ENERGY PERFORMANCE

POWER QUALITY
Transformers
& shunts
Measurement
and Instrumentation
Transformers and shunts
Overview of ranges p. 102
Selection guide p. 104
Info & advice p. 110
Standard industrial transformers p. 112
TCR TCRO TC CLIP ranges

Adaptable industrial transformers p. 123


JVR JVO JVP ranges

Transformers for energy metering p. 129


JVS JVO JVP TRI 500 TRI 700 ranges

Current summation p. 141


JVM 15 TCS ranges

Transformer short-circuit switch p. 143


PRTC range

Shunts p. 144
76-2 77-2 SHMI SHEL SHMO ranges

101
Overview of product ranges
Standard industrial transformers
> Measurement and instrumentation Current transformers (CTs) & shunts

TCR TCR
Wound primary Cable/busbar primary
> page 113 > page 114

TCR TCRO TC CLIP


Busbar primary Split core Split core
> page 117 > page 118 > page 121

Adaptable industrial transformers


JVR JVO
Wound primary Cable primary
> page 124 > page 125

JVO JVP
Cable/busbar primary Busbar primary
> page 126 > page 127

Transformers for energy metering


JVS JVS
Cable/busbar primary Busbar primary
> page 130 > page 132

102
ENERGY PERFORMANCE
Transformers for price metering

POWER QUALITY
Single-phase, single-rating Single-phase, multi-rating
JVP 1045B JVO 40-100 JVO 40-100S JVO 90-160S JVS 1145S
> page 134 > page 135 > page 136 > page 137 > page 138

Transformers
& shunts
Three-phase, single-rating Three-phase, multi-rating
TRI 500 TRI 700
> page 139 > page 140

Current summation Associated product


PRTC
JVM 15 TCS CT short-circuiting switch
> page 141 > page 142 > page 143

shunts
Class 0.5 Class 1
76/2 77/2 range SHMI range SHEL range
> page 145 > page 147 > page 149

SHMO range
DIN rail mounting
> page 150

103
Choosing your standard industrial
Choosing your adaptable industrial current transformer: page 112
Choosing your transformer for energy metering: page 114
> Measurement and instrumentation Current transformers (CTs)

TCR TCR
Wound primary Cable/busbar primary

> page 113 > page 114

TCR 10 TCR 11 TCR 15 TCR 21 TCR 31 TCR 41 TCR 51 TCR 61 TCR 71 TCR 75

Wound primary (threaded rod) aperture wire


M6
25 x 25 16 mm2
Cable primary (mm) 20 22 26 28 44 63
Busbar primary (mm)
15 x 10 20 x 12 20 x 20 20 x 25 50 x 30 50 x 50
20 x 10 25 x 11 25 x 12 30 x 15 60 x 12 60 x 37 3 x 100 x 10
25 x 5 30 x 10 30 x 10 40 x 10 80 x 30
Primary 5A
10 A
15 A
20 A
25 A
30 A
40 A
50 A
60 A
75 A
100 A
125 A
150 A
200 A
250 A
300 A
400 A
500 A
600 A
750 A
800 A
1000 A
1200 A
1500 A
2000 A
2500 A
3000 A
4000 A
5000 A
Strengths
Combining a high level of accuracy Come in a wide range of primaries.
and compact design. Mounting accessories supplied as standard.

5 A or 1 A secondary 5 A secondary as standard 5 A secondary only


as standard 1 A on request

104
ENERGY PERFORMANCE
current transformer

POWER QUALITY
TCR TCRO TC CLIP
Busbar primary Split core Split core

> page 117 > page 118 > page 121

Transformers
& shunts
TCR 80 TCR 90 TCR 100 TCRO 2030 TCRO 5080 TCRO 8080 TCRO 80120 TCRO 80160 TCC 241 TCC 242 TCC 364 TCC 366

24 24 36 36
100 x 20 100 x 30 1025 x 60 20 x 30 50 x 80 80 x 80 80 x 120 80 x 160

Implementation without disconnecting


Complete products for 100 and A wide range suitable for most primaries.
the power cables.
125mm busbar type. Installation without disconnecting busbars.
Compact format.

105
Choosing your adaptable industrial
Choosing your standard industrial current transformer: page 110
Choosing your transformer for energy metering: page 114
> Measurement and instrumentation Current transformers (CTs)

JVR JVO
Wound primary Cable primary

> page 124 > page 125

JVR 64 JVR 75 JVR 86 JVO 12-46 JVO 18-51 JVO 21-64 JVO 21-75 JVO 32-75 JVO 36-75 J3R 80 B

Wound primary (threaded rod)


M8 M8 - M10 M8 - M10
Cable primary (mm)
12 18 21 21 32 36 66
Busbar primary (mm)

Primary 5A
10 A
15 A
20 A
25 A
30 A
40 A
50 A
60 A
75 A
100 A
125 A
150 A
200 A
250 A
300 A
400 A
500 A
600 A
750 A
800 A
1000 A
1200 A
1250 A
1500 A
2000 A
2500 A
3000 A
Strengths Primary connection via threaded A wide choice of primaries.
rod for more compact size.

SPECIFIC PRODUCTS POSSIBLE IN THIS RANGE

5 A secondary as standard / 1 A on request

106
ENERGY PERFORMANCE
current transformer

POWER QUALITY
JVO JVP
Cable/busbar primary Busbar primary

> page 126 > page 127

Transformers
& shunts
JVO 25 CR JVO 32 CR JVP 624 JVP 1025 JVP 1045

32.5 x 10.5 40.5 x 10.5 65 x 22 105 x 22 105 x 42

JVO version for cable or busbar primary. A wide choice of busbars from 60 to 100 mm.

SPECIFIC PRODUCTS POSSIBLE IN THIS RANGE

107
Choosing your current transformer for
Choosing your standard industrial current transformer: page 104
Choosing your adaptable industrial current transformer: page 106
> Measurement and instrumentation Current transformers (CTs)

JVS JVS
Cable/busbar primary Busbar primary
> page 130 > page 132

JVS 25B JVS 26B JVS 30B JVS 38B JVS 39B JVS 40 JVS 50 JVS 60

Cable primary (mm)


26 28 44 63
Busbar primary (mm)
20 x 20 20 x 25 50 x 30 50 x 50 100 x 20 100 x 30 125 x 60
25 x 12 30 x 15 60 x 12 60 x 30 3 x 100 x 10
30 x 10 40 x 10 80 x 30
Primary 100 A
150 A
200 A
250 A
300 A
400 A
500 A
600 A
750 A
800 A
1000 A
1200 A
1500 A
2000 A
2500 A
3000 A
4000 A
5000 A
Strengths High-accuracy range with very low phase shift, ideal for electronic measurement instruments,
including energy metering

5 A secondary as standard 5 A secondary as standard with


individual test certificate

1 A secondary with individual test certificate on request

108
ENERGY PERFORMANCE
energy and price metering

POWER QUALITY
Single-phase Single-phase multi-rating Three-phase Three-phase multi-rating
single-rating single-rating
> pages 134-135 > pages 136-137-138 > page 139 > page 140

Transformers
& shunts
JVO JVS TRI 700
JVO 40-100S TRI 700 S TRI 700 S TRI 700 S
JVP 1045 B JVO 40-100 90-160 S 1145 S TRI 500 100-200-
bi-rating 50-100/5 A 100-200/5 A 200-500/5 A
tri-rating tri-rating 500/5 A
Accuracy class (according
0.5 0.5 0.2s 0.2s 0.2s 0.5 0.2s 0.2s 0.2s 0.5
to EN 600044-1)
Cable primary
42 mm 40 mm 90 mm 40 mm
(diameter in mm)
63 x 12
Busbar primary (mm) 100 x 40
100 x 12
Cable clamp
(section in mm) 22 to 240 mm2 50 to 240 mm2 50 to 240 mm2 50 to 240 mm2 50 to 240 mm2
50 A
100 A
150 A
Primary 200 A
(secondary 5 A) 300 A
500 A
1000 A
2000 A

109
Info & advice
> Measurement and instrumentation Current transformers (CTs) & shunts

TRANSFORMERS
Function
Current transformers power low-voltage measuring
instruments and isolate them from the network. They
supply their secondary winding with a standard current
proportional to the primary current. They are divided
into four main families:
- wound primaries;
- split-core primaries;
- cable primaries;
- busbar primaries. The transformers accuracy class can then be deduced
These transformers can be used with all types of measuring from the results obtained by referring to the table op-
instruments: posite (provided as an example):
ammeters, energy meters, power monitors, etc. - Class 3 for a CT with a ratio of 150/5
- Class 1 for a CT with a ratio of 200/5
How to choose a current transformer? - Class 0.5 for a CT with a ratio of 250/5
The choice is based on two main criteria:
Power (VA) on Class
- the current on the primary (transformation ratio Ip / 5 A); Primary 0.5 1 3
- the type of installation. 100 A - 1 1.5
In other words, the choice depends on the type of 125 A - 1 1.5
cable or busbar on the installation and the intensity of 150 A 1 1.75 2.5
the currents flowing through them. 200 A 1.5 2.75 3.75
250 A 2 3.25 3.75
300 A 2.5 3.25 4
Determining a CTs accuracy class 400 A
500 A
3
3.5
3.75
3.75
5
5
The accuracy class of a current transformer depends 600 A 3.75 5 7.5
on the transformers apparent power (VA) and the
consumption of the entire measurement line. It is the
result of the measurement errors of each element in
the line and must therefore be less than or equal to Accuracy limit tables according to
the accuracy class of the measuring instrument which the IEC 60044-1 standard
it supplies, particularly for energy metering where
accuracy has a direct impact on billing. For a given Limit errors Table 1
accuracy class, the measurement lines consumption Class Error (in %) depending on In (in %)
must not exceed the current transformers apparent 5 20 100 120
power (VA). 0.2 0.75 0.35 0.20 0.20
0.5 1.50 0.75 0.50 0.50
1 3.00 1.50 1.00 1.00
Example of measurement chain
consumption at 20 C Limit errors Table 2
Power dissipated per metre of line (2 ways) Class Error (in %) depending on In (in %)
1 5 20 100 120
Copper-wire section (mm) Secondary 5 A Secondary 1 A
0.2 S 0.75 0.35 0.20 0.20 0.20
1.5 0.61 0.025 VA 0.5 S 1.50 0.75 0.50 0.50 0.50
2.5 0.37 0.015 VA
4 0.23 0.009 VA
6 0.15 0.006 VA

