BALANCE VALVE IN 3-WAY CONTROL VALVE W/BALANCE VALVE 3-WAY CONTROL VALVE W/BALANCE VALVE IN
BYPASS, ONE BALL VALVE, IN BYPASS, ONE BALL VALVE, BYPASS, TWO BALL VALVES
& ADJUST. FLOW SETTER ADJUST. FLOW SETTER, & Y-STRAINER & ADJUST. FLOW SETTER

53- - 0 0 54- - 0 55- - 0 0

CODE - 56 (3) CODE - 57 (3)


M

COIL COIL

3-WAY CONTROL VALVE W/BALANCE 3-WAY CONTROL VALVE W/BALANCE


VALVE IN BYPASS VALVE IN BYPASS & Y-STRAINER

56- - 0 0 57- - 0

CODE - 58 (3) CODE - 59 (3)


M

COIL COIL

3-WAY CONTROL VALVE W/BALANCE VALVE IN 3-WAY CONTROL VALVE W/BALANCE VALVE IN BYPASS,
BYPASS & ADJUST. FLOW SETTER ADJUST. FLOW SETTER, & Y-STRAINER

58- - 0 0 59- - 0

NOTES:
1. ALL DRAWINGS SUBJECT TO CHANGE WITHOUT 3. NON-CATALOGED VALVE PACKAGE. CONTACT
PRIOR NOTICE. FACTORY.
2. THIS DIAGRAM SHOWS COMPONENT POSITION
IN RELATION TO FLUID FLOW. ACTUAL VALVE
PACKAGE CONFIGURATION VARIES WITH UNIT
TYPE, HAND CONNECTION, AND PIPE SIZE.

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 15
FCU PIPING PACKAGES GLOSSARY
NOTE: Photos are for representation purposes only. Vendors and models subject to change without notice.

Manual Ball Valve


A full port forged brass ball valve used to isolate the Fan
Coil Unit and/or associated piping. The valve requires man-
ual operation.

Nominal Size: " "


Body Material: Brass Brass
Ball: Hard Chrome Hard Chrome
Plated Plated
Seats: Teflon Teflon
Stem Seal: (2) Viton O-Rings (2) Viton O-Rings
Connection: Sweat Sweat
Pressure Rating (psig): 600 600
Temp. Rating, F: 325 325
Cv: 21 42

Manual Ball Valve With Memory Stop


An adjustable stop position lever to limit travel of the On/Off
handle. This allows the ball valve to be closed, and returned
to the balance setting position without re-testing the
system.

(See above ratings).

Typical 2-Way Control Valve


A 2-position water control valve driven open or closed upon
a call for heating or cooling to maintain space tempera-
ture. In open position, water can flow through the Fan
Coil Units water coil to heat or cool the space depend-
ing on supply water temperature. In closed position, water
cannot flow through the water coil. Control valves are
piped normally closed to the coil as standard. Valve actu-
ators can be line or low (24VAC) voltage.
Nominal Size: " 2-Way " 2-Way
Body Material: Brass Brass
Connection: Sweat Sweat
Pressure Rating (psig): 300 300
Temp. Rating, F: 200 200
Cv: 2.5 5.0
Max. Close-off Press. (psig): 30 13
Power Consumption: 7VA 7VA

16 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
GLOSSARY FCU PIPING PACKAGES
NOTE: Photos are for representation purposes only. Vendors and models subject to change without notice.

Typical 3-Way Control Valve


A 2-position water control valve driven open or closed (bypass)
upon a call for heating or cooling to maintain space tempera-
ture. Energized, water can flow through the Fan Coil Units water
coil to heat or cool the space depending on the supply water
temperature. The bypass port is blocked. De-energized, water
cannot flow through the water coil but is forced to flow through
the bypass port, bypassing the coil. Control valves are piped
normally closed to the coil as standard (in full bypass). Valve
actuators can be line or low (24VAC) voltage.
Nominal Size: " 3-Way " 3-Way
Body Material: Brass Brass
Connection: Sweat Sweat
Pressure Rating (psig): 300 300
Temp. Rating, F: 200 200
Cv: 3.0 5.0
Max. Close-off Press. (psig): N/A N/A
Power Consumption: 7VA 7VA

Automatic Fixed Flow Control


A pressure compensated automatic fixed flow control device
designed to limit the GPM (gallons per minute) flow through
the Fan Coil Unit. Automatic fixed flow control increments
are: 0.5 to 4.0 GPM (in 0.5 GPM increments) and 5.0 to
20.0 GPM (in 1.0 GPM increments), 10%. Desired GPM
must be specified when ordering.

