CB SF1&SFset PDF
CB SF1&SFset PDF
CB SF1&SFset PDF
SF circuit breakers
up to 40.5 kV
fixed and withdrawable versions
Catalogue
2008
SF circuit breakers
One range of comprehensive and proven SF1 circuit breakers fixed version from 12 kV to 36 kV
three-pole circuit breaker units for indoor
installation using SF6 technology.
Both compact and dependable, it is ideally
suited to the most demanding applications.
This circuit breaker range meets
PE56503
IEC standard 62271-100.
General presentation 2
Panorama 4
1
General presentation SF circuit breakers
The advantages of proven technology
Less maintenance
Throughout the devices service life, which in normal operating conditions may be
at least 30 years, the only maintenance required is on the mechanical operating
mechanism, once every 10 years or every 10,000 operations.
Although no maintenance is performed on poles, a diagnosis is possible:
b contact wear can be checked by external pole measurement
b SF6 pressure can be continually monitored by a pressure switch.
Environmentally-friendly
Schneider Electric devices have been designed to ensure protection of
the environment:
b the materials used, both insulating and conductive, are identified and easy
to separate and recycle
b the SF6 gas is under control from production through to the circuit breakers end
of life. In particular it can be recovered at the end of the circuit breakers life and
re-used after treatment in line with the new European directive
b an end of life manual for the product details procedures for dismantling and
recycling components.
Quality Assurance
During production, each circuit breaker undergoes systematic routine tests
in order to check quality and conformity:
b pole sealing check
b checking the correct mechanical operation of the device,
b plus its associated locking mechanisms
b checking simultaneous closing of contacts
b checking power frequency insulation level
b checking main circuit resistance
b checking auxiliary circuit insulation
b checking auxiliary circuit electrical resistance
b checking switching speeds
b checking the switching cycle
b measuring the switching times.
The results are recorded on the test certificate for each device
which is initialed by the quality control department.
DE55745
DE55746
Certification
The quality system for the design and production of SF range circuit breakers is
certified in conformity with ISO 9001: 2000 quality assurance standard requirements.
The environmental management system adopted by Schneider Electric production
sites for the production of SF range circuit breakers has been assessed and judged
to be in conformity with requirements in standard ISO 14001.
2
General presentation SF circuit breakers
Breaking principle
DE51238
c
b
d
3
Panorama SF circuit breakers
Circuit breakers
4
Panorama SF circuit breakers (cont.)
I1 = 165A RMS
I2 = 166A RMS
I3 = 167A RMS
Separate catalogue
40 kA from 25 to 40 kA 31.5 kA
5
6
SF circuit breakers SF1 and SFset circuit breakers
fixed version
General presentation 2
Panorama 4
Presentation 9
General characteristics 10
Description of functions 12
RI stored energy operating mechanism 12
Wiring diagram 12
Opening circuit 13
Remote control 14
Indication and locking/interlocking 15
Protection, monitoring and control 16
VIP300 protection unit 16
Trip curves for VIP300P and VIP300LL 17
Current sensors and test unit for VIP300 18
Dimensions 19
Order form 22
SF2 circuit breakers fixed version 25
SF F400 circuit breakers withdrawable version 35
7
8
SF1 and SFset Presentation
circuit breakers
fixed version
kA
25
20 VIP300LL
16
0 17,5 24 kV
SFset circuit breakers with a B1 side operating mechanism
Depending on the model, the unit provides protection against phase over-currents
and earthing faults.
VIP protection units are associated with functional current sensors.
Two interchangeable sensors, CSa and CSb, are sufficient to cover all requirements
from 10 to 1250 A.
SFset is delivered equipped and cabled with its protection chain, this simplifies panel
builders installation work.
DE57401
SF1
Mitop
CS VIP
Applications
SF circuit breakers are 3-pole MV circuit breakers for indoor installation.
They are mainly used for switching and protection of networks from 12 to 36 kV
in primary and secondary power distribution.