Enerium 50 Power Monitor 0.15 VA


5 m of double 2.5 mm wire 0.37 x 5 = 1.85 VA
Measurement line consumption 0.15 + 1.85 = 2 VA

110
ENERGY PERFORMANCE
SELECTING A TRANSFORMER

POWER QUALITY
Enerdis current transformers offer 4 types of connection:

Transformers
WOUND PRIMARY CABLE PRIMARY BUSBAR PRIMARY SPLIT CORE PRIMARY

& shunts
for currents less than 200 A for currents between 40 and 2,500 A for currents between 750 and 5,000 A for easy connection to an existing installation
using a busbar or cable primary

Supply Use

CONNECTING YOUR CT S1 S2 Secondary

It is important to always install the transformer in P2/L:


installation
the right direction, especially on three-phase networks, side

so as not to invert the phase shift between the current


and the voltage on one or more of the phases.
P1/K: power supply side
Primary
SHUNTS
Shunts cause a standard voltage drop which can be processed by measuring
instruments. Although mainly used on DC currents, they can also be used
on AC currents.
Installing a shunt it is recommended not to go beyond 80% of the rated
current of the shunt and to ensure that its tempera-
Avoid overheating ture does not exceed 150C (heating plus ambient
A shunt emits heat that must be evacuated in order temperature). For high currents, forced convection
to maintain the accuracy class. Up to 100 A, heat is compulsory.
evacuation is by natural convection.
Beyond this, natural convection must be associated Limit derivation currents
with thermal dissipation in the conductors on which It is possible to connect one or more receivers to one
it is mounted. Natural convection is best achieved shunt as long as the derivation current or the sum of the
when the shunt is in the horizontal position, with the derivation current is relatively small compared to the
blades oriented vertically. nominal rating. You must take into account the addi-
Calculation of the heat evacuated is carried out by the tional voltage drop introduced by the length of the deri-
contractor, especially evacuation by linking bars (size, vation wires. The derivation current generally accepted
disposition, number). For use on direct currents, to remain in the accuracy class is 5 mA.

Financial impact of a TCs CT safety rules


FOCUS

accuracy class
For a consumption of 12,000 MWh/year and a cost of You must never open the secondary circuit of a CT supplied
e 0.10/kWh on the primary. The very high voltage created may cause
CT class 1: 120,000 kWh = e 12,000 bodily harm or irreparable damage to the transformer.
CT class 0.5: 60,000 kWh = e 6,000 Before working on the secondary of a CT, it must be short-
CT class 0.2S: 2,500 kWh = e 2,500 circuited.
This calculation takes into account neither the class of the When a CT is not in use (secondary open) the secondary must
measuring instruments, nor loss occurring on the network cables. be short-circuited before powering up the system.

111
TCR Range
CTs designed for submetering. Accuracy class 0.5/1/3
> Measurement and instrumentation Current transformers (CTs)

PRODUCT Outputs on split terminals


ADVANTAGES enabling short-circuiting of
the secondary current
(M4 or cage for 4 mm2 wire).
EXTENDED RANGE:
primary currents from
5 to 5,000 A and 5 A
or 1 A secondary currents

DIN RAIL MOUNTING:


on plate mounting or
fixed around busbars

COMPACT DESIGN

DIN rail mounting using Plate mounting using


Supplied with bar clamp
supplied clip-on adapters for removable
fitting accessories.
TCR 21 - 31 - 41 - 51. screw-on clips.

> General specifications


Reference standards: Operating conditions
EN 60044-1 (ex IEC 185) Temperature: -10C to +50C
Maximum network voltage: Relative humidity: < 90%
720 Vac Protection
Dielectric test voltage: Protection rating: IP 50
3 kV/50 Hz/1 min (terminal covers supplied)
Frequency response: 50/60 Hz Dry winding with self-extinguishing ABS
Short-circuit thermal current covering (UL 94VO)
(Ith): 60 In - 1 second
Dynamic current (Idyn): 2.5 Ith
Safety factor: < 5

> 3CT Mounting > Mounting accessories


B B E

Dimensions DIN rail Plate mounting Sealable terminal


Model A B C D E F G Model fittings fittings cover*
C

TCR 10 - - - - - - - TCR 10 1923 0021


TCR 11 - - - - - - -
Gmax
TCR 11 1923 0021
A TCR 15 D- - - - - - - TCR 15
TCR 21 176 59 32 143.6 85.6 98 25.6 TCR 21 1923 0022
B B E TCR 31 176 59 32 148.6 90.6 98 30.6 TCR 31 1923 0022
TCR 41 194 65 44 160.6 96.6 134 30.6 TCR 41 1923 0022
TCR 51 194 65 44 170.6 106.6 134 40.6 TCR 51 1923 0022
TCR 61 255.5 85.5 50 231.6 147.1 152 60.6 TCR 61 1923 0022
TCR 71 326 109 50 298.6 190.6 152 80.6 TCR 71 1923 0022
C

TCR 80 287 96 59 215 120 179 23 TCR 75 1923 0022


TCR 90 347 116 44 264 149 134 32 TCR 80
Gmax
A D TCR 100 374 125 44 310 186 134 60 TCR 90
TCR 100
Standard accessories *sold in pairs
112
ENERGY PERFORMANCE
TCR Wound primary

POWER QUALITY
75

TCR 10 TCR 11 TCR 15


43

25 x 25 mm aperture
104.5 M4 and M6 Primary: 16 mm2 wire
82
Secondary: 4 mm2 wire

10.5 10.5 75 40
40

Transformers
50 75
43 32
43 32 52.5 70

& shunts
75 134
108 M6 M4
43 M6 M4 20 48
32
104
104
82
82 PRIMARY
104.5
82

85

45
M10X25 10 5,5
10 5,5

P1 S1 SECONDARY
10.5 10.5 40 5.5 50 P1 S1
50 50 50 P2 S2
80 P2 S2 DIN 46277 (EN 50022)
134 FIXATION
108
50
32 50

Power (VA) class Weight Power (VA) class Weight Power (VA) class Weight
Primary 0.5 M10X25 1 3 (kg) Primary 1 (kg) Primary 0.5 1 3 (kg)
5 A 15 20 30 0.70 5 A 5 0.50 5 A 2.5 5 7 0.28
40
10 A 50 15 5.5 20 30 0.70 10 A 5 0.50 10 A 2.5 5 7 0.28
80
15 A 15 20 30 0.70 15 A 5 0.50 15 A 2.5 5 7 0.28
20 A 15 20 30 0.70 20 A 5 0.50 20 A 2.5 5 7 0.28
25 A 15 20 30 0.70 25 A 5 0.50 25 A 2.5 5 7 0.28
30 A 15 20 30 0.70 30 A 5 0.50 30 A 2.5 5 7 0.28
40 A 15 20 30 0.70 40 A 5 0.50 40 A 2.5 5 7 0.28
50 A 15 20 30 0.80 50 A 5 0.50 50 A 2.5 5 7 0.28
60 A 15 20 30 0.80 60 A 5 0.50
75 A 15 20 30 0.75
100 A 15 20 30 0.70
125 A 15 20 30 0.70
150 A 15 20 30 0.70

T O O R D E R

Primary Secondary 1 A Secondary 5 A Primary Secondary 1 A Secondary 5 A Primary Secondary 1 A Secondary 5 A


5 A 1921 1507 1920 1507 5 A 1921 1607 1920 1607 5 A 1921 1707 1920 1707
10 A 1921 1512 1920 1512 10 A 1921 1612 1920 1612 10 A 1921 1712 1920 1712
15 A 1921 1514 1920 1514 15 A 1921 1614 1920 1614 15 A 1921 1714 1920 1714
20 A 1921 1515 1920 1515 20 A 1921 1615 1920 1615 20 A 1921 1715 1920 1715
25 A 1921 1516 1920 1516 25 A 1921 1616 1920 1616 25 A 1921 1716 1920 1716
30 A 1921 1517 1920 1517 30 A 1921 1617 1920 1617 30 A 1921 1717 1920 1717
40 A 1921 1518 1920 1518 40 A 1921 1618 1920 1618 40 A 1921 1718 1920 1718
50 A 1921 1519 1920 1519 50 A 1921 1619 1920 1619 50 A 1921 1719 1920 1719
60 A 1921 1521 1920 1521 60 A 1921 1621 1920 1621
75 A 1921 1523 1920 1523
100 A 1920 1525
125 A 1920 1526
150 A 1920 1528

> Associated products PRTC


CT protection unit
Mounting
accessories

> page 143 > page 112

113
TCR Range
Cable/busbar primary
> Measurement and instrumentation Current transformers (CTs)

TCR 21 TCR 31 TCR 41


Cable 20 mm Cable 22 mm Cable 26 mm
Bar: 15 x 10 mm - 20 x 10 mm Bar: 20 x 12 mm - 25 x 11 mm Bar: 20 x 20 mm - 25 x 12 mm
25 x 5 mm 30 x 10 mm 30 x 10 mm

