Temptek Manual Veteran LS
Temptek Manual Veteran LS
Temptek Manual Veteran LS
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-6352 fax: 317-881-1277
Service Department fax: 317-885-8683
www.TempTek.com
e-mail: sales@TempTek.com
INSTRUCTION MANUAL
VETERAN TEMPERATURE CONTROL UNIT
with LS SERIES INSTRUMENT
COVERING
INSTALLATION
OPERATION
MAINTENANCE
TABLE OF CONTENTS
1.0 GENERAL 9
1.1 Safety 10
1.2 Efficiency 10
1.3 Typical Label Placement 10
1.4 Component placement 11
2.0 INSTALLATION 13
2.1 General 14
2.2 To and from process connections 14
2.3 Water supply connection 15
2.4 Drain connection 15
2.5 Electrical connection 16
4.0 TROUBLESHOOTING 33
4.1 Unit will not start (Power light off) 34
4.2 Unit will not start (Power light on) 34
4.3 Unit stops 34
4.4 Unit overheats 35
4.5 Unit underheats 36
4.6 Pressure relief valve leaks 37
4.7 Cooling valve fault 38
5.0 MAINTENANCE 35
5.1 Pump seal replacement 36
5.2 Heater replacement 39
5.3 PVTTM cooling valve service 41
5.4 Probe calibration 43
5.5 Voltage changeover 45
5.6 Sensor probe service 48
5.7 Pressure switch service 50
5.8 Instrument service 51
5.9 Celsius temperature display 53
5.10 Electronic instrument repair policy 54
And procedure
6.0 COMPONENTS55
6.1 Mechanical system 56
6.2 Electrical system 58
8.0 APPENDIX 69
8.1 Specifications 70
8.2 Model # and suffix coding 71
8.3 Interpretation of process pressure gauges 72
8.4 Mold purge operation 73
8.5 Closed Circuit Operation 74
8.6 AS5 pump parts list - 1/2 HP to 1 HP 75
8.7 AS5 pump parts list - 1 1/2 HP to 3 HP 76
8.8 Parts list - LS instrument 77
UNIT INSTALLED TO 'TO PROCESS' TO 'WATER IN' ON 'FROM PROCESS' TO 'WATER OUT'
NO ...
PROCESS CORRECTLY? PROCESS MANIFOLD ON PROCESS MANIFOLD
YES
NO
NO
WATER SUPPLY YES
PRESSURE SWITCH OPEN
ENGAGE POWER
PRESSURE LOW? SUPPLY UNIT WITH 15 PSI
NO
INSTRUMENT DEFECTIVE
REPLACE
UNIT STOPS
NO
WATER SUPPLY YES
PRESSURE SWITCH OPEN
ENGAGE POWER
PRESSURE LOW? SUPPLY UNIT WITH 20 PSI
NO
INSTRUMENT DEFECTIVE
REPLACE
UNIT OVERHEATS
LOW PROCESS CHECK FOR A CLOSED KINKED HOSE OR BLOCKED WATER CHANNEL
YES OR OR
FLOW RATE? PROCESS VALVE EXCESSIVE PIPE FITTINGS IN TOOLING OR MOLD
NO
INSTRUMENT DEFECTIVE
REPLACE
UNIT UNDERHEATS
INSTRUMENT DEFECTIVE
REPLACE
Page: 8
Temperature Control Units : With LS Series Instrument
1.0 GENERAL
1.1 SAFETY
1.2 EFFICIENCY
1.3 TYPICAL LABEL PLACEMENT
1.4 COMPONENT PLACEMENT
1.1 SAFETY
1.2 EFFICIENCY
Warning Label
Summarizes the safety precautions
when unit is in use.
Pressure Gauges
Heater
Instrument
Cooling Valve
Temperature Sensor
Heating Cylinder
Electrical Panel
(Inside stainless steel cabinet.)
Cooling Cylinder
Pump
Pump Motor
Thermoformed
Cover Panel
Vented Stainless
Steel Cabinet
Caster
Electrical Panel
Lift-Off Cover
Panel
2.0 INSTALLATION
2.1 GENERAL
2.2 TO AND FROM PROCESS CONNECTIONS
2.3 WATER SUPPLY CONNECTION
2.4 DRAIN CONNECTION
2.5 ELECTRICAL CONNECTION
2.1 GENERAL
To process connection:
Connect to water in on process manifold
Drain connection:
Connect to one of the following:
(Depending on water supply source)
plants open drain
tower water system return
chilled water system return
B. Connect the units From Process port to the Water Out port on the
process manifold.
