Cycle Counter: C1Cm/C1Cf C1Sm/C1Sf
Cycle Counter: C1Cm/C1Cf C1Sm/C1Sf
Cycle Counter: C1Cm/C1Cf C1Sm/C1Sf
CYCLE COUNTER
MODEL C1CM/C1CF C1SM/C1SF
STAINLESS STEEL
COUNTER FOR MONITORING THE NUMBER OF PUMP CYCLES OF POWERTRAPS
Features
Enables monitoring of the number of pumping
cycles of GP series PowerTraps to help determine
the timing of maintenance, or estimate the volume
of pumped condensate.
1. Two different types are available to support various
system requirements.
2. The Counter Unit types (C1CM(-EX) / C1CF(-EX)) C1SM/C1SM-EX
include a built-in LCD display and LED that flashes C1SF/C1SF-EX
with each operation cycle to allow easy direct
observation.
3. The Terminal Box Types (C1SM(-EX) / C1SF(-EX))
combine with an external display to enable remote
observation or integration into a broader monitoring
system. C1CM/C1CM-EX
4. Can be equipped on currently installed GP series C1CF/C1CF-EX
PowerTraps.
5. OK for installation outdoors.
Specifications
Model C1CM C1CM-EX C1CF C1CF-EX C1SM C1SM-EX C1SF C1SF-EX
Type Counter Unit Terminal Box
GP10, GP10M, GP10L, GP10, GP10M, GP10L,
Installable PowerTrap Models GP14, GP14M, GP14L GP10F, GP21F GP14, GP14M, GP14L GP10F, GP21F
Intrinsically Intrinsically Intrinsically Intrinsically
Description Standard Standard Standard Standard
Safe 1) Safe 1) Safe 1) Safe 1)
Connection Screwed
Size ½”
Max Operating Pressure (barg) PMO 2) 21
Max Operating Temperature (°C) TMO 2) 220
Ambient Pressure 2) Atmospheric
Ambient Temperature 2) -10 to 55 °C -45 to 90 °C -20 to 80 °C -45 to 90 °C -20 to 80 °C
Applicable Fluids 3) Steam, Air, Nitrogen, Steam Condensate, Water
Max. Input Power (Pi): 1W
Max. Incoming Voltage (Ui): 28V
Special Built-in Lithium Battery (3.6V) Max. Incoming Current (Ii): 120 mA
Power Supply 4)
Battery Life: approx. 10 years Max. Internal Capacitance (Ci): 3nF
Max. Internal Inductance (Li): 0
Note: (Ui)V x (Ii)A ≤ 1 W (Pi)
5)
Display 8 digit LCD —
Terminal — Wiring Inlet: G ½
Protection Class IP65
Accessories Counter Resetter —
1)
ATEX/IECEx or cULus. See reverse side for details of applicable standards. 1 bar = 0.1 MPa
2)
PMO and TMO apply to the inserted portion only. Ambient Pressure/Temperature apply to the external portion.
3) 4) 5)
Do not use for toxic, flammable or otherwise hazardous fluids. Battery cannot be replaced. Counter display can be reset to zero by using the included resetter.
DESIGN CONDITIONS FOR INSERTED PORTION (NOT OPERATING CONDITIONS): Maximum Allowable Pressure (barg) PMA: 21
Maximum Allowable Temperature (°C) TMA: 260
To avoid abnormal operation, accidents or serious injury, DO NOT
CAUTION use this product outside of the specification range. Local regulations
may restrict the use of this product to below the conditions quoted.
No. Description Material DIN* ASTM/AISI*
q Sensor Body Stainless Steel SUS303 1.4305 AISI303
w Sensor Arm Stainless Steel SUS304 1.4301 AISI304
e Counter Body Polyetherimide PEI PEI —
r Cap Polysulfone PSF PSF —
t Display (LCD) — — —
y LED — — —
u Switch Unit Polyetherimide PEI PEI —
i Terminal Box Die Cast Aluminium ADC ADC —
o Hex Socket Head Bolt Stainless Steel SUS304 1.4301 AISI304
!0 Nameplate Polyester — —
!1 Magnet Booster Kit Stainless Steel SUS304 1.4301 AISI304
* Equivalent materials
Dimensions
¡C1CM(-EX) / C1CF(-EX) Screwed C1CM(-EX) / C1CF(-EX) Screwed* (mm)
R½
L4
L3 L2
C1CM/C1CM-EX C1CF/C1CF-EX
L1
Inserted Portion
L3 L2
G½
L1
Inserted Portion
C1SM/C1SM-EX C1SF/C1SF-EX