49 58 49 60.5
58 64
32 32 44

4.5
4.5
4.5

5.6
5.6

5.6
P2 P2
P2

48

48
80.5
S1 S2 S2
70

15.6

S1 S2

10.6

20.6
70
5.5

20.6
10.6

26
.3

3
P1 P1 P1
20

22.
29

34
29
2.5

2.5
39 39

2.5
58 49 60.5 46
49 64
58 25.6 32 30.6 59 44 30.6
32 59 71
4.5
4.5

5.6
5.6
5.6

P2 P2
P2
80.5

60
248

S2 S1 S2

10.6
48

20.6
S1 S2
6
15.6

70

20.6
10.6

P1
5.5

3
.3

P1 P1
22.
20

34
29

29

2.5
2.5

39 39 46
2.5

30.6
25.6 71
59 30.6 59

Power (VA) class Weight Power (VA) class Weight Power (VA) class Weight
Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
40 A - - 1.5 0.41 100 A - 1 1.5 0.53 100 A 1.75 3.75 7.5 0.53
50 A - - 3 0.42 125 A - 1 2 0.53 125 A 3.75 7.5 10 0.53
60 A - 1.25 3.5 0.43 150 A 1 2 2.5 0.53 150 A 5 7.5 10 0.53
75 A - 2 3.5 0.44 200 A 2.5 3 3.5 0.54 200 A 7.5 10 10 0.54
100 A 1.5 2.5 3.75 0.44 250 A 3.5 3.75 5 0.54 250 A 7.5 10 15 0.54
125 A 1.75 3.5 5 0.45 300 A 3.5 3.75 5 0.51 300 A 10 10 15 0.51
150 A 2.5 3.5 5 0.29 400 A 3.5 5 7.5 0.51 400 A 10 10 15 0.51
200 A 3.75 5 5 0.30 500 A 5 7.5 10 0.51 500 A 15 15 20 0.51
250 A 5 7.5 7.5 0.31 600 A 5 7.5 10 0.52 600 A 15 20 25 0.51

T O O R D E R

Primary Secondary 1 A Secondary 5 A Primary Secondary 1 A Secondary 5 A Primary Secondary 1 A Secondary 5 A


40 A 1921 2318B 1920 2318B 100 A 1921 2425B 1920 2425B 100 A 1921 2525B 1920 2525B
50 A 1921 2319B 1920 2319B 125 A 1921 2426B 1920 2426B 125 A 1921 2526B 1920 2526B
60 A 1921 2321B 1920 2321B 150 A 1921 2428B 1920 2428B 150 A 1921 2528B 1920 2528B
75 A 1921 2323B 1920 2323B 200 A 1921 2430B 1920 2430B 200 A 1921 2530B 1920 2530B
100 A 1921 2325B 1920 2325B 250 A 1921 2431B 1920 2431B 250 A 1921 2531B 1920 2531B
125 A 1921 2326B 1920 2326B 300 A 1921 2433B 1920 2433B 300 A 1921 2533B 1920 2533B
150 A 1921 2328B 1920 2328B 400 A 1921 2435B 1920 2435B 400 A 1921 2535B 1920 2535B
200 A 1921 2330B 1920 2330B 500 A 1921 2436B 1920 2436B 500 A 1921 2536B 1920 2536B
250 A 1921 2331B 1920 2331B 600 A 1921 2438B 1920 2438B 600 A 1921 2538B 1920 2538B

> Associated products PRTC


CT protection unit
Mounting
accessories

> page 143 > page 112

114
ENERGY PERFORMANCE
POWER QUALITY
TCR 51 TCR 61
Cable 28 mm Cable 44 mm
Bar: 20 x 25 mm - 30 x 15 mm Bar: 50 x 30 mm - 60 x 12 mm
40 x 10 mm

64 60.5 84.5 76

Transformers
44

4.5
50
4.5

& shunts
5.6

5.6
P2
60 P2

12.5
30.6
80.5

S1 S2

102
10.6
25.2

60
28.5

44
S1 S2
P1
P1

46
34

2.5

64 60.5 84.5 46 76
50.6
40.6 60.6
44 71
4.5

50 78
5.6

5.6
P2
60

P2
12.5
30.6

S1 S2
10.6
25.2

102
8.5

60
44

P1 S1 S2
P1
46
2.5

46
0.6 50.6
71
60.6
78

Power (VA) class Weight Power (VA) class Weight


Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
100 A 0.5 1 2.5 0.36 400 A 5 7.5 10 0.5
125 A 0.75 1.5 3.75 0.37 500 A 7.5 10 15 0.52
150 A 1 3.5 5 0.37 600 A 10 15 20 0.52
200 A 3.5 5 7.5 0.38 750 A 15 20 25 0.59
250 A 5 7.5 10 0.39 800 A 15 20 30 0.60
300 A 5 7.5 10 0.40 1000 A 15 20 30 0.61
400 A 5 7.5 10 0.41 1200 A 15 20 30 0.63
500 A 7.5 10 15 0.41 1500 A 15 20 30 0.65
600 A 7.5 10 15 0.42
750 A 10 15 20 0.43
800 A 10 15 20 0.44

T O O R D E R

Primary Secondary 1 A Secondary 5 A Primary Secondary 1 A Secondary 5 A


100 A 1921 3425B 1920 3425B 400 A 1921 4735B 1920 4735B
125 A 1921 3426B 1920 3426B 500 A 1921 4736B 1920 4736B
150 A 1921 3428B 1920 3428B 600 A 1921 4738B 1920 4738B
200 A 1921 3430B 1920 3430B 750 A 1921 4740B 1920 4740B
250 A 1921 3431B 1920 3431B 800 A 1921 4741B 1920 4741B
300 A 1921 3433B 1920 3433B 1000 A 1921 4742B 1920 4742B
400 A 1921 3435B 1920 3435B 1200 A 1921 4751B 1920 4751B
500 A 1921 3436B 1920 3436B 1500 A 1921 4744B 1920 4744B
600 A 1921 3438B 1920 3438B
750 A 1921 3440B 1920 3440B
800 A 1921 3441B 1920 3441B

> Associated products PRTC


CT protection unit
Mounting
accessories

> page 143 > page 112

115
TCR Range
Cable/busbar primary
> Measurement and instrumentation Current transformers (CTs)

TCR 71 TCR 75
Cable 63 mm Bar: 3 x 100 mm x 10 mm
Bar: 50 x 50 mm - 60 x 37 mm
80 x 30 mm

129 50

4,5
108 76
4,5

50
M5 6,6
50
M5
130

50,8
37,6
30,6
63

150

54
86
61

70
50,6
60,6 64 101 78
78
80,6

6,6
P2
6,6

64
S1 S2

P1
64

106

86
M5

78
50

Power (VA) class Weight Power (VA) class Weight


Primary 0.5 1
50,8
3 (kg) Primary 0.5 1 3 (kg)
400 A 5
37,6 7.5 10 0.82 1500 A 15 20 30 1.47
500 A 5
30,6
7.5 10 0.80 2000 A 15 20 30 1.55
600 A 7.5 10 15 0.83 2500 A 20 30 40 1.63
750 A 7.5 10 15 0.88 3000 A 30 40 60 1.71
50,6
60,6
80,6
108

800 A 7.5 10
63
15 0.66 4000 A 35 40 60 1.87
1000 A 10 15 20 0.72
1200 A
4,5 10 15 20
61 0.68
1500 A 15 20 25 0.84
130

2000 A 15 20 25 0.82
2500 A 15 20 30 0.88
3000 A 15 20 30 0.88

T O O R D E R

Primary Secondary 1 A Secondary 5 A Primary Secondary 1 A Secondary 5 A


400 A 1921 4635B 1920 4635B 1500 A 1921 5044B 1920 5044B
500 A 1921 4636B 1920 4636B 2000 A 1922 5045B 1920 5045B
600 A 1921 4638B 1920 4638B 2500 A 1923 5046B 1920 5046B
750 A 1921 4640B 1920 4640B 3000 A 1924 5047B 1920 5047B
800 A 1921 4641B 1920 4641B 4000 A 1925 5049B 1920 5049B
1000 A 1921 4642B 1920 4642B
1200 A 1921 4651B 1920 4651B
1500 A 1921 4644B 1920 4644B
2000 A 1921 4645B 1920 4645B
2500 A 1921 4646B 1920 4646B
3000 A 1921 4647B 1920 4647B

> Associated products PRTC


CT protection unit
Mounting
accessories

> page 143 > page 112

116
ENERGY PERFORMANCE
TCR Range
Busbar primary

POWER QUALITY
TCR 80 TCR 90 TCR 100
Bar: 100 x 20 mm Bar: 100 x 30 mm Bar: 125 x 60 mm

124 44
95 115 32 32

Transformers
43 32 43 32 60 32

& shunts
38

128
187.5

202.5 193 72
103 103
165

185
55
82.5

27
90
78 62

23 40
59 44
32
63 71 57

Power (VA) class Weight Power (VA) class Weight Power (VA) class Weight
Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
750 A 15 20 30 0.80 1500 A 15 30 40 0.76 1000 A 15 20 30 0.75
800 A 15 20 30 0.80 2000 A 20 40 50 0.82 1200 A 15 20 30 0.80
1000 A 15 20 30 0.76 2500 A 20 40 50 0.78 1500 A 15 20 30 0.83
1200 A 15 20 30 0.76 3000 A 20 45 60 0.90 2000 A 15 20 30 0.92
1500 A 15 30 40 0.76 4000 A 35 50 70 0.90 2500 A 20 30 40 1.01
2000 A 20 40 50 0.76 3000 A 30 40 60 1.09
4000 A 35 50 70 1.21
5000 A 40 60 80 1.44

T O O R D E R

Primary Secondary 1 A Secondary 5 A Primary Secondary 1 A Secondary 5 A Primary Secondary 1 A Secondary 5 A


750 A 1921 5640 1920 5640 1500 A 1921 6644 1920 6644 1000 A 1921 6842 1920 6842
800 A 1921 5641 1920 5641 2000 A 1921 6645 1920 6645 1200 A 1921 6851 1920 6851
1000 A 1921 5642 1920 5642 2500 A 1921 6646 1920 6646 1500 A 1921 6844 1920 6844
1200 A 1921 5651 1920 5651 3000 A 1921 6647 1920 6647 2000 A 1921 6845 1920 6845
1500 A 1921 5644 1920 5644 4000 A 1921 6649 1920 6649 2500 A 1921 6846 1920 6846
2000 A 1921 5645 1920 5645 3000 A 1921 6847 1920 6847
4000 A 1921 6849 1920 6849
5000 A 1920 6850

