Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

ProReact EN Digital - LHD - Installation Instructions Rev 1-1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

ProReact EN Digital

Linear Heat Detection Cable

Installation Instructions

www.quality07.com.pl Document
Document
Page1 1ofof1111 Revision
Page Revision1.11.1 Sept Sept2019
2019
R Ref. ProReact EN Digital Installation Instructions
Contents:

Important Guidelines – read before commencing installation Page 3

General Overview Page 4


Product Features
Technical Data
Detection Temperatures & Coatings
Chemical Resistance

Technical Specifications Page 5

Typical System Configurations Page 6


Addressable Fire Alarm Systems
ProReact Digital Sensor Control Unit (DSCU-EN)

Installation Specifications Page 7


Leader Cable
Ambient Temperature
Low Temperature Installation Considerations

Installation Hardware Page 8

Splicing Page 10

Testing and Verification Page 10

Glossary Page 11

Page 2 of 11   Revision 1.1   Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
Important Guidelines
Please read this instruction leaflet thoroughly before commencing installation.

Install the Digital Linear Heat Detection Cable accordingly to meet local and country
installation requirements.

Digital Linear Heat Detection Cable must be installed by a qualified


professional in accordance with BS 5839-1:2017 (or country equivalent) and
IEC 60364 and authorities having jurisdiction.

Support the detection cable at 0.6m (2ft) to 1.5m (5ft) intervals.

Using a multimeter, test the detection cable on the reel before installation.

Ensure the maximum ambient temperature rating of the detection cable will not be
exceeded during transport, storage or normal operating conditions.

Ensure adjacent runs of detection cable are spaced at less than or equal to the
maximum approved spacing.

Ensure the detection cable is not in contact with any material which may conduct heat
onto the cable directly.

A silicone sleeve should be placed between fixing clips and linear heat detection cable.

Ensure any cable glands used are tightened to form a secure and moisture proof seal
around the detection cable.

Avoid allowing the detection cable to come in contact with any material which acts as a
heat sink. This may delay the activation of the cable in alarm situations.

Do not connect two lengths of detection cable which have different


action temperatures.

Do not connect lengths of fixed temperature cable in ‘T’ connections or spurs.

Do not paint the detection cable

Do not place the detection cable under excessive tension.

Do no bend the detection cable at right angles. The minimum bend radius is
100mm (4”).

Avoid subjecting the detection cable to mechanical damage which could result in false
activation.

Avoid laying the detection cable in areas where heavy traffic may result in the cable
being crushed.

Page 3 of 11   Revision 1.1   Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
General Overview Core conductors
Ø0.9mm (Ø0.035")

ProReact EN Digital Linear Heat Detection (LHD) cable uses fixed temperature
detection technology to provide a straightforward method for sensing changes Advanced Temperature
in temperature. The cable can offer alternative overheat protection in a vast Sensitive Polymer
range of applications and environments, from tunnels, Ø2.11mm (Ø0.083")
cable trays, warehousing to sensing changes in temperature within escalators
and other applications where many risks of fire are hidden from view.

ProReact EN Digital LHD cable is a non-resettable line-type heat detector.


The two twisted cores and held apart by an advanced temperature sensitive
polymer. At a temperature, set by the manufacturing processes of the cable, the
temperature sensitive polymer surrounding the two cores softens, allowing the
cores to come into contact. This is an irreversible process and once the cable
has activated, the section which has triggered must be cut out and replaced Specific Twist Ratio
(not the whole cable). (to suit temperature rating)

Digital Sensor Control Unit (DSCU-EN)


The ProReact EN Digital LHD cable has been approved to EN54-28:2016 in Protective Outer Coating
conjunction with the ProReact Digital Sensor Control Unit (DSCU-EN). The UV stable, LSZH,
DSCU-EN monitors up-to two zones of Digital LHD cable and has separate fault Oil resistant,
Flame retardant
and alarm outputs for each zone. It is straightforward to connect the DSCU-EN
Ø5.72mm (Ø0.225")
to a conventional fire alarm panel or to an addressable system using an I/O,
zone or switch monitor module. It also has a built-in display which shows the
state of each zone, including the distance in metres and feet to the alarm point,
Figure 1. ProReact EN Digital LHD Cable Construction
if an alarm is triggered. Furthermore, an RS-485 Modbus RTU/ASCII output is
available as standard for integration with a PLC or SCADA system.

