Keeprite Refrigeration KMP
Keeprite Refrigeration KMP
Keeprite Refrigeration KMP
Medium Profile
PRODUCT DATA &
Unit Cooler
INSTALLATION Air, Electric, Hot Gas
Bulletin K30-KMP-PDI-8 & Warm Fluid Defrost
Electrical Power:
We are on the Internet 208-230/1/60, 208-230/3/60,
www.keepriterefrigeration.com 460/1/60, 460/3/60, 575/1/60, 575/3/60
CONTENTS
Page
Nomenclature.................................................................................................................. 2
Features & Options......................................................................................................... 2
Capacity Data.................................................................................................................. 3
Electrical Data................................................................................................................. 4 - 12
Wiring Diagrams.............................................................................................................. 13 - 21
Dimensional Data/Specifications..................................................................................... 22 - 23
Shipping Weights............................................................................................................ 24
Factory Installed Distributor Nozzles.............................................................................. 25
Recommended Expansion Valve Selections.................................................................. 26 - 27
Installation Instructions................................................................................................... 28 - 30
Hot Gas Piping Schematics............................................................................................ 31 - 32
Glycol Fluid Cooler Data................................................................................................. 33
Generic Service Parts List.............................................................................................. 33 - 34
Warranty......................................................................................................................... 35
Project Information......................................................................................................... 35
As Built Service Parts.................................................................................................. BACK
03/03/10
NOMENCLATURE
K MP 3 15 V E - T5 A
STANDARD FEATURES
Modern look Proven motor/fan/motor mount design
Totally enclosed high efficiency PSC motors Liquid line solenoid valve wire harness factory
installed
High efficiency and high strength fan guard
Schrader valve on suction header
Hinged doors
Reverse cycle & 3 pipe hot gas available Large 3/4 ID (3/4 MPT) drain hole
Ample electrical and header compartments Shipped in upright position
Lower heater wattage
OPTIONAL FEATURES
Hot gas loop pan with hot gas defrost models EC Motors
-2-
K30-KMP-PDI-8 03/03/10
CAPACITY DATA
ALL MODELS 60Hz
Medium Temperature Models - Capacity @ 6 F.P.I. *
Medium Temp. Models 118M 122M 228M 236M 245M 355M 368M 480M 488M *
Number Of Fans 1 1 2 2 2 3 3 4 4
25/20 18000 22000 28000 36000 45000 55000 68000 80000 88000
(-4/-7) (5270) (6440) (8200) (10500) (13200) (16100) (19900) (23400) (25800)
Capacity E vap
B TU H Temp. 15 17820 21780 27720 35640 44550 54450 67320 79200 87120
(WATTS) F (C) (-9) (5223) (6383) (8124) (10445) (13057) (15958) (19730) (23212) (25533)
10 17640 21560 27440 35280 44100 53900 66640 78400 86240
(-12) (5170) (6319) (8042) (10340) (12925) (15797) (19531) (22978) (25275)
3430 3240 7260 6870 6480 10300 9720 13000 12200
Air Flow CFM (L/S)
(1620) (1530) (3430) (3240) (3060) (4860) (4590) (6140) (5760)
Refrigerant Charge LB . 3.6 4.8 4.2 7.0 9.1 10 14 16 16
(R404A) (KG) (1.6) (2.2) (1.9) (3.2) (4.1) (4.7) (6.3) (7.4) (7.4)
* "488M" models are 8 F.P.I.
Capacities rated using R404A with 10F(5.6C) TD & 100F(38C) liquid temperature.
Capacities at other TD within a range of 8 to 15 F(4.4 to 8.3C) are directly proportional to TD, or use formula:
Capacity = Rated capacity 10 x TD.
For capacities at TD outside of range 8 to 15 F(4.4 to 8.3C), or liquid temperature lower than75F (24C), consult factory.
-3-
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA - 208-230/1/60
AIR DEFROST & 60Hz
HOT GAS DEFROST WITH HOT GAS LOOP PAN MODELS
FAN MOTORS
STANDARD PSC MOTORS OPTIONAL EC MOTORS
MODEL FP I
QTY. FLA MIN. CIRC. MAX. FUSE FLA MIN. CIRC. MAX. FUSE
HP WATTS HP WATTS
TOTAL AMPACITY (A) (AMPS) TOTAL AMPACITY (A) (AMPS)
118M#-S2A 1 1/3 1.7 320 2.1 15 1/3 2.6 2 45 3.3 15
122M#-S2A 1 1/3 1.7 320 2.1 15 1/3 2.6 2 45 3.3 15
228M#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
236M#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
6
245M#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
355M#-S2A 3 1/3 5.1 960 5.5 15 1/3 7.8 735 8.5 15
368M#-S2A 3 1/3 5.1 960 5.5 15 1/3 7.8 735 8.5 15
480M#-S2A 4 1/3 6.8 1280 7.2 15 1/3 10.4 980 11.1 15
488M#-S2A 8 4 1/3 6.8 1280 7.2 15 1/3 10.4 980 11.1 15
116L-S2A 1 1/3 1.7 320 2.1 15 1/3 2.6 2 45 3.3 15
119L-S2A 1 1/3 1.7 320 2.1 15 1/3 2.6 2 45 3.3 15
225L#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
232L#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
6
240L#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
348L#-S2A 3 1/3 5.1 960 5.5 15 1/3 7.8 735 8.5 15
356L#-S2A 3 1/3 5.1 960 5.5 15 1/3 7.8 735 8.5 15
471L#-S2A 4 1/3 6.8 1280 7.2 15 1/3 10.4 735 11.1 15
113V-S2A 1 1/3 1.7 320 2.1 15 1/3 2.6 2 45 3.3 15
117V-S2A 1 1/3 1.7 320 2.1 15 1/3 2.6 2 45 3.3 15
222V#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
228V#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
4
234V#-S2A 2 1/3 3.4 6 40 3.8 15 1/3 5.2 490 5.9 15
339V#-S2A 3 1/3 5.1 960 5.5 15 1/3 7.8 735 8.5 15
350V#-S2A 3 1/3 5.1 960 5.5 15 1/3 7.8 735 8.5 15
459V#-S2A 4 1/3 6.8 1280 7.2 15 1/3 10.4 980 11.1 15
# = A, H or R. Refer to Nomenclature for details
= H or R. Refer to Nomenclature for details
-4-
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA - 460/1/60
AIR DEFROST & 60Hz
HOT GAS DEFROST WITH HOT GAS LOOP PAN MODELS
FAN MOTORS
MODEL FP I
QUANTITY HP FLA TOTAL MIN. CIRC. AMPACITY (A) MAX. FUSE (AMPS)
118M#-S4A 1 1/3 0.9 1.1 15
122M#-S4A 1 1/3 0.9 1.1 15
228M#-S4A 2 1/3 1.8 2.0 15
236M#-S4A 2 1/3 1.8 2.0 15
6
245M#-S4A 2 1/3 1.8 2.0 15
355M#-S4A 3 1/3 2.7 2.9 15
368M#-S4A 3 1/3 2.7 2.9 15
480M#-S4A 4 1/3 3.6 3.8 15
488M#-S4A 8 4 1/3 3.6 3.8 15
116L-S4A 1 1/3 0.9 1.1 15
119L-S4A 1 1/3 0.9 1.1 15
225L#-S4A 2 1/3 1.8 2.0 15
232L#-S4A 2 1/3 1.8 2.0 15
6
240L#-S4A 2 1/3 1.8 2.0 15
348L#-S4A 3 1/3 2.7 2.9 15
356L#-S4A 3 1/3 2.7 2.9 15
471L#-S4A 4 1/3 3.6 3.8 15
113VS4A 1 1/3 0.9 1.1 15
117VS4A 1 1/3 0.9 1.1 15
222V#-S4A 2 1/3 1.8 2.0 15
228V#-S4A 2 1/3 1.8 2.0 15
4
234V#-S4A 2 1/3 1.8 2.0 15
339V#-S4A 3 1/3 2.7 2.9 15
350V#-S4A 3 1/3 2.7 2.9 15
459V#-S4A 4 1/3 3.6 3.8 15
# = A, H or R. Refer to Nomenclature for details
= H or R. Refer to Nomenclature for details
-5-
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA - 575/1/60
AIR DEFROST & 60Hz
HOT GAS DEFROST WITH HOT GAS LOOP PAN MODELS
FAN MOTORS
MODEL FP I
QUANTITY HP FLA TOTAL MIN. CIRC. AMPACITY (A) MAX. FUSE (AMPS)
118M#-S5A 1 1/3 0.7 0.9 15
122M#-S5A 1 1/3 0.7 0.9 15
228M#-S5A 2 1/3 1.4 1.6 15
236M#-S5A 2 1/3 1.4 1.6 15
6
245M#-S5A 2 1/3 1.4 1.6 15
355M#-S5A 3 1/3 2.1 2.3 15
368M#-S5A 3 1/3 2.1 2.3 15
480M#-S5A 4 1/3 2.8 3.0 15
488M#-S5A 8 4 1/3 2.8 3.0 15
116L-S5A 1 1/3 0.7 0.9 15
119L-S5A 1 1/3 0.7 0.9 15
225L#-S5A 2 1/3 1.4 1.6 15
232L#-S5A 2 1/3 1.4 1.6 15
6
240L#-S5A 2 1/3 1.4 1.6 15
348L#-S5A 3 1/3 2.1 2.3 15
356L#-S5A 3 1/3 2.1 2.3 15
471L#-S5A 4 1/3 2.8 3.0 15
113V-S5A 1 1/3 0.7 0.9 15
117V-S5A 1 1/3 0.7 0.9 15
222V#-S5A 2 1/3 1.4 1.6 15
228V#-S5A 2 1/3 1.4 1.6 15
4
234V#-S5A 2 1/3 1.4 1.6 15
339V#-S5A 3 1/3 2.1 2.3 15
350V#-S5A 3 1/3 2.1 2.3 15
459V#-S5A 4 1/3 2.8 3.0 15
# = A, H or R. Refer to Nomenclature for details
= H or R. Refer to Nomenclature for details
-6-
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA -
208-230/1/60 - ELECTRIC DEFROST MODELS 60Hz
FAN MOTORS DEFROST HEATERS
STANDARD PSC MOTORS OPTIONAL EC MOTORS
MODEL FP I MAX.
