Cardcblx: Chemetron
Cardcblx: Chemetron
CHEmETROn
Fire Systeml;
CARBON DIOXIDE FIRE PROTECTION -
The use of raised floors in computer rooms and similar facilities has
been the practice for many years. These spaces have traditionally been
used as areas in which to run cables point to point, interconnecting
power and control. They are also often the main means of distributing
cooling air to the equipment. When listed or approved cables are used?
the fire hazard from these is very small. However, fires at connecting
points have been reported. These areas can also become the repository
for extraneous material, and fires from this source have also been re-
ported.
CARDCBlX system is not easy. It was particularly difficult with Halon 1301 due to
the rapid discharge and relatively low concentration used. Loss of agent
became more acute.
1
could be detected first by the room detectors
or by detectors in the equipment. NFPA Stan-
dard No. 75, Protection of Electronic Com-
puter/Data Processing Equipment, calls for an -L I
early war&g smoke detection system to alert
personnel to a fire problem. Its design param-
eters would be different from a system used The purpose of using spot nozzles in underfloors
for extinguishing system release. Therefore, is to achieve a good circulation of the CO, with a low
we shall not discuss this problem here as it is velocity discharge. This is accomplished by using
one that transcends the scope of this bulletin. 5 Yz nozzles mounted horizontally and, in effect,
However, most of the underfloor CO, flooding gently laying the CO2 into the underfloor.
systems use the required smoke detection for
warning and use manual release for the CO,
flooding. Rate compensated thermal detectors
can provide back-up automatic detection.
CHEmETROn co 2 Application Bulktin
Fire Systems
This sketch shows the proper installation of In those situations where the underfloor is of
spot nozzles in underfloor areas. an irregular shape, it is best to divide the under-
floor into a separate volume per nozzle and use
teach volume to calculate its particular nozzle flow
r-ate.
The nozzles should be spaced approximately When the room above and the underfloor are
40 feet apart and 20 feet from a wall. flooded simultaneously, the discharge rate per
nozzle orifice may be increased. However, it is
The most commonly used radial nozzle will be suggested that the rate not exceed 50 pounds per
the 4-port, although 2-port and l-port radial noz- minute per orifice. At this rate, a $-port radial
zles will be used in situations where the shape of nozzle would flow 200 pounds per minute, which
the underfloor shows it to be practical. In those would still fall within the flow capacity of 1 inch
underfloor areas where the recommended nozzle pipe.
spacing cannot be followed due to size andlor
shape, the radial nozzles may be placed closer Raised floor stanchions may be used to sup-
together and the discharge flow rate adjusted port the CO, piping only if they are securely fas-
proportionately. tened to the subfloor and are of sufficient
strength.
The radial nozzle affords the opportunity to
orient the orifices to direct the CO, discharge most This sketch shows the installation of a radial
effectively. If there are openings in the floor near nozzle in the underfloor area.
the perimeter of the room, a CO, discharge aimed
directly at the wall will be deflected up and out - RAISED FLOOR
the openings into the room, causing excessive loss
of agent. The orifices should be directed to strike
the wall at an angle.
SUBFLOOR
/- SINGLE
FOUR
PORT
PORT
RADIAL
RADIAL
NOZZLE
NOZZLE
Fire System;
CARBON DIOXIDE FIRE SUPPRESSION -
co2 Automated
Systems For Computer
Information Storage
Operations
In trocfuc tion
a
CL for larger operations.
Since the units contain some semi-enclosed This is not new technology. For years many
equipment and many nooks and crannies, the use of other CO1 applications used higher CO, levels (thus
a 3-dimensional agent has a big advantage over reducing 0: levels) to effect quicker extinguishment.
water, which is 2-dimensional. For example, the standard CO, design method for
internal protection of metal clad switchgear calls for
Reducing the risk of releasing water in a com- a 3 minute discharge with high CO, levels. The
puter environment is another reason for using a combustibles in these cabinets are cables, arc guides,
gaseous extinguishant. molded plastics, etc., not dissimilar to the combusti-
bles we are discussing here.
