Sensepoint XCD

Flammable, toxic and


Oxygen gas detector for
industrial applications
Sensepoint XCD

One-Stop Shop
Flammable (catalytic or infrared), toxic and
The Sensepoint XCD range provides
Oxygen versions available
New and retrofit applications
comprehensive monitoring of flammable,
Suitable for indoor or outdoor use
Stainless steel or aluminium toxic and Oxygen gas hazards in potentially
explosion-proof housing options
IP66 as standard explosive atmospheres, both indoors and
Proven and Reliable outdoors. Users can modify detector
Sensor Technology
SurecellTM electrochemical sensors
Poison resistant flammable sensors
operation using the LCD and magnet
Long life sensors switches without ever needing to open the
Global Approvals
European, North American and Asian unit. This enables one-man, non-intrusive
Compliant with ATEX, IECEx, UL/c-UL, KTL,
PA, GB and CCCF standards operation and reduces routine maintenance
Easy to Use time and costs.
User friendly and intuitive tri-colour
backlit display with digits, bar graph
and icons A tri-colour backlit LCD clearly indicates the Sensepoint XCD has an integral mounting plate
Fully configurable via magnetic switches units status at a glance, even from a distance. for surface mounting or can be mounted to a
Selectable sink or source 4-20mA output A steady green backlight indicates normal horizontal or vertical pipe using the optional
Auto-inhibit during maintenance operation, flashing yellow indicates fault and pipe mounting bracket. Electrical installation
Optional MODBUS communications for remote flashing red indicates an alarm. can be made using either conduit or cable
diagnostics/configuration
with suitable mechanical protection. Two M20
All detectors are supplied pre-configured or NPT entries are provided (depending
Cost Effective and include 2 programmable alarm relays,
Common transmitter platform on certification). A weatherproof cap is also
1 programmable fault relay as well as an included for use in the harshest outdoor
Minimal training required
industry standard 4-20mA output (sink or conditions. Other optional accessories include
Reduced spares
Non-intrusive, one-man operation source selectable) and MODBUS. a sunshade/deluge protection, duct mounting
Plug-in sensor replacement The scale, range, relay operation, alarm set kit and collecting cone.
Optional MODBUS multi drop option offers point and electronic tag number of the detector
cabling savings Sensepoint XCD ensures easy installation
can be adjusted using the transmitter's LCD and the fastest routine operation by removing
Simple Installation and non-intrusive magnetic switches. Outputs the need for hot work permits in hazardous
Plug-in display module removes to give access are automatically inhibited during adjustment, areas. Using easy to replace plug-in sensors,
to terminal area thereby reducing the risk of false alarm at the downtime is also reduced and on-going costs
Integral mounting bracket control panel during maintenance. are minimised through the use of poison
2 x M20 or NPT cable/conduit entries resistant flammable sensors and patented
(certification dependent)
Surecell toxic sensors.
Removable plug/socket type terminal blocks for
ease of wiring
Sink/source switch to suit preferred wiring
topology
8.
Range of Optional Accessories 11.
Sunshade/deluge protection 5.
4.
Duct mounting kit
Calibration gas flow housing
Collecting cone 10.
3.
2.
1.

1. Cover
2. Display module
6. 3. Terminal area
4. Blanking plug
5. Transmitter
Typical Applications
Industrial manufacturing facilities Refineries and chemical plants 7. 6. Plug-in XCD sensor
Power plants Onshore oil and gas terminals 7. Sensor retaining ring
Waste water facilities Production platforms 8. Integral mounting plate
Utilities Exploration and drilling 9. Weather protection assembly
Food and beverage production 9. 10. Cable/conduit entry (x2)
11. Certification label
Sensepoint XCD Overview

