Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Danfoss Cas Temperature Switches

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

MAKING MODERN LIVING POSSIBLE

Data sheet

Pressure switch and Thermostat


Type CAS

The CAS Series consists of a series of pressure


controlled switches and temperature
controlled switches. In this series, special
attention has been given to meeting
demands for a high level of enclosure, robust
and compact construction, and resistance
to shock and vibration.

The series is suitable for use in alarm


and regulation systems in factories, diesel
plants, compressors, power stations and
on board ships.

Features yy A high level of enclosure yy Resistance to shock and vibration

yy Fixed differential yy Available with all major marine approvals

yy Robust and compact construction

Approvals CE-marked in accordance with LVD 2006/95/EC:


EN 60947-1, EN-60947-4-1, EN 60947-5-1

Ship approvals American Bureau of Shipping, Det Norske Veritas, DNV


ABS (excl. CAS 139) Registro Italiano Navale, RINA
Lloyds Register of Shipping, LR (excl. CAS 1080) Maritime Register of Shipping, RMRS
Germanischer Lloyd, GL Nippon Kaiji Kyokai, NKK
Bureau Veritas, BV

IC.PD.P10.G7.02 / 520B674 Danfoss A/S (RC-MCGP /jmn), 2015-04


Data sheet Pressure switch nad Thermostat, type CAS

Overview Standard pressure switches

[bar]
Range Pe
Type
0 10 20 30 40 50 60
[bar]
0 3.5 CAS 133
0 10 CAS 136
0 18 CAS 137
10 35 CAS 139

Pressure switches for high pressure and strongly pulsating media

[bar]
Range Pe
Type
0 10 20 30 40 50 60
[bar]
1 10 CAS 143
4 40 CAS 145
6 60 CAS 147

Differential pressure switches

[bar]
Range Pe
Type
0 10 20 30 40 50 60
[bar]
0.2 2.5 CAS 155

Thermostats

[C] Range
Type
0 20 40 60 80 100 120 140 160
[C]
20 80 CAS 178
70 120 CAS 180
60 150 CAS 181

2 IC.PD.P10.G7.02 / 520B674 Danfoss A/S (RC-MCGP /jmn), 2015-04


Data sheet Pressure switch and Thermostat, type CAS

PRESSURE SWITCH

Technical data
Switch Microswitch with single pole changeover (SPDT)

Alternating current AC-14 / AC-15: 0.1A, 220V


Contact load
Direct current DC-13: 12W, 125V

CAS 133 139 -40 70 C


Ambient temperature
CAS 143 155 -25 70 C

Temperature CAS 133 139 -40 100 C


of medium 1) CAS 143 155 -25 100 C

Vibration resistance Vibration-stable in the range 2 30 Hz amplitude 1.1 mm and 30 100 Hz, 4 g.

Cable entry Pg 13.5 for cable diametrers from 5 14 mm.

1)
For water and seawater, max. 80 C

Materials in contact with the medium

Type Materials

Bellows: Stainless steel, material no. 1.4306 (DIN 17440)


CAS 133, CAS 136,
CAS 137, CAS 139
Pressure connection: Brass material no. 2.0401 (DIN 17660)

Diaphragm connection: Nickel plated brass CuZn 40 Ob3 ISO R 426 (DIN 17569)
CAS 143, CAS 145,
CAS 147, CAS 155
Diaphragm: Nitrile-butadien rubber

Enclosure Identification
IP67 acc. to EN 60529. The type designation and code no. of the unit
The pressure control housing is enamelled is stamped in the side of the housing.
pressure die cast aluminium (GD-AISi 12).
The cover is fastened by four screws which
are anchored to prevent loss.
The enclosure can be sealed with fuse wire.