Because the SFset protection chain is autonomous in terms of power, this circuit
breaker is particularly suited to certain dispersed installations on the network.
The autocompression breaking technique used in these circuit breakers means that
making or breaking all types of compacitive or inductive currents can be achieved
without dangerous overvoltages for the switchgear connected to the network.
The SF circuit breaker is therefore well suited to operating capacitor banks.
9
SF1 and SFset General characteristics
circuit breakers
fixed version
PE56503
Rated voltage Ur kV 50/60 Hz 12 17.5
Insulation voltage
- power frequency withstand Ud kV 50 Hz 1min 28 38
- lightning impulse withstand Up kV peak 75 95
Rated current Ir A 400 b
630 b b b b
1250 b b b
Short circuit current Isc kA 25 12.5 20 25
Short time withstand current Ik/tk kA/3 s 25 12.5 20 25
Short-circuit making current Ip kA peak 50 Hz 62.5 31.3 50 62.5
60 Hz 65 32.5 52 65
Rated switching sequence O-3 min-CO-3 min-CO b b
O-0.3 s-CO-3 min-CO b b
O-0.3 s-CO-15 s-CO b b
Phase to phase mm 220 b b b
250 b b b b
280
350
380
Operating mechanism A1 lateral (*) b b b
B1 lateral (*) b b b
C1 frontal (*) b b b
For SM6 switchgear b b
Operating times Opening (ms) < 50
Breaking (ms) < 60
Closing (ms) < 65
Service temperature T C 25 to +40
Mechanical endurance Class M2
Number of switching operations 10,000
Electrical endurance Class E2
Capacitive current breaking capacity Class C2
b Available
Not available
(*) See chapter Dimensions.
Specific applications
Switching and protection of capacitor banks
SF range circuit breakers are particularly well suited to switching and protection
of capacitor banks; they are classed C2 according to standard IEC 62271-100.
Tests carried out according to the standard for breaking at 400 A with making
and breaking cycles in case of a capacitor bank with a making current of 20 kA.
Additional tests have been carried out: please consult us.
10
SF1 and SFset General characteristics (cont.)
circuit breakers
fixed version
SFset
PE56504
24 36 12 17.5 24
50 70 28 38 50
125 170 75 95 125
b b b b b b
b b b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b
12.5 16 20 25 12.5 16 20 25 25 12.5 20 25 12.5 16 20 25
12.5 16 20 25 12.5 16 20 25 25 12.5 20 25 12.5 16 20 25
31.3 40 50 62.5 31.3 40 50 62.5 62.5 31.3 50 62.5 31.3 40 50 62.5
32.5 41.6 52 65 32.5 41.6 52 65 65 32.5 52 65 32.5 41.6 52 65
b b b b b
b b b b b
b b b b b
b b b
b b b b b b b b b b b b
b b b b b b b b
b b b
b b b b
b b b b b b b b b b b b b b
b b b b b b b b b b b b b b
b b b b b b b b b b b b b b
b b b b b b b b b b b b
< 50 < 50
< 60 < 60
< 65 < 65
25 to +40 25 to +40
M2 M2
10,000 10,000
E2 E2
C2 C2
11
SF1 and SFset Description of functions
circuit breakers RI stored energy operating mechanism
fixed version Wiring diagram
operating mechanism
This gives the device an opening and closing speed that is independent of the
operator whether the order is electrical or manual.
The electrical control mechanism carries out reclosing cycles and is automatically
recharged by a geared motor each time after closing.
It consists of:
b the stored energy operating mechanism which stores in springs the energy
required to open and close the device
b a manual lever-operated spring arming device
b a geared electrical arming device which automatically re-arms the control
mechanism as soon as the circuit breaker is closed (optional)
b manual order devices by push buttons on the front panel of the device
b an electrical remote closing device containing a release with an antipumping relay
b an electrical opening order device comprising one or several release units which
can be of the following type:
v shunt opening
v undervoltage
v Mitop, a low consumption release, used only with the Sepam 100 LA
protection relay.
b an operation counter
b an open/closed position indicator device with a mechanical indicator
b a device for indicating charged operating mechanism status by mechanical
indicator and electrical contact (optional)
b a module of 14 auxiliary contacts whose availability varies according
to the diagram used.