MAX. MAX. TOTAL TOTAL MCA
QTY. HP FLA MCA FLA MCA FU S E
WATTS FU S E WATTS FU S E WATTS AMPS (A)
TOTAL (A) TOTAL (A) (AMPS)
(AMPS) (AMPS)
118ME-S2A 1 1/3 1.7 320 2.1 15 2.6 245 3.3 15 3330 14.5 18 20
122ME-S2A 1 1/3 1.7 320 2.1 15 2.6 245 3.3 15 3330 14.5 18 20
228ME-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
236ME-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
6
245ME-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
355ME-S2A 3 1/3 5.1 960 5.5 15 7.8 735 8.5 15 9 0 40 39.3 49 50
368ME-S2A 3 1/3 5.1 960 5.5 15 7.8 735 8.5 15 9 0 40 39.3 49 50
480ME-S2A 4 1/3 6.8 1280 7.2 15 10.4 980 11.1 15 10600 46.1 58 60
488ME-S2A 8 4 1/3 6.8 1280 7.2 15 10.4 980 11.1 15 10600 46.1 58 60
116LE-S2A 1 1/3 1.7 320 2.1 15 2.6 245 3.3 15 3330 14.5 18 20
119LE-S2A 1 1/3 1.7 320 2.1 15 2.6 245 3.3 15 3330 14.5 18 20
225LE-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
232LE-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
6
240LE-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
348LE-S2A 3 1/3 5.1 960 5.5 15 7.8 735 8.5 15 9 0 40 39.3 49 50
356LE-S2A 3 1/3 5.1 960 5.5 15 7.8 735 8.5 15 9 0 40 39.3 49 50
471LE-S2A 4 1/3 6.8 1280 7.2 15 10.4 735 11.1 15 10600 46.1 58 60
113VE-S2A 1 1/3 1.7 320 2.1 15 2.6 245 3.3 15 3330 14.5 18 20
117VE-S2A 1 1/3 1.7 320 2.1 15 2.6 245 3.3 15 3330 14.5 18 20
222VE-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
228VE-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
4
234VE-S2A 2 1/3 3.4 6 40 3.8 15 5.2 490 5.9 15 6190 26.9 34 35
339VE-S2A 3 1/3 5.1 960 5.5 15 7.8 735 8.5 15 9 0 40 39.3 49 50
350VE-S2A 3 1/3 5.1 960 5.5 15 7.8 735 8.5 15 9 0 40 39.3 49 50
459VE-S2A 4 1/3 6.8 1280 7.2 15 10.4 980 11.1 15 10600 46.1 58 60
-7-
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA -
460/1/60 & 460/3/60 60Hz
ELECTRIC DEFROST MODELS
FAN MOTORS DEFROST HEATERS
460/1/60 460/3/60
MODEL FP I MAX.
FLA MCA TOTAL MAX. MAX.
QTY. HP FU S E TOTAL MCA TOTAL MCA
TOTAL (A) WATTS FU S E FU S E
(AMPS) AMPS (A) AMPS (A)
(AMPS) (AMPS)
118ME-*A 1 1/3 0.9 1.1 15 3330 7.2 9.0 15 5.0 6.2 15
122ME-*A 1 1/3 0.9 1.1 15 3330 7.2 9.0 15 5.0 6.2 15
228ME-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
236ME-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
6
245ME-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
355ME-*A 3 1/3 2.7 2.9 15 9040 19.7 25 25 13.4 17 20
368ME-*A 3 1/3 2.7 2.9 15 9040 19.7 25 25 13.4 17 20
480ME-*A 4 1/3 3.6 3.8 15 10600 23.0 29 30 15.6 19 20
488ME-*A 8 4 1/3 3.6 3.8 15 10600 23.0 29 30 15.6 19 20
116LE-*A 1 1/3 0.9 1.1 15 3330 7.2 9.0 15 5.0 6.2 15
119LE-*A 1 1/3 0.9 1.1 15 3330 7.2 9.0 15 5.0 6.2 15
225LE-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
232LE-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
6
240LE-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
348LE-*A 3 1/3 2.7 2.9 15 9040 19.7 25 25 13.4 17 20
356LE-*A 3 1/3 2.7 2.9 15 9040 19.7 25 25 13.4 17 20
471LE-*A 4 1/3 3.6 3.8 15 10600 23.0 29 30 15.6 19 20
113VE-*A 1 1/3 0.9 1.1 15 3330 7.2 9.0 15 5.0 6.2 15
117VE-*A 1 1/3 0.9 1.1 15 3330 7.2 9.0 15 5.0 6.2 15
222VE-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
228VE-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
4
234VE-*A 2 1/3 1.8 2.0 15 6190 13.5 17 20 9.2 11 15
339VE-*A 3 1/3 2.7 2.9 15 9040 19.7 25 25 13.4 17 20
350VE-*A 3 1/3 2.7 2.9 15 9040 19.7 25 25 13.4 17 20
459VE-*A 4 1/3 3.6 3.8 15 10600 23.0 29 30 15.6 19 20
* = S4 or T4. Refer to Nomenclature for details
-8-
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA -
575/1/60 & 575/3/60 60Hz
ELECTRIC DEFROST MODELS
FAN MOTORS DEFROST HEATERS
575/1/60 575/3/60
MODEL FP I MAX.
FLA MCA TOTAL MAX. MAX.
