Chapter 4 - Synchronuous Generator (Part A)
Chapter 4 - Synchronuous Generator (Part A)
Chapter 4
Synchronous Generators (Part A)
3
Ir. Dr. Dahaman Ishak
Difference Between AC and DC machines
Armature windings are located on the stator,
while their field windings are located on the
rotor.
The rotating magnetic field from the rotor field
winding of an ac machine induces a three-
phase set of ac voltages in the stator
windings
Synchronous generator
5
Ir. Dr. Dahaman Ishak
Synchronous generator- brushless excitation
system
6
Ir. Dr. Dahaman Ishak
3-phase synchronous machine
7
Type of rotor for Synchronous
machine
Cylindrical Rotor or Nonsalient Rotor
8
Ir. Dr. Dahaman Ishak
Type of rotor for Synchronous
machine
Salient Rotor
six-pole rotor
9
Ir. Dr. Dahaman Ishak
Speed of rotation in
synchronous generator
Synchronous generator is by definition synchronous,
meaning that the electrical frequency produced is locked
in or synchronized with the mechanical rate of rotation of
the generator :-
For example, in order to generate 50 Hz
supply in 2 poles machine, the rotor
nP 120 f should turn at 3000 rev per min (rpm).
f n
120 p 2 poles 3000 rpm
4 poles 1500 rpm
where, 6 poles 1000 rpm
f = electrical frequency in Hz 8 poles 750 rpm
n = mechanical speed (rpm) 10 poles 600 rpm
P = number of poles
10
Ir. Dr. Dahaman Ishak
No-load saturation curve of the
synchronous generator
E0 is proportional to IF
12
Ir. Dr. Dahaman Ishak
Equivalent circuit of an ac generator
Vф
E0 V X S I A RA I A
V E0 jX S I A RA I A
Vф Eo is the induced phase voltage
Vф is the phase terminal voltage
XS is the synchronous reactance
Per-phase equivalent circuit
RA is the phase winding resistance
Ir. Dr. Dahaman Ishak 14
Phasor diagram of synchronous
generator supplying a load
E A o V 0 RA I A jX S I A
Power
from
Primemover
i.e. wind turbine,
Steam turbine,
Diesel engine, etc
17
Ir. Dr. Dahaman Ishak
Power and Torque in Synchronous
Generator
If the armature resistance RA is ignored (since Xs >>RA),
then a very useful equation can be derived to approximate
the output power of the generator
torque angle δ
EA sin X S I A cos
VФ
E A sin
I A cos
XS
3V E A sin
Pout ,3 3V I A cos
XS
EA
IA
RA jX S
EA
IA
RA2 X S2
EA
Z S RA2 X S2
IA
X S RA
E A E ,OC
XS
IA IA
Ir. Dr. Dahaman Ishak 24
Determination of synchronous
reactance
Approximate method to determine the synchronous
reactance XS at a given field current IF :-
a) Obtain the internal generated voltage EA from
OCC at that field current
b) Obtain the short-circuit current flow IA,SC from
SCC at that field current
2
E E
Z S RA2 X S2 A X S A RA2 1.02
IA IA
Ir. Dr. Dahaman Ishak 26
Ir. Dr. Dahaman Ishak
27