> Associated products PRTC


CT protection unit

> page 143

117
TCRO range
CTs designed for insertion on electrical installations
without opening the conductor.
> Measurement and instrumentation Current transformers (CTs)

PRODUCT
ADVANTAGES

PRIMARY
from 200 to 5,000 A
and wide choice of
primary options

FULLY OPENING
primary

Plate mounting Bar clamp fitting Captive sealable terminal covers.


fitting Split output terminals enabling
risk-free short-circuiting of
the secondary current

> General specifications


(cage for 4 mm2 wire)

Reference standard: Operating conditions:


EN 60044-1 (ex IEC 185) Temperature: -10C to +50C
Maximum network voltage: Relative humidity: < 90%
720 Vac Protection:
Dielectric test voltage: Protection rating: IP 50
3 kV/50 Hz/1 min (terminal covers supplied)
Frequency response: 50/60 Hz Dry winding with self-extinguishing ABS
Short-circuit thermal current covering (UL 94 VO)
B B (Ith): E60 In - 1 second
Dynamic current (Idyn): 2.5 Ith
Safety factor: < 5
C

A
> 3CT Mounting
Gmax
D
> Mounting accessories
B B E Dimensions Plate mounting Busbar clamp
Model A B C D E F G Model fittings
TCRO 2030 269 90 40 200 111 122 20 TCRO 2030
TCRO 5080 344 115 32 280 166 98 50 TCRO 5080
C

TCRO 8080 434 145 32 370 226 98 80 TCRO 8080


Gmax TCRO 80120 434 145 32 370 226 98 80 TCRO 80120
A D
TCRO 80160 554 185 52 450 266 158 80 TCRO 80160
Standard accessories

118
ENERGY PERFORMANCE
POWER QUALITY
TCRO 2030 TCRO 5080 TCRO 8080
Bar: 20 x 30 mm Bar: 50 x 80 mm Bar: 80 x 80 mm

20 20 20 50 50 50 80 80 80

Transformers
& shunts
30 110
30 11030 110 80 145
80 14580 145 80 145
80 14580 145

89 89 89 114 114 114 144 144 144

40 59 40 59 40 59 32 59 32 59 32 59 32 59 32 59 32 59

Power80(VA) class
80 80 Weight 80 Power
80 (VA)
80 class Weight Power (VA) class Weight
Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
100 A - - 1.5 0.75 250 A 1 2 4 0.90 250 A 1 2 4 1.00
150 A - - 2 0.75 300 A 1.5 3 6 0.90 300 A 1.5 3 6 1.00
200 A - 1.5 2.5 120 0.75
185
120 185120 400
185A 1.5 3 160 245
10 0.90245
160 245160 400 A 1.5 3 10 1.00
250 A - 2 4 0.75 500 A 2.5 5 15 0.90 500 A 2.5 5 15 1.00
300 A 1.5 4 6 0.75 600 A 2.5 5 17.5 0.90 600 A 2.5 5 17.5 1.00
400 A 2.5 6 10 0.75 800 A 3 7 18 0.90 800 A 3 7 18 1.00
144 144 144 1000 A 184 5 184 10 20
184 0.90 1000 A 5 10 20 1.00

32 59 32 59 32 59 52 59 52 59 52 59

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A Primary Secondary 5 A


100 A 1920 8328 250 A 1920 8431 250 A 1920 8531
150 A 1920 8329 300 A 1920 8433 300 A 1920 8533
200 A 1920 8330 400 A 1920 8435 400 A 1920 8535
250 A 1920 8331 500 A 1920 8436 500 A 1920 8536
300 A 1920 8333 600 A 1920 8438 600 A 1920 8538
400 A 1920 8335 800 A 1920 8441 800 A 1920 8541
1A on request 1000 A 1920 8442 1000 A 1920 8542
1A secondary on request 1A secondary on request

> Associated products PRTC


CT protection unit

> page 143

119
TCRO Range 20 20 50 5080 80

Split core 30 110 30 80110145 8080 145


145
> Measurement and instrumentation Current transformers (CTs)

89 89 114 114
144 144

TCRO 80120 40 59 40 32
59 59 TCRO 80160 32325959

Bar: 80 x 120 mm Bar: 80 x 160 mm

80 8080 80

120 185 160 185


120 245 160 245

144 144
184 184

32 59 52325959 52 59

Power (VA) class Weight Power (VA) class Weight


Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
500 A - 4 12 1.20 1000 A 10 15 20 3.50
600 A - 5 14 1.20 1500 A 15 20 25 3.50
800 A 3 7 18 1.20 2000 A 15 20 25 3.50
1000 A 5 9 20 1.20 2500 A 15 20 25 3.50
1200 A 6 11 28 1.20 3000 A 20 25 30 3.50
1500 A 8 17 30 1.20 4000 A 20 25 30 3.50
5000 A 20 25 30 3.50

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A


500 A 1920 8636 1000 A 1920 8742
600 A 1920 8638 1500 A 1920 8744
800 A 1920 8641 2000 A 1920 8745
1000 A 1920 8642 2500 A 1920 8746
1200 A 1920 8643 3000 A 1920 8747
1500 A 1920 8644 4000 A 1920 8749
1A on request 5000 A 1920 8750
1A on request

> Associated products PRTC


CT protection unit

> page 143

120
ENERGY PERFORMANCE
TC CLIP Range
Very compact current transformer for inclusion on electrical installations
without disconnecting the power cables

POWER QUALITY
PRODUCT
ADVANTAGES

QUICK AND EASY

Transformers
IMPLEMENTATION

& shunts
without cutting off the
power

VERY
COMPACT

PRIMARY
from 100 to 600 A

> General specifications


Maximum network voltage: 720 Vac
Dielectric test voltage: 3 kV 50 Hz 1 min
Secondary current: 1 A
Power: 0.5 VA
Frequency: 50/60 Hz
Operating temperature: -20C to +50C
Storage temperature: -30C to 90C
Accuracy class: 1 %

121
TCC241 / TCC242 TCC364 / TCC366
> Measurement and instrumentation Current transformers (CTs)
Cable 24 mm Cable 36 mm

33.08 45 33.08 57.1 45


18 24 18 35.9 24
16.8

16.8
23.4

23.4
35.9
91.4

91.4
74.5

64.1

74.5
41.1
47

47
57

57
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2

34.4 33.7 34.4 40.2 33.7


26.23 18 26.23 21.1 18

P1 P2 P1
P2 P1 P2 P1
P2 P1

P1 P2 P2 P1 P1 P2 P2 P1 P1

Power (VA) in class Weight Power (VA) in class Weight


TRIAC TRIAC TRIAC TRIAC TRIAC
P1 Primary
P2 P2 P1 1 (g) P1 Primary
P2 P2 P1 P1 1 (g)

100 A 0.5 162 400 A 0.5 263


SC 200 A SC 0.5
SC 187 600 A SC SC 0.5 300
w M3 Screw M3 Screw M3
M3Screw
Screw M3 Screw M3 Screw M3
M3Screw
Screw M3 Screw

T O O R D E R

Model Primary 1 A secondary


TCC241 100 A P01379601
TCC242 250 A P01379602
TCC364 400 A P01379603
TCC366 600 A P01379604

Pack of 3 TC CLIP Reference


Pack 3 TCC241 P01379605
Pack 3 TCC242 P01379606
Pack 3 TCC364 P01379607
Pack 3 TCC366 P01379608

> Related products


RENOV ENERGY
Metering solutions

> page 70

122
ENERGY PERFORMANCE
JVR-JVO-JVP Ranges
CTs designed to supply analogue or digital measurement instruments.
Accuracy class 0.5/1/3

POWER QUALITY
PRODUCT
ADVANTAGES Sealable cover
M5 terminals with
2 grooves for dual
COMPLETE RANGE: connection on secondary

Transformers
primary from 1 to 3,000 A

& shunts
and 5 A or 1 A secondary

TOTALLY ADAPTABLE
RANGE
for specific requirements
(primary, secondary,
power class, frequency)

Central pipe accessory on cable Mounting on symmetrical


primary JVO for compact lateral rail (except for JVP) or plate
primary connection mounting in cabinet

> General specifications


Reference standard: EN 60044-1 Dynamic current (Idyn): 2.5 Ith
(ex IEC 185) Safety factor: 5 in Class 1
Maximum network voltage: Operating conditions:
720 Vac Temperature: -5C to +50C
Dielectric test voltage: Relative humidity: 93% at 40C
3 kV/50 Hz/1 min Protection:
Frequency response: 50/60 Hz Protection rating: IP 50
B B E
Short-circuit thermal current (Ith): (with terminal cover supplied)
JVO, JVP: 80 In Dry winding with self-extinguishing ABS
JVR 86: 60 In covering (UL 94 VO)
JVR 64, JVR 75: 40 In
C

> 3 CT mounting > Mounting accessories


Gmax
A D

B B E
Dimensions
Model A B C D E F G For 1CT 2CT 3CT
JVO 25 CR 227 76 45 184.5 109.5 137 32.5 model mounting rail mounting rail mounting rail
F

JVO 32 CR 260 87 58 214.5 128.5 176 40.5 JVR ACCE 7652 ACCE 7653 ACCE 7655
JVP 624 296 99 35 220 122 107 22 JVO 12-18 ACCE 7650 ACCE 7651 ACCE 7654
Gmax
A D JVP 1025 344 115 45 252 138 137 22 JVO 21-25-32-36 ACCE 7652 ACCE 7653 ACCE 7655
JVP 1045 404 135 45 312 178 137 42 J3R 80 B ACCE 7640

123
Sealable cover

JVR-JVO-JVP Ranges

79
16.5

42 38

JVR Wound primary


64 84
2 mounting points (M6)