However, if the area in which this equipment is
installed is sprinklered, sound fire protection practice CO, Calculation Method Recommended For
would be to extend coverage inside the storage The Library Storage Modules
modules to back up any gaseous agent protection.
Remember that a gaseous agents primary function For a typical unit, we have a gross volume of
is to protect continuity of operation of the facility, approximately 688 cubic feet for the LSM. There
while sprinklers are to protect the equipment and are some ventilation openings on the side, small
facility from a catastrophic loss. Therefore, they are cable openings in floor, and openings to adjacent
not mutually exclusive of one another. LSMs if two or more are coupled together.
CHEmErRon
Fire System; co2 Application Bulletin
Based on tests and considerable experience de- tion until operating personnel have time to re-
signing CO, extinguishing systems, we have deter- spond to the system actuation.
mined the CO, discharge required to flood the mod-
ule to a satisfactory level for suppressing surface Our analysis of the equipment protected here is
fires. involving solid materials when this level is held that deep-seated fires are unlikely. Power cut-off
for 3 minutes or more. can be accomplished through the fire system control
panel and/or a pressure operated switch. And there
The 3 minute discharge approach is consistent is little bundling of combustibles to be concerned
with the IRI Interpretive Guide P-6.2 Para. 2-3.5.5. about.
l There is a tight bundling of cables or similar In this case, we consider that the worst case
material, requiring some time for the agent to condition is that the CO, discharged inside the mod-
penetrate the bundle; or time is needed for the ule will totally leak from same, be picked up by the
fire supporting oxygen in the air spaces between room air conditioning and then circulated and mixed
the cable components to be consumed by the in the air that serves the room in which the module
fire. is installed.
There is really no difference here than if the It is recommended that the CO, discharge be
space under the raised floor were to be protected by odorized. It is also recommended that the system be
C02, which has been done for many years. (For this arranged to prevent automatic discharge without
application refer to Chemetron Bulletin #0600, Pro- warning when someone is inside a module.
tection of Spaces Beneath Raised Floors.)
Fire System;
CARBON DIOXIDE FIRE PROTECTION -
The incidence of major fires in such facilities is rare, but the ability
to continue vital operations without the aid of the computer continues
to diminish. Chemetron Fire Systems has addressed the problem of
providing active fire protection for the central computer with a scheme
that not only prevents the possibility of catastrophic loss, but is also
people compatible and environmentally acceptable.
4801 Southwick Drive Fires involving computer equipment, starting small and evolving
Third Floor slowly, require early detection that can result in their extinguishment
Matteson, IL 60443 simply by removal of power or use of a hand-held fire extinguisher.
Telephone: 708/748-l 503
Fax: 7081748-2847
0 1996 CHEMETAON FIRE SYSTEMS, all rights reserved. (9196)
CHEWlETROll
Fire Systemi co2 Application Bull&in
Relatively inaccessible portions of the computer Under floor Pro tee tion
room and its facilities, such as the space beneath the
raised floor, the interior of automated information In the 1960s, the popular choice for protecting
the space beneath the raised floor of a computer room
storage systems, and possibly some equipment enclo-
sures, necessitate special fire protection. was total flooding with carbon dioxide. This was re-
placed with the advent of Halon systems, which
totally flooded the entire room, underfloor included.
This bulletin details the innovative advantages
and features of the solutions that Chemetron Fire
Systems recommends for these protection needs. However, in the concept of Protection for the
1990s as outlined here, protection of the underfloor
space by gaseous agent flooding is vital.
