Single-Phase Power Supply Unit, Primary Switched For Universal Use QUINT-PS-100-240AC/48DC/20
Single-Phase Power Supply Unit, Primary Switched For Universal Use QUINT-PS-100-240AC/48DC/20
Single-Phase Power Supply Unit, Primary Switched For Universal Use QUINT-PS-100-240AC/48DC/20
1. Short Description
The QUINT POWER product range offers universal
DC power supplies from 60 - 960 W. Depending on the
type, regulated and adjustable output voltages of
12 V DC, 24 V DC or 48 V DC are available for output
currents of 2.5 A, 5 A, 10 A, 20 A, 30 A, and 40 A.
These devices, which are designed as primary
switched-mode regulators, operate with a high level of
efficiency so that heat loss is kept to a minimum.
The high level of operational safety is also ensured in
complex global networks. QUINT POWER also 2. Area of Application
operates in applications where static voltage dips, QUINT POWER can be used globally due to the
transient power supply failures or phase failure are consistent provision of a wide-range input.
common. In this way, your entire system can be tested at any
Powerful capacitors ensure mains buffering of more production location in the world and can be delivered to
than 20 ms at full load. All 3-phase QUINT POWER any location in the world without faulty switching of the
units provide the complete output power even in the input voltage. This reduces storage costs and logistical
event of a continuous phase failure. effort.
Reliable startup of heavy loads is ensured by a An international approval package including CB
power reserve of up to 50% the POWER BOOST. Scheme, UL 60950 for IT equipment, and UL 508 for
Preventive function monitoring diagnoses an industrial control equipment enables the device to be
impermissible operating state and minimizes used globally.
downtimes in your system. An active transistor output Safe operation in adverse conditions is emphasized
and a floating relay contact are provided for remote by the approval of all QUINT POWER units with
monitoring of this state. 24 V output voltage by Germanischer Lloyd.
This signal not only provides information on the
device function, but also indicates a system overload at
an early stage.
Headquarters: Phoenix Contact GmbH & Co. KG Flachsmarktstrae 8 32825 Blomberg Germany
Phone +49 - 52 35 - 30 0 Fax +49 - 52 35 - 34 12 00 www.phoenixcontact.com
Local contact: www.phoenixcontact.com/salesnetwork
Single-Phase Primary-Switched Power Supply Unit for Universal Use QUINT 48 V DC/20 A
3. Technical Data
125 mm
L (+ )
a c tiv e
130 mm
N (-) P F C
P E D C O K
1 3
1 4
240 mm
QUINT 48 V DC/20 A
Scheme U uB
1 AC CB
Solid Stranded Torque
[mm2] AWG Nm] [Ib in.]
Pcs.
Description Type Order No. Pkt.
Power supply unit,
primary switched for universal use QUINT-PS-100-240AC/48DC/20 29 38 97 6 1
Technical Data
Input Data 1
Nominal input voltage 110 - 240 V AC (wide-range input)
Input voltage range 85 - 264 V AC 120 - 350 V DC
Frequency 45 - 65 Hz 0 Hz
Current consumption (for nominal values) 11 A (120 V AC)/5 A (230 V AC)
Inrush current limiting/I2t (+25C) 15 A, approximately/3.2 A2s, approximately
Mains buffering for a nominal load (typical) > 20 ms
Switch-on time after applying the mains voltage <1s
Transient surge protection Varistor
Input fuse, internal 20 AF (device protection)
Recommended backup fuse 16 A or 25 A circuit breaker,
characteristic B (EN 60 898)
Discharge current for PE < 3.5 mA
Output Data 2
Nominal output voltage UN/tolerance 48 V DC 1%
Setting range for the output voltage 30 - 56 V DC
Output current (continuous) during convection cooling
and nominal values Nominal output current IN -25C to +60C 20 A (Uout = 48 V DC)
IBOOST 22.5
Derating From +60C 2.5% per Kelvin/below 100 V AC: 2.5%/V
Short-circuit current limit 27.5 A, approximately
Startup of capacitive loads Unlimited
System deviation on: Static load change 10 - 90% < 1%, typical
Dynamic load change 10 - 90% < 5%, typical
Input voltage change 10% < 0.1%, typical
Maximum power dissipation No load/nominal load 20 W/80 W, approximately
Efficiency > 92% (for 230 V AC and nominal values)
Response time UOUT (10% - 90%) < 2 ms
Residual ripple/switching peaks (20 MHz) < 100 mVpp (for nominal values)
Can be connected in parallel To increase redundancy and power
Internal surge protection Yes, limited to 60 V DC, approximately
Resistance to return supply 60 V DC
General Data
Insulation voltage: Input/output 3 kV AC (type test)/2 kV AC (routine test)
Input/PE 3 kV AC (type test)/1.5 kV AC (routine test)
Output/PE 500 V DC (routine test)
Approval package CB
Scheme B
Electrical equipment of machines EN 60 204 (Surge Voltage Category III)