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 3


Data sheet Pressure switch and Thermostat, type CAS

Ordering Standard pressure switches

Permissible
Setting Mechanical Max test Min. burst
operating
range pe differential pressure pressure Pressure
Type pressure Code no.
connection
[bar] [bar] [bar] [bar] [bar]

CAS 133 0 3.5 0.1 10 10 40 G 060-315066

CAS 136 0 10 0.2 22 22 40 G 060-315166

CAS 137 6 18 0.3 27 27 72 G 060-315266

CAS 139 10 35 0.6 53 53 100 G 060-315366

Pressure switches for high pressure and strongly pulsating media

Permissible
Setting Mechanical Max test Min. burst
operating Pressure
Type range pe differential pressure pressure Code no.
pressure connection
[bar] [bar] [bar] [bar] [bar]

CAS 143 1 10 0.2 0.6 120 180 240 G 060-316066

CAS 145 4 40 0.8 2.4 120 180 240 G 060-316166

CAS 147 6 60 13 120 180 240 G 060-316266

Differential pressure switch

Permissible
Setting Mechanical operating Max test Min. burst
range pe differential pressure for pressure pressure Pressure
Type Code no.
low pressure connection

[bar] [bar] [bar] [bar] [bar]

CAS 155 0.2 2.5 0.1 08 22 42 2G 060-313066

Preferred version

Terminology Range setting Max. test pressure


The pressure range within which the unit will The highest pressure the unit may be subjected
give a signal (contact changeover). to when, for example, testing the system for
leakage. Therefore, this presure must not occur
Differential as a recurring system pressure.
The difference between make pressure and
break pressure (see also page 6). Min. burst pressure
The pressure which the pressure-sensitive
Permissible burst pressure element will withstand without leaking.
The highest permanent or recurring pressure the
unit can be loaded with.

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 4


Data sheet Pressure switch nad Thermostat, type CAS

Function a. CAS 155 I. Alarm for rising differential pressure given at


Contacts 1-4 make and contacts 1-2 break the set range value.
when the differential pressure rises above
the set range value. The contacts changeover to II. Alarm for falling differential pressure given at
their initial position when the differential the set range value minus the differential.
pressure again falls to the range value minus the
differential (see fig. 1).

[bar]

[s]
Scale setting

Fig. 1 Mechanical differential

b. All other CAS pressure controls I. Alarm for falling pressure given at the set range
Contacts 1-2 make and contacts 1-4 break when value.
the pressure falls under the set range value. The
contacts changeover to their initial position II. Alarm for rising pressure given at the set range
when the pressure again rises to the set range value plus differential.
value plus the differential (see fig. 2).

[bar]

60-516.13
Danfoss

[s]
Scale setting

Fig. 2 Mechanical differential

Example 1: Example 2:
An alarm must be given when the lubrication oil When the differential pressure exceeds 1.3 bar
pressure in a motor falls below 0.8 bar. Select a filter must be cleaned.
CAS 133 (range 0 3.5 bar). The maximum static pressure (LP) for the CAS 155
The minimum permissible lubricating oils of 8 bar must not be exceeded.
pressure of 0.8 bar must be set using the range The pressure control range spindle must be set
spindle. The differential is fixed at 0.1 bar, i.e. the at 1.3 bar.
alarm will not cut out before the pressure rises to The alarm must be connected to terminals
0.9 bar. 1 and 2 (alarm for broken circuit).
The switch break function is normally used for
alarm purposes, i.e. the alarm must be connected
to terminals 1 and 4.

5 IC.PD.P10.G7.02 / 520B674 Danfoss A/S (RC-MCGP /jmn), 2015-04


Data sheet Pressure switch and Thermostat, type CAS

Accessories Part Description Qty. Code no.

Connector with nipple Pipe thread ISO 228-1, G 3/8 connector,


nipple and AL washer (10 mm ext. 8 mm int. diam)
5 017-436866
for solering onto steel or copper tubing,
steel span of jaws 22

Connector with nipple


G 3/8 connector, nipple and washer
(10 mm ext./ 6.5 mm int. diam.) for welding, 1 017-422966
steel span of jaws 22

Reducer
Pipe thread ISO 228-1, G 3/8 7/16 - 20 UNF
5 017-420566
reducer, washer, brass span of jaws 22

Adaptor
Pipe thread ISO 228-1, G 3/8 1/8 - 27 NPT
1 060-333466
with copper washer brass span of jaws 22

Adaptor
Pipe thread ISO 228-1, G 3/8 A 1/4 - 18 NPT
1 060-333566
with copper washer brass span of jaws 22

Adaptor
Pipe thread ISO 228-1, G 3/8 1/4 - 18 NPT
1 060-333666
with copper washer brass span of jaws 22

Adaptor
7
/16 - 20UNF R 3/8 (ISO 7-1) brass, span of jaws 19 1 060-324066

Nipple G 1/4 A G 3/8 A 060-333266

G 1/4 A ext. M10 x 1 with washer 060-333866

Damping coil

Pipe thread ISO 228-1, damping coil with G 3/8


connector and 1.5 m copper capillary tube. 1 060-104766
Standard washers are supplied.