QTY. HP FU S E TOTAL MCA TOTAL MCA
TOTAL (A) WATTS FU S E FU S E
(AMPS) AMPS (A) AMPS (A)
(AMPS) (AMPS)
118ME-*A 1 1/3 0.7 0.9 15 3330 5.8 7.2 15 4.0 5.0 15
122ME-*A 1 1/3 0.7 0.9 15 3330 5.8 7.2 15 4.0 5.0 15
228ME-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
236ME-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
6
245ME-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
355ME-*A 3 1/3 2.1 2.3 15 9040 15.7 20 20 10.7 13 15
368ME-*A 3 1/3 2.1 2.3 15 9040 15.7 20 20 10.7 13 15
480ME-*A 4 1/3 2.8 3.0 15 10600 18.4 23 25 12.5 16 20
488ME-*A 8 4 1/3 2.8 3.0 15 10600 18.4 23 25 12.5 16 20
116LE-*A 1 1/3 0.7 0.9 15 3330 5.8 7.2 15 4.0 5.0 15
119LE-*A 1 1/3 0.7 0.9 15 3330 5.8 7.2 15 4.0 5.0 15
225LE-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
232LE-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
6
240LE-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
348LE-*A 3 1/3 2.1 2.3 15 9040 15.7 20 20 10.7 13 15
356LE-*A 3 1/3 2.1 2.3 15 9040 15.7 20 20 10.7 13 15
471LE-*A 4 1/3 2.8 3.0 15 10600 18.4 23 25 12.5 16 20
113VE-*A 1 1/3 0.7 0.9 15 3330 5.8 7.2 15 4.0 5.0 15
117VE-*A 1 1/3 0.7 0.9 15 3330 5.8 7.2 15 4.0 5.0 15
222VE-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
228VE-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
4
234VE-*A 2 1/3 1.4 1.6 15 6190 10.8 13 15 7.3 9.2 15
339VE-*A 3 1/3 2.1 2.3 15 9040 15.7 20 20 10.7 13 15
350VE-*A 3 1/3 2.1 2.3 15 9040 15.7 20 20 10.7 13 15
459VE-*A 4 1/3 2.8 3.0 15 10600 18.4 23 25 12.5 16 20
* = S5 or T5. Refer to Nomenclature for details
-9-
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA - 208-230/1/60
HOT GAS DEFROST 60Hz
WITH DRAIN PAN HEATER MODELS
FAN MOTORS DRAIN PAN HEATERS
MODEL FP I FLA MCA MAX. FUSE TOTAL MCA MAX. FUSE
QTY. HP TOTAL AMPS
TOTAL (A) (AMPS) WATTS (A) (AMPS)
118M^-S2A 1 1/3 1.7 2.1 15 534 2.3 2.9 15
122M^-S2A 1 1/3 1.7 2.1 15 534 2.3 2.9 15
228M^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
236M^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
6
245M^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
355M^-S2A 3 1/3 5.1 5.5 15 1240 5.4 6.7 15
368M^-S2A 3 1/3 5.1 5.5 15 1240 5.4 6.7 15
480M^-S2A 4 1/3 6.8 7.2 15 1430 6.0 7.8 15
488M^-S2A 8 4 1/3 6.8 7.2 15 1430 6.0 7.8 15
116L^-S2A 1 1/3 1.7 2.1 15 534 2.3 2.9 15
119L^-S2A 1 1/3 1.7 2.1 15 534 2.3 2.9 15
225L^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
232L^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
6
240L^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
348L^-S2A 3 1/3 5.1 5.5 15 1240 5.4 6.7 15
356L^-S2A 3 1/3 5.1 5.5 15 1240 5.4 6.7 15
471L^-S2A 4 1/3 6.8 7.2 15 1430 6.2 7.8 15
113V^-S2A 1 1/3 1.7 2.1 15 534 2.3 2.9 15
117V^-S2A 1 1/3 1.7 2.1 15 534 2.3 2.9 15
222V^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
228V^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
4
234V^-S2A 2 1/3 3.4 3.8 15 887 3.9 4.8 15
339V^-S2A 3 1/3 5.1 5.5 15 1240 5.4 6.7 15
350V^-S2A 3 1/3 5.1 5.5 15 1240 5.4 6.7 15
459V^-S2A 4 1/3 6.8 7.2 15 1430 6.2 7.8 15
^ = T or G. Refer to Nomenclature for details
- 10 -
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA - 460/1/60
HOT GAS DEFROST 60Hz
WITH DRAIN PAN HEATER MODELS
FAN MOTORS DRAIN PAN HEATERS
MODEL FP I FLA MCA MAX. FUSE TOTAL MCA MAX. FUSE
QTY. HP TOTAL AMPS
TOTAL (A) (AMPS) WATTS (A) (AMPS)
118M^-S4A 1 1/3 0.9 1.1 15 534 1.2 1.5 15
122M^-S4A 1 1/3 0.9 1.1 15 534 1.2 1.5 15
228M^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
236M^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
6
245M^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
355M^-S4A 3 1/3 2.7 2.9 15 1240 2.7 3.4 15
368M^-S4A 3 1/3 2.7 2.9 15 1240 2.7 3.4 15
480M^-S4A 4 1/3 3.6 3.8 15 1430 3.1 3.9 15
488M^-S4A 8 4 1/3 3.6 3.8 15 1430 3.1 3.9 15
116L^-S4A 1 1/3 0.9 1.1 15 534 1.2 1.5 15
119L^-S4A 1 1/3 0.9 1.1 15 534 1.2 1.5 15
225L^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
232L^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
6
240L^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
348L^-S4A 3 1/3 2.7 2.9 15 1240 2.7 3.4 15
356L^-S4A 3 1/3 2.7 2.9 15 1240 2.7 3.4 15
471L^-S4A 4 1/3 3.6 3.8 15 1430 3.1 3.9 15
113V^-S4A 1 1/3 0.9 1.1 15 534 1.2 1.5 15
117V^-S4A 1 1/3 0.9 1.1 15 534 1.2 1.5 15
222V^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
228V^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
4
234V^-S4A 2 1/3 1.8 2.0 15 887 1.9 2.4 15
339V^-S4A 3 1/3 2.7 2.9 15 1240 2.7 3.4 15
350V^-S4A 3 1/3 2.7 2.9 15 1240 2.7 3.4 15
459V^-S4A 4 1/3 3.6 3.8 15 1430 3.1 3.9 15
^ = T or G. Refer to Nomenclature for details
- 11 -
K30-KMP-PDI-8 03/03/10
ELECTRICAL DATA - 575/1/60
HOT GAS DEFROST 60Hz
WITH DRAIN PAN HEATER MODELS
FAN MOTORS DRAIN PAN HEATERS
MODEL FP I FLA MCA MAX. FUSE TOTAL MCA MAX. FUSE
QTY. HP TOTAL AMPS
TOTAL (A) (AMPS) WATTS (A) (AMPS)
118M^-S5A 1 1/3 0.7 0.9 15 534 0.9 1.2 15
122M^-S5A 1 1/3 0.7 0.9 15 534 0.9 1.2 15
228M^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
236M^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
6
245M^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
355M^-S5A 3 1/3 2.1 2.3 15 1240 2.2 2.7 15
368M^-S5A 3 1/3 2.1 2.3 15 1240 2.2 2.7 15
480M^-S5A 4 1/3 2.8 3.0 15 1430 2.5 3.1 15
488M^-S5A 8 4 1/3 2.8 3.0 15 1430 2.5 3.1 15
116L^-S5A 1 1/3 0.7 0.9 15 534 0.9 1.2 15
119L^-S5A 1 1/3 0.7 0.9 15 534 0.9 1.2 15
225L^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
232L^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
6
240L^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
348L^-S5A 3 1/3 2.1 2.3 15 1240 2.2 2.7 15
356L^-S5A 3 1/3 2.1 2.3 15 1240 2.2 2.7 15
471L^-S5A 4 1/3 2.8 3.0 15 1430 2.5 3.1 15
113V^-S5A 1 1/3 0.7 0.9 15 534 0.9 1.2 15
117V^-S5A 1 1/3 0.7 0.9 15 534 0.9 1.2 15
222V^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
228V^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
4
234V^-S5A 2 1/3 1.4 1.6 15 887 1.5 1.9 15
339V^-S5A 3 1/3 2.1 2.3 15 1240 2.2 2.7 15
350V^-S5A 3 1/3 2.1 2.3 15 1240 2.2 2.7 15
459V^-S5A 4 1/3 2.8 3.0 15 1430 2.5 3.1 15
^ = T or G. Refer to Nomenclature for details
- 12 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM - 208-230/1/60
AIR DEFROST MODELS
WITH DEFROST TIME CLOCK WITHOUT DEFROST TIME CLOCK
DEFROST CLOCK L1 L2 L1 L2
PARAGON # 8145
OR EQUIVALENT
GND GND
TM
FUSE OR
FUSE OR CIRCUIT
CIRCUIT BREAKER
3 4 X BREAKER NOTE #3
1 2
NOTE #3
N
GND
M2 TO MULTIPLE
M1 EVAPORATORS (IF APPLIC)
M2 TO MULTIPLE EVAPS
M1 (IF APPLIC)
N.C.
4 N 4 N
M1 M2 TERMINAL BOARD M1 M2 TERMINAL BOARD
GND. GND.
FAN MOTOR FAN MOTOR
POWER POWER
PLUGS PLUGS
REFER TO REFER TO
FAN FAN FAN EVAPORATOR FAN FAN FAN EVAPORATOR
MTR MTR MTR DATA PLATE MTR MTR MTR DATA PLATE
FOR MOTOR FOR MOTOR
EVAPORATOR QUANTITY EVAPORATOR QUANTITY
TERMINALS
NOTES
-COMPONENT TERMINAL
1). USE COPPER CONDUCTORS ONLY
-TERMINAL BLOCK TERMINAL
2). USE 90C WIRE (OR HIGHER)
CONDUCTORS/WIRING
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND DEFROST FACTORY WIRING
HEATERS MUST NOT EXCEED MAXIMUM WIRING BY OTHERS
VALUE SHOWN ON EVAPORATOR NAMEPLATE.
