MOTOR PROTECTION RELAYS


2.1 Thermal Overload Relays
TH-N Series Thermal Overload Relays Will Make a Convenience and Safer
Systems.

TH-N12 TH-N20 TH-N12CX

A Selection of Relays for Optimum • Display and External Trip Mechanism


Motor Protection Characteristics TH-N12(KP)/TH-N18(KP)
The thermal relay line-up includes two-element units as well as Display External Trip
the phase failure protection type models (three-element relays), Screw driver
Display Display window
all with the same external dimensions. window
This array of protection characteristics allows you to choose
the units best suited to your motor protection needs. When the green of the display Display Display
lever can be seen, the device lever lever
has been reset.
Maintenance and Inspection Are Easy Display
An operation indicator makes maintenance and inspection easy. window When reset When tripped
Checks can be performed using manual operations.
When the green of the lever tuned Can be tripped manually by turning in the display lever.

1NO11NC Contacts in, the device has been tripped.

External Trip
Display
TH-N20(KP)~N600(KP) Driver window
97 95 Display
Display Display window Display
window lever

98 96

Reset Tripped
The NO and NC contacts can be
used independently as signals When the display window is When the display window is Can be tripped manually by
green the device has been white the device has been pushing in with a screwdriver
contacts. reset. tripped. and turning the display lever.

• Switching Between Automatic and Manual Reset


Rated Current Can Be Set Easily
The value of the rated current is displayed on a dial. TH-N12(KP)/TH-N18(KP)
Manual Reset Mode Automatic Reset Mode
Simply adjust the dial to the full-load current of the motor and Stopper
motor protection is assured.

Finger Protectors
Models with finger protectors that conform to DIN VDE 0106
Part 100 (TH-N CX) are also available.
Switchover Switchover
Various Accessories plate plate
Switching from manual to automatic : Break the stopper off and then, slide the
• Independent mount adaptor for TH-N12(CX). switchover plate to the right (to position “A”) to immobilize the reset bar.
Switching from automatic to manual : Slide the switchover plate to the left (to
: UN-HZ12(CX) position “H”).
• Reset release : UN-RR
• Trip indicating LED : UN-TL TH-N20(KP)~N600(KP)

Trip-Free Reset Bar


Choose between automatic and manual reset. Also features
tripfree reset bar mechanism.

Switching from manual to automatic : Flip the stopper on the end of


the reset bar down and then, after pushing it all the way in, rotate it
counterclockwise 90° (to position “A”).
Switching from automatic to manual : Rotate the reset bar 90°
clockwise (to position “H”) and the reset bar will pop out.

40
Series TH-N
2.1.1 Selection Guide of Thermal Overload Relays Table 2.1.1

Max. Fuse Rating (660Vac) Overload Relay


Motor Capacity [kW, (hp)]
IEC 269-1
Heater (Three phase 50/60Hz, based on four poles)
(A) Setting range Model
desig-
(A) (TH-)
aM gG gM nation AC220-240V AC380V AC400-440V AC500V

0.5 0.5 — 0.12A 0.1-0.16 — — — —


0.5 1 — 0.17A 0.14-0.22 — — — —
1 2 — 0.24A 0.2-0.32 0.03(1/24) 0.06(1/12) 0.06(1/12) 0.09(1/8)
1 2 — 0.35A 0.28-0.42 0.05(1/16) 0.09(1/8) 0.09(1/8) 0.12(1/6)
1 2 — 0.5A 0.4-0.6 0.06(1/12) 0.12(1.6) 0.12(1.6) 0.18(1/4)
2 4 — 0.7A 0.55-0.85 0.09(1/8) 0.18(1/4) 0.18(1/4) 0.25(1/3)

N12
2 4 — 0.9A 0.7-1.1 0.12(1/6) 0.25(1/3) 0.25(1/3) 0.37(1/2)
0.37(1/2)
2 4 — 1.3A 1.0-1.6 0.18(1/4) 0.37(1/2) 0.55(3/4)
0.55(3/4)
4 6 — 1.7A 1.4-2.0 0.25(1/3) 0.55(3/4) 0.75(1) 0.75(1)
4 6 — 2.1A 1.7-2.5 0.37(1/2) 0.75(1) — 1.1(1-1/2)

N20
6 10 — 2.5A 2.0-3.0 0.55(3/4) 1.1(1-1/2) 1.1(1-1/2) 1.5(2)
6 10 — 3.6A 2.8-4.4 0.75(1) 1.5(2) 1.5(2) 2.2(3)
N18

8 16 — 5A 4.0-6.0 1.1(1-1/2) 2.2(3) 2.2(3) 3(4)


12 20 — 6.6A 5.2-8.0 1.5(2) 3(4) 3,3.7(4.5) 3.7(5)
3.7(5) 3(4)
12 20 — 9A 7.0-11 2.2(3) 5.5(7-1/2)
4(5-1/2) 3.7(5)
16 25 32M35 11A 9.0-13 3(4) 5.5(7-1/2) 5.5(7-1/2) 7.5(10)
7.5(10)
N60

20 32 32M50 15A 12-18 3.7(5) 7.5(10) 9(12/5)


9(12.5)
1
25 40 32M63 19A 16-22 5.5(7-1/2) 11(15) 11(15) 11(15)
40 63 32M63 22A 18-26 5.5(7-1/2) 11(15) 11(15) 15(20)
N20TA

50 80 63M80 29A 24-34 7.5(10) 15(20) 15(20) 18.5(25)


N60

63 80 63M80 35A2 30-40 9(12.5) 18.5(25) 18.5(25) 22(30)


63 100 100M100 42A 34-50 11(15) 22(30) 22(30) 30(40)
N220

80 125 100M125 54A 43-65 15(20) 30(40) 30(40) 37(50)


N120

100 160 100M160 67A 54-80 18.5(25) 37(50) 37(50) 45(60)


N60TA

125 200 100M200 82A 65-100 22(30) 45(50) 45(60) 55(75)


— 200 100M200 95A3 85-105 30(40) 55(75) 55(75) —
— 250 200M250 105A 85-125 30(40) 55(75) 55(75) 75(100)
— 250 200M250 125A 100-150 37(50) 75(100) 75(100) 90(125)
N400

— 315 200M315 150A 120-180 45(60) 90(125) 90(125) 110(150)


N220

N120TA

— 400 — 180A 140-220 55(75) 110(150) 110(150) 132(175)


— 500 — 210A4 170-250 75(100) 132(180) 132(180) —
132(180) 132(180)
— 630 — 250A 200-300 75(100) 160(220)
160(220) 160(220)
N400

90(125) 220(300)
— 630 — 330A 260-400 200(270) 200(270)
110(150) 250(340)
N600

220(300) 220(300)
132(180)
— 800 — 500A 400-600 250(340) 250(340) 400(530)
160(220)
300(400) 300(400)
200(270)
— 1000 — 660A 520-800 400(530) 400(530) 500(670)
220(300)

Notes: 1. For starter size N20, N21 only. 2. For starter size N35 only. 3. For starter size N95 only. 4. For starter size N220 only.
5. Selection by mounting

W/o F/P TH-N12(KP) TH-N18(KP) TH-N20(KP) TH-N20TA(KP) TH-N60(KP) TH-N60TA(KP) TH-N120(KP) TH-N120TA(KP) TH-N220RH(KP) TH-N400RH(KP) —
Contactor (2) (1) (1) (1) (1) (1) (1)
mounting With F/P TH-N12CXKP TH-N18CXKP TH-N20CXKP TH-N20TAKPCX TH-N60CXKP — — — — — —
(3) (1) (1) (1)
W/o F/P TH-N12(KP) — TH-N20(KP) — TH-N60(KP) — TH-N120(KP) TH-N120TAHZ(KP) TH-N220HZ(KP) TH-N400HZ(KP) TH-N600(KP)
(4)
Independent (2) + UN-HZ12 + CT
mounting With F/P TH-N12CXKP — TH-N20CXHZKP — TH-N60CXKP — — — — — —
(4)
(3) + UN-HZ12CX
Notes: 1. Use “Connecting parts” when couple with contactor (see Table 2.1.6(3)). 2. W/o F/P:Without Finger Protection.
3.With F/P:With Finger Protection. 4. UN-HZ12(CX) is shipped separately from TH-N12(CX)(KP).
5. CT should be supplied by customer.

41
2.1.2 Selection Guide of the Current Transformers for TH-N600KP Table 2.1.2
Heater Designation(A) 250 330 500 660
Setting Range(A) 200⬃300 260⬃400 400⬃600 520⬃800
Current Transformer Ratio 400/5A 500/5A 750/5A 1,000/5A
Current Transformer Capacity At least 15VA
Current Transformer for
TH-N600KP CW-15L CW-15L CW-15L
Cable
400/5A 500/5A 750/5A —
wiring
Recommended MITSUBISHI Current 15VA 15VA 15VA
Transformer Model Number CW-15LM CW-15LM CW-15LM CW-40LM
Bus bar
400/5A 500/5A 750/5A 1000/5A
wiring
15VA 15VA 15VA 40VA
* Current transformer to be supplied by customer.
2.1.3 Technical Data Table 2.1.3
Three heater type TH- N12(CX)KP N18(CX)KP N20(CX)KP N20TA(CX)KP N60(CX)KP N60TAKP N120KP N120TAKP N220RHKP N400RHKP N600KP
Two heater type TH- N12(CX) N18(CX) N20(CX) N20TA(CX) N60(CX) N60TA N120 N120TA N220RH N400RH N600
Max. setting current A 13 18 22 40 65 105 100 150 220 400 800
Range of setting current A 0.1-13 2.8-18 0.2-22 18-44 12-65 54-105 34-100 85-150 65-250 85-400 200-800
Rated insulation voltage V 690 690 690 690 690 690 690 690 1000 1000 690
Permissible ambient temperature °C –25 to`55
Single phase protection Types TH-N KP provide the protection.
Bimetal heating Direct Via CTs Via CTs1
Max. heater dissipation per current path
Min. setting W 0.8 0.9 0.8 1.4 1.7 2.4 2.5 3.2 2.5 2.5 2.5
Max. setting W 1.8 2.2 2.2 3.5 4.9 5.2 7.1 8.6 6.0 6.0 6.0
Auxiliary contact 1NO`1NC
Rated operating current of aux. contacts
Category NO 120V A 2 2
AC-15 contact 240V A 1 1
500V A 0.5 0.5
NC 120V A 2 3
contact 240V A 1 2
500V A 0.5 1
Category 48V A 0.4 0.5
DC-13 110V A 0.2 0.2
220V A 0.1 0.1
Main terminal screw size
Line side mm — M4 M4 M6 M6 M8 M8 — — M4
Load side mm M3.5 M4 M4 M5 M6 M6 M8 M8 M10 M12 M4
Standard wire sizes 0.24A-2 3.6A-2 0.24A-2 22A-5.5 15A-3.5 67A-22 42A-14 105A-60 — — —

recommended 29/35A-8 22A-5.5 82/95A-38 54/67A-22 125A-60 — — —


Heater designation-wire size 11A-2 11A-2 11A-2 29/35A-8 82A-38
(mm2) 15A-3.5 15A-3.5 42A-14
19A-3.5 54A-22
Max. conductor size
Main Line side mm2 (2.5)2 — 6 — 25 — 38 60 — — 6
Load side mm2 2.5 6 6 16 25 38 38 60 150 240 6
Busbar width
Line side mm — — — 15 — 20 20 — — —
Load side mm — — — 15 20 20 20 25 30 —
Aux. contacts mm2 2.5 4 4 4 4 4 4 4 4 4
Notes: 1. Used with current transformer (to be supplied by the customer). See Table 2.1.2.
2. When used with UN-HZ 12(CX)adaptor.

2.1.4 Selection Guide of Quick Trip Thermal Overload Relay Table 2.1.4
Applicable contactor S-N10 S-N20 S-N25 S-N50 S-N80
S-N11 S-N21 S-N35 S-N65 S-N95
S-N12 S-N25 S-N80
S-N35 S-N95
Three heater type with TH-N12KF TH-N20KF TH-N20TAKF TH-N60KF TH-N60TAKF
phase failure protection
Two heater type — TH-N20FS TH-N20TAFS TH-N60FS TH-N60TAFS

Heater setting range 1.7⬃2.5(2.1A) 1.7⬃2.5 (2.1A) 18⬃26 (22A) 34⬃50 (42A) 54⬃80 (67A)
(Ordering designation) 2.8⬃4.4(3.6A) 2.8⬃4.4 (3.6A) 24⬃34 (29A) 43⬃65 (54A) 65⬃93 (82A)2
4⬃6(5A) 4⬃6 (5A) 30⬃40 (35A)1
5.2⬃8(6.6A) 5.2⬃8 (6.6A)
7⬃11(9A) 7⬃11 (9A)
9⬃13(11A) 9⬃13 (11A)
12⬃18 (15A)

Notes: *1. Only for S-N35.