Close CB
Open CB
M3
YF + Mitop
anti-pumping YO1 YO2 YM
Remote control
12
SF1 and SFset Description of functions
circuit breakers Opening circuit
fixed version
Composition
DE57612EN
This release unit causes the systematic opening of the circuit breaker when its
supply voltage drops below a value less than 35% of the rated voltage, even if this
drop is slow and gradual. It can open the circuit breaker between 35% and 70% of
its rated voltage. If the release unit is not supplied power, manual or electrical closing
of the circuit breaker is impossible. Closing of the circuit breaker is compulsory when
Shunt opening release (1) the supply voltage of the release unit reaches 85% of its rated voltage.
Characteristics
DE58093
13
SF1 and SFset Description of functions
circuit breakers Remote control
fixed version
Function
DE57604
Remote control enables the remote opening and closing of the circuit breaker.
Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.
Operation counter
The operation counter is visible on the front panel.
Operation counter (6)
It displays the number of switching cycles (CO) that the device has carried out.
14
SF1 and SFset Description of functions
circuit breakers Indication and locking/interlocking
fixed version
The number of contacts available depends on the options chosen on the operating
mechanism.
In the basic configuration, the circuit breakers operating mechanism comprises
a total of:
b 5 normally closed contacts (NC)
b 5 normally open contacts (NO)
b 1 changeover contact (CHG).
The usage procedure for auxiliary contacts is given in the following table:
Options
NC contact NO contact
Shunt opening release (each one) 0 1
Undervoltage release 0 0
Low energy release (Mitop) 0 0
In order to know the final number of available contacts, you must deduct the total
number of contacts included in the circuit breaker (5 NC + 5 NO + 1 CHG),
the number of contacts used given in the table above.
E.g.: a circuit breaker equipped with a remote control and a shunt trip unit has
Operating mechanism the following available contacts:
5 NC + 4 NO + 1 CHG.
With a undervoltage release instead of the shunt trip, this circuit breaker would have
DE58098
Shunt opening release 5NC + 3NO + 1CHG 5NC + 4NO+ 1CHG 5NC + 4NO + 1CHG
YO2
Undervoltage release 5NC + 4NO + 1CHG 5NC + 5NO + 1CHG
YM
Mitop 5NC + 4NO + 1CHG 5NC + 5NO + 1CHG
15
SF1 and SFset Protection, monitoring and control
circuit breakers VIP300 protection unit
fixed version
protection system
The SFset circuit breaker comprises an SF1 into which is integrated a protection system
comprising:
b a set of current sensors installed on the lower current terminals of the pole units.
Two interchangeable sensors, CSa and CSb, sufficient to cover all requirements
from 10 A to 1250 A.
b a VIP type protection relay mounted on the control unit.
b a Mitop low consumption, release unit installed on the switching device.
The unit is fully independent and functions without an auxiliary power supply.
Operating principle
The protection system is supplied power by sensors which supply:
b the current information, processed by the protection unit
b the electrical power required for the whole protection system to operate ;
VIP unit and Mitop release.
SFset with a VIP protection unit installed on the front panel All settings are visible and accessible from the front of the device.