A. Connect the units Water Supply port to the plants city water, well
water, tower water or chilled water supply.
OPERATING TEMPERATURE
180F 190F 200F 210F 220F 230F 240F 250F
20 PSI 25 PSI 30 PSI 35 PSI 40 PSI 45 PSI 50 PSI 55 PSI
WATER SUPPLY PRESSURE
Figure 2.2A
D. CAUTION: The unit must never be operated with a closed drain line
valve. A closed drain line valve prevents adequate system cooling
and will lead to unit overheating. Overheating of the unit may lead
to unit damage and/or serious personal injury.
A. NEMA 1 MODELS
B. NEMA 12 MODELS
D. GENERAL
1. Make certain all ground Control circuit transformer fuse Figure 2.5C
3.0 OPERATIONS
3.1 GENERAL
3.2 MACHINE START UP/OPERATIONS PROCEDURE
3.3 INSTRUMENT OPERATION
3.4 SHUT DOWN/DISCONNECT PROCEDURE
3.1 GENERAL
A. SYSTEM FILL
2. Once the water supply source is open, the unit will fill
automatically. Allow a few moments for the unit to
completely fill. The operator can determine the unit is
properly filled when the To Process pressure gauge and the
From Process pressure gauge stabilize at equal or closely
similar pressure.
3. The operator must check for any water leakage in the units
mechanical system, the process, and throughout the plants
water supply system. If a water leak is observed, the
operator must disengage the water supply system, relieve
all pressure, and repair the leak. The operator must verify
the leak is repaired by refilling the system as outlined in this
procedure.
1. The operator must determine and set proper water flow rate
for the most efficient and trouble free operation.
Setpoint
Adjustment Machine
Buttons Status Lights
Temperature
Display
Figure 3.3A
Unit On/Off
Switch
A. INSTRUMENT START-UP
B. INSTRUMENT OPERATION
C. INSTRUMENT CONTROLS
the valve also allows cooling water flow from the water
supply source to enter the circulating system and mix with
the heated process water to reduce process temperature.
A. PRECAUTIONS/WARNINGS
4.0 TROUBLESHOOTING
4.1 UNIT WILL NOT START (POWER LIGHT IS NOT ILLUMINATED)
4.2 UNIT WILL NOT START (POWER LIGHT IS ILLUMINATED)
4.3 UNIT STOPS
4.4 UNIT OVERHEATS
4.5 UNIT UNDERHEATS
4.6 PRESSURE RELIEF VALVE LEAKS
4.7 COOLING VALVE FAULT ULU
A. One or more fuses at the main disconnect device are open (blown).
Determine continuity at each fuse. If continuity is not determined,
replace the fuse. Then determine cause of blown fuse.
A. The operator should determine the main power supply to the unit is
ON by an illuminated Power light on the display. With the main
power supply on, the unit will be prevented from starting by the
following conditions:
B. The operator should check the Power light on the display. The
operator should check the following conditions:
A. The unit has a 150 psi pressure relief valve mounted in the cooling
cylinder. If the valve is found to be leaking, the operator should
check the following:
5.0 SERVICE/MAINTENANCE
5.1 PUMP SEAL REPLACEMENT
5.2 HEATER REPLACEMENT
5.3 PVTTM COOLING VALVE SERVICE
5.4 PROBE CALIBRATION
5.5 VOLTAGE CHANGEOVER
5.6 SENSOR PROBE SERVICE
5.7 PRESSURE SWITCH SERVICE
5.8 INSTRUMENT SERVICE
5.9 CELSIUS TEMPERATURE DISPLAY
5.10 ELECTRONIC INSTRUMENT REPAIR POLICY & PROCEDURE
carbon/ceramic shaft
seal assembly including
a stationary member,
rotating member and
tension spring (figure
5.1A).
use, operating
temperature and water
quality. Poor water quality is the
primary reason for premature pump
seal failure.
1. Disengage process
operations and relieve all
system pressure.
Remove lift-off access panel Figure 5.1B
2. Disengage main power
supply. Verify the Power
light on the display is off.
7. Reduce the units set point, via the Down Arrow push button
to 32F.
c. Use a non-conductive
device, to adjust the
potentiometer.
Adjust the Calibration port Figure 5.4C
potentiometer until
the to process temperature on the display equals
the temperature of the ice bath.