OPTIONAL FACTORY OR
4). MAY BE FACTORY INSTALLED-MOUNTED AND BY OTHERS
WIRED ON EVAPORATOR .
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
1-MP AIR 230V 11/05 AND NATIONAL CODES.
- 13 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM -
460/1/60, 575/1/60
AIR DEFROST MODELS
WITH DEFROST TIME CLOCK WITHOUT DEFROST TIME CLOCK
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL REFER TO EVAPORATOR
REQUIREMENTS NAMEPLATE FOR ELECTRICAL
CONTROL VOLTAGE REQUIREMENTS
L1 L2
L1 L2(N) L1 L2
FUSE OR
CIRCUIT
CONTROL VOLTAGE
BREAKER GND GND
GND NOTE #3 L1 L2(N)
FUSE OR
TO MULTIPLE CIRCUIT FUSE OR FUSE OR
EVAPORATORS BREAKER CIRCUIT CIRCUIT
GND
NOTE #3 BREAKER
(IF APPLIC) BREAKER
M1 NOTE #3
2ND FUSE NOTE #3
M2
OMITTED IF N
TO MULTIPLE 2ND FUSE
EVAPORATORS OMITTED IF N
TM
M1
M2
3 4 X (IF APPLIC)
1 2 N
GND
N.C. N.C.
EVAPORATOR EVAPORATOR
GND. GND.
FAN MOTOR FAN MOTOR
POWER POWER
PLUGS PLUGS
REFER TO REFER TO
FAN FAN FAN EVAPORATOR FAN FAN FAN EVAPORATOR
MTR MTR MTR DATA PLATE MTR MTR MTR DATA PLATE
FOR MOTOR FOR MOTOR
QUANTITY QUANTITY
TERMINALS
NOTES
-COMPONENT TERMINAL
1). USE COPPER CONDUCTORS ONLY
-TERMINAL BLOCK TERMINAL
2). USE 90C WIRE (OR HIGHER)
CONDUCTORS/WIRING
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND DEFROST FACTORY WIRING
HEATERS MUST NOT EXCEED MAXIMUM WIRING BY OTHERS
VALUE SHOWN ON EVAPORATOR NAMEPLATE.
OPTIONAL FACTORY OR
4). MAY BE FACTORY INSTALLED-MOUNTED AND BY OTHERS
WIRED ON EVAPORATOR .
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
2-MP AIR 460-575 10/05 AND NATIONAL CODES.
- 14 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM -
208-230/1/60, 460/1/60, 575/1/60
ELECTRIC DEFROST MODELS -SINGLE EV APORATOR
FOR ALL MODELS USING DEFROST HEATER CONTACTOR AND FAN CONTACTOR
REFER TO EVAPORATOR
DEFROST CLOCK NAMEPLATE FOR ELECTRICAL
CONTROL VOLTAGE
PARAGON # 8145 REQUIREMENTS
OR EQUIVALENT L1 L2(N) L1 L2
TM GND GND
FUSE OR
FUSE OR
CIRCUIT
CIRCUIT
3 4 X BREAKER
BREAKER
1 2 N NOTE #3
NOTE #3
L1 L2
DEFROST HEATER
C CONTACTOR
COMPR INTERLOCK T1 T2
(IF USED)
EVAP FAN
L1 L2 SPACE
C CONTACTOR THERMOSTAT
T1 T2
NOTE #4 N.C.
M1 M2 4 X H1 H2 N
BN
DT
GND. C
BK RD
FD
KLIXON DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
DT-DEFROST TERM
FD-FAN DELAY DEFROST HEATERS
FAN MOTOR
POWER PLUGS
REFER TO EVAPORATOR
FAN FAN FAN EVAPORATOR
MTR MTR MTR DATA PLATE FOR
MOTOR QUANTITY
NOTES TERMINALS
- 15 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM - 208-230/3/60
ELECTRIC DEFROST MODELS
WITHOUT FAN CONTACTOR
FOR ALL MODELS USING THREE PHASE DEFROST HEATER CONTACTOR
WITHOUT FAN CONTACTOR
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL
DEFROST CLOCK
REQUIREMENTS
PARAGON # 8145
OR EQUIVALENT L1 L2 L3
TM GND
FUSE OR
FUSE OR
CIRCUIT
CIRCUIT
BREAKER
3 4 X BREAKER
NOTE #3 NOTE #3
1 2 N
DEFROST HEATER
L1 L2 L3
C CONTACTOR
T1 T2 T3
COMPR INTERLOCK
(IF USED)
SPACE
THERMOSTAT
NOTE #4 N.C.
M1 M2 H1 H2 H3 N
4 X
BN
DT
GND. C
BK RD
FD
KLIXON DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
DT-DEFROST TERM
FD-FAN DELAY
DEFROST HEATERS
FAN MOTOR
POWER PLUGS
REFER TO
EVAPORATOR
FAN FAN FAN EVAPORATOR
MTR MTR MTR DATA PLATE FOR
MOTOR QUANTITY
NOTES TERMINALS
- 16 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM -
208-230/3/60, 460/3/60, 575/3/60
ELECTRIC DEFROST MODELS - SINGLE EV APORATOR
FOR ALL MODELS USING DEFROST HEATER CONTACTOR AND FAN CONTACTOR
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL
DEFROST CLOCK CONTROL VOLTAGE REQUIREMENTS
PARAGON # 8145
OR EQUIVALENT L1 L2(N) L1 L2 L3
TM GND GND
FUSE OR
FUSE OR
CIRCUIT
CIRCUIT
3 4 X BREAKER
BREAKER
1 2 N NOTE #3
NOTE #3
L2
DEFROST HEATER
L1 L3
C CONTACTOR
COMPR INTERLOCK T1 T2 T3
(IF USED)
EVAP FAN
L1 L2 SPACE
C CONTACTOR THERMOSTAT
T1 T2
NOTE #4 N.C.
M1 M2 4 X H1 H2 H3 N
BN
DT
GND. C
BK RD
FD
KLIXON DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
DT-DEFROST TERM
FD-FAN DELAY DEFROST HEATERS
FAN MOTOR
POWER PLUGS
REFER TO
EVAPORATOR
FAN FAN FAN EVAPORATOR
MTR MTR MTR DATA PLATE FOR
MOTOR QUANTITY
NOTES TERMINALS
- 17 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM - 208-230/3/60, 460/3/60, 575/3/60
ELECTRIC DEFROST MODELS -
MULTIPLE SINGLE PHASE EVAPORATORS
FOR ALL MODELS USING DEFROST HEATER CONTACTOR AND FAN CONTACTOR
REFER TO EVAPORATOR
DEFROST CLOCK NAMEPLATE FOR ELECTRICAL
CONTROL VOLTAGE REQUIREMENTS
PARAGON # 8145
OR EQUIVALENT L1 L2(N) L1 L2 L3
TM GND GND
FUSE OR
FUSE OR
CIRCUIT
CIRCUIT
3 4 X BREAKER
BREAKER
1 2 N NOTE #3
NOTE #3
L1 L2 L3 DEFROST HEATER
C
COMPR INTERLOCK CONTACTOR
T1 T2 T3
(IF USED)
*
M1 M2 4 X H1 H2 N
M1 M2 4 X H1 H2 N
BN
DT BN
GND. C
DT GND.
BK RD C
FD BK RD
FD
KLIXON DEFROST TERMINATION
& FAN DELAY KLIXON DEFROST TERMINATION
CONTROL & FAN DELAY
(10.0A MAX.) CONTROL
DT-DEFROST TERM
FD-FAN DELAY DEFROST HEATERS
SECONDARY
EVAPORATOR
*FAN DELAY NOT USED ON 2ND EVAP.
FAN MOTOR
POWER PLUGS
REFER TO PRIMARY
FAN FAN FAN EVAPORATOR
MTR MTR MTR DATA PLATE FOR EVAPORATOR
MOTOR QUANTITY
NOTES TERMINALS
- 18 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM - 208-230/3/60, 460/3/60, 575/3/60
ELECTRIC DEFROST MODELS -
MULTIPLE THREE PHASE EVAPORATORS
FOR ALL MODELS USING DEFROST HEATER CONTACTOR AND FAN CONTACTOR
REFER TO EVAPORATOR
DEFROST CLOCK NAMEPLATE FOR ELECTRICAL
CONTROL VOLTAGE REQUIREMENTS
PARAGON # 8145
OR EQUIVALENT L1 L2(N) L1 L2 L3
TM GND GND
FUSE OR
FUSE OR
CIRCUIT
CIRCUIT
3 4 X BREAKER
BREAKER
1 2 N NOTE #3
NOTE #3
L1 L2 L3 DEFROST HEATER
C
COMPR INTERLOCK CONTACTOR
T1 T2 T3
(IF USED)
*
M1 M2 4 X H1 H2 H3 N
M1 M2 4 X H1 H2 H3 N
BN
DT BN
GND. C
DT GND.