DE57403
Mitop
VIP300LL protection unit
VIP300
t>
t >>
I
1,2 Is 10 Is I >>
Simplified connection arrangement Phase and earthing protection curve
16
SF1 and SFset Protection, monitoring and control
circuit breakers Trip curves
fixed version VIP300P and VIP300LL
Trip curves
DE57404
t> t>
t >> t >>
t (s) t (s)
100 100
10 10
6 6
4
3 4
2 3
1.5 2
1 1 1 1.5
1
0.6
0.4 0.6
0.3 0.4
0.2 0.3
0.15 0.2
0.1 0.1 0.1 0.15
0.07 0.1
0.05 0.07
0.05
I/Is I/Is
0.01 0.01
1 10 100 1 1.2 Is 10 100
RI curve SI curve
DE57406
t (s) t (s)
1000 1000
100 100
10 10
6
4
3 6
1 2 1 4
1.5 3
1 2
0.6 1.5
0.4 1
0.3 0.6
0.1 0.2 0.1 0.4
0.15 0.3
0.1 0.2
0.07 0.15
0.05 0.1
I/Is 0.07 I/Is
0.01 0.01 0.05
1 1.2 Is 10 100 1 1.2 Is 10 100
VI curve EI curve
17
SF1 and SFset Protection, monitoring and control
circuit breakers Current sensors and test unit for VIP300
fixed version
In order to achieve the specified performance levels, the VIP300 protection unit
must be used with the specified sensors. The combination of the unit/sensor
is essential in order to comply with characteristics and in particular with:
b operation throughout the whole range
b response time
b accuracy
b short circuit thermal withstand.
Two interchangeable sensors, CSa and CSb, suffice to cover all requirements
from 10 A to 1250 A.
18
SF1 and SFset Dimensions
circuit breakers
fixed version
E E P/D P/D
350 350
L/W 270
P/D P/D E E
350 350
270 L/W
345 345
L/W
19
SF1 and SFset Dimensions (cont.)
circuit breakers
fixed version
E E P/D P/D
H (1)
L/W
P/D P/D E E
H (1)
L/W
E E P/D P/D
H (1)
L/W
20
SF1 and SFset Dimensions (cont.)
circuit breakers
fixed version
Connection
Top
Ir y 630 A
SF1, SFset (A) SF1, SFset (B)
20 24 20
DE57413-A
40
DE57414
DE57413-B
M8 kA M8
25
20 (B)
56 56
16 20
17 17
8 13 +0.2
0 12,5 (A) 8 +0.2
13 0
17,5 24 36 kV
Ir = 1250 A
SF1, SFset (B)
20 40
DE57413-B
DE57415
M8 kA
25
20
56
20 16 (B)
17 +0.2 12,5
8 13 0
17,5 24 36 kV
Bottom
SF1, insulation y 125 kV impulse SF1, insulation y 170 kV impulse SFset
2 M8 25 0,5 2 M8
DE57416
DE57417
DE57418
2 10,5 52
20
10
18 40 40
20 20
60
75
21
SF1 and SFset Order form
circuit breakers SF1 lateral/frontal fixed up to 36 kV
fixed version
Only one of the boxes (ticked X or filled by Basic fixed circuit breaker Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Impulse voltage Up (kVbil)
Frequency 50 Hz 60 Hz
Remote control
Electrical motor M 2432 Vdc 110127 Vdc/ac
4860 Vdc/ac 220250 Vdc/ac
Shunt closing release YF
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
22
SF1 and SFset Order form
circuit breakers SFset lateral/frontal fixed up to 24 kV
fixed version
Only one of the boxes (ticked X or filled by Basic fixed circuit breaker Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Impulse voltage Up (kVbil)
Frequency 50 Hz 60 Hz
Remote control
Electrical motor M 2432 Vdc 110127 Vdc/ac
4860 Vdc/ac 220250 Vdc/ac
Shunt closing release YF
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
23
24
SF circuit breakers SF2 circuit breakers
fixed version
General presentation 2
Panorama 4
SF1 and SFset circuit breakers fixed version 7
Presentation 26
General characteristics 27
Description of functions 28
GMH stored energy operating mechanism 28
Wiring diagram 28
Opening circuit 29
Remote control 30
Indication and locking/interlocking 31
Dimensions 32
Order form 33
SF F400 circuit breakers withdrawable version 35
25
SF2 circuit breakers Presentation
fixed version
Applications
SF circuit breakers are 3-pole MV circuit breakers for indoor installation.