*2. Only for S-N95.
42
2.1.5 Operating Characteristics of Thermal Overload Relays
(Connecting wire size: Refer to “standard wire size” of Table 2.1.3)
TH-N12 TH-N18 TH-N20·TH-N20KP
TH-N12KP·TH-N12SR TH-N18KP TH-N20SR·TH-N20KPSR
(h) (h)
(h)
2 2
2
1 Amb. Temp.: 20: 1 Amb. Temp.: 20: Amb. Temp.: 20:
1

(s) (s)
(s)
1000 1000
800 800 1000
600 600 800
400 600
400
400
With reactors 200
200 200

Operating Time
(TH-N12SR)
Operating Time

With reactors

Operating Time
100 100
80 80 100 (TH-N20SR)
60 60 80
60
40 40
30 40
30 30
20
20 20
10 10
8 8 10
6 6 8
4 6
4 4
2 Single phasing 2 Single phasing
Single phasing 2
(TH-N20KP,
1
(TH-N12KP 1
0.8 0.8 (TH-N18KP 1 Mean value)
0.6 Mean value) 0.6 0.8
Mean value) 0.6
0.4 0.4
0.4
0.2 0.2
0.8 1 1.5 2 3 4 5 6 8 10 15 0.8 1 1.5 2 3 4 5 6 8 10 15 0.2
0.8 1 1.5 2 3 4 5 6 8 10 15
Multiples of Setting Current Multiples of Setting Current
Multiples of Setting Current

TH-N20TA·TH-N20TAKP TH-N60·TH-N60TA TH-N120·TH-N120KP


TH-N20TASR·TH-N20TAKPSR TH-N60KP·TH-N60TAKP TH-N120SR·TH-N120KPSR
TH-N60SR·TH-N60TASR TH-N120TA·TH-N120TAKP
TH-N60KPSR·TH-N60TAKPSR TH-N120TASR·TH-N120TAKPSR
(h) (h) (h)
2 2 2
Amb. Temp.: 20: Amb. Temp.: 20: Amb. Temp.: 20:
1 1 1

(s) (s) (s)


1000 1000 1000
800 800 800
600 600 600
400 400 400
With reactors With reactors With reactors
200 200 (TH-N60SR) 200
(TH-N20TASR) (TH-N120(TA)SR)
Operating Time
Operating Time

Operating Time

100 100 100


80 80 80
60 60 60
40 40 40
30 30 30
20 20 20

10 10 10 Single phasing
8 8 8
6 6 6 (TH-N120(TA)KP,
4 Single phasing 4 Single phasing 4 Mean value)
2 (TH-N20TAKP, 2
(TH-N60(TA)KP, 2
Mean value) Mean value)
1 1 15A,22A,29A 1
0.8 0.8 0.8
0.6 0.6 35A,42A,67A 0.6
0.4 0.4 54A,82A 0.4

0.2 0.2 0.2


0.8 1 1.5 2 3 4 5 6 8 10 15 0.8 1 1.5 2 3 4 5 6 8 10 15 0.8 1 1.5 2 3 4 5 6 8 10 15
Multiples of Setting Current Multiples of Setting Current Multiples of Setting Current

(h) (h)
2
TH-N220RH Amb. Temp.: 20:
TH-N600 2
Amb. Temp.: 20:
1
TH-N220RHKP 1
TH-N600KP
TH-N220RHSR (s) TH-N600SR (s)
1000 1000
TH-N220RHKPSR 800 TH-N600KPSR 800
600 With reactors 600
TH-N400RH 400
(TH-N220, 400
TH-N400RHKP 200 N400RHSR) 200
With reactors
Operating Time

Operating Time

TH-N400RHSR 100 100


(TH-N600SR)
80 80
TH-N400RHKPSR 60 60
40 40
30 30
20 20

10 10
8 8
6 6
4 Single phasing 4
(TH-N220RHKP, Single phasing
2 2 (TH-N600KP,
N400RHKP,
1 1 Mean value)
0.8 Mean value) 0.8
0.6 0.6
0.4 0.4

0.2 0.2
0.8 1 1.5 2 3 4 5 6 8 10 15 0.8 1 1.5 2 3 4 5 6 8 10 15
Multiples of Setting Current Multiples of Setting Current

43
2.1.6 Optional Parts and Accessories
Saturable Reactors for Slow Tripping
Ordering designation

THR - G22 PT

Part number 3 heater 2 heater


see table 2·1·6(1) PT PD

Table 2.1.6 (1)


Part number
Heater
Designation TH-N60(KP) TH-N120(KP) TH-N220 (KP)
TH-N121 TH-N20(KP) TH-N20TA(KP) TH-N600(KP)
TH-N60TA(KP) TH-N120TA(KP) TH-N400 (KP)
0.24A TSR-A0Y TSR-C0Y — — — — —
0.35A TSR-A0Y TSR-C0Y — — — — —
0.5A TSR-A01 TSR-C0Y — — — — —
0.7A TSR-A03 TSR-C03 — — — — —
0.9A TSR-A05 TSR-C03 — — — — —
1.3A TSR-A09 TSR-C07 — — — — —
1.7A TSR-A11 TSR-C09 — — — — —
2.1A TSR-A12 TSR-C10 — — — — —
2.5A TSR-A13 TSR-C12 — — — — —
3.6A TSR-A15 TSR-C15 — — — — —
5A TSR-A18 TSR-C17 — — — — —
6.6A TSR-A21 TSR-C20 — — — — —
9A TSR-A23 TSR-C23 — — — — —
11A TSR-A25 TSR-C25 — — — — —
15A — TSR-C26 — THR-G22 — — —
19A — TSR-C29 — — — — —
22A — — TSR-D28 THR-G24 — — —
29A — — TSR-D29 THR-G26 — — —
35A — — TSR-D28 THR-G27 — — —
41A — — — THR-G27 THR-H41 — —
54A — — — THR-G29 THR-H42 — —
67A — — — THR-G29 THR-H43 — —
82A — — — THR-G30 THR-H43 THR-F10 —
95A — — — THR-G30 — — —
105A — — — — THR-H44 THR-F13 —
125A — — — — THR-H45 THR-F13 —
150A — — — — — THR-F15 —
180A — — — — — THR-F16 —
210A — — — — — THR-F17 —
250A — — — — — THR-F18 THR-E13
330A — — — — — THR-F19 THR-E13
500A — — — — — — THR-E13
660A — — — — — — THR-E13

Note: 1. Saturable reactors can be adopted only for the two heater type TH-N12

Table 2.1.6 (2)


Trip indicator Thermal overload relay Voltage(50/60Hz) Part number
TH-N12(CX)(KP) AC 24/DC24V UN-TL15DC24V
TH-N18(CX)(KP) AC 100-127V UN-TL15AC100V
AC 200-240V UN-TL15AC200V
TH-N20,N20TA(CX)(KP) AC 24/DC24V UN-TL20DC24V
TH-N60(CX)(KP)⬃N600(KP) AC 100-127V UN-TL20AC100V
AC 200-240V UN-TL20AC200V
Reset release Thermal overload relay Part number Length (mm)
TH-N12(CX)(KP) UN-RR205 200
TH-N18(CX)(KP) UN-RR405 400
UN-RR555 550
UN-RR705 700
TH-N20,N20TA(CX)(KP) UN-RR200 200
TH-N60(KP)⬃-N600(KP)1 UN-RR400 400
UN-RR550 550
UN-RR700 700
Separate mounting adaptor Thermal overload relay Part number
TH-N12(TP/KP) UN-HZ12
TH-N12CX(TP/KP) UN-HZ12CX
Note: 1. Except for type TH-N60CX and TH-N60CXKP.

44
• Connecting Parts for Contactors to Thermal Overload Relays Table 2.1.6 (3)
For connection between
contactor (non-reversing type) Overload relay Contactor Part number Mass(kg)
and thermal overload relay
TH-N20(CX)(KP) S-N20(CX), S(D)-N21(CX) UN-TH21(CX) 0.02

TH-N20(CX)(KP),-N20TA(CX)(KP) S-N25(CX), S(D)-N35(CX) UN-TH25(CX) 0.02

TH-N60(CX)(KP) S-N50(CX), -N65(CX) BH559N350 0.02


SD-N50, -N65
* Connecting bars and TH-N60(KP), -N60TA(KP) S-N80, -N95 BH569N350 0.04
mounting plate are included in SD-N80, -N95 BH569N352 0.04
the OLR of TH-N220RH(KP)
and TH-N400RH(KP) for TH-N120(KP), N120TA(KP) S(D)-N125 BH579N355 0.36
S-N180, -N220, -N300, -N400. S(D)-N150 BH589N355 0.36

2.1.7 Outline Dimensions


M3.5 screws ø5 mtg. hole 7

6
55

65.5
55
46 76.5 Mounting rail
(35mm )
M3.5 screws
8 35 4.5
TH-N12(CX)(KP) (Mass: 0.11kg)
48 83.5
M3.5 screws

TH-N12(CX)(KP) with mounting adapter UN-HZ12(CX)


59

54 80

M4 screws

TH-N18(CX)(KP) (Mass: 0.14kg)


Mass
Type A B C AA AB BA BB CC N M P Q
(kg)
BB

N-fM mtg.holes P screws


TH-N20(CX)(KP) 63 51 79 19 15 33 8.5 7 2 4.5 M4 M3.5 0.14
BA
B

TH-N60(KP) 91.5 57 87 70 12 45 6 9 2 4.5 M6 M4 0.28


AB AA CC TH-N60CX(KP) 91.5 57 87 70 12 45 6 9 2 4.5 M6 M4 0.28
A Q C
TH-N120(KP) 103 67 105 75 14 50 6 10 2 6 M8 M4 0.48
screws
TH-N600(KP) 63 42 83.5 19 14 33 2 7 2 4.5 M4 M4 0.14

N-fM mtg.holes
BB

(P’) screws
Mass
Type A B C AA AB BA BB CC N M P(Ṕ) Q
(kg)
BA
B

TH-N20TA(CX)(KP) 74 72 83.5 — — — — — — — M5 (M4) M3.5 0.2


CC
AB AA TH-N60TA(KP) 89 73.5 83.5 — — — — — — — M6 (M6) M4 0.32
A C
Q TH-N120TA(KP) 112 87 105 — — — — — — — M8 (M8) M4 0.75
P screws screws
TH-N120TAHZ(KP) 112 103 105 75 25 50 25 10 2 6 M8 (M8) M4 1.0
M4 screws

Mass
B

Type A B C AA AB BA BB CC N M P
(kg)
TH-N220RH(KP) 144 114 179.5 — — — — — — — M10 2.5
P bolts A C TH-N400RH(KP) 144 160 193.5 — — — — — — — M12 2.7

N-fM mtg.holes
BB

Mass
Type A B C AA AB BA BB CC N M P
(kg)
BA
B

TH-N220HZ(KP) 144 104 166.5 47 48.5 62 21 18 4 6 M10 2.5


TH-N400HZ(KP) 144 173 166.5 47 48.5 62 55.5 18 4 6 M12 2.7
M4 screws CC
AB AA
P bolts A C Note: Suffix “HZ” denotes separate mounting type.

45
2.2 Electronic Motor Protection Relays Series ET-N

The MITSUBISHI series ET-N relay is an excellent relay that can protect motors electrically.
Those series ET-N relays have the following excellent features.

■ Features
• Selectable Protection Mode Quick trip (3s.)
Overload (including locked rotor condition) Fast trip (5s.)
Phase failure (including current unbalance) Medium trip (15s.)
Incorrect phase sequence Slow trip (30s.)
• Excellent Wide Current Range • Withstands High Overcurrent
• Easy Wiring • Fine Indication of Trip Mode
• Easy Setting and Maintainance • Conformity to International Standards
• Selectable Tripping Time at 600% of setting. • Can be mounted on 35mm rail (ET-N60)
ET-N60 60A Standard trip (7s.)

Type Designation
ET - N60 ✽ 8A ✽ AC100/200V

FRAME SIZE CURRENT RANGE CONTROL VOLTAGE


N60 60A frame 1A 0.25⬃1A AC100V 100-120V 50/60Hz
N150 150A frame 4A 1⬃4A AC200V 200-240V 50/60Hz
N360 360A frame 8A 2⬃8A
20A 5⬃20A
60A 15⬃60A
150A 40⬃150A
360A 110⬃360A

■ Specifications
• Ratings and characteristics Table 2.2.1
Frame size [Current range] N60[1A] N60[4A] N60[8A] N60[20A] N60[60A] N150[150A] N360[360A]
Rated insulation voltage VAC 690
Adjustable setting range A 0.25-1 1-4 2-8 5-20 15-60 40-150 110-360
200-240VAC kW 0.03-0.2 0.2-0.75 0.4-1.5 1.5-4 3.7-11 11-37 30-90
Applicable motor 380-440VAC kW 0.05-0.4 0.4-1.5 0.75-2.2 2.2-7.5 7.5-22 22-75 55-150
capacity
3-ph 200-240VAC HP 1/16-1/4 1/4-1 1/2-2 2-5 5-15 15-50 40-125
380-440VAC HP 1/8-1/2 1/2-2 1-3 3-10 10-30 30-100 75-200
Category 120VAC A 2
Rated operating AC-15 240VAC A 1
current of aux. Category 24VDC A 1
contacts DC-13 110VDC A 0.2
Permissible ambient temperature/humidity °C/%RH –10 to`55/45 to 85
Control circuit consumption VA 7.5 (AC100V)/15 (AC200V)
Control voltage tolerance times 0.85 to 1.1 (rated control voltage)
Tripping time See Fig. 2.2.1
Overload % [minimum tripping current] 110 to 120 (at setting current)
Tripping condition Phase failure % more than 70 (at setting current) [Tripping time : 2-4 sec.]
Reversal phase % more than 70 (at setting current) [Tripping time : less than 0.5 sec.]
Withstand voltage VAC 2500 [1 minute]
Vibration 10-55Hz m/s2 19.6
Shock resistance
Sine wave pulse m/s2 49
Main terminals mm2 2-14 3.5-22 5.5-60 14-200
Conductor size
Control terminals mm2 1.25-2
Note: ET-N relay cannot be used on DC circuit

46
• Characteristic Curves
Fig 2.2.1
(h)
2
(min)
1 60
50
40
30
(s)
1000 20
800
600 10
8
400 6
5
4
200 3
Tripping time

2
100
80 Overload
60 1
40
(600%)
30 30s
20
15s
10
8 7s
6
Phase failure 5s
4
3s
2

1
0.8
0.6 Reverse phase
0.4

0.2
0.8 1 1.5 2 3 4 5 6 8 10 15

Multiple of Setting current

• Selection of Protection Mode & Tripping Time Table 2.2.2


Overload tripping time
ET-N60 Protection mode Symbol on changeover switch
MODE at 600% of setting(s)
20A 10 15 TEST RESET
PWR OC PF REV 0 12 3 0
EF
BCD

34 5

Overload, phase failure and 5 1


67
5 20 8 9A
reversal phase 7 2
RC.A
CURRENT [3E] 15 3
30 4
Current Setting Function Selector 3 5
Switch 5 6
Overload and phase failure
The selector switch is set at position “7” (overload 7 7
[2E]
and phase failure protection mode; standard trip 15 8
type) when shipping. 30 9
So please reset the position of the changeover 3 A
switch according to Table 2.2.2 before installation. 5 B
Overload only
7 C
[1E]
15 D
30 E

• Application to High Voltage or Big Motor Circuit


The high voltage current transformer (secondary current: smaller than 5A:
capacity: more than 5VA) should be connected to ET-N60✽8A in the star
connection, when the load is high voltage or big AC motor.

47
■ Wiring Precautions
Indicators
LED1:Source
• The control source should be
MCCB
LED2:Overload Mode selection wired in the same phases as the
LED3:Phase failure contactor control source.
LED4:Reverse phase Current setting

1/L1 3/L2 5/L3


MC Test button Reset button • When the load is a single phase
LED1 LED2 LED3 LED4 motor, use 1/ L1-2/T1 and 5/L3-
6/T3 phases.
And re-set the position of
changeover switch to “A” to “E”.
RA

NC NO

2/T1 4/T2 6/T3 A1 A2 MC 96 95 98 97

MC

M ~
Control source
ON OFF

• If capacitors are used to correct the power factor, connect the capacitor in the power source side of the ET-N relay.