Nominal Size: " & "


Body Material: Copper
Connection: Sweat
Pressure Rating (psig): 500
Temp. Rating, F: 225
Cv: Variable With
Inlet Pressure

Manual Circuit Setter


A control fitting designed to allow maximum water flow
through the Fan Coil Unit in the Open (0%) position, and
as little as 10% of flow through the Fan Coil Unit in the
Closed (90%) position. Has a calibrated nameplate, built
in test ports and adjustable mechanical stops, and is suit-
able for positive shutoff.

Nominal Size: " & "


Body Material: Bronze
Connection: Sweat
Pressure Rating (psig): 300
Temp. Rating, F: 250
Cv: Variable

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 17
FCU PIPING PACKAGES GLOSSARY
NOTE: Photos are for representation purposes only. Vendors and models subject to change without notice.

Balancing Fitting
A plug type valve designed to balance the waterside of
the fan coil to ensure proper flow through the bypass cir-
cuit of a 3-way control valve. Manual adjustment is required.
No calibration is provided at the valve.

Nominal Size: " & "


Body Material: Bronze
Connection: Sweat
Pressure Rating (psig): 150
Temp. Rating, F: 200
Cv: Adjustable

Unions
A fitting used to provide a means of quickly disconnect-
ing and re-connecting valve packages or field piping from
a unit. The large nut on the union can be unscrewed and
the piping can be separated without cutting the pipe or
unsoldering a joint. When ordered, unions are installed
at the coil on the VF and HL Series Fan Coils. Unions are
not mounted on the VH Series Fan Coil.

Nominal Size: " & "


Body Material: Bronze/Copper
Connection: Sweat
Pressure Rating (psig): 125
Temp. Rating, F: 200

Y Strainer
Designed to allow water to flow through a built in screen
to filter debris or contaminates from the water system.
With the water system isolated, the plug can be removed
from the blowdown leg of the strainer and the captured
debris removed from the screen. After the plug is
replaced, the system can be put back in operation and
the strainer will continue to filter the units water.
Nominal Size: " & "
Body Material: Bronze
Connection: Sweat
Pressure Rating (psig): 200
Temp. Rating, F: 150
Screen: 20 Mesh Stainless Steel

18 Fan Coil Unit Valve Piping Packages April, 2001 2001 Environmental Technologies, Inc.
GLOSSARY FCU PIPING PACKAGES
NOTE: Photos are for representation purposes only. Vendors and models subject to change without notice.

Cleanout Valve for Y Strainer


A standard ball valve with a cleanout valve installed on
the strainer blowdown leg to allow flushing the strainer
screen without removing the plug in the blowdown leg.
This valve has a standard " garden hose connection to
allow fluid to be piped to a container or remote location
during cleaning.

Nominal Size: "


Body Material: Bronze
Connection: Sweat
Pressure Rating (psig): 125
Temp. Rating, F: 200

Optional Pressure/Temperature
Test Port Locations
Designed to allow testing of water pressure, differential
pressure or water temperature without interrupting the
waterside operation of the Fan Coil Unit. Sensor probes
(1/8") are not included.

Nominal Size: "


Body Material: Brass
Connection: Threaded
Pressure Rating (psig): 400
Temp. Rating, F: 250

Aqua Thermostat
Also called an Automatic Seasonal Changeover Switch.
The Aquastat is a line or low voltage changeover switch
designed to switch a thermostat from heating to
cooling based on a change in supply water temperature.
Can be mounted on " or " copper tube. Switching
action is SPDT.
Specifications: Switch on temperature rise, 85 (6)
Switch on temperature fall, 70 (6)
Current Rating:
- 5.8 FLA, 34.8 LRA (inductive); 10 amps (resistive) at 120VAC
- 2.9 FLA, 17.4 LRA (inductive); 5 amps (resistive) at 240VAC
- 3.6 FLA, 21.6 LRA (inductive); 1 amps (resistive) at 277VAC
Agency Approval: UL Listed, CSA Approved

Note: Specifications may vary.

2001 Environmental Technologies, Inc. April, 2001 Fan Coil Unit Valve Piping Packages 19
Research & Development,
Engineering, and Manufacturing.
6750 Bryan Dairy Rd. Largo, FL 33777 Variable Volume Terminals
www.enviro-tec.com Fan Coil Units
727-541-3531 Air Handling Units
2001 Environmental Technologies, Inc. Blower Coil Units
Stock ID: CAT-FCU-PIPING Grilles, Registers and Diffusers, & Fire Dampers
April, 2001 Part No. PX-00-0018 Electronic Controls

You might also like