They are mainly used for switching and protection of networks from 24 to 40.5 kV
in primary and secondary power distribution.
The autocompression breaking technique used in these circuit breakers means that
making or breaking all types of compacitive or inductive currents can be achieved
without dangerous overvoltages for the switchgear connected to the network.
The SF circuit breaker is therefore well suited to operating capacitor banks.
26
SF2 circuit breakers General characteristics
fixed version
b Available
Not available.
Specific applications
Switching and protection of capacitor banks
SF range circuit breakers are particularly well suited to switching and protection
of capacitor banks; they are classed C2 according to standard IEC 62271-100.
Tests carried out according to the standard for breaking at 400 A with making
and breaking cycles in case of a capacitor bank with a making current of 20 kA.
Additional tests have been carried out: please consult us.
27
SF2 circuit breakers Description of functions
fixed version GMH stored energy operating mechanism
Wiring diagram
This gives the device an opening and closing speed that is independent of the
operator whether the order is electrical or manual.
The electrical control mechanism carries out reclosing cycles and is automatically
recharged by a geared motor each time after closing.
It consists of:
b the stored energy operating mechanism which stores in springs the energy
required to open and close the device
b a manual lever arming device for the springs
b an electrical arming device with a motor to automatically rearm the control
mechanism as soon as the circuit breaker is closed (optional)
b manual push-button controls on the front face of the circuit breaker (red and black)
b an electrical remote-closing device comprising a release and an anti-pumping relay.
b an electrical opening device comprising one or several releases of the following
type:
v shunt opening
v undervoltage
v Mitop, low energy release only used Sepam 100 LA protection relays
b an operation counter
b an open/closed position indicator with a mechanical indicator (black and white)
b an armed control mechanism status indicator with a mechanical indicator
and an electrical contact (optional)
b a block of 14 auxiliary contacts, available according to the wiring layout used
b a pressure switch contact activated by a drop in gas pressure (optional: single
or double threshold pressure switch)
Close CB
Open CB
M3
YF + Mitop
anti-pumping YO1 YO2 YM
Motor Shunt closing Control Shunt Under- Low energy Changeover NO NC Pressostat
release mechanism opening voltage release contact contacts contacts
+ anti-pumping armed release release (Mitop)
system indicator contact
Remote control
28
SF2 circuit breakers Description of functions
fixed version Opening circuit
Composition
DE57421EN
Characteristics
Power supply See Order form page
Threshold Opening 0.35 to 0.7 Ur
Closing 0.85 Ur
Consumption Triggering V AC 400 VA
V DC 100 W
Undervoltage release (2) Latched V AC 100 VA
V DC 10 W
DE57391
29
SF2 circuit breakers Description of functions
fixed version Remote control
Function
DE57422
Remote control enables the remote opening and closing of the circuit breaker.
Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.
Consumption V AC 380 VA
V DC 380 W
Characteristics
Power supply See Order form page
Threshold V AC 0.85 to 1.1 Ur
V DC 0.85 to 1.1 Ur
Consumption V AC 160 VA
Shunt closing release (5)
V DC 50 W
The shunt closing release is combined with an anti-pumping relay that enables priority
DE57393
to be given to opening in the case of a permanent closing order. This thus avoids
the device being caught in an uncontrolled opening-closing cycle.
Operation counter
The operation counter is visible on the front panel.
It displays the number of switching cycles (CO) that the device has carried out.
30
SF2 circuit breakers Description of functions
fixed version Indication and locking/interlocking
The number of contacts available depends on the options chosen on the operating
mechanism.
In the basic configuration, the circuit breakers operating mechanism comprises
a total of:
b 5 normally closed contacts (NC)
b 5 normally open contacts (NO)
b 1 changeover contact (CHG).