■ Outline Dimensions
100 M8 screw 150
78 2–M4 mtg. hole Mounting rail 92
32 32 26.5
M5 screw 68 (35mm ) 4–M4 mtg. hole
24.5 24.5 50 2.5

2.5
48

1/L1 3/L2 5/L3


25.5

1/L1 3/L2 5/L3


49

63
50

108
75
84

A1 A2 96 95 98 97 A1 A2 96 95 98 97
A1 96 98 A1 96 98
A2 95 97 A2 95 97
19

2/T1 4/T2 6/T3


2/T1 4/T2 6/T3
41.5
3

15.7 9.5 10.5


M3.5 screw 70
100 15.7 26 21.5 7
M3.5 screw
120

ET-N60(1-60A) (Mass: 0.3kg) ET-N150 (Mass: 1.6kg)

144 M12 screw


55 188
30 30 2.5 62

R/1/L1 S/3/L2 T/5/L3


80.5
143
173
62

A1 A2 96 95 98 97
9.5
A1 96 98
A2 95 97

U/2/T1 V/4/T2 W/6/T3

18
4–M5 mtg. hole 47 20 158

M3.5 screw

ET-N360 (Mass: 2.5kg)

48
3. DEFINITE PURPOSE CONTACTORS & STARTERS
Series DU
3.1 DC Contactors
The MITSUBISHI series DU contactors are designed for DC circuits, that is the variable-speed drive-control
circuits (SCR switching circuit) and DC motor control circuits.

■ Features
• Compact design • Double break contacts • Long Life
• High break capacity • UL recognized component
DU-A60 • CSA cirtified models are also (If marking is required add
available on AC operated type, suffix “UR” immediately after
add suffix “UR” immediately the Frame size).
after the Frame size.

Type Designation

DU-K180 DU - A60 ✽ AC 200V

CONTROL TYPE FRAME SIZE COIL DESIGNATION


DU AC operated A30 50A frame see Table 3.1.3
DUD DC operated A60 90A frame
A120 160A frame
K180 260A frame
K260 360A frame
Note: Mark ✽ indicates a blank space.

■ Specifications
• Number of main contacts type DU : 2NO1NC, type DUD : 2NO
Number of auxiliary contacts type DU & DUD : 2NO2NC

• Ratings Table 3.1.1


Frame size A30 A60 A120 K180 K260
Conventional free air thermal current A 50 90 160 260 360
Rated operating NO 110VDC A 40 80 160 260 360
current for SCR contact 240VDC A 40 80 160 260 360
switching circuit* 440VDC A 15 30 60 90 130
500VDC A 15 30 60 90 130
NC 110VDC A 120 240 480 720 1.040
1-pole contact 240VDC A 120 240 480 720 1.040
440VDC A 120 240 480 720 1.040
500VDC A 120 240 480 720 1.040
Rated operating current for SCR NO 110VDC A 50 90 160 260 360
switching circuit contact 240VDC A 50 90 160 260 360
440VDC A 40 80 160 260 360
2-pole 500VDC A 40 80 160 260 360
Rated operating NO 110VDC A 30 60 120 180 260
current contact 240VDC A 20 40 80 120 175
category DC 2 & 4 440VDC A 7.5 15 30 — —
NC 110VDC A 20 40 80 100 150
1-pole contact 240VDC A 15 30 60 75 100
440VDC A 7.5 15 25 — —
Rated operating current NO 110VDC A 40 80 160 240 350
category DC2 & 4 contact 240VDC A 30 60 120 180 260
2-pole 440VDC A 20 40 80 120 175

Rated Category 110VAC A 6


operating AC-15 240VAC A 5
current of
Category 110VDC A 0.6
aux. contacts
DC-13 240VDC A 0.2
Note: For SCR switching, making current of NO contacts is 2 times the rated operating current and making current of NC contact is 1 times,
the rated operating current which means the peak value at making. In this application NO and NC contacts do not break any current.

49
• Characteristics Table 3.1.2
Frame size A30 A60 A120 K180 K260
Mechanical life operations 2.5 million
Electrical life operations 0.5 million
Permissible ambient temperature °C –10 to 55
Coil voltage tolerance times 0.85 to 1.1 (rated coil voltage)
Coil consumption Inrush VA 240 520 1260 480 480
Sealed VA 28 47 100 44 54
Watts W 7 (26) 13 (35) 25 (50) 5(41) 7.3(55)
Operating time Make NO contacts ON msec 15 (60) 20 (100) 20 (140) 30(150) 40(180)
NC contact OFF msec 12 13 13 26 37
Break NO contacts OFF msec 6(18) 11 (27) 11 (37) 110(25) 125(30)
NC contact ON msec 12 18 18 112 135
Make and break capacity Make tmes 4 (at the rated operating current)
Category DC2 & DC4 Break times 4 (at the rated operating current)
Permissible switching frequency operations/hour 1,200
Vibration resistance 10-55Hz m/s2 19.6
Shock resistance 10 msec half sine wave m/s2 49
Conductor size Main terminals mm2 2-25 2-35 6-70 10-150 16-185
Control terminals mm2 1-4 1-2.5
Note: Parenthesized data is for type DUD, DC operated contactors.

• Coil designation Table 3.1.3


Coils for type DU-A Coils for type DU-K Coils for type DUD

Coil Appicable voltage Coil Coil Applicable


Applicable voltage
designation 50Hz 60Hz designation designation voltage

AC100V 100VAC 100-110VAC AC100V 100-127VAC 50/60Hz DC24V 24VDC


AC120V 110-120VAC 115-120VAC DC48V 48VDC
AC200V 200VAC 200-220VAC AC200V 200-240VAC 50/60Hz DC100V 100VDC
AC230V 220-240VAC 230-240VAC DC110V 110VDC
AC300V 260-350VAC 50/60Hz DC120V1 120VDC
AC400V 380-415VAC 400-440VAC AC400V 380-440VAC 50/60Hz DC125V 120-125VDC2
AC440V 415-440VAC 460-480VAC DC200V 200VDC
AC500V 500VAC 500-550VAC AC500V 460-550VAC 50/60Hz DC220V 220VDC
Notes: 1. Only for type DUD-A60
2. 125V DC for type DUD-A60

■ Spare parts Table 3.1.4


Spare parts Ordering designation
Main contact kits for DU- 1 MAIN KIT DU-
Main contact kits for DUD- 2 MAIN KIT DUD-
Auxiliary contact kits for DU(D)-A 3 Z926783G30
Auxiliary contact Units for DU(D)-K 4 UN-AX150
Coils for DU- 5 DU- -COIL AC··V
Coils for DUD- 6 DUD- -COIL DC··V
Notes: 1. Contact kit of type DU consists of three moving contacts and six stationary contacts.
2. Contact kit of type DUD consists of two moving contacts and four stationary contacts.
3. Aux. contact kits of type DU(D)-A are all the same.
4. Aux. contact units of type DU(D)-K , UN-AX 150 are the same as those of the standard series S-N contactors.
5. Coils for DU-K 180/K 260 are the same as S-N220/N300 each.
6. Coil for DUD-A30 includes only one coil. Other DC operated coils of type DUD include two coils.

50
■ Contact Arrangements

A1 A1 A1 A2
/ 21 /1 /3 /5 43 31 / 21 /1 /5 43 31 / / /1 /5
a 13 (31) (23) (41) a 13 (31) (23) (41) a b 13 31 23 41

14 22 44 32 14 22 44 32 14 32
A2
(32) /2 /4 /6 (24) (42)
A2
(32) /2 /6 (24) (42) A2 A1 /2 /6 24 42
/ / / /
b b b a
D.B. resistor

M M M

DU-A30, DU-A60, DU-A120 DUD-A30,DUD-A60 DUD-A120


DU-K180, DU-K260 DUD-K180,DUD-K260

Note: Values in parenthesis are shown on auxiliary terminals of DU-A or DUD-A .

■ Outline Dimensions
N-fM mtg holes
M4 screws P screws
AA
BA

T CC
A C

Type A AA B BA C CC N M P Mass(kg) T
DU-A30 100 86 118 90 105.5 12.5 3 5 6 1.2 10
DU-A60 120 100 144 100 128.5 16 3 5 6 2.0 10
DU-A120 162 130 160 140 162 2.3 4 6 10 4.1 10
DU-K180 138 120 204 190 174 1.6 4 6 10 5.5 30
DU-K260 163 145 243 225 195 2.3 4 8 12 10 50
DUD-A30 101 86 108 90 135.5 3.2 3 5 6 2.1 10
DUD-A60 120 100 144 100 161.5 2 3 5 6 3.5 10
DUD-A120 162 130 160 140 187 2.3 4 6 10 7.1 10
DUD-K180 138 120 204 190 200 1.6 4 6 10 7.5 30
DUD-K260 163 145 243 225 220 2.3 4 8 12 13.5 50

51
Series SH-V
3.2 Medium Voltage Vacuum Contactors

The MITSUBISHI series SH-V contactors are specially designed for the areas of mining, pumping,
sawing and other applications where voltage above 1500VAC are frequently used.

■ Features
 Compact design  Easy inspection & maintenance
 Lightweight  Applications over a wide range of voltage
 Long service life  High insulation strength
SH-V160

Type Designation

SH – V 160 * AC200V

CONTROL TYPE CONTACTOR TYPE FRAME SIZE COIL DESIGNATION


SH AC operated V Non-reversing 160 160A frame See Table 3.3.3
SHD DC operated 2XV Reversing 320 320A frame
400 400A frame
SHL AC & latched
6001 600A frame
SHLD DC & latched
Note: Mark* indicates
a blank space.

Note: 1. Only AC operated non-reversing type is available for Frame size 600.
SH-V600 is not presently certified by CSA.

■ Specifications
 Ratings Table 3.2.1
Frame size V160 V320 V400 V600
Rated insulation voltage V 1,500 1,500 1,500 1,500
240V 55(180) 90(320) 115(400) 160(630)
Three phase motor 440V 110(180) 200(320) 250(400) 300(630)
category AC3 660V kW(A) 160(180) 315(320) 400(400) 600(600)
1,000V 225(160) 450(320) 550(400) 750(600)
Rated operating 1,500V 315(160) 700(320) 800(400) 1,000(600)
capacity 240V 50(150) 75(250) 100(300) 200(580)
Three phase 440V 100(150) 150(250) 200(300) 400(580)
kVar(A)
capacitor 1,000V 250(150) 300(200) 300(200) –
1,500V 350(150) 500(200) 500(200) –
Resistance load rating category AC-1 A 200 350 450 750
Conventional free air thermal current Ith A 200 350 450 750
Short circuit interrupting current A 4,000 5,040
Withstand current for 2 seconds kA 4 6
for short time for 10 milliseconds kA 33
Category 240VAC 5
480VAC A 3
Rated operating AC-15
660VAC 3
current of
aux. contacts Category 110VAC 1.2
DC-13 A
220VAC 0.2
Note: A surge absorber is required for motors less than 5.5kW only.

52
 Characteristics Table 3.2.2
Frame size V160 V320 V400 V600
Mechanical life1.2. operations 2.5 million
Electrical life3.4.(category AC3) operations 0.5 million
Permissible ambient temperature °C -10 to +55
Coil voltage tolerance times 0.85 to 1.1(rated coil voltage)
AC operated lnrush VA 550 1150
Sealed VA 45 55
Watts W 5.2 7.3
Coil consumption
DC operated lnrush VA 500 —
Sealed VA 40 —
Mechanically latched lnrush VA 550 —
Make msec 40 65
Operating time(approx.)
Break msec 130 80
Make times 10(at AC3 rated operating current)
Make and break current capacity
Break times 8(at AC3 rated operating current)
Permissible switching frequency operations/hour 1,200
Vibration resistance 10-55Hz m/s2 19.6
Shock resistance Sine wave pulse m/s2 49
Main terminals mm2 5.5-100 14-200 70-325
Conductor size
Control terminals mm2 1-2.5
Notes: 1. Mechanical life of the latched type is 0.25 million operations.
2. Mechanical life of vacuum tube is 1 million.
3. When the load is three pahse capacitors, electrical life is 0.1 million operations.
4. Electrical life of the latched type is 0.25 million operations.

 Coil Designation Table 3.2.3


Coil designation Rated voltaege
AC100V 100~127V 50/60Hz
AC200V 200~240V 50/60Hz
AC300V 260~350V 50/60Hz
AC400V 380~440V 50/60Hz
AC500V 460~550V 50/60Hz Note: When ordering the latched type contactor, specify the coil
designation of the closing coil and the tripping coil.
DC100V 100-110 VDC Place“MC”before the closing coil designation and
DC200V 200-220 VDC place“MT”before the tripping coil designation.

■ Spare Parts & Accessories Table 3.2.4


Contactor Catalog Main Contact Part Auxiary Contacts Number Vaccum Tube Gauge
Number Coil Part Number1 Number Replacement(1NO 1NC) Add-on(2NO 2NC) Part Number
SH-V160 SH-V160TUBES2
SH-V320 SH-V160COIL AC ........... V SH-V320TUBES2 UA-AXVV1 UA-AXVV23 SH-V160 GAUGE
SH-V400 SH-V400TUBES2
SH-V600 SH-V600COIL AC ........... V SH-V600TUBES2 UA-AXVV4 SH-V600 GAUGE

Notes: 1. See Table 3.3.3 for Coil Designation.


2. Set of three vacuum bottles suppled.
3. Consists of two UA-AXVV1 contact blocks on the mounting plate. Mounts on left side of contactor.

 Surge absorber Table 3.2.5


As the vacuum tubes of SH-V use a special contact material, Applicable voltage Ordering designation
the surge voltage by current chopping is very small. Surge
absorbers are required only for motors smaller than 5.5kW. up to 440VAC UA-SU4
up to 550VAC UA-SU5
up to 660VAC UA-SU6
up to 1,000VAC UA-SU10
up to 1,500VAC UA-SU15

53
■ Contact Arrangement
TRIPPING
CLOSING

E2 55 13

E1 E2 55 A1 A2 53 61 83 71 1/L1 3/L2 5/L3 13 21 43 31


A1 A2 53 61 83 71 1/L1 3/L2 5/L3 13 21 43 31

54 62 84 72 2/T1 4/T2 6/T3 14 22 44 32


56
54 62 84 72 2/T1 4/T2 6/T3 14 22 44 32

SH-V□ SHL-V□
SHLD-V□

■ Outline Dimensions
210 210 210 210
N screws 190 181 N screws 190 181
4-f9 4-f9
mtg 2 mtg 2
holes holes
A

KEYS N A
SH-V160 M8 10
210

190
210
210

190

210
SH-V320 M10 12.5
SH-V400 M10 12.5
SHL(D)-V160 M8 10
10
10

A
A

SHL(D)-V320 M10 12.5

90
SHL(D)-V400 M10 12.5
25 25
80

SH-V160, V320, V400 (Mass:12.5kg) SHL-V160, V320, V400 (Mass:14kg)


SHLD-V160, V320, V400

290 225
270 219
15

175
11

40
2.3
260
285

43.5 29 121 28
100
49

49

M16 BOLTS
160

4-f 9 MTG.
HOLES

SH-V600(Mass:22kg) UA-AXVV1(Mass:0.2kg) UA-AXVV2 (Mass:0.5kg)

54
Series S-N 8
3.3 Compact 3-Pole Contactors
The MITSUBISHI series S-N 8 compact 3-pole contactors are designed for limited panel space
applications such as machine control panels.

