E2000 Manual UK - Compressed
E2000 Manual UK - Compressed
E2000 Manual UK - Compressed
E2000
0,4kW – 400kW (IP20)
Safety instructions Installation
& operating manual
ENGLISH
E2000_Rev.02 -EN- SOFT Rev. 5.09
www.eur a dri ve s. e u © 2017 EURA Drives GmbH
INDEX PAGE
3) Inverter mounting 16
6) Operating panel 31
Rev. 02-EN-2016-06-KPP
Software revision: 5.09
1) Common installation- and safety rules for EURA DRIVES inverters, series
E2000+
IMPORTANT!!
This instruction manual explains rules for correct installation and safe operation of frequency
inverters, series E2000+ (denominated inverter, or drive in the following guidance). It is
mandatory to follow exactly, what reported in this instruction manual.
This instruction manual must be read and fully understood before any action of installation or
placing in operation of the inverter.
Anybody, who operates the inverter, or the machine, equipped with inverter, must have access
to this operation manual, and must become familiar with drives technology, especially
regarding safety and warning issues
DANGER-WARNING-CAUTION
ATTENTION – OBSERVE
Common:
All activity for mounting, cabling, placing into operation and operation
DANGER of the inverter must be done exclusively by proper educated and
trained people.
The standards IEC 364 and/or CENELEC HD384, DIN VDE 0100 and
all other national safety standards are to observe.
The E2000+ inverter serves exclusively for the control and regulation
of three phase motors (asynchronus / synchronus motors)
The connection of loads, other than above listed, may result in
damage of the machinery, destruction of the inverter or connected
equipment, and serious risk of personnel injury.
Use proper shielded cables, for inverter control signals and feed back
signals
LVD – DOUBLE
INSULATON
All connection terminals for control and feed-back are single insulated
in sense of EN50178.
In case of connection to external equipment with double insulation,
the user has to provide proper arrangement, to guarantee double
insulation in sense of EN50178 for the whole system
Insulation testing
In case of insulation testing of the whole network, it is recommended
to disconnect the inverter and all optionally mounted filter
components. Some components, used inside the inverter may impact
measurement accuracy, o may become destroyed
Potential equalization
For life protection, all plant with inverters must have following:
-Review all inverter and motor cabling, including correct terminal tightening torque
(torque values: see table).
-Use proper cable for all control wiring, separate control cable from power cable, min. 15 cm distance.
Use shielded cable for all control connections, exceeding 1 meter
-Shielded cables are recommended for motor connection too, especially with distances, exceeding 30
meters.
-Avoid earth loops, all earth connections should have large contact areas, all leading to one central
grounding point (star connected)
IMPORTANT FOR One separate circuit breaker is recommended for each inverter –
SAVE INVERTER allowing separate switch off of single inverters.
OPERATION
CHECK FOR PROPER INVERTER PROGRAMMING
Inverter protection-functions
Although the inverter is equipped with intelligent protections functions,
the repetitive triggering of those functions may result in inverter
damage.
The inverter is protected against output short circuit and earth fault,
each displayed by a specific code on the display.
Repetitive earth faults and short circuits may damage the power
stage of the inverter.
The motor must be fixed connected, in case, where interruption of the
motor line is required (for safety reason), the circuit should open/close
with inverter in STOP condition only (final stage disabled).
It is recommended, to keep the inverter powered on at all time, if for
application reason repetitive power on cycling is required, it should
not exceed one cycles every 5 minutes – otherwise contact the
manufacturer.
Power-grid specification:
The inverter is build for symmetric three phase power supply
systems, with voltage phase to earth/neutral not exceeding 300V.
A transformer can be used for adaptation to higher voltages.
For single phase inverters the maximum input voltage is 240V +15%,
400V class thee phase inverters can work up to 460V +15%.
Contact the inverter manufacturer, before connecting to unbalanced,
floating, or unsymmetrical power systems.
The E2000+ series inverters are electrical devices, designed for installation in industrial area.
E2000+ inverters are not designed to work stand alone, these inverters are considered as part of a
complex system, for this reason, no separate EMC marking is applied on the inverter.
The machine builder / system integrator is obligated to prove the compliance with actual EMC
standards for the whole system.
Normally, the inverter integrated EMC filters are sufficient, to meet the actual EMC limits (this has
been confirmed by measurements, performed by independent body).
Inverters E2000+ are designed for use in "second environment", (in sense of EN61800-3).
This means installation in industrial area, where power supply is done via separate
transformer.
Fore installation in "first environment" (residential area – public low voltage power grid),
additional filter components may become necessary, to meet EMC rules.
Mounting in metal cabinet, if possible, the cabinet should be divided into power and control area, using
metal shielding barrier, or similar
Connect all metal parts, grounding cables, cable shields on one central point, using the blank
mounting plate as contact area.
Use 10mm2 cables for potential equalization, "star" connected on one central point.
Please consider, that inverters and filters may have more than 3,5 mA leakage current, therefore use
proper earth/ground conductors:
Use shielded cables, wherever possible, with copper mesh, common cable steel protection is not
working as shield.
Connect shields on large blank areas with potential equalization bars. Use special cable glands, with
integrated contact brushes.
It is not allowed to extend cable shield, using single wire.
Mount all external filter components as close as possible to the noise source (inverter) – get perfect
contact, mounting directly on the blank cabinet plate.
Keep all wiring as short as possible, separate different networks, min. 15 cm distance.
Different networks are: power supply, motor cable (incl. brake resistor), low voltage control wiring
(control signals, feed back, data line).
UL Standards
The UL/cUL mark applies to products in the United States and Canada and it means that UL has performed product testing and evaluation
and determined that their stringent standards for product safety have been met. For a product to receive UL certification, all components
inside that product must also receive UL certification.
UL Standards Compliance
This drive has been tested in accordance with UL standard UL508C, File No. E363934 and complies with UL requirements.
To ensure continued compliance when using this drive in combination with other equipment, meet the following conditions:
1)Do not install the drive to an area greater than pollution severity 2 (UL standard)
2)Installation and operating instructions shall be provided with each device.
The following markings shall appear in one of the following locations: shipped separately with the device; on a separable, self-adhesive
permanent label that is shipped with the device; or anywhere on the device itself.
a) Designation markings for each wiring diagram;
b) Markings for proper wiring connections.
c) “Maximum Surrounding Air Temperature 40ºC.” or equivalent;
d) “Solid State motor overload protection reacts when reaches 150% of FLA” or equivalent;
e) “Install device in pollution degree 2 environment.” or equivalent;
f) For Models of Frame Size(E2000-0007T3UBR;E2000-0011T3 UBR;E2000-0015T3 UBR;E2000-0022T3UBR): “Suitable For Use On A
Circuit Capable Of Delivering Not More Than 5,000 rms Symmetrical Amperes, 480 Volts Maximum When Protected By made by COOPER
BUSSMANN L L C Class T Fuse: JJS-15.” or equivalent.
For Models of Frame Size (E2000-0030T3UBR;E2000-0037T3UBR;E2000-0040T3UBR): “Suitable For Use On A Circuit Capable Of
Delivering Not More Than 5,000 rms Symmetrical Amperes, 480 Volts Maximum When Protected By made by COOPER BUSSMANN L L C
Class T Fuse: JJS-25.” or equivalent.
For Models of Frame Size (E2000-0055T3UBR;E2000-0075T3UBR): “Suitable For Use On A Circuit Capable Of Delivering Not More Than
5,000 rms Symmetrical Amperes, 480 Volts Maximum When Protected By made by COOPER BUSSMANN L L C Class T Fuse: JJS-35.” or
equivalent..
g) “Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in
accordance with the National Electrical Code and any additional local codes” or the equivalent;
h) “CAUTION – Risk of Electric Shock” should be provided, followed by instructions to discharge the Bus Capacitor or indicating the time
required (5 minutes) for Bus Capacitor to discharge to a level below 50 Vdc;
i) “Drives have no provision for motor over temperature protection” or equivalent;
j) For used in Canada only: “TRANSIENT SURGE SUPPRESSION SHALL BE I NSTALLED ON THE LINE SIDE OF THIS
EQUIPMENT AND SHALL BE RATED __480_ V (PHASE TO GROUND), 480 V (PHASE TO PHASE), SUITABLE FOR
OVERVOLTAGE CATEGORY _III_, AND SHALL PROVIDE PROTECTION FOR A RATED IMPULSE WITHSTAND VOLTAGE PEAK
OF _6 kV” or equivalent.
