NX301E

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

13.

Case Dimensions NX301E Earth Leakage Relay


96 mm
User’s Guide
A BRIEF OVERVIEW
96 mm

Front

b
c
90mm
f
70mm d

Side
e

TEST RESET g
NX 301E
h

a - Auxiliary power supply indicator

b - Trip status indicator

90mm c - Trip start indicator

d - Time delay selector

e - Sensitivity selector
90mm

f - Sensitivity multiplier switch

g - Reset button

h - Test button
TECHNICAL DATA 6. Settings
Sensitivity adjustment : 0.03 A to 30 A
1. Light Indicators Delay time adjustment : 0 sec to 3.0 sec

The light indicators display the status of the system. 7. Contacts


Status indicators Contact arrangement : 2 x latching type with manual reset
: NC and NO contacts available
Indicator Contact rating : 5A, 250VAC (cos ɵ =1) contact rating
Status Contact material : Silver alloy
AUX TRIP DELAY Expected electrical life : 100,000 operations at rated current
Off Off Off No auxiliary power supply Expected mechanical life : 5 million operations

On Off Off System normal, no tripping


8. Inputs
On Off On Trip start, time delay countdown started Remote Test/Reset Inputs*: N.O. dry input
Auxiliary supply
On On Off Earth leakage tripped NX301E-240A(6) : 198~265 VAC
NX301E-110A(6) : 90~120 VAC
On On Blink ZCT not connected
Rated frequency : 50 or 60 Hz
VA rating : 3VA typical
Setting accuracy :-15% to +0%
2. Sensitivity Adjustment Timing accuracy : ± 5%

The NX301E features 2 rotary selector switches for sensitivity


setting: 9. Indicators
Auxiliary supply : Green colour LED indicator
Time delay :Red colour LED indicator
(i) 9 position sensitivity selector(e) offer setting range of 30mA, 50mA, Trip : Red colour LED indicator
75mA, 100mA, 125mA, 150mA, 200mA, 250mA and 300mA.

(ii) 3 position sensitivity multiplier selector (f) switch offer selection of 10.Zero-phase Current Transformer
1x, 10x and 100x.
To operate with ZCT series of current transformer

3. Tripping Delay Time Adjustment


11. Mechanical
• The 9 position time delay selector ( d ) provides additional delay for fault discrimination. Mounting method :Panel mounting
• Selectable delays are: Instantaneous (no delay), 50ms, 100ms, 150ms, 250ms, 350ms, Front panel : Standard DIN96mmx96mm
500ms, 1s and 3s. Approximate weight : 0.6kg (exclude ZCT)

4. Push Button 12. Connection Diagram


Reset Button
• The reset button is for resetting the light indicator and the latching trip contact after NX 301E
a trip has occured. LOAD
• To reset, press the reset button once.

Test Button
• Press and hold the test button for 3s to simulate an earth leakage trip condition. SHUNT
TRIP CONTACT 1 TRIP CONTACT 2 TRIP

5. Output Contact
Trip Contact
• This is a latching type contact. It operates when tripped.

L3
L2
L1
N