BK RD C
FD BK RD
FD
KLIXON DEFROST TERMINATION
& FAN DELAY KLIXON DEFROST TERMINATION
CONTROL & FAN DELAY
(10.0A MAX.) CONTROL
DT-DEFROST TERM
FD-FAN DELAY DEFROST HEATERS
SECONDARY
EVAPORATOR
*FAN DELAY NOT USED ON 2ND EVAP.
FAN MOTOR
POWER PLUGS
REFER TO PRIMARY
FAN FAN FAN
EVAPORATOR
EVAPORATOR
MTR MTR MTR DATA PLATE FOR
MOTOR QUANTITY
NOTES TERMINALS
- 19 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM -
208-230/1/60
HOT GAS DEFROST MODELS
- 20 -
K30-KMP-PDI-8 03/03/10
WIRING DIAGRAM -
460/1/60, 575/1/60
HOT GAS DEFROST MODELS
USING FAN CONTACTOR ( AND HEATER CONTACTOR IF APPLIC)
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL
REQUIREMENTS
L1 L2
GND
FUSE OR
CIRCUIT
BREAKER
F H1 H2 N
M1 M2 X 3
BN
*FAN HEATER
GND. C CONTROL
BK RD DRAIN PAN HEATER
ON REVERSE CYCLE LOCATED AT SUCTION LINE.
(IF APPLICABLE)
ON THREE-PIPE LOCATED AT DISTRIBUTOR SIDE PORT.
*FAN HEATER
CONTROL NOTE: DURING THE HOT GAS DEFROST CYCLE
THE FAN/HEATER CONTROL DE-ENERGIZES THE
RD
RD EVAPORATOR FANS AND ENERGIZES THE
DRAIN PAN HEATER.
(ANYTIME THE TEMPERATURE OF THE INCOMING
**DEFROST TERMINATION
CONTROL REFRIGERANT GAS IS ABOVE 50 F).
**DEFROST TERMINATION
FAN MOTOR
CONTROL
POWER PLUGS OPTIONAL FACTORY WIRED OR BY OTHERS
REFER TO
EVAPORATOR LOCATED ON TUBE END SHEET
FAN FAN FAN EVAPORATOR THE CONTROL CLOSES WHEN REACHES 55` F (20 F DIFF)
MTR MTR MTR DATA PLATE FOR
MOTOR QUANTITY
NOTES TERMINALS
- 21 -
K30-KMP-PDI-8 03/03/10
DIMENSIONAL DATA
50 1/4
(1276)
27 3/4
APPROX. 75 FEET
(704)
(23 METERS)
COMPARTMENT
COMPARTMENT
MTG SLOTS
IN OPEN SPACE
ELECTRICAL
1 FAN MODEL
PIPING
16 3/4
(425)
TOP VIEW
84 1/4
(2140)
8 1/8 34 36 6 1/8
(206) (864) (914) (156)
COMPARTMENT
COMPARTMENT
MTG SLOTS
ELECTRICAL
2 FAN MODEL
PIPING
16 3/4
(425)
TOP VIEW
118 1/4
(3004)
8 1/8 34 34 36 6 1/8
(206) (864) (864) (914) (156)
COMPARTMENT
COMPARTMENT
MTG SLOTS
ELECTRICAL
3 FAN MODEL
PIPING
16 3/4
(425)
TOP VIEW
136 1/4
(3461)
8 1/8 30 30 30 32 6 1/8
(206) (762) (762) (762) (813) (156)
COMPARTMENT
COMPARTMENT
MTG SLOTS
ELECTRICAL
4 FAN MODEL
PIPING
16 3/4
(425)
TOP VIEW
- 22 -
K30-KMP-PDI-8 03/03/10
DIMENSIONAL DATA/SPECIFICATIONS
Medium Temperature Air and Electric Defrost Models
MODEL NO. OF FANS SUCTION CONNECTION (ID) SWEAT DISTRIBUTOR INLET SIZE
118M# 1 7/8 5/8
122M# 1 1 1/8 5/8
228M# 2 1 1/8 5/8
236M# 2 1 3/8 5/8
245M# 2 1 3/8 7/8
355M# 3 1 5/8 7/8
368M# 3 1 5/8 7/8
480M# 4 1 5/8 7/8
488M# 4 1 5/8 7/8
# = A or E. Refer to Nomenclature for details
Low Temperature Electric Defrost Models
MODEL NO. OF FANS SUCTION CONNECTION (ID) SWEAT DISTRIBUTOR INLET SIZE
116LE 1 1 1/8 5/8
119LE 1 1 1/8 5/8
225L E 2 1 3/8 5/8
232L E 2 1 3/8 7/8
240L E 2 1 5/8 7/8
348L E 3 1 5/8 7/8
356L E 3 1 5/8 1 1/8
471L E 4 2 1/8 1 1/8
113VE 1 1 1/8 5/8
117VE 1 1 1/8 5/8
222V E 2 1 3/8 5/8
228V E 2 1 3/8 7/8
234V E 2 1 5/8 7/8
339V E 3 1 5/8 7/8
350V E 3 1 5/8 7/8
459V E 4 1 5/8 1 1/8
-24 -
K30-KMP-PDI-8 03/03/10
FACTORY INSTALLED DISTRIBUTOR NOZZLES
Note: For Hot Gas Defrost models only. Air and Electric Defrost models use Venturi distributors and no nozzle is required.
- 25 -
K30-KMP-PDI-8 03/03/10
RECOMMENDED EXPANSION VALVE SELECTIONS
MEDIUM TEMPERATURE MODELS
DANFOSS SPORLAN*
MODEL R 404A / R 507 R 22 R 134a MODEL R 404A / R 507 R 22 R 134a
118M TUAE-07 TUAE-06 TUAE-07 118M EGSE-1 1/2-C EGVE-1-1/2-C EGJE-1-C
122M TUAE-08 TUAE-07 TUAE-08 122M EGSE-1 1/2-C EGVE-1-1/2-C EGJE-1 1/2-C
228M TUAE-09 TUAE-08 TUAE-09 228M EGSE-2-C EGVE-2-C EGJE-1 1/2-C
236M TUAE-09 TUAE-08 TUAE-09 236M SSE-3-C EGVE-3-C SJE- 2 1/2-C
245M TCAE-2 TUAE-09 TCAE-2 245M SSE-4-C EGVE-3-C SJE-3-C
355M TCAE-3 TCAE-1 TCAE-3 355M SSE-4-C SVE-4-C SJE-3-C
368M TDEBS 5.8 TCAE-2 TDEBN 8.5 368M SSE-6-C SVE-5-C SJE-5-C
480M TDEBS 8.0 TCAE-3 TDEBN 9.6 480M SSE-7-C SVE-5-C SJE-6-C
488M TDEBS 8.0 TCAE-3 TDEBN 9.6 488M SSE-7-C SVE-8-C SJE-6-C
* For R507, refrigerant code for Sporlan expansion valve w ill be
""P"" instead of ""S"" . i.e.: ""EGSE"" becomes ""EGPE""
ALCO
MODEL R 404A / R 507 R 22 R 134a If c o r r e c t n o z z le is n o t a v a ila b le , t h e p r o p e r
118M HFESC - 1-1/4 - SC HFESC - 1-1/2 - HC HFESC - 1-1/2 - MC o r if ic e s iz e c a n b e d r ille d in t h e f ie ld u s in g
122M HFESC - 1-1/2 - SC HFESC - 2 - HC HFESC - 1-3/4- MC t h e f o llo w in g c h a r t
228M HFESC - 2 - SC HFESC - 2 - HC HFESC - 1-3/4 - MC N OZZL E D R IL L S IZE
236M HFESC - 3-1/2 - SC HFESC - 2-1/2 - HC HFESC - 2-1/2 - MC OR IF IC E N o . IN .