Field Wiring Terminal Markings – Wiring terminals shall be marked to indicate the proper connections for power supply and load, or a
wiring diagram coded to the terminal marking shall be securely attached to the device:
a.“Use 60/75°C CU wire” or equivalent;
b. Required wire torque, type and range listed: see chapter 4) Empfohlene Leitungsquerschnitte – Sicherungen Leistungsklemmen
Grounding – The wire connector intended for ground connection for field installed equipment, shall be clearily identified such as being
marked “G”, “GRD”, “Ground”, “Grounding”, or equivalent or with the grounding symbol (IEC 417, Symbol 5019).
Tightening torque and wire section for field grounding wiring are marked adjacent to the terminal or on the EMV: Grundlagen und
ire section for field grounding wiring are marked adjacent to the terminal or on the wiring diagram.
Power supply:
S2 single phase 220/230 VAC +/-15%
T3 three phase 400/460 VAC +/-15%
Codierung-siehe Typenübersicht
Motor rated power
Type-serial-class (E2000+)
Options identifier
D F1 Y K B R
EMC Filter:
--- No filter
R EMC filter integated
Brake Chopper
--- No chopper
B Chopper integrated
Keypad /potentiometer
--- Keypad without potentiometer
K Keypad with potentiometer
Keypad concept
--- Fix integrated, not removable
Y Removable, inverter has remote control function
Fieldbus
--- No fieldbus
F1 MODBUS
Mechanical concept
--- Wallmount (inside cabinet)
D Inverter integrated in cabinet
Nameplate
Mechanical construction
Inverter with power range from 0,2 to 22 kW: POLYCARBONATE enclosure, build on a constructional base (heatsink) with
the keypad integrated on the cover (not removable) – framesize E1 – E6
Inverter with power range from 30 to 400 kW: Steel panel, power and control terminals inside, with the keypad integrated in
the cover and removable - framesize C3 – C6
Rated voltage 3-phase 380…460V +/- 15% - 1phase 230V +/- 15%
Power supply Input frequency 44….67 Hz
EMC filter Integrated for 2. environment (up to 90 kW)
Output voltage 0……...U-input
Output frequency 0……...650 Hz
Output
Resolution of output frequency 0,01 Hz
Overload capability 150% - 60 sec. / 10 Min
V/Hz - Mode
PWM control-modes SENSORLESS VECTOR (SLV) – Speed / torque control
Permanentmagnet Synchronus Motor PMM control
PWM frequency 0,8.....16 kHz
V/Hz characteristic Linear, quadratic, and user-programmable curve – Voltage setpoint
Starting torque 150% rated torque at 0,5 Hz (in SLV mode)
Control mode Torque boost Automatic / manual
Motor data input Manual input / intelligent AUTOTUNING function
Speed range 1:100 in SLV mode
Speed precision +/- 0,5% (SLV)
Torque precision +/- 5% (SLV)
DC-Brake Freq. threshold, duration and intensity programmable – DC injection
Brake chopper Integrated chopper transistor (Brake resistors – see product table)
Display 7 Segment LED display -4- digit For programming and visualization of different operating parameters
Inverter control - Start/Stop To configure: terminals / operation panel / serial link
Digital control inputs 8 (6) digital inputs (HIGH/LOW configurable), pulse input
Potentiometer (on operating panel / Extern), analogue input (terminals),
Speed / torque reference signal
operating panel keys, pulse input, serial link
2 Analogue channels 0…10V, -10V/+10V, 0..(4)20 mA (with programmable
Reference analogue channels
offset, gain – to concatenate mathematically each other)
I/O Channels, 2 analogue output channels, both programmable in gain, different functions to
Analogue outputs
control assign (0…10V, 0..20 mA)
functions Digitale outputs 2 digital outputs (different functions to assign)
Relays output 1 switchover contact 5 A 230 V (programmable for different functions)
Interface Serial link (MODBUS – ASCI/RTU)
Jog mode, 12V / 50 mA auxiliary power supply on terminals
Special function - control options PI-control / Pump control, Master/Slave control
Fixed frequency control, programmable cycling frequency sequence
"Catch on the fly function", AUTORESET/RESTART function
Overvoltage, Undervoltage
Protection Electrical protection functions Overcurrent, Overload, Motor-Overload, Output-short
functions, incl. Phaseloss, Motor-Phase imbalance
fault memory Heatsink overtemperature – Motor overtemperature (PTC/KLIXON),
Thermal protection functions
Motor I2xt
Operating panel Remote keypad / programming tool
Brake resistors High power resistors for heavy duty operation
Optionals Filter / chokes PFC chokes – dv/dt limiting output filter - sinusfilter
Parameter copy stick USB Stick with parameter dublication function – USB/RS485 converter
PC-Link Software (via MODBUS) Special tool for programming, control and diagnostic (parameter set memory)
Protection IP20 – IP21 (optional)
Operating temperature -10……+50 °C
Environmental
Humidity Max. 90 % not condensing, no corrosion
conditions
Elavation 1000 m - 1% derating / 100m above
Vibration Max. 0,5 g
SLV 0,2……400 kW
Power range
V/Hz 0,2……400 kW
EMC EN61800-3(2004)
Standards
Safety EN61800-5-1 2003
current
Rated power /
Input current
Framesize
Enclosure
Weight (kg)
(WxHxD - mm)
Dimension
Brake chopper
value
resistance
Min. brake
INTEGRIERT
E2000-0004 S2B 0,4 kW - 2,5A 5A 1,4
POLYCARB.
E1 80x140x135
E2000-0007 S2B 0,75 kW - 4,5A 9A 1,5
80 Ohm/200W
E2000-0015 S2B 1,5 kW - 7A 15A 2,0
E2 106x180x150
E2000-0022 S2B 2,2 kW - 10A 22A 2,1
Inverter 400V
Model
current
Rated power /
RMS
Input current
Framesize
Enclosure
Weight (kg)
(WxHxD - mm)
Dimension
Brake chopper
value
resistance
Min. brake
E2000-0007 T3 0,75 kW - 2 A 2,4A 2,0
E2000-0015 T3 1,5 kW - 4 A 4,6A E2 2,1 106x180x150 150 Ohm/200W
E2000-0022 T3 2,2 kW - 6,5 A 7A 2,2
POLYCARBONATE
30 Ohm/1.500W
E2000-0185 T3 18,5 kW - 38 A 45A E6 8,5 205x340x196
E2000-0220 T3 22 kW - 44 A 54A 9,0
20 Ohm/2.000W
E2000-0300 T3 30 kW - 60 A 72A C3 22,5 270x435x235
E2000-0370 T3 37 kW - 75 A 85A 24,0 20 Ohm/3.000W
C4 315x480x235
E2000-0450 T3 45 kW - 90 A 110A 24,5
12 Ohm/5.000W
E2000-0550 T3 55 kW - 110 A 132A 41,5
C5 360x555x265
E2000-0750 T3 75 kW - 150 A 180A 42,0 10 Ohm/8.000W
E2000-0900 T3 90 kW - 180 A 220A 56,0
C6 410x650x300 8 Ohm/10.000W
E2000-1100 T3 110 kW - 220 A 264A 56,5
STEELPLATE
OPTION
3) Inverter mounting
Please read all, what reported on chapter 1) Common installation- and safety rules for EURA DRIVES inverters, series
E2000+ before proceeding with inverter mounting, cabinet wiring, and putting into service the system.
Mounting in cabinet
Accordingly to the protection degree class (IP20/21), the inverter must be placed in a proper cabinet.
The inverter should be mounted vertically, using all available mounting holes.
Avoid mounting of more inverters in vertical array. If absolutely necessary, keep double mounting distances
The table below, shows the minimum mounting distances in vertical and horizontal direction
Sufficient heat exchange of the cabinet must be guaranteed, to keep all operating conditions within the specified limits.
INVERTER
B B
Fans: All inverters out of the E2000+ series are forced ventilated. Specific parameters are used to set various fan
operating modes: Always ON (F702=2), ON with inverter in running mode (F702=1), or temperature controlled (F702=0)
(F703=Temp. threshold)
see 14) Parameter group 700: Error handling and protection functions (F702-F703)
Provided that the inverter is working in respect of specified environmental conditions, provided that the inverter is
used for proper application, and all instructions have been exactly followed for installation, putting in service and
operation, the inverter does not need any specific maintenance.