The usage procedure for auxiliary contacts is given in the following table:
Options
NC contact NO contact
Shunt opening release (each one) 0 1
Undervoltage release 0 0
Low energy release (Mitop) 0 0
In order to know the final number of available contacts, you must deduct the total
number of contacts included in the circuit breaker (5 NC + 5 NO + 1 CHG),
the number of contacts used given in the table above.
Operating mechanism E.g.: a circuit breaker equipped with a remote control and a shunt trip unit has
the following available contacts:
5 NC + 4 NO + 1 CHG.
DE57394
With a undervoltage release instead of the shunt trip, this circuit breaker would have
the following available contacts:
5 NC + 5 NO + 1 CHG.
Shunt opening release combination
Auxiliary contacts (7) 1st release Shunt opening Undervoltage release Mitop
release YO1 YM
2nd release
DE57395
Without 5NC + 4NO + 1CHG 5NC + 5NO+ 1CHG 5NC + 5NO + 1CHG
Shunt opening release 5NC + 3NO + 1CHG 5NC + 4NO+ 1CHG 5NC + 4NO + 1CHG
YO2
Undervoltage release 5NC + 4NO + 1CHG 5NC + 5NO + 1CHG
YM
Mitop 5NC + 4NO + 1CHG 5NC + 5NO + 1CHG
Keylocking kit (8)
31
SF2 circuit breakers Dimensions
fixed version
E E 190
372
L/W
E E
190
630
L/W 644
Connection
630, 1250 A (24-36 kV) 2500, 3150 A (24-36 kV) 2000, 2500 A (40.5 kV)
35 78 2 M12
DE57426
DE57419
32,5
10 70 30
100
90 30 20 60
35
8 13 49,5
18,5 90
63 70
26
26 47 10 117
32
SF2 circuit breakers Order form
fixed version SF2 fixed up to 40.5 kV
Only one of the boxes (ticked X or filled by Basic fixed circuit breaker Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Impulse voltage Up (kVbil)
Frequency 50 Hz 60 Hz
Colour for push buttons and indicators
Push buttons open/close: Red/black
Indicator open/close: Black/white
Operating mechanism charged/discharged: White/yellow
Remote control
Electrical motor M 2432 Vdc 110127 Vdc/ac
4860 Vdc/ac 220250 Vdc/ac
Shunt closing release YF
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
32 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
33
34
SF circuit breakers SF F400 circuit breakers
withdrawable version
General presentation 2
Panorama 4
SF1 and SFset circuit breakers fixed version 7
SF2 circuit breakers fixed version 25
Presentation 36
General characteristics 37
Description of functions 38
Racking-in 38
MV and LV connection 40
GMH stored energy operating mechanism 41
Wiring diagram 41
Opening circuit 42
Remote control 43
Indication and locking/interlocking 44
Safety functions 45
Dimensions 46
Order form 48
35
SF F400 circuit breakers Presentation
withdrawable version
Device description
PE56502
Applications
SF circuit breakers are 3-pole MV circuit breakers for indoor installation.
They are mainly used for switching and protection of networks from 24 to 40.5 kV
in primary and secondary power distribution.
The autocompression breaking technique used in these circuit breakers means that
making or breaking all types of compacitive or inductive currents can be achieved
without dangerous overvoltages for the switchgear connected to the network.
The SF circuit breaker is therefore well suited to operating capacitor banks.
36
SF F400 circuit breakers General characteristics
withdrawable version
b Available
Not available.
Specific applications
Switching and protection of capacitor banks
SF range circuit breakers are particularly well suited to switching and protection
of capacitor banks; they are classed C2 according to standard IEC 62271-100.
Tests carried out according to the standard for breaking at 400 A with making
and breaking cycles in case of a capacitor bank with a making current of 20 kA.
Additional tests have been carried out: please consult us.
37
SF F400 circuit breakers Description of functions
withdrawable version Racking-in
Overall composition
DE57396
Protective shutters
38
SF F400 circuit breakers Description of functions
withdrawable version Racking-in (cont.)