245M HFESC - 3-1/2 - SC HFESC - 3 - HC HFESC - 4 - MC
1 /2 .0 7 0
355M HFESC - 3-1/2 - SC HFESC - 5-1/2 - HC HFESC - 4 - MC
368M HFESC - 5 - SC HFESC - 5-1/2 - HC HFESC - 6- MC 3 /4 .0 8 6
480M HFESC - 7 - SC HFESC -5-1/2 - HC HFESC - 6 - MC 1 .0 9 9 5
488M HFESC - 7 - SC HFESC - 8 - HC HFESC - 7-1/2 - MC 1 - 1 /2 .1 2 0
2 .1 4 0 6
Above selections based on:
1) 100F (38C) vapor free liquid entering expansion valve 2 - 1 /2 .1 5 7
2) 110F (43C) Condensing temperature 3 .1 7 2
3) 8 -12F (4.4 -6.7C) evaporator TD
4 .1 9 9
5 .2 11
6 .2 4 2
8 .2 6 6
10 .2 8 1
- 26 -
K30-KMP-PDI-8 03/03/10
RECOMMENDED EXPANSION VALVE SELECTIONS
LOW TEMPERATURE R404A/7507 MODELS
SPORLAN*
MODEL 0 F (-18 C) EVAP. -10 F (-23 C) EVAP. -20 F (-29 C) EVAP. -30 F (-34 C) EVAP. -40 F (-40 C) EVAP.
116L EGSE-1-C EGSE-1 1/2-ZP EGSE-1 1/2-ZP EGSE-1 1/2-ZP EGSE-2-ZP
119L EGSE-1 1/2-C EGSE-1 1/2-ZP EGSE-2-ZP EGSE-2-ZP EGSE-2-ZP
225L EGSE-2-C EGSE-2-ZP SSE-3-ZP SSE-3-ZP SSE-3-ZP
232L SSE-3-C SSE-3-ZP SSE-4-ZP SSE-4-ZP SSE-4-ZP
240L SSE-4-C SSE-4-ZP SSE-4-ZP SSE-6-ZP SSE-6-ZP
348L SSE-4-C SSE-6-ZP SSE-6-ZP SSE-7-ZP SSE-7-ZP
356L SSE-6-C SSE-6-ZP SSE-7-ZP SSE-7-ZP OSE-9-ZP
471L SSE-7-C SSE-7-ZP OSE-9-ZP OSE-12-ZP OSE-12-ZP
113V EGSE-1-C EGSE-1-ZP EGSE-1-ZP EGSE-1 1/2-ZP EGSE-1 1/2-ZP
117V EGSE-1 1/2-C EGSE-1 1/2-ZP EGSE-1 1/2-ZP EGSE-2-ZP EGSE-2-ZP
222V EGSE-2-C EGSE-2-ZP EGSE-2-ZP EGSE-2-ZP SSE-3-ZP
228V EGSE-2-C SSE-3-ZP SSE-3-ZP SSE-3-ZP SSE-3-ZP
234V SSE-3-C SSE-3-ZP SSE-4-ZP SSE-4-ZP SSE-4-ZP
339V SSE-4-C SSE-4-ZP SSE-4-ZP SSE-4-ZP SSE-6-ZP
350V SSE-4-C SSE-6-ZP SSE-6-ZP SSE-7-ZP SSE-7-ZP
459V SSE-6-C SSE-6-ZP SSE-7-ZP OSE-9-ZP OSE-9-ZP
* For R507, refrigerant code for Sporlan expansion valve w ill be ""P"" instead of ""S"" . i.e.: ""EGSE"" becomes ""EGPE""
ALCO
MODEL 0 F (-18 C) EVAP. -10 F (-23 C) EVAP. -20 F (-29 C) EVAP. -30 F (-34 C) EVAP. -40 F (-40 C) EVAP.
116L HFESC - 1-1/4 - SC HFESC - 1-1/2 - SW45 HFESC - 2 - SW45 HFESC - 2 - SW45 HFESC - 2 - SW45
119L HFESC - 1-1/2 - SC HFESC - 1-1/2 - SW45 HFESC - 2 - SW45 HFESC - 2 - SW45 HFESC - 3-1/2 - SW45
225L HFESC - 2 - SC HFESC - 2 - SW45 HFESC - 3-1/2 - SW45 HFESC - 3-1/2 - SW45 HFESC - 3-1/2 - SW45
232L HFESC - 2- SC HFESC - 3-1/2 - SW45 HFESC - 3-1/2 - SW45 HFESC - 3-1/2 - SW45 HFESC - 5 - SW45
240L HFESC - 3-1/2 - SC HFESC - 3-1/2 - SW45 HFESC - 5 - SW45 HFESC - 5 - SW45 HFESC - 5 - SW45
348L HFESC - 3-1/2 - SC HFESC - 5- SW45 HFESC - 5 - SW45 HFESC - 7 - SW45 HFESC - 7- SW45
356L HFESC - 3-1/2 - SC HFESC - 5 - SW45 HFESC - 7 - SW45 HFESC - 7 - SW45 HFESC - 10 - SW45
471L HFESC - 5 - SC HFESC - 7 - SW45 HFESC - 10 - SW45 HFESC - 10 - SW45 HFESC - 13 - SW45
113V HFESC - 1 - SC HFESC - 1-1/4 - SW45 HFESC - 1-1/2 - SW45 HFESC - 1-1/2 - SW45 HFESC - 2 - SW45
117V HFESC - 1-1/4 - SC HFESC - 1-1/2 - SW45 HFESC - 2 - SW45 HFESC - 2 - SW45 HFESC - 3-1/2 - SW45
222V HFESC - 1-1/2 - SC HFESC - 2 - SW45 HFESC - 2 - SW45 HFESC - 3-1/2 - SW45 HFESC - 3-1/2 - SW45
228V HFESC - 2 - SC HFESC - 2 - SW45 HFESC - 3-1/2 - SW45 HFESC - 3-1/2 - SW45 HFESC - 3-1/2- SW45
234V HFESC - 3-1/2 - SC HFESC - 3-1/2 - SW45 HFESC - 3-1/2 - SW45 HFESC - 5 - SW45 HFESC - 5 - SW45
339V HFESC - 3-1/2 - SC HFESC - 3-1/2 - SW45 HFESC - 5 - SW45 HFESC - 5 - SW45 HFESC - 5 - SW45
350V HFESC - 3-1/2 - SC HFESC - 5 - SW45 HFESC - 5 - SW45 HFESC - 7 - SW45 HFESC - 7 - SW45
459V HFESC - 5 - SC HFESC - 5 - SW45 HFESC - 7 - SW45 HFESC - 10 - SW45 HFESC - 10 - SW45
- 27 -
K30-KMP-PDI-8 03/03/10
INSTALLATION INSTRUCTIONS
INSTALLATION EXPANSION VALVE (TXV) SELECTION
The installation and start-up of Unit Coolers should only All units require the use of an externally equalized
be performed by qualified refrigeration mechanics. expansion valve. (A 1/4(6 mm) O.D. equalizer line has
This equipment should be installed in accordance with all been provided on the coil) TX valves shouldnot be
applicable codes, ordinances and local by-laws. selected strictly by their nominal ton rating. (This rating
is based at a specific pressure differential and entering
INSPECTION liquid temperature). Since applications will differ it is
Inspect all equipment before unpacking for visible signs of suggested the following selection procedure be followed.
damage or loss. Check shipping list against material
received to ensure shipment is complete. 1. Determine actual unit cooler capacity.
The nominal rating is based at 10OF T.D. (5 .6C)
IMPORTANT: Remember, you, the consignee, must make (Entering Air Temp. minus Evap. Temp.), R404A
any claim necessary against the transportation company. refrigerant. For R22, use the rated capacity x 0.95.
Shipping damage or missing parts, when discovered at For medium temperature R134a, use the rated
the outset, will prevent later unnecessary and costly capacity x 0.90. Note that a higher / lower operating
delays. T.D.will increase / decrease this capacity rating by
If damage or loss during transport is evident, make their direct ratio within a range of 8 to 12F(4.4 to
claim to carrier, as this will be their responsibility,
6.7C) T.D.
not the manufacturers.
Should carton be damaged, but damage to equipment is
not obvious, a claim should be filed for concealed 2. Determine the pressure drop across the valve by
damage with the carrier. subtracting the evaporating pressure and distributor
pressure drop from the high side liquid pressure.
IMPORTANT: The electrical characteristics of the unit The distributor pressure drop is typically in the range
should be checked at this time to make sure they of 20 to 35 psig (1.4 to 2.4 bar) depending on the type
correspond to those ordered and to electrical power of refrigerant and operating conditions.
available at the job site.
3. Estimate entering liquid temperature.Temperatures
Save all shipping papers, tags and instruction sheets for lower than 100F (38 C) increase valve capacity
reference by installer and owner. ratings. Refer to valve manufacturers specs for
details.