Power terminals:
There are different arrangements for power terminals, depending on inverter size and number of input phases.
Brake resistor:
E2000+ inverters have build in chopper transistor as standard. An adequate brake resistor can be connected externaly. The
maximus lenght of the cable is 2mt, crossection depends on the current through the resistor, calculated, considering the brake
switch on voltage of 800V and the resistor value.
The minimum resistor value for single inverter power ranges is reported in table on chapter: 2) Product overview / Product data
– the value in the table is the absolute minimum value – resistors with up to three times higher resistance value are
allowed.
Right dimensioning of the resistor, especially in sense of continuous power and peak power depends on the application (inertia,
speed, brake cycle rate).
EURADRIVES accessories program offers special resistors for all kind of application.
EURADRIVES does not take any responsibility for any damage or risk, if
improper brake resistors are used.
Control cables
0,75-1 AWG20 /2,7
– all framesizes
Earth/ground connection
S ≤ 16 =S
16<S ≤ 35 min 16
Minimum earth/ground wiring cross section – for chassis connection (on designed "G"
"GND" "GROUND" connection points)
2 2
Motor wiring section: S (mm ) Minimum earth wiring cross ection /PE/E (mm )
S ≤ 16 AWG8 / 6,2
Two different configurations of control terminals and control boards are available, depending on
inverter frame size
Inverter size E1 – E6
0,20...22 kW
Inverter size C3 – C6
30….400 kW
10V
analogue ground max. current 20 mA
Set-point – current/voltage input
Programmable (F400-F405)
Analogue -
DI2 Programmable
(F317)
Emergency stop
digital input 2 external signal
DI3 Programmable
(F318) Terminal (FWD)
digital input 3
HIGH/LOW active (NPN/PNP) selectable
DI4 Programmable
(F319) Terminal (REV)
digital input 4 via hardware - see: (Hardware and
configuration of I/O channels)
Programmable (DI7 – DI8 on inverters above 22 kW only
DI5 (F320) RESET
digital input 5
Programmable All digital I/O are floating, including 24V Power stage
DI6 (F321)
digital input 6 supply and CM enable
Programmable
DI7 (F322) START
digital input 7
Programmable
DI8 (F323) STOP
digital input 8
Common for digital Common for digital inputs and 24V aux.
COMM
CM I/O supply
RS485 Terminal
Microprocessor ground, reference point
GND Analogue ground
for all analogue signals
+5V
RS 485
Analogue speed reference 0....10V (potentiometer) through input channel AI1: Set F203=1
START/STOP command and inversion through terminal signals: set F208=2 (two wire control)
Fault signalling on relays contact: F300=1 (already default set)
„Inverter enabled“ message on DO1 F301=14 (already default set)
Frequency indication output: AO1 0…10V = 0-50 Hz F423=1, F431=0 (already default set)
Two different type of control boards are used in E2000+ inverter concept:
Control-board inverter
0,4...22kW
SIZE E1 - E6:
A total of 6 digital input channels DI1....DI6 are available on inverter, size E1-E6. Different functions can be assigned to
these inputs, programming the parameter F316….F321 – description: see chapter 10) Parameter group 300: Configuration of
digital I/O channels
DI1 is preset for digital input and fast pulse signal input as well.
Attention: A function can be assigned to one single digital input only (no multiple inputs for same function allowed) If a
function is already assigned to a certain input (due to factory set), this assignment must be deleted (set function-code
0), before assigning to another input.
HIGH/LOW active (PNP/NPN) control-mode selection: This selection is done via hardware setting of the NPN-PNP DIP-
SWITCH on the control board.
All digital inputs are isolated from analogue ground, the 24 V (50mA) auxiliary power supply may be used for input control in
PNP mode. CM is the common reference point for all digital inputs.
E2000+ inverters SIZE E1…E6 have two independent analogue input channels AI1 and AI2, both have a resolution of
12 Bit.
Signal level configuration is done by hardware setting on the control board, and corresponding parameter setting.
For software parameter setting see: 11) Parameter group 400: Configuration of analogue I/O channels
AI1 Voltage signal input: programmable for 0….10V or -10V…0…+10V (factory-default setting 0...10V)
AI2 Voltage/Current signal input: to configure for 0…5V, 0…10V or 0....20 mA - (4...20 mA: offset, to set via software
parameter – F406, F408) – (factory-default setting 0....20 mA)
Configuration AI1
Configuration AI2
Inverters of the E2000+series, SIZE E1...E6 have one relay contact output, and one open collector output DO1, both are
free programmable for different functions, assignation codes are set in parameters F300 – F301.
TA-TB-TC Relay output: isolated switch over contacts, max. contact-load: 2A 230V (F300)
DO1 Digital output: OPEN COLLECTOR, referred to CM - U/High=24V, max. sink-current 100mA. (F301)
DO1 may work as fast pulse signal output too, set via parameter F303. max. frequency 50 kHz, Uss=24V
Two analogue output channels are available on inverters E2000+ SIZE E1-E6: AO1 and AO2.
AO1 : To configure for voltage or current loop signal – function assignation code: F431, signal conditioning F423, range
setting F424 - F426
Software parameter F423…F434, for signal type configuration and function assignation – see chapter: Parameter group 400
Following hardware setting is necessary for AO1 (voltage signal / current loop selection):
Control-board inverter
30...400kW
SIZE C3 – C6:
A total of 8 digital input channels DI1....DI8 are available on inverter, size C3-C6. Different functions can be assigned to
these inputs, programming the parameter F316….F323 – description: see chapter 10) Parameter group 300: Configuration of
digital I/O channels
DI1 is preset for digital input and fast pulse signal input as well.
Attention: A function can be assigned to one single digital input only (no multiple inputs for same function allowed) If a
function is already assigned to a certain input (due to factory set), this assignment must be deleted (set function-code
0), before assigning to another input.
HIGH/LOW active (PNP/NPN) control-mode selection: This selection is done via hardware setting of the NPN-PNP DIP-
SWITCH on the control board.
All digital inputs are isolated from analogue ground, the 24 V (50mA) auxiliary power supply may be used for input control in
PNP mode. CM is the common reference point for all digital inputs.
E2000+ SIZE C3…C6 have two independent analogue input channels AI1 and AI2, both have a resolution of 12 Bit.
Signal level configuration is done by hardware setting on the control board, and corresponding parameter setting
For software parameter setting see: 11) Parameter group 400: Configuration of analogue I/O channels
AI1 - Voltage signal / current loop: programmable for 0…5V, 0…10V, -10V…0…+10V or 0...20 mA.
(4...20 mA: offset, to set via software parameter F400, F402 - (factory-default setting 0...10V)
AI2 - Voltage signal / current loop: to configure for 0…5V, 0…10V or 0....20 mA.
(4...20 mA: offset, to set via software parameter – F406, F408) – (factory-default setting 0....20 mA)
Inverters of the E2000+ series, SIZE C3...C6 have one relay contact output, and two open collector output DO1 and
DO2, both are free programmable for different functions, assignation codes are set in parameters F300 – F302.
TA-TB-TC Relay output: isolated switch over contacts, max. contact-load: 5A 230V (F300)
DO1 Digital output: OPEN COLLECTOR, referred to CM - U/High=24V, max. sink-current 100mA. (F301)
DO1 may work as fast pulse signal output too, set via parameter F303 max. frequency 50 kHz, Uss=24V
DO2 Digital output: OPEN COLLECTOR, referred to CM - U/High=24V, max. sink-current 100mA (F302).
Two analogue output channels are available on inverters E2000+ SIZE C3 - C6: AO1 and AO2. Different functions can
be mapped to both channels
Motor protection using PTC/KLIXON: For all inverter size E1 - E6 and C3- C6
For simple applications and short motor cables (<5m) the digital inputs DI1…DI6 (8) can be used as PTC/NTC/KLIXON signal
input channel.
For hardware set-up, see picture below, the value of the resistor depends on the PTC value, if KLIXON is used for motor
protection, a 1 kOhm resistor, 1 WATT is recommended. Each digital input is programmable for PTC/KLIXON signal evaluation
The trigger threshold is about 4 V – it means about 20V input signal level for PNP configuration - about 4V input signal level for
NPN configuration.