There are three different types of the XCD


Sensepoint XCD Sensor Families, Gases and Ranges
transmitter for use with three different families
of sensors. User Selectable Default Selectable Cal
Gas Steps Default Cal Point
Full Scale Range Range Gas Range
The mV type transmitter is for use with the Catalytic Bead Sensors
mV family of XCD sensors including catalytic
Flammable 1 to 8* 20 to 100%LEL 100%LEL 10%LEL 50%LEL
sensors to detect flammable gases in the
range 0-100%LEL and infrared (IR) sensors for Infrared Sensors

mV
detection of Hydrocarbon gases in the range Methane 20 to 100%LEL 100%LEL 10%LEL 50%LEL
0-100%LEL. Two IR Hydrocarbon sensors are 50%LEL
Sensor Family
Propane 20 to 100%LEL 100%LEL 10%LEL
available; one linearised to Methane and one Carbon Dioxide 2.00%Vol. only 2.00%Vol. n/a 30 to 70% of selected
1.00%Vol.
linearised to Propane. The Propane version has full scale range
linear cross sensitivities factors for Ethylene, Electrochemical Sensors
Butane and Pentane. There is also an IR CO2 Hydrogen Sulphide 10.0 to 100.0ppm 50.0ppm 0.1ppm 25ppm
sensor available in the range 0-2%Vol.
EC

Carbon Monoxide 100 to 1,000ppm 300ppm 100ppm 100ppm

The EC type transmitter is for use with Hydrogen 1,000ppm only 1,000ppm n/a 500ppm
the EC family of XCD sensors including Nitrogen Dioxide 10.0 to 50.0ppm 10.0ppm 5.0ppm 5.0ppm
Carbon Monoxide (CO), Hydrogen Sulphide,
O2

Oxygen 25.0%Vol. only 25.0%Vol. n/a 20.9%Vol. (Fixed) 20.9%Vol.


(H2S), Nitrogen Dioxide (NO2) and Hydrogen
(H2).
The Oxygen transmitter is for use with the
Oxygen (O2) XCD sensors. mV Transmitter EC Transmitter O2 Transmitter

A transmitter can auto-recognise any sensor


from within its sensor family. The sensor simply
plugs into the bottom of the transmitter and
the transmitter automatically configures itself
accordingly.
IR Methane %LEL

IR Propane %LEL

IR Carbon Dioxide %Vol

Catalytic Flammable 1* to 8* %LEL


(default CH4 0-100%LEL)

EC H2S

EC CO

EC H2

EC NO2

EC O2

Ready, Steady, Go!


Sensepoint XCD uses three instantly
recognisable traffic light colours to indicate
its status. The large tri-colour backlit LCD
is steady green to indicate normal operation,
flashes yellow to indicate a fault/warning
and flashes red to indicate an alarm. This
allows anyone in the area to clearly see at a
glance the status of any detector. This can be
Normal Fault/Warning Alarm
particularly useful to identify detector status if
the detector is located in a difficult to access
area or if a number of detectors are located in
the same area.
Installation

Outline Installation Dimensions Installation Options

The Sensepoint XCD transmitter has an integral mounting plate consisting of four mounting holes
on the transmitter body. The transmitter may be fixed directly to a surface mounting, or to a
horizontal or vertical pipe/structure, 40.0-80.0mm (1.6 to 3.1") in diameter/cross section.
The pipe mounting bracket accessory (optional) may be used for this purpose.

User cable entries shown (2 x M20) are for ATEX/IECEx version enclosures. UL/c-UL versions
have 2 x "NPT conduit entries. A suitable blanking plug is supplied which must be used to
seal any unused entry. The blanking plug must be suitably sealed to maintain the IP rating of
the detector.

Wall Mounted

8.5 80 12
106

225

Vertical or horizontal pipe mounted


(Using optional pipe mounting bracket)

164 99

All dimensions in mm.


1" = 25.4mm
Duct Mounted

Other Accessories

Various accessories are available for different applications:

Sunshade/Deluge protection Collecting Cone Gassing Cap


Installation

Electrical Wiring Schematics

Sensepoint XCD is designed for use in potentially explosive atmospheres. As such, installation The Sensepoint XCD transmitter may be
should follow national guidelines using suitable mechanically protected cable and glands or wired in either Current Sink or Current
conduit. Use 0.5mm2 (20AWG) to 2.5mm2 (~13AWG) cross sectional area cable as needed Source configuration. These two options
to ensure minimum operating voltage at the detector, depending on installed cable length. are offered to allow greater flexibility in
Cable diameter should be selected to maintain the minimum required voltage for the longest the type of control system that it can be
installed cable length under maximum power. used with. Sink/Source is selectable via
the switch located on the back side of the
display module; accessible by removing
Terminal Module Connections the display module during installation/
Terminal Number Marking Connection Description commissioning.