Armoured damping coil

Pipe thread ISO 228-1, damping coil with G 3/8


connector and 1 m copper capillary tube. 1 060-333366
Standard washers are supplied.

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 6


Data sheet Pressure switch nad Thermostat, type CAS

Installation

Fig. 4

60L641.13
Danfoss
1. Range spindle
2. Range scale Fig. 3 Fig. 5
3. Locking screw

Installation Pulsations
CAS pressure controls are fitted with a 3 mm If the pressure medium is superimposed
steel mounting plate. The units should not be with severe pulsations, which occur in automatic
allowed to hang from the pressure connection. sprinkler systems (fire protection), fuel systems
for diesel motors (priming lines), and hydraulic
Pressure connection systems (e.g. propeller systems), etc, types
When fitting or removing pressure lines, the case CAS 143, CAS 145, CAS 147 are
spanner flats on the pressure connection should recommended.
be used to apply counter-torque. The maximum permissible pulsation level
for these types is 120 bar.
Steam plant
To protect the pressure element from excessive Setting
heat, the insertion of a water-filled loop is When the pressure control cover is removed,
recommended. The loop can, for example, be and the locking screw (3) is lossened, the range
made of 10 mm copper tube as shown in fig. 3. can be set with the spindle (1) while at the same
time the scale (2) is being read (fig. 4).
Water systems
Water in the pressure element is not harmful, Electrical connection
but in case of frost a water-filled pressure CAS pressure controls are fitted with a PG 13.5
element may burst. To prevent this happening, screwed cable entry that is suitable for cable
the pressure control can be allowed to operate diameters from 5 13 mm.
on an air cushion.
Contact function is shown in fig. 5.
Media resistance
Se table of materials in contact with the medium,
page 3. If seawater is involved, types CAS 143,
CAS 145, CAS 147 are recommended.

7 IC.PD.P10.G7.02 / 520B674 Danfoss A/S (RC-MCGP /jmn), 2015-04


Data sheet Pressure switch and Thermostat, type CAS

Dimensions [mm]
and weights [kg]
6
116
90 7
68

120
3

103
79

29
41 35
81 44
68

Fig. 6 Fig. 7

CAS 133, CAS 136, CAS 143, CAS 145


CAS 137, CAS 139 CAS 147

30
40

19
G 1/4

60-648.10
22

Danfoss
50
Fig. 8

CAS 155 Net weight:


50 CAS 133-139 approx. 1.0 kg
CAS 143-147 approx. 1.3 kg
LP CAS 155 approx. 1.5 kg
20
55

G1/4

Fig. 9

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 8


Data sheet Pressure switch and Thermostat, type CAS

THERMOSTAT

Technical data Type CAS 178, CAS 180, CAS 181 CAS 1080

Microswitch with single pole Microswitch with single pole


Switch
changeover (SPDT) changeover (2 x SPDT)

Alternating current AC-14 / AC-15: 0.1A, 220V


Contact load
Direct current DC-13: 12W, 125V
Ambient temperature -25 70 C
Vibration-stable in the range 2 30 Hz, amplitude 1.1 mm
Vibration resistance
and 30 100 Hz, 4 g.
Pg 13.5 for cable diameters 2 x g 13.5 for cable diameters
Cable entry
from 5 14 mm from 5 14 mm

Ordering Suitable
Mechanical Capillary
Setting Max. sensor sensor length
differential tube
range temperature (see also
Type adjustable / fixed length Code no.
Accessories)

[C] [C] [C] [mm] [m]

CAS 178 20 80 2.0 130 65 75 110 160 2 060L315166

CAS 180 70 120 2.0 220 65 75 110 160 2 060L315366

CAS 181 60 150 2.0 250 65 75 110 160 2 060L315566

Preferred version

2-step thermostat, type CAS 1080

Factory setting Mechanical Max. Insert sensor


Type differential temperature length Code no.
Step 1 Step 2 [C] [C] [mm]
CAS 1080 80 C 80 C 2.0 220 200 060L502066

Enclosure Identification
IP67 acc. to EN 60529. The type designation and code no. of the
The thermostat housing is enamelled pressure unit is stamped in the side of the housing.
die cast aluminium (GD-AISI 12). The cover
is fastened by four screws which are anchored
to prevent loss.
The enclosure can be sealed with fuse wire.