Sealable cover Sealable cover


> Measurement and instrumentation Current transformers (CTs)

93
79
JVR 64 JVR 75 42
16.5

38
JVR 86 45
16.5/20

45

M8 M8/M10 >64 75 A 84 M8/M10 >7575 A 94/101

2 mounting points (M6) 2 mounting points (M6)

Sealable cover Sealable cover Sealable cover

104,5
79

93
16.5 16.5/20 16.5/20

42 38 45 45 56 58
64 84 75 94/101 86 107/114
2 mounting points (M6) 2 mounting points (M6) 2 mounting points (M6)

Sealable cover Sealable cover

Power (VA) class Weight Power (VA) class Weight Power (VA) class Weight
Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
104,5
Primary 0.5 1 3 (kg)
5 A * 5 5 0.45 5 A * 10 10 0.6 5 A * 20 30 1.2
93

10 A * 5 5 16.5/20 0.45 10 A * 10 10 16.5/20 0.6 10 A * 20 30 1.2


15 A 5 5
* 45 0.45 15 A
* 56 10 10 0.6 15 A * 20 30 1.2
45 58
20 A * 5 5
75 94/101 0.45 20 A * 86 10 10 107/114 0.6 20 A * 20 30 1.2
25 A 2 mounting* 5 5
points (M6) 0.45 25 A 2 mounting*
points (M6)10 10 0.6 25 A * 20 30 1.2
30 A * 5 5 0.45 30 A * 10 10 0.6 30 A * 20 30 1.2
Sealable cover
40 A * 5 5 0.45 40 A * 10 10 0.6 40 A * 20 30 1.2
50 A * 5 5 0.45 50 A * 10 10 0.6 50 A * 20 30 1.2
60 A * 5 5 0.45 60 A * 10 10 0.6 60 A * 20 30 1.2

75 A * 5 5 0.45 75 A * 10 10 0.6 75 A * 20 30 1.2
104,5

100 A * 5 5 0.45 100 A * 10 10 0.6 100 A * 20 30 1.2


16.5/20
*On request 125 A * 10 10 0.6 125 A * 20 30 1.2
56 58 150 A * 10 10 0.6 150 A * 20 30 1.2
86 107/114 200 A * 10 10 0.6 200 A * 20 30 1.2
2 mounting points (M6)
*On request *On request

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A Primary Secondary 5 A


5 A JVRA 8700 5 A JVRB 8725 5 A JVRC 8742
10 A JVRA 8701 10 A JVRB 8726 10 A JVRC 8743
15 A JVRA 8702 15 A JVRB 8727 15 A JVRC 8744
20 A JVRA 8703 20 A JVRB 8728 20 A JVRC 8745
25 A JVRA 8704 25 A JVRB 8729 25 A JVRC 8746
30 A JVRA 8705 30 A JVRB 8730 30 A JVRC 8747
40 A JVRA 8706 40 A JVRB 8731 40 A JVRC 8748
50 A JVRA 8707 50 A JVRB 8732 50 A JVRC 8749
60 A JVRA 8708 60 A JVRB 8733 60 A JVRC 8750
75 A JVRA 8709 75 A JVRB 8734 75 A JVRC 8751
100 A JVRA 8710 100 A JVRB 8735 100 A JVRC 8752
Sealable cover ACCE 7668 125 A JVRB 8736 125 A JVRC 8753
150 A JVRB 8737 150 A JVRC 8754
200 A JVRB 8738 200 A JVRC 8755
Sealable cover ACCE 7668 Sealable cover ACCE 7668

> Customized product > Associated products


Mounting PRTC
Model Primary Secondary Class Power Frequency accessories CT protection unit

Example JVR 64 100 A 1A 1 5 VA 50 Hz > page 123 > page 143


JVR 64
JVR 75
JVR 86

124
ENERGY PERFORMANCE
JVR-JVO-JVP Ranges
JVO Cable primary

POWER QUALITY
JVO 12-46 JVO 18-51 JVO 21-64
Cable 12 mm Cable 18 mm Cable 21 mm

Sealable cover Sealable cover Sealable cover

12 18 21

63 56 70 62

Transformers
79 71

& shunts
29 32 37

30 30 32 30 38
42
46 51 64
2 mounting points (M5) 2 mounting points (M5) 2 mounting points (M6)

Power (VA) class Weight Power (VA) class Weight Power (VA) class Weight
Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
40 A - - 1.5 0.20 100 A - - 2 0.25 100 A - - 4 0.35
50 A - - 2 0.20 125 A - 2.5 3 0.25 125 A - - 5 0.35
60 A - - 2.5 0.20 150 A - 3 4 0.25 150 A - - 5 0.35
75 A - - 3 0.20 200 A - 4 6 0.25 200 A - 5 5 0.35
100 A - - 4 0.20 250 A - 5 7 0.25 250 A - 5 5 0.35
125 A - - 5 0.20 300 A - 5 8 0.25 300 A * 5 10 0.35
150 A - - 5 0.20 400 A * 5 10 0.35
500 A * 10 20 0.35
600 A * 10 20 0.35
*On request

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A Primary Secondary 5 A


40 A JVOA 8759 100 A JVOB 8769 100 A JVOC 8778
50 A JVOA 8760 125 A JVOB 8770 125 A JVOC 8779
60 A JVOA 8761 150 A JVOB 8771 150 A JVOC 8780
75 A JVOA 8762 200 A JVOB 8772 200 A JVOC 8781
100 A JVOA 8763 250 A JVOB 8773 250 A JVOC 8782
125 A JVOA 8764 300 A JVOB 8774 300 A JVOC 8783
150 A JVOA 8765 Central tube ACCE 7661 400 A JVOC 8784
Central tube ACCE 7660 500 A JVOC 8785
600 A JVOC 8786
Central tube ACCE 7662
Sealable cover ACCE 7668

> Customized product > Associated products


Mounting PRTC
Model Primary Secondary Class Power Frequency accessories CT protection unit

Example JVR 64 100 A 1A 1 5 VA 50 Hz > page 123 > page 143


JVR 64
JVR 75
JVR 86

125
JVR-JVO-JVP Ranges
JVO Cable primary
> Measurement and instrumentation Current transformers (CTs)

JVO 21-75 JVO 32-75 JVO 36-75


Cable 21 mm Cable 32 mm Cable 36 mm

Sealable cover Sealable cover Sealable cover

21 32 36

93 85 93 85 93 85

44 44 44

45 45 45 45 45 45
75 75 75
2 mounting points (M6) 2 mounting points (M6) 2 mounting points (M6)

Power (VA) class Weight Power (VA) class Weight Power (VA) class Weight
Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
50 A - - 5 0.65 100 A - - 5 0.65 100 A - - 5 0.45
60 A - - 5 0.65 125 A - - 5 0.65 125 A - - 5 0.45
75 A - - 10 0.65 150 A - 5 10 0.65 150 A - - 10 0.45
100 A - 4 10 0.65 200 A - 5 10 0.65 200 A - 5 10 0.45
125 A - 5 10 0.65 250 A * 5 15 0.65 250 A * 5 15 0.45
150 A * 10 15 0.65 300 A * 10 15 0.65 300 A * 5 15 0.45
200 A * 10 15 0.65 400 A * 10 15 0.65 400 A * 5 15 0.45
250 A * 15 20 0.65 500 A * 10 20 0.65 500 A * 10 20 0.45
300 A * 15 20 0.65 600 A * 10 20 0.65 600 A * 20 20 0.45
400 A * 20 30 0.65 *On request *On request
500 A * 30 30 0.65
600 A * 30 30 0.65
*On request

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A Primary Secondary 5 A


50 A JVOE 8795 100 A JVOF 8814 100 A JVOG 8829
60 A JVOE 8796 125 A JVOF 8815 125 A JVOG 8830
75 A JVOE 8797 150 A JVOF 8816 150 A JVOG 8831
100 A JVOE 8798 200 A JVOF 8817 200 A JVOG 8832
125 A JVOE 8799 250 A JVOF 8818 250 A JVOG 8833
150 A JVOE 8800 300 A JVOF 8819 300 A JVOG 8834
200 A JVOE 8801 400 A JVOF 8820 400 A JVOG 8835
250 A JVOE 8802 500 A JVOF 8821 500 A JVOG 8836
300 A JVOE 8803 600 A JVOF 8822 600 A JVOG 8837
400 A JVOE 8804 Sealable cover ACCE 7668 Sealable cover ACCE 7668
500 A JVOE 8805
600 A JVOE 8806
Central tube ACCE 7663
Sealable cover ACCE 7668

> Customized product > Associated products


Mounting PRTC
Model Primary Secondary Class Power Frequency accessories CT protection unit

Example JVR 32-75 500 A 1A 0.5 10 VA 50 Hz > page 123 > page 143
JVR 21-75
JVR 32-75
JVR 36-75

126
ENERGY PERFORMANCE
JVR-JVO-JVP Ranges
JVO Cable primary

POWER QUALITY
J3R 80 B JVO 25 CR JVO 32 CR
Cable 66 mm Cable 25 mm Cable 32 mm
Bar: 32 x 10 mm Bar: 40 x 10 mm

134 Sealable cover Sealable cover Sealable cover


Busbar Busbar
clamp clamp
25 32

Transformers
& shunts
32,5 10,5 93 85 40,5 10,5 104,5 96,5
154
44 50
76

66
75 45 56 58

42 86
2 mounting points (M6) 2 mounting points (M6)