Locking/interlocking functions
Possibilities for padlocking
PE50201
A blocking system for the circuit breaker opening order, when it is closed
PE50204
This device can also be used as an additional way of prohibiting racking-in and out.
A transparent shutter blocks access to the opening and closing pushbutton.
The device allows independent locking of the opening or closing button.
It is often associated with an electrical motor (M). Locking is achieved by
a padlock (not supplied) mounted on the shutter protecting the mechanical
opening pushbutton.
This keylocking system prohibits disconnection of the moving part. It may be used
for a circuit breaker or for a racking base.
Optional accessories
b a self-adhesive front plate shows circuit breaker racking-in and racking-out
operations. It is systematically delivered when the circuit breaker is ordered
with the cassette or can be ordered separately.
b 4 racked-in/racked-out position contacts.
b 1 position contact for the cassette locked in the racked-in/racked-out position.
b a keylocking system (Ronis or Profalux) for the circuit breaker in the racked-in
or racked-out position.
39
SF F400 circuit breakers Description of functions
withdrawable version MV and LV connection
MV Connection
The customer connection is easily carried out from the back of M1 and M2 cassettes
using the upper and lower bushings.
PE50194
PE50195
MV connection with M1 cassette MV connection with M2 cassette
LV connection
With the withdrawable circuit breaker, LV wiring uses an LV connector with:
b the moving part (male Harting socket) at the end of a flexible cable, entirely
connected to the control mechanism terminal via a bellow
b the fixed part (female Harting socket) compatible with the male part mounted
on the top inside part of the cassette.
Interlocking function
In conformity with standard IEC 62271-200, an interlocking function prohibits:
b racking-in when the LV connector is not connected
b disconnection of the LV connector if the circuit breaker is in the racked-in position.
PE50197
LV plug connection
40
SF F400 circuit breakers Description of functions
withdrawable version GMH stored energy operating mechanism
Wiring diagram
This gives the device an opening and closing speed that is independent of the
operator whether the order is electrical or manual.
The electrical control mechanism carries out reclosing cycles and is automatically
recharged by a geared motor each time after closing.
It consists of:
b the stored energy operating mechanism which stores in springs the energy
required to open and close the device
b a manual lever arming device for the springs
b an electrical arming device with a motor to automatically rearm the control
mechanism as soon as the circuit breaker is closed (optional)
b manual push-button controls on the front face of the circuit breaker (red and black)
b an electrical remote-closing device comprising a release and an anti-pumping relay.
b an electrical opening device comprising one or several releases of the following
type:
v shunt opening
v undervoltage
v Mitop, low energy release only used Sepam 100 LA protection relays
b an operation counter
b an open/closed position indicator with a mechanical indicator (black and white)
b an armed control mechanism status indicator with a mechanical indicator
and an electrical contact (optional)
b a block of 14 auxiliary contacts, available according to the wiring layout used
b a pressure switch contact activated by a drop in gas pressure (optional: single
or double threshold pressure switch)
Close CB
Open CB
M3
YF + Mitop
anti-pumping YO1 YO2 YM
Motor Shunt closing Control Shunt Under- Low energy Changeover NO NC Pressostat
release mechanism opening voltage release contact contacts contacts
+ anti-pumping armed release release (Mitop)
system indicator contact
Remote control
41
SF F400 circuit breakers Description of functions
withdrawable version Opening circuit
Composition
DE57421EN
Characteristics
Power supply See Order form page
Threshold Opening 0.35 to 0.7 Ur
Closing 0.85 Ur
Consumption Triggering V AC 400 VA
V DC 100 W
Undervoltage release (2) Latched V AC 100 VA
V DC 10 W
DE57391
42
SF F400 circuit breakers Description of functions
withdrawable version Remote control
Function
DE57422
Remote control enables the remote opening and closing of the circuit breaker.
Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.