1 24V +V Supply Controller Connections


2 0V -V Supply (0VDC) Controller Detector

3 4~20mA Current Output Signal +VE +VE


1 1
4 COM Drain MODBUS RTU.
5 TxD MODBUS B (+) RS485 (Optional)
Signal Signal
6 RxD MODBUS A (-) 2 3
7 RLY1/NC Normally Closed Programmable Relay 1 RL
8 RLY1/COM Common (Default A1) -VE -VE
3 2
9 RLY1/NO Normally Open
10 RLY2/NC Normally Closed Programmable Relay 2
11 RLY2/COM Common (Default A2)
12 RLY2/NO Normally Open XCD Source Configuration
13 RLY3/NC Normally Closed Programmable Relay 3
14 RLY3/COM Common (Default Fault)
15 RLY3/NO Normally Open Controller Detector

Internal Earth/ +VE


1 1
+VE
Ground Point
RL
Signal Signal
2 3

24V NC 7
1 -VE -VE
2 0V RLY1 COM 8 3 2
4~20mA NO 9
3
COM NC 10
4 RLY2
TxD Digital COM 11
5 Comm
RxD NO 12
6
NC 13 XCD Sink Configuration
RLY3 COM 14
NO 15 SINK
Note: Terminate cable screen at the
SOURCE
4-20mA MODE detector or the controller, not both.

Terminal Module Puck Rear View


Note: Terminal Blocks are plug/socket type
and may be removed to ease wiring.

Typical Cable Lengths

Typical Cable Data Maximim Cable Length


Cable Size Cable Resistance Catalytic EC IR
(Cross Sectional Area)
/km /mi Metres Feet Metres Feet Metres Feet
0.5mm2 (20AWG*) 36.8 59.2 356 1167 478 1568 420 1379
1.0mm2 (17AWG*) 19.5 31.4 671 2201 902 2956 793 2599
1.5mm2 (16AWG*) 12.7 20.4 1031 3387 1384 4549 1217 4000
2.0mm2 (14AWG*) 10.1 16.3 1296 4239 1741 5694 1531 5006
2.5mm2 (13AWG*) 8 12.9 1636 5356 2197 7194 1932 6326

Note: Table given for guidance only. Users should calculate maximum distances using actual
data for cable being used. Typical calculation assumes minimum guaranteed controller supply
of 24VDC, minimum detector voltage of 16VDC and maximum power supply under full alarm.
RL (max) is 250ohms.
Technical Summary

Sensepoint XCD Detector


Use 3 wire, 4-20mA and RS485 MODBUS output fixed point detector with in-built alarm and fault relays for the protection of personnel and plant from flammable, toxic and
Oxygen hazards. Incorporating a transmitter with local display and fully configurable via non-intrusive magnetic switch interface. Wide range of sensors available.
Electrical
Input Voltage Range 16 to 32VDC (24VDC nominal) for ATEX/IECEx/AP Versions
12 to 32VDC (24VDC nominal) for UL/CSA version
Max Power Consumption Maximum power consumption is dependent on the type of gas sensor being used. Electrochemical cells = 3.7W, IR = 3.7W
and catalytic = 4.9W. Maximum inrush current = 800mA at 24VDC
Current Output Sink or source
0.0<1.0mA Fault
2.0mA or 4.0mA (17.4mA) Inhibit (during configuration/user settings)
4.0mA to 20.0mA Normal gas measurement
22.0mA Maximum over range
Terminals 15 x screw terminals suitable for wire diameter 0.5mm2 to 2.5mm2 (20AWG to 13AWG)
Relays 3 x 5A@250VAC. Selectable normally open or normally closed (switch) and energised/de-energised (programmable)
Alarm relays default normally open/de-energised. Fault relay default normally open/energised
Communication RS485, MODBUS RTU (Optional)

Construction
Material Housing Epoxy painted aluminium alloy LM25 or 316 stainless steel
Sensor 316 stainless steel
Weather Protection Plastic
Weight (approx) Aluminium Alloy LM25 2.0kg (4.4lbs)
316 Stainless Steel 5.0kg (11lbs)
Mounting Integral mounting plate with 4 x mounting holes suitable for M8 bolts
Optional pipe mounting kit for horizontal or vertical pipe 1.5 to 3" (2" nominal)
Entries European ATEX/IECEx versions: 2 x M20 cable entries
North American UL/c-UL versions: 2 x "NPT conduit entries. Suitable blanking plug supplied for use if only 1 entry used. Seal to maintain IP rating
Detectable Gases and XCD Sensor Performance
Gas User Selectable Default Steps User Selectable Default Cal Response Accuracy Operating Temperature* Default Alarm Points
Full Scale Range Range Cal Gas Range Point Time (T90)
Secs Min Max A1 A2