Power (VA) class Weight Power (VA) class Weight Power (VA) class Weight
Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
200 A - 5 10 1.6 100 A - - 5 0.6 100 A - - 5 0.9
250 A - 5 10 1.6 125 A - - 5 0.6 125 A - - 10 0.9
300 A 5 10 15 1.6 150 A - - 5 0.6 150 A - 5 15 0.9
400 A 10 20 25 1.6 200 A - 5 10 0.6 200 A - 5 15 0.9
500 A 15 20 25 1.6 250 A * 5 15 0.6 250 A * 10 20 0.9
600 A 15 20 25 1.6 300 A * 5 15 0.6 300 A * 10 30 0.9
750 A 15 20 25 1.6 400 A * 10 15 0.6 400 A * 15 30 0.9
800 A 15 20 25 1.6 500 A * 20 20 0.6 500 A * 15 30 0.9
1000 A 15 20 25 1.6 600 A * 20 20 0.6 600 A * 15 30 0.9
1250 A 15 20 25 1.6 *On request *On request
1500 A 15 20 25 1.6

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A Primary Secondary 5 A


200 A J3RC 7514 100 A JVOD 8850 100 A JVOH 8866
250 A J3RC 7524 125 A JVOD 8851 125 A JVOH 8867
300 A J3RC 7525 150 A JVOD 8852 150 A JVOH 8868
400 A J3RC 7528 200 A JVOD 8853 200 A JVOH 8869
500 A J3RC 7527 250 A JVOD 8854 250 A JVOH 8870
600 A J3RC 7529 300 A JVOD 8855 300 A JVOH 8871
750 A J3RC 7526 400 A JVOD 8856 400 A JVOH 8872
800 A J3RC 7531 500 A JVOD 8857 500 A JVOH 8873
1000 A J3RC 7530 600 A JVOD 8858 600 A JVOH 8874
1250 A J3RC 7532 Busbar clamp ACCE 7665 Busbar clamp ACCE 7666
1500 A J3RC 7533 Sealable cover ACCE 7668 Sealable cover ACCE 7668
Sealable cover ACCE 7671

> Customized product > Associated products


Mounting PRTC
Model Primary Secondary Class Power Frequency accessories CT protection unit

Example JVR 25 CR 600 A 1A 0.5 10 VA 60 Hz > page 123 > page 143
J3R 80 B
JVO 25 CR
JVO 32 CR

127
JVR-JVO-JVP Ranges
JVP Busbar primary
> Measurement and instrumentation Current transformers (CTs)

JVP 624 JVP 1025 JVP 1045


Bar: 63 x 20 mm Bar: 100 x 20 mm Bar: 100 x 40 mm

Sealable Sealable Sealable


42 52 52
cover cover cover

181.5 Busbar 181.5


130.5
65 Busbar 105 105 Busbar
clamping clamping clamping
plates plates
plates
32.5
27.5 32.5
Mounting
Mounting 45 Mounting
35 base 45
base 22
42
base
22 74
74 114 74
98 134

Power (VA) class Weight Power (VA) class Weight Power (VA) class Weight
Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg) Primary 0.5 1 3 (kg)
100 A - - 5 1.2 200 A - - 5 2 300 A - 5 5 2.5
125 A - - 5 1.2 250 A - - 5 2 400 A * 5 10 2.5
150 A - - 5 1.2 300 A - 10 20 2 500 A * 10 15 2.5
200 A - - 5 1.2 400 A * 5 30 2 600 A * 15 15 2.5
250 A - 5 15 1.2 500 A * 15 15 2 750 A * 20 20 2.5
300 A - 5 15 1.2 600 A * 15 15 2 800 A * 20 20 2.5
400 A 750 A * 20 20 2
* 10 15 1.2 800 A
1000 A * 30 30 2.5
500 A * 15 20 1.2 * 20 30 2 1250 A * 30 30 2.5
600 A 1000 A * 30 30 2
* 20 20 1.2 1250 A
1500 A * 30 30 2.5
750 A * 30 30 2
* 20 20 1.2 1500 A
2000 A * 30 30 2.5
800 A * 30 30 2
* 20 20 1.2 2000 A * 30 30 2
2500 A * 30 30 2.5
1000 A * 20 20 1.2 2500 A 3000 A * 30 30 2.5
* 30 30 2
*On request 3000 A *On request
* 30 30 2
*On request

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A Primary Secondary 5 A


100 A JVPR 8879 200 A JVPT 8890 300 A JVPU 8906
125 A JVPR 8880 250 A JVPT 8891 400 A JVPU 8918
150 A JVPR 8881 300 A JVPT 8892 500 A JVPU 8907
200 A JVPR 8882 400 A JVPT 8893 600 A JVPU 8908
250 A JVPR 8883 500 A JVPT 8896 750 A JVPU 8909
300 A JVPR 8884 600 A JVPT 8897 800 A JVPU 8919
400 A JVPR 8885 750 A JVPT 8898 1000 A JVPU 8910
500 A JVPR 8886 800 A JVPT 8895 1250 A JVPU 8911
600 A JVPR 8887 1000 A JVPT 8899 1500 A JVPU 8912
1250 A JVPT 8900
750 A JVPR 8888 2000 A JVPU 8913
1500 A JVPT 8901
800 A JVPR 8890 2000 A JVPT 8902 2500 A JVPU 8920
1000 A JVPR 8889 2500 A JVPT 8921 3000 A JVPU 8914
Mounting base ACCE 7669 3000 A JVPT 8922 Mounting base ACCE 7669
Sealable cover ACCE 7672 Mounting base ACCE 7669 Sealable cover ACCE 7672
Sealable cover ACCE 7672

> Customized product > Associated products


PRTC
Model Primary Secondary Class Power Frequency CT protection unit

Example JVP 1025 1000 A 1A 0.5 10 VA 50 Hz > page 143


JVP 624
JVP 1025
JVP 1045

128
ENERGY PERFORMANCE
JVS Range
CTs designed to supply IEC 687 electronic measurement instruments,
power monitors, digital transducers, etc.

POWER QUALITY
PRODUCT
ADVANTAGES Captive sealable
terminal covers

CHOICE OF PRIMARY

Transformers
from 100 to 5,000 A

& shunts
ACCURACY CLASS:
0.2 S for high-performance
applications

Split output terminals enabling Cabinet base fitting


risk-free short-circuiting (or directly on busbar
of the secondary current primary)
(M4 or cage for 4 mm2 wire)

> General specifications


Reference standard: EN 60044-1 Safety factor: < 5
(ex IEC 185) Operating conditions:
Maximum network voltage: Temperature: -10C to +50C
720 Vac Relative humidity: < 90%
Dielectric test voltage: Protection:
3 kV/50 Hz/1 min Protection rating: IP 50
Frequency response: 50/60 Hz (terminal covers supplied)
Short-circuit thermal current Dry winding with self-extinguishing ABS
B B
(Ith): 60 EIn - 1 second covering (UL 94 VO)
Dynamic current (Idyn): 2.5 Ith

> 3CT Mounting > Mounting accessories


C

Gmax Dimensions Plate mounting Busbar Sealable


A D
Model A B C D E F G Model fittings clamp terminal cover*
JVS 25B 243.5 81.5 60.5 189 108.5 183.5 26 JVS 25B 1923 0022
B B E JVS 26B 243.5 81.5 60.5 191 110.5 183.5 28 JVS 26B 1923 0022
JVS 30B 308 103 69 250 148 209 44 JVS 30B 1923 0022
JVS 38B 392 131 69 325 195 209 63 JVS 38B 1923 0022
F

JVS 40 287 96 40 215 120 122 23 JVS 39B 1923 0022


JVS 50 347 116 44 264 149 134 32 JVS 40
Gmax
A D JVS 60 374 125 44 310 186 134 60 JVS 50
JVS 60
Standard accessories * sold in pairs

129
JVS Range
Cable/busbar primary
> Measurement and instrumentation Current transformers (CTs)

JVS 25B JVS 26B


60.5 64 60.5
64
44 44

4.5
4.5

5.6
5.6

P2 P2

60
80.5

80.5
60
S1 S2

10.6
S1 S2

25.2
10.6

20.6

28,5
26

P1 P1
34

34
2.5

2.5
46 46
60.5 30.6 60.5 40.6
64 71 64
44 71
44
4.5
5.6

5.6
Cable 26 mm Cable 28 mm
P2 P2
Bar: 20 x 20 mm Bar: 20 x 25 mm

60
60

80.5

S1 S2 S1 S2
10.6

20.6

10.6
25.2
28,5
26

P1 P1
25 x 12 mm 30 x 15 mm
34

30 x 10 mm 40 x 10 mm
2.5

2.5

46 46
30.6 40.6
71 71

Power (VA) Weight Power (VA) Weight


Primary in class 0.2 S (kg) Primary in class 0.2 S (kg)
100 A 1 0.53 150 A 1 0.37
150 A 2.5 0.53 200 A 1.25 0.38
200 A 3.5 0.54 250 A 1.5 0.39
250 A 5 0.54 300 A 1.75 0.4
300 A 5 0.51 400 A 1 0.41
400 A 7.5 0.51 500 A 5 0.41
600 A 5 0.42
750 A 7.5 0.43
800 A 7.5 0.44

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A


100 A JVSB25 100/5 150 A JVSB26 100/5
150 A JVSB25 150/5 200 A JVSB26 200/5
200 A JVSB25 200/5 250 A JVSB26 250/5
250 A JVSB25 250/5 300 A JVSB26 300/5
300 A JVSB25 300/5 400 A JVSB26 400/5
400 A JVSB25 400/5 500 A JVSB26 500/5
600 A JVSB26 600/5
750 A JVSB26 750/5
800 A JVSB26 800/5

> Associated products Mounting


accessories
PRTC
CT protection unit

> page 129 > page 143

130
ENERGY PERFORMANCE
JVS Range
Cable/busbar primary

POWER QUALITY
JVS 30B JVS 38B JVS 39B
Cable 44 mm Cable 63 mm Bar: 3 x 100 x 10 mm
Bar: 50 x 30 mm Bar: 50 x 50 mm
60 x 12 mm 60 x 30 mm
80 x 30 mm
84.5 69 108 50
4.5