■ Features
 Compact design–Very limited required mounting space.
 Front clip-on type auxiliary contact block can be added.
 Coil surge absorbers are available.  Can be mounted on 35mm rail.
Type Designation
S – 2X N38 CX * AC 200V

REVERSING OR
S-N48 FRAME SIZE FINGER PROTECTION COIL DESIGNATION
NON-REVERSING
None Non-reversing None Not provided See Table 1.5.1 on
See table 3.3.1
2X Reversing CX Provided page12

■ Specifications Note: Mark* indicates a blank space


 Rating and characteristics Table 3.3.1
Type S-N18 (CX) S-N28 (CX) S-N38 (CX) S-N48 (CX)
Rated insulation voltage V AC690
220-240V A(kW) 18(4.5) 26(7.5) 39(11) 50(15)
Rated operational current
380-440V A(kW) 16(7.5) 17(7.5) 32(15) 40(18.5)
500V A(kW) 13(7.5) 13(7.5) 24(15) 32(18.5)
3-ph, category AC-3
690V A(kW) 9(7.5) 9(7.5) 12(11) 17(15)
Conventional free air thermal current A 25 30 60 80
Electrical life operations 1
Mechanical life (million) 10 5
Rated making current for 100,000 cycle operations
A 200 300 500 670
Peak let through time 0.5ms
Switching frequency(AC3) operations/hour 1800 1800 1800 1200
Inrush VA 60 110
Coil consumption
(at rated coil voltage) Sealed VA 10 13
Watts W 3 4·5
Main terminal M4 M4 M5 M5
Terminal screw size
Control terminal M3.5 M3.5 M3.5 M3.5
Conductor size Main terminal 1~6 2~16
(Compression terminal size) Control terminal 1~2.5 1~2.5
Additional auxiliary contact block UN-AX2 or UN-AX4
Note: 1. For finger protection type, order model name followed by suffix “CX”.

■ Contact Arrangement ■ Outline Dimensions


2 mtg. holes for M4 screws
Mounting rail 4 mtg. holes for M4 screws
a) M3.5 screw
(35mm ) M3.5 screw Mounting rail
P screw (35mm )
A2 A1 1/L1 3/L2 5/L3
13
BB

79
B

60
BA

2/T1 4/T2 6/T3

S-N□ 8 (CX) AB AA CC 5.5 30 23 30


M4 screw 10
4

96 5 109
A T C

S-2xN18 (CX), N28 (CX)


M3.5 screw
3 mtg. holes for M4 screws
5

A2 A1 1/L1 3/L2 5/L3 53 61 71 83 A2 A1 1/L1 3/L2 5/L3 53 61 71 83


110
120

2/T1 4/T2 6/T3 54 62 72 84 2/T1 4/T2 6/T3 54 62 72 84

S-2xN□ 8 (CX)
11 100 1.6
M5 screw
122 5 127

S-2xN38 (CX), N48 (CX)


Fig. A B C AA AB BB BA CC CA D P Q Mass(kg) T
S-N18 (CX), N28 (CX) a 43 79 81 30 7 60 6 10 109 4 M4 M3.5 0.33 5
S-N38 (CX), N48 (CX) a 54 90 93 40 7 80 6 7 121 4 M5 M3.5 0.4 5

55
3.4 NC Main Contact Contactors

The MITSUBISHI series B-N contactors are specially designed for the dynamic braking circuit of motors,
switching motor-starting resistors and switching of emergency lighting.

■ Features
 2 or 3 NC main contacts.  Conpact design
 Suitable for a variety of loads.  Both AC operated models & DC operated models
B-N20
Type Designation

B − N20 * AC100V * 3B

CONTROL TYPE FRAME SIZE COIL DESIGNATON MAIN CONTACT ARRANGEMENT


B-N65 B AC operated N20 25A frame See Table 3.4.4 * 1NO 2NC
BD DC operated N65 80A frame 3B 3NC
N100 120A frame
Note: Mark* indicates a blank space.

■ Specifications
 Number of main contacts: Special arrangement 3 NC can be supplied only with type B-N20/N65.

 Ratings Table 3.4.1


 Rated operating current of
FRAME SIZE N20 N65 N100
aux. contacts. Table 3.4.2
Category Rated voltage A
Conventional free air thermal current lth A 25 80 120
110VDC A 8 20 30 120VAC 6
2NC1 240VAC 5
DC 220VDC A 1 3 3 AC-15
440VAC 3
Rated operating current 110VDC A 15 50 – 500VAC 3
category DC-2 & DC-4 3NC2
220VDC A 5 20 –
48VDC 3
Electrical life Operations 0.5 million DC-13 110VDC 0.6
110VDC A 15 30 40 220VDC 0.2
2NC1
DC 220VDC A 5 10 20
Rated operating current 110VDC A 20 65 –
category DC-1 3NC2
220VDC A 10 30 –
Electrical life Operations 0.5 million
200-220VAC A 18 50 80
1NC Notes:1. At 2NC series 2. At 3NC series
AC 3-ph 380-440VAC A 13 35 55
connection connection
Rated operating current Electrical life 0.5 million
Operations
(Making/Breaking) (6 (rated operating current)/no breaking)
2NC1 200-220VAC A 18 50 80
AC 1-ph
Rated operating current Electrical life 0.5 million
Operations
(Making/Breaking) (6 (rated operating current)/rated operating current)
Notes: 1. At 2NC series connection
2. At 3NC series connection

 Characteristics Table 3.4.3  Coil Designation Table 3.4.4


FRAME SIZE N20 N65 N100 Type Coil Applicable voltage
designation
Mechanical life Operations 5 million AC100V 100V/50Hz, 100-110V/60Hz
Inrush VA 90 ( – ) 210 ( – ) 270 ( – ) B-N20 AC200V 200V/50Hz, 200-220V/60Hz
Coil consumption Sealed VA 15 ( – ) 23 ( – ) 24 ( – ) AC400V 380-415V/50Hz, 400-440V/60Hz
Watts W 4 (9) 2.8 (24) 2.9 (24) AC100V 100-127V/50Hz, 100-127V/60Hz
B-N65
Coil voltage tolerance times 0.85 to 1.1(at rated coil voltage) AC200V 200-240V/50Hz, 200-240V/60Hz
B-N100
AC400V 380-440V/50Hz, 380-440V/60Hz
Coil off / NC on msec 19 (16) 75 (21) 120 (50)
Operating time DC100V DC100V
Coil on / NC off msec 11 (35) 20 (80) 22 (130)
BD-N20
DC110V DC110V
Make and break current BD-N65
DC-2 & DC-4 times 4(rated operating current L/R≦15 msec) DC200V DC200V
capacity BD-N100
DC220V DC220V
2
Main terminals mm 1-6 2-25 (6-70)2
Conductor size
2
Control terminals mm 1-2.5

Notes: 1. Parenthesized data if for type BD-□ DC operated contactors.


2. Conductor size in parentheses indicate compression terminal style not for bare
clamping.

56
■ Spare Parts Table 3.4.5

Spare parts Ordering designation

Main contact kits for B(D)-N20 1NO2NC PARTS MAIN KIT B(D)-N20 1A2B BH739N304
for B-N20 3NC B-N20 3B BH739N302
for B(D)-N65 1NO2NC B(D)-N65 1A2B BH769N305
for B-N65 3NC B-N65 3B BH769N306
for B(D)-N100 B(D)-N100 BH779N303
Auxiliary contact kits for B(D)-N20 PARTS AUX KIT B(D)-N20 BH739N312
for B(D)-N65 B(D)-N65 BH539N315
for B(D)-N100 B(D)-N100 BH579N312
Coils for B-N AC operation B-N -COIL AC....V
for BD-N DC operation BD-N -COIL DC....V

■ Contact Arrangements
main contacts: 1NO2NC main contacts: 3NC main contacts: 1NO2NC main contacts: 3NC
aux. contacts: 2NO aux. contacts: 2NO aux. contacts: 2NO2NC aux. contacts: 2NO2NC
13 21 3/L2 43 31 13 21 3/L2 43 31
A2 A1 13 1/L1 3/L2 5/L3 23 A2 A1 13 1/L1 3/L2 5/L3 23 A1 A2 (13) (31) 1/L1 5/L3 (23) (41)
A1 A2 (13) (31) 1/L1 5/L3 (23) (41)

14 2/T1 4/T2 6/T3 24 14 2/T1 4/T2 6/T3 24 14 22 44 32 14 22 44 32


2/T1 6/T3 2/T1 6/T3
(14) (32) 4/T2 (24) (42) (14) (32) 4/T2 (24) (42)

B-N20, BD-N20 B-N20 B-N65, B-N100 B-N65


BD-N65, BD-N100

■ Outline Dimensions
Q screws
N-mtg. holes for M screws
P screws
BB
BA

AB AA CC
A CD C

Type A B C AA AB BA BB CC CD N M P Q Mass(kg)

B-N20 63 81 81 54 4.5 60 14 6.5 5 2 M4 M4 M3.5 0.4


B-N65 100 124 127 80 10 110 7 12 10 2 M5 M6 M4 1.7
B-N100 100 150 137 90 5 125 12.5 2 10 4 M4 M8 M4 2.7
BD-N20 63 81 113 54 4.5 60 14 6.5 5 2 M4 M4 M3.5 0.7
BD-N65 100 134 158 80 10 110 17 12 10 2 M5 M6 M4 3.0
BD-N100 102 150 162 90 6 125 12.5 1.6 10 4 M4 M8 M4 4.3

57
3.5 Delay Open Type Magnetic Starters & Contactors
Series S/MSO-N DL

The MITSUBISHI series MSO-N DL starters and S-N DL contactors are specially designed to
prevent instantaneous “drop-out” when connected to motors, resulting from momentary voltage drop
or power interruption caused by lightening or similar.
A capacitor connected in parallel with the operating coil of the contactor discharges so that the starter
or contactor will remain closed for 1 to 4 seconds.

MSO-N DL
Type Designation

MSO – N21 DL * 7.5kW * 380V * AC200V

TYPE FRAME SIZE MOTOR MAIN


CONTROL CIRCUIT VOLTAGE
MSO Starter See LOAD CIRCUIT
S Contactor Table 3.5.1 CAPACITY VOLTAGE AC100V 100-110V 50/60Hz
AC200V 200-220V 50/60Hz

Note: Mark * indicates a blank space.

■ Specifications
 Ratings and Characteristics Table 3.5.1
Frame size N12 N21 N35 N50 N65 N80 N95 N150 N220 N300 N400
Three phase 220-240VAC kW 3.5 5.5 11 15 18.5 22 30 45 75 90 125
motor 380-440VAC kW 5.5 11 18.5 22 30 45 55 75 132 160 220
500-550VAC kW 5.5 11 18.5 22 30 45 55 90 132 160 225
220-240VAC A 13 22 40 55 65 85 105 150 250 300 400
Category 380-440VAC A 12 22 40 50 65 85 105 150 250 300 400
AC-3 500-550VAC A 9 17 32 38 60 75 85 140 200 250 350
Conventional free air thermal current lth A 20 32 60 80 100 135 150 200 260 350 450
Available aux. contacts – 1NO1NC
Holding time sec. 2 +2
–1

Control circuit power Inrush VA 21 40 44 55 55 66 66 76 100 140 140


consumption Sealed VA 13 18 19 26 26 27 27 55 66 85 85

 Diagrams Circuit  Typical Wiring Diagram


MC C(+)

R2
OFF
NO THR

R1
NF RF
1/L1 5/L3
(P3) (–)

ON
C

MC ON 3/L2
VAR
NO/NC

A2 A1 13 21
VAR
R3

R/1S/3 P1 P3 P4 (P4)
C

C R3 R2 MC OFF
R1

22
14
RF

VAR

MC 97 95

THR 2/T1 4/T2 6/T3 98 96

Note: R/1-R/1 & S/3-S/3 (– - - –) wiring is omitted if the control


circuit voltage is 100VAC or the main circuit voltage differs
from the control circuit voltage.

58
 Caution
1. When the circuit breaker (NF) is made (ON) and disconnected (OFF) repeatedly within a short time interval [eg: when the
instantaneous power failure occurs within a short time interval], electrical parts might be damaged or specified holding time
might not be assured.
Causes; 1) Overload occurs by frequent inrush current to RF and R1.
2) Enough electricity is not charged into the capacitor (C).
2. Even after the power is turned off (after the NF is disconnected), current might remain in the capacitor (C). So please take
care to avoid the electrical shock, when you check or repair the system.

■ Outline Dimensions

D screws
AD CB C

BD
E screws

BC
(+)
C

THR
MC

NO/NC
(-)

NO
C

(P3)

(P4)
R/1 S/3 P1 P3 P4
R3

BA
B
R1

VAR

R4
R3
VAR

R2
R1

CA
Mtg hole for F Screw

AC AB

■ Dimensions Table 3.5.2


Dimension
A AB AC AD B BA BC BD C CA CB D E F
Model
MSO-N12DL 132 40 49 69 110 100 5 12.5 98 6 5 M3.5 M3.5 3-M4
MSO-N21DL 137 60 43 73 125 100 19 11 98 6 5 M4 M3.5 3-M4
MSO-N35DL 134 50 42 67 162 150 6 23 114 8 5 M5 M3.5 3-M4
MSO-N50/65DL 150 50 56 81 168 150 9 26.5 141 8 10 M6 M4 3-M5
MSO-N80/95DL 170 100 35 85 220 200 10 39.5 165 8 10 M6 M4 3-M6
MSO-N150DL 210 140 26 105 270 250 10 33 177.5 8 30 M8 M4 3-M8
MSO-N220DL 230 140 20 90 290 250 12 21 208.5 8 30 M10 M4 3-M8
MSO-N300/400DL 300 200 10 – 361.5 200 25 30 229 8 50 M12 M4 4-M8

Notes: 1. Dimensions CB is the arc clearance.


2. Outline dimensions of S-N DL are the same as those of MSO-N DL, except for S-N300/N400DL. Dimension B of S-
N300/N400DL is 250mm.

59
Series SD-Q
3.6 DC Interface Contactors

SD-Q DC interface contactors designed to be directly driven


by the transistor output DC24V are DC operated contactors of
compact size and high ability.
• By combining the efficient electromagnet with permanent
magnet, SD-Q contactors are able to be directly driven by
the transistor output DC24V 0.1A of a programmable logic
controller, etc. SD-Q series is lineup contained reversing
contactors applied to motors of 3φ 440V5.5kW starters with
the thermal overload relay, and additional auxiliary contact
block, etc.