Electrochemical Sensors
Oxygen 25.0%Vol. only 25.0%Vol. n/a 20.9%Vol. (Fixed) 20.9%Vol. <30 <+/-0.5%Vol. -20C / -4F 55C / 131F 19.5%Vol. 23.5%Vol.
Hydrogen Sulphide 10.0 to 100.0ppm 50.0ppm 1ppm 25ppm <50 <+/-1ppm -20C / -4F 55C / 131F 10ppm 20ppm
Carbon Monoxide 100 to 1,000ppm 300ppm 100ppm 100ppm <30 <+/-6ppm -20C / -4F 55C / 131F 100ppm 200ppm
30 to 70% of selected
Hydrogen 1,000ppm only 1,000ppm n/a full scale range 500ppm <65 <+/-25ppm -20C / -4F 55C / 131F 200ppm 400ppm
Nitrogen Dioxide 10.0 to 50.0ppm 10.0ppm 5.0ppm 5.0ppm <40 <+/-3ppm -20C / -4F 55C / 131F 0.7ppm 2.0ppm
or +/-20%

Catalytic Bead Sensors 25 to 95% of selected


Flammable 1 to 8* 20 to 100%LEL 100%LEL 10%LEL full scale range 50%LEL <25 <+/-1.5%LEL -20C / -4F 55C / 131F 20%LEL 40%LEL

Infrared Sensors
Methane 20 to 100%LEL 100%LEL 10%LEL 30 to 70% of selected 50%LEL <30 <+/-1.5%LEL -20C / -4F 55C / 131F 20%LEL 40%LEL
Propane 20 to 100%LEL 100%LEL 10%LEL full scale range 50%LEL <30 <+/-1.5%LEL -20C / -4F 55C / 131F 20%LEL 40%LEL
Carbon Dioxide 2.00%Vol. 2.00%Vol. n/a 1.00%Vol. <30 <+/-0.04%Vol. -20C / -4F 55C / 131F 0.40%Vol. 0.80%Vol.
- Rising Alarm - Falling Alarm
NOTES
Performance data is: 1. Taken at nominal 20C, 50%RH. 2. Applicable over the range 10 to 90% full scale. 3. Measured on units calibrated at 50% full scale. 4. Accuracy at 10% of default full scale (typical A1 alarm) of applied gas, or
minimum (whichever is greater). 5. Measured at 500ml/min for IR, Toxics and O2, 1 Ltr/min for Catalytic bead using the calibration cup (S3KCAL).
*Extended operating temperature range of -40C to +65C (-40F to +149F) for all sensors except for IR and H2 EC sensors, with an accuracy of +/- 30% of applied gas from -20C to -40C (-4F to -40F) and +55C to +65C
(+131F to +149F). Long term operation at this range may cause decline in sensor performance. Contact Honeywell Analytics for any additional data or details.

Certification
European ATEX II 2 GD Ex d IIC Gb T6 (Ta -40C to +65C) T5 (Ta -40C to +75C) Ex tb IIIC T85C Db IP66 T100C (Ta -40C to +75C)
International IECEx Ex d IIC Gb T6 (Ta -40C to +65C) T5 (Ta -40C to +75C) Ex tb IIIC T85C Db IP66 T100C (Ta -40C to +75C)
China GB Ex d IIC T4 GB3836.1&2 -2000, PA, CCCF
Korea KTL Ex d IIC T6 (-40C to +65C)
North America UL/c-UL - Class I, Division 1, Groups B, C and D, Class I, Division 2, Groups B, C & D, Class II, Division 1, Groups E, F & G, Class II, Division 2, Groups F & G.
-40C to +65C
EMC EN50270:2006 EN6100-6-4:2007
Performance ATEX, EN60079-29-1:2007 (flammable), EN45544 (Toxic), EN50104 (Oxygen), EN50271
China: PA Pattern Measurement (for transmitter and toxic gas sensors)
CCCF Shenyang for Flammable (fire dept approval)
CSA C22.2-152
Technical Summary cont.
and Ordering Information

Environmental

IP Rating IP66 in accordance with EN60529:1992

Certified Temperature Range -40C to +75C (-40F to +167F)


Note: The detector display may become illegible at temperatures below -20C, but the detector continues its gas monitoring function. The display is not damaged and recovers when the
temperature rises back above -20C.