10. Shut down the unit. The operator must be certain to remove
the 1/2 plug and replace the sensor probe. Restart
operations.
1. 240/3/60 to 480/3/60
2. 480/3/60 to 240/3/60
3. 480/3/60 to 208/3/60
B. For a field voltage changeover, the Motor Starter and Overload Block
1. Heater (rewiring)
2. Motor (rewiring)
3. Transformer (rewiring)
4. Motor starter and overload
block (replace)
5. Replace unit data tag with
tag stating new voltage and
amp rating. Figure 5.5A
Transformer
Wiring schematics for 240 and 480 volt heaters Revised 4/11 Figure 5.5B
208/240 460/480
4 4
6 7
5
1
L1
8
7
6
2
L2
9
8
3 1 L1
L3 2 L2
9 3 L3
Wiring schematics for 240 and 480 volt pump motors Figure 5.5C
6. Rewire the pump motor for the new voltage. Most Sentra
pump motors are dual voltage. Figure 5.5C shows the
wiring schematic for 240
and 480 voltages.
7. Thread one 1/2 nut onto the pressure switch and then
place the pressure switch through the panel in the original
mounting hole. Thread the second 1/2 nut from the bottom
of the pressure switch. Tighten to lock the pressure switch
in place.
9. Place the instrument into the panel mount, aligning the four
mounting stems. Once the instrument is aligned, tighten the
nuts to secure the instrument.
13. The operator can now start the unit as outlined in section 3
of this manual. The operator must reconfigure (if necessary)
the instrument to restore the preferred operating
parameters.
1. Disengage process
operations and relieve all
system pressure.
3. If you are sending your instrument back for repair, call the
Service Department for more information. Do not
disassemble the instrument.
D. Other Information:
6.0 COMPONENTS
6.1 MECHANICAL SYSTEM
6.2 ELECTRICAL SYSTEM
C. HEATER/PUMP DISCHARGE
CYLINDER. The heater/pump
discharge cylinder is a custom cast
tank. The tank is flanged mounted
to the pump casing. Reinforced
machined bosses accept the to
process/high temperature limit
sensor probe and the to process Heater Figure 6.1E
Discharge tank
connection (figure 6.1E).
PVT valve
Figure 6.1G
Page: 60
Temperature Control Units : With LS Series Instrument
7.1 PHYSICAL
To Process
Instrument
Drain
Pressure Gauges
From Process
26 5/8
Water Supply
L4
GROUND
1
1 1
2 2
3
3 3
1 MOL
5 8 8
6
ELECTRICAL
4
M1 H1 NOTE
7 9 7 9
2nd HEATER EXISTS
Temperature Control Units : With LS Series Instrument
50
MOLD PURGE SOLENOID (OPTIONAL)
MOTOR COIL
1 MOL
TAN 15 50
M1 PUMP MOTOR COIL
PINK Q
GRN 50 50
GROUND (INSTRUMENT)
ORE
M1 HEATER COIL
BRN 50
H1 HEATER COIL
UNIT
ON/OFF
Q
TEMPTEK, INC.