SD-Q11 MSOD-Q11

■ Features
 Special design to be directly driven by the transistor output DC24V
 By combining an electromagnet with permanent magnet, coil operating current is reduced to DC24V55mA(1.3W) for SD-Q11
and DC24V75mA(1.8W) for SD-Q19
 Compliance with many international standards
Applicable standards: IEC, DIN, VDE, BS, JIS, JEM
Approved standards: UL, CSA, TÜV
 Built-in surge absorber
 Provision of terminal covers
 Mountable on a IEC 35mm width rail
 Compact size and high performance
SD-Q11, SD-Q12 : 3φ 240V3kW SD-Q19 : 3φ 240V4.5kW
3φ 440V4kW 3φ 440V5.5kW
 Mirror contact: Normally closed auxiliary contact cannot be closed when power contact is welded. The function conform to
requirements of IEC60947-4-1.
 Variable combination: Auxiliary contact block (UQ-AX2(KR)) can be added onto a contactor (SD-Q11 (SD-QR11))

Type Designation
 Magnetic motor starter MSOD Q11 CX KP * 9A * 200V * DC24V * 1B

BASIC TYPE THERMAL OVERLOAD HEATER DESIGNATION OF OVERLOAD RELAY AUXILIARY CONTACT ARRANGEMENT ※
RELAY WITH CAN TERMINAL 0.12 (0.1 to 0.16), 0.17 (0.14 to 0.22)
MSOD DC operation No
Please designate when the contact
type Standard Q11 0.24 (0.2 to 0.32), 0.35 (0.28 to 0.42) arrangement is special.
symbol Q12 0.5 (0.4 to 0.6), 0.7 (0.55 to 0.85) The standard contact arrangement
With CAN will be used if there is no designation.
CX QR11 0.9 (0.7 to 1.1), 1.3 (1 to 1.6), 1.7 (1.4 to 2)
terminal
FRAME SIZE QR12 2.1 (1.7 to 2.5), 2.5 (2 to 3), 3.6 (2.8 to 4.4)
5 (4 to 6), 6.6 (5.2 to 8), 9 (7 to 11),11 (9 to 13)
reversing

Q11 COIL DESIGNATION


Non-

THERMAL OVERLOAD RELAY COMBINATIONS 1.3 (1 to 1.6), 1.7 (1.4 to 2), 2.1 (1.7 to 2.5) DC24V
Q12
No Overload protection type with Q19 2.5 (2 to 3), 3.6 (2.8 to 4.4), 5 (4 to 6)
Q19 QR19 6.6 (5.2 to 8), 9 (7 to 11)
symbol two heater elements MAIN CIRCUIT VOLTAGE
Reversing

QR11 11 (9 to 13), 15 (12 to 18)


Overload and phase failure Do not add AC onto the main circuit
QR12 KP protection type with three Note: The thermal overload relay for each type is as follows. voltage.
QR19 heater elements Q11,Q12,QR11,QR12 : TH-N12 (CX)(KP)
Q19,QR19 : TH-N18 (CX)DM(KP)

 Magnetic contactor SD Q12 * DC24V * 2A

BASIC TYPE COIL DESIGNATION


SD DC operation type DC24V

※Code of arrangement for special Auxiliary contact


FRAME SIZE AUXILIARY CONTACT ARRANGEMENT ※ ARRANGEMENT CODE
Non- Q11, Q12, Please designate when the contact arrangement 1NC 1B
reversing Q19 is special. 2NO 2A
The standard contact arrangement will be used if
Reversing QR11, QR12, there is no designation. A:Normally open
QR19 B:Normally closed

Note: Mark * indicates a blank space.

60
■ Specifications
 Ratings & characteristics Table 3.6.1
Non- SD-Q11
reversing SD-Q19
SD-Q12
Type
Reversing SD-QR11
SD-QR19
SD-QR12
Rated insulation voltage V 690
Conventional free air thermal current A 20 30
Category 220 to 240V AC A 12 18
AC-3 380 to 440V AC A 9 13
Rated 500V AC A 7 13
operational 690V AC A 5 7
current
Category 220 to 240V AC A *1) 10 (15) 30
AC-1 380 to 440V AC A 10 20
Category 220 to 240V AC kW 3 4.5
Rated
(IEC) 380 to 440V AC kW 4 5.5
3ph motor
AC-3 500V AC kW 4 7.5
capacity
690V AC kW 4 5.5
Pick-up voltage(to rated coil voltage) % 85 85
Coil consumption(at rated coil voltage)(at 20℃) W 1.3 1.8
Coil current(at 20℃) mA 55 75
Operating times Closing mS <50 <60
(at rated coil voltage) Opening mS <20 <35
Mechanical endurance operations 10 million 10 million
category AC-3 operations 1 million 2 million
Electrical endurance
category AC-1 operations 0.5 million 0.5 million
Permissible ambient temperature ℃ -10 to 55 -10 to 55
Switching frequency operations/hour 1800 1800
main; 1 to 6
Conductor size mm2 1 to 2.5
control; 1 to 2.5
main; 1.18 to 1.86
Terminal screw tightening torque range 0.94 to 1.17 (1.47)
(standard value) N・m (1.0) control; 0.94 to 1.51
(1.17)
Note:*1. The electrical endurance at the rating given in parentheses is 0.25 million.

 Ratings of auxiliary contacts Table 3.6.2  Coil rating and Ordering designation Table 3.6.3
Rated insulation voltage V 690 Rated voltage
Ordering designation
Conventional free air thermal (V DC)
A 10
current 24VDC 24VDC
Rated Category 240V AC A 3 Note: The operation coil terminal has a polarity. A1(+), A2(-)
opera- AC-15 440V AC A 1
tional Category
current 24V DC A 10
DC-12
Mechanical endurance operations 10 million
Electrical endurance operations *2) 0.5million

Note:*2. The electrical endurance for the UQ-AX2 (KR) type auxiliary
    contact block is 0.25 million.

 Auxiliary contact block Table 3.6.4


For non-reversing
type and for For reversing type
Use
reversing type left right side
side
Model name UQ-AX2 UQ-AX2KR
Applicable SD-Q11.SD-QR11 SD-QR11
contactor MSOD-Q11 MSOD-QR11
/starter MSOD-QR11

61
■ Contact Arrangement & Wiring Diagram Table 3.6.5
Non-reversing
Type SD-Q11 SD-Q12.Q19
Aux. 1 NO Aux. 1 NO 1 NC

1/L1 3/L2 5/L3 13 A1(+) 13 1/L1 3/L2 5/L3 21 A1(+)

Standard
2/T1 4/T2 6/T3 14 A2(-) 14 2/T1 4/T2 6/T3 22 A2(-)

Aux. 1 NC Aux. 2 NO

1/L1 3/L2 5/L3 21 A1(+) 13 1/L1 3/L2 5/L3 23 A1(+)

Special
2/T1 4/T2 6/T3 22 A2(-) 14 2/T1 4/T2 6/T3 24 A2(-)

Reversing
Type SD-QR11 SD-QR12 SD-QR19
(+) (+) (-) (-) (+) (+) (-) (-) (-) (+) (+)

1/L1 3/L2 5/L3 21 21 1/L1 3/L2 5/L3 A2(-) 21 1/L1 3/L2 5/L3 13 13 1/L1 3/L2 5/L3 21 A1(+)
A1(+) A2(-) 13 1/L1 3/L2 5/L3 21 21 1/L1 3/L2 5/L3 13
A1(+) A2(-)
Standard
A1(+) 22 2/T1 4/T2 6/T3 14 14 2/T1 4/T2 6/T3 22 A2(-)
A2(-) A1(+) 14 2/T1 4/T2 6/T3 22 A2(-) A1(+)
2/T1 4/T2 6/T3 22 22 2/T1 4/T2 6/T3 22 2/T1 4/T2 6/T3 14

(-)

■ Outline Dimensions
P screws Mtg.hole for M4 screws Mounting rail Mtg.hole for M4 screws
c

M3.5 screws (35mm) Mounting rail


P screws M3.5 screws
(35mm)
c
A
a

A
a

b d e b d e
B 10 C
B 10 C

Fig.1 SD-Q type Fig.2 SD-QR type

 Magnetic contactors and magnetic motor starters (mm)


Dimensions Mass Reference
Type
A B C a b c d e P [kg] drawing
SD-Q11 51 45 66.5 40 35 4 5 8.5 M3.5 0.19
reversing

Fig.1
Non-

SD-Q12 52 56 67.5 40 35 5 5 8.5 M3.5 0.21 Fig.1


SD-Q19 58 66 78 50 55 4 5.5 9 M4 0.34 Fig.1
Reversing

SD-QR11 59 90 66.5 40 80 11 5 8.5 M3.5 0.42 Fig.2


SD-QR12 59 112 67.5 40 80 11 16 8.5 M3.5 0.46 Fig.2
SD-QR19 79.5 133 77.5 50 110 22 11.5 9 M4 0.72 Fig.2

62
Series UN-SY

3.7 DC Interface Modules

The MITSUBISHI type UN-SY interface module is an optional unit for S-N series contactors or
SR-N series relays, controlled by the transistor output of a programmable controller.

■ Features
 Easy mounting on the Type S-N10 to S-N65 contactors and SR-N series relays.
 Separate mounting type for the Type S-N80 to S-N400 contactors.
S-N21CX+UN-SY21CX  Relay or solid state output versions are available.

Type Designation
UN-SY 1 2 CX

APPLICABLE CONTACTOR OR RELAY OUTPUT FINGER PROTECTION


UN-SY2 S-N10 to N35, SR-N4 1 Solid state relay output None Not provided
UN-SY3 S-N50 to N65 2 Relay output CX Provided
UN-SY1 S-N80 to N400
Note: Suffix “CX” is available only for UN-SY21 or SY22.

■ Specifications Table 3.7.1


Type UN-SY21(CX) UN-SY31 UN-SY11 UN-SY22(CX) UN-SY32 UN-SY12
Output Solid state relay Relay
Direct mounting S-N10 to N35 S-N50, N65 S-N10 to N35 S-N50, N65
to contactor or S-N18, N28, N38, – S-N18, N28, N38, –
Applicable Type of relay N48 N48
contactor or relay
Separate – –
– S-N80 to N400 – S-N80 to N400
mounting

Rated control voltage 24Vdc 24Vdc


Permissible voltage tolerance 80% to 110% of rated control voltage
Input

Min. working voltage 18Vdc 18Vdc


Max. breaking voltage 4Vdc 1Vdc
Power consumption 0.4W 0.24W
Rated voltage 100Vac to 240Vac 50/60Hz
Rated operating current 0.5A (category AC11)
Output

Responce time 11ms or less 10ms or less


OFF-state leakage current 3mA/240Vac –
Mechanical life – 5 million operations
Electrical life – 1 million operations
Ambient temperature –10 to 55°C

63
■ Connection
(1) Solid State Output (2) Relay Output
DC interface module DC interface module
100Vac 100Vac
to to
240Vac A1 A2 240Vac A1 A2

MC MC
A2(A3) A2(A3)
A1 A1

D2(-) D2(-)
Magnetic contactor Coil Magnetic contactor
Contactor reray Contactor reray
Transistor Transistor
24Vdc 24Vdc
D1(+) D1(+)

UN-SY21(CX) UN-SY22(CX)

Type UN-SY21(CX) Type UN-SY22(CX)

100Vac DC interface module 100Vac


DC interface module to
to
240Vac 240Vac
A2 A3 A2
A3

MC MC

A1 A1 A1
A1

D2(–) D2(-)
Magnetic contactor Coil Magnetic contactor
Contactor reray Contactor reray
Transistor Transistor
24Vdc 24Vdc
D1(+) D1(+)

Type UN-SY11/31 Type UN-SY12/32

■ Mounting
 Direct mounting Type S-N10 to S-N65 and SR-N4
Remove the coil terminal screw from the contactor or relay, then slide the tab on the interface module to the groove on the
contactor or relay. Fasten the connecting conductor with the coil terminal screw.
 Separate mounting Type S-N80 to S-N400
Mount the interface module (UN-SY11/12) with screw on a panel as follows.

■ Outline Dimensions
Type Number UN-SY21/22(CX) UN-SY-31/32 UN-SY11/12
Module 10 8
Outline 44 5
dimensions
8 21.5
23

30

30.5
39

44 30.5
39 M3.5 screw 2.5
3

39
39 f4.5 mtg. hole
42

Coupling outline Mtg. hole layout for separate mounting


Overall
Mounting
dimensions
24.5
24.5

24.5

M4 screw 3.2 hole


(A2) (A1) (A2) (A1) (A2) (A1)
20
30

S-N10 S-N20
78(79)

S-N11
81(89)

78

S-N21
SR-N4 S-N25 S-N12
SR-N8 SR-N5 34
S-N35
S-N18 S-N38 44
S-N28 S-N48

43 63(75/154) 53

64
4. RELAYS Series SR-N

4.1 Contactor Relays

The MITSUBISHI series SR-N contactor relays are specially designed for use in low voltage control
circuit applications. Series SR-N have many superior features.
■ Features
 High reliability: By adopting bifurcated moving contacts and by improving the shape of the
contacts, contact performance has been made more reliable than ever.
 Long life  Can be mounted on 35mm rail  Dust-proof construction
 Easily visible coil ratings  Easy wiring (self-rising terminal screws)
 Various accessories common with the series S-N contactors
(Head-and side clip-on type additional aux. contact blocks, surge absorbers, safety covers)
SR-N4  Finger protected types are available (DIN 57106/VDE 0106 Part 100)

Type Designation
 Standard types
SR – N4 LC * AC200V * 2A2B

CONTROL TYPE TYPE COIL VOLTAGE2 CONTACT ARRANGEMENT (CODE)


SR AC operated * Standard type See Table 4.1.1(2) See Table 4.1.1(1)
SRD DC operated JH Big capacity type
SRL1 AC & Latched LC With overlap contact type
SRLD1 DC & Latched CX3 With finger protection cover

Notes: 1. For latched type relays, JH and LC types cannot be available.


2. When ordering the latched type relays, please specify the closing coil and tripping coil voltage.
ex: SRL-N4*MC-AC200V* MT-AC100V* 4A
closing coil tripping coil
3. Only suffix “CX” is admitted to make any combination with other tabulated suffixes.

Note: Mark * indicates a blank space.