Operating Humidity Continuous 20-90%RH (non-condensing), Intermittent 10-99%RH (non-condensing)

Operating Pressure 90-110kPa (EC Toxic Sensors), 80-12kPa (EC Oxygen, Catalytic Bead and Infrared Sensors)

Storage Conditions -25C to +65C (-13F to 131F)


Ordering Information

Standard Supply Sensepoint XCD is supplied complete with integral wall mounting plate, 2 x M20 cable entry (ATEX/IECEx) or 2 x NPT conduit entries (UL/cUL),
1 x M20 or 1 x NPT plug, Allen key for locking screw, weatherproof cap, operating magnet, sensor cartridge with retainer, quick start guide and instruction
manual CD. Default settings, ranges and calibrations are 100% tested at the factory. Each unit is supplied with a calibration and test certificate.

Shipping Details Shipping carton dimensions: L312mm (12.3) x W223mm (8.8) x D110mm (4.3) Approximate weight: Aluminium 2.5kg (5.5lbs), Stainless Steel 5.5kg (12.1lbs)

Enclosure Material Sensor Type

L- LM25 F- Flammable Catalytic Bead


S- Stainless Steel R- Flammable IR Methane %LEL
Sensepoint XCD
P- Flammable IR Propane (Cross Sensitivities)
O- Oxygen

SPXCDALMFX H- Hydrogen Sulphide


C- Carbon Monoxide Note: Add 'M' to the end of the part number to
order an XCD with the optional MODBUS output
Certification* Entry Gas Range G- Hydrogen e.g. the first part number in the table would become
SPXCDALMFXM.
A- ATEX/IECEx/KTL/PA and GB M- M20 (ATEX/IIECEx) X- User Adjustable N- Nitrogen Dioxide
*Other Asian and Chinese approvals available.
U- UL/CSA N- 3/4"NPT (UL/CSA) 1- Fixed B- Carbon Dioxide IR 0-2%Vol
Contact Honeywell Analytics for more information.