50 129

Transformers
4.5
4.5

50 M5 6.6

& shunts
5.6

50
P2 M5
12.5
30.6

130

50.8
37.6
30.6
102

60
44

63

S1 S2
P1

86

150
46

54
61

50.6

70
50.6
60.6
69 78 60.6 64
78 101 78
50 80.6
5.6

6.6

6.6
P2 P2
60

64

S1 S2

64
S1 S2

P1 P1

106
86
M5

78
78
50

Power (VA) Weight Power (VA) Weight Power (VA) Weight


Primary Class 0.2 S (kg) Primary Class 0.2 S (kg) Primary Class 0.2 S (kg)
50.8
600 A 5 0.52 1000 A 37.6 7,5 0.72 1500 A 10 1.47
750 A 7.5 0.59 1200 A 30.6 10 0.68 2000 A 10 1.55
800 A 7.5 0.60 1500 A 10 0.84 2500 A 15 1.63
1000 A 10 0.61 2000 A 10 0.82 3000 A 20 1.71
50.6
60.6
80.6
108

63
1200 A 10 0.63 2500 A 10 0.88 4000 A 25 1.83
1500 A 10 0.65 3000 A 10 0.88
61
4.5
130

T O O R D E R

Primary Secondary 5 A Primary Secondary 5 A Primary Secondary 5 A


600 A JVSB30 600/5 1000 A JVSB38 1000/5 1500 A JVSB39 1500/5
750 A JVSB30 750/5 1200 A JVSB38 1200/5 2000 A JVSB39 2000/5
800 A JVSB30 800/5 1500 A JVSB38 1500/5 2500 A JVSB39 2500/5
1000 A JVSB30 1000/5 2000 A JVSB38 2000/5 3000 A JVSB39 3000/5
1200 A JVSB30 1200/5 2500 A JVSB38 2500/5 4000 A JVSB39 4000/5
1500 A JVSB30 1500/5 3000 A JVSB38 3000/5

> Associated products Mounting


accessories
PRTC
CT protection unit

> page 129 > page 143

131
JVS Range
Busbar primary
> Measurement and instrumentation Current transformers (CTs)

JVS 40 JVS 50
Bar: 100 x 20 mm Bar: 100 x 30 mm

115
95 43 32
43 32

187,5 202,5
165
103 103
180
82,5
90

40
23 44
59 32
63

Power (VA) Weight Power (VA) Weight


Primary Class 0.2 S (kg) Primary Class 0.2 S (kg)
1000 A 1.5 0,76 1500 A 10 0.76
1200 A 4 0,76 2000 A 10 0.82
1500 A 10 0.76 2500 A 10 0.78
2000 A 10 0.76 3000 A 10 0.90
4000 A 10 0.90

T O O R D E R

Primary Secondary 5A Primary Secondary 5A


1000 A JVS40-1000/5 1500 A JVS50-1500/5
1200 A JVS40-1200/5 2000 A JVS50-2000/5
1500 A JVS40-1500/5 2500 A JVS50-2500/5
2000 A JVS40-2000/5 3000 A JVS50-3000/5
4000 A JVS50-4000/5

> Associated products PRTC


CT protection unit

> page 143

132
ENERGY PERFORMANCE
POWER QUALITY
JVS 60
Bar: 125 x 60 mm

124 44
32 60 32
32

Transformers
38

& shunts
193 72
128

55
27
78 62

71 57

Power (VA) Weight


Primary Class 0.2 S (kg)
1000 A 1.5 0.75
1500 A 7.5 0.83
2000 A 10 0.92
2500 A 10 1.01
3000 A 10 1.09
4000 A 10 1.21
5000 A 10 1.44

T O O R D E R

Primary Secondary 5A
1000 A JVS60-1000/5
1500 A JVS60-1500/5
2000 A JVS60-2000/5
2500 A JVS60-2500/5
3000 A JVS60-3000/5
4000 A JVS60-4000/5
5000 A JVS60-5000/5

> Associated products PRTC


CT protection unit

> page 143

133
Single-phase, single-rating: JVP1045B
Transformers for tariff metering

JVP1045 B
> Measurement and instrumentation Current transformers (CTs)

Busbar primary

PRODUCT
ADVANTAGES

DELIVERED
WITH SEALABLE
PROTECTIVE COVER
for the secondary.
Simple M5 terminals

DIRECT MOUNTING
on primary busbar by
means of plate and
tightening screw or panel
mounting with mounting
plate

> General specifications


Reference standard: Safety factor:
EN 60044-1 (ex-IEC 185) 10 in class 0.5
and NFC 42-502 Except * SF = 6.4/10.5
Maximum network voltage: and **SF = 4.7/8.2
720 Vac Operating conditions:
Dielectric test voltage: Temperature: -20C to +60C
3 kV/50 Hz/1 min Relative humidity: 93% to 40C
Frequency response: Protection:
50/60 Hz Protection rating: IP 50
Thermal short-circuit current Dry winding in self-extinguishing ABS
(Ith):80In envelope (UL 94 VO)
Dynamic current (Idyn):
2.5 Ith

T O O R D E R
Barre 100 x 40 mm 65
Power (VA) in class 0.5 Weight Capot
plombable
7.5 15 (kg)
Primary Secondary 5A
181,5
105

500 A JVPA 7569 2.50 Plaquettes


de serrage
1000 A JVPA 7573 2.50 de barre
32,5

2000 A JVPA 7576 2.50 45


42 Plaquette
500-1000 A* JVPA 7589 JVPA 7585 2.50 134
74 de fixation

1000-2000 A** JVPA 7590 JVPA 7588 2.50

134
ENERGY PERFORMANCE
Single-phase, single-rating: JVO 40-100
Transformers for tariff metering

JVO 40-100

POWER QUALITY
Cable primary

PRODUCT
ADVANTAGES

DELIVERED

Transformers
WITH SEALABLE

& shunts
TERMINAL COVER
for the secondary.
Simple M5 terminals with
two grooves for double
connection

MOUNTING ON
SYMMETRICAL
MOUNTING RAIL
or panel mounting

> General specifications


Reference standard: Safety factor:
EN 60044-1 (ex-IEC185) and NFC 42-502 10 in class 0.5
Maximum network voltage: Except * SF = 6.4/10.5
720 Vac and **SF = 4.7/8.2
Dielectric test voltage: Operating conditions:
3 kV/50 Hz/1 min Temperature: -5C to +50C
Frequency response: Relative humidity: 93 % to 40C
50/60 Hz Protection:
Thermal short-circuit current Protection rating: IP 50
(Ith):80In Dry winding in self-extinguishing ABS
Dynamic current (Idyn): envelope (UL 94 VO)
2.5 Ith

T O O R D E R

Power (VA) in class 0.5


Capot
15 7.5 15 Weight S1 S2 plombable

Primary Secondary 2.5 A 5 A 5 A (kg) 42


110
125

200 A JVON 7103 JVON 7100 0.97


56

500 A JVON 7101 0.97 P1

200-500 JVON 7104 JVON 7102 0.97 2 fixations M6 70 36


S3
1-CT mounting rail ACCE 7679
66

2-CT mounting rail ACCE 7680 S1


S2

100
3-CT mounting rail ACCE 7681

135
Single-phase, multi-rating: JVO 40-100 S
Transformers for tariff metering ERDF application

JVO 40-100 S
> Measurement and instrumentation Current transformers (CTs)

Cable primary 40 mm

PRODUCT
ADVANTAGES

CLASS 0.2s
ACCORDING TO
IEC60044-1
Particularly SUITABLE
FOR ERDF-QUALIFIED
BI-RATING AND
TRI-RATING
ELECTRONIC METERS

> General specifications


Cable primary: 40mm Type of casing:
Transformation ratio: Self-extinguishing thermoplastic (UL94V0)
200-500/5 A Protection: IP30
Accuracy class:0.2s Mechanical shock resistance: IK7
Precision power: 7.5 VA Rated withstand voltage:
Highest network voltage: 720 Vac 3 kV (RMS value) at 50 Hz for 1 minute
Rated frequency: 50/60 Hz Rated lightning impulse
Rated short-circuit thermal current withstand voltage:
(Ith): 20 kA for 1 s 8 kV (peal value) Wave 1.2/50 s
Rated dynamic current (Idyn): 2.5 Ith Insulation class:
Safety factor: E (heating limit: 75 K)
SF = 3 (200/5 A); SF = 6 (500/5 A) Weight: 1.1 kg
Rated thermal current: 1.2 Ipn
Operating temperature:
T O O R D E R
-25C to +40C
Model Reference
JVO 40-100 S bi-rating P01379512

> Dimensions
Bi-rating

136
ENERGY PERFORMANCE
Single-phase, multi-rating: JVO 90-160 S
Transformers for tariff metering ERDF application

JVO 90-160 S

POWER QUALITY
Cable primary 90 mm

PRODUCT
ADVANTAGES

CLASS 0.2s

Transformers
& shunts
ACCORDING TO
IEC60044-1
Particularly SUITABLE
FOR ERDF-QUALIFIED
TRI-RATING
ELECTRONIC METERS

> General specifications


Cable primary: 90mm Type of casing:
Transformation ratio: Self-extinguishing thermoplastic (UL94V0)
500-1,000-2,000/5 A Protection: IP30
Accuracy class: 0.2s Mechanical shock resistance: IK7
Precision power: 7.5 VA Rated withstand voltage:
Highest network voltage: 720 Vac 3 kV (RMS value) at 50 Hz for 1 minute
Rated frequency: 50/60 Hz Rated lightning impulse withstand
Rated short-circuit thermal current voltage:
(Ith): 30 kA for 1 s 8 kV (peak value) Wave 1.2/50 s
Rated dynamic current (Idyn): 2.5 Ith Insulation class: E(heating limit: 75 K)
Safety factor: Weight: 1.9 kg
SF = 4 (500/5 A); SF = 6 (1 000/5 A) ;
SF = 9 (2 000/5 A)
Rated thermal current: 1.2 Ipn
T O O R D E R
Operating temperature:
-25C to +40C Model Reference
JVO 90-160 S tri-rating P01379513

> Dimensions

137
Single-phase, multi-rating: JVP 1145 S
Transformers for tariff metering ERDF application

JVP 1145 S
> Measurement and instrumentation Current transformers (CTs)