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 9


Data sheet Pressure switch nad Thermostat, type CAS

Accessories Sensor pockets for thermostats

Brass sensor pocket Steel 18/8 sensor pocket

A B A
Thread
Code no. Code no.
B
[mm] Thread [mm]

65 NPT 060L326566

75 NPT 060L326466 75 GA 060L326766

75 GA 060L326266

75 GA 060L326666

75 G A (ISO 228/1) 060L328166

110 NPT 060L328066 110 GA 060L326866

110 GA 060L327166 110 NPT 060L327066

110 G A (ISO 228/1) 060L340666

110 G A (ISO 228/1) 060L340366

160 GA 060L326366 160 GA 060L326966

200 GA 060L320666

200 G A (ISO 228/1) 060L340866

200 G A (ISO 228/1) 060L340266

250 GA 060L325466

330 GA 060L325566

Note:
all sensor pockets are supplied without gland nut, gaskets and washes

Other Accessories Description Qty./unit Code no.


Clamping band

For CAS temperature controls with remote


10 017-420466
sensor (L = 392 mm).

Heat conductive compound


(Tube with 4.5 cm3)
For CAS with sensor fitted in a sensor pocket.
For filling sensor pocket to improve heat
transfer between pocket and sensor. 1 041E0114
Application range for compound:
-20 150 C, momentarily up to 220 C.

10 IC.PD.P10.G7.02 / 520B674 Danfoss A/S (RC-MCGP /jmn), 2015-04


Data sheet Pressure switch and Thermostat, type CAS

Installation Location of unit: CAS thermostats are designed Sensor position


to withstand the shocks that occur, for example, As far as possible the sensor should be
in ships on compressors and in large machine positioned so that its longitudinal axis is at right
installations. CAS thermostats are fitted with a angles to the direction flow. The active part of
base of 3 mm steel plate for fixing to bulkheads, the sensor is 13 mm 47.5 mm.
etc.
The medium
Resistance to media The fastest reaction is obtained from a medium
Material specifications for sensor pockets. having high specific heat and high thermal
conductivity. It is therefore advantageous to use
Sensor pocket brass a medium that fulfils these conditions (provided
The tube is made of Ms 72 to DIN 17660, the there is a choice). The flow velocity of the
threaded portion of So Ms 58 Pb to DIN 17661. medium is also of significance. (The optimum
flow velocity for liquids is about 0.3 m/s).
Sensor pocket, stainless steel 18/8 For permissible media pressure see fig. 10.
Material designation 1.4305 to DIN 17440.

Permissible media pressure on the sensor pocket as a function of temperature

[bar] Brass Stainless steel 18/8

[C]
Fig. 10

Setting
When the thermostat cover is removed, and the
3 locking screw (3) fig. 2 is loosened, the range can
be set with the spindle (1) while at the same time
1 the scale (2) is being read (fig.11).

1. Range spindle
2. Range scale
3. Locking screw Fig. 11

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 11


Data sheet Pressure switch nad Thermostat, type CAS

Installation Scale correction However, such a charge is to some extent


(continued) The sensor on CAS temperature controls sensitive to changes in the temperature of
contains an adsorption charge. Therefore bellows and capillary tube. Under normal
function is not affected whether the sensor conditions this is of no importance, but if the
is placed warmer or colder than the remaining thermostat is to be used in extreme ambient
part of the thermostatic element (bellows and temperatures there will be a scale deviation.
capillary tube). The deviation can be compensated for as follows:
Scale correction = Z a
Z can be found from fig. 12, while a is the
correction factor from the table below.
(See example, page 14).