Sprinkler Pro tee tion for Computer Areas
W/r]) the need for protection ? Fire incidents in-
Providing automatic sprinklers throughout the volving wiring, cables, debris, etc., in the underfloor
computer area ensures against a catastrophic loss. space are rare. But tests have shown that if ignited,
The reliability of sprinkler systems is well established the combustibles beneath the floor can generate sig-
and incidents of accidental water discharge from such nificant fires. With the vital computer equipment in-
systems are extremely rare. However, Chemetron stalled directly over, and often receiving its cooling
Fire Systems has recognized that computer operations air from, the underfloor space, this exposure without
managers are concerned about the effects of water on some form of fixed fire suppression is unacceptable.
computer equipment. This is addressed by incorpo-
rating a Double Interlock Pre-Action Sprinkler Sys- Installation of an early warning detection system
tem as part of the Protection for the 1990s concept. will provide early identification of a problem under
the raised floor. But what to do about it? Shut down
Sprinklers are installed to light hazard occupancy the room ventilation and possibly shut off the power?
standards or to the requirements of the Authority Yes, but how do you find and deal with a fire in a
Having Jurisdiction. A separate fire detection sys- smoke filled space thats often thousands of square
tem, electrically operated and utilizing Chemetronics feet in area? Hand portable extinguishers would only
Series 600 heat detectors, is designed to detect a fire be effective if the agent could be applied directly to
before a sprinkler head has operated. Electrical detec- the seat of the fire. Its unlikely this could be easily
tion of the fire releases water to the first stage of the located.
pre-action valving while manual extinguishment of the
fire is attempted. If the fire progresses to where a However, if carbon dioxide flooding fills the
head operates, the air in the sprinkler piping (which entire underfloor space to an extinguishing level and
serves to supervise the piping) is released; water this inerted atmosphere is maintained to ensure extin-
flows into the sprinkler piping and is discharged from guishment of any deep-seated burning material,
the open sprinkler(s). theres no need to pinpoint the exact location of the
fire. The entire space is protected.
Neither accidental operation of the pre-action sys-
tem valving nor accidental operation of the heat W@ Carbon Dioxide? While total flooding of a
actuated fire detection system can result in release of normally occupied space with CO, is to be avoided,
water. But a significant fire can be quickly control- the amount of CO, used to flood just the raised floor
led by the sprinklers when both electrical detection space, even if distributed throughout the computer
and sprinkler heads are operated, thus ensuring room, should not present a personnel risk.
against a major loss.
CHEmETROn
Fire Systems co 2 Application Bulktin
CO, is the most efficient gaseous agent avail- vent effective portable extinguisher use, or their
able for extinguishing deep-seated burning materi- size may necessitate agent requirements that
al fires. It is dry, three dimensional, and will sur- exceed the extinguishing capacity of portables.
round and easily penetrate cable bundles. It will Internal gaseous agent flooding, with detection
not break down in an electrical fire and it is a matching the protection needs, is the answer. For
nonconductor environmental reasons, carbon dioxide is the agent
of choice.
Good design of the CO, underfloor flooding
system will ensure that most of the CO2 discharg- Cabinet Protection: A question usually
ed is retained under the floor. raised with CO, cabinet flooding is: Is it effective
and would an inadvertent CO, discharge have a
Why be concerned with system design? A to- detrimental effect on the protected equipment?
tally effective CO, underfloor flooding system is
one where the CO, discharged is properly distrib- The best published tests verifying CO,s effec-
uted, effectively applied, and retained in the space tiveness and lack of detrimental side effects were
as long as possible. Since the gas is much heavier those done at the Allianz Centre for Technology,
than air and the underfloor space resembles a Mumch, Germany2.
large tub, why should this be difficult?
Designing cabinet protection, due to varied
To achieve the flooding concentration within cabinet openings and extensive ventilation require-
the code-specified time period, high discharge ments, involves factors not properly covered by the
velocities have often been used. This fast moving CO, system standards. Chemetron Fire Systems
stream of CO, gas can deflect off cables, structure, Engineering has the experience to help develop
walls, etc., and exit through the myriad of ventila- proper design parameters for effective cabinet
tion openings in the floor. Too much of the gas protection. For further information, see Computer
ends up in the room and not under the floor, re- Operations Bulletin #0615, Critical Computer
sulting in inadequate protection. This, however, and Electrical Control Cabinets.
is not necessary. Chemetron Fire Systems and its
predecessor companies have developed innovative Automated Information Storage Systems:
techniques to ensure efficient gas application and These systems, mounted on the raised floor and
retention in the protected space. This is covered configured so that a number of units can be nested
by Computer Operations Bulletin #0600, Protec- together, centralize the storage of large amounts
tion of Spaces Beneath Raised Floors. of data. The loss of this data in a fire could be
catastrophic for the business owner. Internal
protection utilizing carbon dioxide flooding sys-
Cabinef & Specialized Enclosure Protection tems is particularly effective in quickly extinguish-
ing expected internal fires.