Product Features Technical Data

• EN54-28:2016 approved Product type: Non-resettable line-type heat


detector
• CE Marked
Construction: Overall insulated, twisted pair of
• RoHS compliant
stainless steel cores
• Up-to 1,000m (3,280ft) per zone (when used
Insulation: 1kV tested protective outer
with the DSCU-EN) coatings
• Fixed sensitivity and detection along the entire
Additional insulation options: Stainless Steel over-braiding
length of sensor cable
Approvals: EN54-28:2016, CE Marked, RoHS
• Low smoke and halogen free. Flame retardant. Compliant
• UV stable and hydrocarbon resistant. Maximum Zone Length: 1,000m (3,280ft) (when used with
• Optional stainless steel over-braiding for DSCU-EN)
increased mechanical protection Wire Overall Diameter: 5.72mm (0.225in)
Minimum bend radius: 100mm (4”)

Electrical
Max Voltage Rating: 49Vac, 74Vdc
Resistance: approx 1.25ohms per metre per
core

Page 4 of 11 Revision 1.1 Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
Technical Specifications
Detection Temperatures & Coatings

A stainless steel outer braid is available on the entire range of ProReact EN Digital LHD cable and provides extra mechanical protection to the inner detec-
tion cable without impeding on the performance of the detection cable. It is frequently installed in abrasive environments.

Please Note: ProReact EN Digital LHD cable with Stainless Steel braiding has not been evaluated to EN54-28.

Product ProReact EN Digital LHD Cable - EN78 ProReact EN Digital LHD Cable - EN88

UL File No S36157

UL Model Designation EN78 EN88

Part No F1180 F1181

Description ProReact EN Digital LHD Cable – 78 deg C ProReact EN Digital LHD Cable – 88 deg C

EN54-28 Performance Type T078-V10-A045 T088-V10-A065

EN54-28 Environmental Group II

Nominal Activation Temperature 78 deg C 88 deg C

Maximum Ambient Temperature 45 deg C 65 deg C

Minimum Ambient Temperature -40 deg C

Humidity 0% to 98% RH

Colour Red White

Capacitance per m <100pF

Inductance per m <3.2µH

Resistance per m Approx 2.5ohms

Diameter 5.72mm +/- 0.12mm (0.225” +/- 0.005”)

Minimum bend radius 100mm (4”)

Features Low-Smoke Zero Halogen (LSZH), UV Stable, Oil resistant, Flame retardant

These ratings are given as a guide and for constant exposure to the chemicals shown at
Chemical Resistance
normal (10 to 30 deg C)temperatures. (* - not recommended, ***** - little or no impact)

Ammonia, Liquid / Gas *****

Butane **

Copper Nitrate *****

Fuel Oils ***

Gasoline ***

Hydrofluoric Acid ****

Kerosene *

Diesel Fuel ***

Acetic Acid ****

Technical drawings of ProReact EN Digital Linear Heat Detection Cable are available upon request.

Page 5 of 11   Revision 1.1   Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
Typical System Configurations
The ProReact EN Digital LHD cable is designed to work with the ProReact Digital Sensor Control Unit (DSCU-EN) and ProReact Digital End-of-Line Unit
(EOLU-EN). The ProReact DSCU-EN has been specifically designed to monitor the ProReact EN Digital LHD Cable and be immune to any electro-magnetic
interference that may be present in the typical applications the cable is installed into.

ProReact EN ProReact EN
Digital LHD Digital LHD
Cable Cable

Figure 1: Typical Installation of the ProReact Digital Sensor Control Unit

Page 6 of 11   Revision 1.1   Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
Installation Specifications

Leader Cable

An approved type of leader cable, preferably Fire Rated cable, should
be used between the fire alarm control panel or addressable switch/
zone monitor and the Digital Linear Heat Detection Cable. A secure
waterproof (IP65 or greater) junction box must be used to connect the
leader cable to the detection cable. It is recommended that leader cable
with the following minimum cross sectional area (CSA) per conductor
is used when using the maximum length of detection cable. Consult
with the authority having jurisdiction and the fire alarm control panel
manufacturer for further information.