65
4.1.1 Specifications
■ Rating and characteristics Table 4.1.1 (1)

Type SR- N4LC (CX)


N4 (CX) N4JH (CX)
SRD-
Available contact arrangements (code) 4NO (4A) 4NO (4A) 4NO (4A)
3NO+1NC (3A1B) 2NO+2NC (2A2B) 2NO+2NC (2A2B)
2NO+2NC (2A2B)
Rated insulation voltage V 660
Conventional free air thermal current lth A 16 20 16
Rated operating current 110VAC A 6 10 6 (3)2
Category AC-15 230VAC A 5 10 5 (3)2
(coil load) 440VAC A 3 5 3 (3)2
550VAC A 3 4 3 (3)2
110VAC A 16 20 16
Category AC-12 230VAC A 12 16 12
(resistive load) 440VAC A 5 10 5
550VAC A 5 10 5
24VDC A 5 3
Category DC-13 48VDC A 3 2
(large coil load) 110VDC A 0.8(2)1 0.5
220VDC A 0.2(0.8)1 0.1
24VDC A 8 5
48VDC A 3 2
Category DC-14
110VDC A 2(4)1 1
220VDC A 0.4(1)1 0.2
24VDC A 10 8
Category DC-12 48VDC A 8 5
(resistive load) 110VDC A 5(8)1 3
220VDC A 1(3)1 0.5
Mechanical life Operations 10 million (latched type 1 million)
Electrical life Operations 0.5 million
Permissible ambient temperature/humidity °C/%RH -25 to +55/45 to 85
Coil consumption Inrush VA 60
Ac-operated Sealed VA 10
Watts W 3
DC-operated Watts W 7
Coil voltage tolerance times 0.85 to 1.1 (rated coil voltage)
Operating time Make ms 15
(average) Break ms 10 ( AC
operated )
50 DC
(
10 operated )
operations
Switching frequency 1,800
/hour
Vibration resistance 10-55Hz m/s2 19.6
Shock resistance 10 msec. half sine wave m/s2 49
Conductor size mm2 1.0 to 2.5
Notes: 1. Parenthesized rated operating current is for switching the load in 2-pole series connection.
2. Parenthesized rated operating current is for switching of NC contact.

■ Coil voltage Table 4.1.1 (2)


Coil Rated voltage (AC) Coil Rated voltage (AC) Coil Rated
designation 50Hz 60Hz designation 50Hz 60Hz designation voltage (DC)

AC12V 12V 12V AC220V 208-220V 220V DC24V 24VDC


AC24V 24V 24V AC230V 220-240V 230-240V DC48V 48VDC
AC48V 48-50V 48-50V AC260V 240-260V 260-280V DC100V 100VDC
AC100V 100V 100-110V AC380V 346-380V 380V DC110V 110VDC
AC120V 110-120V 115-120V AC400V 380-415V 400-440V DC125V 120-125VDC
AC127V 125-127V 127V AC440V 415-440V 460-480V DC200V 200VDC
AC200V 200V 200-220V AC500V 500V 500-550V DC220V 220VDC
Note: AC operated coils are the same as those of S-N10 etc., and DC operated coils are the same as those of SD-N11 etc.

66
4.1.2 Auxiliary Contact Blocks

Type Designation
 Front clip-on types
UN-AX 4 CX * 2A2B [FOR LOW SIGNAL LEVEL] UN-LL22 CX

POLES FINGER PROTECTION CONTACT FINGER PROTECTION


4 4 pole None Not provided ARRANGEMENTS None Not provided
2 2 pole CX Provided See Table 4.1.2(1) CX Provided
 Side clip-on types
UN-AX11 CX

FINGER PROTECTION
None Not provided
CX Provided

Note: Mark * indicates a blank space.

■ Ratings and characteristics Table 4.1.2 (1)

Type UN- AX2 (CX) AX4 (CX) AX11(CX) LL22 (CX)

2NO 4NO
1NO+1NC 3NO+1NC 1NO+1NC 1NO+1NC1
Applicable contact arrangements INO+INC
2NC 2NO+2NC [Standard] [Low level]

Rated insulation voltage V 690 250


Conventional free air thermal current lth A 16 1
Rated 110VAC A 6 240VAC 20mA
Category AC-15 (COSj≧0.95)
operating 220VAC A 5
(coil load) 48VDC 100mA
current 440VAC A 3
(L/R≦1msec)
48VDC A 3 Minimum
Category DC-13 A 0.8
110VDC operating current
(large coil load) A 0.2
220VDC 5VDC 5mA
Mechanical life operations 10 million 2.5 million
Electrical life operations 0.5 million 0.5 million
Permissible ambient temperature/humidity °C/%RH –25 to +55/45 to 85
operations
Switching frequency 1,800
/hour
Conductor size mm 2 1.0 to 2.5
Note: 1. Contact reliability may be decreased if it is operated more than 1 million operations

■ Selection guide & contact arrangements Table 4.1.2 (2)

UN-AX2 2A UN-AX2 1A1B 51 63 UN-AX2 2B UN-LL22


53 63 51 61
53 63 71 81

Front 2NO 54 64 1NO+1NC 52 64 2NC 52 62


clip-on 54 64 72 82
types UN-AX4 4A UN-AX4 3A1B UN-AX4 2A2B standard
53 63 73 83 53 61 73 83 53 61 71 83
1NO+1NC

low level
1NO+1NC
4NO 54 64 74 84 3NO+1NC 54 62 74 84 2NO+2NC 54 62 72 84

UN-AX11
53 61 83 71

Side
clip-on
types 54 62 84 72

When mount on left side When mount on right side


1NO+INC

Note: Front clip-on types and side clip-on contact block should not be mounted both.

67
4.1.3 Contact Arrangements of Contactor Relay Table 4.1.3
With standard contacts
4NO 3NO 2NO
+ +
A2 A1 13 23 33 43 1NC A2 A1 13 21 33 43 2NC A2 A1 13 21 31 43

14 24 34 44 14 22 34 44 14 22 32 44

SR-N4(CX)AC……V 4A SR-N4(CX)AC……V 3A1B SR-N4(CX)AC……V 2A2B


SRD-N4(CX)DC……V 4A SRD-N4(CX)DC……V 3A1B SRD-N4(CX)DC……V 2A2B

With big capacity contacts


4NO 2NO
+
A2 A1 13 23 33 43 2NC A2 A1 13 21 31 43

14 24 34 44 14 22 32 44

SR-N4JH(CX)AC……V 4A SR-N4JH(CX)AC……V 2A2B


SRD-N4JH(CX)DC……V 4A SRD-N4JH(CX)DC……V 2A2B

With late break contacts


3NO 2NO
+ A2 A1 13 21 33 43
+ A2 A1 13 21 31 43
1NC 2NC
(late break) (late break)

14 22 34 44 14 22 32 44

SR-N4LC(CX)AC……V 3A1B SR-N4LC(CX)AC……V 2A2B


SRD-N4LC(CX)DC……V 3A1B SRD-N4LC(CX)DC……V 2A2B

With mechanical latching


4NO 3NO 2NO
CLOSING CLOSING CLOSING
+ +
1NC A2 A1 E1
2NC
A2 A1 13 23 33 43 55 E1 13 21 33 43 55 A2 A1 13 21 31 43 55 E1
TRIPPING

TRIPPING
TRIPPING

MC MC MC

14 24 34 44 56 MT 14 22 34 44 56 MT 14 22 32 44 56 MT

E2 E2 E2
SRL-N4 AC……V 4A SRL-N4 AC……V 3A1B SRL-N4 AC……V 2A2B
SRLD-N4 DC……V 4A SRLD-N4 DC……V 3A1B SRLD-N4 DC……V 2A2B

4.1.4 Spare Coils & Accessories


Spare coils and accessories are common with the series S-N contactors.
 Spare coils ......................................................................................... See Table 1.8.1(except for Type SRL(D)latched relays)
 Surge absorbers(suppressors) .......................................................................................................................... See Table 1.8.6

4.1.5 Outline Dimensions


2 mtg holes for M4 screws
M3.5 screws  Key to Dimensions
Mass
Model C1 C2
19

Mounting rail (kg)


(35mm )

SR-N4(CX) 78 106 0.3


78
50

SRD-N4(CX) 110 138 0.62

SRL-N4(CX)
4
SRLD-N4(CX) 134 – 0.45
4.5 35
10
13.5 43 C1
70 C2
(with side clip-on aux. (with front clip-on aux.
contact blocks) contact block)

Note: Front clip-on and side clip-on contact block should not be mounted both.

68
Series SRE
4.2 Voltage Detection Relays

The MITSUBISHI series SRE relays are specially designed for voltage sensing.The type SRE-A
is specially designed for the detection of undervoltage or overvoltage conditions.The type SRE-K
is particularly useful for the switching of automatic transfer panels.The type SRE-K can detect
undervoltage by simply connecting to the power-source terminals.

SRE-AA
■ Features
 High sensibility  High reliability  Easy wiring
 High surge tolerance  Wide detective voltage range
Type Designation
SRE-A AU – 050 D SRE-K T – AC120V

OPERATION VOLTAGE DETECTABLE DETECTABLE SETTING VOLTAGE OPERATION VOLTAGE


VOLTAGE RANGE CURRENT TYPE Drop-out voltage See Table 4.2.1
A 100-110/200-220VAC *
AU 115-120/230-240VAC See Table 4.2.1 D DC T Pick-up voltage
A AC

■ Specifications
 Selection table Table 4.2.1

Detectable Permissible Input Operation


Type input voltage
voltage range impedance voltage
(continuous)
0P5D 0.1-0.5VDC ± 100VDC 20KΩ
1P5D 0.3-1.5VDC ± 100VDC 50KΩ
Type SRE-AA
005D 1- 5VDC ± 150VDC 100KΩ
100-110V 50/60Hz
015D 3-15VDC ± 150VDC 100KΩ
200-220V
SRE-AA 050D 10-50VDC ± 200VDC 500KΩ
SRE-AAU 150D 30-150VDC ± 300VDC 800KΩ
250D 50-250VDC ± 300VDC 800KΩ Type SRE-AAU
015A 3-15VAC 150VAC 100KΩ 115-120V
050A 10-50VAC 200VAC 500KΩ 50/60Hz
230-240V
150A 30-150VAC 300VAC 800KΩ
250A 50-250VAC 300VAC 800KΩ
AC100V 75-105VAC 120VAC 100-110V,50/60Hz
AC120V 90-125VAC 132VAC Input 115-120V,50/60Hz
AC200V 150-210VAC 240VAC 1.8VA 200-220V,50/60Hz
SRE-K AC240V 180-250VAC 264VAC 230-240V,50/60Hz
DC 12V 9-12.5VDC 14VDC 12VDC
Input
DC 24V 18-25VDC 28VDC 1.7W 24VDC
DC100V 75-105VDC 120VDC 100VDC
AC100V 80-115VAC 120VAC 100-110V,50/60Hz
AC120V 95-130VAC 132VAC Input 115-120V,50/60Hz
1.8VA 200-220V,50/60Hz
AC200V 160-230VAC 240VAC
SRE-KT AC240V 190-260VAC 264VAC 230-240V,50/60Hz
DC 12V 10-14VDC 14VDC 12VDC
Input
DC 24V 20-28VDC 28VDC 24VDC
1.7W
DC100V 80-115VDC 120VDC 100VDC
Note: The type SRE-A D, for DC detection can be used for full-wave rectification voltage.
 Operating Condition Fig 4.2.1
YPE:SRE-AA/AAU,SRE-KT TYPE:SRE-K

Output Output
relay relay

Setting value Setting value


V1 V2

Drop-out Pick-up Drop-out Pick-up

OFF ON Voltage OFF ON Voltage


V1 is about 90% of the setting value. V2 is about 110% of the setting value.

69
 Ratings and characteristics Table 4.2.2
Type SRE-A SRE-K
Output contact arrangement 1 changeover
Conventional free air thermal current Ith A 3
Category 110VAC A 1.5
Rated operating AC-15 220VAC A 1.0
current of output
contact Category 24VDC A 1.0
DC-13 110VDC A 0.2
Repetitive operation1 % ±1
Accuracy Control voltage fluctuation % ±1.5 –
Ambient temperature change % ±2.5
Response time(at 150% of the rated voltage) msec 100 to 200
Mechanical life operations 10 million
Electrical life operations 0.25 million
Permissible ambient temperature/humidity °C/ %RH –10 to +55/max. 85
Power consumption VA 2
Operation voltage tolerance (ambient temperature 40°C) % 85 to 110 –
Withstand voltage VAC 1500 [1 minute]
Insulation resistance (500VDC insulation tester) MΩ min. 100
Vibration resistance 10 to 55Hz m/s2 19.6
Shock resistance 10msec half sine wave m/s2 98

Note: 1. Repetitive operation accuracy (%) = ± 1 × max. measurement – min. measurement × 100.
2 max. scale value

■ Wiring precautions Fig 4.2.2

Type SRE-A Type SRE-K

V2 7 8 7 8
Power V1 5 6 (~ ,+) 5 6

Output
source Power source
3 4 & detection
Common (~ ,–) 3 4
( ~ ,+) 1 2 1 2
Detection
( ~ ,–)

SRE-AA SRE-AAU
V1-Common AC100 ~ 110V AC115 ~ 120V
V2-Common AC200 ~ 220V AC230 ~ 240V

■ Outline dimensions

M3.5×8 93(terminal height)


self-lifting terminal
52

60

30 2 10
2-4.8×6.8
mtg holes 16 107
43 (for M4 screws)

70
Series UA-DL
4.3 Re-Starting Relay

The MITSUBISHI series UA-DL re-starting relays are specially designed for automatic re-starting.
When the power recovers from an instantaneous power failure or voltage drop the UA-DL re-starts
the stopped equipment or machines.
■ Features
 Easy installation and easy wiring  Compact design
 Versatility of the control voltage (100VAC & 200VAC)
UA-DL2 with PF-08RM  Indicator lamp is provided.
 Selectable permissible max. power failure time (1sec. & 2sec.).

Type Designation

UA-DL2 * AC100/200V SOCKETS type: PF-08RM/08TM


See page 66
CONTROL VOLTAGE

Ordering designation Rated control


voltage (50/60Hz)
AC100/200V 100-110/200-220VAC
AC120V 100-110/110-120VAC
AC240V 200-220/220-240VAC
Notes: 1. DC control voltage type is not available.
2. Mark* indicates a blank space.

■ Specifications
 Ratings & characteristics Table 4.3.1

Output contact arrangement 1 NO

Rated operating current Category 110VAC A 1.5


of output contact AC-15 220VAC A 1.0

Selection of permissible max. power failure time sec. 1 and 2

Set permissible power failure time % –20 to +50 (when 100VAC/200VAC is applied)

Accuracy Control voltage fluctuation % ±35

Ambient temperature change % ±25

Minimum energizing time sec. 5

Electrical life operations 0.5 million

Permissible ambient temperature/humidity °C/ %RH –10 to +55/max. 85

Control voltage tolerance % 85 to 110 (rated control voltage)

Power consumption VA 3
2
Vibration resistance 10 to 55Hz m/s 19.6

Shock resistance 10 msec. half sine wave m/s2 98

Withstand voltage VAC 2000 (50/60Hz 1min.)

Insulation resistance MΩ min. 100

Note: 1. When shipping, permissible power failure is set to 2 secs.


When the required re-setting time is 1 sec., please turn the time setting dial to left until it stops.
When you want the permissible power failure time longer than 2 sec., please consult with MITSUBISHI.