The presence of ultra-important cabinetized
computer components and modern automated in- Testing of a typical unit to establish the CO,
formation storage systems in the computer room discharge requirements, verify lack of detrimental
may necessitate specially designed protection. effects on the equipment or stored data, and estab-
Automatic sprinklers, while excellent backup pro- lish proper safety procedures has been done. Ap-
tection cannot operate quickly enough to prevent propriate information on the use of CO2 to protect
major damage in case of fire. Equipment cabinets these units is covered by Computer Operations
or enclosures prevent room sprinkler water dis- Bulletin #0605, Automated Information Stor-
charges from reaching internal fires. age Sys terns.
Good fire protection practice dictates that the Use of aspirating type detection, such as the
computer room sprinkler system be extended into Cirrus IFD with its ability to function in high air
the automated information storage system (AISS) flow situations, can be an important part of the
modules to back up the CO, flooding system. The detectlon scheme. However, we do not recom-
CO, system utilizes its own smoke detection sys- mend using this type of detection to actuate the
tem for actuation. Actuation of the CO, system fire protection system.
will also initiate release of the water in the sprin-
kler piping within the protected area. The sprin- Smoke detectors, cross-zoned ionization and
kler system design is usually based on Ordinary optical detectors can serve as the actuating meth-
Hazard, Group 1 occupancy. od for the underfloor flooding and automated in-
formation storage system automatic protection. It
When no gaseous agent room flooding system may or may not be as a part of the overall early
is installed in the computer room, it is especially warning detection scheme.
important to identify critical equipment requiring
special attention to ensure that proper protection The development of the detection plan by an
measures are provided. Such protection may be experienced and qualified professional is mandato-
an essential part of Protection for the 1990s. ry to ensure proper detection without false actua-
tions.
Detection
Critical Facilities
Early detection of fire in the computer room
is another essential part of the Protection for A fire risk analysis of critical facilities that
the 1990s concept. If a fire, such as one involv- must be occupied may indicate the need for a peo-
ing smoldering electrical equipment, is detected in ple compatible gaseous agent room flooding sys-
its incipient stage, it can often be extinguished tem. -4 Chemetron system using FM-200 will fulfill
simply by cutting off the electrical power source, this need. Detailed information is available on
or by the application of CO, from a hand portable same from Chemetron Fire Systems or one of our
extinguisher. engineered systems distributors.
Fire System6
CARBON DIOXIDE FIRE SUPPRESSION -
Much of this success can be traced to the use of better fire detec-
tion, as well as the universal acceptance of protecting these facilities with
Halon 1301 flooding systems, backed up by pre-action sprinklers.
Although the use of Halon 1301 is now being phased out due to
environmental concerns, there is no need for these critical operations to
accept a significantly lower level of fire security.
When halon was used, the entire computer room was flooded,
including the space beneath the raised floor. This ensured that the three-
dimensional gas reached all potential points of fire origin, especially
those within the cabinets of the computer equipment. Without room
flooding, how can these critical internal areas be protected? Sprinkler
discharges on the outside of the cabinets wont do the job.
CARIX!X It should be noted that cabinet flooding systems were used before
halon room flooding systems proved their worth. These utilized carbon
dioxide (CO,), and they were combined with carbon dioxide flooding of
the space under raised floors. This resulted in using little enough CO,
that concentrations throughout the occupied portion of the room were not
4801 Southwick Drive
high enough to create a personnel hazard. At the same time, critical
Third Floor
components, such as central processors and hard-to-reach areas in
Matteson, IL 60443
underfloor spaces, had engineered fixed fire suppression.