Sensepoint XCD Detector ATEX/IECEx/KTL, PA & GB (Aluminium LM25)*


SPXCDALMFX ATEX/IECEx/KTL/PA and GB approved SP XCD Flammable CAT 0-100%LEL (20 to 100%LEL, 10%LEL) with LM25, M20 Entry
SPXCDALMRX ATEX/IECEx/KTL/PA and GB approved SP XCD (Methane) IR 0-100%LEL (20 to 100%LEL, 10%LEL) with LM25, M20 Entry
SPXCDALMPX ATEX/IECEx/KTL/PA and GB approved SP XCD (Propane) IR 0-100%LEL (20 to 100%LEL, 10%LEL) with LM25, M20 Entry
SPXCDALMO1 ATEX/IECEx/KTL/PA and GB approved SP XCD Oxygen 25.0%/Vol. with LM25, M20 Entry
SPXCDALMHX ATEX/IECEx/KTL/PA and GB approved SP XCD Hydrogen Sulphide 0-50.0ppm (10.0 to 100.0ppm, 1.0ppm) with LM25, M20 Entry
SPXCDALMCX ATEX/IECEx/KTL/PA and GB approved SP XCD Carbon Monoxide 0-300ppm (100-1000ppm, 100ppm) with LM25, M20 Entry
SPXCDALMG1 ATEX/IECEx/KTL/PA and GB approved SP XCD Hydrogen 0-1000ppm with LM25, M20 Entry
SPXCDALMNX ATEX/IECEx/KTL/PA and GB approved SP XCD Nitrogen Dioxide 0-50.0ppm (10.0-50.0, 5.0ppm) with LM25, M20 Entry
SPXCDALMB1 ATEX/IECEx/KTL/PA and GB approved SP XCD Carbon Dioxide IR 0-2.00%Vol. with LM25, M20 Entry
Sensepoint XCD Detector ATEX/IECEx/KTL, PA & GB (316 Stainless Steel)*
SPXCDASMFX ATEX/IECEX and AP approved SP XCD Flammable CAT 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry
SPXCDASMRX ATEX/IECEX and AP approved SP XCD (Methane) IR 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry
SPXCDASMPX ATEX/IECEX and AP approved SP XCD (Propane) IR 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry
SPXCDASMO1 ATEX/IECEX and AP approved SP XCD Oxygen 25.0%/Vol. with 316SS, M20 Entry
SPXCDASMHX ATEX/IECEX and AP approved SP XCD Hydrogen Sulphide 0-50.0ppm (10.0 to 100.0ppm, 1.0ppm) with 316SS, M20 Entry
SPXCDASMCX ATEX/IECEX and AP approved SP XCD Carbon Monoxide 0-300ppm (100-1000ppm, 100ppm) with 316SS, M20 Entry
SPXCDASMG1 ATEX/IECEX and AP approved SP XCD Hydrogen 0-1000ppm with 316SS, M20 Entry
SPXCDASMNX ATEX/IECEX and AP approved SP XCD Nitrogen Dioxide 0-50.0ppm (10.0-50.0, 5.0ppm) with 316SS, M20 Entry
SPXCDASMB1 ATEX/IECEX and AP approved SP XCD Carbon Dioxide IR 0-2.00%Vol. with 316SS, M20 Entry
Optional Accessories Spare XCD Sensors (316 Stainless Steel)
S3KCAL Calibration cup SPXCDXSFXSS Flammable CAT 0-100%LEL (20 to 100%LEL, 10%LEL)**
SPXCDCC Collecting cone for use with lighter than air gases SPXCDXSRXSS Methane IR 0-100%LEL (20 to 100%LEL, 10%LEL)**
SPXCDDMK Duct mounting kit SPXCDXSPXSS Propane IR 0-100%LEL (20 to 100%LEL, 10%LEL)**
SPXCDHMANEN Hard copy manual in English SPXCDXSO1SS Oxygen 25.0%/Vol. only
SPXCDMTBR Mounting bracket (inc. bolts, nuts, brackets) SPXCDXSHXSS Hydrogen Sulphide 0-50.0ppm (10.0 to 100.0ppm, 1.0ppm)**
SPXCDSDP Sunshade/Deluge Protection SPXCDXSCXSS Carbon Monoxide 0-300ppm (100-1000ppm, 100ppm)**
00780-A-0100 ATEX approved junction box (Explosion-proof) SPXCDXSG1SS Hydrogen 0-1000ppm only
SPXCDXSN1SS Nitrogen Dioxide 0-50.0ppm (10.0-50.0ppm, 5.0ppm)**
SPXCDXSB1SS Carbon Dioxide IR 0-2.00%Vol. only

*For UL/c-UL versions simply change the letters in the part number for certification and entry e.g. first part number in table above would become SPXCDULNFX.
**For further details of user configurable ranges refer to "Detectable Gases and XCD Sensor Performance" table on page 6.
Note: Add 'M' to the end of the part number to order an XCD with the optional MODBUS output e.g. the first part number in the table would become SPXCDALMFXM.
Our Product Range