A minimum driving voltage of 20 V is required for common passive 2 wire sensors connected to burden resistor of 500
Ohm. If such sensors are in place, the internal 24 V supply can be used, however, the digital ground must be
connected to the analogue ground (CM - GND).
Galvanic separation will become lost in this case. This may create more noise on control inputs.
Therefore all control cables must be shielded and wired in sense of EMC standards, especially, if the cable length
exceeds the 5 meters.
The schematic below shows the wiring for a passive 4...20 mA sensor
6) Operating panel
Inverter control, parameter setting, operating-parameter display and inverter-
status information are all done through the operation panel.
A seven segment, 4-digit display, combined with six button keypad field and
4-LED status line is build in on front of E2000+ inverters.
7-segment display:
The content of the display can be configured, to show different operating
parameters, while inverter in STOP or START mode, error messages,
parameters and parameter values (for configuration see chapter: Parameter
group 100 – BASIC parameter)
Status LED:
To display the inverter status:
STOP command
Cycling through
Toggle Parameter: Increment /
different display START command
switch for Selection, and save Decrement Key
content
ERROR RESET
DISPLAY DESCRIPTION
F 152 The leading F displays configuration parameter number (Parameter Nr. 152)
10.00 Output frequency (if FRQ=ON), operating parameter, configuration parameter value
Flashing numbers in STOP mode: Target frequency/speed after START command is given
A100 U100,
Operating parameters in START / STOP mode: Motor current, Motor voltage, DC-voltage,
b*.*, o*.*y, Temperature PID-controller feed-back value.......for programming: see parameter F131 – F132
L*.*,H*.*
STO STO Save Torque Off mode activated by optional STO board
Inverter 30.…400kW – SIZE C3-C6: The keypad/display unit is removable, connection to the control-board is made via 8 pole
RJ style cable. An optional mounting frame for the remote unit is available as option. Standard LAN cable (Cat.5, 8 pole) can
be used for remote connection.
7) Parameter setting
For easier parameter setting, the whole parameter list is divided into 11 parameter groups:
Once on parameter level, the keys are used to flip through parameters.
key toggles between single and multi parameter step. If is on, single mode is
selected, if off, group mode is selected, and keys moves in steps of 100.
key selects the parameter on the display, and the parameter value is shown. The blinking
digit may be changed, using keys (eventually use key to switch through single
digits). Pressing again memorizes the modified parameter value.
Parameter types:
Read only parameters: These parameters can not be changed, the tentative to modify will end up in Err0 message – read-
only parameters are listed in GRAY characters
Dynamic parameters: These parameters are allowed to modify with inverter in START and in STOP mode, listed in red
bold characters on this description: Fxxx
Static parameters: To modify with inverter in STOP mode only, otherwise, Err0 is displayed, static parameters are listed in
red, italic bold characters as Fxxx
If F107=1 (password enabled): enter correct password, to unlock parameter modification function. Incorrect password results in
Err1 on the display
F102 Rated current (A) Range: 1.0 – 800.0 Factory set, depending on model, read only
F103 Rated power (KW) Range: 0.2 – 800.0 Factory set, depending on model, read only
F105 Software version No. Range: 1.00 - 10.00 Factory set, depending on model, read only
Attention!!
All motor parameters must be set precisely, to guarantee correct function in SENSORLES VECTOR control mode
(F106=0/3). Motor parameters can be set manually (see parameter group 800), The AUTOTUNING function is used to
fine-tune parameters.
For drives applications with quadratic torque characteristic (pump, fan) the V/Hz setting is recommended (F106=2).
Inverter rated power should match motor power.
Catch on the fly function is in V/Hz mode available only.
F109 Start – frequency (Hz) Range: 0.00 - 10.00 Hz Default setting: 0.00 Hz
F110 Start – frequency duration (sec.) Range: 0.0 - 10.0 sec. Default setting: 0.0 sec.
The inverter always starts running with the selected Start-frequency, if the target frequency is lower than the Start-frequency,
F109 will be ignored.
After the inverter gets a START command, it will remain at the Start-frequency, (set in F110), for the time, set in F111. After the
delay, it will proceed with the acceleration ramp to reach the final frequency. The acceleration ramp does not take into account
the start frequency delay time
The Start-frequency value is independent and not limited by the minimum frequency F112. In case F109 is lower, than F112, the
inverter will start running with the values in F109 and F110. After the inverter reaches the minimum frequency F112, the values
F111 and F112 are considered as frequency limits.
It is recommended, to chose Start-frequency lower than maximum frequency (F111).
F111 Maximum frequency (Hz) Range: F113 - 650.0 Hz Default setting: 50.00Hz
F112 Minimum working frequency (Hz) Range: 0.00 - F113 Hz Default setting: 0.50Hz
The parameter F111 limits the inverter output frequency
In SENSORLESS VECTOR mode it is recommended to limit the maximum frequency to 400 Hz
The parameter F112 defines the minimum allowed output frequency. If speed reference corresponds to frequency lower than
the value in F112, the inverter behaviour depends on Parameter F224: F224=0: Inverter stops, F224=1: Inverter continues to
run on F-min, defined by F112.
Attention!! Continuous operation at low speed may overheat the motor – forced ventilation is recommend
F113 Internal speed reference (Hz) Range: F112 - F111 Default setting: 50.00 Hz
Virtual internal speed reference, it is selectable in the same way, as any external speed reference (see F203, F204). If selected
F203/204 = 0, after the START command, the inverter will reach this speed value.
F114 Acceleration ramp 1 (sec.) Default setting: 0.2 - 3.7KW, 5.0 sec.
5.5 - 30KW, 30.0 sec.
F115 Deceleration ramp 1 (sec.) > 37KW, 60.0 sec.
Range: 0.1 – 3000 sec.
F116 Acceleration ramp 2 (sec.) Default setting: 0.2 - 3.7KW, 5.0 sec.
5.5 - 30KW, 30.0 sec.
F117 Deceleration ramp 2 (sec.) > 37KW, 60.0 sec.
Acceleration ramp: Time to reach 50 Hz, or F-max (it depends on F119)
Deceleration ramp: Time, to decelerate to 0 Hz, referred to 50 Hz, or F-max (depending on F119)
The second ramp set is selectable via programmable digital input (DI1...DI8) - (F316...F323).
F118 Knee frequency (Hz) Range: 15.00 - 650.0 Default setting: 50.00Hz
Frequency, corresponding to the maximum inverter output voltage, the U/F characteristics reaches the horizontal range
Below the knee-frequency, the drive system operates in constant torque, above it works with constant power
F120 Dead time during reversion (sec.) Range: 0.0 – 3000 sec. Default setting: 0.00 sec.
If activated (>0), the inverter will stop at 0Hz during the reversing cycle, indicated as 0. on the display. (these parameter has no
effect, if automatic frequency cycling is chosen).
This function may be useful, to avoid torque/current peaks during reversion
F124 Jog frequency (Hz) Range: F112 - F111 Default setting: 5.00 Hz
F125 Accel. ramp – Jog Mode (sec.) Range:
Default setting: 0.2 - 3.7KW: 5.0 sec.
5.5 - 30KW: 30.0 sec.
0.1 – 3000 sec.
F126 Decel. ramp –Jog Mode (sec.) > 37KW: 60.0 sec.
There are two modes to activate the Jog frequency: Keypad-control, and terminal-control (programmable digital inputs
DI1…DI6(8) – configuration: F316…F323).
Keypad-control: With the inverter in STOP mode press key, to display HF-0, in this condition the key works as a
Jog frequency start/stop toggle (F132 must be configured in the proper way 1+x+x+x).
Terminal control: A proper configured digital input works as Jog frequency start/stop toggle
Remark: In Jog mode the "catch on the fly" function is deactivated
F127/F129 Cut-Off frequency A,B (Hz) Range: 0.00 - 650.0 Default setting: 0.00 Hz
F128/F130 Cut-Off frequency window A,B (Hz) Range: ±2.5 Hz Default setting: 0.0 Hz
Cut-Off frequency to avoid resonance problems – the inverter transits during accel. / decel. ramps through this frequency areas,
but it can not stay stable within this frequency ranges.
Display configuration:
To display a specific parameter, just set Parameter F131 to one of the values in the table above, to display more parameters,
the sum of all values must be set in F131
The key is used to cycle through the various selected parameter values
With inverter in STOP mode, the display will always show the target frequency - flashing
Following table shows the units and display-mode for various parameters:
Motorspeed (rpm): (NNNN) integer value – the decimal point indicates values above 9999.