Consumption V AC 380 VA
V DC 380 W
Characteristics
Power supply See Order form page
Threshold V AC 0.85 to 1.1 Ur
V DC 0.85 to 1.1 Ur
Consumption V AC 160 VA
Shunt closing release (5)
V DC 50 W
The shunt closing release is combined with an anti-pumping relay that enables priority
DE57393
to be given to opening in the case of a permanent closing order. This thus avoids
the device being caught in an uncontrolled opening-closing cycle.
Operation counter
The operation counter is visible on the front panel.
It displays the number of switching cycles (CO) that the device has carried out.
43
SF F400 circuit breakers Description of functions
withdrawable version Indication and locking/interlocking
The number of contacts available depends on the options chosen on the operating
mechanism.
In the basic configuration, the circuit breakers operating mechanism comprises
a total of:
b 5 normally closed contacts (NC)
b 5 normally open contacts (NO)
b 1 changeover contact (CHG).
The usage procedure for auxiliary contacts is given in the following table:
Options
NC contact NO contact
Shunt opening release (each one) 0 1
Undervoltage release 0 0
Low energy release (Mitop) 0 0
In order to know the final number of available contacts, you must deduct the total
number of contacts included in the circuit breaker (5 NC + 5 NO + 1 CHG),
the number of contacts used given in the table above.
Operating mechanism E.g.: a circuit breaker equipped with a remote control and a shunt trip unit has
the following available contacts:
5 NC + 4 NO + 1 CHG.
DE57394
With a undervoltage release instead of the shunt trip, this circuit breaker would have
the following available contacts:
5 NC + 5 NO + 1 CHG.
Shunt opening release combination
Auxiliary contacts (7) 1st release Shunt opening Undervoltage release Mitop
release YO1 YM
2nd release
DE57395
44
SF F400 circuit breakers Description of functions
withdrawable version Safety functions
This table describes the safety functions available on the SF circuit breaker
withdrawable version.
How to use the table
Each of the boxes describes the functional status of each circuit breaker position
and the associated parts:
Possible status
Possible status, impossible operation
Impossible status
Extraction Racking-out
Removed Disconnected Test position Service
1 - Cassette Fool-proof
protection (1)
No opening shutters
(1) This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cassette..
(2) Option.
(3) Interlocking device to be fitted to the cubicle door.
(4) Because the door is closed.
45
SF F400 circuit breakers Dimensions
withdrawable version
DE57431
DE57432
1250 A 2500/3150 A
Dimensions (mm) A 738 752
B 540 533
C 2030 2030
D 36 40
Weight (kg) 750 850
DE57433
SF F400/M2
Dimensions and weights
DE57442
DE57441
1250 A 2500/3150 A
Dimensions (mm) A 1278 1285
C 2030 2030
D 36 40
Weight (kg) 750 850
DE57433
46
SF F400 circuit breakers Dimensions (cont.)
withdrawable version
Connection
SF F400/M1
1250 A 2500/3150 A
DE57437
DE57438
SF F400/M2
1250 A 2500/3150 A
DE57443
DE57444
47
SF F400 circuit breakers Order form
withdrawable version SF F400 withdrawable up to 40.5 kV
Only one of the boxes (ticked X or filled by Basic withdrawable circuit breaker Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Impulse voltage Up (kVbil)
Frequency 50 Hz 60 Hz
Colour for push buttons and indicators
Push buttons open/close: Red/black
Indicator open/close: Black/white
Operating mechanism charged/discharged: White/yellow
Remote control
Electrical motor M 2432 Vdc 110127 Vdc/ac
4860 Vdc/ac 220250 Vdc/ac
Shunt closing release YF
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
M1/M2 cassettes
MC cassette type M1 M2
Rated short-circuit current Isc y 40 kA
Rated current Ir 1250 A 2500/3150 A
48
ART.95993 Schneider Electric Industries SAS - All rights reserved
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
89, boulevard Franklin Roosevelt of the information given in this publication.
F-92506 Rueil-Malmaison Cedex
Tel: +33 (0)1 41 29 85 00 This document has been printed
www.schneider-electric.com on ecological paper
AMTED304010EN 01-2008