AutoTransfer Switch(ATS)
Main Power Genset Power
Lamp Lamp
Genset Power
Main Power
Voltage Meter
Voltage Meter
20~250A
Wall hanging type
400~3200A
Vertical type
1. ATS switch choice
Page:1/5
○
R
○
R
Conventional thermal 80 A 100 125 160 250 400 630 800 1000 1250 1600
20A 40A 63A
current Ith A A A A A A A A A A
Rated conditional
100KA 70KA 100KA 120KA
short-circuit current
Rated short-time
7KA 9KA 13KA 26KA 50KA
withstand current
Control power
AC220V
supply voltage
400
Startup 300W 325W 355W 440W
Rated control W
voltage 90
Normal 55W 62W 74W 98W
W
Weight(kg) Grade 4 7.0 7.2 7.2 7.2 7.5 7.5 8.8 9 16.5 17 32 36 40 43
3. General Specification
For emergency power in building or other circumstances, Auto Transfer Switch (ATS) is essential. ATS can
automatically transfer load between the main power and the emergency power (generating set) without
operator. When the main power fails or voltage drop below 80% of normal voltage, the ATS will start
emergency generating set after a preset time 0-10 seconds (adjustable), and transfer the load to
emergency power(generating set). Contrarily, when the main power recover normal, the ATS will transfer
the load form the emergency power (generating set) to the main power, and then stop the emergency
power(generating set).