Fixed Gas Monitoring Portable Gas Monitoring Technical Services


Honeywell Analytics offers a wide range When it comes to personal protection from At Honeywell Analytics, we believe in the
of fixed gas detection solutions for a gas hazards, Honeywell Analytics has a wide value of great service and customer care.
diverse array of industries and applications range of reliable solutions ideally suited for Our key commitment is providing complete
Find out more
including: Commercial properties, industrial use in confined or enclosed spaces. Find
andout more
total customer satisfaction. Here are just
www.honeywellanalytics.com
applications, semiconductor manufacturers, These include: a few of the services we can offer:
www.honeywellanalytics.com
energy plants and petrochemical sites.
Contact Honeywell Analytics: Detection of flammable, Oxygen and FullHoneywell
Contact technical support
Analytics:
Detection of flammable, Oxygen and toxic toxic gases Expert team on hand to answer
gases (including exotics)
Europe, Middle East, Africa, India Single gas personal monitors worn by questions
Europe, Middleand queries
East, Africa, India
Innovative use of four core sensing
Life Safety Distribution AG
the individual
Life Safety
Fully Distribution
equipped workshops
AG to ensure
technologies paper tape,
Javastrasse 2 Multi-gas portable gas monitors used quick turnaround
Javastrasse 2 on repairs
electrochemical cell, catalytic bead
8604 Hegnau
and infrared
for confined space entry and regulatory Hegnau
8604 Comprehensive service engineer network
compliance
Switzerland
Training on product use and maintenance
Switzerland
Capability to detect down to Parts Per
Tel: +41 (0)44 943 4300 out
Find Multi-gas
more transportable monitors used +41
Tel: (0)44calibration
Mobile 943 4300service
Billion (ppb) or Percent by Volume (%v/v) for temporary protection of area
Fax: +41 (0)44 943 4398 www.honeywellanalytics.com Fax: +41 (0)44 943 4398
Cost effective regulatory compliance during site construction and Customised programmes of
India Tel: +91 124 4752700 India Tel: +91 124 4752700 maintenance
preventative/corrective
solutions maintenance activities
gasdetection@honeywell.com Contact Honeywell Analytics: gasdetection@honeywell.com
Extended warranties on products
Americas Europe, Middle East, Africa, India Americas
Honeywell Analytics Inc. Life Safety Distribution AG Honeywell Analytics Inc.
405 Barclay Blvd. Javastrasse 2 405 Barclay Blvd.
Lincolnshire, IL 60069 8604 Hegnau Lincolnshire, IL 60069
USA Switzerland USA
Find+1
Tel: out more
847 955 8200 Tel: +41 (0)44 943 4300 Tel: +1 847 955 8200
Toll free: +1 800 538 0363
www.honeywellanalytics.com Fax: +41 (0)44 943 4398 Toll free: +1 800 538 0363
Fax: +1 847 955 8210 India Tel: +91 124 4752700 Fax: +1 847 955 8210
detectgas@honeywell.com
Contact Honeywell Analytics: gasdetection@honeywell.com detectgas@honeywell.com

Asia Pacific
Europe, Middle East, Africa, India Americas Asia Pacific
Honeywell
Life Safety Analytics Asia
Distribution AGPacific Honeywell Analytics Inc. Honeywell Analytics Asia Pacific
#508, Kolon 2Science Valley (I)
Javastrasse 405 Barclay Blvd. #508, Kolon Science Valley (I)
187-10 Guro-Dong, Guro-Gu
8604 Hegnau Lincolnshire, IL 60069 187-10 Guro-Dong, Guro-Gu
Seoul, 152-050
Switzerland USA Seoul, 152-050
Korea
Tel: +41 (0)44 943 4300 Tel: +1 847 955 8200 Korea
Tel:
Fax:+82
+41(0)2
(0)446909
9430300
4398 Toll free: +1 800 538 0363 Tel: +82 (0)2 6909 0300
Fax:
India+82
Tel: (0)2
+912025 0329
124 4752700 Fax: +1 847 955 8210 Fax: +82 (0)2 2025 0329
analytics.ap@honeywell.com
gasdetection@honeywell.com detectgas@honeywell.com analytics.ap@honeywell.com

Technical
Americas Services Asia Pacific Technical Services
EMEAI: HAexpert@honeywell.com
Honeywell Analytics Inc. Honeywell Analytics Asia Pacific EMEAI: HAexpert@honeywell.com
US: ha.us.service@honeywell.com
405 Barclay Blvd. #508, Kolon Science Valley (I) US: ha.us.service@honeywell.com
AP: ha.ap.service@honeywell.com
Lincolnshire, IL 60069 187-10 Guro-Dong, Guro-Gu AP: ha.ap.service@honeywell.com
USA Seoul, 152-050
www.honeywell.com
Tel: +1 847 955 8200 Korea www.honeywell.com
Toll free: +1 800 538 0363 Tel: +82 (0)2 6909 0300
Fax: Note:
Please +1 847 955 8210 Fax: +82 (0)2 2025 0329
detectgas@honeywell.com analytics.ap@honeywell.com
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions.
Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations,
standards, and guidelines. This publication is not intended to form the basis of a contract.

Asia Pacific Technical Services


H_Sensepoint XCD_DS01077_V5_EMEAI