Motor Current A (A.A)
Motor-Voltage: U (VVV)
Counter status: (ZZZZ)
DC-Voltage: u (VVV)
Heatsink temperature: H (TTT)
Calculated speed L(sss). Decimal point to indicate values above 999, two decimal points for values above 9999
PID controller Set-Point (normalized): (o*.*)
PID Feed-Back (normalized): (b *.*)
Motor-Power (normalized): (x.x)
Motor-Torque (normalized): (m.m)
Single phase inverter size E1 (0.2 - 0.75KW) do not have temperature indication.
Example: Max. Frequency F111=50.00Hz, number of poles F804=4, transmission ration F133=1.00, pulley diameter R=0.05m
(F134=0,05), calculation result: pulley circumference: 2πr =2×3.14×0.05=0.314 (meter), shaft speed: 60×frequency / (number of
poles × transmission ratio) = 60×50/ (2×1.00) =1500rpm. For linear speed: speed (rpm) × pulley circumference =
1500×0.314=471(meter/second)
Selection: 0: Linear
F137 Voltage frequency 1: Quadratic
characteristic (for V/Hz mode 2: User defined (6 - Punkt) Default setting: 3
only) 3: Automatic
4: Defined by separate voltage setpoint
Default: 0.2-3.7 kW : 7
5.5-30 kW : 6
F138 Lineare characteristic Range: 1 - 20 37-75 kW : 5
> 90 kW: 3
U
Voltage increase on low frequencies is necessary to compensate the
stator copper resistance.
With F137=0 lineare voltage increase is chosen, suitable for constant
torque load. 16
F137=1 quadratic increase, the right curve for load with quadratic
characteristic, like pump and fan.
1
1
F141
6
f
F140 Knee-frequency
Voltage characteristic linear/quadratic/BOOST
F137=2, serves to possible to program a user specific V/Hz curve – see table below
A total of 12 parameter are necessary to define the user specific curve (F140 bis F151) .
F140 User defined frequency F1 Range: 0 - F142 Default setting: 1.00
F141 Assigned motor voltage V1 Range: 0 - 100% Default setting: 4
F142 User defined frequency F2 Range:F140 - F144 Default setting: 5.00
F143 Assigned motor voltage V2 Range: 0 - 100% Default setting: 13
F144 User defined frequency F3 Range: F142 - F146 Default setting: 10.00
F145 Assigned motor voltage V3 Range: 0 - 100% Default setting: 24
F146 User defined frequency F4 Range: F144 - F148 Default setting: 20.00
F147 Assigned motor voltage V4 Range: 0 - 100% Default setting: 45
F148 User defined frequency F5 Range: F146 - F150 Default setting: 30.00
F149 Assigned motor voltage V5 Range: 0 -100% Default setting: 63
F150 User defined frequency F6 Range: F148 - F118 Default setting: 40.00
F151 Assigned motor voltage V6 Range: 0 - 100% Default setting: 81
Remark: V1<V2<V3<V4<V5<V6,F1<F2<F3<F4<F5<F6. Voltage (%)
V6
V5
V4
If F137=3, the slip compensation works in automatic – correct setting V3
for all motor parameter is necessary to guarantee correct operation – V2
AUTOTUNING may be used to find motor parameters, like V1
inductance and stator resistance (see parameter group 8).
F1 F2 F3 F4 F5 F6 Frequency (Hz)
Selection: 0: deactivated
F154 Power supply voltage compensation 1: activated Default setting: 0
2: deactivated during deceleration ramp
This function keeps the motor-voltage stable and independent from power supply voltage fluctuation. It may stretch the
deceleration phase, therefore it can be deactivated during deceleration only (F154=2)
F155 Internal value for secondary speed reference Range: 0…F111 Default setting: 0
F156 Polarity secondary speed ref. (direction) Range: 0 (FWD) oder 1(REV) Default setting: 0
Select parameter F160, press SET, original parameter F160 value is 0, press UP key to set F160 to 1 press SET again
After a few seconds all factory default parameters are restored.
ATTENTION:
The process will not reset to factory default the following parameters:
F400 F402 F406 F408 F412 F414 F421 F732 F742 F745 F901
Selection: 0: forward
F202 Rotation direction preset 1: reverse Default setting: 0
2: depending on terminal signals
If no other rotation direction signal (logic) present, the rotation depends on this parameter – e.g. in case of keypad control.
Otherwise the direction depends on logical function of more direction signals
If (F500=2) – automatic frequency cycling – this parameter is ignored
F205 Reference point for the range setting Selection: 0: referred on F-max
of the secondary speed reference channel, 1: referred on the primary Default setting: 0
using AI1 or AI2 speed channel “X”
F206 Range for secondary speed ref. „Y“ (%) Range: 0….100 % Default setting: 100
In case of combined speed control and secondary speed ref. input via AI1 or AI2, parameter F205 and F206 determine the relation to the
primary reference
9 PID
● ● ● ● 〇 〇
controller
10 MODBUS ● ● ● ● ● ●
-The automatic cycling frequency control algorithm can not work in any combination with others
Selection:
0: Deactivated
1: Two-wire, Type 1 (static)
F208 Activation special Default
2: Two-wire, Type 2 (static)
Two / Three wire control setting: 0
3: Three wire, Typ1 (Impulse / pushbutton control – dynamic)
4: Three wire, Typ2 (Impulse / pushbutton control – dynamic)
5: Pulse / pushbutton control (dynamic)
F208=0: If Fixed-frequency control is required this mode must be deactivated!
If F208>0: functions F200, F201 and F202 are ignored.
“FWD”, “REV” and “X” are digital terminal input signals for two / three wire control mode. This logical signals are assigned to
DI1.....DI6 (DI8) through parameters F316....F323
Assigning-code for DIxx: FWD=15, REV=16, X=17 – see chapter: Parameter group 300 – Digital I/O configuration
FWD FWD
FWD(SB2)=START-impulse FWD(SB1)=START-impulse
forward FWD=NO SB2
SB3 X
FWD=NO X K1
SB1
X(SB2)=cancel-impulse (STOP) REV
REV(SB1)=START-impulse REV X=NC CM
reverse CM
REW=NO K1=Direction
Selection: 0: deactivated
F212 Status memory with (208=3) Default setting: 0
1: activated
If activated, after power down or reset, the inverter will restart with the same status, as before (the previous start impulse
forward/reverse was memorized)
Selection: 0: deactivated
F213 Autostart after power-down Default setting: 0
1: activated
Selection: 0: deactivated
F214 Inverter-Error AUTO-RESET Default setting: 0
1: activated
F215 Power-on Autostart delay (sec.) Bereich: 0.1…3000.0 sec. Default setting: 60.0
F213=1 will force the inverter to restart automatically in case of power off. On power-on, the inverter will restart with the same
conditions, as before (frequency/direction). F215 defines the delay time for power-on autostart.
Power-on autostart works only with F208=0 (dynamic start command)
F214=1 will cause an automatic reset in case of inverter error. F217 is the delay time for error-reset, while F215 works as delay
time for restart after error-reset.
Autostart is performed only if error occurs during START condition (motor running), in case of STOP condition, only error-reset
will be done.
In case of deactivated automatic error-reset, manual reset (keypad/terminal signal) must be done
F217 Delay time for error-reset Range: 0.0 - 10.0 sec. Default setting: 3.0 sec.
WARNING: Activation of AUTOSTART and/or AUTORESET may result in unexpected START up of the drive system!!
Selection: 0: deactivated
F219 EEprom write protection under MODBUS control Default setting: 1
1: activated
Please note that F219, the EE-prom write protection it is activated by default (to prevent EE-prom from getting destroyed due to
repetitive write operations). With this configuration all data sent by MODBUS are stored in the RAM only and get lost after
power-down.
If inverter works with continuously varying parameter values, like speed reference, it is recommended, to work in the RAM only.