Safety transformers for switched-mode power supply units EN 61 558-2-17
Electrical safety EN 60950/VDE 0805,
(of IT equipment) UL/C-UL Recognized UL 60 950 u
Industrial control equipment UL/C-UL Listed UL 508 U
Electronic equipment for use in electrical LISTED
power installations EN 50 178 (VDE 0160)
Safety extra-low voltage PELV (EN 60 204)
SELV (EN 60 950)
Safe isolation VDE 0100-410
Protection against electric shock DIN 57100-410
Protection against electric shock,
basic requirements for safe isolation
in electrical equipment DIN VDE 0106-101
Limitation of harmonic line currents According to EN 61000-3-2
Climatic Data
Ambient temperature Operation -25C to +70C (> +60C derating)
Storage -40C to +85C
Humidity Up to 95% at +25C, no condensation
Vibration According to IEC 68-2-6 < 15 Hz, amplitude 2.5 mm/15 Hz - 150 Hz, 2.3g, 90 minutes
Shock According to IEC 68-2-27 30g in all space directions
Pollution degree 2 (according to EN 50 178)
Climatic category 3K3 (according to EN 60 721)
c
Conformance With EMC Directive 89/336/EEC and
Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility) Requirements
Noise Immunity According to EN 61000-6-2: EN 61 000-6-2 QUINT-PS-100-240AC/48DC/20
6
DC
O
K O
DC 7
13
14
DC
O
K
QUINT POWER
+ O
u
+ tput DC
48
V
20
A
In
pu
5 tA
C
N 100- /20
24
L 0V DC
/48
4 00
40
-2 7 6
-1 8 9
www.interface.phoenixcontact.com
- PS 29 3
T
IN o.:
QU er-N
d
Or
C
60 F
3 2 DC -1
3
+ 40
5+1
-2
95
0
5 60 04 -17
O 2 EN 02 -2
6 58
K OK EN 615
DC
B
Ad EN
ju 0-6
-2
30 st 00
-5 S
L 61 81-1
6V RIA N
AL ST L E 50 0
OV DU RO NT
IN NT ME
EN
PR COUIP
13 AP EQKA
43 ns
U
14 io s
DC ct
r u a in
D
TE
O LIS st
K in o m
1 + O n t
io
ut
pu ll a t t in g
+ a ec
tD st
C in o n n
48 ad c
V R ef o r e
20
A be
5
Figure 04
6. Installation
6.1. Mounting
The power supply unit can be snapped onto all DIN
rails according to EN 60715 and should be mounted
horizontally (input terminal blocks facing downwards).
Installation Dimensions
QUINT POWER
To ensure sufficient convection, we
recommend the following minimum
spacing be used between modules:
In
pu
5 tA
C
N 100-2
4
L 0V /20
www.interface.phoenixcontact.com
-2
00 97
S-1 38
B
EN
2
A 6-
0-
30 djust L 00 1
61 1-
.0-5 LS RIA EN 5008
6.0 O VA DUSTOL T EN
IN NTRMEN
V PR COUIP
AP EQKA
13 ns
U
43
ti o s
14 D
u c in
s tr m a
TE
DC LIS
O in
K n to
ti o g
+ O
utp ll a c ti n
s ta e
+ ut in o n n
DC e ad c
24 R fo re
V be
40
A
Figure 05
240 mm 122 mm
80 mm
145 mm
QUINT POWER
DC OK
130 mm
290 mm
Figure 06
Mounting:
Place the module with the DIN rail guideway on the
Mounting
top edge of the DIN rail and then snap it downwards.
Removal:
Release the snap-on catch using a screwdriver and
then detach the module from the bottom edge of the
DIN rail.
Figure 08
L L L L1
N PEN N L2
PE L3
L N PE L N PE L N PE
+ + + L N PE
QUINT QUINT QUINT +
QUINT
Figure 09
Connecting Cable:
To maintain UL approvals, use copper cables, which
Q
are designed for operating temperatures > +75C.
30 - 56 V DC on the potentiometer 5.
U
14
It should be ensured that all output cables are the DC
O
K LIS
TE
D
Figure 12
Active Signal Output (Figure 13)
The 24 V DC signal is between the "DC OK" and "-"
connection terminal blocks and can be loaded with
20 mA maximum. This signal output indicates that the
output voltage has fallen more than 10% below the set
value when "active high" changes to "low".
The DC OK signal is isolated from the power output.
This ensures that a separate supply does not enter Output 48 V DC
from devices connected in parallel.
DC OK
DC OK
24 V DC
20 mA
Figure 13
DC OK
DC OK
This signal combination saves on wiring costs and 13 14 ++ 13 14 ++
logic inputs.
24 V DC
DC OK
DC OK LED 20 mA
7. Function
UOUT 960 W 1060 W
7.1. Output Characteristic Curve
[V]
With heavy loads, the working point demonstrates
the U/I characteristic curve shown in Figure 13. UN48
The output current is limited to 25 A.
The secondary voltage is reduced until the short < 60 C < 40 C
circuit on the secondary side is removed.
The U/I characteristic curve ensures that both heavy
capacitive loads and devices with DC/DC converters
can be supplied by QUINT POWER in the input circuit IOUT
without any problems. 20 22.5
[A]
Connected fuses are reliably tripped. The selectivity IN IBOOST
in your system configuration is ensured at all times.
20
0
0 20 40 60
Figure 16
http://www.phoenixcontact.com
connection is recommended if the power supply unit
does not cover the current consumption of the most
powerful load. Otherwise, the loads should be divided
over independent individual devices.
A maximum of five devices can be connected in
parallel.
TNR:102314-01-gb
01/15/05
PHOENIX CONTACT