APPLICATION
MP unit coolers are designed for walk-in cooler, walk-in 4. Select valve from the valve manufacturer selection
refrigerated warehouse and food processing plant applica- charts or software for the appropriate refrigerant,
tions used with refrigerant R22 or R404A. For room evaporating tempand pressure drop.
temperatures above 35F (2C) AND evaporating tempera-
tures above 26F (-3C), positive defrosting means (with
electric or hot gas) may not be required, otherwise, For best performance, the outlet of the expansion valve
electric defrost or hot gas defrost models should be used. should be installed directly to the distributor body. If this
Electric defrost models come with defrost termination and is not possible, a straight tube up to 12 inches may be
fan delay as standard to control the defrost cycle termina- used for the connection.
tion and fan delay, while defrost initiation means (e.g.
defrost timer) is not included. Locate the expansion valve bulb on a horizontal length
of suction line preferably 3 to 6 inches from the suction
For other types of refrigerant, contact factory
. header. Locate the bulb at 4 or 8 clock position and
insulate with a waterproof type of insulation. Clamp the
The coil must not be exposed to any abnormal
atmospheric or acidic environments. This may result in bulb to ensure 100% contact of the bulb with the
corrosion to the cabinet and possible coil failure (leaks). suction line.
(Consult manufacturer for optional baked on phenolic
protective coatings). For hot gas defrost models, ensure appropriate nozzle
has been installed in the distributor before installing
LOCATION valve. After following the manufacturers installation
The unit location in the room should be selected to ensure instructions and after the room has reached the desired
uniform air distribution throughout the entire space to be temperature the valve superheat should be checked.
refrigerated. Be sure that the product does not obstruct This will confirm that the evaporator is operating
the free circulation of air. Allow a minimum of 24 clear- properly and performing to maximum efficiency. The
ance at each end. Do not locate evaporators over doors. superheat should be around 60 to 80% ofT.D. Too high
Consideration should be given to the coil location in order or low a super heat will result in unsatisfactory system
to minimize the piping run length to the
performance and possible compressor problems.
condensing unit and floor drain.
- 28 -
K30-KMP-PDI-8 03/03/10
INSTALLATION INSTRUCTIONS
NOZZLE INSTALLATION
All air defrost and electric defrost models use venturi To prevent freeze-up when the temperature of the
distributors and no nozzles required. For hot gas defrost refrigerated space is 35oF (2 C) or lower, the drain line
models, a nozzle has been pre-selected and factory should be heated along its run inside the cold room. The
installed for common applications (Medium temp. R404A, heated drain line should be insulated. It is recommended
R22, 8 to 12F (4.4 to 6.7C) T.D.; low temp. R404A, 8 to that the heater be energized at all times.A heat input of
12F (4 .4 to 6.7C) T.D.). For other applications, refer to 20 watts per foot in a 28F(-2C) room and 30 watts per
the nozzle manufacturer for selection method. When foot for -20F (-29C) rooms, is satisfactory. Drain line
replacing a nozzle, the nozzle retainer clip (in distributor) heaters are not required for constant room temperature
must be removed before inserting nozzle. Re-install clip above 35F (2C).
ensuring nozzle is properly in place.A small nozzle can Always trap evaporator drain line individually to prevent
be drilled larger using the drill size listed in table on page vapor migration.
25. Ensure the hole must be accurately centered and
smooth. A lathe is preferred for the drilling. Ensure that the drain line has sufficient slope for
proper drainage (prevention of ice build up/blockage
MOUNTING in pan).
Refer to dimensional drawing for recommended mounting
arrangements. Ensure adequate clearance is provided PIPING
behind the coil as well as each end. The evaporators may Refrigeration grade piping must be used for all field
be mounted flush with ceiling with bolts, or hanging down refrigeration piping. Refrigerant line sizes are important
with rod hangers. When using rod hangers, allow ad- and may not be the same size as the coil connections.
equate space between the top of the unit and the ceiling Consult ASHRAE handbook or other similar reference
for cleaning to comply with NSF Standard 7. book for proper line sizing.
Ensure that the ceiling is level since the drain pan Refrigerant piping and control system should be designed
has been sloped for drainage during the defrost to prevent possible liquid slugging (from oil or refrigerant)
cycle. of the compressors on start-up after the defrost cycle.
Also, it should prevent oil logging and minimize refrigerant
DRAIN LINE pressure drop.
The drain line should be run from the drain connection,
sloping at least 1(25 mm) per foot and should have the For hot gas models, see pages 31 to 32 for
size at least as large as the drain connection.A trap in a recommended piping.
warm area outside the room must be provided to allow
proper draining through the tubing. Connection should be
made to proper drainage facilities that comply with local
regulations.
- 29 -
K30-KMP-PDI-8 03/03/10
INSTALLATION INSTRUCTIONS
WIRING SYSTEM CHECK
Wire system in accordance with governing standards and Before Start-Up:
local codes. See data and wiring diagrams on pages 4 to
21 for typical wiring arrangement. Electrical wiring is to be 1. All wiring should be in accordance with local codes.
2. Refrigerant lines should be properly sized.
sized in accordance with minimum circuit ampacity rating
3. All systems preferably include a liqud line solenoid
(MCA). Size fuses used must not exceed the Maximum
valve at immediately up stream of the expansion
Fuse Size ratings.
valve.
4. Thorough evacuation and dehydration has been
For ease of identifying the proper wiring terminal, unit performed.
wiring is color coded and terminal block connections are 5. The suction, discharge, and receiver service valves
identified. must be open.
6. The system preferably include a liquid line filter drier
When fan delay thermostats (combination fan delay and moisture indicator and suction filter.
defrost termination) are installed, on start-up, the fans do 7. Pour enough water into the drain pan to allow a
good check on drainage and seal the trap.
not operate until the coil temperature is reduced to
approximately 25oF (-4C). It is normal for the fans to
After Start-Up:
cycle a few times until the room temperature is brought 1. Check the oil level to be sure the oil charge is
down. At higher evaporating temperatures this control may correct.
not close and therefore should either be by-passed 2. On initial start up the fans do not start until coil
temporarily or replaced with an adjustable type. (set for a temperature is pulled down to approximately 25F
higher temperature cut-in point). (-4 C) on the coil. Also, it is normal for the fan to
cycle a few times until the room temperature is
pulled down.
MAINTENANCE 3. If necessary, temporarily by-pass fan delay control
The unit should be periodically inspected for any dirt or ice (to run fans until room temp is lowered).
build-up on the fin surface and cleaned if necessary with a 4. Be sure that the expansion valve is properly set to
provide the correct amount of superheat.
soft whisk or brush.Also ensure coils inner (and outer)
5. After the box temperature is close to reaching the
drain pans do not have any ice build-up from improper
desired temperature, the evaporator superheat must
defrost operation. When replacing heater elements first be checked and adjustment made if necessary.
remove heater retainer brackets and heater clips. In general, evaporators running with a TD of 10F
(5.6 C) should have a superheat reading of 6 to 8F
(3.3C to 4.4 C). For evaporators withanother T.D.,
the general rule is that the superheat should be around
60 to 80% of T.D.
6. Heavy moisture loads are usually encountered
when starting the system for the first time. This may
cause a rapid build-up of frost on the unit cooler .
During the initial pull down, we suggest that the frost
build-up be watched and defrosted manually as required.
7. Observe that the system goes through at least one
complete DEFROST CYCLE.