71
 Connection diagrams Fig. 4.3.1 * Selection table of terminals Table 4.3.2
UA-DL UA-DL Control voltage
AC100/200V AC120V AC240V
1 Terminal No.
5
OFF ON MC
5 6 2 100-110VAC 100-110VAC 200-220VAC

ON MC OFF 1 7 200-220VAC 110-120VAC 220-240VAC


~ MC
6

3
~ MC
3
1. The terminal (2) and (7) connections differ according to the
2 or 7 +
2 or 7 + control circuit voltage. Connect according to the circuit voltage.
THR THR (Refer to conffarm, above Table 4.3.2)
2. The external switch (OFF push-button switch in connection
diagram) which issues the OFF command requires an OFF time
Connection of control switch differs in the above of 50ms or more.
2 connection diagrams. 3. When using a relay contact instead of the push-button switch
(OFF), use a contact that does not open when the power fails. If
the push-button switch (OFF) section opens, UA-DL2 will turn
OFF, and the magnetic contactor will not restart.
4. An electrolytic capacitor is used, so periodically check the
operation time.

 Operation characteristics Fig. 4.3.2

Normal condition Within permissible Over permissible


power failure time power failure time
Control switch ON

Control switch OFF

Circuit voltage

Out-put of UA-DL

Contactor

T : permissible max. power failure time (set)


T T

■ Outline Dimensions
50

Note: 2 pcs of locking springs are enclosed in the each package of


UA-DL.
40 58.3 14

UA-DL2 (Mass: 0.1kg)

M3.5 screws 4 M3.5 screws


Mounting rail 2-f4.5
(35mm ) mtg. holes
6 5 4 3 6 5 4 3
2-f4.5
(min 24)

mtg. holes 2-f4.5


41
61

mtg. holes
50~52
56
71

7 8 1 2

7 8 1 2
33 15
2.5

40 22 10
33~35
22.5 22
34~35
23.5
43.5
PF-08RM (Mass: 0.05kg)
PF-08TM (Mass: 0.05kg)
72
4.4 Solid State Time Delay Relays Series SRS-H

The MITSUBISHI series SRS-H solid state time delay relays are specially designed for high
accuracy and easy mounting.

■ Features
 High accuracy  Compact design  High reliability
 Easy mounting (for direct panel mounting or mounting on 35mm rail)
 With finger protection (terminal cover) model is available
 1 delayed & 1 instantaneous changeover contact for ON-delay relay.
SRS-HNPS

Type Designation
ON-delay : SRS-H NP S – AC200V

DELAYING TIME CONTROL VOLTAGE


S 3 sec.-30sec. See Table 4.4.2

■ Specifications
 Time delay selection Table 4.4.1  Control voltages Table 4.4.2
Relay type Adjustable time range Contacts Ordering
Rated voltage
designation
1 delayed and
ON-delay SRS-HNPS 3 sec. - 30 sec. 1 instantaneous AC100V 100-120V 50/60Hz
changeover
AC200V 200-240V 50/60Hz

AC400V 380-440V 50/60Hz

 Rating & characteristics Table 4.4.3


Type ON-delay  Internal wiring
Conventional free air thermal current A 2
( + ) INPUT ( – )
Rated
Category 120VAC A 1.5 ~ ~
AC-15 240VAC A 1
operating (A1) (21)
440VAC A 0.3
current (15) (22)

Repetitive operation % ±0.5


Accuracy Control voltage fluctuation % ±1
Ambient temperature change % ±5 (16) (24)

Minimum pause time msec. 100 (18) (A2)

Mechanical life operations 10 million ON-delay

Electrical life operations 0.1 million


Permissible ambient temperature °C –10 to 55
Permissible ambient relative humidity %RH 45 to 80 ■ Outline Dimensions
Control voltage tolerance % 85 to 110 (rated control voltage) Mounting rail
(35mm ) 2-M4
Power Control 5 (AC100V/AC200V) 6 mtg. holes
AC VA M3.5 screws
consumption voltage 10 (AC400V)

Vibration resistance 10-55Hz m/s2 19.6


62
75

35

Shock resistance 10msec half sine wave m/s2 49


Withstand voltage [live parts to ground] VAC 2000 (1 min.)
22.5 97 3.5
5 12

SRS-HNPS (Mass: 0.15kg)

73
4.5 Pneumatic Time Delay Relays Series SRT-N

The MITSUBISHI series SRT pneumatic time delay relays are designed for general purpose time
delaying,such as star-delta starters and transfer panels.

■ Features
 Easy delaying time adjustment  Can be mounted on 35mm rail
 High contact reliability:By using bifurcated moving contacts,contact performance has been made
more reliable than ever.
 Finger protected types are available
 Manual testing
 2 delayed contacts(1NO1NC)&4 instantaneous contacts(2NO2NC)
SRT-NN
Type Designation
SRT D – NN CX * DC100V

CONTROL CIRCUIT TYPE OF DELAY FINGER PROTECTION CONTROL COIL VOLTAGE


* AC NN ON None Not provided Same as page 19,
Table 1.5.1,Table 1.5.3
D DC NF OFF CX Provided

Note: Mark * indicates a blank space.

■ Specifications ■ Contact arrangement


 Ratings & characteristics Table 4.5.1 Table 4.5.2
Adjustable delay time range sec. 0.1 to 60 ON-delay OFF-delay
Type of contacts – Delayed Instantaneous 67 55 67 55
(37) (25) (37) (25)
Conventional free air thermal current Ith A 10 16
Rated category 110VAC A 5 6
operating 220VAC A 3 5
current 1 3 68 56 68 56
AC-15 440VAC A (38) (26)
(38) (26)
550VAC A 1 3
A1/a 13 21 31 43 A1/a 13 21 31 43
category 110VAC A 6 16
220VAC A 4 12
AC-12 440VAC A 1.5 5
550VAC A 1.5 5 A2/b 14 22 32 44 A2/b 14 22 32 44
category 24VDC A 1 5
48VDC A 0.5 3 SRT-NN(CX)AC ......... V SRT-NF(CX)AC ......... V
DC-13 110VDC A 0.3 0.8
220VDC A 0.15 0.2 SRTD-NN(CX)DC ...... V STRD-NF(CX)DC ...... V
category 24VDC A 2 10
48VDC A 1 8 Notes: 1. 13-14,43-44 Instantaneous NO contacts
DC-12 110VDC A 0.6 5 23-24,33-34 Instantaneous NC contacts
220VDC A 0.3 1 55-56,65-66 Delayed NC contacts
Rated insulation voltage VAC 660 57-58,67-68 Delayed NO contacts
Mechanical life operations 1 million 2. Aux. contact block should not be mounted.
Electrical life operations 1 million 0.5 million
Repeat accuracy % ±10
Min. pause time msec. 500  Delay time characteristics
Min. energizing time AC operated msec. 15 Fig. 4.5.1
DC operated msec. 30
120
Permissible ambient temperature °C –5 to 55
Control coil voltage tolerance % 85 to 110
Make and break capacity AC times 11
90
Time delay (sec.)

(at rated operating current) DC times 2


Average AC Make msec. – 11
operating operated Break msec. 10
times DC Make msec. 45 60

operated Break msec. 10
Coil AC Inrush VA 50
consumption operated Sealed VA 10 30
DC operated W 7
Switching frequency operations 1,800
/hour 3
Vibration resistance 10-55Hz m/s2 19.6 0 90 180 270 300 330
Shock resistance 10msec. half sine wave m/s2 49 Dial rotation (degress)
Conductor size mm2 1.0 to 2.5

74
Pneumatic Time Delay Modules

Type UA-TR pneumatic time delay modules are designed for attachment to series S-K
contactors and SR-K contactor relays.

Type Designation
UN – TR4 AN CX

TYPE OF DELAY FINGER PROTECTION


AN ON None Not provided

CX Provided
UN-TR4AN

 Applicable contactor and relay selection Table 4.5.3


Type Type of delay Applicable contactors and relays
S-N10(CX),N11(CX),N18(CX)
AC operated
SR-N4( )(CX)
UN-TR4AN(CX) ON delay
SD-N11(CX)
DC operated
SRD-N4( )(CX)
Note: When this module is mounted, aux. contact block should not be mounted.

Contact arrangement  Ratings & characteristics


ON-delay ........................... See delayed contacts of Table 4.5.1
 Delay time characteristics
67 55 Note: 55-56 Delayed NC
contacts ................................................................... See Fig.4.5.1
67-68 Delayed NO
contacts

68 56
 Key to Dimensions
UN-TR4AN(CX)
Type A B Mass(kg)
SRT-NN(CX),
121.5 – 0.36
-NF(CX)
SRTD-NN(CX),
153.5 – 0.68
-NF(CX)
Outline Dimensions UN-TR4AN(CX) – 48.5 0.06

2-mtg. holes for Adjustment dial


M4 screws M3.5 screws Mounting rail
(35mm ) M3.5 screws Manual test button
78
50

45

4
45
9

10 1 B
35 A
4.5
45 1

75
5. STAR-DELTA STARTERS Series EYD-N

The MITSUBISHI series EYD-N star-delta starters are generally suitable for squirrel-cage
motors of 4kW to 250kW which can be started at no-load or reduced load during starting,
the motor is star-connected, reducing current and torque to 1/3 of direct-on-line starting
values.
So the voltage drop, due to starting current, can be reduced.Series EYD-N star-delta
starters are the simplest and cheapest methods of all reduced-voltage starting methods.
Series EYD-N star-delta starters comprise three contactors (for running, delta operation and
star operation), one thermal overload relay and one time-delay relay (series SRS-H, solid-
EYD-N35 state time delay relay). The star-delta changeover time is set to 10 sec when shipped,but is
easily adjustable from 3 sec. to 30 sec. The O.L.R.heater is set at the heater designation
value (following) when shipped, and be sure to re-set to suit the motor full-load current in
the field.
Type Designation
EYD – N35 PB KP * 29A * 440V * AC200V

TYPE FRAME SIZE HEATER DESIGNATION MAIN CIRCUIT CONTROL VOLTAGE


EYD enclosed See Table 5.1 See Table 5.1 VOLTAGE See Table 5.2.2
EYDO open
P/B & LAMP THERMAL OVER LOAD RELAY TYPE

* None * 2-heater elements


PB Pushbutton KP 3-heater elements & phase failure protection
WL Indicator lamp

Note: Mark * indicates a blank space

5.1 Selection Table Table 5.1


Rated 3-phase motor capacity Star-delta starter Heater Setting Components1
220-240VAC 380-440VAC Type designation range Running & delta Star Thermal
kW HP kW HP EYD(O)– A A contactors contactor O.L.R
11 15 18.5 25 N20(KP) 35 30~40 S-N20 S-N20 TH-N60(KP)
18.5 25 30 40 N35(KP) 54 43~65 S-N35 S-N20 TH-N60(KP)
22 30 45 60 N50(KP) 82 65~100 S-N50 S-N20 TH-N120(KP)
30 40 55 75 N65(KP) 105 85~125 S-N65 S-N25 TH-N120TA(KP)
45 60 75 100 N80(KP) 125 100~150 S-N80 S-N25 TH-N120TA(KP)
– – 90 125 150 120~180
N95(KP)
55 75 – – 180 140~220 S-N95 S-N35 TH-N220HZ(KP)
62 85 110 150 N125(KP) 180 140~220 S-N125 S-N50 TH-N220HZ(KP)
75 100 132 180 N150(KP) 210 170~250 S-N150 S-N50 TH-N220HZ(KP)
110 150 220 300 N220(KP) 330 260~400 S-N220 S-N65 TH-N400HZ(KP)
160 220 250 340 N300(KP) 500 400~600 S-N300 S-N125 TH-N600(KP)2

Notes: 1. Time delay relays are all SRS-HNPS.


2. TH-N600(KP)and current transformer,CW-15L or CW-15LM(by MITSUBISHI).

76
5.2 Specifications
 Characteristics Table 5.2.1
Item Frame size N20 N35 N50 N65 N80 N95 N125 N150 N220 N300
Mechanical life operations 1 million
Electrical life operations 0.25 million
Permissible and temp. °C –25 to 55
Coil consumption
At star connection VA 35(40) 33(38) 40(45) 38(43) 41(46) 49(54) 65(70) 79(84)
At delta connection VA 35(40) 31(36) 45(50) 45(50) 51(56) 53(57) 85(90) 105(110)
Coil voltage tolerance % 85 to 110(rated coil voltage)
Couductor size
Line side mm2 4-16 4-25 6-35 10-50 10-70 16-95 16-120 16-150 16-210 70-300
Motor side mm2 2.5-6 2.5-10 4-25 4-25 6-35 6-35 10-70 16-95 16-150 35-200
Control terminal mm2 1-2.5 1-2.5 1-2.5 1-2.5 1-2.5 1-2.5 1-2.5 1-2.5 1-2.5 1-2.5

Notes: 1. The value in the bracket “( )” indicates the coil consumption for control voltage “380~440V”.

 Connection
MCD

MCCB(not supplied)

THR
R MCM U X MCS

S V Y
M
T W Z

RT MCD
PB THR
R1 MCM S1
4 3 RT
(OFF) (A1)
(ON) RT
(A2)
RT MCS
MCD
MCM MCD
MCS
 Control Voltage
Table 5.2.2
EYD(O)-N20(KP)to N95(KP) EYD(O)-N125(KP)to N300(KP)

Control voltage Rated voltage Control voltage Rated voltage

designation 50Hz 60Hz designation 50Hz/60Hz

AC100V 100V 100-110V AC100V 100-120V

AC120V 110-120V 115-120V AC200V 200-240V

AC220V 208-220V 220V AC400V 380-440V

AC230V 220-240V 230-240V


AC380V 380V 380V
AC400V 380-415V 400-440V
AC415V 380-415V 400-440V
AC440V 415-440V 460-480V

77
50(N220 only)
5.3 Outline Dimensions
5.3.1 Open Type RT
RT MCS
OLR OLR

BA
BA

B
B
MCM MCD MCS MCM MCD

TE TE
AA AA

15

15
4mtg. holes for A
4mtg. holes for
M screws M screws A

Type EYDO-N20, N35

C
E
OLR
TERMINAL
MCS t
CT CT RT
Type EYDO-N50~N220
BA

 Dimensions
B

Table 5.3.1
MCM MCD
Mass
Type A B C AA BA E M t (kg)
TE
EYDO-N20 230 220 114 200 200 12 M6 2.3 4
AA EYDO-N35 270 270 114 250 250 12 M6 2.3 5
4mtg. holes for
M screws A EYDO-N50 270 270 118 250 250 12 M6 2.3 5.5
EYDO-N65 270 270 118 250 250 12 M6 2.3 5.5
EYDO-N80 270 270 140 250 250 12 M6 2.3 7
EYDO-N95 380 430 180 350 400 15 M8 3.2 11
C

EYDO-N125 380 430 180 350 400 15 M8 3.2 13


E

EYDO-N150 380 430 189 350 400 15 M8 3.2 14


t
EYDO-N220 380 430 189 350 400 15 M8 3.2 21
EYDO-N300 600 600 210 550 550 15 M12 3.2 42
Type EYDO-N300, N400 EYDO-N400 600 600 210 550 550 15 M12 3.2 42