F220 Memory function for speed and rotation direction in case of Selection: 0: deactivated
Default setting: 0
power-down 1: activated
Valid in case of internal speed reference (F113), (F155 – F156)
I/O Inverter size E1-E6 (up to 22 kW) Inverter size C3-C6 (above 22 kW)
Digital inputs 6 (DI1…DI6) 8 (DI1…DI8)
Digital outputs 1 (DO1) Open Collector 100 mA / 24 V 2 (DO1, DO2) Open Collector 100 mA / 24 V
Relay output 1 Switch over contact 2 A 230V 1 Switchover contact 5 A 230V
Pulse input DI1 to configure as pulse input DI1 to configure as pulse input
Hardware-configuration: to perform as described in chapter 5) Control hardware-configuration of I/O channels
Parameters F300-F302 (for outputs) and F316–F323 (for inputs) allow assignation of various functions to digital I/O
channels
Current threshold
F310 Current threshold (A) Range: 0…1000 A Default setting rated current
F311 Hysteresis current thresh. Range: 0…100% Default setting 10%
Current threshold, signalled through programmable digital outputs - function assignation: 17.
Hysteresis to subtract from threshold value
F312 Hysteresis to end- frequency (Hz) Range: 0.00…5.00 Hz Default setting 0.00
Valid for the "end of ramp" message through digital outputs – output function assignation: 15
Hysteresis to subtract from threshold value
30 Lack of WATER IF FA26=1, this input will set the inverter in alarm mode EP1 will show up on the display
K4 K3 K2 K1
Frequency Programming parameter
6 5 4 3
0 0 0 0
0 0 0 1 Fixed-frequency 1 F504/F519/F534/F549/F557/F565
0 0 1 0 Fixed-frequency 2 F505/F520/F535/F550/F558/F566
0 0 1 1 Fixed-frequency 3 F506/F521/F536/F551/F559/F567
0 1 0 0 Fixed-frequency 4 F507/F522/F537/F552/F560/F568
0 1 0 1 Fixed-frequency 5 F508/F523/F538/F553/F561/F569
0 1 1 0 Fixed-frequency 6 F509/F524/F539/F554/F562/F570
0 1 1 1 Fixed-frequency 7 F510/F525/F540/F555/F563/F571
1 0 0 0 Fixed-frequency 8 F511/F526/F541/F556/F564/F572
1 0 0 1 Fixed-frequency 9 F512/F527/F542/F573
1 0 1 0 Fixed-frequency 10 F513/F528/F543/F574
1 0 1 1 Fixed-frequency 11 F514/F529/F544/F575
1 1 0 0 Fixed-frequency 12 F515/F530/F545/F576
1 1 0 1 Fixed-frequency 13 F516/F531/F546/F577
1 1 1 0 Fixed-frequency 14 F517/F532/F547/F578
1 1 1 1 Fixed-frequency 15 F518/F533/F548/F579
Please note: binary selection K1...K4 (F500=1) – for direct selection via K1...K4, use fixed-frequency 1, 2, 4 and 8
Direct selection of only 3 fixed frequencies: K1....K3 (F500=0)
BIT1 BIT2
Accel./Decel. Programming
Function assignation Function assignation
Ramp-set parameter
18 34
1 0 Ramp set 1 F114 / F115
0 0 Ramp set 2 F116 / F117
1 1 Ramp set 3 F277 / F278
0 1 Ramp set 4 F279 / F280
F324 "STOP - DISABLE" logic selection (8) Selection: 0=LOW active (NPN) Default setting 0
F325 "EMERGENCY -STOP EXTERN" logic (9) 1=HIGH active (PNP) Default setting 0
F326 Watchdiog delay time Range: 0,1…30.000 sec. Default setting10,0 sec
Both control boards offers independent analogue input/output channels. Each of them can be adapted to various
input/output signals – all configuration must be done by software/hardware setting
Details and instruction for hardware setting: see chapter 5) Control hardware and IO/ channel configuration
Configuration of analogue speed reference channels AI1, AI2, AI3 (A3 = potentiometer on
keypad):
F400 Range definition AI1 – lower limit (V) Range 0.00V…F402 Default setting: 0.00V
F401 Assignation lower limit AI1 Range: 0…F403 Default setting: 1.00
F402 Range definition AI1 – upper limit (V) Range: F400…10.00V Default setting: 10.00V
F403 Assignation upper limit AI1 Range: (1.00, F401)…2.00 Default setting: 2.00
F404 Gain factor AI1 Range: 0.0…10.0 Default setting: 1.0
F405 AI1 Filter factor AI1 Range: 0.1…10.0 Default setting: 0.10
The speed range is defined by upper and lower limits, the area in between corresponds to 100%
(example: F400=2, F402=8, 2…8V correspond to 0....100%)
Parameter F401 and F403 are used to move the range limits (in %). Rules: 0 = -100%, 1 = 0%, 2 = +100%.
(example: F401=0, F403=2 then 100% signal (the range between upper and lower limit) correspond to -
100%...+100% reference). In this case 0...10V input signal corresponds to - 50 Hz…0Hz…+50 Hz).
A= (F401-1)*100% B
B= (F403-1)*100%
C= F400
AI1
D= F402
A
C D
Configuration examples:
Speed reference Output frequency F400 F401 F402 F403 F404 Hardware setting
F412 Range definition AI3 – lower limit (V) Range 0.00V…F402 Default setting: 0.00V
F413 Assignation lower limit AI3 Range: 0…F403 Default setting: 1.00
F414 Range definition AI3 – upper limit (V) Range: F400…10.00V Default setting: 10.00V
F415 Assignation upper limit AI3 Range: (1.00, F401)…2.00 Default setting: 2.00
F416 Gainfactor AI3 (%) Range: 0.0…10.0 Default setting: 1.0
F417 Filter factor AI3 Range: 0.1…10.0 Default setting: 0.10
F418 0 HZ Dead band 0 Hz AI1 Range: +/- 0…0.50V Default setting: 0.00
F419 0 HZ Dead band 0 Hz AI2 Range: +/- 0…0.50V Default setting: 0.00
F420 0 HZ Dead band 0 Hz AI2 Range: +/- 0…0.50V Default setting: 0.00
0 Hz dead band: If frequency crosses 0Hz range (depending on signal range setting), 0 Hz output frequency will
result, within the 0 Hz dead band.
F440 Min. pulse frequency (kHz) Range: 0.00…F442 Default setting: 0.00 kHz
F441 Assignation min. frequency Range: 0.00…2.0 Default setting: 1.00
F442 Max. pulse frequency (kHz) Range: F440…50.00 kHz Default setting: 10.00 kHz
F443 Assignation min. frequency Range: Max(1.00,F441)…2.00 Default setting: 2.00
F445 Filter factor pulse input Range: 0…100 Default setting: 0
F446 0 Hz dead-band Range: 0…+/- F442 Default setting: 0.00
- Range configuration and dead band selection will be done in the same way, as for analogue input signals
F468 input level 1 for AI2 Range: F406 - F470 Default setting: 2.00V
F469 Assignation input level 1 (%) Range: F407 - F471 Default setting: 1.20
F470 input level 2 for AI2 Range: F468 - F472 Default setting: 5.00V
F471 Assignation input level 2 (%) Range: F469 - F473 Default setting: 1.50
F472 input level 3 for AI2 Range: F470 - F412 Default setting: 8.00V
F473 Assignation input level 3 (%) Range: F471 - F413 Default setting: 1.80
100
Assignation of intermediate pints, in the same way as for endpoints
(0= -100%, 1=0%, 2=+100%)
F400 A1 A2 A3 F402
Assignation motor current: The full range corresponds to 0…2x inverter rated current
Assignation motor voltage: The full range corresponds to the inverter rated voltage (230V/400V)
Selection:0=Motor frequency
1=Motor-current normalized on 2xI-n)
2=Motor-voltage (normalized 230/400V)
3=AI1
F453 Assignation of 4=AI2
operating parameters 5=Impulse input Default setting: 0
to DO1 6=Torque – normalized to m-n
7=Set via MODBUS
8=Target frequency
9=Calculated speed
10=Torque (motoric)
RUN/STOP control in fix.freq. mode: If (F208=0) via keypad, or via dig input, function assignement: 61.
alternative: F208=1/2, FWD/REV mapping for dig. input required
Auto-cycling parameter:
F501 Number of different frequencies for
Selection: 2…8 Default setting: 7
auto-cycling function
Range: 0….9999
F502 Number of automatic cycles Default setting: 0
0 = Endless cycling
Selection: 0: Stop
F503 Status after cycle completed Default setting: 0
1: Keep last valid frequency
1 - 8 (0,1....3000sec.)
for fixed-frequencies
Auto-cycle - duration
1 - 8 (0,1...3000sec.)