www.Temptek.com
Q
RED 19 WHT
ALARM
INACTIVE/ACTIVE M1
21 22 23 50
GRY 20 BLK ALARM BUZZER (OPTIONAL)
HEATER
TO PROCESS
PRESSURE GAUGE
TO PROCESS
CONNECTION
DRAIN CONNECTION
TO PROCESS SENSOR
HI TEMP SAFETY
DISCHARGE TANK
FROM PROCESS
CONNECTION
PRESSURE RELIEF
VALVE
FROM PROCESS
PRESSURE GAUGE
WATER SUPPLY
CONNECTION
SUCTION TANK
PUMP
DRAIN
TO PROCESS
FROM PROCESS
DRAIN
SENTRA '1"
DRAIN CONNECTION
SENTRA '2"
FROM PROCESS
CONNECTION
DRAIN CONNECTION
TO PROCESS
CONNECTION
TO PROCESS CONNECTION
C F POWER SELECT
CONNECTION
SETUP
FLOW
START STOP
PUMP ON LPM GPM
CAPACITY %
RS-485
FROM PROCESS
CONNECTION
WATER SUPPLY
CONNECTION
WATER SUPPLY
MANIFOLD
CONNECTIONS
TO PROCESS
CONNECTION
TEMPERATURE
POWER SELECT
TO FROM C F
PUMP ON
SETUP
NETWORK MACHINE
FLOW
LPM GPM
START STOP
CAPACITY %
DRAIN
RS-485
CONNECTION
FROM PROCESS
CONNECTION
WATER SUPPLY
CONNECTION
CONNECTION TO CONNECTION TO
21.5" 29" PLANT WATER SUPPLY PLANT DRAIN
Page: 68
Temperature Control Units : With LS Series Instrument
8.0 APPENDIX
8.1 SPECIFICATIONS
8.2 MODEL # AND SUFFIX CODING
8.3 INTERPRETATION OF PROCESS PRESSURE GAUGES
8.4 OPERATION OF MOLD PURGE
8.5 CLOSED CIRCUIT OPERATION
8.6 AS5 PUMP PARTS LIST - 1/2 HP TO 1 HP
8.7 AS5 PUMP PARTS LIST - 1.5 HP TO 3 HP
8.8 PARTS LIST - LS INSTRUMENT
8.1 SPECIFICATIONS
620 635 645 665 675 680 1020 1035 1045 1065 1075 1080 1090 10100 1620 1635 1645 1665
1
Heater kW 6 6 6 6 6 6 10 10 10 10 10 10 10 10 16 16 16 16
Process Pump HP /2
1 3
/4 1 11/2 2 3 1
/2 3
/4 1 11/2 2 3 5 71/2 1
/2 3
/4 1 11/2
GPM 20 35 45 62 75 80 20 35 45 62 75 80 90 100 20 35 45 62
PSI 30 30 30 30 30 30 30 30 30 30 30 30 34 54 30 30 30 30
Full Load Amperage 230 volt 17.0 17.8 18.6 20.2 21.8 24.6 27.0 27.8 28.6 30.2 31.8 34.6 40.3 47.1 42.0 42.8 43.6 45.2
2
@3/60hz 460 volt 8.5 8.9 9.3 10.1 10.9 12.3 13.5 13.9 14.3 15.1 15.9 17.3 20.2 23.5 21.0 21.4 21.8 22.6
Dimensions (inches) Height 281/4 281/4 281/4 281/4 281/4 281/4 281/4 281/4 281/4 281/4 281/4 281/4 44 44 281/4 281/4 281/4 281/4
Width 121/2 121/2 121/2 121/2 121/2 121/2 121/2 121/2 121/2 121/2 121/2 121/2 16 16 121/2 121/2 121/2 121/2
Depth 19 /2 1
19 /2 1
19 /2 1
19 /2 1
19 /2 1
19 /2 1
19 /2 1
19 /2 1 19 /2 1
19 /2 1
19 /2 1
19 /2 1
24 24 19 /2 1
19 /2 1
19 /2 1 191/2
3
Connections (inches) T/F 1 /41
1 /41
1 /41
1 /41
1 /41
1 /41
1 /41
11/4 1 /41
1 /41
1 /41
1 /41
2 2 1 /41
1 /41
1 /41 11/4
4
S/D /2
1 1
/2 1
/2 /2
1 1
/2 /2
1 1
/2 1
/2 1
/2 1
/2 1
/2 /2
1 1
/2 1
/2 1
/2 1
/2 /2
1 1
/2
5
Weight (pounds) Shipping 195 200 205 205 210 220 198 200 208 208 213 223 275 290 200 205 210 210
1675 1680 1690 16100 2435 2445 2465 2475 2480 2490 24100 3435 3445 3465 3475 3480 3490 34100
1
Heater kW 16 16 16 16 24 24 24 24 24 24 24 34 34 34 34 34 34 34
PSI 30 30 34 54 30 30 30 30 30 34 54 30 30 30 30 30 34 54
Full Load Amperage 230 volt 46.8 49.6 55.4 62.2 63.1 63.9 65.5 67.1 69.9 75.5 82.3 88.2 89.0 90.6 92.2 95.0 100.6 107.4
2
@3/60hz 460 volt 23.4 24.8 27.7 31.1 31.6 32.0 32.8 33.6 35.0 37.8 41.2 44.1 44.5 45.3 46.1 47.5 50.3 53.7
Depth 19 /2 1
19 /2 1
24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24
3
Connections (inches) T/F 11/4 11/4 2 2 11/4 11/4 11/4 11/4 11/4 2 2 11/4 11/4 11/4 11/4 11/4 2 2
4
S/D /2
1 1
/2 1
/2 /2
1 1
/2 /2
1 1
/2 1
/2 1
/2 1
/2 1
/2 /2
1 1
/2 1
/2 1
/2 1
/2 /2
1 1
/2
5
Weight (pounds) Shipping 220 225 285 300 270 275 280 285 290 295 310 280 285 290 295 300 305 320
Notes: 1. Derate heater output by 25% for 208/3/60 operation. 2. Consult factory for 50hz operations. 3. T - to process; F - from process. 4. S - water supply; D - drain. 5. Approximate unit shipping weight.