5.3.2 Enclosed Type


fP Hole with rubber bushing

150×450
SQUARE HOLE
(WITH COVER)
75
BA
B

NP
1240

AA
4mtg. holes for 14 A
M screws NP
40
C
E

650
D D 4mtg. holes for
20

2-fPA Holes with f28 Hole with M12 screws


rubber bushings rubber bushing

150×450SQUARE HOLE
150
330
380

Type EYD-N20~N220 (WITH COVER)


190

 Dimensions Table 5.3.2 450


25

600
Mass
Type A B C AA BA D E M P PA (kg)
EYD-N20 260 360 165 200 300 75 60 M6 40 28 7
Type EYD-N300, N400 (Mass 120kg)
EYD-N35 310 460 165 250 400 75 60 M8 52 40 9
EYD-N50 310 460 165 250 400 75 60 M8 52 40 10
EYD-N65 310 460 165 250 400 75 60 M8 52 40 10
EYD-N80 310 460 165 250 400 75 60 M8 52 40 12
EYD-N95 460 660 225 400 600 125 80 M12 78 62 24
EYD-N125 460 660 225 400 600 125 80 M12 78 62 26
EYD-N150 460 660 225 400 600 125 80 M12 78 62 28
EYD-N220 460 660 225 400 600 125 80 M12 78 62 34

78
6. SOLID STATE CONTACTORS
6.1 Features
US-N/K Series (for motor/heater load)

US-N5SSTE US-N20TE US-K70

High-accuracy opening/closing, Standard installation protection cover for


maintenance-free live part location to improved safety (US-
With no electrical or mechanical wear sections, this type is a N Series)
suitable maintenance-free selection for high-accuracy A live part location protection cover, with finger protection
opening/closing (motor, heater, light, capacitor switching, etc.) complying with DIN and VDE Standards, is provided as a
standard to improve safety.
No sound noise, clean operation
The best suitable for applications that reduce to avoid sound Various line up and series
noise (Ex.: hotels, hospitals, offices, or clean rooms, etc.). <Heater load>
●2-circuit, 3-circuit integrated type
Applicable to a wide range of main circuit ●Cycle control type power adjuster
voltage (US-N20(TE) to US-N50(TE)) <Motor load>
Can be used with a wide main voltage range from 100 to ●2-circuit, 3-circuit integrated type
480VAC. <Current frame>
200VAC 5A to 200A frame
Conformity to International Standards 400VAC 20A to 200A frame
(US-N Series)
The standard model complies with or is approved to be
compliant with not only domestic standards but also various
overseas standards.

US-H Series (for heater load)

US-H20 US-H40DD US-H20HZ

Best suitable for heater loads Conformity to International Standards


Suitable for high-accuracy opening/closing applications such The standard model complies with or is approved to be
as injection molding machines and semiconductor compliant with not only domestic standards but also various
manufacturing machines, etc. overseas standards.

Applicable to a wide rang of main circuit Live part location protection cover
voltage available for improved safety (option)
Can be used with a wide main voltage range from 24 to A live part location protection cover (Type UN-CV501US)
480VAC. can be easily mounted after the control cabinet is mounted
to improve safety.

79
6.2 Product Scope
US-N/K • US-H Series Models
Table 1. US-N type, US-K type solid state contactors (standard model)
AC-1 class rated operating
current (A) (Note 5) 5 8 20 30 40 50 70
1 f 200V
Heater (Note 2) 1 1.6 4 6 8 10 14
capacity
(kW) 3 f 200V 1.7 2.7 6.9 10.3 13.8 17.3 24.2 (Note 1)
Maximum motor capacity
200VAC class (100 to 240VAC)

(kW) 0.4 0.4 2.2 3.7 5.5 5.5 11 (Note 1)

For three-phase load


US-NM
US-KM
US-N5SS US-N8SS US-N20 US-N30 US-N40 US-N50 US-N70NS
US-N5SSTE US-N8SSTE US-N20TE US-N30TE US-N40TE US-N50TE US-N70NSTE

For single-phase load


For three-phase load
(using two or three)
US-KM

US-K70

AC-1 class rated operating


current (A) (Note 5) 20 30 40 50 70
1 f 400V
Heater (Note 2) 8 12 16 20 28
capacity
(kW) 3 f 400V 13.8 20.7 27.7 34.6 48.5 (Note 1)
Maximum motor capacity
400VAC class (200 to 440VAC)

(kW) 3.7 7.5 7.5 15 22 (Note 1)

For three-phase load


US-NM
US-NHM
US-KHM
US-N20 US-N30 US-N40 US-N50 US-NH70NS
US-N20TE US-N30TE US-N40TE US-N50TE US-NH70NSTE

For single-phase load


For three-phase load
(using two or three)
US-KHM

US-KH70

Mounting on 35mm rail Possible with standard product (Note 4)

Protection cover for live part location Mounted as a standard part (Not mounted for US-K70 or KH70)

Driving unit UA-DR1

Driving unit with output UA-SH8 (Note 6) UA-SH1

Reversing unit UA-RE

Fault detecting unit UN-FD (for main circuit 200V), UN-FD4 (for main circuit 400V)

Power control unit UA-PC

Options
(Note 3)

UA-SH8 UA-DR1 UA-SH1 UA-RE

80
Table 2. US-K type solid state contactor
(for DC lord)
DC-1 class rated operating
80 100 120 150 200 current (A) 8

16 20 24 30 40 Rated voltage DC24~110V

Direct current
27.7 34.6 (Note 1) 41.5 52 (Note 1) 69 (Note 1)

11 15 (Note 1) 15 18.5 (Note 1) 22 (Note 1)


For DC load
US-KD8

US-KD8
Option Driving unit
with output UA-SH8
US-N80NS
US-N80NSTE US-K100TE US-K120TE US-K150TE Possible with
Mounting on 35mm rail standard product

Note 1. For the US-K(H)M type, the capacity when


applied for a three-phase load using two or
three US-K(H)M type units for the single-
phase load is shown.
US-K100 US-K150 US-K200 Note 2. This is the capacity per pole.
Note 3. M in the option unit field indicates the
80 100 120 150 200 applicable range.
Note 4. Possible with a dedicated part (US-MRM).
32 40 48 60 80 Note 5. If ambient temperature is higher than 40°C,
the derating factor shown in Fig.1 should
55.4 69.3 (Note 1) 83 103.9 (Note 1) 138.5 (Note 1) be applied to the rated operating current.
Note 6. When installing the output driving unit UA-SH8
22 30 (Note 1) 30 37 (Note 1) 45 (Note 1) type onto the US-N5SS/N8SS (TE) type,
remove the US-NM type unit's cover first.

1.0
Derating factor

0.9
0.8

US-NH80NS 0.7
US-NH80NSTE US-KH100TE US-KH120TE US-KH150TE 0.6
0.5
0 20 40 60
Ambient temperature (°C)

Fig.1

US-KH100 US-KH150 US-KH200

UN-FD UA-PC

81
US-H Series Models
Solid state contactor for heater loads, suitable for high-frequency heater switching applications such as injection molding machines
and semiconductor manufacturing machines.

Table 3. US-H type solid state contactor


Rated operating current (AC-51)
(-10 to 40°C) (Note 1) 20A 30A 40A 50A 20A 30A 40A 50A

1 f 200V 4kW 6kW 8kW 10kW 4kW 6kW 8kW 10kW


Heater
capacity
3 f 400V 6.9kW 10.3kW 13.8kW 17.3kW – – – –
(-10 to 40°C)
(Note 1)
3 f 400V 13.8kW 20.7kW 27.7kW 34.6kW – – – –
Tolerable maximum current
(peak) 60Hz 1 cycle 330A 800A 1000A 1300A 330A 800A 1000A 1300A

Rated operating voltage AC24V~AC480V 50/60Hz

Operating voltage range AC20V~AC528V

Main circuit control method Batch control Individual control


US-H20 US-H30 US-H40 US-H50 US-H20DD US-H30DD US-H40DD US-H50DD

Standard

US-H20 US-H40 US-H20DD US-H40DD

Mounting on 35mm rail US-H20RM US-H30RM – – US-H20DDRM US-H30DDRM – –

UN-FD (for main circuit 200V)


Fault detecting unit
UN-FD4 (for main circuit 400V)
Options
Power control unit UA-PC
Protection cover of UN-CV501US
live part location

Note:1. If ambient temperature is higher than 40°C, the derating factor shown in fig.2 should be applied to the rated operating current.

1.0
Derating factor

0.9
0.8
0.7
0.6
0.5
0 20 40 60
Ambient temperature (°C)

Fig.2

82
MITSUBISHI ELECTRIC WORLDWIDE SALES NETWORK
Country/Region Company name and address Telephone

Australia Mitsubishi Electric Australia Pty. Ltd., 348 Victoria Road, Rydalmere N.S.W. 2116, Austraria +61-(0)2-9684-7586
Belgium Emac S.A., Industrialaan 1, B-1702 Groot-Bijgaarden, Belgium +32-(0)2-4810211
Chile Rhona S.A., Varinate Aqua Santa 4211 Vina Del Mar-Chile +56-32-320652
China Mitsubishi Electric Automation (Shang Hai) Ltd. 1-3/F., Block 5, 103 Cao Bao Road, Shanghai China +86-(0)21-6120-0808
Colombia Inpovarltda Proelectrico, Carrera 43G No.27-12, Medellin, Colombia +57-1-232-2300
Denmark Louis Poulsen Co.A/S., Geminivej 32, DK-2670 Greve, Denmark +45-(0)43-95-95-95
Egypt Cairo Electrical Group, 9 Rostoum Street, Garden City, Apt.5, P.O.Box : 165-11516 Cairo, Egypt +20-2-796-1337
Germany Mitsubishi Electric Europe B.V., German Branch, Gother Strasse 8, 40880 Ratingen, Germany +49-(0)2102-486-0
Greece Antonios Drepanias S.A., 52.Arkadias Street GR 12132, Peristeri Athens Greece +30-(1)57815995781699
Hong Kong Mitsubishi Electric Automation (Hong Kong) Ltd. 10/F., Manulife Tower, 169 Electric Road, North Point,
Hong Kong +852-2887-8870
Indonesia P.T.Sahabat Indonesia, Muara Karang Selatan Blok A/Utare No.1, Kav No.11 Kawasan Industri
Pergudangan Jakarta Utare 14440 +62-21-661-0651
Ireland Mitsubishi Electric Europe B.V., Irish Branch, Westgate Business Park, Ballymount, Dublin 24, Ireland +353-(0)1-450-5007
Italy Mitsubishi Electric Europe B.V., Italy, C.D. Colleoni-P. Perseolng.2, Via Paracelso 12 1-20041 Agrate
Brianza (M1) +39-(0)396-0531
Korea Mitsubishi Electric Automation (Korea) Ltd. 2/F., 660-11, Deungchon-Dong, Kangseo-ku, Seoul 157-030,
Korea +822-3660-9607
Kuwait Salem M. Al-Nisf Electrical Co. W.L.L., P.O.Box 4784 Safat 13048 Safat, Kuwait +965-481-5282
Lebanon Comptoir Delectricite Generate-International, Cebaco Center-Block A, Autostrade Dore, P.O.Box 90-953,
Beirut-Lebanon +961-1-240430
Myanmar Peace Myanmar Electric Co., Ltd., No.137/139, Botataung Pagoda Road, Botataung Town Ship 11161,
Yangon, Myanmar +95-(0)1-202589
Netherlands Imtech Marine & Industry, Postbox 5054, Nl-3008 Ab-Rotterdam, Netherlands +31-(0)10-487-1911
New Zealand Melco Sales (N.Z.) Ltd., 1 Parliament Street, Lower Hut1, New Zealand +644-569-7350
Norway SCANELECAS, 5074 Godvik-Bergen Leirvikasen 43B, Norway +47-55-506000
Pakistan Prince Electric Co., 16 Brandreth Road Lahore 54000, Pakistan +92-765-4342
Peru I.T.E., Ingenieros s.a., Paseo de la Republica 3573, Lima 27, Peru +51-14-41-1825
Philippines Edison Electric Integrated, Inc., 24TH Floor, Galleria Corporate Center, Edsa cor. Ortigas Ave., Quezon City +632-634-8691-96
Poland MPL Technology Sp Zo.o., Ul.Sliczna 36 31-444 Krakow, Poland +48-(0)12-632-28-85
Saudi Arabia Center of Electrical Goods, Al-Nabhaniya Street-4th Crossing Al-Hassa Road, P.O. Box 15955, Riyadh
11454, Saudi Arabia +966-1-477-149
Singapore Mitsubishi Electric ASIA PTE Ltd. 307 Alexandra Road #05-01/02 Mitsubishi Electric Building Singapore +65-6473-2308
Slovenia INEA, Ljubijanska 80, 61230 Domzale, Slovenia +386-61-718000
South Africa Circuit Breaker Industries Ltd., Private Bag 2016. Isando 1600, Johannesburg, South Africa +27-(0)11-928-2000
Spain Mitsubishi Electric Europe B.V., Spanish Branch, Caretera De Rubi 76-80, 08190-Sant Cugat Del Valles
(Barcelona) Spain +34-(0)93-595-3131
Sweden Euro Energy Components AB, Energigatan 15 S-43422 Kungsbacka Sweden +46-(0)300-51800
Switzerland Trietec A G., Mühlenstrasse 136, 8200 Schafthausen, Switzerland +41-52-6258425
Taiwan Setsuyo Enterprise Co., Ltd., 6th, Fl., Number 105, Wu Kung 3rd Rd, Wu-Ku Hsiang Taipei. Taiwan, ROC +886-(0)2-2298-8889
Thailand United Trading & Import Co. Ltd., 77/12 Burmrungmuang Road, Klong Mahanak, Pomprab, Bangkok
10100, Thailand +66-2-6649647-50
Turkey HEDEF, Balmumcu-Istanbul Barboros Bulv. Iba Bloklari Gazi Umur P. So Turkey +90-(0)212-2754876
U.K. Mitsubishi Electric Europe B.V., UK Branch, Travellers Lane, Hatfield, Herts Al10 8XB, United Kingdom +44-(0)1707-276100
U.S.A. Mitsubishi Electric Automation, Inc., 500 Corporation Woods Parkway, Vernon Hills, IC60061, U.S.A. +1-847-478-2100
Uruguay Fivia., AV. Uruguay 1274/76 11100 Montevideo Urguay +598-2-920808
Venezuela Adesco S.A., P.O.Box 78034 Caracas 1074A, Venezuela +58-241-4439
Vietnam Sa Giang Techno Co., Ltd., 207/4 Nguyen Van Thu St., Dakao Ward, Dist1, Ho Chi Minh City, Vietnam +84-8-825-6453

Safety tip: Be sure to read the instruction manual thoroughly before using these products.

HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

Revised publication effective Dec. 2007,


L(NA)74109218-N(0712)MDOC Specifications subject to change without notice.

You might also like