Asme Standards For Boilers
Asme Standards For Boilers
Asme Standards For Boilers
Boiler type: Industrial watertube, high duty, primary fuel fired, drum type
Makeup water percentage: Up to 100% of feedwater
Conditions: Includes superheater, turbine drives, or process restriction on steam purity
Steam: superheated and/or turbine
Saturated steam purity target: See tabulated values below
Drum Operating Pressure psig 0-300 301-450 541-600 601-750 751-900 901-1000 1001-1500 1501-2000
(1) (11) (MPa) (0-2.07) (2.08-3.10) (3.11-4.14) (4.15-5.17) (5.18-6.21) (6.22-6.89) (6.90-10.34) (10.35-13.79)
Feedwater (7)
Dissolved oxygen ppm (mg/l) O2 <0.007 <0.007 <0.007 <0.007 <0.007 <0.007 <0.007 <0.007
measured before chemical oxygen
scavenger addition (8)
Total iron ppm (mg/l) Fe <0.1 <0.05 <0.03 <0.025 <0.02 <0.02 <0.01 <0.01
Total copper ppm (mg/l) Cu <0.05 <0.025 <0.02 <0.02 <0.015 <0.01 <0.01 <0.01
Total hardness ppm (mg/l) CaCO3 <0.3 <0.3 <0.2 <0.2 <0.1 <0.05 ND ND
pH range @ 25C 8.3-10 8.3-10 8.3-10 8.3-10 8.3-10 8.8-9.6 8.8-9.6 8.8-9.6
Chemicals for preboiler system protection NS NS NS NS NS VAM VAM VAM
Nonvolatile TOC ppm (mg/l) C (6) <1 <1 <0.5 <0.5 <0.5 <0.2 <0.2 <0.2
Oily matter ppm (mg/l) <1 <1 <0.5 <0.5 <0.5 <0.2 <0.2 <0.2
Boiler Water
Silica ppm (mg/l) SiO2 <150 <90 <40 <30 <20 <8 <2 <1
Total alkalinity ppm (mg/l) CaCO3 <700 (3) <600 (3) <500 (3) <200 (3) <150 (3) <100 (3) NS (4) NS (4)
Free hydroxide ppm (mg/l) CaCO3 (2) NS NS NS NS NS NS ND (4) ND (4)
Unneutralized conductivity mhos/cm 5400- 4600-900(5) 3800-800(5) 1500-300(5) 1200-200(5) 1000-200(5) <150 <80
(S/cm) 25C (12) 1100(5)
NOTES TO TABLE
(1) With local heat fluxes >1.5 x 105 Btu/hr/ft2 (>473.2 kW/m2), use values for at least the next higher pressure range.
(2) Minimum hydroxide alkalinity concentrations in boilers below 900 psig (6.21 MPa) must be individually specified by a qualified water treatment consultant with
regard to silica solubility and other components of internal treatment.
(3) Maximum total alkalinity consistent with acceptable steam purity. If necessary, should override conductance as blow-down control parameter. If makeup is
demineralized quality water and boiler operates at less than 1000 psig (6.89 MPa) drum pressure, the boiler water conductance should be that in table for 1001-
1500 psig (6.9-10.34 MPa) range. In this case, the necessary continuous blowdown will usually keep these parameters below the tabulated maximum values.
Alkalinity values in excess of 10% of specific conductance values may cause foaming.
(4) Not detectable in these cases refers to free sodium or potassium hydroxide alkalinity. Some small variable amount of total alkalinity will be present and
measurable with the assumed congruent or co-ordinated phosphate-pH control or volatile treatment employed at these high pressure ranges.
(5) Maximum values are often not achievable without exceeding maximum total alkalinity values, especially in boilers below 900 psig (6.21 MPa) with >20% makeup
of water whose total alkalinity is >20% of TDS naturally or after pre-treatment by lime-soda, or sodium cycle ion exchange softening. Actual permissible
conductance values to achieve any desired steam purity must be established for each case by careful steam purity measurements. Relationship between
conductance and steam purity is affected by too many variables to allow its reduction to a simple list of tabulated values.
(6) Nonvolatile TOC is that organic carbon not intentionally added as part of the water treatment regime.
(7) Boilers below 900 psig (6.21 MPa) with large furnaces, large steam release space, and internal chelant, polymer, and/or antifoam treatment can sometimes
tolerate higher levels of feedwater impurities than those in the table and still achieve adequate deposition control and steam purity. Removal of these impurities
by external pretreatment is always a more positive solution. Alternatives must be evaluated as to practicality and economics in each individual case.
(9) Achievable steam purity depends on many variables, including boiler water total alkalinity and specific conductance as well as design of boiler steam drum
internals and operating conditions [(Note (5)]. Since boilers in this category require a relatively high degree of steam purity for protection of the superheaters and
turbines, more stringent steam purity requirements such as process steam restrictions on individual chemical species or restrictions more stringent than 0.1 ppm
(mg/l) TDS turbine steam purity must be addressed specifically.
(10) As a general rule, the requirements for attemperation spray water quality are the same as those for steam purity. In some cases boiler feedwater is suitable;
however, frequently additional purification is required. In all cases the spray water should be obtained from a source that is free of deposit forming and corrosive
chemicals such as sodium hydroxide, sodium sulfite, sodium phosphate, iron, and copper. The suggested limits for spray water quality are <30 ppb (g/l) TDS
maximum, <10 ppb (g/l) Na maximum, <20 ppb (g/l) SiO2 maximum, and it should be essentially oxygen free.
(11) Low pressure boilers frequently use feedwater that is suitable for use in higher pressure boilers. In these cases the boiler water chemistry limits should be based
on the pressure range that is most consistent with the feedwater quality.
(12) Conversion from ppm (mg/l) TDS values in the ABMA standards [12] used a factor of 0.65.