MODEL # SUFFIX
VT-1045-LX-41CX
HEATER KILOWATTS
6 = 6 KW
10 = 10 KW
16 = 16 KW
24 = 24 KW
36 = 36 KW
GPM BY HP
35 = 35 GPM @ 3/4 HP
45 = 45 GPM @ 1 HP
65 = 65 GPM @ 1 1/2 HP
75 = 75 GPM @ 2 HP
90 = 90 GPM @ 5 HP
100 = 100 GPM @ 7 1/2 HP
INSTRUMENTATION
LS = LS instrument
LX = LX instrument
300 = 300F instrument
VOLTAGE
2 = 208-230/3/60
3 = 380/3/50
4 = 460/3/60
5 = 575/3/60
6 = 415/3/60
ELECTRICS
1 = NEMA 1
2 = NEMA 12
J = JIC
VALVE SIZE
A = None
B = 1/4"
C = 3/8"
D = 1/2"
E = 3/4"
F = 1"
SPECIAL OPTIONS
Consult factory for more information
LINE TO DRAIN
CHECK VALVE
DRAIN CONNECTION Prevents compressed air from purging
unit
AVT VALVE
TO PROCESS CONNECTION
Closed to prevent purge of unit
SOLENOID VALVE
Opens to purge water to drain
BYPASS VALVE
FROM PROCESS
TO PROCESS WATER
SUPPLY
HEAT
DRAIN EXCHANGER
AVT VALVE
BYPASS VALVE
HEAT
EXCHANGER
FROM PROCESS
WATER SUPPLY
DRAIN
PART # DESCRIPTION
PART # DESCRIPTION
Note: Typical parts list shown. Please supply model and serial numbers when order-
ing parts
PART # DESCRIPTION
299082 Bracket, home switch SI MD-1642
781000 Caster 2 swivel #EY459R
1835050 Contactor #3030APS 30 AMP
1843601 Adapter coupling SI MD-1642
2735358 Sentra top SS - DWG #EP-103
2746237 Electrical enclosure door SS - DWG #EP-103
2761201 Electrical sub panel - DWG #EP-103
2851112 Gauge panel - DWG #EP-103
2877542 Base - DWG #EP-103
3581000 Pressure gauge 0-160 PSI 2 face
3708505 Plastic handle P2-41
3775510 Heater 10KW 2/4/3/60 square flange
3520005 Heater flange gasket 4.50 OD
4439900 Instrument kit SK-SI
4713377 Drip Cover SI MD-1642
6207000 Motor/pump assembly AS5 3/4HP ODP 230/460
414 Adapter iron C2-4551 AS5
771599 Pump case iron 137-001-166 AS5
3444400 Tank gasket 2-3/8 A-9159 AS5
3444401 Gasket, tank flange 4-1/2 AS5
4310602 Impeller B2-5264 4.5 AS5
4310611 Impeller AS5 #100345 4.5 mfg. After 2-97
4714466 Motor 3/4HP 113-000-354T 2/4/3/60
4757862 Motor AE5/AS5/A5W 3/4HP #S-2772R
5486522 Nut S-4989 AS5
5622271 O-ring case 116.000.252
6490000 Shaft seal niresist 5/8
6491000 Shaft seal ceramic 5/8
6748201 Cap screw #102RO3A2
9118502 Impeller washer #100301
7370000 Motor starter CR354AB3AA1B
1733456 Auxiliary contact kit #353XAAA
7541000 Panel mount pressure switch #82681
7732250 Heater cylinder AS5 #D2-1841
8240000 Transformer 9T58B42
8764940 AVT valve SI 1/2
8764939 AVT SI repair kit #EH-124
8764949 AVT drive kit for 3/8 and 1/2 valves #977700
9060000 Pressure relief valve #150 PSI
Page: 78
END
2013 Temptek, INC.
RE 1 02/13