Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Unit Planned Shutdown Operations

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 3

UNIT PLANNED SHUT DOWN PROCEEDURE

1. LOAD can be reduce by 3 ways:-


a. Fully manual ( up to 5% load)
b. Load may be reduced up to 60% under CMC mode,
then change over to either Press Control Mode or
Manual Mode.
c. Load may be reduced up to 40% under Pressure
Control Mode, then change over to Manual Mode.
d. CMC (up to 60% load then either Press. Control mode
or Manual mode)

2. At 60% Load can be carried out Auto Turbine Test (ATT)


to test its availability.
3. Reduce load up to 40% Load
.
Procedure of Cutting out a coal mills:-
Reduce coal feeder position to minimum
Stop coal feeder
Wait to stop mills, till its Amps drops to
minimum e.g. no load condition.
Stop mill motor & Close all dampers.

4. Change over Pressure Control Mode to Manual Load
Control Mode
5. Cut off HP Heaters
6. Change Over DEA Pegging Steam source from
Extraction to CRH.
7. Reduce coal feeding further & reduce Load accordingly
up to 20-25%.
8. MONITOR Scanners, If required Cut in Oil support to
avoid Flame failure Protection.
9. Cut out LPHs, Change Over UAT to Station Bus and
DEA Pegging Steam from CRH to APRDS.
10 FCS to Change Over from Hi range to Low range
.
11 Put HPLP Bypass in service
.
12 Reduce Fuel & Load.
.
13 Trip Turbine at 5% load (Gen Protection can be Tested).
.
..
i.
Ensure turbine ESVs & IVs, CRH NRVs,
Extraction NRVs &Block Valve Closed.
ii.
Trip Oil= Zero, Control oil = 4.8 kg/cm2
iii.
Gen Field Breaker OPEN
iv.
AOP start auto < 2950 rpm or < 4.8 kg/cm 2
oil pressure.
v.
JOP start auto < 510 rpm
vi.
Barring Gear valve open < 210 rpm

14 Ensure opening of the following drains:-
.
15 HP casing, Seal Steam Hdr, before ESVs & Extraction
. NRVs, after CRH NRVs, before / after IV valve NRVs
16 Stop turbine barring if casing / shaft temp < 1200 C
.
17 Stop CEP at CASING TEMP OF 1000 C
.
18 Shutdown Oil System at 80 0C to 90 0C
.

Generator Side Shutdown Operations

1. REDUCE MVAR with load


2. CHANGEOVER to station supply from UAT at 20% Load
3. ISOLATE hydrogen coolers after 15 to 20 minutes of
Gen tripping.
4. REDUCE Exciter controller to minimum.
5. Open Generator Breaker at 5% load.
6. STOP stator water pump ( If Stator Cooling System is
in service )
7. OPEN line isolators.
8. PURGE H2 by filling CO2 & purge the CO2 by filling dry
compressed Air

You might also like