- 30 -
K30-KMP-PDI-8 03/03/10
HOT GAS PIPING SCHEMATICS
STANDARD CONFIGURATIONS
LEAVING ENTERING
HOT GAS HOT GAS
CHECK CHECK
VALVE VALVE
STD-R LEAVING
HOT GAS STD-H
HOT GAS DRAIN PAN FACTORY PIPING HOT GAS DRAIN PAN FACTORY PIPING
DEFROST LOOP DEFROST LOOP
REVERSE CYCLE DEFROST WITH DRAIN PAN HEATER 3-PIPE DEFROST WITH DRAIN PAN HEATER
WITH CHECK VALVE LOOSE WITH CHECK VALVE LOOSE
EVAPORATOR COIL DISTRIBUTOR EVAPORATOR COIL DISTRIBUTOR
CHECK CHECK
VALVE VALVE
LEAVING ENTERING
HOT GAS HOT GAS
ENTERING
STD-G STD-T
HOT GAS LEAVING
HOT GAS
- 31 -
K30-KMP-PDI-8 03/03/10
HOT GAS PIPING SCHEMATICS
OPTIONAL CONFIGURATIONS
CHECK
CHECK VALVE
VALVE
ENTERING
HOT GAS DRAIN PAN HOT GAS
FACTORY PIPING DEFROST LOOP FACTORY PIPING
HOT GAS DRAIN PAN
DEFROST LOOP
REVERSE CYCLE DEFROST WITH DRAIN PAN HEATER 3 PIPE DEFROST WITH CHECK VALVE MOUNTED
CHECK VALVE MOUNTED WITH TXV BY OTHERS OR FACTORY INSTALLED
COMPLETE ASSY PROVIDED WHEN TXV IS MTD
TXV EVAPORATOR COIL DISTRIBUTOR
EVAPORATOR COIL DISTRIBUTOR
LEAVING
HOT GAS TXV
CHECK
CHECK VALVE
VALVE ENTERING
OPT1
HOT GAS
LEAVING
OPT1
G
HOT GAS
T
(SUCTION LINE)
CHECK
VALVE
OPT2
R
ENTERING
HOT GAS
CHECK
VALVE
- 32 -
K30-KMP-PDI-8 03/03/10
GLYCOL FLUID AIR COOLER DATA
60Hz
CAPACITY * - 15 USGPM (.095 L/S), 3/8" TUBING CAPACITY * - 40 USGPM (.25 L/S), 1/2" TUBING
NO.
MODEL OF AIR FLOW CONN. AIR FLOW CONN.
P.D. P.D. P.D. P.D.
FANS BTU/H (WATTS) SIZE BTU/H (WATTS) SIZE
C FM (L/S) (FT. H20) (kPa) C FM (L/S) (FT. H20) (kPa)
(IN/OUT) (IN/OUT)
118W 1 3430 (1620) 8980 (2630) 4.8 (14.3) 1 3/8 3150 (1486) 11100 (3250) 7.8 (23.3) 1 5/8
122W 1 3240 (1530) 10400 (3050) 2.8 (8.4) 1 3/8 2990 (1411) 12700 (3720) 4.6 (13.7) 1 5/8
236W 2 6870 (3240) 15400 (4510) 8.1 (24.2) 1 3/8 6300 (2973) 21700 (6360) 13 (37.4) 1 5/8
245W 2 6480 (3060) 18100 (5300) 4.8 (14.3) 1 3/8 5980 (2822) 22800 (6680) 7.4 (22.1) 1 5/8
355W 3 10300 (4860) 20700 (6060) 11 (33.2) 1 3/8 9480 (4474) 31900 (9340) 17 (51.7) 1 5/8
368W 3 9720 (4590) 24200 (7090) 6.7 (20.0) 1 3/8 8940 (4219) 31600 (9260) 10 (31.1) 1 5/8
480W 4 13000 (6140) 27700 (8110) 7.6 (22.7) 1 3/8 11990 (5658) 37500 (11000) 12 (35.3) 1 5/8
The above capacities were rated based on 30% Propylene Glycol, 25F (-4C) glycol entering temperature and 35F (2C) air entering termperature
with glycol flow rate listed. For all other conditions, please use "Pi-Coil" software (contact factory).
Miscellaneous
GENERIC SERVICE PARTS LIST
60Hz
DESCRIPTION PART # DESCRIPTION PART #
FAN MOTOR (PSC) 208-230/1/60, 200-220/1/50 1082710 HEATER RETAINER CLIP-COIL LP/MP (WIRE CLIP) 1048609
FAN MOTOR (PSC) 460/1/60, 380-400/1/50 1082711 HINGE ASSY #8820-16GA-2"X2"OP-STAINLESS STEEL 160401
FAN MOTOR (PSC) 575/1/60 1082712 TERMINAL BOARD AIR DEFROST (460V) 1045017
MOTOR MOUNT (PSC) 1045031 INSULATOR, for 460V terminal board #1045017 171159
FAN MOTOR (EC) 208-230/1/60 1087430 TERMINAL BOARD ED & HG 1083880
MOTOR MOUNT (EC) 1087601 DRAIN FITTING 1085310
FAN BLADE 1082709 LOCKNUT - DRAIN FITTING 1081102
FAN GUARD (PLASTIC) 1082703 GASKET - DRAIN FITTING 1081103
FAN GUARD (WIRE) 1045091 HEATER HOLD DOWN BRKT-DRAIN PAN 1083005
ACORN NUT #CN3/8-16 PANTONE GREY#429-C 1082951 HANGER BRKT MP 1082481
NUT/WHIZ-LOCK 3/8-16-UNC #N-70 for use with SCREWS: #12 x 5/8" lg. 1081100
1045090
WIRE GUARD SCREWS: #14 x 3/4" lg. 1043774
- 33 -
K30-KMP-PDI-8 03/03/10
GENERIC SERVICE PARTS LIST
60Hz
Defrost Heaters - Hot Gas Defrost with Electric Drain Pan
PART NUMBER
MODELS DRAIN PAN HEATER (1 REQUIRED)
208-230V 460V 575V
118MT 118MG 116LT 116LG 113VT 113VG 534W / 1083029-001 534W / 1083029-101 534W / 1083029-201
122MT 122MG 119LT 119LG 117VT 117VG 534W / 1083029-001 534W / 1083029-101 534W / 1083029-201
228MT 228MG 225LT 225L G 222V T 222V G 887W / 1083029-002 887W / 1083029-102 887W / 1083029-202
236MT 236MG 232LT 232L G 228V T 228V G 887W / 1083029-002 887W / 1083029-102 887W / 1083029-202
245MT 245MG 240LT 240L G 234V T 234V G 887W / 1083029-002 887W / 1083029-102 887W / 1083029-202
355MT 355MG 348LT 348L G 339V T 339V G 1240W / 1083029-003 1240W / 1083029-103 1240W / 1083029-203
368MT 368MG 356LT 356L G 350V T 350V G 1240W / 1083029-003 1240W / 1083029-103 1240W / 1083029-203
480MT 480MG 471LT 471L G 459V T 459V G 1430W / 1083029-004 1430W / 1083029-104 1430W / 1083029-204
488MT 488MG N/A N/A N/A N/A 1430W / 1083029-004 1430W / 1083029-104 1430W / 1083029-204
- 34 -
K30-KMP-PDI-8 03/03/10
FINISHED GOODS WARRANTY
The terms and conditions as described below in the General W
arranty Policy cover all products
manufactured by National Refrigeration.
GENERAL WARRANTY POLICY
Subject to the terms and conditions hereof, the Company warrants all Products, including Service
Parts, manufactured by the Company to be free of defects in material or workmanship, under normal
use and application for a period of one (1) year from the original date of installation, or eighteen (18)
months from the date of shipment from the Company, whichever occurs first. Any replacement
part(s) so supplied will be warranted for the balance of the products original warranty. The part(s) to
be replaced must be made available in exchange for the replacement part(s) and reasonable proof of
the original installation date of the product must be presented in order to establish the effective date
of the warranty, failing which, the effective date will be based upon the date of manufacture plus thirty
(30) days. Any labour, material, refrigerant, transportation, freight or other charges incurred in con-
nection with the performance of this warranty will be the responsibility of the owner at the current
rates and prices then in effect. This warranty may be transferred to a subsequent owner of the
product.
No one is authorized to change this WARRANTY or to create for or on behalf of the Company any
other obligation or liability in connection with the Product(s). There is no other representation, warranty
or condition in any respect, expressed or implied, made by or binding upon the Company other than the
above or as provided by provincial or state law and which cannot be limited or excluded by such law , nor
will we be liable in any way for incidental, consequential, or special damages however caused.
The provisions of this additional written warranty are in addition to and not a modification of or subtraction
from the statutory warranties and other rights and remedies provided by Federal, Provincial or S tate
laws.
PROJECT INFORMATION
S ys t e m
M o d e l N um b e r D a t e o f St a r t - U p
S e r i a l N um b e r S e r vi c e C o nt r a c t o r
R e f r i g e r a nt P ho ne
E l e c t r i c a l S up p l y Fax
- 35 -
K30-KMP-PDI-8 03/03/10
AS BUILT SERVICE PARTS LIST
CANADA USA
159 ROY BLVD., BRANTFORD, ONTARIO, CANADA N3R 7K1 985 WHEELER WAY, LANGHORNE, PA. 19047 USA
PHONE: 1-800-463-9517 (519)751-0444 F AX (519)753-1140 PHONE:1-888-KEEPUS1 OR 1-888-533-7871
Due to National Refrigerations policy of continuous product improvement, we reserve the right to make changes without notice.