Telephone: 7081748-I 503
Fax: 708/748-2847
D 1996 CHEMETRON FIRE SYSTEMS, all rights reserved. (9196)
CHEmETROn
Fire System; co2 Application Bulktin
A major user of such protection was the U.S. In the last 20 years, we have fortunately learned
Navy, whose design standard (Tech Note 38) called many things that make CO, cabinet flooding more
for CO, flooding of cabinets over 100 cu.ft. and practical today. The problems have not all gone
underfloors over 2,000 cu.ft. away, but most have become manageable.
The use of CO, for cabinet flooding was not We owe a debt in this regard to a test program
without problems, however. One concern was the done in Europe by Allianz Loss Control Services,
inherent cooling caused by a CO, discharge. When Munich, with the report, Fire and Extinguishing
a cylinder of COZ, stored at 70F, is discharged, Tests on Computer Equipment, as published by
approximately 18% of its contents will be discharged TELA Versicherung AG, Munich, reporting on same.
as dry ice particles at -109F. These very cold parti-
cles - although they quickly sublime to gas - will They tested extinguishment of computer equip-
refrigerate the air in the cabinets. If the components ment fires in a number of configurations, demon-
are cooled below the dew point, moisture (distilled strating that CO, discharges quickly extinguished the
water) will precipitate on their surfaces, requiring that fires with concentrations well under 50%, and in a
the equipment be de-energized and dried before re- very short time period as well. The result: A devel-
turning it to service. On a number of installations, oping consensus that the combustibles present are
this was dealt with by adding heat to the CO, dis- more surface burning and that reasonable CO, appli-
charge to have it vapor only; however, this vaporiz- cation times will suffice.
ing equipment added substantially to the cost and
maintenance of the system. Managing the inherent A major insurer has indicated that holding a 50%
cooling and its effects is a more practical approach. CO: concentration for 3 minutes, with the power shut
down, is a reasonable basis of design. We agree.
Another concern was the possibility of a buildup
of static electricity. As it is well known that dis- Ideally, we would like to be able to put just
charging an ungrounded CO, fire extinguisher can enough CO, in a cabinet to reach 50% and then have
create a high potential for static electricity, there was it stay there. However, with the equipment setting on
also fear that this could be the case on a fixed pro- a raised floor, cooling air discharging into the cabinet
tection system discharge. However, extensive expe- bottom, and cabinet ventilation openings at the top
rience on grounded, fixed CO, systems has shown and sides, the task of flooding the cabinet with CO,
this to be an unfounded concern. gas in such a way that most of the gas is kept inside
is not easy.
Determining the basis for the system design for
CO, cabinet flooding was another problem. The In the recent testing of a component of an auto-
NFPA Standard for carbon dioxide extinguishing mated information storage system, we were faced
systems specified a 50% CO, design concentration for with cooling air from the floor and component fans
Miscellaneous Electrical Equipment, with a need to on the sides, plus significant uncloseable openings
hold this concentration long enough to ensure total near both the top and the bottom. The only hope of
extinguishment. Some interpreted the combustibles retaining the CO, within the enclosure was a gentle,
involved to be of a deep-seated burning nature, re- billowing discharge that distributed the CO, cooling
quiring the CO, holding time to be the minimum 20 as much as possible without forcing the CO2 out the
minute time specified in Standard 12 for deep-seated openings.
fires. Holding 50% CO, in a cabinet for 20 minutes
obviously would result in an impractical system.
CHErnETROII
Fire Systemg co 2 Application Bull&in
Computer Operations Bulletin #06 1.5 Page 3
We found a way to dissipate energy from the dis- Evaiua ting Pro tee tion of
charge and use air flow to help retain the discharge. Specific Equipment
This was possible because of new nozzles developed
since the earlier days of cabinet flooding. To properly evaluate the protection of a specific
piece of equipment, the operator should obtain the
The results obtained in full discharge testing indi- following:
cated good CO, retention. Metal components cooled
only to where they were cool to the touch, but show- I. Drawing or photographs of equipment showing ar-
ed no moisture condensation. No damage to equip- rangement of internal components, cabinetry. and
ment, tapes, or data was detected. ventilation openings in the cabinet.
Automated Information