Recommended Maximum Leader Cable Length and CSA for


copper conductors (with maximum length of Linear Heat Detection
Cable 1km/3.28kft)

0.8 mm2 (18AWG) — Upto 1,000m (3,280ft)

Low Temperature Installation Considerations


Fixed temperature Linear Heat Detection cable is suitable for use in A silicone pad should be placed around the cable before clipping into the
ambients down to -40°C (-40°F). Such conditions occur in cold storage support bracket. This prevents damage to the cable and reduces the heat
freezer warehouses and outdoors for example. sink effect of the clip.
Take special care when installing LHD cable in low ambients or for use in The minimum bend radius of the detection cable should be increased to
low temperature conditions careful consideration of the conditions and 150mm (6" ) to account for the reduced flexibility. The maximum distance
environment should be undertaken. between support brackets should be no more than 1m (3ft) and it is
Wherever possible the LHD cable should not be installed when the important to support the cable close to either side of any bend.
ambient temperature is below -10°C (14°F). The materials within the cable Ensure any junction boxes other enclosures are waterproof and suitable
will become less flexible and are more prone to damage. If the ambient for the expected operating temperatures.
temperature is likely to drop significantly after installing the cable take
into account linear shrinkage of the cable when attaching support
brackets. The cable can shrink in length by 12% at -40°C (-40°F).

Page 7 of 11   Revision 1.1   Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
Installation Hardware
There are many applications where Digital Linear Heat Detection Cable When pulling the detection cable from a reel, a reel stand must be used.
is used to provide protection. Please refer to the ProReact Linear Heat Do not pull the cable off the reel vertically with the reel stationary as
Detection Applications Guide for more information on the types of this will twist and damage the cable. A guide wire may be required for
fittings which should be used. The list is not exhaustive, however, any installations where supporting the cable at the recommended spacing is
fitting not mentioned in the Application Guide which may be used not practical. Ensure the diameter or gauge of the guide wire is adequate
should be evaluated to ensure it is fit for purpose. Consult the authority for the distance which is being spanned. Commercially available stainless
having jurisdiction for more information. steel wire with a diameter of approximately 2mm is suitable for use as a
The Digital Linear Heat Detection Cable should be adequately supported guide wire.
to prevent sagging. Ideally cable supports should be placed every 1m Connections into junction boxes and other enclosures must use strain
(3ft) and no more than 1.5m (5ft) apart. It may be necessary to place more relief connectors which provide dust and moisture protection (IP65 or
supports around corners and other transition areas. greater protection). The standard diameter of detection cable is 5.72mm
Care should be taken when mounting the cable in clips (or equivalent) (0.225”). Suitable cable glands are shown below which fit an M12
that they are not done so tight as to crush the cable. The detection cable standard knockout.
should be held firmly without deformation. Avoid placing excessive
tension in the cable, no greater than 50N. Ensure also that the minimum
bend radius is observed at all times – 100mm (4" ).
It is of particular importance to use a silicone pad between the heat
sensing cable and the fixing clip if the metal clip is exposed to the sun
or attached to a piece of equipment which may get hot and transfer the
heat to the cable. See a typical mounting configuration in the image below.
Where possible, it is preferable to install the Digital Linear Heat Detection Figure 4: Typical Cable Glands for connection Digital Linear Heat Detection
Cable in one continuous run of cable with as few splices as possible. Cable into an enclosure

Page 8 of 11 Revision 1.1 Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
Area Protection
Digital Linear Heat Detection Cable is suitable for broad or wide
area detection of overheat or fire conditions, e.g. warehouses
etc. The Digital LHD cable should be installed with a
minimum distance between the cable and the ceiling of 20mm to
allow hot gases rising from an event to trigger the detection cable.
Maximum support spacings should be followed (see illustration
right) and the cable securely attached to the ceiling or beams.
Section 22.6 of BS 5839-1 (or country equivalent) should be
consulted for guidelines of installing line-type heat
detectors. The main point to consider is that no point in the
protected space is further than 5.3m from the nearest
point on a line-type heat detector. However, this value may
change for sloped ceilings and ceilings which have closely
spaced structural beams, for example. For an application
which has a smooth ceiling, this means the maximum
spacing between runs of LHD cable is as follows:

for ceilings up-to Spacing between runs (A) Recommended minimum spacing to wall, partition or obstruction (B)