for fixed-frequencies
Auto-cycle – pausing time
Default setting:
Accel./Decel. time,
depending on
inverter model
F504 Fixed-frequency 1 (Hz) F519 F534 F549 F557 F565 Default: 5.00Hz
F505 Fixed-frequency 2 (Hz) F520 F535 F550 F558 F566 Default: 10.00Hz
Range for
F506 Fixed-frequency 3 (Hz) F521 F536 F551 F559 F567 F504 – F518: Default: 15.00Hz
F507 Fixed-frequency 4 (Hz) F522 F537 F552 F560 F568 F112 .......F 111 Default: 20.00Hz
F508 Fixed-frequency 5 (Hz) F523 F538 F553 F561 F569 Default: 25.00Hz
F509 Fixed-frequency 6 (Hz) F524 F539 F554 F562 F570 Default: 30.00Hz
F510 Fixed-frequency 7 (Hz) F525 F549 F555 F563 F571 Default: 35.00Hz
F511 Fixed-frequency 8 (Hz) F526 F541 F556 F564 F572 Default: 40.00Hz
F512 Fixed-frequency 9 (Hz) F527 F542 F573 Default: 5.00Hz
F513 Fixed-frequency 10 (Hz) F528 F543 F574 Default: 10.00Hz
F514 Fixed-frequency 11 (Hz) F529 F544 F575 Default: 15.00Hz
F515 Fixed-frequency 12 (Hz) F530 F545 F576 Default: 20.00Hz
F516 Fixed-frequency 13 (Hz) F532 F546 F577 Default: 25.00Hz
F517 Fixed-frequency 14 (Hz) F532 F547 F578 Default: 30.00Hz
F518 Fixed-frequency 15 (Hz) F533 F548 F579 Default: 35.00Hz
Warning: Function REV (assignation 16) with F208=2 inverts rotation
Hz
Attention!! Improperly programmed DC-
Brake function may result in inverter
overcurrent trip and/or motor overheating F601
t
In case of braking by DC injection
all kinetic energy will be dissipated V/A
in the motor rotor. Repeatedly use
of the DC brake function may F602
result in motor overheating t
F604 F605
Message "DC-Brake active" may be configured through digital output – assignation code 6
Current limiting function: To program a motor current threshold. If motor current reaches the threshold (F608) during
acceleration, the acceleration ramp will delay, until current drops below the limit.
If current exceed the limit at target frequency (ramp completed), the frequency will be reduced, if necessary, down to
the minimum frequency.
Current limiting function is always deactivated during deceleration ramp.
Voltage limiting function: To limit the DC-link voltage increase, due to energy regeneration during deceleration phase.
If voltage reaches the limit (F609), the limiting function will stretch the deceleration ramp.
The limiting status of the inverter can be signalized through any programmable digital output. Function assignation
code: 12
F608 Current limit (% rated current) Range: 60…200 % Default setting: 160 %
F609 DC voltage limit (% rated voltage) Range: 60…200 % Default setting: 140 %
F610 Max. duration if limiting status (sec.) Bereich: 0.1…3000.0 sec. Default setting: 5.0 sec.
If limiting status of the inverter takes longer than time, set in F610, the system will stop, signalized by OL1 on the
display
Default setting:
F611 Brake chopper activation
Range: 200…1000 V DC 400V inverter: 770V DC
Threshold (V)
230V inverter: 380 V DC
F612 Max. duty-cycle chopper Range: 0…100 % Default setting: 80 %
"Catch on the fly" function: To get already spinning motor controlled (V/Hz mode only)
Selection: 0: Function deactivated
F613 Activation of the function 1: Always active Default setting: 0
2: Active after POWER_ON
Selection: 0: Last memorized frequency
F614 Scan process starting from: 1: Starting from 0 Hz Default setting: 0
2: Starting from F-max.
F615 Scan speed Range: 1…100 Default setting: 20
F627 Current limiting Range: 50....200% Default: 100 %
DC-voltage control
Selection: 0: Active
F631 DC-voltage control setting Default setting: 0
1: Deactivated
F632 Nominal voltage for DC-control Range: 200....800 V Default: 380V DC / 700V DC
F633 DC-control frequency adaption band (Hz) Range: 0,01...10 Hz Default: 5,00 Hz
IF F631=1: The inverter will try to keep DC-voltage constant for different regenerating load conditions (during deceleration ramp
or in case of motor generator function). Reduction of braking torque, or frequency adaption
Attenuation function to prevent from torque oscillation (motor vibration at low frequencies)
Range:
F660 Voltage threshold to start Default: 230V Inverter: 250V
230V Inverter: 215V.......F661
compensation function 400V Inverter: 450V
400V Inverter: 400V.......F661
Range:
F661 Voltage threshold to stop Default: 230V Inverter: 270V
230V Inverter: F660.......300V
compensation function 400V Inverter: 480V
400V Inverter: F660......530V
In case if power drop (short interruptions), the inverter try to compensate the DC voltage. If the voltage falls below the threshold,
programmed in F660, the inverter try to keep the DC voltage constant, performing controlled deceleration (inertial energy feed
back). If DC voltage reaches the value in F661, the inverter will continue with normal operation, heading to the target frequency.
Accel./Decel. ramp, programmed in F658 and F659 are in function during the compensation process.
For special applications, the motor voltage may be controlled independently from output frequency (F137=4)
F674 Upper limit motor voltage (%) F673...100% Default setting : 100%
Selection:
F677 STOP mode for independent 0: Voltage and frequency drop simultaneously
Default setting: 0
motor voltage control 1: Voltage drops first
2: Frequency drops first
ERR0 Parametrizing error Parameter change not accepted Stop inverter for parameter setting
EEP (47) EEPROM error EEPROM write/read error Replace control board
Programmable delay for STOP- DISABLE with STOP signal through terminal
Selection: 0: immediate STOP/DISABLE
F700 Delay selection Default setting: 0
1: with delay
F701 Delay time setting (sec.) Range: 0.0…60.0 sec. Default setting: 0.0 sec.
only for signal through terminal (digital input) (F201=1/2/4, F209=1)
F703 Fan control temperature threshold (C°) Read Only Factory set: 35C°
F704 Threshold for warning INVERTER OVERLOAD (%) 10 Range: 50 - 100% Werk: 80 %
F705 Threshold for warning MOTOR OVERLOAD (%) 11 Range: 50 – 100% Werk: 80 %
F706 Threshold for INVERTER overload trip (%) Range: 120 – 190% Werk: 150 %
F707 Threshold for motor overload trip (%) Range: 20 – 100% Werk: 100 %
% values refer to relative motor / inverter rated values
All warnings are delayed, depending on overload grade
Warning for motor overload depends on working frequency too
时间
Delay 70% 100%
(min.) Delay <5Hz 5 -10Hz >10Hz
(min.)
10
10
1
1
Fault history
Read only:
F720 Overcurrent OC
F721 Overvoltage OE
F722 Overtemperature OH
F723 Overload OL1
Selection: 0: deactivated
F726 Over-temperature monitoring Default setting: 1
1: activated
Selection: 0: deactivated
F727 Output phase-loss monitoring Default setting: 1
1: activated
F728 Delay phase-loss detection (sec.) Range: 0.1 - 60.0 sec. Default setting: 0.5 sec.
F729 Delay for under-voltage detection (sec.) Range: 0.1 - 60.0 sec. Default setting: 5.0 sec.
F730 Delay for over-temperature detection (sec.) Range: 0.1 - 60.0 sec. Default setting: 5.0 sec.
F732 Threshold for under-voltage detection (V) 230V inverter: 215 V
Range: 0.1 – 450V
(DC-Link voltage) 400V inverter: 400 V
Selection: 0: deactivated
F737 Software controlled overcurrent detection Default setting: 0
1: activated
F738 Software current limit (rated current unit) Range: 0.50 - 3.00 Default setting: 2.5
F739 SW over-current inverter-trip counter OC1
F752 Motor overload integration coefficient Range: 0,1...20% Default setting: 1.0
Selection:
F753 Motor type definition 0: Standard motor Default setting: 1
1: Forced cooled inverter motor
For F753=0, motor protection threshold will be lowered for frequencies below 30 Hz
Idling detection
F755 Delay time for idling detection (sec.) Range: 0...60 sec. Default setting: 0.5 sec.