Cable primary

PRODUCT
ADVANTAGES

CLASS 0.2s
ACCORDING TO
IEC60044-1
Particularly SUITABLE
FOR ERDF-QUALIFIED
TRI-RATING
ELECTRONIC METERS

> General specifications


Cable primary: Operating temperature:
Busbar: 63 x 12 mm or 100 x 12 mm -25C to +40C
Cable: 40 mm Type of casing:
Transformation ratio: Self-extinguishing thermoplastic (UL94V0)
500 1,000 2,000 / 5 A Protection: IP30
Accuracy class: 0.2s Mechanical shock resistance: IK7
Precision power: 7.5 VA Rated withstand voltage:
Highest network voltage: 720 Vac 3 kV (RMS value) at 50 Hz for 1 minute
Rated frequency: 50/60 Hz Rated lightning impulse withstand
Rated short-circuit thermal current voltage:
(Ith): 30 kA for 1 s 8 kV (peak value) Wave 1.2/50 s
Rated dynamic current (Idyn): 2.5 Ith Insulation class: E (heating limit: 75 K)
Safety factor: Weight: 1.7 kg
SF = 3 (500/5 A); SF = 4 (1000/5 A);
SF = 6 (2000/5 A) T O O R D E R
Rated thermal current: 1.2 Ipn
Model Reference
JVP 1145 S tri-rating P01379510

> Dimensions

138
ENERGY PERFORMANCE
Single-phase, multi-rating: TRI 500
Transformers for tariff metering

TRI 500

POWER QUALITY
PRODUCT
ADVANTAGES

Compliant

Transformers
with NF-C-42-502

& shunts
standard

Designed for
three-phase LV
metering
> General specifications
Maximum network voltage: 500Vac
Dielectric test voltage: 2 kV - 50 Hz - 1 min
Rated withstand voltage: 8 kV
Frequency response: 50 Hz
Primary via cable clamp: conductors from 50 to 240 mm2

3 sealable screws Fixed by 4 screws 8

Input

Output voltage current


194
166

measurement

Output

32
430

Thickness of
the base
= 20
70
107

67 60 60 55

T O O R D E R

Primary 5A Secondary
Power (VA) Weight
Primary Class 0.5 (kg) 50 A TRI5 7823
50 A 15 7.50 100 A TRI5 7825
100 A 15 7.50 150 A TRI5 7826
150 A 15 7.50
200 A TRI5 7827
200 A 15 7.50
300 A 15 7.50 300 A TRI5 7828
500 A 15 7.50 500 A TRI5 7831

139
Three-phase, multi-rating: TRI 700
Transformers for tariff metering ERDF application
> Measurement and instrumentation Current transformers (CTs)

PRODUCT
ADVANTAGES

CLASS 0.2s ACCORDING


TO IEC60044-1

CHOICE OF PRIMARY
CONDUCTOR type: copper
> General specifications
Primary via cable clamp: Rated thermal current:
or aluminium Conductor cross-section from 50 mm to 240mm Bi-rating / tri-rating model: 1.2 Ipn
Transformation ratio: Operating temperature:
B uilt-in short-circuiting TRI700S bi-rating model 50 A - 100 A / 5 A Bi-rating / tri-rating model: -25C to +40C
switch TRI700S bi-rating model 100 A - 200 A / 5 A Type of casing:
TRI700S bi-rating model 200 A - 500 A / 5 A Bi-rating / tri-rating model:
TRI700 tri-rating model 100 A - 200 A - 500A / 5 A Self-extinguishing thermoplastic (UL94V0)
Accuracy class: Protection rating:
Bi-rating model 0.2s; tri-rating model: 0.5 With additional cover: IP40
Precision power: Mechanical shock resistance:
Bi-rating model: 7.5 VA; tri-rating model: 3.75 VA Bi-rating / tri-rating model: (IK7)
Maximum network voltage: Rated withstand voltage:
Bi-rating / tri-rating model: 720 Vac Bi-rating / tri-rating model: 3 kV
Rated frequency: (RMS value) at 50 Hz for 1 minute
Bi-rating / tri-rating model: 50/60 Hz Lightning impulse withstand voltage:
Rated thermal short-circuit current (Ith): Bi-rating / tri-rating model:
Bi-rating / tri-rating model: (8 kV) (peak value) Wave 1.2/50 s
80 Ipn with a maximum of 20 kA for 1 s Insulation class:
Rated dynamic current (Idyn): Bi-rating / tri-rating model:
Bi-rating / tri-rating model: 2.5 Ith E (heating limit: 75 K)
Safety factor: Weight: Bi-rating / tri-rating model: 7 Kg
TRI700S 50 - 100 / 5 A:
FS = 2.3 (50 A); FS = 4.2 (100 A)
TRI700S 100-200/5 A: T O O R D E R
FS = 2.3 (100 A); FS = 4.2 (200 A) Model Reference
TRI700S 200 - 500 / 5 A:
TRI 700 tri-rating P01379514
FS = 2,3 (200 A); FS = 5 (500 A)
TRI700 100 - 200 - 500 / 5 A: TRI 700 S bi-rating 50 - 100 / 5 A P01379515
FS = 3 (100 A); FS = 4 (200 A); FS = 6 (500 A) TRI 700 S bi-rating 100 - 200 / 5 A P01379516
TRI 700 S bi-rating 200 - 500 / 5 A P01379517

> Dimensions

140
ENERGY PERFORMANCE
Current summation: JVM 15
CT designed for adding or subtracting instantaneous values from the
secondaries of 2 or 3 current transformers. Used to supply measuring or
metering instruments on installations with several feeder and feed points.

POWER QUALITY
PRODUCT
ADVANTAGES

COMPACT DESIGN

Transformers
& shunts
M
 ounting on plate
or rail

Sealable cover. Mounting on plate or


Terminal connections: symmetrical rail
M5; 2 secondary slots
for double connections;
primary side connections.

> General specifications


Reference standard: Sealable cover
EN 60044-1 (Ex IEC 185)
Maximum network voltage: 720 Vac
Dielectric test voltage:
M5
3 kV/50 Hz/1 min
104,5

Frequency response: 50/60 Hz


Short-circuit thermal current
(Ith): 80 In - 1 second
Dynamic current (Idyn): 2.5 Ith 56 58
Safety factor: < 5 86 92

Internal power: 4 VA 2 mounting points (M6)

Operating conditions:
Temperature: -5C to +60C
Relative humidity: 93% at 40C Power (VA) class Weight
Protection: Primary 0.5 1 3 (kg)
Protection rating: 5+5 A 15 20 30 1.20
IP 40 (module casing) and IP 10 (terminals) 5+5+5 A 15 20 30 1.20
Dry winding with self-extinguishing ABS
covering (UL 94 VO)

> Cabinet accessories


T O O R D E R

Primary Secondary 5A
Model 1 CT slide 2 CT slide 3 CT slide 5+5 A JVMA 7523
rail mounting rail mounting rail mounting 5+5+5 A JVMA 7524
JVM 15 ACCE 7652 ACCE 7653 ACCE 7655 Sealable cover ACCE 7668

141
Current summation: TCS
CT designed to add together the instantaneous current values
from the secondaries of 2 to 4 current transformers. In this way,
it provides data for the measurement or metering equipment
> Measurement and instrumentation Current transformers (CTs)

on installations with several feeders or feeds.

PRODUCT
ADVANTAGES

MADE-TO-MEASURE
PRODUCT
with different totalized
CT ratios

Primary and secondary con- Mounting on DIN


nection by cages rail or plate
for 2.5 mm2 wire

> General specifications


Reference standard: Dynamic current (Idyn): 2.5 Ith
EN 60044-1 (Ex IEC 185) Safety factor: 5
Maximum network voltage: 720 Vac Operating conditions:
Dielectric test voltage: 3 kV/50 Hz/1 min Temperature: -20C to +50C
Frequency response: 50/60 Hz Relative humidity: < 80%
Short-circuit thermal current (Ith): Protection:
40 In - 1 second Casing protection rating: IP 20

> Dimensions

Power (VA) in class 0.5 Weight
6 0.9 kg

T O O R D E R

Primary 5 A Secondary
5+5 A TCS 02N
5+5+5 A TCS 03N
5+5+5+5 A TCS 04N
Different primary
5+5 A TCS 02C
5+5+5 A TCS 03C
5+5+5+5 A TCS 04C

> Customized product


Model Secondary No. of CTs Ratio of
connected CTs connected

Example TCS 5A 2 100 A / 5 A


200 A / 5 A

142
ENERGY PERFORMANCE
Transformer short-circuit switch
Protection against the dangers caused by opening the secondary
circuit on low-voltage measurement CTs

POWER QUALITY
PRODUCT Mounting on DIN
rail or plate
ADVANTAGES

PROTECTS USERS

Transformers
AND EQUIPMENT

& shunts
AGAINST
OVERVOLTAGES
caused by opening the
CT 5 A or 1 A secondary

AUTOMATIC
SHORT-CIRCUITING
of CT secondary to which
it is permanently connected

Equipment connected on
CT secondary side can be
operated by user without Four terminals
supply interruption available for 6 mm2 wires Connection diagram

> General specifications


Reference standards: 61
NFC 15100 art 411-1) 42
24 29
Connections: double
terminals capable of receiving
6mm2 cables. DIN rail
33 28
mounting (supplied with fittings) 20
or plate mounting using 47
clamp bolts.
Weight: 90 g
23
TC
Operating conditions: 35
Temperature: -10C to +50C
Relative humidity: < 95%
S1
S'1
Protection: PRTC
S2
Protection rating: IP 20 S'2
Self-extinguishing polyamide
casing (UL 94VO) Instrument
Measurement current:
5 A/50 Hz or 1 A/50 Hz
Maximum permitted current: T O O R D E R
25 Aac
Peak voltage: 22 Vac Reference PRTC 1001

143