Factor for scale deviation

Relative scale
setting in %

Fig. 12

Regulation range
Type Correction factor a for thermostats
[C]
CAS 178 20 80 2.5

CAS 180 70 120 2.4

CAS 181 60 150 3.7

12 IC.PD.P10.G7.02 / 520B674 Danfoss A/S (RC-MCGP /jmn), 2015-04


Data sheet Pressure switch and Thermostat, type CAS

Installation Electrical connection


(continued)
CAS thermostats are fitted with a Pg 13.5
screwed cable entry suitable for cables
from 5 14 mm.

60L1049.11
60L1049.11
Danfoss
Danfoss
Fig. 13

2-step CAS thermostat, type CAS 1080

60-1121.16
Danfoss
60-1121.16

Fig. 14
Danfoss

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 13


Data sheet Pressure switch and Thermostat, type CAS

Function
Differentials Thermostat function

The mechanical differential is the differential Contacts 1-4 make while contacts 1-2 break
determined by the design of the thermostat. The when the temperature rises above the scale
thermal differential (operating differential) is the setting.
differential the system operates on.
The contacts changeover to their initial position
The thermal differential is always greater than when the temperature falls to the scale setting
the mechanical differential and depends on minus the differential. See fig. 16.
three factors:
1) Medium flow velocity I. Alarm for rising temperature given
2) Temperature change rate of the medium at range setting value.
3) Heat transmission to the sensor
II. Alarm for falling temperature given
at range setting value minus the differential.

[C]

[s]
Scale setting

Mechanical differential
Fig. 16

Example 1 The relative scale setting Z can be calculated


Diesel engine with cooling water temperature of from the following formula:
85 C (normal). An alarm must be triggered if the
cooling water temperature exceeds 95 C. Setting value - min. scale value
Choose a CAS thermostat 180 (range 70 120 C). 100=%
Main spindle setting: 95 C. max. scale value - min. scale value
The required alarm function is obtained by
connecting to thermostat terminals 1-4. Relative scale setting: 95-70100
=50%
Example 2 120-70
Find the necessary scale correction for a CAS 180.
Set 95 C at 50 C ambient temperature. Factor for scale deviation Z fig. 12, Z 0.7
Correction factor a=2.4, see table page 12.
Scale correction = Za=0.72.4=1.7 C
CAS must be set at 95+1.7=96.7 C

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 14


Data sheet Pressure switch and Thermostat, type CAS

Function CAS 1080 thermostats have fixed factory Thermostat function


(continued) settings.
The thermostats with factory setting Contacts 1 4 make while contacts 1 2 break
at 80 C of step 1 and step 2 is used for special when the temperature rises above the scale
application, where double warning like cranck setting.
case fire is requested.
The contacts automatically reset when the The contacts changeover to their initial position
temperature decreases in accordance with the when the temperature falls to the scale setting
differential. minus the differential. See fig. 17.

Differentials The contacts marked A correspond to step 1.


The contacts marked B correspond to step 2.
The mechanical differential is the differential
determined by the design of the thermostat. I. Alarm for rising temperature given
The thermal differential (operating differential) is at range setting value.
the differential the contact system operates on. II. Alarm for falling temperature given
The thermal differential is always greater than at range setting value minus the differential
the mechanical differential and depends on
three factors:
1) Medium flow velocity
2) Temperature change rate of the medium and
3) Heat transmission to the sensor

[C][C]
Temp

60-1415.11
Danfoss
A1 A4 A4 A1 A4
A1 A2 A2
A2

B1 B4 B4 B1 B4
B1 B2
B2 B2

Mechanical
II I II
differential 80 C
Diff. 3 C

[s] [s]
Time
Fig. 17

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 15


Data sheet Pressure switch and Thermostat, type CAS

Dimensions [mm] CAS with remote sensor and 2 m armoured capillary tube
and weights [kg]

Fig. 18 Net weight: approx. 1.4 kg

2-step thermostat, type CAS 1080

A: 200 or 80 mm
B: G 3/4 A

Fig. 19 Net weight: approx. 1.4 kg

Danfoss A/S (RC-MCGP /jmn), 2015-04 IC.PD.P10.G7.02 / 520B674 16

You might also like