Message via digital output (function code 20)
Ground protection
Selection 0: disable
F760 Ground short monitoring Default setting: 1
1: enable
AUTOTUNING mode:
F800=0: No AUTOTUNING, after parameter F801...F803, F805 and F810 are set, standard values are chosen for remaining
parameters
F800=1: Dynamic AUTOTUNING – motor without load. After input of motor nameplate data in F801…F805 and F810, the
process can be started in the following way:
Set F800=1, press key; The automatic process starts now, „TEST“ shown on display, after a few
seconds, the motor will accelerate and decelerate, with ramps, programmed in F114 and F115. After
completion of the cycle, all motor data will be stored, and F800 will reset to 0
F800=2: Static AUTOTUNING, if there is no way to separate the motor from the load, static data measurement is available – the
motor will not rotate during the cycle, and it is not allowed, to rotate it. Following, to start the static cycle:
Set F800=2, press key; The automatic process starts, „TEST“ shown on display, after a few
seconds it will terminate; All values for rotor resistance main inductivity and leakage inductivity are
stored automatically on parameters F806 to F808, F800 will reset to 0.
F812 Start excitation time (sec.) Range: 0…30.0 sec. Default setting: 0.3
Selection 0: no check
F903 Parity check 1: ODD parity Default setting: 0
2: EVEN parity
Selection: 0: 1200
1: 2400
2: 4800
F904 Baudrate 3: 9600 Default setting: 3
4: 19200
5: 8400
6: 57600
F905 MODBUS Time-out Range: 0.0.....3000 sec. Default: 0.0 sec
F907 M-BUS Time-out warning Range: 0.0.....3000 sec. Default: 0.0 sec
F905: MODBUS time-out, in case of missing MODBUS command within the timeframe, set in F905 inverter will STOP for safety
reason and CE will appear on the display. For F905=0, the safety function is disabled.
F907: MODBUS time-out warning. If F907>0, and MODBUS signal is missing for the time, set by F907, the inverter will send an
error warning trough a programmable digital output (mapping code 43). This signal may be reset via digital input (mapping code
60).
Integrated PID-controller
An integrated PID-controller is available on standard E2000+ inverters. It is suitable for simple closed loop control
projects. Specific pump control algorithm allow constant pressure control of single pumps and dual pump booster
stations. Cascade control and master slave control with automatic interchange functions are available as well
Selection: 0: closed loop control – single pump control Default setting: 0
FA00 Controller configuration 1: Master/Slave Mode
2: Master/Slave with interchange
FA00=0: Suitable for standard closed loop control projects (single pump pressure control).
FA00=1: Dual pump cascade mode control, master pump with variable speed, slave pump fixed speed (direct grid connected)
FA00=2: Dual pump cascade mode control, master pump with variable speed, slave pump fixed speed (direct grid connected),
including master - slave interchange, (time set by (FA25)
Controller configuration for set-point and feed-back channel (see graphic on following page)
FA03 Upper controller limit (% of set-point) Range: 0.0…100.0 % Default setting: 100.0
FA04 Internal set-point value (%) Range: FA05....FA03 % Default setting: 50.0
FA05 Lower controller limit (% of set-point) Range: 0.0…100.0% Default setting: 0.0
If the controller works beyond the limits in FA03 - FA05 inverter will be disabled and (nP) on display
Selection: 0: Positive
FA06 PID controller polarity Default setting: 1
1: Negative
Selection: 0: activated
FA07 Automatic sleep mode Default setting: 1
1: disactivated
FA09 Frequency threshold for sleep mode activation Range: between F112...F111 Default setting: 5.00 Hz
FA10 Time delay for sleep mode activation (sec.) Range: 0…500 sec. Default setting: 15 sec.
If the inverter runs for a programmed time, (set by FA10) below the minimum frequency, (set by FA09), it will stop and enter in
sleep mode, displayed as nP. (feed-back value must stay within programmed limits FA03-FA04).
If feed back (pressure) falls below the value in (FA05), inverter will restart again, after the delay-time in (FA11)
FA12 Maximum working frequency in PID Range: FA09.....Fa111 (Hz) Default setting: 50 Hz
This parameter limits the maximum working frequency in PID mode
Selection: 0: deactivated
FA18 Variable set-point allowed Default setting: 1
1: activated
If FA18=0: It is not possible, to change the fixed set-point in (FA04) during controller operation
Selection: 0: No protection
FA26 Lack of water protection 1: Sensor signal through digital input
Default setting: 0
concept 2: Controller algorithm
3: Motor idling current detection
FA26=1: Lack of water is triggered through digital input (function assignation code 30) – it will stop the inverter and display
EP1. The „Water OK“ signal through a different digital input (function assignation code 31) will reset the system. FA26=1:
there is no delay for fault trigger.
FA26=2: In case the controller reaches the maximum frequency, and the motor current still remains below the value in
FA27, the controller will interpret the situation as lack of water. EP2 will show up on the display. The inverter will stop
immediately.
FA26=3: Detection via motor current measuring only. If the motor current falls below the value in FA66, the fault will be
triggered with delay, set in FA66. Inverter will stop and EP3 will show up on the display.
FA28 Recheck time, timeframe for the inverter to recheck, if lack of water condition still persists, before it restarts. It is anytime
possible to reset the system, pressing.
Dual pump booster control (one pump inverter controlled, one pump fixed speed)
FA30 Delay-time to start inverter pump (sec.) Range: 2.0 - 999.9 sec. Default setting: 20.0
FA31 Delay-time, to start fixed speed pump (sec.) Range: 0.1 - 999.9 sec. Default setting: 30.0
FA32 Delay-time to stop fixed speed pump (sec.) Range: 0.1 - 999.9 sec. Default setting: 30.0
If the feed-back value (actual value) exceeds the limits, given by FA29, the fixed pump will be started or respectively stopped.
Start /Stop delay time is set by FA31 and FA32.
Emergency functions
+
Selection: 0: no function selected
FA59 Selection of different emergency
1: FIREMODE 1 Default setting: 0
functions
2: FIREMODE 2
FA60 Frequency for emergency condition Range F112…F111 Default setting: 50 Hz
FA58 Pressure for emergency conditions Range 0.0….100% Default setting: 80%
Selection: 0: no function selected
FA62 Trigger mode
1: FIREMODE 1
Emergency condition is triggered through specific terminal command (digital input - DIx assignation code 33) in this case, all
protection functions are deactivated, and all auto-restart functions are activated.
Emergency pressure mode is activated by terminal, digital input (DIxx assignation code 32)
FA62=0: Inverter stays in FIREMODE, once triggered by digital input, FA62=1: inverter quits from FIREMODE, after trigger
input is disactivated.
FC01 Delay-time for speed/torque switchover (sec.) Range: 0,0....1,0 sec. Default setting: 0,1 sec.
FC02 Torque ramp-up/down time Range: 0,1....100 sec. Default setting: 1 sec.
FC07 Torque range, referred to rated motor torque Range: 0.0…3,000 Default setting: 3,000
FC09 Internal torque reference value (%) Range: 0…300.0 % Default setting: 100 %
FC07: Torque range, corresponding to 0-100% set-point signal
FC09: Internal torque set-point value
Torque boost for low frequencies (additional torque for heavy startup condition))
Selection: 0: Internal set FC17
1: Analogue input AI1
2: Analogue input AI2
FC14 Torque increase signal origin Default setting: 0
3: Analogue input AI3
4: Pulse signal input
5: Reserved
FC15 Torque increase in (%) motor rated torque Range: 0.0…0,5 Default setting: 0,5
FC16 Frequency threshold for torque BOOSTS (%) f-max. Range: 0…100 % Default setting: 10 %
FC17 Internal setting for torque BOOST value Range: 0..50,0% Default setting: 10 %
FC15: 100% of torque BOOST signal correspond to the % of rated motor torque value, set in FC15
FC16: The threshold for torque boost
FC23 Internal speed limiting value forward Range: 0...100 % Default setting: 10%
FC25 Internal speed limiting value reverse Range: 0...100 % Default setting: 10%
(All values are referred to f-max –F111)
+
Torque / Current limit for field wakening area
Selection: 0: Limiting fixed
FC 48 Activation of secondary limiting Default setting: 0
1: Depending on frequency threshold
FC49 Sekundary torque/current limit (%) Range: 50...200 % Default setting: 120%
FC50 Start transition frequency (Hz) Range: 1.0 Hz....FC51 Default setting: 15 Hz
FC608/30
FC49
FREQUENCY
F50 F51
www. e u r a d r i v e s . e u