3.75m in height 7.5m 0.5m


4.5m in height 5.6m 0.5m
5m in height 3.5m 0.5m

Page 9 of 11 Revision 1.1 Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
Splicing
If the non-resettable Digital Linear Heat Detection Cable gets damaged
or has triggered due to an overheat condition, the section can be When replacing a section of the detection cable
removed and a new section spliced in its place. due to an overheat condition having occurred,
Care should be taken during splicing to ensure the two core conductors the section including at least 3m (10ft) either
do not come into contact with each other at any point and the final side of the known event should be replaced.
spliced joint is secure and made waterproof. It is recommended junction
box is used, with an IP rating suitable for the environment, to join two
lengths of LHD cable together. Do not solder the two cores of the LHD
cable together. A secure connection should be made with DIN rail
mounted terminal blocks or equivalent.

Testing and Verification


Routine maintenance and checking should be carried out to ensure the Shorting out the End of Line device should put the system into alarm.
Digital Linear Heat Detection Cable will function as expected and has not Disconnecting either leg from the end of line device should put the
been damaged etc. system into fault.
A visual inspection should be performed to ensure all support brackets Functional testing
and other aspects of the physical installation are suitable. The cable Fixed Temperature Digital Linear Heat Detection Cable is non-restorable
should also be visually checked for damage to the outer or inner – any section which has alarmed must be cut out and replaced. Therefore
insulation. Check to make sure the silicone pads are correctly installed functional testing of the installed cable will not normally be carried out.
around the cable in the clips.
However, if required, any Digital LHD cable leftover after installation can
Any joints which have been made should be checked to make sure they be used to periodically perform a functional test. A 1m (3ft) section of
are secure. cable should be attached between the end of the Digital LHD cable run
Electrical tests should be carried out to determine the circuit created and the end-of-line device.
by the conductors is working. Remove the conductors from the fire Using a suitable device heat the test length of detection cable up. Once
alarm control panel or addressable switch monitor and measuring the the action temperature (including any tolerances) has been reached the
resistance across them. The resulting value should equal the end-of-line system should alarm.
resistance plus approximately 1250Ω/km for each leg.
Ensure the test length is removed before placing the system back into
To test in circuit with a fire alarm control panel or addressable switch normal operation.
monitor re-attach the Digital LHD cable.

Page 10 of 11   Revision 1.1   Sept 2019


Document Ref. ProReact EN Digital Installation Instructions
Glossary

Alarm condition – A fire or overheat around the Digital LHD cable which activates the cable and triggers
the DSCU.

Cable glands – Used to form a dust-proof and weatherproof seal around a cable entering the DSCU unit.

Detection temperature – The nominal temperature at which the cores in the LHD cable irreversibly come
into contact.

Digital linear heat detection cable – A sensing cable comprised of a pair of twisted conductors that fuse
together at a specific temperature and induce an alarm on a fire panel via the DSCU.

End of line resistor – A component which allows a residual current flow through a circuit to monitor the
integrity of the circuit. In the event of a break in the circuit, current will stop flowing completely and a
trouble or fault signal will be triggered.

Fault condition – A break in one or both cores of the Digital LHD cable or a malfunction of the DSCU.

Junction box – A secure, dust-proof and weatherproof enclosure to protect a join between two lengths of
Digital LHD cable or a length of Digital LHD cable and leader cable.

Leader cable – A non-temperature sensing cable which transmits the signals between two components in
the system, e.g. the DSCU and the Digital LHD cable. Does not provide fire detection and may be fire-
rated to continue functioning even in a fire condition.

Maximum ambient temperature – The maximum allowed temperature which should be experienced in
normal operating conditions around the Digital LHD cable.

Spacing – The distance between adjacent runs of LHD cable on a ceiling, for example.

Two-wire RS-485 Modbus RTU/ASCII Communications – An industry standard, signalling protocol used to
communicate information between components in a system, for example a SCADA system or PLC. Often
used to provide more information to be communicated than simple open or closed status communicated
by a relay output.

Zone – A single circuit of ProReact linear heat detection cable connected across either a ProReact DiMM or a
fire panel and an end of line resistor

Tel: +48 508124087 Email: tadeusz@quality07.com.pl


Quality07 T.M. Markiewicz Sp.J.
www.quality07.com.pl 02-495 Warszawa
Ul. Górna Droga 5/3 Page 11 of 11 Revision 1.1 Sept 2019
Document Ref. ProReact EN Digital Installation Instructions

You might also like